NASEEM AP
apnaseem@gmail.com
AIR DISTRIBUTION
SYSTEM
AIR DITRIBUTION
SYSTEM ..
AIR FLOW PATTERN
AIR DITRIBUTION
SYSTEM ..
AIR FLOW PATTERN
AIR DITRIBUTION
SYSTEM ..
AIR FLOW PATTERN
AIR DITRIBUTION
SYSTEM ..
HEAT LOAD ESTIMATION
CONTD ..
AIR DISTRIBUTION
CONTD..
SOME FUNDAMENTALS
1. DUCT IS SIMPLY A PATH TO DISTRIBUTE & MANAGE
THE AIR FLOW TO THE REQUIRED /DESINED
ZONES/AREAS
2. DUCT SHAPE MAY BE CIRULAR,SQUARE,RECTANGULAR
OR SPIRAL
3. GALVANIZED IRON,ALUMINIUM,STAINLESS STEEL,
BLACK IRON ETC ARE SOME OF THE COMMONLY USED
DUCT MATERIALS
AIR DISTRIBUTION
CONTD..
SOME FUNDAMENTALS
1. THE THICKNESS OF THE DUCT SHEET IS MENTIOINED BY ITS
GAUGE
2. ASPECT RATIO IS THE RATIO OF DUCT WIDTH TO HIGHT
3. ASPECT RATIO 1 TO 4 IS GENAERALLY ADVISED FOR DUCT
SIZING.
4. THE SIZE & SHAPE OF THE DUCT WILL DEPEND UP ON THE
CFM ,AVAILABLE SPACE FOR DUCTING, APPLICATION ETC
AIR DISTRIBUTION
CONTD..
SOME FUNDAMENTALS
1. THE DUCT IS CONNECTED TO THE EQUIPMENT THROUGH
FLEXIBLE CONNECTOR
2. ALL THE BRANCEHS ARE FITTED WITH VCD
3. FIRE DAMPER IS PROVIDED AT THE EQUIPMENT OUTLET &
OTHER DUCT PENITRATING FIRE WALL AREAS
4. THERMAL INSULATION IS DONE FOR SUPPLY AIR DUCT
5. ACCAUSTIC INSULATION IS DONE FOR SUPPLY DUCT
AIR DISTRIBUTION
CONTD..
SOME FUNDAMENTALS
1. AIR OUTLETS ARE SELECTED BASED ON THE MANUFACTURES
DESIGN DATA
2. TYPE & LOCATION OF THE AIR TERMINALS WILL DEPEND UP
ON THE ROOM DESIGN AND AESTHATICS
3. LOUVERS ARE FITTED AT THE FRESH AIR DUCT ENTRY
4. FITTINGS AND TRANSITIONS ARE DESIGNED ACCORDING TO
SMACNA & ASHRAE
AIR DISTRIBUTION
CONTD..
SOME FUNDAMENTALS
1. FLEXIBLE CANVAS CONNECTION SHOULD BE USED TO
CONNECT THE EQUIPMENT & DUCTING SYSTEM
2. ACCESS SHUOLD BE PROVIDED FOR DAMPERS
3. AHU SHOULDE BE PROVIDED WITH DRAIN PAN & U TRAP
4. GASKETS TO BE USED BETWEEN DUCT JOINTS TO PREVENT
LEAKAGE
5. NEVER RUN THE AHU UNLESS THE AHU ROOM IS CLEANED
AND FILTERS ARE MOUNTED
AIR DISTRIBUTION
CONTD..
TYPE OF DUCTS
1. SUPPLY AIR DUCT
2. RETURN AIR DUCT
3. FRESH AIR DUCT
4. EXHAUST AIR DUCT
AIR DISTRIBUTION
CONTD..
DUCT DESIGNING METHODS
1. VELOCITY REDUCTION METHOD
2. EQUAL FRICTION METHOD
3. STATIC REGAIN METHOD
AIR DISTRIBUTION
CONTD..
VELOCITY REDUCTION METHOD
1. VELOCITY(FPM) = VOLUME(CFM)/AREA (SQFT)
2. MAIN DUCT VELCOITY -1200 TO 1500 FPM
3. BRANCH DUCT VELOCITY - 750 TO 900 FPM
4. COLLAR/DROPPER VELOCITY - 300 TO 500 FPM
5. PLENUM BOXES – 500 FPM
6. RETURN AIR DUCT VELOCITY SHALL BE LEES THAN
SUPPLY AIR DUCT VELOCITY
AIR DISTRIBUTION
CONTD..
EQUAL FRICTION METHOD
1. CONSIDERS THE TOTAL DUCTING WILL BEAR THE
SAME FRICTIONAL LOSS
2. 0.08”WATER/100 FT TO 1” WATER/100 FEET
3. THE RANGE WILL DIFFER DEPENDING UP ON THE
APPLICATION AND USE OF SPACE
AIR DISTRIBUTION
CONTD..
DUCT CLASSIFICATION DW-
144
DUCT
PRESSURE
CLASS
STATIC
PRESSURE LIMIT
+ve -ve
pa pa
MAXIMUM AIR
VELOCITY
PERMISSIBLE AIR
LEAKAGE
M/sec
Litters per sec per
square meter
Low Pressure
Class-A
500 500 10 0.027 X p^0.65
Medium Pressure
Class-B 1000 750 20 0.009 X p^0.65
High Pressure
Class-C 2000 750 40 0.003 X p^0.65
Where p is in Pascal
AIR DISTRIBUTION
CONTD..
● Duct Classification as per SMACNA
1
7
DUCT PRESSURE
CLASS OPERATING PRESSURE
IN WG Pa
1/2 125 Not exceeding 1/2” wg
1 250 Exceeding 1/2” wg but not exceeding 1” wg
2 500 Exceeding 1” wg but not exceeding 2” wg
3 750 Exceeding 2” wg but not exceeding 3” wg
4 1000 Exceeding 3” wg but not exceeding 4” wg
6 1500 Exceeding 4” wg but not exceeding 6” wg
10 2000 Exceeding 6” wg but not exceeding 10” wg
AIR FLOW MANAGEMENT
● Duct seal class.
SEAL
CLASS
APPLICABLE STATIC
PRESSURE CLASS SEALING REQUIREMENTS
A
More than 3” wg
(750 Pa)
All transverse joints, longitudinal seams
and duct wall penetrations.
B
More than 2” & upto 3”
wg (750 Pa)
All transverse joints & longitudinal seams
C Upto 2”wg (500Pa) Transverse joints only
PRASHANT
DESAI
10
AIR FLOW MANAGEMENT
PRASHANT DESAI 19
AIR DISTRIBUTION
CONTD..
DUCT DESIGN & CONSTRUCTION CONSIDERATIONS
1. THE DUCT SHOULD CONSIDER THE AVILABLE SPACE FOR
DUCTING
2. DUCTS SHOULD BE TESTED FOR LEAKAGE
3. TRANSITIONS & FITTINGS PRESSURE LOSE SHOULD BE
CONSIDERED FOR BLOWER DESIGNING
4. 20 % MAX AREA REDUCTION IS ALLOWED IN DUCTING IN
CASE OF OBSTRUCTION
AIR TERMINAL DESIGN..
FACTORS TO BE CONSIDERED
1. AIR FLOW
2. THROW
3. NOISE LEVEL
4. APPERANCE
5. SPACE RESTRICTIONS
DISTRIBUTION SYSTEM
PLANS & SYMBOLS
Positive Pressure (supply)
Negative Pressure (return or exhaust)
Arrow indicates
air flow direction
FLOW PATTERNS
1-way
4-way
2-way
3-way
Thermostat
Smoke/Fire
Damper
T
AIR DISTRIBUTION
CONTD..
AHU FAN DESIGNING
1. THE CFM TO BE DELIVERED IS OBTAINED FROM HEAT LOAD
CALCULATION
2. THE FAN STATIC WILL DEPENED UP ON:
1. THE PRESSURE LOSS THROGH DUCT AND DUCT FITTINGS
2. THE PRESSURE LOSS AT DAMPERS
3. THE PRESSURE LOSS AT FLEXIBLE DUCT
4. THE PRESSURE LOSS AT TERMINAL
5. INTERNAL FAN LOSSES
FAN SELECTION..
CALCULATING THE PRESSURE DROP
1. IDENTIFY THE PATH HAVING THE MAXIMUM PRESSURE
2. CALCULATE THE PRESSURE DROP IN THE SELECTED PATH
DUCTING & DUCT FITTINGS
3. CALCULATE THE PRESSURE DROP IN THE PATH DAMPERS &
OTHER ACCESSORIES
4. CALCULATE THE PRESSURE DROP @ THE TERMINAL
5. ADD INTERNAL LOSS & SUM UP THE CALCULATION

HVAC Air distribution fundamentals

  • 1.
  • 2.
  • 3.
  • 4.
  • 5.
  • 6.
  • 7.
    AIR DISTRIBUTION CONTD.. SOME FUNDAMENTALS 1.DUCT IS SIMPLY A PATH TO DISTRIBUTE & MANAGE THE AIR FLOW TO THE REQUIRED /DESINED ZONES/AREAS 2. DUCT SHAPE MAY BE CIRULAR,SQUARE,RECTANGULAR OR SPIRAL 3. GALVANIZED IRON,ALUMINIUM,STAINLESS STEEL, BLACK IRON ETC ARE SOME OF THE COMMONLY USED DUCT MATERIALS
  • 8.
    AIR DISTRIBUTION CONTD.. SOME FUNDAMENTALS 1.THE THICKNESS OF THE DUCT SHEET IS MENTIOINED BY ITS GAUGE 2. ASPECT RATIO IS THE RATIO OF DUCT WIDTH TO HIGHT 3. ASPECT RATIO 1 TO 4 IS GENAERALLY ADVISED FOR DUCT SIZING. 4. THE SIZE & SHAPE OF THE DUCT WILL DEPEND UP ON THE CFM ,AVAILABLE SPACE FOR DUCTING, APPLICATION ETC
  • 9.
    AIR DISTRIBUTION CONTD.. SOME FUNDAMENTALS 1.THE DUCT IS CONNECTED TO THE EQUIPMENT THROUGH FLEXIBLE CONNECTOR 2. ALL THE BRANCEHS ARE FITTED WITH VCD 3. FIRE DAMPER IS PROVIDED AT THE EQUIPMENT OUTLET & OTHER DUCT PENITRATING FIRE WALL AREAS 4. THERMAL INSULATION IS DONE FOR SUPPLY AIR DUCT 5. ACCAUSTIC INSULATION IS DONE FOR SUPPLY DUCT
  • 10.
    AIR DISTRIBUTION CONTD.. SOME FUNDAMENTALS 1.AIR OUTLETS ARE SELECTED BASED ON THE MANUFACTURES DESIGN DATA 2. TYPE & LOCATION OF THE AIR TERMINALS WILL DEPEND UP ON THE ROOM DESIGN AND AESTHATICS 3. LOUVERS ARE FITTED AT THE FRESH AIR DUCT ENTRY 4. FITTINGS AND TRANSITIONS ARE DESIGNED ACCORDING TO SMACNA & ASHRAE
  • 11.
    AIR DISTRIBUTION CONTD.. SOME FUNDAMENTALS 1.FLEXIBLE CANVAS CONNECTION SHOULD BE USED TO CONNECT THE EQUIPMENT & DUCTING SYSTEM 2. ACCESS SHUOLD BE PROVIDED FOR DAMPERS 3. AHU SHOULDE BE PROVIDED WITH DRAIN PAN & U TRAP 4. GASKETS TO BE USED BETWEEN DUCT JOINTS TO PREVENT LEAKAGE 5. NEVER RUN THE AHU UNLESS THE AHU ROOM IS CLEANED AND FILTERS ARE MOUNTED
  • 12.
    AIR DISTRIBUTION CONTD.. TYPE OFDUCTS 1. SUPPLY AIR DUCT 2. RETURN AIR DUCT 3. FRESH AIR DUCT 4. EXHAUST AIR DUCT
  • 13.
    AIR DISTRIBUTION CONTD.. DUCT DESIGNINGMETHODS 1. VELOCITY REDUCTION METHOD 2. EQUAL FRICTION METHOD 3. STATIC REGAIN METHOD
  • 14.
    AIR DISTRIBUTION CONTD.. VELOCITY REDUCTIONMETHOD 1. VELOCITY(FPM) = VOLUME(CFM)/AREA (SQFT) 2. MAIN DUCT VELCOITY -1200 TO 1500 FPM 3. BRANCH DUCT VELOCITY - 750 TO 900 FPM 4. COLLAR/DROPPER VELOCITY - 300 TO 500 FPM 5. PLENUM BOXES – 500 FPM 6. RETURN AIR DUCT VELOCITY SHALL BE LEES THAN SUPPLY AIR DUCT VELOCITY
  • 15.
    AIR DISTRIBUTION CONTD.. EQUAL FRICTIONMETHOD 1. CONSIDERS THE TOTAL DUCTING WILL BEAR THE SAME FRICTIONAL LOSS 2. 0.08”WATER/100 FT TO 1” WATER/100 FEET 3. THE RANGE WILL DIFFER DEPENDING UP ON THE APPLICATION AND USE OF SPACE
  • 16.
    AIR DISTRIBUTION CONTD.. DUCT CLASSIFICATIONDW- 144 DUCT PRESSURE CLASS STATIC PRESSURE LIMIT +ve -ve pa pa MAXIMUM AIR VELOCITY PERMISSIBLE AIR LEAKAGE M/sec Litters per sec per square meter Low Pressure Class-A 500 500 10 0.027 X p^0.65 Medium Pressure Class-B 1000 750 20 0.009 X p^0.65 High Pressure Class-C 2000 750 40 0.003 X p^0.65 Where p is in Pascal
  • 17.
    AIR DISTRIBUTION CONTD.. ● DuctClassification as per SMACNA 1 7 DUCT PRESSURE CLASS OPERATING PRESSURE IN WG Pa 1/2 125 Not exceeding 1/2” wg 1 250 Exceeding 1/2” wg but not exceeding 1” wg 2 500 Exceeding 1” wg but not exceeding 2” wg 3 750 Exceeding 2” wg but not exceeding 3” wg 4 1000 Exceeding 3” wg but not exceeding 4” wg 6 1500 Exceeding 4” wg but not exceeding 6” wg 10 2000 Exceeding 6” wg but not exceeding 10” wg
  • 18.
    AIR FLOW MANAGEMENT ●Duct seal class. SEAL CLASS APPLICABLE STATIC PRESSURE CLASS SEALING REQUIREMENTS A More than 3” wg (750 Pa) All transverse joints, longitudinal seams and duct wall penetrations. B More than 2” & upto 3” wg (750 Pa) All transverse joints & longitudinal seams C Upto 2”wg (500Pa) Transverse joints only PRASHANT DESAI 10
  • 19.
  • 20.
    AIR DISTRIBUTION CONTD.. DUCT DESIGN& CONSTRUCTION CONSIDERATIONS 1. THE DUCT SHOULD CONSIDER THE AVILABLE SPACE FOR DUCTING 2. DUCTS SHOULD BE TESTED FOR LEAKAGE 3. TRANSITIONS & FITTINGS PRESSURE LOSE SHOULD BE CONSIDERED FOR BLOWER DESIGNING 4. 20 % MAX AREA REDUCTION IS ALLOWED IN DUCTING IN CASE OF OBSTRUCTION
  • 21.
    AIR TERMINAL DESIGN.. FACTORSTO BE CONSIDERED 1. AIR FLOW 2. THROW 3. NOISE LEVEL 4. APPERANCE 5. SPACE RESTRICTIONS
  • 22.
    DISTRIBUTION SYSTEM PLANS &SYMBOLS Positive Pressure (supply) Negative Pressure (return or exhaust)
  • 23.
  • 24.
  • 25.
  • 26.
    AIR DISTRIBUTION CONTD.. AHU FANDESIGNING 1. THE CFM TO BE DELIVERED IS OBTAINED FROM HEAT LOAD CALCULATION 2. THE FAN STATIC WILL DEPENED UP ON: 1. THE PRESSURE LOSS THROGH DUCT AND DUCT FITTINGS 2. THE PRESSURE LOSS AT DAMPERS 3. THE PRESSURE LOSS AT FLEXIBLE DUCT 4. THE PRESSURE LOSS AT TERMINAL 5. INTERNAL FAN LOSSES
  • 27.
    FAN SELECTION.. CALCULATING THEPRESSURE DROP 1. IDENTIFY THE PATH HAVING THE MAXIMUM PRESSURE 2. CALCULATE THE PRESSURE DROP IN THE SELECTED PATH DUCTING & DUCT FITTINGS 3. CALCULATE THE PRESSURE DROP IN THE PATH DAMPERS & OTHER ACCESSORIES 4. CALCULATE THE PRESSURE DROP @ THE TERMINAL 5. ADD INTERNAL LOSS & SUM UP THE CALCULATION