INTRODUCTION

Low Voltage Systems
Depending on the application, they include equipment for switching, protecting,
conversion, control, regulation, monitoring and measurement of electrical equipment
such as motor pumps, fans, lighting and emergency system.

The dimensions and terms of low voltage switchgear assemblies have been standardized.
Also, barriers and partition, such as internal segregation of functional areas, i.e. between
the busbars, switching apparatus, cables and as protection for the operating personnel
have been considered.

Depending on the type, switchgear apparatus can be used for single or multiple switching
tasks. Switching tasks can also be conducted by a combination of several switchgear units
of fixed or draw-out installation type and can be actuated by different types of protection
as in case of motor control centers (MCC). The main switching apparatus are:

      Circuit breakers (CB)
      Contactors
      Motor starter
      Fuse combination unit
      Miniature circuit breaker (MCB)

In most cases of power plant low voltage switchgear, several over current protection
devices are connected in series between the current source and apparatus to be protected
in case of fault. These devices must operate selectively to limit a fault to the place of its
origin as far as possible. Redundancies in the switchgear design ensure the availability of
energy supply.

Separated Extra Low Voltage (SELV)

A Separated Extra Low Voltage (SELV) circuit must be

      safely separated from other circuits that carry higher voltages;
      isolated from earth (ground) and from the protective earth conductors of other
       circuits.

The safety of an SELV circuit is provided by

      the extra low voltage;


                                              1
   the low risk of accidental contact with a higher voltage;
      the lack of a return path through earth (ground) that a current could take in case of
       contact with a human body.

The design of an SELV circuit typically involves an insulation transformer, guaranteed
minimum distances between conductors, and insulation barriers. The connectors of SELV
circuits should be designed such that they do not mate with connectors commonly used
for non-SELV circuits.

Protected Extra Low Voltage (PELV)

In contrast to an SELV circuit, a Protected Extra Low Voltage (PELV) circuit has a
protective earth (ground) connection. A PELV circuit, just as with SELV, requires a
design that guarantees a low risk of accidental contact with a higher voltage. For a
transformer, this can mean that the primary and secondary windings must be separated by
an extra insulation barrier or by a conductive shield with a protective earth connection.

Functional Extra Low Voltage (FELV)

The term Functional Extra Low Voltage (FELV) describes any other extra low voltage
circuit that does not fulfill the requirements for an SELV or PELV circuit. Although the
FELV part of a circuit uses an extra low voltage, it is not adequately protected from
accidental contact with higher voltages in other parts of the circuit. Therefore the
protection requirements for the higher voltage have to be applied to the entire circuit.

Examples for FELV circuits include those that generate an extra low voltage through a
semiconductor device or a potentiometer.

1. Make a overview drawing of the installation with: 60 / 10kV transformer station
and connection to T , TR.T. , HT , UT , L1 , L2 , L3.Determinate the point of supply.




2.1 Give a theoretically description of the dimension purpose and methods for the
overload protection and current value calculation Iz.

Current Carrying Capacity of Copper Conductors




                                             2
Current carrying capacity is defined as the amperage a conductor can carry
before melting either the conductor or the insulation.
        Heat, caused by an electrical current flowing through a conductor, will determine
the amount of current a wire will handle. Theoretically, the amount of current that can be
passed through a single bare copper wire can be increased until the heat generated
reaches the melting temperature of the copper.
       There are many factors which will limit the amount of current that can be passed
through a wire. These major determining factors are:
Conductor Size:
The larger the circular mil area, the greater the current capacity.

  Table 4.6 - Current ratings and volt drops for unsheathed single core p.v.c. insulated cables

                  In           In
    Cross      conduit      conduit       In        In
                                                            Clipped    Clipped
  sectional       in           in       conduit   conduit                              Volt drop   Volt drop
                                                             direct     direct
    area       thermal      thermal     on wall   on wall
              insulation   insulation

   (mm²)          (A)         (A)        (A)       (A)       (A)         (A)       (mV/A/m)        (mV/A/m)

                            3 or 4        2       3 or 4      2         3 or 4                      3 or 4
      -        2 cables                                                                2 cables
                            cables      cables    cables    cables      cables                      cables

     1.0         11.0        10.5        13.5      12.0      15.5        14.0            44.0        38.0

     1.5         14.5        13.5        17.5      15.5      20.0        18.0            29.0        25.0

     2.5         19.5        18.0        24.0      21.0      27.0        25.0            18..0       15.0

     4.0         26.0        24.0        32.0      28.0      37.0        33.0            11.0         9.5

     6.0         34.0        31.0        41.0      36.0      47.0        43.0             7.3         6.4

    10.0         46.0        42.0        57.0      50.0      65.0        59.0             4.4         3.8

    16.0         61.0        56.0        76.0      68.0      87.0        79.0             2.8         2.4


Insulation:
The amount of heat generated should never exceed the maximum temperature rating,
of the insulation material.
           Table 4.5 - Derating factors (CI) for cables up to 10mm² in cross-sectional
           ---------------- area buried in thermal insulation.

                     Length in insulation (mm)                        Derating factor (CI)

                                 50                                             0.89

                                100                                             0.81

                                200                                             0.68

                                400                                             0.55



                                                     3
500 or more                                      0.50


If a cable is totally surrounded by thermal insulation for only a short length (for example,
where a cable passes through an insulated wall), the heating effect on the insulation will
not be so great because heat will be conducted from the short high-temperature length
through the cable conductor. Clearly, the longer the length of cable enclosed in the
insulation the greater will be the derating effect. {Table 4.5} shows the derating factors
for lengths in insulation of up to 400 mm and applies to cables having cross-sectional
area up to 10 mm²

Ambient Temperature:

The higher the ambient temperature, the less heat required to reach the maximum
temperature rating of the insulation.

         Table 4.3 Correction factors to current rating for ambient temperature
         -------------- (Ca) (from [Tables 4C1 and 4C2] of BS 7671: 1992)

            Ambient
                                               Type of insulation
          temperature

             (°C)         70°C p.v.c     85°C rubber        70°C m.i            105°C m.i

              25         1.03 (1.03)      1.02 (1.02)      1.03 (1.03)          1.02 (1.02)

              30         1.00 (1.00)      1.00 (1.00)      1.00 (1.00)          1.00 (1.00)

              35         0.94 (0.97)      0.95 (0.97)      0.93 (0.96)          0.96 (0.98)

              40         0.87 (0.94)      0.90 (0.95)      0.85 (0.93)          0.92 (0.96)

              45         0.79 (0.91)      0.85 (0.93)      0.77 (0.89)          0.88 (0.93)

              50         0.71 (0.97)      0.80 (0.91)      0.67 (0.86)          0.84 (0.91)


For example, if a cable has a rating of 24 A and an ambient temperature correction factor
of 0.77, the new current rating becomes 24 x 0.77 or 18.5 A.

Conductor Number:
Heat dissipation is lessened as the number of individually insulated conductors,
bundled together, is increased.
Installation Conditions:
Restricting the heat dissipation by installing the conductors in conduit, duct, trays or
raceways lessens the current carrying capacity. This restriction can be alleviated
somewhat by using proper ventilation methods, forced air cooling, etc.
Taking into account all the variables involved, no simple chart of current ratings can be
developed
and used as the final word when designing a system where amperage ratings can become
critical.



                                               4
The chart shows the current required to raise the temperatures of single insulated
conductor in
free air (30°C ambient) to the limits of various insulation types. The following table gives
a derating
factor to be used when the conductors are bundled. These charts should only be used as a
guide
when attempting to establish current ratings on conductor and cable.

4.1 Give a theoretically description of the dimension purpose and methods for the
protection against direct and indirect contact. The installation is a TN-C-S- system.

Direct contact protection

        The methods of preventing direct contact are mainly concerned with making sure
that people cannot touch live conductors. These methods include:
1-The insulation of live parts - this is the standard method. The insulated conductors
should be further protected by sheathing, conduit, etc.
2-The provision of barriers, obstacles or enclosures to prevent touching (IP2X). Where
surfaces are horizontal and accessible, IP4X protection (solid objects wider than 1 mm
are excluded - see {Table 2.4}), applies

         Table 2.4 - Numbers in the I P system

         First        Mechanical             Second         Water protection
         Number       protection against     Number         against

         0            Not protected          0              Not protected

                      Solid objects
         1                                   1              Dripping water
                      exceeding 50mm

                      Solid objects                         Dripping water when
         2                                   2
                      exceeding 12mm                        tilted up to 15

                      Solid objects
         3                                   3              Spraying water
                      exceeding 2.5mm

                      Solid objects
         4                                   4              Splashing Water
                      exceeding 1.0mm

         5            Dust protected         5              Water jets

         6            Dust tight             6              Heavy seas

         -            -                      7              Effects of immersion

         -            -                      8              Submersion




                                             5
3-placing out of reach or the provision of obstacles to prevent people from reaching live
parts
4-the provision of residual current devices (RCDs) provides supplementary protection
{5.9.1} but only when contact is from a live part to an earthed part.

        Indirect contact protection

There are three methods of providing protection from shock after contact with a
conductor which would not normally be live:
1-making sure that when a fault occurs and makes the parts live, it results in the supply
being cut off within a safe time. In practice, this involves limitation of earth fault loop
impedance, a subject dealt with in greater detail in {5.3.1}.
2-cutting off the supply before a fatal shock can be received using a residual current
device {5.9.1}.
3-applying local supplementary equipotential bonding which will ensure that the
resistance between parts which can be touched simultaneously is so low that it is
impossible for a dangerous potential difference to exist between them. It is important to
stress that whilst this course of action will eliminate the danger of indirect contact, it will
still be necessary to provide disconnection of the supply to guard against other faults,
such as overheating.
It is important to appreciate that in some cases a dangerous voltage may be maintained if
an un-interruptible power supply (UPS) or a standby generator with automatic starting is
in use.

5.3.1 – Principle

The path followed by fault current as the result of a low impedance occurring between
the phase conductor and earthed metal is called the earth fault loop. Current is driven
through the loop impedance by the supply voltage.
The extent of the earth fault loop for a TT system is shown in {Fig 5.7}, and is made up
of the following labeled parts.




                                 Fig 5.7 The earth fault loop



                                               6
l. - The phase conductor from the transformer to the installation
2- The protective device(s) in the installation
3- The installation phase conductors from the intake position to the fault
4 - The fault itself (usually assumed to have zero impedance)
5 - The protective conductor system
6 - The main earthing terminal
7 - The earthing conductor
8- The installation earth electrode
9- The general mass of earth
10- The Supply Company's earth electrode
11- The Supply Company's earthing conductor
12- The secondary winding of the supply transformer
For a TN-S system (where the Electricity Supply Company provides an earth terminal),
items 8 to 10 are replaced by the PE conductor, which usually takes the form of the
armoring (and sheath if there is one) of the underground supply cable.
For a TN-C-S system (protective multiple earthing) items 8 to 11 are replaced by the
combined neutral and earth conductor.
For a TN-C system (earthed concentric wiring), items 5 to 11 are replaced by the
combined neutral and earth wiring of both the installation and of the supply.
It is readily apparent that the impedance of the loop will probably be a good deal higher
for the TT system, where the loop includes the resistance of two earth electrodes as well
as an earth path, than for the other methods where the complete loop consists of metallic
conductors

5.9.1 - Why do we need residual current devices?

{5.3.1} has stressed that the standard method of protection is to make sure that an earth
fault results in a fault current high enough to operate the protective device quickly so that
fatal shock is prevented. However, there are cases where the impedance of the earth-fault
loop, or the impedance of the fault itself, are too high to enable enough fault current to
flow. In such a case, either:
1. - current will continue to flow to earth, perhaps generating enough heat to start a fire,
or
2. - metalwork which is open to touch may be at a high potential relative to earth,
resulting in severe shock danger.
Either or both of these possibilities can be removed by the installation of a residual
current device (RCD).
In recent years there has been an enormous increase in the use of initials for residual
current devices of all kinds. The following list, which is not exhaustive, may be helpful to
readers:
          RCD               residual current device
         RCCD            residual current operated circuit breaker
         SRCD            socket outlet incorporating an RCD
         PRCD            portable RCD, usually an RCD incorporated into a plug
         RCBO            an RCCD which includes overcurrent protection


                                             7
SRCBO            a socket outlet incorporating an RCBO




TN-C-S system

In this system, the installation is TN-S, with separate neutral and protective conductors.
The supply, however, uses a common conductor for both the neutral and the earth. This
combined earth and neutral system is sometimes called the 'protective and neutral
conductor' (PEN) or the 'combined neutral and earth' conductor (CNE). The system,
which is shown diagrammatically in Fig, is most usually called the protective multiple
earth (PME) system, which will be considered in greater detail in fig.




               Fig - TN-C-S earthing system - protective multiple earthing

TN-C-S System: The neutral and earth terminals are combined, but separated just
outside the consumer's installation.
Protective Devices
        All electrical circuits must be protected against over current therefore a protective
device has to be installed in order to isolate the fault from the supply so as to protect the
equipment and appliances from being damaged.
Over current is caused by:

                                               Two or more live conductors touching each
1) Short circuit
                                               other



                                              8
Adding loads greater than that of the rated
2) Overload
                                              value
                                              A phase conductor touching the protective
 3) Earth fault                               conductor by means of direct or indirect
                                              contact

If the electricity passes through a human body, the person will suffer electric shock and
burns. It could also cost damage to properties.
  The main causes of electrical accidents are:
  A) Lack of maintenance
  B) Failure or lack of earthing
  C) Unsafe and carelessness operating procedures
  D) Electrical wiring and equipment's physical form could have been damaged
  E) Incorrectly connected wires and other mistakes are usually caused by ignorance or
negligence

Direct and indirect contact

       There are two possible ways one can get electric shock. They are direct contact
and indirect contact.
       The severity of an electric shock is determined by the amount of current flowing
through the body. The effects of the electric shock can be very dangerous. It may even
prove fatal.
Here are the results:
~ 1mA - 2mA           No harmful effects
~ 5mA - 10mA          Painful and burning sensation
~ 10mA - 15mA         Muscular contraction
~ 20mA - 30mA         Impairs breathing or having breathing difficulties
~ 40mA and above Ventricular fibrillation or death

5.2 Describe the principal building of the 10kV switchboard and one single cubicle.

                              12kV ZS1 SWITCHBOARD

ZS1: simple, robust construction

The factory-assembled, typetested switchgear panels of type ZS1 tor 12 kV to 24 kV
rated voltage are metalclad, airinsulated and subdivided into part-compartments for
busbars, circuit-breaker, cable termination connections and low voltage equipment. ZS
switchgear panels contain withdrawable parts to accommodate the relevant switching
devices. These can be fitted either with vacuum circuit-breakers type
VD4 and VM1, SF6 circuitbreaker type or with vacuum contactors up to 12 kV.

ZS1: quickly installed




                                            9
The factory-assembled switchgear panels are erected side-by-side at site to form
switchgears. A baseframe laid in or on the floor is recommended for speedier and easier
alignment. The new type of busbar system can be installed in a very short time.




                                           10
12kV ZS1 SWITCHBOARD




STRUCTURE OF ONE SINGLE CUBICLE




              11
2.3 Dimensions and weights




                             12
2. Technical data
2.1 Electrical data
2.1.1 Main parameters for panels with circuit breakers




2.1.2 Dimensions and weights of 12/17.5 kV units




Cable connection of 12/17.5 kV units:

In the 550 and 650 mm wide panel, up to three parallel plastic cables can be connected
with singlecore cable protection and push-on sealing ends with a maximum cross-section
of 630 mm2.
In the 800 or 1000 mm wide panel, up to six parallel plastic cables can be connected with
single-core cable protection and push-on sealing ends with a maximum cross-section of
630 mm2.
Customer requests regarding connections to bars, three-core cables, special cables or
sealing ends
of different types must be considered during the order-planning stage


                                           13
Cable connection in the panels for 12kV, 17,5 kV and 24 kV:

In the panel with switch-disconnector 1 plastic one-core cable can be connected on each
phase with the cross-section up to 240 mm2 as standard.

2.1.3 Operating conditions
2.1.4 Normal operating conditions

The switchgears are basically suitable for normal operating conditions for indoor
switchgears and switchboards in accordance with IEC 60694. The following limit values,
among others, apply:
Ambient temperature:
Maximum + 40 0 C
Maximum 24 h average + 35 0 C
 Minimum (according to “minus 5 indoor class”) - 5 0 C
The maximum site altitude is 1000 m above sea level.

5.3 Describe the line protection equipment.

Circuit breaker

A circuit breaker is an automatically-operated electrical switch which is designed to
protect an electrical circuit from damage caused by overload or short circuit. Unlike a
fuse which operates once and then has to be replaced, a circuit breaker can be reset
(either manually or automatically) to resume normal operation. Circuit breakers are made
in varying sizes, from small devices which protect an individual household appliance up
to large switchgear designed to protect high voltage circuits feeding an entire city.
Some circuit breakers are implemented using a solenoid (electromagnet) whose pulling
force increases as the current increases. The circuit breaker's contacts are held closed by a
latch and, as the current in the solenoid increases, the solenoid's pull releases the latch
which then allows the contacts to open by spring action. Another method of sensing
current is with a bimetallic strip, which heats and bends with increased current, and is
similarly arranged to release the latch. Some circuit breakers incorporate both techniques,
with the electromagnet responding to short, large surges in current (short circuits) and the
bimetallic strip responding to less extreme but longer-term overcurrent conditions.
Circuit breakers for larger currents are usually arranged with pilot devices to sense a fault
current and to operate the trip opening mechanism.
Under short-circuit conditions a current of many times greater than normal can flow (see
maximum prospective short circuit current). When electrical contacts open to interrupt a
large current, there is a tendency for an arc to form between the opened contacts, which
would allow the flow of current to continue. Therefore, circuit breakers must incorporate
various features to divide and extinguish the arc. In air-insulated and miniature breakers
an arc chute structure consisting (often) of metal plates or ceramic ridges cools the arc,
and blowout coils deflect the arc into the arc chute. Larger circuit breakers such as those


                                             14
used in electrical power distribution may use vacuum, an inert gas such as sulfur
hexafluoride or have contacts immersed in oil to suppress the arc.
The maximum short-circuit current that a breaker can interrupt is determined by testing.
Application of a breaker in a circuit with a prospective short-circuit current higher than
the breaker's rating may result in failure of the breaker to safely interrupt a fault.
Small circuit breakers are either installed directly in equipment, or are arranged in a
breaker panel. Power circuit breakers are built into switchgear cabinets. High-voltage
breakers may be free-standing outdoor equipment or a component of a gas-insulated
switchgear line-up.

Miniature circuit breaker (MCB)

The advantages of a miniature circuit breaker (MCB) are:
1) Shorter tripping time
2) Can be reused
3) Easy to reset
4) Has a switch that can isolate the equipment
The disadvantages of a miniature circuit breaker (MCB) are:
1) The most expensive protection device for home use
2) Slow tripping time due to aging
3) Surrounding temperature may affect the MCB

FUSES

The fuse is a piece of wire which can carry a stated current. If the current rises above this
value it will melt.
If the fuse melts (blows) then there is an open circuit and no current can then flow thus
protecting the equipment by isolating it from the power supply.
The fuse must be able to carry slightly more than the normal operating current of the
equipment to allow for tolerances and small current surges.
With some equipment there is a very large surge of current for a short time at switch on.
If a fuse is fitted to withstand this large current there would be no protection against
faults which cause the current to rise slightly above the normal value.
Therefore special antisurge fuses are fitted. These can stand 10 times the rated current for
10 milliseconds. If the surge lasts longer than this the fuse will blow.
Always find out why the fuse blew before replacing it. Occasionly they grow tired and
fail. If the fuse is black and silvery then it is likely that there is a dead short (very low
resistance) somewhere.
What is the Difference Between a Fuse and a Circuit Breaker?
Fuses and circuit breakers are two different ways of protecting against suddenly large
overloads of electrical flow. Large power overloads are dangerous, potentially destroying
electrical equipment or causing a fire. Both fuses and circuit breakers will automatically
block against an incoming surge of electrical power past a certain safety limit. But while
they both accomplish the same task, each uses different technology in the way that it
stops the flow of electricity.


                                             15
Fuses are typically small objects that plug into a fusebox or other central location. They
are an early technology, dating back to the 19th century. Inside the fuse is a small piece
of metal, across which the electricity must pass. During normal flow of electricity, the
fuse permits the power to pass unobstructed. But during an unsafe overload, the small
piece of metal melts, stopping the flow of electricity. When a fuse is tripped, it should be
thrown away and replaced with a new fuse. As there are many varities of fuses available
that handle different capacities of electricity, care should be taken when choosing
replacement fuses.
Circuit breakers are a more recent invention and improve on fuse technology. Circuit
breakers are switches that are tripped when the electrical flow passes a safe limit. The
excess of electricity typically triggers an electromagnet, which trips the circuit breaker
when an unsafe limit is reached. Once tripped, the switches simply turn off. That stops
the flow of electricity, which will remain off until the switch is reset. To reset the flow of
electricity after the problem is resolved, the switch can simply be turned back on. Circuit
breakers are often located in a cabinet of individual switches, typically inside of an
apartment or other central place. While often used in homes, circuit breakers can be used
for much larger industrial applications as well.
Fuses and circuit breakers have unique advantages and disadvantages. One advantage of
fuses is that they are cheap and can be purchased from any hardware store, but they have
the drawback of needing to be replaced once they stop an overload. That can be
challenging in a darkened room. Alternatively, circuit breakers can simply be reset with a
flip of a switch after an overload. However, the technology can be more expensive than a
fusebox. Electricians are best qualified to determine whether fuses or circuit breakers are
better for a particular electrical installation.

5.4 Describe the10kV switchboard protection equipment.

SWITCHGEAR PROTECTION – 12 KV
Circuit Breakers

i) The circuit breakers shall be of standard design and construction conforming to IEC 60056 : 1987. The
interrupting medium of the circuit breaker shall be of Vacuum.

ii) The control mechanism of the circuit breakers shall be of spring assisted trip free type with remote /
local control selector switch and manual operational facility.

iii) The circuit breaker shall have a mechanical counter to register the number of circuit breaker operations.

iv) Characteristics of the Circuit Breakers shall be as follows;

a) Number of poles                                                            -3
b) Type                                                                      - Indoor
c) Rated voltage                                                              kV - 12
d) Rated frequency                                                            Hz - 50
e) Rated insulation level
          i) Impulse (1.2/50µs) withstand voltage (peak)                     kV - 75
          ii) Power frequency withstand voltage (rms)                        kV - 28 /1min.
f) Rated normal current                                                      A - 630/800
g)Rated shortcircuit breaking current (rms )                                 kA - 20
h) Rated short circuit making current                                        kA - 50 rms
i) First pole to clear factor                                                       - 1.5
j) Duty cycle                                                       `O’ - 3 min. - `CO’ - 3 min. -`CO’


                                                      16
k)Tripping supply voltage                                         VDC - 24

Protection

i) The programmable type numerical protection relays, conforming to IEC 60255, shall
be used. The relays used shall only be from the following manufactures of the countries
indicated.

a) ABB Relays AB, Sweden/Switzerland/Germany
b) Alsthom, England
c) Toshiba Corporation, Japan
d) Siemens AG, Germany
e) Group Schneider, England/France/Italy

ii) Necessary software package and the hand held programming unit shall be supplied
with the numerical protection relays to set the protection relays as required. For every
five panels one number of handheld programming unit shall be supplied. Software shall
be compatible with Windows 98 or upper versions.

iii) The numerical relay unit shall be suitable for use in the tropical climatic conditions as
given under the Clause 3.0 Service


iv) It shall be possible to select required type of over current and earth fault protection of
IDMT characteristics.

v) The numerical relay unit shall have provision for accommodating RTU for
incorporating SCADA system in the future.

Earthing

i) The copper earthing conductor shall be provided along the entire length of the panel.
The cross sectional area of earthing conductor shall be such that the current density shall
not exceed 200 A/mm² under the specified earth fault conditions.
5CEB STANDARD 025 : 2001

ii) It shall be possible to earth the cable with facility for padlocking, and mechanical
interlocking shall be provided to prevent earthing the busbar.

iii) All metallic parts of the functional units intended to be earthed shall be bonded to the
earthing conductor of the panel.


5.5 Describe the 60 / 10kV transformer protection equipment.

Transformer Protection

Transformers–600V or Less


                                             17
If secondary fuse protection is not provided then the primary fuses must not be
sized larger than as shown below.
Individual transformer primary fuses are not necessary where the primary circuit fuse
provides this protection.




       Primary Fuse (600V or less) and Secondary Fuse (600V or less). If secondary
(600V or less) fuses are sized not greater than 125% of transformer secondary current,
individual transformer fuses are not required in the primary (600V or less) provided the
primary feeder fuses are not larger than 250% of the transformer rated primary current.




Note: Transformer overload protection will be sacrificed by using overcurrent protective
devices sized much greater than the transformer F.L.A. The limits of 150%, 167%, 250%
and 300% may not adequately protect transformers. It is suggested that for the highest
degree of transformer overload protection the fuse size should be within 125% of the
transformer full-load amperes.

        There is a wide fuse ampere rating range available to properly protect
transformers. FUSETRON® Class RK5 and LOW-PEAK® YELLOW Class RK1 dual-

                                            18
element fuses can be sized on the transformer primary and/or secondary rated at 125% of
the transformer F.L.A. These dual-element fuses have sufficient time-delay to withstand
the high magnetizing inrush currents of transformers. There is a wide ampere rating
selection in the 0 to 15 ampere range for these dual-element fuses to provide protection
for even small control transformers. The required secondary protection may be satisfied
with multiple overcurrent devices that protect feeders fed from the transformer
secondary. The total ampere rating of these multiple devices may not exceed the allowed
value of a single secondary overcurrent device. If this method is chosen, dual-element,
timedelay fuse protection offers much greater flexibility. Note the following examples:




Design 1: Utilizes a single secondary overcurrent device. It provides the greatest degree
of selective coordination, transformer protection, secondary cable protection, and
switchboard/panelboard/ load center protection. The transformer cannot be overloaded
to a significant degree if future loads are added (improperly). With this arrangement the
transformer’s full capacity is utilized.


Design 2: In this case the single secondary overcurrent device is eliminated, much of the
protection described in Design 1 will be reduced.




                                            19
If dual-element fuses are utilized as branch circuit protection, the transformer can
continue to be loaded with the five 83 amp motors because 5 ≈ 110 = 550 amps, (less
than the maximum 600 amps). If additional loads are improperly added in the future,
overload protecton will be lost because the primary device can be sized
at 250%.

Design 3: If the single secondary overcurrent device is eliminated and MCP’s are utilized
as branch circuit protection, the transformer will be seriously under-utilized because only
one motor can be connected.




                                             20
For one motor, 1 ≈ 700% of 83 = 581 amps. For two motors, 2 ≈ 700% of 83 =
1162 amps. Since the sum of the devices cannot exceed 600 amps, only one motor can be
connected when the motor circuit is protected by an MCP.

Design 4: Using the same procedure, if the single secondary main is eliminated and
thermal magnetic circuit breakers are utilized as branch circuit protection per 430.52,
only three of the motors can be connected because the thermal magnetic breakers will
have been sized at approximately 250% of the motor F.L.A. (83 ≈ 250% = 207.5A.)




Using a 200 ampere circuit breaker would allow only three (600 ÷ 200) motors to be
connected. To add two additional motors of the same type as shown in Design 1 and
Design 2 requires a larger transformer - one that would have a 1000 ampere or more
secondary capability. A 300 KVA 208V transformer has a 830 ampere secondary rating
which is not sufficient. Therefore, the next standard size 3Ø transformer is a 400 KVA
with a 1110 ampere capacity to meet the new rule.

6.1 Give a theoretically description of selectivity considerations.

A theoretical outline of selectivity

Selection of the protection system of the electrical installation is fundamental both to
guarantee correct economical and functional service of the whole installation and to
reduce the problems caused by abnormal service conditions or actual faults to a
minimum.
Within the sphere of this analysis, the coordination between the various devices dedicated
to protection of sections of installation or specific components is studied in order to:


                                            21
– guarantee safety of the installation and of people in all cases;
– rapidly identify and exclude just the area involved in the problem, without
indiscriminate trips which reduce the availability of energy in areas not involved in the
fault;
– reduce the effects of the fault on other integral parts of the installation (reduction in the
voltage value, and loss of stability in rotating machines);
– reduce the stress on components and damage to the area involved;
– guarantee service continuity with good quality power supply voltage;
– guarantee adequate support in the case of malfunction of the protection delegated to
opening;
– provide the personnel in charge of maintenance and the management system with the
information needed to restore service to the rest of the network as rapidly as possible and
with the least interference;
– achieve a good compromise between reliability, simplicity and cost-effectiveness.

In detail, a good protection system must be able to:

– perceive what has happened and where, discriminating between abnormal but tolerable
situations and fault situations within its zone of competence, avoiding unwanted trips
which cause unjustified stoppage of a sound part of the installation;
– act as rapidly as possible to limit the damage (destruction, accelerated ageing, etc.),
safeguarding
power supply continuity and stability.

The solutions come from a compromise between these two antithetic requirements –
precise identification of the fault and rapid tripping - and are defined according to which
requirement is privileged.

Selectivity techniques

This section describes the different selectivity techniques and their area of application.
In the overload zone with the protections in play, time-current type selectivity is usually
realised.
In the short-circuit zone with the protections in play, various selectivity techniques can be
used. In particular, the following will be illustrated in the paragraphs below:

Current selectivity
Time selectivity
Energy selectivity
Zone selectivity.

After an initial theoretical description of the different selectivity techniques, the
selectivity technique which can be used appropriately for the different types of circuit-
breakers will then be analysed.




                                              22
Time-current selectivity

In general, the protections against overload have a definite time characteristic, whether
they are made by means of a thermal release or by means of function L of an electronic
release. A definite time characteristic is intended as a trip characteristic where, as the
current increases, the trip time of the circuit-breaker decreases. When there are
protections with characteristics of this type, the selectivity technique used is time-current
selectivity.
Time-current selectivity makes trip selectivity by adjusting the protections so that the
load-side protection, for all possible overcurrent values, trips more rapidly than the
supply-side circuit-breaker.
When the trip times of the two circuit-breakers are analyzed, it is necessary to consider:

- The tolerances over the thresholds and trip times
- The real currents circulating in the circuit-breakers.

1.05 x I1 of the supply-side circuit-breaker
Assuming IA =1.05xI1, with reference to what has been said about
the real currents which circulate in the circuit-breakers, the IB current
is obtained on the load side.
The trip times of the two devices are obtained from the time-current
curves.




1.20XI3 (or I2) of the load-side circuit-breaker
Assuming IB = 1.20XI3 (or I2), the IA current is obtained in the same
way on the supply side and, from the time-current curves, the trip
times of the two devices are obtained.
If the following is true for both the points considered:
tA>tB
then selectivity in the overload zone is guaranteed.




                                              23
Current selectivity

This type of selectivity is based on the observation that the closer the fault point is to the
power supply of the installation, the higher the short-circuit current is. It is therefore
possible to discriminate the zone the fault occurred in by setting the instantaneous
protections to different current values.
Total selectivity can normally be achieved in specific cases only where the fault current is
not high and where there is a component with high impedance interposed between the
two protections (transformer, very long cable or a cable with reduced cross-section, etc.)
and therefore a great difference between the short-circuit current values.

However:

– The ultimate selectivity current is usually low and therefore selectivity is often only
partial;
– The setting level of the protections against overcurrents rises rapidly;
– Redundancy of the protections, which guarantees elimination of the fault (rapidly) in
the case of one of them not operating, is not possible.

– The protection against short-circuit of supply-side circuit-breaker A will be set to a
value which means it
does not trip for faults which occur on the load side of protection B. (In the example in
the figure I3minA >
1kA)
– The protection of load-side circuit-breaker B will be set so as not to trip for faults
which occur on its load
side. (In the example in the figure I3MaxB < 1kA)
Obviously the setting of the protections must take into account the real currents
circulating in the circuitbreakers.




                                             24
The ultimate selectivity value which can be obtained is equal to the instantaneous trip
threshold of the supply-side protection less any tolerance.

Is = I3minA




Time selectivity

This type of selectivity is an evolution of the previous one. In this type of coordination,
apart from the trip threshold in terms of current, a trip time is also defined: a certain
current value will make the protections trip after a defined time delay, suitable for
allowing any protections placed closer to the fault to trip, excluding the area which is the
seat of the fault.
The setting strategy is therefore to progressively increase the current thresholds and the
trip delays as one gets closer to the power supply sources (level of setting directly
correlated to the hierarchical level). The delayed trip thresholds must take into account
the tolerances of the two protection devices and the effective currents which circulate in
them.
As in the case of current selectivity, the study is made by comparing the time-current trip
curves of the protection devices.

Generally this type of coordination:

- is easy to study and realize;
- is not very costly with regard to the protection system;
- allows even high selectivity limit values to be obtained (if Icw is high);

                                             25
- allows redundancy of the protection functions.

However:

- the trip times and energy levels let through by the protections, especially by those close
to the sources, are high.
It is a type of selectivity which can also be made between circuit-breakers of the same
size, equipped with electronic releases with delayed protection against short-circuit.
The protections against short-circuit of the two circuit-breakers will be set:
- with the I2 trip thresholds against delayed short-circuit adjusted so as not to create trip
overlapping,
taking into consideration the tolerances and the real currents circulating in the circuit-
breakers.
- with t2 trip times adjusted so that the load-side circuit-breaker B extinguishes the fault
whereas the
supply-side circuit-breaker A, still in the timing phase, manages to “see” the extinction of
the current
and therefore remains closed.




The ultimate selectivity limit which is obtained is equal:

– to the instantaneous trip threshold of the supply-side protection,
if this function is enabled, less any tolerance:

Is = I3minA

– to the value of Icw for supply-side air circuit-breakers when the instantaneous
protection function is set to OFF.




                                             26
Energy selectivity

Coordination of energy type is a particular type of selectivity which exploits the current-
limiting
characteristics of moulded-case circuit-breakers. It is pointed out that a current-limiting
circuit-breaker is “a circuit-breaker with a sufficiently short trip time to prevent the short-
circuit current from reaching the peak value which would otherwise be reached” (IEC
60947-2). In practice, all the ABB SACE moulded-case circuitbreakers of the Isomax and
Tmax series, the modular circuit-breakers and the E2L E3L air current-limiting circuit-
breakers have more or less marked current-limiting characteristics.

The protections against short-circuit of the two circuit-breakers must respect the
conditions given below.

- Supply-side release of thermomagnetic type
the magnetic trip thresholds must be such so as not to create trip overlapping, taking into
consideration the tolerances and the real currents circulating in the circuit-breakers; the
magnetic threshold of the supply-side circuit-breaker must be equal to or higher
than10xIn or set to the maximum value when it is adjustable.


- Supply-side release of electronic type
any protections against delayed short-circuit S must be adjusted following the same
indications as time selectivity;
the instantaneous protection function I of the supply-side circuit-breakers must be set to
off




                                              27
The Is ultimate selectivity limit obtained is the one given in the tables




Zone selectivity

This type of coordination is an evolution of time coordination. In general, zone selectivity
is made by means of dialogue between the current measuring devices which, once the
setting threshold has been detected as having been exceeded, allows just the fault zone to
be identified correctly and the power supply to it to be cut off.

It can be realised in two ways:

– the measuring devices send the information linked to
the current setting threshold having been exceeded to a
supervision system and the latter identifies which
protection has to intervene;
– when there are current values higher than their setting,
each protection sends a lock signal by means of a direct
connection or a bus to the hierarchically higher level
protection (on the supply side in relation to the power
flow direction) and, before intervening, checks that a
similar lock signal has not arrived from the load-side
protection. In this way only the protection immediately
to the supply side of the fault intervenes.




                                             28
Compared with coordination of time type, zone selectivity allows:

- reduction of the trip times (these can be lower than hundred milliseconds);
- reduction both of the damage caused by the fault and of interferences to the power
supply system;
- reduction of the thermal and dynamic stresses on the components of the installation;
- a very high number of selectivity levels to be obtained. However:
- it is more burdensome both in terms of cost and of complexity of the installation
- it requires an auxiliary supply.

This is a type of selectivity which can be realised:

- between Emax air circuit-breakers equipped with PR122 and PR123 releases.
The ultimate selectivity limit which can be obtained is equal to the Icw Is = Icw
- between Tmax T4L,T5L and T6L moulded-case circuit-breakers equipped with PR223
EF releases.
The ultimate selectivity limit which can be obtained is 100kA Is = 100kA
Then, by means of the additional IM210 module, it is possible to make a chain of zone
selectivity between Tmax and Emax.




                                             29
FINAL CONCLUSION

        In this report, we had some knowledge about low voltage installations. At the
same time, this report includes protection techniques. We learnt that in TNCS systems,
fuses and circuit breakers are very important for protecting from direct and indirect
contact ( and overload, short circuit) . Furthermore, we tried to describe principal
building of the 12 KV switchboard, one single cubicle and protection equipment. We saw
that selectivity considerations are quiet important for installation. And it is not easy to
select devices, because it is about safety.

        Of course this report will not satisfy you, but we tried to do our best. We tried to
find all theoretical information about this report.




                                             30

More Related Content

What's hot

What's hot (20)

Electrical wiring system
Electrical wiring systemElectrical wiring system
Electrical wiring system
 
Electrical System Design
Electrical System Design Electrical System Design
Electrical System Design
 
HV testing of insulator
HV testing of insulatorHV testing of insulator
HV testing of insulator
 
Generators
GeneratorsGenerators
Generators
 
underground cable in transmission grid
underground cable in transmission gridunderground cable in transmission grid
underground cable in transmission grid
 
Supply system (Electrical Power System)
Supply system (Electrical Power System)Supply system (Electrical Power System)
Supply system (Electrical Power System)
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ec
 
Lightening Arrester.pptx
Lightening Arrester.pptxLightening Arrester.pptx
Lightening Arrester.pptx
 
Transmission and distribution system of electricity
Transmission and distribution system of electricity Transmission and distribution system of electricity
Transmission and distribution system of electricity
 
Earthing or Grounding
Earthing or GroundingEarthing or Grounding
Earthing or Grounding
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system
 
WIRING ACCESORIES AND LIGHTING.pptx
WIRING ACCESORIES AND LIGHTING.pptxWIRING ACCESORIES AND LIGHTING.pptx
WIRING ACCESORIES AND LIGHTING.pptx
 
Wiring systems
Wiring systemsWiring systems
Wiring systems
 
ELECTRICAL WIRING
ELECTRICAL WIRINGELECTRICAL WIRING
ELECTRICAL WIRING
 
Earthing, grounding and isolation
Earthing, grounding and isolation Earthing, grounding and isolation
Earthing, grounding and isolation
 
Earthing
EarthingEarthing
Earthing
 
Domestic wiring
Domestic wiringDomestic wiring
Domestic wiring
 
Electrical services
Electrical servicesElectrical services
Electrical services
 
Electrical wiring system - and estimation
Electrical wiring system -  and estimation Electrical wiring system -  and estimation
Electrical wiring system - and estimation
 
Electrical wiring domestic and industries
Electrical wiring domestic and industriesElectrical wiring domestic and industries
Electrical wiring domestic and industries
 

Viewers also liked

03 ptcc under over voltage protection
03 ptcc under over voltage protection03 ptcc under over voltage protection
03 ptcc under over voltage protectionduytn1
 
voltage regulators
voltage regulatorsvoltage regulators
voltage regulatorsRahul Jadhav
 
Zener diode voltage regulator (ALIV - Bangladesh)
Zener diode voltage regulator (ALIV - Bangladesh)Zener diode voltage regulator (ALIV - Bangladesh)
Zener diode voltage regulator (ALIV - Bangladesh)Md Abu Jauad Khan Aliv
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulatorsgajju177
 
Voltage regulation
Voltage regulationVoltage regulation
Voltage regulationpopet
 
Protection against over voltage under voltage using oamp
Protection against over voltage under voltage using oampProtection against over voltage under voltage using oamp
Protection against over voltage under voltage using oampAnkan Biswas
 
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEDETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEvishalgohel12195
 
Grid Voltage Regulation
Grid Voltage RegulationGrid Voltage Regulation
Grid Voltage RegulationAditya Nehwal
 
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...Michael George
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulatorJohnny Chan
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical applianceNishant Kumar
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulatorniiraz
 
electrical distribution system ppt/13b61a0221
electrical distribution system ppt/13b61a0221electrical distribution system ppt/13b61a0221
electrical distribution system ppt/13b61a0221saikrishna kandhikatla
 
Electrical Engineering Presentation
Electrical Engineering PresentationElectrical Engineering Presentation
Electrical Engineering Presentationjoe2002
 
Controller area network -ppt
Controller area network -pptController area network -ppt
Controller area network -pptvelichetiphani
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulatorsAnita Thattil
 
Zener diode as a voltage Regulator
Zener diode as a voltage RegulatorZener diode as a voltage Regulator
Zener diode as a voltage RegulatorSanjaySingh011996
 

Viewers also liked (20)

03 ptcc under over voltage protection
03 ptcc under over voltage protection03 ptcc under over voltage protection
03 ptcc under over voltage protection
 
voltage regulators
voltage regulatorsvoltage regulators
voltage regulators
 
Zener diode voltage regulator (ALIV - Bangladesh)
Zener diode voltage regulator (ALIV - Bangladesh)Zener diode voltage regulator (ALIV - Bangladesh)
Zener diode voltage regulator (ALIV - Bangladesh)
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulators
 
Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
Voltage regulation
Voltage regulationVoltage regulation
Voltage regulation
 
Protection against over voltage under voltage using oamp
Protection against over voltage under voltage using oampProtection against over voltage under voltage using oamp
Protection against over voltage under voltage using oamp
 
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEDETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
 
Zener diode
Zener diodeZener diode
Zener diode
 
Grid Voltage Regulation
Grid Voltage RegulationGrid Voltage Regulation
Grid Voltage Regulation
 
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
SINGLE PHASING, PHASE REVERSAL, OVERVOLTAGE, UNDER VOLTAGE AND OVERHEATING PR...
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulator
 
Zener diodes
Zener diodesZener diodes
Zener diodes
 
Presentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliancePresentation on Over-/under-voltage protection of electrical appliance
Presentation on Over-/under-voltage protection of electrical appliance
 
Voltage regulator
Voltage regulatorVoltage regulator
Voltage regulator
 
electrical distribution system ppt/13b61a0221
electrical distribution system ppt/13b61a0221electrical distribution system ppt/13b61a0221
electrical distribution system ppt/13b61a0221
 
Electrical Engineering Presentation
Electrical Engineering PresentationElectrical Engineering Presentation
Electrical Engineering Presentation
 
Controller area network -ppt
Controller area network -pptController area network -ppt
Controller area network -ppt
 
Ic voltage regulators
Ic voltage regulatorsIc voltage regulators
Ic voltage regulators
 
Zener diode as a voltage Regulator
Zener diode as a voltage RegulatorZener diode as a voltage Regulator
Zener diode as a voltage Regulator
 

Similar to Low voltage systems

General condition-relating-to-electricity new
General condition-relating-to-electricity newGeneral condition-relating-to-electricity new
General condition-relating-to-electricity newDineshsenthil
 
2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)Sofics
 
Current carrying capacities & other technical tables
Current carrying capacities & other technical tablesCurrent carrying capacities & other technical tables
Current carrying capacities & other technical tablesasif raza
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 
Proposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorProposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorIOSR Journals
 
Components resistors
Components   resistorsComponents   resistors
Components resistorssld1950
 
Cable ampacity calculations iec
Cable ampacity calculations  iecCable ampacity calculations  iec
Cable ampacity calculations iecJoe Khan
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IECJoe Khan
 
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN ApprovedNexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN ApprovedThorne & Derrick International
 
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN ApprovedNexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN ApprovedThorne & Derrick International
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable SizingLeonardo ENERGY
 
[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf
[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf
[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdfwilliamaro2
 

Similar to Low voltage systems (20)

General condition-relating-to-electricity new
General condition-relating-to-electricity newGeneral condition-relating-to-electricity new
General condition-relating-to-electricity new
 
2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)2012 Protection strategy for EOS (IEC 61000-4-5)
2012 Protection strategy for EOS (IEC 61000-4-5)
 
Current carrying capacities & other technical tables
Current carrying capacities & other technical tablesCurrent carrying capacities & other technical tables
Current carrying capacities & other technical tables
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
Fuses mv
Fuses mvFuses mv
Fuses mv
 
Testing
TestingTesting
Testing
 
Proposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorProposal Technique for an Static Var Compensator
Proposal Technique for an Static Var Compensator
 
Components resistors
Components   resistorsComponents   resistors
Components resistors
 
H046044147
H046044147H046044147
H046044147
 
Cable ampacity calculations iec
Cable ampacity calculations  iecCable ampacity calculations  iec
Cable ampacity calculations iec
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IEC
 
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN ApprovedNexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
 
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN ApprovedNexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
Nexans 11kV Single Core XLPE Cables (300mm2 Cu) UKPN Approved
 
Mcb c60 h dc
Mcb c60 h dcMcb c60 h dc
Mcb c60 h dc
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable Sizing
 
O0704080084
O0704080084O0704080084
O0704080084
 
22
2222
22
 
Sheath bonding method for underground cables
Sheath bonding method for underground cablesSheath bonding method for underground cables
Sheath bonding method for underground cables
 
HVM NFPA 70E White Paper
HVM NFPA 70E White PaperHVM NFPA 70E White Paper
HVM NFPA 70E White Paper
 
[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf
[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf
[Gönen,_Turan]_Electrical_power_transmission_system2-95-132.pdf
 

More from freelay

Control And Programingof Synchronous Generator
Control And Programingof Synchronous GeneratorControl And Programingof Synchronous Generator
Control And Programingof Synchronous Generatorfreelay
 
Ruido y vibraciones de instalaciones electricas en edificios
Ruido y vibraciones de instalaciones electricas en edificiosRuido y vibraciones de instalaciones electricas en edificios
Ruido y vibraciones de instalaciones electricas en edificiosfreelay
 
Proyecto centros de transformacion
Proyecto centros de transformacionProyecto centros de transformacion
Proyecto centros de transformacionfreelay
 
Lighting protection of an office building
Lighting protection of an office buildingLighting protection of an office building
Lighting protection of an office buildingfreelay
 
La transicion energetica y el cambio climatico
La transicion energetica y el cambio climaticoLa transicion energetica y el cambio climatico
La transicion energetica y el cambio climaticofreelay
 
Ensayos en un transformacion trifasico
Ensayos en un transformacion trifasicoEnsayos en un transformacion trifasico
Ensayos en un transformacion trifasicofreelay
 
Diseño de una subestacion de intermperie 132 45 kv
Diseño de una subestacion de intermperie 132 45 kvDiseño de una subestacion de intermperie 132 45 kv
Diseño de una subestacion de intermperie 132 45 kvfreelay
 

More from freelay (7)

Control And Programingof Synchronous Generator
Control And Programingof Synchronous GeneratorControl And Programingof Synchronous Generator
Control And Programingof Synchronous Generator
 
Ruido y vibraciones de instalaciones electricas en edificios
Ruido y vibraciones de instalaciones electricas en edificiosRuido y vibraciones de instalaciones electricas en edificios
Ruido y vibraciones de instalaciones electricas en edificios
 
Proyecto centros de transformacion
Proyecto centros de transformacionProyecto centros de transformacion
Proyecto centros de transformacion
 
Lighting protection of an office building
Lighting protection of an office buildingLighting protection of an office building
Lighting protection of an office building
 
La transicion energetica y el cambio climatico
La transicion energetica y el cambio climaticoLa transicion energetica y el cambio climatico
La transicion energetica y el cambio climatico
 
Ensayos en un transformacion trifasico
Ensayos en un transformacion trifasicoEnsayos en un transformacion trifasico
Ensayos en un transformacion trifasico
 
Diseño de una subestacion de intermperie 132 45 kv
Diseño de una subestacion de intermperie 132 45 kvDiseño de una subestacion de intermperie 132 45 kv
Diseño de una subestacion de intermperie 132 45 kv
 

Recently uploaded

FILIPINO PSYCHology sikolohiyang pilipino
FILIPINO PSYCHology sikolohiyang pilipinoFILIPINO PSYCHology sikolohiyang pilipino
FILIPINO PSYCHology sikolohiyang pilipinojohnmickonozaleda
 
GRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTS
GRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTSGRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTS
GRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTSJoshuaGantuangco2
 
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...Postal Advocate Inc.
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxthorishapillay1
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Jisc
 
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdfInclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdfTechSoup
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfSpandanaRallapalli
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfMr Bounab Samir
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxHumphrey A Beña
 
Culture Uniformity or Diversity IN SOCIOLOGY.pptx
Culture Uniformity or Diversity IN SOCIOLOGY.pptxCulture Uniformity or Diversity IN SOCIOLOGY.pptx
Culture Uniformity or Diversity IN SOCIOLOGY.pptxPoojaSen20
 
AUDIENCE THEORY -CULTIVATION THEORY - GERBNER.pptx
AUDIENCE THEORY -CULTIVATION THEORY -  GERBNER.pptxAUDIENCE THEORY -CULTIVATION THEORY -  GERBNER.pptx
AUDIENCE THEORY -CULTIVATION THEORY - GERBNER.pptxiammrhaywood
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptxmary850239
 
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONTHEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONHumphrey A Beña
 
4.16.24 21st Century Movements for Black Lives.pptx
4.16.24 21st Century Movements for Black Lives.pptx4.16.24 21st Century Movements for Black Lives.pptx
4.16.24 21st Century Movements for Black Lives.pptxmary850239
 
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITYISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITYKayeClaireEstoconing
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomnelietumpap1
 
Science 7 Quarter 4 Module 2: Natural Resources.pptx
Science 7 Quarter 4 Module 2: Natural Resources.pptxScience 7 Quarter 4 Module 2: Natural Resources.pptx
Science 7 Quarter 4 Module 2: Natural Resources.pptxMaryGraceBautista27
 

Recently uploaded (20)

FILIPINO PSYCHology sikolohiyang pilipino
FILIPINO PSYCHology sikolohiyang pilipinoFILIPINO PSYCHology sikolohiyang pilipino
FILIPINO PSYCHology sikolohiyang pilipino
 
GRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTS
GRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTSGRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTS
GRADE 4 - SUMMATIVE TEST QUARTER 4 ALL SUBJECTS
 
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
USPS® Forced Meter Migration - How to Know if Your Postage Meter Will Soon be...
 
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptxYOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptx
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...
 
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdfInclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdf
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
 
Culture Uniformity or Diversity IN SOCIOLOGY.pptx
Culture Uniformity or Diversity IN SOCIOLOGY.pptxCulture Uniformity or Diversity IN SOCIOLOGY.pptx
Culture Uniformity or Diversity IN SOCIOLOGY.pptx
 
AUDIENCE THEORY -CULTIVATION THEORY - GERBNER.pptx
AUDIENCE THEORY -CULTIVATION THEORY -  GERBNER.pptxAUDIENCE THEORY -CULTIVATION THEORY -  GERBNER.pptx
AUDIENCE THEORY -CULTIVATION THEORY - GERBNER.pptx
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx
 
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptxYOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
 
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONTHEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
 
4.16.24 21st Century Movements for Black Lives.pptx
4.16.24 21st Century Movements for Black Lives.pptx4.16.24 21st Century Movements for Black Lives.pptx
4.16.24 21st Century Movements for Black Lives.pptx
 
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITYISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choom
 
Raw materials used in Herbal Cosmetics.pptx
Raw materials used in Herbal Cosmetics.pptxRaw materials used in Herbal Cosmetics.pptx
Raw materials used in Herbal Cosmetics.pptx
 
Science 7 Quarter 4 Module 2: Natural Resources.pptx
Science 7 Quarter 4 Module 2: Natural Resources.pptxScience 7 Quarter 4 Module 2: Natural Resources.pptx
Science 7 Quarter 4 Module 2: Natural Resources.pptx
 

Low voltage systems

  • 1. Esta obra está bajo una licencia de Creative Commons. INTRODUCTION Low Voltage Systems Depending on the application, they include equipment for switching, protecting, conversion, control, regulation, monitoring and measurement of electrical equipment such as motor pumps, fans, lighting and emergency system. The dimensions and terms of low voltage switchgear assemblies have been standardized. Also, barriers and partition, such as internal segregation of functional areas, i.e. between the busbars, switching apparatus, cables and as protection for the operating personnel have been considered. Depending on the type, switchgear apparatus can be used for single or multiple switching tasks. Switching tasks can also be conducted by a combination of several switchgear units of fixed or draw-out installation type and can be actuated by different types of protection as in case of motor control centers (MCC). The main switching apparatus are:  Circuit breakers (CB)  Contactors  Motor starter  Fuse combination unit  Miniature circuit breaker (MCB) In most cases of power plant low voltage switchgear, several over current protection devices are connected in series between the current source and apparatus to be protected in case of fault. These devices must operate selectively to limit a fault to the place of its origin as far as possible. Redundancies in the switchgear design ensure the availability of energy supply. Separated Extra Low Voltage (SELV) A Separated Extra Low Voltage (SELV) circuit must be  safely separated from other circuits that carry higher voltages;  isolated from earth (ground) and from the protective earth conductors of other circuits. The safety of an SELV circuit is provided by  the extra low voltage; 1
  • 2. the low risk of accidental contact with a higher voltage;  the lack of a return path through earth (ground) that a current could take in case of contact with a human body. The design of an SELV circuit typically involves an insulation transformer, guaranteed minimum distances between conductors, and insulation barriers. The connectors of SELV circuits should be designed such that they do not mate with connectors commonly used for non-SELV circuits. Protected Extra Low Voltage (PELV) In contrast to an SELV circuit, a Protected Extra Low Voltage (PELV) circuit has a protective earth (ground) connection. A PELV circuit, just as with SELV, requires a design that guarantees a low risk of accidental contact with a higher voltage. For a transformer, this can mean that the primary and secondary windings must be separated by an extra insulation barrier or by a conductive shield with a protective earth connection. Functional Extra Low Voltage (FELV) The term Functional Extra Low Voltage (FELV) describes any other extra low voltage circuit that does not fulfill the requirements for an SELV or PELV circuit. Although the FELV part of a circuit uses an extra low voltage, it is not adequately protected from accidental contact with higher voltages in other parts of the circuit. Therefore the protection requirements for the higher voltage have to be applied to the entire circuit. Examples for FELV circuits include those that generate an extra low voltage through a semiconductor device or a potentiometer. 1. Make a overview drawing of the installation with: 60 / 10kV transformer station and connection to T , TR.T. , HT , UT , L1 , L2 , L3.Determinate the point of supply. 2.1 Give a theoretically description of the dimension purpose and methods for the overload protection and current value calculation Iz. Current Carrying Capacity of Copper Conductors 2
  • 3. Current carrying capacity is defined as the amperage a conductor can carry before melting either the conductor or the insulation. Heat, caused by an electrical current flowing through a conductor, will determine the amount of current a wire will handle. Theoretically, the amount of current that can be passed through a single bare copper wire can be increased until the heat generated reaches the melting temperature of the copper. There are many factors which will limit the amount of current that can be passed through a wire. These major determining factors are: Conductor Size: The larger the circular mil area, the greater the current capacity. Table 4.6 - Current ratings and volt drops for unsheathed single core p.v.c. insulated cables In In Cross conduit conduit In In Clipped Clipped sectional in in conduit conduit Volt drop Volt drop direct direct area thermal thermal on wall on wall insulation insulation (mm²) (A) (A) (A) (A) (A) (A) (mV/A/m) (mV/A/m) 3 or 4 2 3 or 4 2 3 or 4 3 or 4 - 2 cables 2 cables cables cables cables cables cables cables 1.0 11.0 10.5 13.5 12.0 15.5 14.0 44.0 38.0 1.5 14.5 13.5 17.5 15.5 20.0 18.0 29.0 25.0 2.5 19.5 18.0 24.0 21.0 27.0 25.0 18..0 15.0 4.0 26.0 24.0 32.0 28.0 37.0 33.0 11.0 9.5 6.0 34.0 31.0 41.0 36.0 47.0 43.0 7.3 6.4 10.0 46.0 42.0 57.0 50.0 65.0 59.0 4.4 3.8 16.0 61.0 56.0 76.0 68.0 87.0 79.0 2.8 2.4 Insulation: The amount of heat generated should never exceed the maximum temperature rating, of the insulation material. Table 4.5 - Derating factors (CI) for cables up to 10mm² in cross-sectional ---------------- area buried in thermal insulation. Length in insulation (mm) Derating factor (CI) 50 0.89 100 0.81 200 0.68 400 0.55 3
  • 4. 500 or more 0.50 If a cable is totally surrounded by thermal insulation for only a short length (for example, where a cable passes through an insulated wall), the heating effect on the insulation will not be so great because heat will be conducted from the short high-temperature length through the cable conductor. Clearly, the longer the length of cable enclosed in the insulation the greater will be the derating effect. {Table 4.5} shows the derating factors for lengths in insulation of up to 400 mm and applies to cables having cross-sectional area up to 10 mm² Ambient Temperature: The higher the ambient temperature, the less heat required to reach the maximum temperature rating of the insulation. Table 4.3 Correction factors to current rating for ambient temperature -------------- (Ca) (from [Tables 4C1 and 4C2] of BS 7671: 1992) Ambient Type of insulation temperature (°C) 70°C p.v.c 85°C rubber 70°C m.i 105°C m.i 25 1.03 (1.03) 1.02 (1.02) 1.03 (1.03) 1.02 (1.02) 30 1.00 (1.00) 1.00 (1.00) 1.00 (1.00) 1.00 (1.00) 35 0.94 (0.97) 0.95 (0.97) 0.93 (0.96) 0.96 (0.98) 40 0.87 (0.94) 0.90 (0.95) 0.85 (0.93) 0.92 (0.96) 45 0.79 (0.91) 0.85 (0.93) 0.77 (0.89) 0.88 (0.93) 50 0.71 (0.97) 0.80 (0.91) 0.67 (0.86) 0.84 (0.91) For example, if a cable has a rating of 24 A and an ambient temperature correction factor of 0.77, the new current rating becomes 24 x 0.77 or 18.5 A. Conductor Number: Heat dissipation is lessened as the number of individually insulated conductors, bundled together, is increased. Installation Conditions: Restricting the heat dissipation by installing the conductors in conduit, duct, trays or raceways lessens the current carrying capacity. This restriction can be alleviated somewhat by using proper ventilation methods, forced air cooling, etc. Taking into account all the variables involved, no simple chart of current ratings can be developed and used as the final word when designing a system where amperage ratings can become critical. 4
  • 5. The chart shows the current required to raise the temperatures of single insulated conductor in free air (30°C ambient) to the limits of various insulation types. The following table gives a derating factor to be used when the conductors are bundled. These charts should only be used as a guide when attempting to establish current ratings on conductor and cable. 4.1 Give a theoretically description of the dimension purpose and methods for the protection against direct and indirect contact. The installation is a TN-C-S- system. Direct contact protection The methods of preventing direct contact are mainly concerned with making sure that people cannot touch live conductors. These methods include: 1-The insulation of live parts - this is the standard method. The insulated conductors should be further protected by sheathing, conduit, etc. 2-The provision of barriers, obstacles or enclosures to prevent touching (IP2X). Where surfaces are horizontal and accessible, IP4X protection (solid objects wider than 1 mm are excluded - see {Table 2.4}), applies Table 2.4 - Numbers in the I P system First Mechanical Second Water protection Number protection against Number against 0 Not protected 0 Not protected Solid objects 1 1 Dripping water exceeding 50mm Solid objects Dripping water when 2 2 exceeding 12mm tilted up to 15 Solid objects 3 3 Spraying water exceeding 2.5mm Solid objects 4 4 Splashing Water exceeding 1.0mm 5 Dust protected 5 Water jets 6 Dust tight 6 Heavy seas - - 7 Effects of immersion - - 8 Submersion 5
  • 6. 3-placing out of reach or the provision of obstacles to prevent people from reaching live parts 4-the provision of residual current devices (RCDs) provides supplementary protection {5.9.1} but only when contact is from a live part to an earthed part. Indirect contact protection There are three methods of providing protection from shock after contact with a conductor which would not normally be live: 1-making sure that when a fault occurs and makes the parts live, it results in the supply being cut off within a safe time. In practice, this involves limitation of earth fault loop impedance, a subject dealt with in greater detail in {5.3.1}. 2-cutting off the supply before a fatal shock can be received using a residual current device {5.9.1}. 3-applying local supplementary equipotential bonding which will ensure that the resistance between parts which can be touched simultaneously is so low that it is impossible for a dangerous potential difference to exist between them. It is important to stress that whilst this course of action will eliminate the danger of indirect contact, it will still be necessary to provide disconnection of the supply to guard against other faults, such as overheating. It is important to appreciate that in some cases a dangerous voltage may be maintained if an un-interruptible power supply (UPS) or a standby generator with automatic starting is in use. 5.3.1 – Principle The path followed by fault current as the result of a low impedance occurring between the phase conductor and earthed metal is called the earth fault loop. Current is driven through the loop impedance by the supply voltage. The extent of the earth fault loop for a TT system is shown in {Fig 5.7}, and is made up of the following labeled parts. Fig 5.7 The earth fault loop 6
  • 7. l. - The phase conductor from the transformer to the installation 2- The protective device(s) in the installation 3- The installation phase conductors from the intake position to the fault 4 - The fault itself (usually assumed to have zero impedance) 5 - The protective conductor system 6 - The main earthing terminal 7 - The earthing conductor 8- The installation earth electrode 9- The general mass of earth 10- The Supply Company's earth electrode 11- The Supply Company's earthing conductor 12- The secondary winding of the supply transformer For a TN-S system (where the Electricity Supply Company provides an earth terminal), items 8 to 10 are replaced by the PE conductor, which usually takes the form of the armoring (and sheath if there is one) of the underground supply cable. For a TN-C-S system (protective multiple earthing) items 8 to 11 are replaced by the combined neutral and earth conductor. For a TN-C system (earthed concentric wiring), items 5 to 11 are replaced by the combined neutral and earth wiring of both the installation and of the supply. It is readily apparent that the impedance of the loop will probably be a good deal higher for the TT system, where the loop includes the resistance of two earth electrodes as well as an earth path, than for the other methods where the complete loop consists of metallic conductors 5.9.1 - Why do we need residual current devices? {5.3.1} has stressed that the standard method of protection is to make sure that an earth fault results in a fault current high enough to operate the protective device quickly so that fatal shock is prevented. However, there are cases where the impedance of the earth-fault loop, or the impedance of the fault itself, are too high to enable enough fault current to flow. In such a case, either: 1. - current will continue to flow to earth, perhaps generating enough heat to start a fire, or 2. - metalwork which is open to touch may be at a high potential relative to earth, resulting in severe shock danger. Either or both of these possibilities can be removed by the installation of a residual current device (RCD). In recent years there has been an enormous increase in the use of initials for residual current devices of all kinds. The following list, which is not exhaustive, may be helpful to readers: RCD residual current device RCCD residual current operated circuit breaker SRCD socket outlet incorporating an RCD PRCD portable RCD, usually an RCD incorporated into a plug RCBO an RCCD which includes overcurrent protection 7
  • 8. SRCBO a socket outlet incorporating an RCBO TN-C-S system In this system, the installation is TN-S, with separate neutral and protective conductors. The supply, however, uses a common conductor for both the neutral and the earth. This combined earth and neutral system is sometimes called the 'protective and neutral conductor' (PEN) or the 'combined neutral and earth' conductor (CNE). The system, which is shown diagrammatically in Fig, is most usually called the protective multiple earth (PME) system, which will be considered in greater detail in fig. Fig - TN-C-S earthing system - protective multiple earthing TN-C-S System: The neutral and earth terminals are combined, but separated just outside the consumer's installation. Protective Devices All electrical circuits must be protected against over current therefore a protective device has to be installed in order to isolate the fault from the supply so as to protect the equipment and appliances from being damaged. Over current is caused by: Two or more live conductors touching each 1) Short circuit other 8
  • 9. Adding loads greater than that of the rated 2) Overload value A phase conductor touching the protective 3) Earth fault conductor by means of direct or indirect contact If the electricity passes through a human body, the person will suffer electric shock and burns. It could also cost damage to properties. The main causes of electrical accidents are: A) Lack of maintenance B) Failure or lack of earthing C) Unsafe and carelessness operating procedures D) Electrical wiring and equipment's physical form could have been damaged E) Incorrectly connected wires and other mistakes are usually caused by ignorance or negligence Direct and indirect contact There are two possible ways one can get electric shock. They are direct contact and indirect contact. The severity of an electric shock is determined by the amount of current flowing through the body. The effects of the electric shock can be very dangerous. It may even prove fatal. Here are the results: ~ 1mA - 2mA No harmful effects ~ 5mA - 10mA Painful and burning sensation ~ 10mA - 15mA Muscular contraction ~ 20mA - 30mA Impairs breathing or having breathing difficulties ~ 40mA and above Ventricular fibrillation or death 5.2 Describe the principal building of the 10kV switchboard and one single cubicle. 12kV ZS1 SWITCHBOARD ZS1: simple, robust construction The factory-assembled, typetested switchgear panels of type ZS1 tor 12 kV to 24 kV rated voltage are metalclad, airinsulated and subdivided into part-compartments for busbars, circuit-breaker, cable termination connections and low voltage equipment. ZS switchgear panels contain withdrawable parts to accommodate the relevant switching devices. These can be fitted either with vacuum circuit-breakers type VD4 and VM1, SF6 circuitbreaker type or with vacuum contactors up to 12 kV. ZS1: quickly installed 9
  • 10. The factory-assembled switchgear panels are erected side-by-side at site to form switchgears. A baseframe laid in or on the floor is recommended for speedier and easier alignment. The new type of busbar system can be installed in a very short time. 10
  • 11. 12kV ZS1 SWITCHBOARD STRUCTURE OF ONE SINGLE CUBICLE 11
  • 12. 2.3 Dimensions and weights 12
  • 13. 2. Technical data 2.1 Electrical data 2.1.1 Main parameters for panels with circuit breakers 2.1.2 Dimensions and weights of 12/17.5 kV units Cable connection of 12/17.5 kV units: In the 550 and 650 mm wide panel, up to three parallel plastic cables can be connected with singlecore cable protection and push-on sealing ends with a maximum cross-section of 630 mm2. In the 800 or 1000 mm wide panel, up to six parallel plastic cables can be connected with single-core cable protection and push-on sealing ends with a maximum cross-section of 630 mm2. Customer requests regarding connections to bars, three-core cables, special cables or sealing ends of different types must be considered during the order-planning stage 13
  • 14. Cable connection in the panels for 12kV, 17,5 kV and 24 kV: In the panel with switch-disconnector 1 plastic one-core cable can be connected on each phase with the cross-section up to 240 mm2 as standard. 2.1.3 Operating conditions 2.1.4 Normal operating conditions The switchgears are basically suitable for normal operating conditions for indoor switchgears and switchboards in accordance with IEC 60694. The following limit values, among others, apply: Ambient temperature: Maximum + 40 0 C Maximum 24 h average + 35 0 C Minimum (according to “minus 5 indoor class”) - 5 0 C The maximum site altitude is 1000 m above sea level. 5.3 Describe the line protection equipment. Circuit breaker A circuit breaker is an automatically-operated electrical switch which is designed to protect an electrical circuit from damage caused by overload or short circuit. Unlike a fuse which operates once and then has to be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small devices which protect an individual household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city. Some circuit breakers are implemented using a solenoid (electromagnet) whose pulling force increases as the current increases. The circuit breaker's contacts are held closed by a latch and, as the current in the solenoid increases, the solenoid's pull releases the latch which then allows the contacts to open by spring action. Another method of sensing current is with a bimetallic strip, which heats and bends with increased current, and is similarly arranged to release the latch. Some circuit breakers incorporate both techniques, with the electromagnet responding to short, large surges in current (short circuits) and the bimetallic strip responding to less extreme but longer-term overcurrent conditions. Circuit breakers for larger currents are usually arranged with pilot devices to sense a fault current and to operate the trip opening mechanism. Under short-circuit conditions a current of many times greater than normal can flow (see maximum prospective short circuit current). When electrical contacts open to interrupt a large current, there is a tendency for an arc to form between the opened contacts, which would allow the flow of current to continue. Therefore, circuit breakers must incorporate various features to divide and extinguish the arc. In air-insulated and miniature breakers an arc chute structure consisting (often) of metal plates or ceramic ridges cools the arc, and blowout coils deflect the arc into the arc chute. Larger circuit breakers such as those 14
  • 15. used in electrical power distribution may use vacuum, an inert gas such as sulfur hexafluoride or have contacts immersed in oil to suppress the arc. The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher than the breaker's rating may result in failure of the breaker to safely interrupt a fault. Small circuit breakers are either installed directly in equipment, or are arranged in a breaker panel. Power circuit breakers are built into switchgear cabinets. High-voltage breakers may be free-standing outdoor equipment or a component of a gas-insulated switchgear line-up. Miniature circuit breaker (MCB) The advantages of a miniature circuit breaker (MCB) are: 1) Shorter tripping time 2) Can be reused 3) Easy to reset 4) Has a switch that can isolate the equipment The disadvantages of a miniature circuit breaker (MCB) are: 1) The most expensive protection device for home use 2) Slow tripping time due to aging 3) Surrounding temperature may affect the MCB FUSES The fuse is a piece of wire which can carry a stated current. If the current rises above this value it will melt. If the fuse melts (blows) then there is an open circuit and no current can then flow thus protecting the equipment by isolating it from the power supply. The fuse must be able to carry slightly more than the normal operating current of the equipment to allow for tolerances and small current surges. With some equipment there is a very large surge of current for a short time at switch on. If a fuse is fitted to withstand this large current there would be no protection against faults which cause the current to rise slightly above the normal value. Therefore special antisurge fuses are fitted. These can stand 10 times the rated current for 10 milliseconds. If the surge lasts longer than this the fuse will blow. Always find out why the fuse blew before replacing it. Occasionly they grow tired and fail. If the fuse is black and silvery then it is likely that there is a dead short (very low resistance) somewhere. What is the Difference Between a Fuse and a Circuit Breaker? Fuses and circuit breakers are two different ways of protecting against suddenly large overloads of electrical flow. Large power overloads are dangerous, potentially destroying electrical equipment or causing a fire. Both fuses and circuit breakers will automatically block against an incoming surge of electrical power past a certain safety limit. But while they both accomplish the same task, each uses different technology in the way that it stops the flow of electricity. 15
  • 16. Fuses are typically small objects that plug into a fusebox or other central location. They are an early technology, dating back to the 19th century. Inside the fuse is a small piece of metal, across which the electricity must pass. During normal flow of electricity, the fuse permits the power to pass unobstructed. But during an unsafe overload, the small piece of metal melts, stopping the flow of electricity. When a fuse is tripped, it should be thrown away and replaced with a new fuse. As there are many varities of fuses available that handle different capacities of electricity, care should be taken when choosing replacement fuses. Circuit breakers are a more recent invention and improve on fuse technology. Circuit breakers are switches that are tripped when the electrical flow passes a safe limit. The excess of electricity typically triggers an electromagnet, which trips the circuit breaker when an unsafe limit is reached. Once tripped, the switches simply turn off. That stops the flow of electricity, which will remain off until the switch is reset. To reset the flow of electricity after the problem is resolved, the switch can simply be turned back on. Circuit breakers are often located in a cabinet of individual switches, typically inside of an apartment or other central place. While often used in homes, circuit breakers can be used for much larger industrial applications as well. Fuses and circuit breakers have unique advantages and disadvantages. One advantage of fuses is that they are cheap and can be purchased from any hardware store, but they have the drawback of needing to be replaced once they stop an overload. That can be challenging in a darkened room. Alternatively, circuit breakers can simply be reset with a flip of a switch after an overload. However, the technology can be more expensive than a fusebox. Electricians are best qualified to determine whether fuses or circuit breakers are better for a particular electrical installation. 5.4 Describe the10kV switchboard protection equipment. SWITCHGEAR PROTECTION – 12 KV Circuit Breakers i) The circuit breakers shall be of standard design and construction conforming to IEC 60056 : 1987. The interrupting medium of the circuit breaker shall be of Vacuum. ii) The control mechanism of the circuit breakers shall be of spring assisted trip free type with remote / local control selector switch and manual operational facility. iii) The circuit breaker shall have a mechanical counter to register the number of circuit breaker operations. iv) Characteristics of the Circuit Breakers shall be as follows; a) Number of poles -3 b) Type - Indoor c) Rated voltage kV - 12 d) Rated frequency Hz - 50 e) Rated insulation level i) Impulse (1.2/50µs) withstand voltage (peak) kV - 75 ii) Power frequency withstand voltage (rms) kV - 28 /1min. f) Rated normal current A - 630/800 g)Rated shortcircuit breaking current (rms ) kA - 20 h) Rated short circuit making current kA - 50 rms i) First pole to clear factor - 1.5 j) Duty cycle `O’ - 3 min. - `CO’ - 3 min. -`CO’ 16
  • 17. k)Tripping supply voltage VDC - 24 Protection i) The programmable type numerical protection relays, conforming to IEC 60255, shall be used. The relays used shall only be from the following manufactures of the countries indicated. a) ABB Relays AB, Sweden/Switzerland/Germany b) Alsthom, England c) Toshiba Corporation, Japan d) Siemens AG, Germany e) Group Schneider, England/France/Italy ii) Necessary software package and the hand held programming unit shall be supplied with the numerical protection relays to set the protection relays as required. For every five panels one number of handheld programming unit shall be supplied. Software shall be compatible with Windows 98 or upper versions. iii) The numerical relay unit shall be suitable for use in the tropical climatic conditions as given under the Clause 3.0 Service iv) It shall be possible to select required type of over current and earth fault protection of IDMT characteristics. v) The numerical relay unit shall have provision for accommodating RTU for incorporating SCADA system in the future. Earthing i) The copper earthing conductor shall be provided along the entire length of the panel. The cross sectional area of earthing conductor shall be such that the current density shall not exceed 200 A/mm² under the specified earth fault conditions. 5CEB STANDARD 025 : 2001 ii) It shall be possible to earth the cable with facility for padlocking, and mechanical interlocking shall be provided to prevent earthing the busbar. iii) All metallic parts of the functional units intended to be earthed shall be bonded to the earthing conductor of the panel. 5.5 Describe the 60 / 10kV transformer protection equipment. Transformer Protection Transformers–600V or Less 17
  • 18. If secondary fuse protection is not provided then the primary fuses must not be sized larger than as shown below. Individual transformer primary fuses are not necessary where the primary circuit fuse provides this protection. Primary Fuse (600V or less) and Secondary Fuse (600V or less). If secondary (600V or less) fuses are sized not greater than 125% of transformer secondary current, individual transformer fuses are not required in the primary (600V or less) provided the primary feeder fuses are not larger than 250% of the transformer rated primary current. Note: Transformer overload protection will be sacrificed by using overcurrent protective devices sized much greater than the transformer F.L.A. The limits of 150%, 167%, 250% and 300% may not adequately protect transformers. It is suggested that for the highest degree of transformer overload protection the fuse size should be within 125% of the transformer full-load amperes. There is a wide fuse ampere rating range available to properly protect transformers. FUSETRON® Class RK5 and LOW-PEAK® YELLOW Class RK1 dual- 18
  • 19. element fuses can be sized on the transformer primary and/or secondary rated at 125% of the transformer F.L.A. These dual-element fuses have sufficient time-delay to withstand the high magnetizing inrush currents of transformers. There is a wide ampere rating selection in the 0 to 15 ampere range for these dual-element fuses to provide protection for even small control transformers. The required secondary protection may be satisfied with multiple overcurrent devices that protect feeders fed from the transformer secondary. The total ampere rating of these multiple devices may not exceed the allowed value of a single secondary overcurrent device. If this method is chosen, dual-element, timedelay fuse protection offers much greater flexibility. Note the following examples: Design 1: Utilizes a single secondary overcurrent device. It provides the greatest degree of selective coordination, transformer protection, secondary cable protection, and switchboard/panelboard/ load center protection. The transformer cannot be overloaded to a significant degree if future loads are added (improperly). With this arrangement the transformer’s full capacity is utilized. Design 2: In this case the single secondary overcurrent device is eliminated, much of the protection described in Design 1 will be reduced. 19
  • 20. If dual-element fuses are utilized as branch circuit protection, the transformer can continue to be loaded with the five 83 amp motors because 5 ≈ 110 = 550 amps, (less than the maximum 600 amps). If additional loads are improperly added in the future, overload protecton will be lost because the primary device can be sized at 250%. Design 3: If the single secondary overcurrent device is eliminated and MCP’s are utilized as branch circuit protection, the transformer will be seriously under-utilized because only one motor can be connected. 20
  • 21. For one motor, 1 ≈ 700% of 83 = 581 amps. For two motors, 2 ≈ 700% of 83 = 1162 amps. Since the sum of the devices cannot exceed 600 amps, only one motor can be connected when the motor circuit is protected by an MCP. Design 4: Using the same procedure, if the single secondary main is eliminated and thermal magnetic circuit breakers are utilized as branch circuit protection per 430.52, only three of the motors can be connected because the thermal magnetic breakers will have been sized at approximately 250% of the motor F.L.A. (83 ≈ 250% = 207.5A.) Using a 200 ampere circuit breaker would allow only three (600 ÷ 200) motors to be connected. To add two additional motors of the same type as shown in Design 1 and Design 2 requires a larger transformer - one that would have a 1000 ampere or more secondary capability. A 300 KVA 208V transformer has a 830 ampere secondary rating which is not sufficient. Therefore, the next standard size 3Ø transformer is a 400 KVA with a 1110 ampere capacity to meet the new rule. 6.1 Give a theoretically description of selectivity considerations. A theoretical outline of selectivity Selection of the protection system of the electrical installation is fundamental both to guarantee correct economical and functional service of the whole installation and to reduce the problems caused by abnormal service conditions or actual faults to a minimum. Within the sphere of this analysis, the coordination between the various devices dedicated to protection of sections of installation or specific components is studied in order to: 21
  • 22. – guarantee safety of the installation and of people in all cases; – rapidly identify and exclude just the area involved in the problem, without indiscriminate trips which reduce the availability of energy in areas not involved in the fault; – reduce the effects of the fault on other integral parts of the installation (reduction in the voltage value, and loss of stability in rotating machines); – reduce the stress on components and damage to the area involved; – guarantee service continuity with good quality power supply voltage; – guarantee adequate support in the case of malfunction of the protection delegated to opening; – provide the personnel in charge of maintenance and the management system with the information needed to restore service to the rest of the network as rapidly as possible and with the least interference; – achieve a good compromise between reliability, simplicity and cost-effectiveness. In detail, a good protection system must be able to: – perceive what has happened and where, discriminating between abnormal but tolerable situations and fault situations within its zone of competence, avoiding unwanted trips which cause unjustified stoppage of a sound part of the installation; – act as rapidly as possible to limit the damage (destruction, accelerated ageing, etc.), safeguarding power supply continuity and stability. The solutions come from a compromise between these two antithetic requirements – precise identification of the fault and rapid tripping - and are defined according to which requirement is privileged. Selectivity techniques This section describes the different selectivity techniques and their area of application. In the overload zone with the protections in play, time-current type selectivity is usually realised. In the short-circuit zone with the protections in play, various selectivity techniques can be used. In particular, the following will be illustrated in the paragraphs below: Current selectivity Time selectivity Energy selectivity Zone selectivity. After an initial theoretical description of the different selectivity techniques, the selectivity technique which can be used appropriately for the different types of circuit- breakers will then be analysed. 22
  • 23. Time-current selectivity In general, the protections against overload have a definite time characteristic, whether they are made by means of a thermal release or by means of function L of an electronic release. A definite time characteristic is intended as a trip characteristic where, as the current increases, the trip time of the circuit-breaker decreases. When there are protections with characteristics of this type, the selectivity technique used is time-current selectivity. Time-current selectivity makes trip selectivity by adjusting the protections so that the load-side protection, for all possible overcurrent values, trips more rapidly than the supply-side circuit-breaker. When the trip times of the two circuit-breakers are analyzed, it is necessary to consider: - The tolerances over the thresholds and trip times - The real currents circulating in the circuit-breakers. 1.05 x I1 of the supply-side circuit-breaker Assuming IA =1.05xI1, with reference to what has been said about the real currents which circulate in the circuit-breakers, the IB current is obtained on the load side. The trip times of the two devices are obtained from the time-current curves. 1.20XI3 (or I2) of the load-side circuit-breaker Assuming IB = 1.20XI3 (or I2), the IA current is obtained in the same way on the supply side and, from the time-current curves, the trip times of the two devices are obtained. If the following is true for both the points considered: tA>tB then selectivity in the overload zone is guaranteed. 23
  • 24. Current selectivity This type of selectivity is based on the observation that the closer the fault point is to the power supply of the installation, the higher the short-circuit current is. It is therefore possible to discriminate the zone the fault occurred in by setting the instantaneous protections to different current values. Total selectivity can normally be achieved in specific cases only where the fault current is not high and where there is a component with high impedance interposed between the two protections (transformer, very long cable or a cable with reduced cross-section, etc.) and therefore a great difference between the short-circuit current values. However: – The ultimate selectivity current is usually low and therefore selectivity is often only partial; – The setting level of the protections against overcurrents rises rapidly; – Redundancy of the protections, which guarantees elimination of the fault (rapidly) in the case of one of them not operating, is not possible. – The protection against short-circuit of supply-side circuit-breaker A will be set to a value which means it does not trip for faults which occur on the load side of protection B. (In the example in the figure I3minA > 1kA) – The protection of load-side circuit-breaker B will be set so as not to trip for faults which occur on its load side. (In the example in the figure I3MaxB < 1kA) Obviously the setting of the protections must take into account the real currents circulating in the circuitbreakers. 24
  • 25. The ultimate selectivity value which can be obtained is equal to the instantaneous trip threshold of the supply-side protection less any tolerance. Is = I3minA Time selectivity This type of selectivity is an evolution of the previous one. In this type of coordination, apart from the trip threshold in terms of current, a trip time is also defined: a certain current value will make the protections trip after a defined time delay, suitable for allowing any protections placed closer to the fault to trip, excluding the area which is the seat of the fault. The setting strategy is therefore to progressively increase the current thresholds and the trip delays as one gets closer to the power supply sources (level of setting directly correlated to the hierarchical level). The delayed trip thresholds must take into account the tolerances of the two protection devices and the effective currents which circulate in them. As in the case of current selectivity, the study is made by comparing the time-current trip curves of the protection devices. Generally this type of coordination: - is easy to study and realize; - is not very costly with regard to the protection system; - allows even high selectivity limit values to be obtained (if Icw is high); 25
  • 26. - allows redundancy of the protection functions. However: - the trip times and energy levels let through by the protections, especially by those close to the sources, are high. It is a type of selectivity which can also be made between circuit-breakers of the same size, equipped with electronic releases with delayed protection against short-circuit. The protections against short-circuit of the two circuit-breakers will be set: - with the I2 trip thresholds against delayed short-circuit adjusted so as not to create trip overlapping, taking into consideration the tolerances and the real currents circulating in the circuit- breakers. - with t2 trip times adjusted so that the load-side circuit-breaker B extinguishes the fault whereas the supply-side circuit-breaker A, still in the timing phase, manages to “see” the extinction of the current and therefore remains closed. The ultimate selectivity limit which is obtained is equal: – to the instantaneous trip threshold of the supply-side protection, if this function is enabled, less any tolerance: Is = I3minA – to the value of Icw for supply-side air circuit-breakers when the instantaneous protection function is set to OFF. 26
  • 27. Energy selectivity Coordination of energy type is a particular type of selectivity which exploits the current- limiting characteristics of moulded-case circuit-breakers. It is pointed out that a current-limiting circuit-breaker is “a circuit-breaker with a sufficiently short trip time to prevent the short- circuit current from reaching the peak value which would otherwise be reached” (IEC 60947-2). In practice, all the ABB SACE moulded-case circuitbreakers of the Isomax and Tmax series, the modular circuit-breakers and the E2L E3L air current-limiting circuit- breakers have more or less marked current-limiting characteristics. The protections against short-circuit of the two circuit-breakers must respect the conditions given below. - Supply-side release of thermomagnetic type the magnetic trip thresholds must be such so as not to create trip overlapping, taking into consideration the tolerances and the real currents circulating in the circuit-breakers; the magnetic threshold of the supply-side circuit-breaker must be equal to or higher than10xIn or set to the maximum value when it is adjustable. - Supply-side release of electronic type any protections against delayed short-circuit S must be adjusted following the same indications as time selectivity; the instantaneous protection function I of the supply-side circuit-breakers must be set to off 27
  • 28. The Is ultimate selectivity limit obtained is the one given in the tables Zone selectivity This type of coordination is an evolution of time coordination. In general, zone selectivity is made by means of dialogue between the current measuring devices which, once the setting threshold has been detected as having been exceeded, allows just the fault zone to be identified correctly and the power supply to it to be cut off. It can be realised in two ways: – the measuring devices send the information linked to the current setting threshold having been exceeded to a supervision system and the latter identifies which protection has to intervene; – when there are current values higher than their setting, each protection sends a lock signal by means of a direct connection or a bus to the hierarchically higher level protection (on the supply side in relation to the power flow direction) and, before intervening, checks that a similar lock signal has not arrived from the load-side protection. In this way only the protection immediately to the supply side of the fault intervenes. 28
  • 29. Compared with coordination of time type, zone selectivity allows: - reduction of the trip times (these can be lower than hundred milliseconds); - reduction both of the damage caused by the fault and of interferences to the power supply system; - reduction of the thermal and dynamic stresses on the components of the installation; - a very high number of selectivity levels to be obtained. However: - it is more burdensome both in terms of cost and of complexity of the installation - it requires an auxiliary supply. This is a type of selectivity which can be realised: - between Emax air circuit-breakers equipped with PR122 and PR123 releases. The ultimate selectivity limit which can be obtained is equal to the Icw Is = Icw - between Tmax T4L,T5L and T6L moulded-case circuit-breakers equipped with PR223 EF releases. The ultimate selectivity limit which can be obtained is 100kA Is = 100kA Then, by means of the additional IM210 module, it is possible to make a chain of zone selectivity between Tmax and Emax. 29
  • 30. FINAL CONCLUSION In this report, we had some knowledge about low voltage installations. At the same time, this report includes protection techniques. We learnt that in TNCS systems, fuses and circuit breakers are very important for protecting from direct and indirect contact ( and overload, short circuit) . Furthermore, we tried to describe principal building of the 12 KV switchboard, one single cubicle and protection equipment. We saw that selectivity considerations are quiet important for installation. And it is not easy to select devices, because it is about safety. Of course this report will not satisfy you, but we tried to do our best. We tried to find all theoretical information about this report. 30