PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 85
Barbara FLORKOWSKA1
, Marek FLORKOWSKI2
, Józef ROEHRICH1
, Paweł ZYDROŃ1
AGH University of Science and Technology, Krakow, Poland (1), ABB sp. z o. o., Corporate Research Center, Krakow, Poland (2)
Modelling of degradation process of electrical insulation
systems due to inverter pulses
Abstract. In-service stresses are the cause of progressive degradation of electrical insulation systems. The assessment of intensity and dynamics of
these processes which are, among others, consequence of local working electric field strength is usually performed at sinusoidal voltage. However,
in applications where power electronics converters are used the voltage stress has usually a form of fast switching pulses composing of repetitive
sequences. Special problems for Pulse Width Modulation (PWM) driven induction motors arise from overvoltages and partial discharges (PD) in
insulating systems of feeding cables and motors. The PWM waveforms produce complex overvoltages that stress the insulation more severely than
sinusoidal voltage waveforms. The overvoltages form trials of pulses with very short rise times. Such conditions have essential influence on inception
and activity of partial discharges in insulation systems. Selected aspects of these problems are presented in the paper: the numerical simulations of
electric stress in coil-to-coil insulation of stator windings, the influence of the pulsed voltages modelling the PWM sequences, and the experimental
results of PD in model twisted pair (TP) samples.
Streszczenie. Narażenia eksploatacyjne są powodem postępującej degradacji elektrycznych układów izolacyjnych. Ocena intensywności i dynamiki
tych procesów, będących m.in. konsekwencją lokalnego, roboczego natężenia pola elektrycznego jest zwykle prowadzona dla napięcia
sinusoidalnie zmiennego. W aplikacjach, w których stosowane są energoelektroniczne układy przekształtnikowe narażenia napięciowe mają formę
impulsów szybkozmiennych, tworzących powtarzalne sekwencje. Szczególne problemy powstają w układach napędowych silników indukcyjnych
z modulacją szerokości impulsów (PWM), a związane są one z przepięciami oraz wyładowaniami niezupełnymi (wnz) w izolacji kabli zasilających
oraz silników. Przebiegi PWM wytwarzają złożone przepięcia, które narażają izolację w większym stopniu niż napięcia przemienne. Przepięcia
tworzą ciągi impulsów o bardzo krótkich czasach narastania, co ma zasadniczy wpływ na powstawanie i aktywność wyładowań niezupełnych w
układach izolacyjnych. Artykuł przedstawia wybrane aspekty tych problemów: symulacje numeryczne naprężeń elektrycznych izolacji
międzyzwojowej, wpływ napięć impulsowych modelujących sekwencje PWM oraz wyniki badań eksperymentalnych wnz w próbkach modelowych
typu para skręcona (TP). (Modelowanie procesów degradacji układów elektroizolacyjnych wywołanych impulsami inwertera).
Keywords: electrical insulation systems, degradation processes, partial discharges, PWM voltages
Słowa kluczowe: układy izolacyjne, procesy degradacji, wyładowania niezupełne, napięcia PWM
doi:10.12915/pe.2014.10.22
Introduction
The inverter drives based on Pulse Width Modulation
(PWM) technique are the most common type of inverter
drives used for control of electric machines work. A general
scheme of motor control with the PWM inverter drive is
presented in Figure 1. The pulsed output voltage is applied
from PWM drive to the motor terminals by a feeding cable,
which for actual PWM pulses parameters for the most
cases can be treated as transmission line [1]. In those
drives the sequence control unit produces pulse-width
modulated train of voltage pulses with slew rate up to 100
kV·s-1
and repetition rate even up to 100 kHz. In conse-
quence large spikes, overshoots and oscillations could be
observed on motor terminals. Electrical stresses caused by
generated supply voltage distortions often lead to partial
discharges, faster degradation of the insulation system, its
unexpected breakdown, and failure of electrical machine.
The types of insulating systems of electrical machines
The paper is concerned to random wound stator
windings insulation system, where the magnet wire is round
and the arrangement between the turns is not defined (i.e.
random).
The main criterion for classification of winding insulation
is related to assessment of PD activities during the lifetime
and it refers to the random-wound and form-wound stator
windings. According to IEC TS 60034-18-41 [2] the insula-
tion systems of electrical machines fed by voltage inverters
are divided into two types:
Type I systems which are not expected to experience
PD activity in their service,
Type II systems which are expected to withstand PD
activity throughout their service lifetime.
Fig.1. Pulse voltages in single-phase inverter-cable-motor setup: R, L, C, G – parameters of transmission line model, Ld – phase
inductance, Cg – distributed ground capacitance, Re – loss resistance, K – input winding capacitance; UDC – dc-link voltage, Uov – over-
voltage crest value, du/dt – voltage slew rate, VSI – Voltage Source Inverter
86 PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014
Machines with a rated voltage:
 to 700 Vrms may have either Type I or type II windings,
 above 700 Vrms the winding insulation is usually type II.
During the exploitation, the electrical stresses will be
created in the following locations in the insulating system
(Fig.2): between conductors in different phases or phase-to-
phase (UPP), between turn-to-turn (UCC), between
a conductor and ground (UPG).
Fig.2. Electrical stresses of motor insulating system:
a) details of insulation system of inverter fed motor b) voltages for
star connected motor: UPP – phase-to-phase voltage, UCC –
conductor-to-conductor voltage, UPG – phase-to-ground voltage
The elements of inverter fed motor insulation system are
exposed to repetitive short rise time voltage impulses with
significant amplitude. The electric stress is defined by the
peak voltages and the basic stressing parameter is the
peak-to-peak voltage. It means that the unipolar voltage
produces the same stress as a bipolar voltage having a
peak-to-peak voltage of the same value. This problem was
recognized as first by Bonnet [3] and Person [4], who have
recognized that switching devices as IGBT used in PWM
converters create the high amplitude voltage impulses at
the motor terminals.
For modelling of random-wound windings, the samples
called twisted-pair (TP) [5] made of magnet wires with
different diameters are used. Twisted-pair samples are
composed of two enamel-coated together twisted copper
wires. According to IEC standard [6] the normalized number
of twists ts on a nominal sample length l equal to 125 mm
ranges from 3 – for enamelled wire nominal diameter
between 2.15 mm to 3.5 mm to 16 twists – for enamelled
wires with a diameter from 0.35 mm to 0.5 mm.
Partial discharges in motor insulation
The degradation mechanism in insulating systems at
PWM inverter-fed driver is not the same as for sinusoidal
frequency 50/60 Hz. The aging processes, as a result of PD
activity, are accelerated by:
 presence of repetitive overvoltages,
 space charge injection in insulation – depending also on
various PWM sequences,
 high repetition rate of PD pulses,
 high voltage slew rate (dU/dt).
Theoretically, at semi-square voltages, partial dischar-
ges should occur only at a rising and falling slope and
vanish during the voltage plateau. The PD intensity should
be related to du/dt. However, as shown by many
researchers, the PD occurs in the whole voltage period [7,
8, 9], also when U = const. This necessitates a further
recognition of the PD mechanism in insulation systems
subjected to PWM-based drives.
The whole stator winding is resin impregnated. The
resin penetrates and fills the space between wires and
stator slots in order to increase the dielectric capability, thus
increasing the level of PD inception. The accumulated
moisture and contaminants can promote tracking and
deterioration, leading to failure. Tracking failures are caused
by small partial discharges, which develop localised heating
and cause chemical decomposition of any weak insulation
barrier. Arcs of relatively high currents develop additional
heating, which carbonizes the resin surface. Hence, the
need for diagnosing stator windings is twofold:
 already during the manufacturing process the magnet
wire coated insulation may be damaged, causing
galvanic short circuits, and leading to turn-to-turn /
phase-to-phase faults (Fig.3a). Imperfect resin
impregnation may result in voids formation and partial
discharge development (Fig.3b),
 during operation environmental conditions and mecha-
nical stress, especially vibrations may lead to the
insulation degradation. PWM-controlled motors might be
subjected to an additional stress related to high voltage
peaks, which can deteriorate the insulation system. The
high electric field between wires in the slot or in the end
winding section might start ionization and formation of
corona (Fig.3c), which can lead to chemical damage
and thermal hot spots.
Fig.3. Turn-to-turn faults: a) electrical short-circuits, b) void
between magnet wires and internal PD, c) magnet wire insulation
failure and corona
The insulation failure occurs when the magnitude and
rise time of the repetitive transient voltage stress exceeds
the withstand capability of the insulating system (Fig.4). The
breakdown of insulation most commonly occur at the
highest voltage stress spot, i.e. the first turn of the line end
coil to the last turns of the coil group as well as in the end
winding region, where wires from different coils can come
into contact.
Fig.4. Supply voltage of PWM driven motor with overvoltages
The overvoltage stresses can be analyzed at semi-
square voltage with a specified rise time tr, and the
overvoltage magnitude Uov depends on the steepness of the
semi-square voltage as illustrated in Figure 5. In PD model
for such voltage stimulus the rise time tr is equal to:
(1)


tg
U
t OV
r
The occurrence of partial discharges depends on incep-
tion voltage Uci with respect to the value of Uov and is
triggered when Uci < Uov (Fig.5), whereas the discharge
intensity and their development also depends on the
extinction voltage Uce. The attributes describing the PD
sources depend on the ratio Uce / Uci, just like at sinusoidal
voltage, and additionally on the rise time tr.
PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 87
Fig.5. Definition of overvoltage parameters
The factors affected the PD at impulse voltage are:
voltage, frequency and pulse rise/fall time. The voltage rise
time has special impact on the initiation conditions and on
the inception voltage Ui of PD (Fig.6).
Fig.6. PD pulses acquired in samples of thermosetting insulation for
50 Hz (left) and 1000 Hz (right) and for three rise-time parameters
800-1250-3000 ns (in the case of 3000 ns the time scale is 2 s/div
otherwise 400 ns/div) [10]
PD pulses acquisition at semi-square voltages
Classic methods of PD detection described in IEC-
60270 [11] refer to measurements performed in the frequ-
ency range up to 1 MHz and are not useful for voltages with
high slew rate, due to frequency spectrum overlapping.
Thus, in the case of PD measurements at semi-square
voltages (e.g. generated by IGBT inverter) other specific
detection methods operating in VHF/UHF range should be
applied [12]. In the presented experiments three different
types of detectors have been used for PD pulse acquisition:
1) E-field detector with 350 MHz amplifier connected to HP-
8591E spectrum analyzer, 2) Rogowski coil, and 3) non-
inductive resistors. Electric signals from detectors were
digitalized and registered by oscilloscopes with imple-
mented DPO function (Digital Phosphor Oscilloscope)
TDS784D or DPO2014 (Tektronix). The challenge in this
kind of experiment, performed at fast stimulus is to separate
the PD pulse from the pulses interfering due to HV
modulator switching, as shown in Figure 7a. The narrow
spike is the PD pulse, however charging current is also
detected on wideband resistor. A single PD event, with 6 ns
FWHM value (Full Width at Half Maximum), is observed in
Figure 8. Determination of PDIV (Partial Discharge
Inception Voltage) under impulse voltages at a level just
above ionisation threshold is difficult to monitor precisely
because of transient development of ionisation. Acquisition
of PD signals in DPO mode for the semi-square voltage
(Fig.8b) shows its appearance after the time lag on the
rising slope of voltage pulse. The results confirm high
repeatability of pulse voltage and stochastic nature of PD
manifested by blurring of amplitude and time location.
Fig.7. Semi-square voltage and current signal detected on 50 
resistor – time scale 1µs/div (a) and individual PD pulse
registered with 4 GHz sampling frequency (25 ns/div) (b)
Fig.8. Partial discharges in thermosetting insulation sample for
pulse voltage close to inception voltage. Acquisition of semi-square
voltage and PD signal from Rogowski coil: a) single-shot
acquisition by DPO2014, b) result of 3075 accumulations in DPO
mode by TDS784D oscilloscope
PD measurements in model insulation systems
The TP samples have been used for studying the PD
phenomena in enameled wires as a substitute of the motor
winding. The twisted-pair of TP sample can be regarded as
a pair of enameled wires being in contact (Fig.9a) or
separated by a micro-air gap g (Fig.9b).
Fig.9. Cross section of the enameled wires in TP sample
(insulation thickness not in scale with wire diameter):
a) g = 0, b) g > 0, c) PD zones in insulating system of TP sample
The conditions for PD inception are determined by the
electric field distribution between the wires. Without PD it
88 PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014
can be approximated by capacitive field distribution, which
is formed by a series of two capacitances of dielectric layer
of insulation. When PDs are present, one can assume that
the air space due to ionization starts to be conductive.
Corona-like discharge is the mechanism of PD initiation
between two insulated wires. Thus, the PD inception
voltage Ui depends on the wire’s diameter in TP samples.
At 50 Hz sinusoidal voltages the PD -q-n patterns can be
acquired and analyzed [1]. The PD intensity, described by
the total number of PD pulses N(U) is shown in Figure 10.
Fig.10. The number of PD pulses N vs. voltage U for TP samples
made from wires with 0.7 mm, 1.4 mm, and 2.5 mm diameter
Analysis of electric field distributions in elements of
motor windings
The wound wires in TP samples create an insulating
system with solid dielectric (coatings of enameled wires) or
with micro-gap g between them. Along the TP sample, there
are many distributed contact points of adjacent wires, which
are in close proximity separated only by a micro gap in air.
During the PD measurements the TP samples are exposed
to the electric field higher than PD inception field. Electric
field distribution in TP sample depends on: wire diameter D,
insulation thickness a, number of twists ts, and airgap g
between wires. For investigations of PD initiation and
development in TP insulation systems, the two zones have
been distinguished (Fig.9c):
 Zone 1: micro-air gap exists at the contact of insulated
wires, which form the insulation system composed of
serial dielectrics. In this zone the electric field distribution
is approximately uniform, therefore only normal electric
field components occur. Their values are high in the air
gap and much lower in the solid dielectric. The reason is
that dielectric stress is reversely proportional to dielectric
constant r the value of which is 3.8 – 4.2.
 Zone 2: boundary region, adjacent to the contact point.
Apart from regular electric field components also
tangential components occur there.
The electric field calculations along the profile A and B
(Fig.9c) provide information about those field components.
The distribution of electric field in insulating systems
represented by twisted-pair model samples is directly
connected with the mechanism of inception and
development of partial discharges and electric breakdown.
In parallel configuration of wires in TP sample no twists
occur (ts = 0). One can considerate two cases:
a) without air gap between the wires g = 0,
b) the air gap exists, g = 100 µm.
a) No distance between wires g = 0 mm
The electric field distribution for parallel, adjoin wires for
exemplary TP0.7 sample at 1 kV is presented in Figure 11.
Fig.11. Electric field for parallel wires without air gap (g = 0)
The electric field is depicted in three characteristic
spots, one in the region of highest filed near the contact
point of wires, the second one in the region of strong
electric field (E = 9.5 kV/mm) and the third one on the
boundary region, where the electric field drops below
2 kV/mm. The electric field in the cross sections of the
wire’s contact point, along A and B profiles depicted in
Figure 9c, is shown in plot in Figure 12. A high electric field
of 30 – 40 kV/mm exists in the micro-air gap between wires
and exceeds approx. 9 kV/mm corona inception stress
characteristic for 0.1 mm gap. The diameter of wires in the
twisted pair samples is particularly influencing the electric
field distribution in the non-homogenous areas in twisted
pair sample (Fig.12b).
Fig.12. Electric field distribution along: a) profile A for TP0.7
and TP2.5, b) profile B for TP0.7 and TP2.5 [1]
PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 89
b) Distance between wires g = 100 µm
The electric field distribution for parallel wires placed in
the proximity g = 100 µm at 1 kV is presented in Figure 13.
In such a way a micro-air gap is formed between wires.
Similarly like for adjacent wires, also in case of air slice,
the electric field is depicted in three characteristic spots,
one in the region of highest filed, the second one in the
region of moderate electric field (E = 4 kV/mm) and the third
one on the boundary region, where the electric field drops
below 2 kV/mm.
Fig.13. Electric field for parallel wires with air gap (g = 100 µm)
Results of simulations show characteristic regions with
significantly different values of electric field. These
conditions influence the development of partial discharge
forms, which can be indirectly confirmed by microscopic
observation of the surface of wires insulation (Fig.14). It
refers to the need of development a special wires design
with higher resistance to fast surges [10, 13, 14].
Fig.14. Microphotographs of twisted wires from TP sample with
insulation deterioration traces and breakdown hotspot
Conclusions
Partial discharge measurement is sensitive tool for
assessment of winding wires quality and properties of new
insulating materials.
In motor windings, represented here by twisted-pair
samples, partial discharges may occur in air gaps with
a width from several m up to tens of m, at the inception
voltage from approximately 850 V to 1400 V [10].
Modern methods of pulse signals detection and
acquisition help us in better understanding of physical
processes leading to inception and development of partial
discharges in motor winding insulation. Numerical analysis
of electric fields with modelling of real, imperfect
configurations of winding wires pointed out possible ways of
impulsive degradation processes of their insulating layers.
The development of an enamelled wire that can
withstand coil winding stress increases the reliability of
electric motors fed by inverters.
REFERENCES
[1] Florkowska B., Zydroń P., Florkowski M.: Effects of converter
pulses on the electrical insulation system of motors, Proc.
2011 IEEE ISIE, 573 – 578, Gdańsk, 2011
[2] IEC/TS 60034-18-41 ed. 1 (2006-10): Rotating electrical
machines – Part 18-41: Qualification and type tests for Type I
electrical insulation systems used in rotating electrical
machines fed from voltage converters
[3] Bonnet A. et all: Cause and analysis of stator and rotor
failures in three phase squirrel cage induction motors, IEEE
Trans. IAS, vol. 1992, 921 – 937
[4] Persson E.: Transient effects in applications of PWM
inverters in induction motors, IEEE Trans. IAS, vol. 1992,
1095-1101
[5] IEC 60851-5 ed. 4.0 (2008-07): Winding wires. Test methods
– Part 5: Electrical properties
[6] IEC 60172 ed. 3.0: Test procedure for the determination of
the temperature index of enamelled winding wires
[7] Florkowska B., Florkowski M., Zydroń P., Roehrich J.,
Pędzisz K.: Degradation processes of polymer cable
insulation at non-sinusoidal voltage stresses, Conf. Rec.
2010 IEEE ISEI, San Diego, CA, USA, paper 132
[8] Lindell E., Bengtsson T., Blennow J., Gubanski S.M.,
Influence of rise time on partial discharge extinction voltage
at semi-square voltage waveforms, IEEE Trans. Dielectr.
Electr. Insul., vol. 17, no. 1, 2010, 141–148
[9] Cavallini A., Montanari G.C.: Effect of supply voltage
frequency on testing of insulation system, IEEE Trans.
Dielectr. Electr. Insul., vol. 13, no. 1, 2006, 11 – 21
[10] Florkowska B., Florkowski M., Furgał J., Roehrich J., Zydroń
P, Impact of fast transient phenomena on electrical insulation
systems, AGH-UST Press; Kraków, 2012
[11] IEC-60270 ed. 3, (2000-12) High-voltage test techniques –
Partial discharge measurements
[12] IEC/TS 61934 ed. 2.0 (2011-04): Electrical insulating
materials and systems – Electrical measurement of partial
discharges (PD) under short rise time and repetitive voltage
impulses
[13] Manh Quan Nguyen ; Malec D., Mary D., Werynski P.,
Gornicka B., Therese L., Guillot, P., Silica nanofilled varnish
designed for electrical insulation of low voltage inverter-fed
motors, IEEE Trans. Dielectr. Electr. Insul., vol. 17, no. 5,
2010, 1349–1356
[14] Glinka T., Kulesz B.: Wyładowania niezupełne w izolacji
zwojowej silników indukcyjnych zasilanych z falowników
PWM, Prace Naukowe Instytutu Maszyn, Napedów i
Pomiarów Elektrycznych Politechniki Wrocławskiej, Nr 49,
Studia i Materiały Nr 21, 2000
Authors:
Barbara Florkowska, Prof., E-mail: beflor@agh.edu.pl; Józef
Roehrich PhD EE, E-mail: roehrich@agh.edu.pl; Paweł Zydroń
PhD, D.Sc. AGH University of Science and Technology, Dept. of
Electrical and Power Engineering, Mickiewicza 30, 30-059, Krakow,
Poland, E-mail: pzydron@agh.edu.pl; Marek Florkowski PnD D.Sc.,
ABB Corporate Research Center, Starowiślna 13A, 31-038 Krakow,
Poland, E-mail: marek.florkowski@pl.abb.com.

More Related Content

What's hot

Lightning protection for overhead distribution lines
Lightning protection for overhead distribution linesLightning protection for overhead distribution lines
Lightning protection for overhead distribution linesGilberto Mejía
 
UNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATIONUNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATIONPremanandDesai
 
The sheath voltage_limiter
The sheath voltage_limiterThe sheath voltage_limiter
The sheath voltage_limiterGilberto Mejía
 
Mitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoMitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoGilberto Mejía
 
TRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUE
TRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUETRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUE
TRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUEJournal For Research
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Dampers used in electrical transmission lines
Dampers used in electrical transmission linesDampers used in electrical transmission lines
Dampers used in electrical transmission linesadeelshafiq
 
Deicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesDeicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesbindasbhabani
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination designNaresh Surisetti
 
Cable sizing to withstand short circuit current
Cable sizing to withstand short circuit currentCable sizing to withstand short circuit current
Cable sizing to withstand short circuit currentLeonardo ENERGY
 
ASM 2001 Influence of Magnetic Flux Controllers on Induction Heating Systems
ASM 2001 Influence of Magnetic Flux Controllers on Induction Heating SystemsASM 2001 Influence of Magnetic Flux Controllers on Induction Heating Systems
ASM 2001 Influence of Magnetic Flux Controllers on Induction Heating SystemsFluxtrol Inc.
 
How to reduce transformer losses
How to reduce transformer lossesHow to reduce transformer losses
How to reduce transformer losseskamal soni
 
Equipments of power transmission
Equipments of power transmissionEquipments of power transmission
Equipments of power transmissionRasika Ghongade
 

What's hot (20)

Lightning protection for overhead distribution lines
Lightning protection for overhead distribution linesLightning protection for overhead distribution lines
Lightning protection for overhead distribution lines
 
UNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATIONUNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATION
 
The sheath voltage_limiter
The sheath voltage_limiterThe sheath voltage_limiter
The sheath voltage_limiter
 
Mitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoMitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacino
 
TRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUE
TRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUETRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUE
TRANSFORMER WINDING DEFORMATION ANALYSIS USING SFRA TECHNIQUE
 
JTR ( JARINGAN TEGANGAN RENDAH)
JTR ( JARINGAN TEGANGAN RENDAH)JTR ( JARINGAN TEGANGAN RENDAH)
JTR ( JARINGAN TEGANGAN RENDAH)
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
F0333237
F0333237F0333237
F0333237
 
Dampers used in electrical transmission lines
Dampers used in electrical transmission linesDampers used in electrical transmission lines
Dampers used in electrical transmission lines
 
Deicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesDeicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc losses
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination design
 
Cable sizing to withstand short circuit current
Cable sizing to withstand short circuit currentCable sizing to withstand short circuit current
Cable sizing to withstand short circuit current
 
ASM 2001 Influence of Magnetic Flux Controllers on Induction Heating Systems
ASM 2001 Influence of Magnetic Flux Controllers on Induction Heating SystemsASM 2001 Influence of Magnetic Flux Controllers on Induction Heating Systems
ASM 2001 Influence of Magnetic Flux Controllers on Induction Heating Systems
 
Cp4201612617
Cp4201612617Cp4201612617
Cp4201612617
 
How to reduce transformer losses
How to reduce transformer lossesHow to reduce transformer losses
How to reduce transformer losses
 
Equipments of power transmission
Equipments of power transmissionEquipments of power transmission
Equipments of power transmission
 
Akt tl design01
Akt tl design01Akt tl design01
Akt tl design01
 
Gss herapura report
Gss herapura reportGss herapura report
Gss herapura report
 
Power systems (2)
Power systems (2)Power systems (2)
Power systems (2)
 
Tl book
Tl bookTl book
Tl book
 

Similar to Modelling Insulation Degradation from Inverter Pulses

H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...IRJET Journal
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfwhmonkey
 
International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)ijceronline
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Bérengère VIGNAUX
 
Power-Quality report file for b.tech and dip
Power-Quality report file for b.tech and dipPower-Quality report file for b.tech and dip
Power-Quality report file for b.tech and dipOmPrakash781786
 
Building Service Chapter 1
Building Service Chapter 1Building Service Chapter 1
Building Service Chapter 1Izam Lukman
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Jaydeep Chauhan
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat
 
Model of Pulsed Electrical Discharge Machining (EDM) using RL Circuit
Model of Pulsed Electrical Discharge Machining (EDM) using RL CircuitModel of Pulsed Electrical Discharge Machining (EDM) using RL Circuit
Model of Pulsed Electrical Discharge Machining (EDM) using RL CircuitIJPEDS-IAES
 
Vocational Training Report ( Sealdah Power House)
Vocational Training Report ( Sealdah Power House)Vocational Training Report ( Sealdah Power House)
Vocational Training Report ( Sealdah Power House)shovandey07
 
A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...
A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...
A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...paperpublications3
 
An Overview of Harmonic Sources in Power System
An Overview of Harmonic Sources in Power SystemAn Overview of Harmonic Sources in Power System
An Overview of Harmonic Sources in Power SystemIOSR Journals
 

Similar to Modelling Insulation Degradation from Inverter Pulses (20)

ashwani ppt
ashwani pptashwani ppt
ashwani ppt
 
Power Quality Improvement using AC To AC PWM converter for distribution line
Power Quality Improvement using AC To AC PWM converter for distribution linePower Quality Improvement using AC To AC PWM converter for distribution line
Power Quality Improvement using AC To AC PWM converter for distribution line
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdf
 
International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)International Journal of Computational Engineering Research (IJCER)
International Journal of Computational Engineering Research (IJCER)
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks
 
If3415111540
If3415111540If3415111540
If3415111540
 
Power-Quality report file for b.tech and dip
Power-Quality report file for b.tech and dipPower-Quality report file for b.tech and dip
Power-Quality report file for b.tech and dip
 
Building Service Chapter 1
Building Service Chapter 1Building Service Chapter 1
Building Service Chapter 1
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 Webinar
 
Reduction of transients in switches using embedded machine learning
Reduction of transients in switches using embedded machine learningReduction of transients in switches using embedded machine learning
Reduction of transients in switches using embedded machine learning
 
Model of Pulsed Electrical Discharge Machining (EDM) using RL Circuit
Model of Pulsed Electrical Discharge Machining (EDM) using RL CircuitModel of Pulsed Electrical Discharge Machining (EDM) using RL Circuit
Model of Pulsed Electrical Discharge Machining (EDM) using RL Circuit
 
Power Quality
Power QualityPower Quality
Power Quality
 
Vocational Training Report ( Sealdah Power House)
Vocational Training Report ( Sealdah Power House)Vocational Training Report ( Sealdah Power House)
Vocational Training Report ( Sealdah Power House)
 
L44086268
L44086268L44086268
L44086268
 
A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...
A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...
A Soft Switched Dual Buck Inverter with Series Connected Diodes and Single In...
 
An Overview of Harmonic Sources in Power System
An Overview of Harmonic Sources in Power SystemAn Overview of Harmonic Sources in Power System
An Overview of Harmonic Sources in Power System
 

Recently uploaded

BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur EscortsRussian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
Russian Call Girls in Nagpur Grishma Call 7001035870 Meet With Nagpur Escorts
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 

Modelling Insulation Degradation from Inverter Pulses

  • 1. PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 85 Barbara FLORKOWSKA1 , Marek FLORKOWSKI2 , Józef ROEHRICH1 , Paweł ZYDROŃ1 AGH University of Science and Technology, Krakow, Poland (1), ABB sp. z o. o., Corporate Research Center, Krakow, Poland (2) Modelling of degradation process of electrical insulation systems due to inverter pulses Abstract. In-service stresses are the cause of progressive degradation of electrical insulation systems. The assessment of intensity and dynamics of these processes which are, among others, consequence of local working electric field strength is usually performed at sinusoidal voltage. However, in applications where power electronics converters are used the voltage stress has usually a form of fast switching pulses composing of repetitive sequences. Special problems for Pulse Width Modulation (PWM) driven induction motors arise from overvoltages and partial discharges (PD) in insulating systems of feeding cables and motors. The PWM waveforms produce complex overvoltages that stress the insulation more severely than sinusoidal voltage waveforms. The overvoltages form trials of pulses with very short rise times. Such conditions have essential influence on inception and activity of partial discharges in insulation systems. Selected aspects of these problems are presented in the paper: the numerical simulations of electric stress in coil-to-coil insulation of stator windings, the influence of the pulsed voltages modelling the PWM sequences, and the experimental results of PD in model twisted pair (TP) samples. Streszczenie. Narażenia eksploatacyjne są powodem postępującej degradacji elektrycznych układów izolacyjnych. Ocena intensywności i dynamiki tych procesów, będących m.in. konsekwencją lokalnego, roboczego natężenia pola elektrycznego jest zwykle prowadzona dla napięcia sinusoidalnie zmiennego. W aplikacjach, w których stosowane są energoelektroniczne układy przekształtnikowe narażenia napięciowe mają formę impulsów szybkozmiennych, tworzących powtarzalne sekwencje. Szczególne problemy powstają w układach napędowych silników indukcyjnych z modulacją szerokości impulsów (PWM), a związane są one z przepięciami oraz wyładowaniami niezupełnymi (wnz) w izolacji kabli zasilających oraz silników. Przebiegi PWM wytwarzają złożone przepięcia, które narażają izolację w większym stopniu niż napięcia przemienne. Przepięcia tworzą ciągi impulsów o bardzo krótkich czasach narastania, co ma zasadniczy wpływ na powstawanie i aktywność wyładowań niezupełnych w układach izolacyjnych. Artykuł przedstawia wybrane aspekty tych problemów: symulacje numeryczne naprężeń elektrycznych izolacji międzyzwojowej, wpływ napięć impulsowych modelujących sekwencje PWM oraz wyniki badań eksperymentalnych wnz w próbkach modelowych typu para skręcona (TP). (Modelowanie procesów degradacji układów elektroizolacyjnych wywołanych impulsami inwertera). Keywords: electrical insulation systems, degradation processes, partial discharges, PWM voltages Słowa kluczowe: układy izolacyjne, procesy degradacji, wyładowania niezupełne, napięcia PWM doi:10.12915/pe.2014.10.22 Introduction The inverter drives based on Pulse Width Modulation (PWM) technique are the most common type of inverter drives used for control of electric machines work. A general scheme of motor control with the PWM inverter drive is presented in Figure 1. The pulsed output voltage is applied from PWM drive to the motor terminals by a feeding cable, which for actual PWM pulses parameters for the most cases can be treated as transmission line [1]. In those drives the sequence control unit produces pulse-width modulated train of voltage pulses with slew rate up to 100 kV·s-1 and repetition rate even up to 100 kHz. In conse- quence large spikes, overshoots and oscillations could be observed on motor terminals. Electrical stresses caused by generated supply voltage distortions often lead to partial discharges, faster degradation of the insulation system, its unexpected breakdown, and failure of electrical machine. The types of insulating systems of electrical machines The paper is concerned to random wound stator windings insulation system, where the magnet wire is round and the arrangement between the turns is not defined (i.e. random). The main criterion for classification of winding insulation is related to assessment of PD activities during the lifetime and it refers to the random-wound and form-wound stator windings. According to IEC TS 60034-18-41 [2] the insula- tion systems of electrical machines fed by voltage inverters are divided into two types: Type I systems which are not expected to experience PD activity in their service, Type II systems which are expected to withstand PD activity throughout their service lifetime. Fig.1. Pulse voltages in single-phase inverter-cable-motor setup: R, L, C, G – parameters of transmission line model, Ld – phase inductance, Cg – distributed ground capacitance, Re – loss resistance, K – input winding capacitance; UDC – dc-link voltage, Uov – over- voltage crest value, du/dt – voltage slew rate, VSI – Voltage Source Inverter
  • 2. 86 PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 Machines with a rated voltage:  to 700 Vrms may have either Type I or type II windings,  above 700 Vrms the winding insulation is usually type II. During the exploitation, the electrical stresses will be created in the following locations in the insulating system (Fig.2): between conductors in different phases or phase-to- phase (UPP), between turn-to-turn (UCC), between a conductor and ground (UPG). Fig.2. Electrical stresses of motor insulating system: a) details of insulation system of inverter fed motor b) voltages for star connected motor: UPP – phase-to-phase voltage, UCC – conductor-to-conductor voltage, UPG – phase-to-ground voltage The elements of inverter fed motor insulation system are exposed to repetitive short rise time voltage impulses with significant amplitude. The electric stress is defined by the peak voltages and the basic stressing parameter is the peak-to-peak voltage. It means that the unipolar voltage produces the same stress as a bipolar voltage having a peak-to-peak voltage of the same value. This problem was recognized as first by Bonnet [3] and Person [4], who have recognized that switching devices as IGBT used in PWM converters create the high amplitude voltage impulses at the motor terminals. For modelling of random-wound windings, the samples called twisted-pair (TP) [5] made of magnet wires with different diameters are used. Twisted-pair samples are composed of two enamel-coated together twisted copper wires. According to IEC standard [6] the normalized number of twists ts on a nominal sample length l equal to 125 mm ranges from 3 – for enamelled wire nominal diameter between 2.15 mm to 3.5 mm to 16 twists – for enamelled wires with a diameter from 0.35 mm to 0.5 mm. Partial discharges in motor insulation The degradation mechanism in insulating systems at PWM inverter-fed driver is not the same as for sinusoidal frequency 50/60 Hz. The aging processes, as a result of PD activity, are accelerated by:  presence of repetitive overvoltages,  space charge injection in insulation – depending also on various PWM sequences,  high repetition rate of PD pulses,  high voltage slew rate (dU/dt). Theoretically, at semi-square voltages, partial dischar- ges should occur only at a rising and falling slope and vanish during the voltage plateau. The PD intensity should be related to du/dt. However, as shown by many researchers, the PD occurs in the whole voltage period [7, 8, 9], also when U = const. This necessitates a further recognition of the PD mechanism in insulation systems subjected to PWM-based drives. The whole stator winding is resin impregnated. The resin penetrates and fills the space between wires and stator slots in order to increase the dielectric capability, thus increasing the level of PD inception. The accumulated moisture and contaminants can promote tracking and deterioration, leading to failure. Tracking failures are caused by small partial discharges, which develop localised heating and cause chemical decomposition of any weak insulation barrier. Arcs of relatively high currents develop additional heating, which carbonizes the resin surface. Hence, the need for diagnosing stator windings is twofold:  already during the manufacturing process the magnet wire coated insulation may be damaged, causing galvanic short circuits, and leading to turn-to-turn / phase-to-phase faults (Fig.3a). Imperfect resin impregnation may result in voids formation and partial discharge development (Fig.3b),  during operation environmental conditions and mecha- nical stress, especially vibrations may lead to the insulation degradation. PWM-controlled motors might be subjected to an additional stress related to high voltage peaks, which can deteriorate the insulation system. The high electric field between wires in the slot or in the end winding section might start ionization and formation of corona (Fig.3c), which can lead to chemical damage and thermal hot spots. Fig.3. Turn-to-turn faults: a) electrical short-circuits, b) void between magnet wires and internal PD, c) magnet wire insulation failure and corona The insulation failure occurs when the magnitude and rise time of the repetitive transient voltage stress exceeds the withstand capability of the insulating system (Fig.4). The breakdown of insulation most commonly occur at the highest voltage stress spot, i.e. the first turn of the line end coil to the last turns of the coil group as well as in the end winding region, where wires from different coils can come into contact. Fig.4. Supply voltage of PWM driven motor with overvoltages The overvoltage stresses can be analyzed at semi- square voltage with a specified rise time tr, and the overvoltage magnitude Uov depends on the steepness of the semi-square voltage as illustrated in Figure 5. In PD model for such voltage stimulus the rise time tr is equal to: (1)   tg U t OV r The occurrence of partial discharges depends on incep- tion voltage Uci with respect to the value of Uov and is triggered when Uci < Uov (Fig.5), whereas the discharge intensity and their development also depends on the extinction voltage Uce. The attributes describing the PD sources depend on the ratio Uce / Uci, just like at sinusoidal voltage, and additionally on the rise time tr.
  • 3. PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 87 Fig.5. Definition of overvoltage parameters The factors affected the PD at impulse voltage are: voltage, frequency and pulse rise/fall time. The voltage rise time has special impact on the initiation conditions and on the inception voltage Ui of PD (Fig.6). Fig.6. PD pulses acquired in samples of thermosetting insulation for 50 Hz (left) and 1000 Hz (right) and for three rise-time parameters 800-1250-3000 ns (in the case of 3000 ns the time scale is 2 s/div otherwise 400 ns/div) [10] PD pulses acquisition at semi-square voltages Classic methods of PD detection described in IEC- 60270 [11] refer to measurements performed in the frequ- ency range up to 1 MHz and are not useful for voltages with high slew rate, due to frequency spectrum overlapping. Thus, in the case of PD measurements at semi-square voltages (e.g. generated by IGBT inverter) other specific detection methods operating in VHF/UHF range should be applied [12]. In the presented experiments three different types of detectors have been used for PD pulse acquisition: 1) E-field detector with 350 MHz amplifier connected to HP- 8591E spectrum analyzer, 2) Rogowski coil, and 3) non- inductive resistors. Electric signals from detectors were digitalized and registered by oscilloscopes with imple- mented DPO function (Digital Phosphor Oscilloscope) TDS784D or DPO2014 (Tektronix). The challenge in this kind of experiment, performed at fast stimulus is to separate the PD pulse from the pulses interfering due to HV modulator switching, as shown in Figure 7a. The narrow spike is the PD pulse, however charging current is also detected on wideband resistor. A single PD event, with 6 ns FWHM value (Full Width at Half Maximum), is observed in Figure 8. Determination of PDIV (Partial Discharge Inception Voltage) under impulse voltages at a level just above ionisation threshold is difficult to monitor precisely because of transient development of ionisation. Acquisition of PD signals in DPO mode for the semi-square voltage (Fig.8b) shows its appearance after the time lag on the rising slope of voltage pulse. The results confirm high repeatability of pulse voltage and stochastic nature of PD manifested by blurring of amplitude and time location. Fig.7. Semi-square voltage and current signal detected on 50  resistor – time scale 1µs/div (a) and individual PD pulse registered with 4 GHz sampling frequency (25 ns/div) (b) Fig.8. Partial discharges in thermosetting insulation sample for pulse voltage close to inception voltage. Acquisition of semi-square voltage and PD signal from Rogowski coil: a) single-shot acquisition by DPO2014, b) result of 3075 accumulations in DPO mode by TDS784D oscilloscope PD measurements in model insulation systems The TP samples have been used for studying the PD phenomena in enameled wires as a substitute of the motor winding. The twisted-pair of TP sample can be regarded as a pair of enameled wires being in contact (Fig.9a) or separated by a micro-air gap g (Fig.9b). Fig.9. Cross section of the enameled wires in TP sample (insulation thickness not in scale with wire diameter): a) g = 0, b) g > 0, c) PD zones in insulating system of TP sample The conditions for PD inception are determined by the electric field distribution between the wires. Without PD it
  • 4. 88 PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 can be approximated by capacitive field distribution, which is formed by a series of two capacitances of dielectric layer of insulation. When PDs are present, one can assume that the air space due to ionization starts to be conductive. Corona-like discharge is the mechanism of PD initiation between two insulated wires. Thus, the PD inception voltage Ui depends on the wire’s diameter in TP samples. At 50 Hz sinusoidal voltages the PD -q-n patterns can be acquired and analyzed [1]. The PD intensity, described by the total number of PD pulses N(U) is shown in Figure 10. Fig.10. The number of PD pulses N vs. voltage U for TP samples made from wires with 0.7 mm, 1.4 mm, and 2.5 mm diameter Analysis of electric field distributions in elements of motor windings The wound wires in TP samples create an insulating system with solid dielectric (coatings of enameled wires) or with micro-gap g between them. Along the TP sample, there are many distributed contact points of adjacent wires, which are in close proximity separated only by a micro gap in air. During the PD measurements the TP samples are exposed to the electric field higher than PD inception field. Electric field distribution in TP sample depends on: wire diameter D, insulation thickness a, number of twists ts, and airgap g between wires. For investigations of PD initiation and development in TP insulation systems, the two zones have been distinguished (Fig.9c):  Zone 1: micro-air gap exists at the contact of insulated wires, which form the insulation system composed of serial dielectrics. In this zone the electric field distribution is approximately uniform, therefore only normal electric field components occur. Their values are high in the air gap and much lower in the solid dielectric. The reason is that dielectric stress is reversely proportional to dielectric constant r the value of which is 3.8 – 4.2.  Zone 2: boundary region, adjacent to the contact point. Apart from regular electric field components also tangential components occur there. The electric field calculations along the profile A and B (Fig.9c) provide information about those field components. The distribution of electric field in insulating systems represented by twisted-pair model samples is directly connected with the mechanism of inception and development of partial discharges and electric breakdown. In parallel configuration of wires in TP sample no twists occur (ts = 0). One can considerate two cases: a) without air gap between the wires g = 0, b) the air gap exists, g = 100 µm. a) No distance between wires g = 0 mm The electric field distribution for parallel, adjoin wires for exemplary TP0.7 sample at 1 kV is presented in Figure 11. Fig.11. Electric field for parallel wires without air gap (g = 0) The electric field is depicted in three characteristic spots, one in the region of highest filed near the contact point of wires, the second one in the region of strong electric field (E = 9.5 kV/mm) and the third one on the boundary region, where the electric field drops below 2 kV/mm. The electric field in the cross sections of the wire’s contact point, along A and B profiles depicted in Figure 9c, is shown in plot in Figure 12. A high electric field of 30 – 40 kV/mm exists in the micro-air gap between wires and exceeds approx. 9 kV/mm corona inception stress characteristic for 0.1 mm gap. The diameter of wires in the twisted pair samples is particularly influencing the electric field distribution in the non-homogenous areas in twisted pair sample (Fig.12b). Fig.12. Electric field distribution along: a) profile A for TP0.7 and TP2.5, b) profile B for TP0.7 and TP2.5 [1]
  • 5. PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 90 NR 10/2014 89 b) Distance between wires g = 100 µm The electric field distribution for parallel wires placed in the proximity g = 100 µm at 1 kV is presented in Figure 13. In such a way a micro-air gap is formed between wires. Similarly like for adjacent wires, also in case of air slice, the electric field is depicted in three characteristic spots, one in the region of highest filed, the second one in the region of moderate electric field (E = 4 kV/mm) and the third one on the boundary region, where the electric field drops below 2 kV/mm. Fig.13. Electric field for parallel wires with air gap (g = 100 µm) Results of simulations show characteristic regions with significantly different values of electric field. These conditions influence the development of partial discharge forms, which can be indirectly confirmed by microscopic observation of the surface of wires insulation (Fig.14). It refers to the need of development a special wires design with higher resistance to fast surges [10, 13, 14]. Fig.14. Microphotographs of twisted wires from TP sample with insulation deterioration traces and breakdown hotspot Conclusions Partial discharge measurement is sensitive tool for assessment of winding wires quality and properties of new insulating materials. In motor windings, represented here by twisted-pair samples, partial discharges may occur in air gaps with a width from several m up to tens of m, at the inception voltage from approximately 850 V to 1400 V [10]. Modern methods of pulse signals detection and acquisition help us in better understanding of physical processes leading to inception and development of partial discharges in motor winding insulation. Numerical analysis of electric fields with modelling of real, imperfect configurations of winding wires pointed out possible ways of impulsive degradation processes of their insulating layers. The development of an enamelled wire that can withstand coil winding stress increases the reliability of electric motors fed by inverters. REFERENCES [1] Florkowska B., Zydroń P., Florkowski M.: Effects of converter pulses on the electrical insulation system of motors, Proc. 2011 IEEE ISIE, 573 – 578, Gdańsk, 2011 [2] IEC/TS 60034-18-41 ed. 1 (2006-10): Rotating electrical machines – Part 18-41: Qualification and type tests for Type I electrical insulation systems used in rotating electrical machines fed from voltage converters [3] Bonnet A. et all: Cause and analysis of stator and rotor failures in three phase squirrel cage induction motors, IEEE Trans. IAS, vol. 1992, 921 – 937 [4] Persson E.: Transient effects in applications of PWM inverters in induction motors, IEEE Trans. IAS, vol. 1992, 1095-1101 [5] IEC 60851-5 ed. 4.0 (2008-07): Winding wires. Test methods – Part 5: Electrical properties [6] IEC 60172 ed. 3.0: Test procedure for the determination of the temperature index of enamelled winding wires [7] Florkowska B., Florkowski M., Zydroń P., Roehrich J., Pędzisz K.: Degradation processes of polymer cable insulation at non-sinusoidal voltage stresses, Conf. Rec. 2010 IEEE ISEI, San Diego, CA, USA, paper 132 [8] Lindell E., Bengtsson T., Blennow J., Gubanski S.M., Influence of rise time on partial discharge extinction voltage at semi-square voltage waveforms, IEEE Trans. Dielectr. Electr. Insul., vol. 17, no. 1, 2010, 141–148 [9] Cavallini A., Montanari G.C.: Effect of supply voltage frequency on testing of insulation system, IEEE Trans. Dielectr. Electr. Insul., vol. 13, no. 1, 2006, 11 – 21 [10] Florkowska B., Florkowski M., Furgał J., Roehrich J., Zydroń P, Impact of fast transient phenomena on electrical insulation systems, AGH-UST Press; Kraków, 2012 [11] IEC-60270 ed. 3, (2000-12) High-voltage test techniques – Partial discharge measurements [12] IEC/TS 61934 ed. 2.0 (2011-04): Electrical insulating materials and systems – Electrical measurement of partial discharges (PD) under short rise time and repetitive voltage impulses [13] Manh Quan Nguyen ; Malec D., Mary D., Werynski P., Gornicka B., Therese L., Guillot, P., Silica nanofilled varnish designed for electrical insulation of low voltage inverter-fed motors, IEEE Trans. Dielectr. Electr. Insul., vol. 17, no. 5, 2010, 1349–1356 [14] Glinka T., Kulesz B.: Wyładowania niezupełne w izolacji zwojowej silników indukcyjnych zasilanych z falowników PWM, Prace Naukowe Instytutu Maszyn, Napedów i Pomiarów Elektrycznych Politechniki Wrocławskiej, Nr 49, Studia i Materiały Nr 21, 2000 Authors: Barbara Florkowska, Prof., E-mail: beflor@agh.edu.pl; Józef Roehrich PhD EE, E-mail: roehrich@agh.edu.pl; Paweł Zydroń PhD, D.Sc. AGH University of Science and Technology, Dept. of Electrical and Power Engineering, Mickiewicza 30, 30-059, Krakow, Poland, E-mail: pzydron@agh.edu.pl; Marek Florkowski PnD D.Sc., ABB Corporate Research Center, Starowiślna 13A, 31-038 Krakow, Poland, E-mail: marek.florkowski@pl.abb.com.