SlideShare a Scribd company logo
1 of 67
Julai02 ITiDi 1
KAPASITOR BANK FAKTUR
KUASA
Oleh
RAIS BIN MA’AT
Ketua Program Kejuruteraan Elektrik
Institut Latihan dan Pembangunan Infrastruktur
Ikram
Julai02 ITiDi 2
TYPES OF LOADS
• Most electrical loads can be placed in one
of three categories:
• Resistive
• Inductive
• Capacitive
• Most common loads are inductive loads
such as motors and flourescent lamps,
followed by resistive loads such as heaters,
filament bulb and electric iron
Julai02 ITiDi 3
Cont.
• All inductive loads require two kinds of
power to function properly, there are:
• Active power (kW) – actually perform the
work
• Reactive power (kVAr) – to sustain the
electromagnetic field
• The motor without load still demand
magnetizing current to maintain the
magnetic field
Julai02 ITiDi 4
JENIS-JENIS KUASA
• Kuasa Sebenar / Kuasa Berguna / True
Power / Real Power / Aktif Power (kW)
• Kuasa Samar / Apparent Power (kVA)
• Kuasa Reaktif / Useless Power /
Magnetising Power (kVAr)
Julai02 ITiDi 5
KUASA SEBENAR
• Kuasa keluaran yang sebenarnya dapat
digunakan untuk membuat kerja atau
menghasilkan apa-apa tenaga
• Unit dalam watt atau kilowatt
• Merupakan kuasa keluaran (output power)
• Arus dan voltan adalah sefasa
Julai02 ITiDi 6
KUASA SAMAR
• Kuasa Samar atau Apparent Power adalah
jumlah kuasa yang termasuk didalamnya
kuasa sebenar dan kuasa reaktif
• Ia adalah hasil dharab voltan dengan arus
tanpa mengambil kira apa-apa kehilangan
atau ketidakcekapan oleh apa-apa sebab
• Unit didalam kilovoltampere (kVA)
Julai02 ITiDi 7
KUASA REAKTIF
• Kuasa Reaktif / Kuasa Regangan atau
Useless power ialah kuasa yang tidak dapat
digunakan sebagai kuasa keluaran
• Disebut juga sebagai Magnetising Power
sebab ia digunakan untuk mengujudkan dan
mengekalkan medan magnet (gelong)
• Arus mengekori voltan
• Unit dalam kVAr
Julai02 ITiDi 8
RAJAH TIGA SEGI KUASA
• Apabila sudut fasa kecil faktur kuasa tinggi
• Apabila faktur kuasa rendah nilai kVA dan
kVAr akan menjadi lebih besar tetapi nilai
kW tetap sama
• Apabila sudut fasa kosong, faktur kuasa
bersamaan satu (kos 0º = 1), oleh itu nilai
kW sama dengan nilai kVA
• Apabila nilai kVAr dikecilkan, faktur kuasa
menjadi tinggi
Julai02 ITiDi 9
SEGITIGA KUASA
Julai02 ITiDi 10
PERSAMAAN KUASA I
kVA² = kW² + kVAr²
Julai02 ITiDi 11
PERSAMAAN KUASA II
PkW = √3 x VL x IL x P.F
Julai02 ITiDi 12
RAJAH VEKTOR
Julai02 ITiDi 13
Julai02 ITiDi 14
RAJAH VEKTOR
Julai02 ITiDi 15
Julai02 ITiDi 16
RUMUSAN RAJAH VEKTOR
• Apabila sudut fasa kecil f.k adalah tinggi
• Apabila sudut fasa besar (f.k rendah) kVA
dan kVAr menjadi besar tetapi kW tetap
sama
• Apabila sudut fasa kosong, f.k bersamaan 1
dan kW sama dengan kVA
• Apabila nilai kVAr kecil f.k adalah tinggi
Julai02 ITiDi 17
FAKTUR KUASA
• Ialah nisbah diantara Kuasa Sebenar dengan
Kuasa Samar atau kos  (sudut fasa)
Kuasa Sebenar (kW)
Faktur Kuasa = -------------------------
Kuasa Samar (kVA)
Julai02 ITiDi 18
MAKNA F.K RENDAH
• Tidak cekap menggunakan kuasa
• Pembaziran kuasa kepada yang tidak
produktif
• Arus akan menjadi lebih tinggi dari yang
sewajarnya
• Pihak penjanaan (TNB) akan terpaksa
menjana lebih kVA, oleh itu kos menjadi
tinggi
Julai02 ITiDi 19
KESAN F.K RENDAH
• Memerlukan saiz kabel yang lebih besar
• Susut voltan berlebihan
• Penggunaan alatubah tidak optimum
• Kehilangan I²R (haba) yang tinggi
• Peralatan elektrik seperti alatubah, motor,
alternator cepat menjadi panas dari yang
sepatutnya
Julai02 ITiDi 20
KESAN LAIN F.K RENDAH
• Didenda oleh pihak TNB atau Pemegang
Lesen jika faktur kuasa purata bulanan
kurang dari 0.85
• Alatubah tidak dapat menghasilkan lebih
watt untuk disalurkan kepada beban-beban
atau pengguna-pengguna yang lain
Julai02 ITiDi 21
PENYEBAB FAKTUR KUASA
RENDAH
1. Induction Motor
2. Alatubah
3. Cok/Ballast/Magnetic coil
4. Pengimpal (welding set)
5. Induction Furnace
Julai02 ITiDi 22
PENGIRAAN ARUS
• Kira arus sebuah motor 40 HP pada:
• a. Faktur kuasa 0.9
• b. Faktur kuasa 0.6
• Apakah perbezaan dari segi nilai arus
tersebut
Julai02 ITiDi 23
MOTOR 40 H.P, 415V PADA
PELBAGAI F.KUASA
Faktur Kuasa Arus (A)
1.0 41.51
0.95 43.68
0.90 46.11
0.85 48.82
0.80 51.87
0.75 55.33
0.70 59.28
0.65 63.85
0.60 69.17
0.55 75.45
0.50 83.00
Julai02 ITiDi 24
JANAKUASA 500kW, 415V PADA
PELBAGAI F.KUASA
F.K Arus (A) kVA Pertambahan
kVA
Pertambahan
Arus
1.0 696 500 0 0
0.9 773 556 77 56
0.8 870 625 174 125
0.7 994 714 298 214
0.6 1159 833 463 333
0.5 1391 1000 695 500
Julai02 ITiDi 25
KADAR DENDA
• 1.5% dari jumlah bil bulanan jika faktur
kuasa dari 0.75 hingga 0.84 bagi setiap 0.01
yang kurang
• 3% dari jumlah bil bulanan jika faktur kuasa
kurang dari 0.75 bagi setiap 0.01 yang
kurang dan dicampur dengan jumlah yang
diatas tadi
Julai02 ITiDi 26
CONTOH
• MD = 100kW
• kWh = 65,000 unit
• kVArh = 85,000 unit
• Bil bulanan = RM18,500
Kira denda dikenakan jika faktur kuasa = 0.61
Kiraan
• (0.85 - 0.75) ÷ 0.01 = 10 x 1.5% = 15%
• (0.75 - 0.61) ÷ 0.01 = 14 x 3% = 42%
• Jumlah = (15%+42%) x RM18,500 = RM10,545.00
Julai02 ITiDi 27
BACAAN BULANAN
• Meter kilowatt-hour (kWh)
• Meter kVArh
• Meter faktur kuasa yang terdapat pada
papan suis utama adalah memberi bacaan
ketika (instantaneous value) dan bukan
bacaan purata bulanan
Julai02 ITiDi 28
PENGUKURAN DITAPAK
Jika boleh hendaklah dibuat semasa operasi berada ditahap
maksima. Bacaan faktur kuasa yang kerap adalah perlu.
Katalah bacaan faktur kuasa yang diperolehi = 0.5
Purata bacaan voltan = 420V
Purata arus talian = 700A
Kuasa digunakan = 3 x 420V x700A x 0.5
= 256kW
Jika faktur kuasa dibaiki kepada 0.95
kVAr = 256kW (tan 1 – tan 2) = 256 (1.73 – 0.329)
= 359 kVAr
Julai02 ITiDi 29
BACAAN BULANAN
Bulan kWh kVArh
Januari 921 546
Februari 1230 742
Julai02 ITiDi 30
PENGIRAAN F.KUASA
• kWh digunakan = 1230  921 = 309 kWh
• kVArh  = 742  546 = 196 kVArh
• Tan  = 196 / 309 = 0.63
• Inverse tan 0.63 = 32.3°
• Kos 32.3° = 0.84
• Faktur kuasa = 0.84
Julai02 ITiDi 31
CARA LAIN
F.K = kWh = 309 .
 (kWh² + kVArh²)  (309² + 196²)
= 309 .
 (95481 + 38416)
= 0.84
Julai02 ITiDi 32
MEMBAIKI FAKTUR KUASA
• Menggunakan kapasitor
• Menggunakan motor segerak (synchronous
motor)
Julai02 ITiDi 33
KAPASITOR
• Arus mendulu voltan
• Harga murah
• Senggaraan murah dan mudah (hampir
tanpa senggaraan – maintenance free)
• Terdapat berbagai-bagai saiz dari kecil
hinggalah besar
• Boleh dipercayai
Julai02 ITiDi 34
KAPASITOR
BANK
Julai02 ITiDi 35
MOTOR SEGERAK
• Harganya mahal & senggaraan juga mahal
• Bersaiz besar
• Kelajuan tetap (bergantung kepada ulangan)
• Stator dibekalkan dengan bekalan AC
• Rotor dibekalkan dengan bekalan DC
• Boleh berfungsi dari lagging power factor ke unity
dan ke leading power factor dengan melaras arus
ujaan ke rotor
• Sesuai digunakan sebagai tugas sampingan
Julai02 ITiDi 36
PEMBAIKAN TUNGGAL
• Bermakna pembaikan faktur kuasa pada
sesuatu alat/mesen seperti motor elektrik
• Jika terlalu banyak motor dengan berbagai-
bagai saiz maka cara ini adalah tidak
praktikal sebab kerja senggaraan menjadi
terlalu banyak
• Faktur kuasa berubah-ubah sepanjang hari
oleh itu cara ini kurang sesuai
Julai02 ITiDi 37
PERMENENT
CONNECTION
Julai02 ITiDi 38
MOTOR
DENGAN
P.F KAPASITOR
SAMBUNGAN
TETAP
Julai02 ITiDi 39
PERTIMBANGAN AM
• Ujaan auto iaitu ujaan diri motor oleh cas
kapasitor yang tersimpan semasa ketiadaan
bekalan hendaklah dielakkan
• Pastikan arus kapasitor adalah sama atau
lebih kecil dari arus kemagnetan motor,
biasanya 90% dari arus tanpa beban motor
Julai02 ITiDi 40
SAIZ KAPASITOR MOTOR
• kW motor x Beban Penuh x (tan 1– tan 2)
• kVAr = ------------------------------------------------------
• Kecekapan Motor (pada beban penuh)
• 1 - faktur kuasa asal
• 2 - faktur kuasa diperbaiki
Julai02 ITiDi 41
PEMBAIKAN CARA PUSAT
• Apabila faktur kuasa berubah-ubah sepanjang hari
dan beban induktif kecil terlalu banyak dimana
cara pembaikan tunggal adalah tidak ekonomik
dan tidak praktikal
• Tidak mempunyai ruang yang mencukupi untuk
menempatkan terlalu banyak kapasitor
• Operasi kapasitor bank dikendalikan secara
otomatik mengikut perubahan beban
Julai02 ITiDi 42
PEMBAIKAN KUMPULAN &
PEMBAIKAN PUSAT TETAP
• Satu kapasitor bank untuk sekumpulan
motor atau apa-apa beban lain
• Pembaikan individu secara tetap asasnya
sama dengan pembaikan cara pusat tetapi ia
tidak mempunyai regulator faktur kuasa
iaitu ia tidak dikawal secara otomatik
Julai02 ITiDi 43
PEMBAIKAN TERGABUNG
Pembaikan tergabung adalah campuran
pembaikan tetap, otomatik, kumpulan dan
tunggal
Julai02 ITiDi 44
SAIZ KAPASITOR BANK
• kVAr = PkW (tan1 – tan 2) = PkW x k
• kVAr - Kadaran kapasitor bank
• PkW - MD pemasangan dalam kW
• tan 1 - Faktur kuasa asal
• tan 2 - Faktur kuasa diperbaiki
• k - tan1 – tan 2
Julai02 ITiDi 45
NILAI K
• tan 1 – tan 2
• Gunakan Nomogram
• Gunakan Jadual Faktur K
Julai02 ITiDi 46
NOMOGRAM
Julai02 ITiDi 47
JADUAL
UNTUK
NILAI
K
Julai02 ITiDi 48
CONTOH 1
• Beban MD = 200kW
• Faktur kuasa asal = 0.74
• Faktur kuasa diperbaiki = 0.9
• Faktur k = 0.42 (dari jadual)
• Saiz kapasitor bank = 200 x 0.42
= 84kVAr
Julai02 ITiDi 49
CONTOH 2
• Sebuah pemasangan menggunakan 49,470 kWh
tenaga. F.K bulan Jun ialah 0.59. pemasangan
digunakan 9 jam sehari, 25 hari sebulan. Kira saiz
kapasitor bank yang diperlukan untuk
memperbaiki F.K kepada 0.95.
• Jumlah jam kerja = 9 x 25 = 225jam
• Beban permintaan = 49,470/225 = 200 kW
• kVAr diperlukan= kW (tan θ1 – tan θ2)
• = 200 (1.386 – 0.329)
• = 229 kVAr
Julai02 ITiDi 50
PENENTUAN BILANGAN STEP
• Tidak ada satu formula khusus untuk
menentukan bilangan step sesuatu kapasitor
bank
• Ia mengikut kesesuaian beban pemasangan
dan hendaklah praktikal, jika satu step
terlalu besar ia akan mengakibatkan over
correction
Julai02 ITiDi 51
MENENTUKAN KADARAN kVAr
SETIAP STEP
• Setiap step boleh mempunyai kadaran kVAr
yang sama atau boleh juga tidak sama
• Ia berpandukan saiz-saiz beban induktif
yang terpasang
• Jika semasa minimum load bebannya
tersangat rendah dan terdapat pula motor
bersaiz besar, maka lazimnya kVAr setiap
step tidak sama
Julai02 ITiDi 52
POWER FACTOR REGULATOR
• Satu device elektronik untuk mengawal
secara otomatik jumlah kVAr yang perlu
dimasukkan kepada atau dikeluarkan
daripada litar pada satu-satu masa
• Ia mengesan perbedaan sudut fasa diantara
voltan dan arus dan menambah atau
mengurangkan kVAr dalam litar mengikut
setting yang telah ditentukan
Julai02 ITiDi 53
P.FACTOR
REGULATOR
Julai02 ITiDi 54
C/K SETTING
• Nilai C/K menentukan pada tahap arus
reaktif yang mana regulator mula bertindak
• Tatahan C/K adalah mengikut step kapasitor
yang paling kecil, selalunya yang pertama
• Diperolehi dengan membahagi kVAr
dengan K, dimana K nisbah alatubah arus
Julai02 ITiDi 55
CONTOH
• Step terkecil = 150 kVAr
• Nisbah c.t = 1000/5A
• Oleh itu K = 1000  5 = 200
• C/K = 150  200 = 0.75
• Kebiasaannya regulator di set agar
bertindak pada kadar 2/3 daripada arus satu
langkah
Julai02 ITiDi 56
TARGET P.F SETTING
• P.F Regulator memerlukan kita menentukan
target P.F setting
• Selalunya kita set pada kedudukan yang
melebehi 0.85, contohnya pada 0.9
Julai02 ITiDi 57
AUTO/MANUAL BUTTON
• Dalam keadaan normal P.F Regulator
hendaklah di set pada kedudukan Auto
• Apabila ujian manual diperlukan tukar
kedudukan pada manual dan tekan butang
plus (+) dan butang minus ( – ) untuk
mengurang dan menambah kapasitor
kepada sistem pemasangan tanpa mengira
beban elektrik pada masa tersebut
Julai02 ITiDi 58
PENUNJUK LED
• Penunjuk LED akan menyala mengikut
bilangan step yang aktif (energised to the
circuit). Ini adalah penunjuk sahaja, tidak
mesti step tersebut berfungsi sekiranya
fius/MCB, kabel, kontaktor atau kapasitor
mengalami masaalah
Julai02 ITiDi 59
C/K SETTING
Julai02 ITiDi 60
JADUAL
SUDUT-
SUDUT
Julai02 ITiDi 61
PROGRAMME MODE
1:1:1:1:1 10:10:10:10:10 KVAR
1:2:2:2:2 10:20:20:20:20 KVAR
1:2:4:4:4 10:20:40:40:40 KVAR
1:2:2:4:4 10:20:20:40:40 KVAR
1:2:4:4:8 10:20:40:40:80 KVAR
1:2:4:8:8 10:20:40:80:80 KVAR
Julai02 ITiDi 62
KOMPONEN-KOMPENEN YANG
DIPERLUKAN
1. Alatubah arus, satu sahaja diperlukan (RED)
2. Fius atau MCB
3. Power factor regulator
4. Bekalan dari dua fasa (Yellow, Blue)
5. Kontaktor
6. Kabel
7. Kapasitor bank
Julai02 ITiDi 63
KADARAN KOMPONEN
1. Fius/MCB : 1.5 x Arus kapasitor
2. Kontaktor : 1.6 ke 2.0 x Arus kapasitor
3. Kabel : 1.7 x Arus kapasitor
Julai02 ITiDi 64
KRITERIA DIPERLUKAN
1. Arus transient semasa pensuisan
2. Voltan transient apabila kapasitor
diputuskan semasa pensuisan dilakukan
yang menyebabkan berlakunya arka
3. Berupaya membawa beban penuh
4. Berupaya membawa peningkatan arus
kapasitor dalam keadaan tertentu
Julai02 ITiDi 65
CONTROL CIRCUIT
Julai02 ITiDi 66
SENGGARAAN KAPASITOR BANK
1. Periksa fius/MCB yang melindungi kapasitor
bank
2. Power factor regulator mungkin tidak berfungsi
3. Sambungan-sambungan mungkin longgar
4. Kapasitor boleh rosak, terbakar atau meletup
5. Terlalu banyak habok atau kotoran
menyebabkan flashover
6. Pengudaraan tersekat menyebabkan panas
Julai02 ITiDi 67
KESAN HARMONIK
• Harmonik yang tinggi dan banyak
menyebabkan galangan kapasitor menjadi
rendah, oleh itu kapasitor mengalami
keadaan hampir-hampir litar pintas
• Kapasitor akan menjadi terlalu panas dan
kadang-kadang meletup

More Related Content

Similar to KAPASITOR BANK FAKTUR KUASA KAPASITOR BANK FAKTUR KUASA

Materi Sosialiasi CSI-11P dan CSI01-S E1R0.pdf
Materi Sosialiasi CSI-11P dan CSI01-S E1R0.pdfMateri Sosialiasi CSI-11P dan CSI01-S E1R0.pdf
Materi Sosialiasi CSI-11P dan CSI01-S E1R0.pdf
AgungNugroho922310
 
Teknologi-SVC-dan-aplikasinya.pdf
Teknologi-SVC-dan-aplikasinya.pdfTeknologi-SVC-dan-aplikasinya.pdf
Teknologi-SVC-dan-aplikasinya.pdf
utimuhadis
 
(Plta) pembangkit listrik tenaga air
(Plta) pembangkit listrik tenaga air(Plta) pembangkit listrik tenaga air
(Plta) pembangkit listrik tenaga air
Putri Berlian Abadi
 
Somar integra industry case epson injection moulding
Somar integra industry case   epson injection mouldingSomar integra industry case   epson injection moulding
Somar integra industry case epson injection moulding
Sherly Saerang
 
Its undergraduate-12857-presentation
Its undergraduate-12857-presentationIts undergraduate-12857-presentation
Its undergraduate-12857-presentation
Bobby Tampubolon
 
Materi Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptx
Materi Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptxMateri Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptx
Materi Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptx
FauzanAdhiSasmita1
 
Kebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdf
Kebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdfKebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdf
Kebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdf
LeoYudha1
 

Similar to KAPASITOR BANK FAKTUR KUASA KAPASITOR BANK FAKTUR KUASA (19)

PPT benar.pptx
PPT benar.pptxPPT benar.pptx
PPT benar.pptx
 
Teknik Instalasi Tenaga Listrik.pptx
Teknik Instalasi Tenaga Listrik.pptxTeknik Instalasi Tenaga Listrik.pptx
Teknik Instalasi Tenaga Listrik.pptx
 
Materi Sosialiasi CSI-11P dan CSI01-S E1R0.pdf
Materi Sosialiasi CSI-11P dan CSI01-S E1R0.pdfMateri Sosialiasi CSI-11P dan CSI01-S E1R0.pdf
Materi Sosialiasi CSI-11P dan CSI01-S E1R0.pdf
 
Teknologi-SVC-dan-aplikasinya.pdf
Teknologi-SVC-dan-aplikasinya.pdfTeknologi-SVC-dan-aplikasinya.pdf
Teknologi-SVC-dan-aplikasinya.pdf
 
pdfslide.tips_nota-power-electronics-1.ppt
pdfslide.tips_nota-power-electronics-1.pptpdfslide.tips_nota-power-electronics-1.ppt
pdfslide.tips_nota-power-electronics-1.ppt
 
Perbaikan Faktor Daya untuk Meningkatkan Daya Aktif by Ahmad Mutawali.pptx
Perbaikan Faktor Daya untuk Meningkatkan Daya Aktif by Ahmad Mutawali.pptxPerbaikan Faktor Daya untuk Meningkatkan Daya Aktif by Ahmad Mutawali.pptx
Perbaikan Faktor Daya untuk Meningkatkan Daya Aktif by Ahmad Mutawali.pptx
 
6 motor-induksi
6 motor-induksi6 motor-induksi
6 motor-induksi
 
Direktur Aneka EBT.pdf
Direktur Aneka EBT.pdfDirektur Aneka EBT.pdf
Direktur Aneka EBT.pdf
 
Macam-macam instalasi listrik rumah
Macam-macam instalasi listrik rumahMacam-macam instalasi listrik rumah
Macam-macam instalasi listrik rumah
 
PPT_D.35EBT15.006.1.ppt
PPT_D.35EBT15.006.1.pptPPT_D.35EBT15.006.1.ppt
PPT_D.35EBT15.006.1.ppt
 
Modul Praktikum Motor Induksi
Modul Praktikum Motor InduksiModul Praktikum Motor Induksi
Modul Praktikum Motor Induksi
 
(Plta) pembangkit listrik tenaga air
(Plta) pembangkit listrik tenaga air(Plta) pembangkit listrik tenaga air
(Plta) pembangkit listrik tenaga air
 
Kapasitor bank
Kapasitor bankKapasitor bank
Kapasitor bank
 
reinstalasi jerakah(revisi).pptx
reinstalasi jerakah(revisi).pptxreinstalasi jerakah(revisi).pptx
reinstalasi jerakah(revisi).pptx
 
Bekalan tenaga
Bekalan tenagaBekalan tenaga
Bekalan tenaga
 
Somar integra industry case epson injection moulding
Somar integra industry case   epson injection mouldingSomar integra industry case   epson injection moulding
Somar integra industry case epson injection moulding
 
Its undergraduate-12857-presentation
Its undergraduate-12857-presentationIts undergraduate-12857-presentation
Its undergraduate-12857-presentation
 
Materi Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptx
Materi Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptxMateri Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptx
Materi Teknologi dan Efisiensi Energi Terbarukan 18 Nopember 2022.pptx
 
Kebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdf
Kebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdfKebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdf
Kebijakan-dan-Implementasi-PLTS-Atap-Rev1.pdf
 

More from QamarinaZainalAbidin

EARTHING tecnology electrical engineering electrical
EARTHING tecnology electrical engineering electricalEARTHING tecnology electrical engineering electrical
EARTHING tecnology electrical engineering electrical
QamarinaZainalAbidin
 
0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx
0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx
0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx
QamarinaZainalAbidin
 

More from QamarinaZainalAbidin (16)

kaedah-membaca kaedah-membaca 6 tahun 5 tahun
kaedah-membaca kaedah-membaca 6 tahun 5 tahunkaedah-membaca kaedah-membaca 6 tahun 5 tahun
kaedah-membaca kaedah-membaca 6 tahun 5 tahun
 
Topik 7 Penskoran, penggredan dan kriteria pentaksiran.pptx
Topik 7 Penskoran, penggredan dan kriteria pentaksiran.pptxTopik 7 Penskoran, penggredan dan kriteria pentaksiran.pptx
Topik 7 Penskoran, penggredan dan kriteria pentaksiran.pptx
 
Topik 6 Reka-Bentuk-Pembinaan-dan-Pentadbiran-Ujian.pptx
Topik 6 Reka-Bentuk-Pembinaan-dan-Pentadbiran-Ujian.pptxTopik 6 Reka-Bentuk-Pembinaan-dan-Pentadbiran-Ujian.pptx
Topik 6 Reka-Bentuk-Pembinaan-dan-Pentadbiran-Ujian.pptx
 
(03) NPA Sistem Pentadbiran Negara Pentadbiran Negara
(03) NPA Sistem Pentadbiran Negara Pentadbiran Negara(03) NPA Sistem Pentadbiran Negara Pentadbiran Negara
(03) NPA Sistem Pentadbiran Negara Pentadbiran Negara
 
UJIAN TEKANAN UJIAN TEKANAN UJIAN TEKANAN
UJIAN TEKANAN UJIAN TEKANAN UJIAN TEKANANUJIAN TEKANAN UJIAN TEKANAN UJIAN TEKANAN
UJIAN TEKANAN UJIAN TEKANAN UJIAN TEKANAN
 
PENGALIR TALIAN AERIAL PENGALIR TALIAN AERIAL
PENGALIR TALIAN AERIAL PENGALIR TALIAN AERIALPENGALIR TALIAN AERIAL PENGALIR TALIAN AERIAL
PENGALIR TALIAN AERIAL PENGALIR TALIAN AERIAL
 
PENCAWANG PENCAWANG PENCAWANG PENCAWANG PENCAWANG
PENCAWANG PENCAWANG PENCAWANG PENCAWANG PENCAWANGPENCAWANG PENCAWANG PENCAWANG PENCAWANG PENCAWANG
PENCAWANG PENCAWANG PENCAWANG PENCAWANG PENCAWANG
 
INJIN DISEL INJIN DISEL INJIN DISEL INJIN DISEL
INJIN DISEL INJIN DISEL INJIN DISEL INJIN DISELINJIN DISEL INJIN DISEL INJIN DISEL INJIN DISEL
INJIN DISEL INJIN DISEL INJIN DISEL INJIN DISEL
 
ASAS ELEKTRIK ASAS ELEKTRIK ASAS ELEKTRIK
ASAS ELEKTRIK ASAS ELEKTRIK ASAS ELEKTRIKASAS ELEKTRIK ASAS ELEKTRIK ASAS ELEKTRIK
ASAS ELEKTRIK ASAS ELEKTRIK ASAS ELEKTRIK
 
BATTERY bateri bateri bateri bateri bateri bateri bate
BATTERY bateri bateri bateri bateri bateri bateri bateBATTERY bateri bateri bateri bateri bateri bateri bate
BATTERY bateri bateri bateri bateri bateri bateri bate
 
EARTHING tecnology electrical engineering electrical
EARTHING tecnology electrical engineering electricalEARTHING tecnology electrical engineering electrical
EARTHING tecnology electrical engineering electrical
 
11KV CIRCUIT BREAKERS.ppt
11KV CIRCUIT BREAKERS.ppt11KV CIRCUIT BREAKERS.ppt
11KV CIRCUIT BREAKERS.ppt
 
0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx
0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx
0. PANDUAN BAHAN PENGAJARAN UNTUK PROGRAM DVM.pptx
 
AKTA BEKALAN ELEKTRIK 1990.pptx
AKTA BEKALAN ELEKTRIK 1990.pptxAKTA BEKALAN ELEKTRIK 1990.pptx
AKTA BEKALAN ELEKTRIK 1990.pptx
 
B16 SISTEM PENDAWAIAN 18ogos2014.ppt
B16 SISTEM PENDAWAIAN 18ogos2014.pptB16 SISTEM PENDAWAIAN 18ogos2014.ppt
B16 SISTEM PENDAWAIAN 18ogos2014.ppt
 
EMPLOYABILITY SKILLS-MODUL 8.pptx
EMPLOYABILITY SKILLS-MODUL 8.pptxEMPLOYABILITY SKILLS-MODUL 8.pptx
EMPLOYABILITY SKILLS-MODUL 8.pptx
 

Recently uploaded

Metode_Sampling bahan galian mineral.pptx
Metode_Sampling bahan galian mineral.pptxMetode_Sampling bahan galian mineral.pptx
Metode_Sampling bahan galian mineral.pptx
HeriGeologist
 
703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx
703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx
703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx
arisvanrush
 
obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...
obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...
obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...
obat aborsi Pangkal pinang 082223109953 Jual obat aborsi
 
Klinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di Depok
Klinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di DepokKlinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di Depok
Klinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di Depok
Klinik Obat Aborsi Di Depok Wa 082223109953
 
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953
 
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai Penuh
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai PenuhObat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai Penuh
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai Penuh
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli
 
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Obat Aborsi Jakarta ( Ampuh _ No. 1 ) Kandungan Jakarta
 
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Obat Aborsi Jakarta ( Ampuh _ No. 1 ) Kandungan Jakarta
 
Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...
Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...
Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...
Obat Aborsi Samarinda ( Asli Ampuh No.1 ) Samarinda
 
Obat Aborsi jakarta WA 082223109953 Jual Obat Aborsi Cytotec Asli Di jakarta
Obat Aborsi jakarta WA 082223109953  Jual Obat Aborsi Cytotec Asli Di jakartaObat Aborsi jakarta WA 082223109953  Jual Obat Aborsi Cytotec Asli Di jakarta
Obat Aborsi jakarta WA 082223109953 Jual Obat Aborsi Cytotec Asli Di jakarta
Obat Aborsi jakarta WA 082223109953 Cytotec Asli Di jakarta
 

Recently uploaded (15)

Pengukuran Topografi menggunakan GPS Geodetik
Pengukuran Topografi menggunakan GPS GeodetikPengukuran Topografi menggunakan GPS Geodetik
Pengukuran Topografi menggunakan GPS Geodetik
 
Perencanaan Pelabuhan perikanan id.pptx
Perencanaan Pelabuhan perikanan  id.pptxPerencanaan Pelabuhan perikanan  id.pptx
Perencanaan Pelabuhan perikanan id.pptx
 
PROSEDUR DALAM MELAKUKAN PERHITUNGAN PEKERJAAN PINTU.pptx
PROSEDUR DALAM MELAKUKAN PERHITUNGAN PEKERJAAN PINTU.pptxPROSEDUR DALAM MELAKUKAN PERHITUNGAN PEKERJAAN PINTU.pptx
PROSEDUR DALAM MELAKUKAN PERHITUNGAN PEKERJAAN PINTU.pptx
 
Metode_Sampling bahan galian mineral.pptx
Metode_Sampling bahan galian mineral.pptxMetode_Sampling bahan galian mineral.pptx
Metode_Sampling bahan galian mineral.pptx
 
703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx
703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx
703618627-PPT-INVESTIGASI-KECELAKAAN-KERJA.pptx
 
obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...
obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...
obat aborsi Pangkal pinang Wa 082223109953 Jual obat aborsi Cytotec asli Di P...
 
Klinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di Depok
Klinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di DepokKlinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di Depok
Klinik Obat Aborsi Di Depok Wa 082223109953 Klinik Aborsi Di Depok
 
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...
Jual Obat Aborsi Batam ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jual Ob...
 
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai Penuh
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai PenuhObat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai Penuh
Obat Aborsi Sungai Penuh 082223109953 Jual Cytotec Asli Di Sungai Penuh
 
STRUKTUR KONSTRUKSI BANGUNAN TINGGI -.pptx
STRUKTUR KONSTRUKSI BANGUNAN TINGGI -.pptxSTRUKTUR KONSTRUKSI BANGUNAN TINGGI -.pptx
STRUKTUR KONSTRUKSI BANGUNAN TINGGI -.pptx
 
2. Bp. Suwardi-MATERI RAKOR DITJEN PLANOLOGI DAN TL.pptx
2. Bp. Suwardi-MATERI RAKOR DITJEN PLANOLOGI DAN TL.pptx2. Bp. Suwardi-MATERI RAKOR DITJEN PLANOLOGI DAN TL.pptx
2. Bp. Suwardi-MATERI RAKOR DITJEN PLANOLOGI DAN TL.pptx
 
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
 
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
Jual Obat Aborsi Jakarta Selatan 0822 2310 9953 Klinik Jual Obat Cytotec Asli...
 
Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...
Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...
Jual Obat Aborsi Samarinda ( Asli Ampuh No.1 ) 082223109953 Tempat Klinik Jua...
 
Obat Aborsi jakarta WA 082223109953 Jual Obat Aborsi Cytotec Asli Di jakarta
Obat Aborsi jakarta WA 082223109953  Jual Obat Aborsi Cytotec Asli Di jakartaObat Aborsi jakarta WA 082223109953  Jual Obat Aborsi Cytotec Asli Di jakarta
Obat Aborsi jakarta WA 082223109953 Jual Obat Aborsi Cytotec Asli Di jakarta
 

KAPASITOR BANK FAKTUR KUASA KAPASITOR BANK FAKTUR KUASA

  • 1. Julai02 ITiDi 1 KAPASITOR BANK FAKTUR KUASA Oleh RAIS BIN MA’AT Ketua Program Kejuruteraan Elektrik Institut Latihan dan Pembangunan Infrastruktur Ikram
  • 2. Julai02 ITiDi 2 TYPES OF LOADS • Most electrical loads can be placed in one of three categories: • Resistive • Inductive • Capacitive • Most common loads are inductive loads such as motors and flourescent lamps, followed by resistive loads such as heaters, filament bulb and electric iron
  • 3. Julai02 ITiDi 3 Cont. • All inductive loads require two kinds of power to function properly, there are: • Active power (kW) – actually perform the work • Reactive power (kVAr) – to sustain the electromagnetic field • The motor without load still demand magnetizing current to maintain the magnetic field
  • 4. Julai02 ITiDi 4 JENIS-JENIS KUASA • Kuasa Sebenar / Kuasa Berguna / True Power / Real Power / Aktif Power (kW) • Kuasa Samar / Apparent Power (kVA) • Kuasa Reaktif / Useless Power / Magnetising Power (kVAr)
  • 5. Julai02 ITiDi 5 KUASA SEBENAR • Kuasa keluaran yang sebenarnya dapat digunakan untuk membuat kerja atau menghasilkan apa-apa tenaga • Unit dalam watt atau kilowatt • Merupakan kuasa keluaran (output power) • Arus dan voltan adalah sefasa
  • 6. Julai02 ITiDi 6 KUASA SAMAR • Kuasa Samar atau Apparent Power adalah jumlah kuasa yang termasuk didalamnya kuasa sebenar dan kuasa reaktif • Ia adalah hasil dharab voltan dengan arus tanpa mengambil kira apa-apa kehilangan atau ketidakcekapan oleh apa-apa sebab • Unit didalam kilovoltampere (kVA)
  • 7. Julai02 ITiDi 7 KUASA REAKTIF • Kuasa Reaktif / Kuasa Regangan atau Useless power ialah kuasa yang tidak dapat digunakan sebagai kuasa keluaran • Disebut juga sebagai Magnetising Power sebab ia digunakan untuk mengujudkan dan mengekalkan medan magnet (gelong) • Arus mengekori voltan • Unit dalam kVAr
  • 8. Julai02 ITiDi 8 RAJAH TIGA SEGI KUASA • Apabila sudut fasa kecil faktur kuasa tinggi • Apabila faktur kuasa rendah nilai kVA dan kVAr akan menjadi lebih besar tetapi nilai kW tetap sama • Apabila sudut fasa kosong, faktur kuasa bersamaan satu (kos 0º = 1), oleh itu nilai kW sama dengan nilai kVA • Apabila nilai kVAr dikecilkan, faktur kuasa menjadi tinggi
  • 10. Julai02 ITiDi 10 PERSAMAAN KUASA I kVA² = kW² + kVAr²
  • 11. Julai02 ITiDi 11 PERSAMAAN KUASA II PkW = √3 x VL x IL x P.F
  • 16. Julai02 ITiDi 16 RUMUSAN RAJAH VEKTOR • Apabila sudut fasa kecil f.k adalah tinggi • Apabila sudut fasa besar (f.k rendah) kVA dan kVAr menjadi besar tetapi kW tetap sama • Apabila sudut fasa kosong, f.k bersamaan 1 dan kW sama dengan kVA • Apabila nilai kVAr kecil f.k adalah tinggi
  • 17. Julai02 ITiDi 17 FAKTUR KUASA • Ialah nisbah diantara Kuasa Sebenar dengan Kuasa Samar atau kos  (sudut fasa) Kuasa Sebenar (kW) Faktur Kuasa = ------------------------- Kuasa Samar (kVA)
  • 18. Julai02 ITiDi 18 MAKNA F.K RENDAH • Tidak cekap menggunakan kuasa • Pembaziran kuasa kepada yang tidak produktif • Arus akan menjadi lebih tinggi dari yang sewajarnya • Pihak penjanaan (TNB) akan terpaksa menjana lebih kVA, oleh itu kos menjadi tinggi
  • 19. Julai02 ITiDi 19 KESAN F.K RENDAH • Memerlukan saiz kabel yang lebih besar • Susut voltan berlebihan • Penggunaan alatubah tidak optimum • Kehilangan I²R (haba) yang tinggi • Peralatan elektrik seperti alatubah, motor, alternator cepat menjadi panas dari yang sepatutnya
  • 20. Julai02 ITiDi 20 KESAN LAIN F.K RENDAH • Didenda oleh pihak TNB atau Pemegang Lesen jika faktur kuasa purata bulanan kurang dari 0.85 • Alatubah tidak dapat menghasilkan lebih watt untuk disalurkan kepada beban-beban atau pengguna-pengguna yang lain
  • 21. Julai02 ITiDi 21 PENYEBAB FAKTUR KUASA RENDAH 1. Induction Motor 2. Alatubah 3. Cok/Ballast/Magnetic coil 4. Pengimpal (welding set) 5. Induction Furnace
  • 22. Julai02 ITiDi 22 PENGIRAAN ARUS • Kira arus sebuah motor 40 HP pada: • a. Faktur kuasa 0.9 • b. Faktur kuasa 0.6 • Apakah perbezaan dari segi nilai arus tersebut
  • 23. Julai02 ITiDi 23 MOTOR 40 H.P, 415V PADA PELBAGAI F.KUASA Faktur Kuasa Arus (A) 1.0 41.51 0.95 43.68 0.90 46.11 0.85 48.82 0.80 51.87 0.75 55.33 0.70 59.28 0.65 63.85 0.60 69.17 0.55 75.45 0.50 83.00
  • 24. Julai02 ITiDi 24 JANAKUASA 500kW, 415V PADA PELBAGAI F.KUASA F.K Arus (A) kVA Pertambahan kVA Pertambahan Arus 1.0 696 500 0 0 0.9 773 556 77 56 0.8 870 625 174 125 0.7 994 714 298 214 0.6 1159 833 463 333 0.5 1391 1000 695 500
  • 25. Julai02 ITiDi 25 KADAR DENDA • 1.5% dari jumlah bil bulanan jika faktur kuasa dari 0.75 hingga 0.84 bagi setiap 0.01 yang kurang • 3% dari jumlah bil bulanan jika faktur kuasa kurang dari 0.75 bagi setiap 0.01 yang kurang dan dicampur dengan jumlah yang diatas tadi
  • 26. Julai02 ITiDi 26 CONTOH • MD = 100kW • kWh = 65,000 unit • kVArh = 85,000 unit • Bil bulanan = RM18,500 Kira denda dikenakan jika faktur kuasa = 0.61 Kiraan • (0.85 - 0.75) ÷ 0.01 = 10 x 1.5% = 15% • (0.75 - 0.61) ÷ 0.01 = 14 x 3% = 42% • Jumlah = (15%+42%) x RM18,500 = RM10,545.00
  • 27. Julai02 ITiDi 27 BACAAN BULANAN • Meter kilowatt-hour (kWh) • Meter kVArh • Meter faktur kuasa yang terdapat pada papan suis utama adalah memberi bacaan ketika (instantaneous value) dan bukan bacaan purata bulanan
  • 28. Julai02 ITiDi 28 PENGUKURAN DITAPAK Jika boleh hendaklah dibuat semasa operasi berada ditahap maksima. Bacaan faktur kuasa yang kerap adalah perlu. Katalah bacaan faktur kuasa yang diperolehi = 0.5 Purata bacaan voltan = 420V Purata arus talian = 700A Kuasa digunakan = 3 x 420V x700A x 0.5 = 256kW Jika faktur kuasa dibaiki kepada 0.95 kVAr = 256kW (tan 1 – tan 2) = 256 (1.73 – 0.329) = 359 kVAr
  • 29. Julai02 ITiDi 29 BACAAN BULANAN Bulan kWh kVArh Januari 921 546 Februari 1230 742
  • 30. Julai02 ITiDi 30 PENGIRAAN F.KUASA • kWh digunakan = 1230  921 = 309 kWh • kVArh  = 742  546 = 196 kVArh • Tan  = 196 / 309 = 0.63 • Inverse tan 0.63 = 32.3° • Kos 32.3° = 0.84 • Faktur kuasa = 0.84
  • 31. Julai02 ITiDi 31 CARA LAIN F.K = kWh = 309 .  (kWh² + kVArh²)  (309² + 196²) = 309 .  (95481 + 38416) = 0.84
  • 32. Julai02 ITiDi 32 MEMBAIKI FAKTUR KUASA • Menggunakan kapasitor • Menggunakan motor segerak (synchronous motor)
  • 33. Julai02 ITiDi 33 KAPASITOR • Arus mendulu voltan • Harga murah • Senggaraan murah dan mudah (hampir tanpa senggaraan – maintenance free) • Terdapat berbagai-bagai saiz dari kecil hinggalah besar • Boleh dipercayai
  • 35. Julai02 ITiDi 35 MOTOR SEGERAK • Harganya mahal & senggaraan juga mahal • Bersaiz besar • Kelajuan tetap (bergantung kepada ulangan) • Stator dibekalkan dengan bekalan AC • Rotor dibekalkan dengan bekalan DC • Boleh berfungsi dari lagging power factor ke unity dan ke leading power factor dengan melaras arus ujaan ke rotor • Sesuai digunakan sebagai tugas sampingan
  • 36. Julai02 ITiDi 36 PEMBAIKAN TUNGGAL • Bermakna pembaikan faktur kuasa pada sesuatu alat/mesen seperti motor elektrik • Jika terlalu banyak motor dengan berbagai- bagai saiz maka cara ini adalah tidak praktikal sebab kerja senggaraan menjadi terlalu banyak • Faktur kuasa berubah-ubah sepanjang hari oleh itu cara ini kurang sesuai
  • 38. Julai02 ITiDi 38 MOTOR DENGAN P.F KAPASITOR SAMBUNGAN TETAP
  • 39. Julai02 ITiDi 39 PERTIMBANGAN AM • Ujaan auto iaitu ujaan diri motor oleh cas kapasitor yang tersimpan semasa ketiadaan bekalan hendaklah dielakkan • Pastikan arus kapasitor adalah sama atau lebih kecil dari arus kemagnetan motor, biasanya 90% dari arus tanpa beban motor
  • 40. Julai02 ITiDi 40 SAIZ KAPASITOR MOTOR • kW motor x Beban Penuh x (tan 1– tan 2) • kVAr = ------------------------------------------------------ • Kecekapan Motor (pada beban penuh) • 1 - faktur kuasa asal • 2 - faktur kuasa diperbaiki
  • 41. Julai02 ITiDi 41 PEMBAIKAN CARA PUSAT • Apabila faktur kuasa berubah-ubah sepanjang hari dan beban induktif kecil terlalu banyak dimana cara pembaikan tunggal adalah tidak ekonomik dan tidak praktikal • Tidak mempunyai ruang yang mencukupi untuk menempatkan terlalu banyak kapasitor • Operasi kapasitor bank dikendalikan secara otomatik mengikut perubahan beban
  • 42. Julai02 ITiDi 42 PEMBAIKAN KUMPULAN & PEMBAIKAN PUSAT TETAP • Satu kapasitor bank untuk sekumpulan motor atau apa-apa beban lain • Pembaikan individu secara tetap asasnya sama dengan pembaikan cara pusat tetapi ia tidak mempunyai regulator faktur kuasa iaitu ia tidak dikawal secara otomatik
  • 43. Julai02 ITiDi 43 PEMBAIKAN TERGABUNG Pembaikan tergabung adalah campuran pembaikan tetap, otomatik, kumpulan dan tunggal
  • 44. Julai02 ITiDi 44 SAIZ KAPASITOR BANK • kVAr = PkW (tan1 – tan 2) = PkW x k • kVAr - Kadaran kapasitor bank • PkW - MD pemasangan dalam kW • tan 1 - Faktur kuasa asal • tan 2 - Faktur kuasa diperbaiki • k - tan1 – tan 2
  • 45. Julai02 ITiDi 45 NILAI K • tan 1 – tan 2 • Gunakan Nomogram • Gunakan Jadual Faktur K
  • 48. Julai02 ITiDi 48 CONTOH 1 • Beban MD = 200kW • Faktur kuasa asal = 0.74 • Faktur kuasa diperbaiki = 0.9 • Faktur k = 0.42 (dari jadual) • Saiz kapasitor bank = 200 x 0.42 = 84kVAr
  • 49. Julai02 ITiDi 49 CONTOH 2 • Sebuah pemasangan menggunakan 49,470 kWh tenaga. F.K bulan Jun ialah 0.59. pemasangan digunakan 9 jam sehari, 25 hari sebulan. Kira saiz kapasitor bank yang diperlukan untuk memperbaiki F.K kepada 0.95. • Jumlah jam kerja = 9 x 25 = 225jam • Beban permintaan = 49,470/225 = 200 kW • kVAr diperlukan= kW (tan θ1 – tan θ2) • = 200 (1.386 – 0.329) • = 229 kVAr
  • 50. Julai02 ITiDi 50 PENENTUAN BILANGAN STEP • Tidak ada satu formula khusus untuk menentukan bilangan step sesuatu kapasitor bank • Ia mengikut kesesuaian beban pemasangan dan hendaklah praktikal, jika satu step terlalu besar ia akan mengakibatkan over correction
  • 51. Julai02 ITiDi 51 MENENTUKAN KADARAN kVAr SETIAP STEP • Setiap step boleh mempunyai kadaran kVAr yang sama atau boleh juga tidak sama • Ia berpandukan saiz-saiz beban induktif yang terpasang • Jika semasa minimum load bebannya tersangat rendah dan terdapat pula motor bersaiz besar, maka lazimnya kVAr setiap step tidak sama
  • 52. Julai02 ITiDi 52 POWER FACTOR REGULATOR • Satu device elektronik untuk mengawal secara otomatik jumlah kVAr yang perlu dimasukkan kepada atau dikeluarkan daripada litar pada satu-satu masa • Ia mengesan perbedaan sudut fasa diantara voltan dan arus dan menambah atau mengurangkan kVAr dalam litar mengikut setting yang telah ditentukan
  • 54. Julai02 ITiDi 54 C/K SETTING • Nilai C/K menentukan pada tahap arus reaktif yang mana regulator mula bertindak • Tatahan C/K adalah mengikut step kapasitor yang paling kecil, selalunya yang pertama • Diperolehi dengan membahagi kVAr dengan K, dimana K nisbah alatubah arus
  • 55. Julai02 ITiDi 55 CONTOH • Step terkecil = 150 kVAr • Nisbah c.t = 1000/5A • Oleh itu K = 1000  5 = 200 • C/K = 150  200 = 0.75 • Kebiasaannya regulator di set agar bertindak pada kadar 2/3 daripada arus satu langkah
  • 56. Julai02 ITiDi 56 TARGET P.F SETTING • P.F Regulator memerlukan kita menentukan target P.F setting • Selalunya kita set pada kedudukan yang melebehi 0.85, contohnya pada 0.9
  • 57. Julai02 ITiDi 57 AUTO/MANUAL BUTTON • Dalam keadaan normal P.F Regulator hendaklah di set pada kedudukan Auto • Apabila ujian manual diperlukan tukar kedudukan pada manual dan tekan butang plus (+) dan butang minus ( – ) untuk mengurang dan menambah kapasitor kepada sistem pemasangan tanpa mengira beban elektrik pada masa tersebut
  • 58. Julai02 ITiDi 58 PENUNJUK LED • Penunjuk LED akan menyala mengikut bilangan step yang aktif (energised to the circuit). Ini adalah penunjuk sahaja, tidak mesti step tersebut berfungsi sekiranya fius/MCB, kabel, kontaktor atau kapasitor mengalami masaalah
  • 61. Julai02 ITiDi 61 PROGRAMME MODE 1:1:1:1:1 10:10:10:10:10 KVAR 1:2:2:2:2 10:20:20:20:20 KVAR 1:2:4:4:4 10:20:40:40:40 KVAR 1:2:2:4:4 10:20:20:40:40 KVAR 1:2:4:4:8 10:20:40:40:80 KVAR 1:2:4:8:8 10:20:40:80:80 KVAR
  • 62. Julai02 ITiDi 62 KOMPONEN-KOMPENEN YANG DIPERLUKAN 1. Alatubah arus, satu sahaja diperlukan (RED) 2. Fius atau MCB 3. Power factor regulator 4. Bekalan dari dua fasa (Yellow, Blue) 5. Kontaktor 6. Kabel 7. Kapasitor bank
  • 63. Julai02 ITiDi 63 KADARAN KOMPONEN 1. Fius/MCB : 1.5 x Arus kapasitor 2. Kontaktor : 1.6 ke 2.0 x Arus kapasitor 3. Kabel : 1.7 x Arus kapasitor
  • 64. Julai02 ITiDi 64 KRITERIA DIPERLUKAN 1. Arus transient semasa pensuisan 2. Voltan transient apabila kapasitor diputuskan semasa pensuisan dilakukan yang menyebabkan berlakunya arka 3. Berupaya membawa beban penuh 4. Berupaya membawa peningkatan arus kapasitor dalam keadaan tertentu
  • 66. Julai02 ITiDi 66 SENGGARAAN KAPASITOR BANK 1. Periksa fius/MCB yang melindungi kapasitor bank 2. Power factor regulator mungkin tidak berfungsi 3. Sambungan-sambungan mungkin longgar 4. Kapasitor boleh rosak, terbakar atau meletup 5. Terlalu banyak habok atau kotoran menyebabkan flashover 6. Pengudaraan tersekat menyebabkan panas
  • 67. Julai02 ITiDi 67 KESAN HARMONIK • Harmonik yang tinggi dan banyak menyebabkan galangan kapasitor menjadi rendah, oleh itu kapasitor mengalami keadaan hampir-hampir litar pintas • Kapasitor akan menjadi terlalu panas dan kadang-kadang meletup