2. WHAT IS TOTAL AIR FLOW?
TOTALAIR flow is sum of total FD fan air
flow and PA fan air flow fed to boiler.
9/27/2023 9:43:14 AM
3. AIR FLOW MESUREMENT
PRIMARY SENSING ELEMENT USED
AIRFOILIS USEDASAPRIMARY SENSING
ELEMENT TO CREATE DPACROSS THE FD AIR
FLOW & PA AIR FLOW.
DP TYPE SMART TX.ARE USED TO MEASURE THE
FLOW.
FLOW RANGE FOR
PAAIR FLOW TX. 0 – 100000 M3/hr
FDAIR FLOW TX. 0 – 600000 M3/hr
9/27/2023 9:43:14 AM
4. TX. USED FOR AIR FLOW
MEASUREMENT
PAAIR FLOW
10HLA40CF051,052 – AT MILL A
10HLA40CF053,054 – AT MILL B
10HLA40CF055,056 – AT MILL C
10HLA40CF057,058 – AT MILL D
FD AIR FLOW
10 HLA50CF051,052,053 – AT AIR BOX ‘A’ INLET
10 HLA50CF054,055,056 – AT AIR BOX ‘B’ INLET
9/27/2023 9:43:14 AM
7. TOTAL PA AIR FLOW
CALCULATIONS
TEMP. COMPENSATION & PRESSURE
COMPENSATION TECHNIQUES ARE USED
TO MEASURE THE PAAIR FLOW.
SQUARE ROOT FUNCTIONAL BLOCK IS
USED TO CALCULATE AIR FLOW IN DCS.
AVERAGE OF THE TWO TX. IS TAKEN TO
CALACULATE THE PA AIR FLOW AT EACH
MILL.
SUM OF ALL FOUR MILL INLET PA AIR
FLOW IS TOTAL PA AIR FLOW.
9/27/2023 9:43:14 AM
10. FD AIR FLOW MEASURING
POINT
9/27/2023 9:43:14 AM
11. TOTAL FD AIR FLOW
CALCULATIONS
TEMP. COMPENSATION & PRESSURE
COMPENSATION TECHNIQUES ARE
USED TO MEASURE THE FD AIR FLOW.
SQUARE ROOT FUNCTIONAL BLOCK IS
USED TO CALCULATE AIR FLOW IN
DCS.
AVERAGE OF THE THREE TX. IS
TAKEN TO CALACULATE THE FD AIR
FLOW.
9/27/2023 9:43:14 AM
14. TOTALAIR FLOW CALCULATION
TOTAL AIR FLOW =
TOTAL PA AIR FLOW +
[ FD AIR FLOW AT AIR BOX ‘A’ INLET
+ FD AIR FLOW AT AIR BOX ‘B’ INLET ]
9/27/2023 9:43:14 AM
17. O₂ CORRECTION & GENERATION OF
AIR DEMAND.
9/27/2023 9:43:14 AM
UNIT LOAD DMD
O₂ A
O₂ B
AIR FLOW DMD
STEAM PRESSURE
200
F (X)
LOAD VS O₂ COMPARE
AVG O₂
PID O₂ correction
(-200 TO 400)
F (X)
LOAD VS
TOTALAIR
HI SELECT
BLOCK
ADD
21. HOW TO CONTROL PA AIR?
9/27/2023 9:43:14 AM
UNIT LOAD DMD
2.75
PA DICHARGE PR.(PV)
IGV A IGV B
F (X)
LOAD VS PA
PID
BALANCE 2
HI SELECT
BLOCK
ESMA ESMA