Understanding and Simulating the IEC 61850 Standard
Article · May 2008
Source: OAI
CITATIONS
36
READS
5,196
2 authors, including:
Some of the authors of this publication are also working on these related projects:
SIFT PROJECT View project
Trustworthy Infrastructure for the Power Grid (TCIP) Information Trust Institute Illinois View project
Roy Campbell
University of Illinois, Urbana-Champaign
606 PUBLICATIONS   14,465 CITATIONS   
SEE PROFILE
All content following this page was uploaded by Roy Campbell on 11 November 2015.
The user has requested enhancement of the downloaded file.
Understanding and Simulating the IEC 61850 Standard ∗
Yingyi Liang Roy H. Campbell
Department of Computer Science
University of Illinois at Urbana-Champaign
Urbana, IL 61801
{yliang6, rhc}@uiuc.edu
Abstract
The recent international standard IEC 61850 proposes a
unified solution of the communication aspect of substa-
tion automation. However, the standard itself is not eas-
ily understood by users other than domain experts. We
present our understanding of the IEC 61850 standard as
well as the design and implementation of our simulation
tool in this report. Also, we give suggestions on the im-
plementation of this standard based on our experience
and lessons in the development of our simulation.
1 Introduction
Today, power substations are mostly managed by substa-
tion automation systems. These systems employ com-
puters and domain specific applications to optimize the
management of substation equipment and to enhance op-
eration and maintenance efficiencies with minimal hu-
man intervention [8].
Once upon a time, substation automation systems
utilized simple, straightforward and highly specialized
communication protocols [7]. These protocols con-
cerned less about the semantics of the exchanged data,
data types of which were relatively primitive. Equipment
was dumb and systems were simple. However, today’s
substation automation systems can no longer enjoy such
simplicity because of their growing complexity — equip-
ment becomes more intelligent and most of those simple
old systems have been gradually replaced by open sys-
tems, which embrace the advantage of emerging tech-
nology like relational database systems, multi-task oper-
ating systems and support for state-of-the-art graphical
display technology.
Besides, devices from different manufacturers used
different substation automation protocols [9, 3, 12], dis-
abling them to talk to each other. Utilities have been pay-
ing enormous money and time to configure these devices
∗This work was funded by NSF CNS 03-05537.
to work together in a single substation. Today most util-
ities and device manufacturers have recognized the need
for a unified international standard to support seamless
cooperation among products from different vendors.
The IEC 61850 international standard, drafted by sub-
station automation domain experts from 22 countries,
seeks to tackle the aforementioned situation. This stan-
dard takes advantage of a comprehensive object-oriented
data model and the Ethernet technology, bringing in great
reduction of the configuration and maintenance cost. Un-
like its predecessor, the Utility Communication Architec-
ture protocol 2.0 (UCA 2.0) [12], the IEC 61850 standard
is designed to be capable for domains besides substation
automation. To make the new protocol less domain de-
pendent, the standard committee endeavored to empha-
size on the data semantics, carving out most of the com-
munication details. This effort, however, could result in
difficulties in understanding the standard.
In this research project, we aim to get a clear under-
standing of the IEC 61850 standard and simulate the pro-
tocol based on J-Sim [11]. Our ultimate goal is to inves-
tigate the security aspect about the IEC 61850 standard.
2 The IEC 61850 standard
The first release of the IEC 61850 consists of a set of
documents of over 1,400 pages. These documents are di-
vided into 10 parts, as listed in Table 1. Part 1 to Part
3 give some general ideas about the standard. Part 4 de-
fines the project and management requirements in an IEC
61850 enabled substation. Part 5 specifies the required
parameters for physical implementation. Part 6 defines
an XML based language for IED configuration, present-
ing a formal view of the concepts in the standard. Part
7 elaborates on the logical concepts, which is further di-
vided into four subparts (listed in Table 2). Part 8 talks
about how to map the internal objects to the presenta-
tion layer and to the Ethernet link layer. Part 9 defines
the mapping from sampled measurement value (SMV)
to point-to-point Ethernet. The last part gives instruc-
tions on conformance testing. Since Part 7 defines the
core concepts of the IEC 61850 standard, we will focus
on this part in this report.
Subpart Title
7-1 Principles and Models
7-2 Abstract Communication Service Interface
7-3 Common Data Classes
7-4 Compatible Logical Node Classes and Data
Classes
Table 2: Subparts of IEC 61850-7
The IEC 61850 standard is not easy to understand for
people other than experts in the substation automation
domain due to the complexity of the documents and the
assumed domain-specific knowledge. Introductory doc-
uments on the standard abound [13, 4, 7, 5, 8, 2], but
most of them are in the view of substation automation do-
main experts. Kostic et al. explained the difficulties they
had in understanding the IEC 61850 standard [7]. In this
section, we provide another experience of understanding
this standard, trying to explain the major concepts of the
IEC 61850 standard.
2.1 Challenges
Understanding the IEC 61850 standard proposes the fol-
lowing challenges for a outsider of the substation au-
tomation domain:
1. As a substation automation standard proposed by a
group of domain experts, the IEC 61850 protocol
assumes quite an amount of domain-specific knowl-
edge, which is hardly accessible by engineers and
researchers out of the substation automation do-
main. To make things worse, the terms used in
the standard is to some extent different from those
commonly used in software engineering, bringing
some difficulties for software engineers in reading
the standard.
2. The entire standard, except Part 6, is described in
natural language with tables and pictures, which is
known to be ambiguous and lack of preciseness.
This situation is problematic because the IEC 61850
concepts are defined by more than 150 mutually rel-
evant tables distributed over more than 1,000 pages.
A formal presentation of all these concepts would
be appreciated.
3. The experts proposing this protocol come from 22
different countries and are divided into 10 working
groups, each responsible to one part of the stan-
dard. Due to the different backgrounds and the in-
formal presentation style of the standard, the stan-
dard contains a considerable number of inconsis-
tencies. Such inconsistencies are more obvious for
different parts of the standard, e.g. the data model
described in Part 6 is clearly different from that de-
scribed in Part 7.
4. The standard committee made a great effort to de-
scribe the protocol in an object-oriented manner but
the result is not so object-oriented. For example,
the ACSI services are grouped by different classes,
but reference to the callee object is not defined as a
mandatory argument of the service function.
5. The standard is designed to be implementation in-
dependent but this is not always true. For exam-
ple, the data attribute TimeAccuracy in Part 7-2
Table 8 is defined as CODED ENUM, while what it
virtually represents is a 5-bit unsigned integer; the
frequent use of PACKED LIST (i.e. “bit fields” in
the C language) also brings implementation details
to interface design.
6. Things are mixed up in the documents. Mandatory
components and optional components are mixed in
the standard, and domain independent concepts are
mixed up with domain specific concepts. Even
though the optional components and mandatory
ones are marked with “O” and “M” alternatively, it
would be a tough task to refine a model consisting
only the mandatory components due to the implicit
dependences between attributes in different tables
and the conditional inclusion of some attributes. In
fact, there are 29 common data classes and 89 com-
patible logical nodes defined in the standard, the re-
lationship among which is unclear.
2.2 Intelligent electronic device
In the past, utility communication standards usually as-
sumed some domain-specific background of the readers.
Consequently, they contained a lot of implicit domain
knowledge, which is hardly accessible to outsiders (e.g.
software engineers) [7]. The IEC 61850 standard does
not escape from this category. To help understanding the
logical concepts of IEC 61850, we would like to lay a
basic idea of intelligent electronic devices (IED), the es-
sential physical object hosting all the logical objects.
Basically, the term intelligent electronic device refers
to microprocessor-based controllers of power system
equipment, which is capable to receive or send data/con-
trol from or to an external source [8]. An IED is usu-
ally equipped with one or more microprocessors, mem-
2
Part Title
1 Introduction and Overview
2 Glossary
3 General Requirements
4 System and Project Management
5 Communication Requirements for Functions and Device Models
6 Configuration Description Language for Communication in Electronic Substations Related to IEDs
7 Basic Communication Structure for Substation and Feeder Equipment
8 Specific Communication Service Mapping (to MMS and to Ethernet)
9 Specific Communication Service Mapping (from Sampled Values)
10 Conformance Testing
Table 1: Parts of the IEC 61850 standard documents
ory, possibly a hard disk and a collection of communi-
cation interfaces (e.g. USB ports, serial ports, Ethernet
interfaces), which implies that it is essentially a computer
as those for everyday use. However, IEDs may contain
some specific digital logics for domain-specific process-
ing.
IEDs can be classified by their functions. Common
types of IEDs include relay devices, circuit breaker con-
trollers, recloser controllers, voltage regulators etc.. It
should be noted that one IED can perform more than one
functions, taking advantage of its general-purpose micro-
processors. An IED may have an operating system like
Linux running in it.
2.3 Substation architecture
A typical substation architecture is shown in Figure 1.
The substation network is connected to the outside wide
area network via a secure gateway. Outside remote op-
erators and control centers can use the abstract commu-
nication service interface (ACSI) defined in Part 7-2 to
query and control devices in the substation. There is one
or more substation buses connecting all the IEDs inside
a substation. A substation bus is realized as a medium
bandwidth Ethernet network, which carries all ACSI re-
quests/responses and generic substation events messages
(GSE, including GOOSE and GSSE). There is another
kind of bus called process bus for communication inside
each bay. A process bus connects the IEDs to the tradi-
tional dumb devices (merge units, etc.) and is realized as
a high bandwidth Ethernet network. A substation usually
has only one global substation bus but multiple process
buses, one for each bay.
ACSI requests/responses, GSE messges and sampled
analog values are the three major kinds of data active in
the substation network. Since we are less interested in
communication on the process buses (like sampled value
multicasting), we focus on the activities on the substation
bus in this report, especially the ACSI activities.
Figure 1: Substation architecture
Interactions inside a substation automation system
mainly fall into three categories: data gathering/setting,
data monitoring/reporting and event logging. The former
two kinds of interactions are the most important — in the
IEC 61850 standard all inquiries and control activities to-
wards physical devices are modeled as getting or setting
the values of the correspondingdata attributes, while data
monitoring/reporting provides an efficient way to track
the system status, so that control commands can be is-
sued in a timely manner.
To realize the above kinds of interaction, the IEC
61850 standard defines a relatively complicated com-
munication structure, as is shown in Figure 2. Five
kinds of communication profiles are defined in the stan-
dard: the abstract communication service interface pro-
file (ACSI), the generic object oriented substation event
profile (GOOSE), the generic substation status event pro-
file (GSSE), the sampled measured value multicast pro-
file (SMV), and the time synchronization profile. ACSI
services enable client-server style interaction between
applications and servers. GOOSE provides a fast way
of data exchange on the substation bus and GSSE pro-
vides an express way of substation level status exchange.
Sample measured value multicast provides an effective
way to exchange data on a process bus.
3
Ethernet Link Layer
SMV GOOSE GSSE TimeSync ACSI
IP
UDP TCP
MMS
GSSE
T-Profile
Specific Communication Service Mapping (SCSM)
Application
Domain
Communication
Stack
Figure 2: The communication profiles
2.4 Abstract communication service inter-
face
ACSI is the primary interface in the IEC 61850 standard
not only because it is the interface via which applications
talk with servers, but also in the sense that the ACSI com-
munication channel is an important part of a logical con-
nection between two logical nodes. ACSI defines the se-
mantics of the data exchanged between applications and
servers, thus it becomes the major part of the IEC 61850
standard.
The standard committee adopt an object-oriented ap-
proach in the design of ACSI, which includes a hierar-
chical and comprehensive data model and a set of avail-
able services for each class in this data model. Al-
though the data model is usually described outside the
scope of the ACSI, it is actually part of it. The ben-
efits of using an object-oriented utility communication
interface are two fold. On the one hand, objects (e.g.
registers) can be referenced in an intuitive way (e.g.
“Relay0/MMXU0.voltage”) instead of by the tradi-
tional physical address (like Reg#02432). On the other
hand, software engineers can build more reliable appli-
cations using such service interface.
In the following two sections, we present a brief de-
scription on these two ACSI components.
2.5 Data model
The hierarchical data model defined in the IEC 61850 is
depicted in Figure 3 and Figure 4.
Server is the topmost component in this hierarchy. It
serves as the joint point of physical devices and logical
objects. Theoretically one IED may host one or more
server instances, but in practice usually only one server
instance runs in an IED. A server instance is basically a
program running in an IED, which shares the same mean-
ing with other servers like FTP server etc.. Each server
has one or more access points, which are the logical rep-
resentation of a NIC. When a client is to access data or
service of the server, it should connect to an access point
of this server and establish a valid association.
Each server hosts several files or logical devices.
Clients can manipulate files in the server like talking to
a FTP server, which is usually used as a means to up-
load/update the configuration file of an IED. A logical
device is the logical correspondence of a physical device.
It is basically a group of logical nodes performing similar
functions.
Functions supported by an IED are conceptually rep-
resented by a collection of primitive, atomic functional
building blocks called logical nodes. The IEC 61850
standard predefines a collection of template logical nodes
(i.e. compatible logical nodes) in Part 7-4. Besides
the regular logical nodes for functions, the standard also
requires every logical device have two specific logical
nodes: Logical Node Zero (LN0) and LPHD, which cor-
respond to the logical device and the physical device,
alternatively. Besides holding status information of the
logical device, LN0 also provides additional functions
like setting-group control, GSE control, sampled value
control etc.. In the IEC 61850 standard, the entire sub-
station system is modeled as a distributed system con-
sisting of a collection of interacting logical nodes, which
are logically connected by logical connections. It should
be noted that the term logical connection refers to the
logical concept of the connections between two logical
nodes, which can be direct or indirect or even a combina-
tion of many different kinds of communication channels.
In fact, the connection of two logical nodes is usually
both indirect and a combination of TCP, UDP and direct
Ethernet connections. We will explain logical connec-
tions in Section 2.9.
Data exchanged between logical nodes are modeled
as data objects. A logical node usually contains sev-
eral data objects. Each data object is an instance of the
DATA class and has a common data class type. Similar to
the concept of objects in most object-oriented program-
ming languages, a data object consists of many data at-
tributes, which are instances of data attributes of the cor-
responding common data class. Data attributes are typed
and restricted by some functional constraints. Instead of
grouping data attributes by data objects, functional con-
straints provide a way to organize all the data attributes in
a logical node by functions. Types of data attributes can
be either basic or composite. Basic types are primitive
types in many programming languages, whereas com-
posite types are composition of a collection of primitive
types or composite types.
In the IEC 61850 standard, data attributes are at least
as important as, if not more than, data objects for two
4
SERVER
LOGICAL-DEVICE
LOGICAL-DEVICE
...
LOGICAL-DEVICE
LOGICAL-NODE
LOGICAL-NODE
...
LOGICAL-NODE
DATA OBJECT
DATA OBJECT
...
DATA OBJECT
DATA ATTRIBUTE
DATA ATTRIBUTE
...
Figure 3: Hierarchy of the IEC 61850 data model
reasons. Firstly, data objects are just logical collections
of the contained data attributes while (primitive) data at-
tributes are the de facto logical correspondence to the
physical entities (memory units, registers, communica-
tion ports, etc.); secondly, the purpose of data objects is
for the convenience of managing and exchanging values
of a group of data attributes sharing the same function.
Despite data objects, the IEC 61850 standard provides
the concept of data set as another ways to manage and
exchange a group of data attributes. Members of a data
set can be data objects or data attributes. The concept of
data set is somewhat similar to the concept of view in the
area of database management systems. In the IEC 61850
standard, most services involve data sets. Members in a
data set unnecessarily come from the same logical node
or the same data object, thus providing high flexibility
of data management. Data sets are categorized into per-
manent ones and temporary ones. Permanent data sets
are hosted by logical nodes and will not be automatically
deleted unless on the owners’ explicit requests; tempo-
rary data sets are exclusively hosted by the association
having created them and will be automatically deleted
when the association ends.
2.6 Service model
Services provided by ACSI include querying object set,
getting/setting data values, controlling system objects,
report manipulation, log manipulation, and other ser-
vices like file upload/download. Table 3 gives a list of
ACSI services defined in the IEC 61850 standard.
All ACSI services are requested by applications and
responded by servers. In order to request a service in
a server, an application must first establish a valid two-
party application association (TPAA) with the server.
The TPAA maintains the session states and provides a
virtual view of the server to the application. A typical
interaction procedure between an application A and a
server S goes as follows:
1. A establishes a TCP connection with S;
2. A “logs in” to S by requesting the Associate ser-
vice from S, providing authentication related infor-
mation as parameters;
LOGICAL NODECompatible Logical Node
LOGICAL DEVICE
SERVER
DATACommon Data Class
FCDA
1
1..n
1
1..n
1
1..n
1
1..n
1
0..n
TrgOp
Functional Constraint
DAType
1
0..2
11
1
1
1
1..n
BasicType
1*
Figure 4: The data model of the IEC 61850
3. S validates the information provided by A and cre-
ates a TPAA object, which provides a virtual view
of S to A;
4. A requests subsequent services while S processes
the requests and responses with appropriate re-
sponses defined in the IEC 61850 standard;
5. A issues a Release request to S;
6. S reclaims the TPAA of A and ends the session.
The virtual view of server provided by a TPAA en-
forces the access control policies set forth by the server.
This virtual view defines which objects in the server are
visible and accessible to the application and what kinds
of service of those objects are accessible from the appli-
cation. The concept of virtual view is very flexible and
5
SERVER: LOG-CONTROL-BLOCK:
GetServerDirectory GetLCBValues
ASSOCIATION: SetLCBValues
Associate QueryLogByTime
Abort QueryLogAfter
Release GetLogStatusValues
LOGICAL-DEVICE: GOOSE:
GetLogicalDeviceDirectory SendGOOSEMessage
LOGICAL-NODE: GetGoReference
GetLogicalNodeDirectory GetGOOSEElementNumber
GetAllDataValues GetGoCBValues
DATA: SetGoCBValues
GetDataValues GSSE:
SetDataValues SendGSSEMessage
GetDataDirectory GetGsReference
GetDataDefinition GetGSSEDataOffset
DATA-SET: GetGsCBValues
GetDataSetValues SetGsCBValues
SetDataSetValues MULTICAST-SAMPLE-VALUE-CONTROL-BLOCK:
CreateDataSet SendMSVMessage
DeleteDataSet GetMSVCBValues
GetDataSetDirectory SetMSVCBValues
Substitution: UNICAST-SAMPLE-VALUE-CONTROL-BLOCK:
SetDataValues SendUSVMessage
GetDataValues GetUSVCBValues
SETTING-GROUP-CONTROL-BLOCK: SetUSVCBValues
SelectActiveSG Control:
SelectEditSG Select
SetSGValues SelectWithValue
ConfirmEditSGValues Cancel
GetSGValues Operate
GetSGCBValues CommandTermination
BUFFERED-REPORT-CONTROL-BLOCK: TimeActivatedOperate
Report Time synchronization:
GetBRCBValues TimeSynchronization
SetBRCBValues FILE transfer:
UNBUFFERED-REPORT-CONTROL-BLOCK: GetFile
Report SetFile
GetURCBValues DeleteFile
SetURCBValues GetFileAttributeValues
Table 3: ACSI services
the IEC 61850 standard does not place any restriction on
the access control policies of the server. One possible
and relatively simple access control is the world-group-
owner access control for files used in many UNIX sys-
tems.
The ACSI interface defines an object-oriented inter-
face for the applications but it does not require the inter-
nal implementation to be object-oriented. In actual fact,
according to our experience on simulating the IEC 61850
protocol, object-oriented approach might not be a wise
choice for the internal implementation.
2.7 Reporting and logging
The IEC 61850 standard provides an efficient mechanism
called reporting for applications to track changes to the
subscribed system objects. Instead of polling the data
attribute values periodically, applications can group the
interesting data attributes into a data set, and require the
logical node hosting this data set report any changes to
6
the members of this data set. Theoretically a data set can
contain data objects/data attributes from different logical
nodes, but data sets for reporting usually contain only
the data objects/data attributes in the same logical node.
The procedure of report generation and transmission is
under the control of an information block called report
control block (RCB). A RCB maintains the necessary in-
formation to generate a report like which fields should
be included in the report, on what events a report should
be generated, the sequence number of the current report,
whether this RCB is enabled, etc..
A typical report generation and transmission proce-
dure is described as follows:
1. client application creates a data set containing all
the data objects and data attributes it concerns;
2. client sets the parameters in a RCB, specifies the
aforementioned data set as the source of the reports
(this step is called to “subscribe to a data set”) and
enables this RCB;
3. on any change to any member of the data set, the
logical node tests this change against the event list
of the RCB, and issues an internal event if any event
in the list gets matched;
4. on receiving the internal event, the RCB stores this
event for later sending;
5. if the condition of sending the report is satisfied, the
logical node collects necessary data, generates the
report and sends it out to the client via the associ-
ation under the direction of the parameters in the
RCB.
Reports can be sent by either two-party application as-
sociation (TPAA) or multi-party application association
(MPAA). TPAA is the association that can serve only one
client while MPAA can serve more than one client si-
multaneously. Reports generated on the request of the
Report service is sent by TPAA, whereas other reports
are sent by MPAA. Reporting uses a publisher/subscriber
mechanism: for every client, the server must assign an
individual RCB to handle the report generation and trans-
mission.
Logging is a mechanism to record the device events.
Logs are stored in the server and hosted by the corre-
sponding logical device. Unlike reporting, every time a
device event is triggered, the logical device merely saves
a log entry into the log database for later inquiries.
2.8 Generic substation event
Besides reporting, the IEC 61850 standard defines
generic substation event (GSE) as another means for ap-
plications to monitor changes to the data objects/data at-
tributes. GSE is designed for fast delivering notification
of system object changes. There are two kinds of GSE,
generic object-oriented substation events (GOOSE) and
generic substation state event (GSSE). GOOSE is used
to exchange a wide range of common data while GSSE
is used to convey state change information. The GSE
mechanism shares a lot of similarities with reporting,
with the major difference that GSE is designed for fast
information exchange inside a substation while reporting
is mainly used for sending notification from the server
side to remote control centers or browsers.
Since real-time performance is critical for GSE mes-
sages, the message format and communication stack for
GSE transmission is very different from those for report-
ing. GSE messages are transmitted in binary format,
which provides shorter message body and higher mes-
sage encoding/decoding speed. In stead of using TCP
or UDP as the underlying transport layer, GSSE uses its
specific transport layer while GOOSE messages are sent
to the Ethernet link layer directly without going through
any transport layer or network layer.
GSE also utilizes a publisher/subscriber mechanism to
transmit the messages. This mechanism is implemented
by the Ethernet multicast feature: the publisher sends the
GSE message to a specific multi-cast MAC address and
the subscribers pick up messages sent to this address, put
them into their local buffer for the local applications to
consume.
2.9 Communication network
The IEC 61850 standard defines a distributed system
consisting of interacting logical nodes, which are con-
nected by logical connections. However, in order for this
distributed system to work correctly and intelligently,
there must be some intelligent components inside this
network. It is not hard to see that applications play this
role. An interesting question is how to integrate appli-
cations into the interacting logical node network. We try
to answer this question by starting from the simple ACSI
server-application network.
Figure 5 shows such a server-application network.
Clearly, each server may serve several applications and
vice versa. The dotted lines in Figure 5 refer to the com-
munication channels for reports and GSE messages. Al-
though there are no restrictions about the relationship be-
tween report subscribers and report publishers, it is not
true for GSE messages. The design of GSE has physical
concerns. GSE messages are sent from one IED to an-
other, thus the subscribers and the publishers should not
reside in the same IED.
To make things more clear, let us transform Figure 5
into Figure 6, which shows the communication between
7
Server1
App1
Server3
Server2
App4
App5
App3
App2
Figure 5: Server-Application network
Server3
LN31
LN32
Server2
LN21
LN22
Server1
LN11
LN12
App1
App2
App4
App5
App3
Figure 6: Logical node-application network
Server3
LN31
LN32
Server2
LN21
LN22
Server1
LN11
LN12
Figure 7: Logical node network
applications and logical nodes (we hid the communica-
tion to server and logical devices). At this point, we
can clearly see that logical connections between logical
nodes are actually a mixture of several kinds of connec-
tions: when a logical node sends a message to another
logical node, it is virtually sending reports/GSE mes-
sages to the relevant applications; after necessary pro-
cessing of the reports/GSE messages, the applications is-
sue relevant requests to the other logical node, and vice
versa. Thus we can deploy the application logic to the
relevant logical nodes and get Figure 7 by abstracting
away the applications. Being aware of this abstraction is
important for both implementation and simulation of the
IEC 61850 protocol.
3 Simulating the IEC 61850
In this section, we talk about the design and implemen-
tation of a simulator of the IEC 61850 standard. Due to
the challenges listed in Section 2.1, simulating the entire
protocol is very difficult. Since the goal of our simula-
tion is to inspect possible security vulnerabilities in the
protocol, we refined the protocol to a version contain-
ing only data gathering/setting related ACSI services and
reporting services. Furthermore we simplified the data
model by abstracting various data attribute types to string
and discarding the concept of functional constraint. Cur-
rently, features of the IEC 61850 protocol supported by
our simulation model include two-party application asso-
ciation, data attribute, data object, data set, logical node,
logical device, server, ACSI services, reporting and un-
buffered report control block.
3.1 Design and implementation of the sim-
ulator
In order to inspect the IEC 61850 standard, we need a
tool to simulate the protocol. Demo software of the pro-
tocol exists [10]. However, they are mostly provided by
the IED manufacturer and are not freely available for re-
search purposes. Kostic et al. proposed an implementa-
tion of ACSI [6]. The work of Kostic et al. focuses on
implementing a set of application programming interface
for device and application development, while we would
like to build our own simulation tool for further study on
the IEC 61850, especially on network security issues.
Our simulator consists of about 3,500 lines of Java
code. Its components are divided into three major cat-
egories: the data model, internal message representation
and the service model. Figure 8 shows the architecture
of the simulator.
8
ApplicationServer
Association Service API
Object
Management
Association
Management
Remote Service API
Internal
Messaging
Reporting
Figure 8: The IEC 61850 simulator architecture
Server
LD
LN
Data DataSet URCB
DA
LD LD
LN
Data
DA DA
...
...
...
...
Figure 9: The IEC 61850 simulator data model
3.1.1 Data model
The internal data model in the simulator is the same as
the one defined in the IEC 61850 standard. All the IEC
61850 objects are instances of the I6Object class and
are organized as a tree as shown in Figure 9. I6Object
class provides a collection of services to manage the ob-
jects. Table 4 lists some frequently used services.
Name Description
addChild adds a child node
removeChild removes a child node
getName gets the node name
getRef gets the object reference
create creates a node in the tree
remove removes a node from the tree
lookup looks up a node in the tree
list lists the specific child nodes
lock locks a specific node
unlock unlocks a specific node
Table 4: Major services of I6Object
The lock and unlock services are necessary be-
cause the IEC 61850 standard allows multiple accesses
to the same object simultaneously. One would resolve
this problem by sequentializing all the received requests,
but since reports could be generated at the time when
the related data objects are being updated, synchroniza-
tion mechanism is still needed. One could implement
lock as locking the whole object tree, but this would
lead to severe performance problems, even dead locks.
Our solution is to lock the whole subtree dominated by
the locked object and mark all the ancestor nodes of that
object as partly locked so that these ancestor nodes can-
not be locked by other Associations.
Each kind of the IEC 61850 objects are implemented
as a subclass of I6Object. These subclasses pro-
vide templates to define the desired specialized classes.
For example, in order to create a specialized logical de-
vice class, one just need to derive a subclass from the
LDevice class and use the declareLN method to de-
clare the member logical nodes in the configure func-
tion.
Using the IEC 61850 data model as the internal data
model has two advantages: on the one hand, there is
no need to map the internal data representation to the
IEC 61850 data model in such an approach; on the other
hand, we can deploy the implementation of the ACSI ser-
vices to the relevant object classes thus achieve a simple
object-oriented approach. However, our simulation ex-
perience shows such a simple internal data representation
might not be a good choice because of the following two
reasons:
1. The data model defined by the IEC 61850 is unnec-
essarily structured as a tree. Functional constraints
present another view of data attributes in a logical
node, breaking the tree structure maintained by data
objects.
2. Some ACSI services are not easy to deploy to
the specific object classes. One example is the
CreateDataSet service, which should be im-
plemented by the LogicalNode class or the
Association class instead of the DataSet
class.
To maintain the tree structure, one can implement
functional constraints as implicit data sets, and redirect
9
+createSimple()
+createComplex()
+createList()
+getType()
+toXML()
+parseXML()
Msg
+getValue()
+setValue()
SimpleMsg
+appendItem()
+listItems()
ListMsg
+getAttribute()
+setAttribute()
ComplexMsg
Figure 10: Internal message of the simulator
the service requests to the appropriate object class us-
ing a dispatcher in the Association class. Instead of
maintaining an internal representation, we recommend
an other approach: using a lightweight database system
as the backend storage support. This approach provides
several benefits:
1. A database system provides the most flexible and
easiest way to maintain the appropriate tables and
views. A database system incorporates all the nec-
essary services to operate on the object tables, re-
ducing the complexity of maintaining an internal
data representation.
2. A database system supports exclusive object ac-
cesses, so the engineer does not need to explicitly
perform lock and unlock operations.
3. Database systems are usually optimized for data
storage and access, thus the database system ap-
proach can give comparable real-time performance
against the internal data representation approach.
3.1.2 Message representation
Messages are used in two cases: as internal events and as
requests/responses of ACSI services. Although the IEC
61850 standard defines manufacturing message specifi-
cation (MMS) as its representation format for informa-
tion exchange, we would like to use another information
representation format because on the one hand, MMS is
relatively complicated and on the other hand, the details
about the MMS standard is not freely available.
Messages in our simulator are represented as at-
tributed trees. There are three kinds of tree nodes (Fig-
ure 10): SimpleMsg, ComplexMsg and ListMsg.
A SimpleMsg node is a leaf node containing a
string value, which is used to represent a value. A
ComplexMsg node is a node containing a collection of
named attributes, the values of which are also nodes. A
Kernel Service API
J-Sim Communication
Interface
Association Service API
Figure 11: Implementation of the ACSI service
ListMsg node is a node that represents a list, with each
member also a node. Our message tree is virtually a sim-
plified version of a XML DOM tree. Using such kind of
message representation, we can easily pass the internal
events and service parameters/responses among different
internal objects.
3.1.3 Service model
Figure 11 shows the internal architecture of the im-
plementation of the ACSI services on the server side.
Each active association is equipped with an instance of
AssocAPI. AssocAPI provides the basic ACSI inter-
face for an association instance. On receiving the appli-
cation requests, the association instance invokes relevant
services provided by AssocAPI to complete the tasks.
AssocAPI is supported both by the underlying kernel
services which provides the basic functions to complete
the ACSI service requests, and by the communication
utilities, which talks to J-Sim [11], a network simulator.
Instead of delivering the reports using multi-party ap-
plication associations, we deliver them to the applica-
tions using the corresponding two-party application as-
sociations. The reporting procedure is rather straight-
forward: when the value of a data attribute is changed
or updated, we check whether this operation satisfies the
trigger condition. If the trigger condition is met, the data
attribute issues an internal event to all the data sets mark-
ing it as a member and those data sets will forward the
internal event to the active report control blocks, which
generate the reports and send them to the subscribing ap-
plications. For the sake of simplification, we assume the
members of a data set are all data attributes in our simu-
lation.
3.2 Running the simulator
One can follow the following steps to create a simulation
scenario and run a simulation:
Step 1 create specialized classes based on the tem-
plate classes.
The simulation package provides the necessary
template classes from Server to DataAttr.
Users just need to derive a specialized class from
10
the appropriate template class and configure this
class in the configure method as follows:
class DemoRelay
extends LDevice {
...
protected void configure() {
declareLN(new DemoXCBR(‘‘XCBR0’’));
declareLN(new DemoMMXU(‘‘MMXU0’’));
}
}
Step 2 create applications based on the
Application class.
Similar to the previous step, one needs to define
his own specialized Application class:
public class DemoApp1
extends Application {
protected void _start() {
...
}
}
Currently, our simulation package only supports
talking to one server for each application in-
stance. Enabling an application instance to talk
to multiple servers remains our future work.
Step 3 create the network topology in J-Sim.
We shall build a network scenario to simu-
late. One could easily create the require network
topology in J-Sim by following the INET Tuto-
rial [1]. It should be noted that only TCP based
communication is supported in current version of
our simulator.
Step 4 bind Application instances to the J-Sim nodes.
After the above steps are done, we should bind
the specialized Application instances to the J-Sim
network nodes:
set server [java::new demo.DemoServer]
mkdir demo.DemoApp1 h3/app1
connect -c h3/tcp/up@
-and h3/app1/down@
mkdir demo.DemoApp2 h4/app2
connect -c h4/tcp/up@
-and h4/app2/down@
Step 5 call createTPAA to create TPAAs and bind
them to the J-Sim nodes.
Then bind the TPAA instances to the J-Sim net-
work nodes:
cp [$server createTPAA] h1/tpaa1
connect -c h1/tcp/up@
-and h1/tpaa1/down@
cp [$server createTPAA] h2/tpaa2
connect -c h2/tcp/up@
-and h2/tpaa2/down@
Step 6 start J-Sim simulation.
Finally, we can start the simulation of the IEC
61850 standard:
set sim [attach_simulator .]
# start the association instances
run h1-2
# then the application instances
run h3-4
4 Conclusions
Due to its complexity and the assumed domain-specific
knowledge, the IEC 61850 standard is difficult for people
other than domain experts to understand and implement.
We presented our understanding of the standard as well
as the design and implementation of our simulation of the
IEC 61850 protocol based on J-Sim. Our experience and
lessons of simulating the protocol show that although the
IEC 61850 adopts an object-oriented approach, imple-
menters still need their own internal data representation
or take the advantage of a database system.
5 Acknowledgments
We would like to thank Zahid Anwar and Jianqing Zhang
for their keen discussions on the IEC 61850 standard.
References
[1] J-sim inet tutorial, December 2003. http://www.j-sim.
org/drcl.inet/inet_tutorial.html.
[2] BRAND, K.-P. The standard iec 61850 as prerequisite for in-
telligent applications in substations. Power Engineering Society
General Meeting, 2004. IEEE (June 2004), 714–718 Vol.1.
[3] DNP USERS GROUP. The distributed network protocol. Website.
http://www.dnp.org/.
[4] DOLEZILEK, D. Iec 61850: what you need to know about func-
tionality and practical implementation. Power Systems Confer-
ence: Advanced Metering, Protection, Control, Communication,
and Distributed Resources, 2006. PS ’06 (March 2006), 1–17.
[5] KIM, G.-S., AND LEE, H.-H. A study on iec 61850 based
communication for intelligent electronic devices. Science and
Technology, 2005. KORUS 2005. Proceedings. The 9th Russian-
Korean International Symposium on (2005), 765–770.
[6] KOSTIC, T., AND FREI, C. Modelling and using IEC 61850-7-2
(ACSI) as an API. In Power Tech 2007 Proceedings (July 2007).
[7] KOSTIC, T., PREISS, O., AND FREI, C. Understanding and us-
ing the iec 61850: a case for meta-modelling. Computer Stan-
dards & Interfaces 27, 6 (June 2005), 679–695.
11
[8] MCDONALD, J. Substation automation. ied integration and avail-
ability of information. Power and Energy Magazine, IEEE 1, 2
(March and April 2003), 22–31.
[9] MODBUS-IDA. Modbus application protocol specification
v1.1b, December 2006. http://www.modbus-ida.org/.
[10] SYSTEMS INTEGRATION SPECIALISTS COMPANY,
I. IEC 61850 evaluation kit CD-ROM. Software.
http://www.nettedautomation.com/solutions/
uca/evalkit/index.html.
[11] TYAN, H. Y., AND HOU, C. J. Javasim: A component-based
compositional network simulation environment. In Proceed-
ings of the Western Simulation Multiconference – Communica-
tion Networks And Distributed Systems Modeling And Simulation
(January 2001).
[12] UCA INTERNATIONAL USERS GROUP, I. Introduction to
UCA R version 2.0. Tech. rep., Institute of Electrical and Elec-
tronics Engineerings, Inc., November 1999.
[13] UDREN, E., KUNSMAN, S., AND DOLEZILEK, D. Significant
substation communication standardization developments. In 2nd
Annual Western Power Delivery Automation Conference (WP-
DAC) Proceedings (April 2000).
12
View publication statsView publication stats

More Related Content

Similar to Understanding20and20 simulating20the20iec206185020standard

Iisrt arshiya hesarur
Iisrt arshiya hesarurIisrt arshiya hesarur
Iisrt arshiya hesarur
IISRT
 
[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...
[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...
[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...
ISGAN Academy
 
empirical analysis modeling of power dissipation control in internet data ce...
 empirical analysis modeling of power dissipation control in internet data ce... empirical analysis modeling of power dissipation control in internet data ce...
empirical analysis modeling of power dissipation control in internet data ce...
saadjamil31
 

Similar to Understanding20and20 simulating20the20iec206185020standard (20)

Iec61850 overview and benefits paper general
Iec61850 overview and benefits paper generalIec61850 overview and benefits paper general
Iec61850 overview and benefits paper general
 
Effect on Substation Engineering Costs of IEC61850 & System Configuration Tools
Effect on Substation Engineering Costs of IEC61850 & System Configuration ToolsEffect on Substation Engineering Costs of IEC61850 & System Configuration Tools
Effect on Substation Engineering Costs of IEC61850 & System Configuration Tools
 
IEC 61850 Technical Overview.pdf
IEC 61850 Technical Overview.pdfIEC 61850 Technical Overview.pdf
IEC 61850 Technical Overview.pdf
 
unit 1vlsi notes.pdf
unit 1vlsi notes.pdfunit 1vlsi notes.pdf
unit 1vlsi notes.pdf
 
B5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
B5 g2 enhanced+protection+functionality+with+iec+61850+and+gooseB5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
B5 g2 enhanced+protection+functionality+with+iec+61850+and+goose
 
1451synopsis 599 f-good nist
1451synopsis 599 f-good nist1451synopsis 599 f-good nist
1451synopsis 599 f-good nist
 
10.1109@jiot.2020.29954
10.1109@jiot.2020.2995410.1109@jiot.2020.29954
10.1109@jiot.2020.29954
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
Survey on IoT application layer protocols
Survey on IoT application layer protocolsSurvey on IoT application layer protocols
Survey on IoT application layer protocols
 
Iisrt arshiya hesarur
Iisrt arshiya hesarurIisrt arshiya hesarur
Iisrt arshiya hesarur
 
UG 2016 Final Project.pdf
UG 2016 Final Project.pdfUG 2016 Final Project.pdf
UG 2016 Final Project.pdf
 
IRJET- Build SDN with Openflow Controller
IRJET-  	  Build SDN with Openflow ControllerIRJET-  	  Build SDN with Openflow Controller
IRJET- Build SDN with Openflow Controller
 
SECURE FILE STORAGE IN THE CLOUD WITH HYBRID ENCRYPTION
SECURE FILE STORAGE IN THE CLOUD WITH HYBRID ENCRYPTIONSECURE FILE STORAGE IN THE CLOUD WITH HYBRID ENCRYPTION
SECURE FILE STORAGE IN THE CLOUD WITH HYBRID ENCRYPTION
 
[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...
[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...
[ISGAN] IEC61850 standard: definition, benefits, challenges. How is the Osmos...
 
Automatically partitioning packet processing applications for pipelined archi...
Automatically partitioning packet processing applications for pipelined archi...Automatically partitioning packet processing applications for pipelined archi...
Automatically partitioning packet processing applications for pipelined archi...
 
Instruction Set Extension of a Low-End Reconfigurable Microcontroller in Bit-...
Instruction Set Extension of a Low-End Reconfigurable Microcontroller in Bit-...Instruction Set Extension of a Low-End Reconfigurable Microcontroller in Bit-...
Instruction Set Extension of a Low-End Reconfigurable Microcontroller in Bit-...
 
Electrical Rule Check Verification Methodology For SoC
Electrical Rule Check Verification Methodology For SoCElectrical Rule Check Verification Methodology For SoC
Electrical Rule Check Verification Methodology For SoC
 
IoT Protocol Stack.pdf
IoT Protocol Stack.pdfIoT Protocol Stack.pdf
IoT Protocol Stack.pdf
 
Modernization of Electrical Substation Automation Systems Using IEC61850
Modernization of Electrical Substation Automation Systems Using IEC61850Modernization of Electrical Substation Automation Systems Using IEC61850
Modernization of Electrical Substation Automation Systems Using IEC61850
 
empirical analysis modeling of power dissipation control in internet data ce...
 empirical analysis modeling of power dissipation control in internet data ce... empirical analysis modeling of power dissipation control in internet data ce...
empirical analysis modeling of power dissipation control in internet data ce...
 

Recently uploaded

Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
hublikarsn
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 

Recently uploaded (20)

Post office management system project ..pdf
Post office management system project ..pdfPost office management system project ..pdf
Post office management system project ..pdf
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 
Introduction to Geographic Information Systems
Introduction to Geographic Information SystemsIntroduction to Geographic Information Systems
Introduction to Geographic Information Systems
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptx
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
Worksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptxWorksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptx
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 

Understanding20and20 simulating20the20iec206185020standard

  • 1. See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/32964907 Understanding and Simulating the IEC 61850 Standard Article · May 2008 Source: OAI CITATIONS 36 READS 5,196 2 authors, including: Some of the authors of this publication are also working on these related projects: SIFT PROJECT View project Trustworthy Infrastructure for the Power Grid (TCIP) Information Trust Institute Illinois View project Roy Campbell University of Illinois, Urbana-Champaign 606 PUBLICATIONS   14,465 CITATIONS    SEE PROFILE All content following this page was uploaded by Roy Campbell on 11 November 2015. The user has requested enhancement of the downloaded file.
  • 2. Understanding and Simulating the IEC 61850 Standard ∗ Yingyi Liang Roy H. Campbell Department of Computer Science University of Illinois at Urbana-Champaign Urbana, IL 61801 {yliang6, rhc}@uiuc.edu Abstract The recent international standard IEC 61850 proposes a unified solution of the communication aspect of substa- tion automation. However, the standard itself is not eas- ily understood by users other than domain experts. We present our understanding of the IEC 61850 standard as well as the design and implementation of our simulation tool in this report. Also, we give suggestions on the im- plementation of this standard based on our experience and lessons in the development of our simulation. 1 Introduction Today, power substations are mostly managed by substa- tion automation systems. These systems employ com- puters and domain specific applications to optimize the management of substation equipment and to enhance op- eration and maintenance efficiencies with minimal hu- man intervention [8]. Once upon a time, substation automation systems utilized simple, straightforward and highly specialized communication protocols [7]. These protocols con- cerned less about the semantics of the exchanged data, data types of which were relatively primitive. Equipment was dumb and systems were simple. However, today’s substation automation systems can no longer enjoy such simplicity because of their growing complexity — equip- ment becomes more intelligent and most of those simple old systems have been gradually replaced by open sys- tems, which embrace the advantage of emerging tech- nology like relational database systems, multi-task oper- ating systems and support for state-of-the-art graphical display technology. Besides, devices from different manufacturers used different substation automation protocols [9, 3, 12], dis- abling them to talk to each other. Utilities have been pay- ing enormous money and time to configure these devices ∗This work was funded by NSF CNS 03-05537. to work together in a single substation. Today most util- ities and device manufacturers have recognized the need for a unified international standard to support seamless cooperation among products from different vendors. The IEC 61850 international standard, drafted by sub- station automation domain experts from 22 countries, seeks to tackle the aforementioned situation. This stan- dard takes advantage of a comprehensive object-oriented data model and the Ethernet technology, bringing in great reduction of the configuration and maintenance cost. Un- like its predecessor, the Utility Communication Architec- ture protocol 2.0 (UCA 2.0) [12], the IEC 61850 standard is designed to be capable for domains besides substation automation. To make the new protocol less domain de- pendent, the standard committee endeavored to empha- size on the data semantics, carving out most of the com- munication details. This effort, however, could result in difficulties in understanding the standard. In this research project, we aim to get a clear under- standing of the IEC 61850 standard and simulate the pro- tocol based on J-Sim [11]. Our ultimate goal is to inves- tigate the security aspect about the IEC 61850 standard. 2 The IEC 61850 standard The first release of the IEC 61850 consists of a set of documents of over 1,400 pages. These documents are di- vided into 10 parts, as listed in Table 1. Part 1 to Part 3 give some general ideas about the standard. Part 4 de- fines the project and management requirements in an IEC 61850 enabled substation. Part 5 specifies the required parameters for physical implementation. Part 6 defines an XML based language for IED configuration, present- ing a formal view of the concepts in the standard. Part 7 elaborates on the logical concepts, which is further di- vided into four subparts (listed in Table 2). Part 8 talks about how to map the internal objects to the presenta- tion layer and to the Ethernet link layer. Part 9 defines the mapping from sampled measurement value (SMV)
  • 3. to point-to-point Ethernet. The last part gives instruc- tions on conformance testing. Since Part 7 defines the core concepts of the IEC 61850 standard, we will focus on this part in this report. Subpart Title 7-1 Principles and Models 7-2 Abstract Communication Service Interface 7-3 Common Data Classes 7-4 Compatible Logical Node Classes and Data Classes Table 2: Subparts of IEC 61850-7 The IEC 61850 standard is not easy to understand for people other than experts in the substation automation domain due to the complexity of the documents and the assumed domain-specific knowledge. Introductory doc- uments on the standard abound [13, 4, 7, 5, 8, 2], but most of them are in the view of substation automation do- main experts. Kostic et al. explained the difficulties they had in understanding the IEC 61850 standard [7]. In this section, we provide another experience of understanding this standard, trying to explain the major concepts of the IEC 61850 standard. 2.1 Challenges Understanding the IEC 61850 standard proposes the fol- lowing challenges for a outsider of the substation au- tomation domain: 1. As a substation automation standard proposed by a group of domain experts, the IEC 61850 protocol assumes quite an amount of domain-specific knowl- edge, which is hardly accessible by engineers and researchers out of the substation automation do- main. To make things worse, the terms used in the standard is to some extent different from those commonly used in software engineering, bringing some difficulties for software engineers in reading the standard. 2. The entire standard, except Part 6, is described in natural language with tables and pictures, which is known to be ambiguous and lack of preciseness. This situation is problematic because the IEC 61850 concepts are defined by more than 150 mutually rel- evant tables distributed over more than 1,000 pages. A formal presentation of all these concepts would be appreciated. 3. The experts proposing this protocol come from 22 different countries and are divided into 10 working groups, each responsible to one part of the stan- dard. Due to the different backgrounds and the in- formal presentation style of the standard, the stan- dard contains a considerable number of inconsis- tencies. Such inconsistencies are more obvious for different parts of the standard, e.g. the data model described in Part 6 is clearly different from that de- scribed in Part 7. 4. The standard committee made a great effort to de- scribe the protocol in an object-oriented manner but the result is not so object-oriented. For example, the ACSI services are grouped by different classes, but reference to the callee object is not defined as a mandatory argument of the service function. 5. The standard is designed to be implementation in- dependent but this is not always true. For exam- ple, the data attribute TimeAccuracy in Part 7-2 Table 8 is defined as CODED ENUM, while what it virtually represents is a 5-bit unsigned integer; the frequent use of PACKED LIST (i.e. “bit fields” in the C language) also brings implementation details to interface design. 6. Things are mixed up in the documents. Mandatory components and optional components are mixed in the standard, and domain independent concepts are mixed up with domain specific concepts. Even though the optional components and mandatory ones are marked with “O” and “M” alternatively, it would be a tough task to refine a model consisting only the mandatory components due to the implicit dependences between attributes in different tables and the conditional inclusion of some attributes. In fact, there are 29 common data classes and 89 com- patible logical nodes defined in the standard, the re- lationship among which is unclear. 2.2 Intelligent electronic device In the past, utility communication standards usually as- sumed some domain-specific background of the readers. Consequently, they contained a lot of implicit domain knowledge, which is hardly accessible to outsiders (e.g. software engineers) [7]. The IEC 61850 standard does not escape from this category. To help understanding the logical concepts of IEC 61850, we would like to lay a basic idea of intelligent electronic devices (IED), the es- sential physical object hosting all the logical objects. Basically, the term intelligent electronic device refers to microprocessor-based controllers of power system equipment, which is capable to receive or send data/con- trol from or to an external source [8]. An IED is usu- ally equipped with one or more microprocessors, mem- 2
  • 4. Part Title 1 Introduction and Overview 2 Glossary 3 General Requirements 4 System and Project Management 5 Communication Requirements for Functions and Device Models 6 Configuration Description Language for Communication in Electronic Substations Related to IEDs 7 Basic Communication Structure for Substation and Feeder Equipment 8 Specific Communication Service Mapping (to MMS and to Ethernet) 9 Specific Communication Service Mapping (from Sampled Values) 10 Conformance Testing Table 1: Parts of the IEC 61850 standard documents ory, possibly a hard disk and a collection of communi- cation interfaces (e.g. USB ports, serial ports, Ethernet interfaces), which implies that it is essentially a computer as those for everyday use. However, IEDs may contain some specific digital logics for domain-specific process- ing. IEDs can be classified by their functions. Common types of IEDs include relay devices, circuit breaker con- trollers, recloser controllers, voltage regulators etc.. It should be noted that one IED can perform more than one functions, taking advantage of its general-purpose micro- processors. An IED may have an operating system like Linux running in it. 2.3 Substation architecture A typical substation architecture is shown in Figure 1. The substation network is connected to the outside wide area network via a secure gateway. Outside remote op- erators and control centers can use the abstract commu- nication service interface (ACSI) defined in Part 7-2 to query and control devices in the substation. There is one or more substation buses connecting all the IEDs inside a substation. A substation bus is realized as a medium bandwidth Ethernet network, which carries all ACSI re- quests/responses and generic substation events messages (GSE, including GOOSE and GSSE). There is another kind of bus called process bus for communication inside each bay. A process bus connects the IEDs to the tradi- tional dumb devices (merge units, etc.) and is realized as a high bandwidth Ethernet network. A substation usually has only one global substation bus but multiple process buses, one for each bay. ACSI requests/responses, GSE messges and sampled analog values are the three major kinds of data active in the substation network. Since we are less interested in communication on the process buses (like sampled value multicasting), we focus on the activities on the substation bus in this report, especially the ACSI activities. Figure 1: Substation architecture Interactions inside a substation automation system mainly fall into three categories: data gathering/setting, data monitoring/reporting and event logging. The former two kinds of interactions are the most important — in the IEC 61850 standard all inquiries and control activities to- wards physical devices are modeled as getting or setting the values of the correspondingdata attributes, while data monitoring/reporting provides an efficient way to track the system status, so that control commands can be is- sued in a timely manner. To realize the above kinds of interaction, the IEC 61850 standard defines a relatively complicated com- munication structure, as is shown in Figure 2. Five kinds of communication profiles are defined in the stan- dard: the abstract communication service interface pro- file (ACSI), the generic object oriented substation event profile (GOOSE), the generic substation status event pro- file (GSSE), the sampled measured value multicast pro- file (SMV), and the time synchronization profile. ACSI services enable client-server style interaction between applications and servers. GOOSE provides a fast way of data exchange on the substation bus and GSSE pro- vides an express way of substation level status exchange. Sample measured value multicast provides an effective way to exchange data on a process bus. 3
  • 5. Ethernet Link Layer SMV GOOSE GSSE TimeSync ACSI IP UDP TCP MMS GSSE T-Profile Specific Communication Service Mapping (SCSM) Application Domain Communication Stack Figure 2: The communication profiles 2.4 Abstract communication service inter- face ACSI is the primary interface in the IEC 61850 standard not only because it is the interface via which applications talk with servers, but also in the sense that the ACSI com- munication channel is an important part of a logical con- nection between two logical nodes. ACSI defines the se- mantics of the data exchanged between applications and servers, thus it becomes the major part of the IEC 61850 standard. The standard committee adopt an object-oriented ap- proach in the design of ACSI, which includes a hierar- chical and comprehensive data model and a set of avail- able services for each class in this data model. Al- though the data model is usually described outside the scope of the ACSI, it is actually part of it. The ben- efits of using an object-oriented utility communication interface are two fold. On the one hand, objects (e.g. registers) can be referenced in an intuitive way (e.g. “Relay0/MMXU0.voltage”) instead of by the tradi- tional physical address (like Reg#02432). On the other hand, software engineers can build more reliable appli- cations using such service interface. In the following two sections, we present a brief de- scription on these two ACSI components. 2.5 Data model The hierarchical data model defined in the IEC 61850 is depicted in Figure 3 and Figure 4. Server is the topmost component in this hierarchy. It serves as the joint point of physical devices and logical objects. Theoretically one IED may host one or more server instances, but in practice usually only one server instance runs in an IED. A server instance is basically a program running in an IED, which shares the same mean- ing with other servers like FTP server etc.. Each server has one or more access points, which are the logical rep- resentation of a NIC. When a client is to access data or service of the server, it should connect to an access point of this server and establish a valid association. Each server hosts several files or logical devices. Clients can manipulate files in the server like talking to a FTP server, which is usually used as a means to up- load/update the configuration file of an IED. A logical device is the logical correspondence of a physical device. It is basically a group of logical nodes performing similar functions. Functions supported by an IED are conceptually rep- resented by a collection of primitive, atomic functional building blocks called logical nodes. The IEC 61850 standard predefines a collection of template logical nodes (i.e. compatible logical nodes) in Part 7-4. Besides the regular logical nodes for functions, the standard also requires every logical device have two specific logical nodes: Logical Node Zero (LN0) and LPHD, which cor- respond to the logical device and the physical device, alternatively. Besides holding status information of the logical device, LN0 also provides additional functions like setting-group control, GSE control, sampled value control etc.. In the IEC 61850 standard, the entire sub- station system is modeled as a distributed system con- sisting of a collection of interacting logical nodes, which are logically connected by logical connections. It should be noted that the term logical connection refers to the logical concept of the connections between two logical nodes, which can be direct or indirect or even a combina- tion of many different kinds of communication channels. In fact, the connection of two logical nodes is usually both indirect and a combination of TCP, UDP and direct Ethernet connections. We will explain logical connec- tions in Section 2.9. Data exchanged between logical nodes are modeled as data objects. A logical node usually contains sev- eral data objects. Each data object is an instance of the DATA class and has a common data class type. Similar to the concept of objects in most object-oriented program- ming languages, a data object consists of many data at- tributes, which are instances of data attributes of the cor- responding common data class. Data attributes are typed and restricted by some functional constraints. Instead of grouping data attributes by data objects, functional con- straints provide a way to organize all the data attributes in a logical node by functions. Types of data attributes can be either basic or composite. Basic types are primitive types in many programming languages, whereas com- posite types are composition of a collection of primitive types or composite types. In the IEC 61850 standard, data attributes are at least as important as, if not more than, data objects for two 4
  • 6. SERVER LOGICAL-DEVICE LOGICAL-DEVICE ... LOGICAL-DEVICE LOGICAL-NODE LOGICAL-NODE ... LOGICAL-NODE DATA OBJECT DATA OBJECT ... DATA OBJECT DATA ATTRIBUTE DATA ATTRIBUTE ... Figure 3: Hierarchy of the IEC 61850 data model reasons. Firstly, data objects are just logical collections of the contained data attributes while (primitive) data at- tributes are the de facto logical correspondence to the physical entities (memory units, registers, communica- tion ports, etc.); secondly, the purpose of data objects is for the convenience of managing and exchanging values of a group of data attributes sharing the same function. Despite data objects, the IEC 61850 standard provides the concept of data set as another ways to manage and exchange a group of data attributes. Members of a data set can be data objects or data attributes. The concept of data set is somewhat similar to the concept of view in the area of database management systems. In the IEC 61850 standard, most services involve data sets. Members in a data set unnecessarily come from the same logical node or the same data object, thus providing high flexibility of data management. Data sets are categorized into per- manent ones and temporary ones. Permanent data sets are hosted by logical nodes and will not be automatically deleted unless on the owners’ explicit requests; tempo- rary data sets are exclusively hosted by the association having created them and will be automatically deleted when the association ends. 2.6 Service model Services provided by ACSI include querying object set, getting/setting data values, controlling system objects, report manipulation, log manipulation, and other ser- vices like file upload/download. Table 3 gives a list of ACSI services defined in the IEC 61850 standard. All ACSI services are requested by applications and responded by servers. In order to request a service in a server, an application must first establish a valid two- party application association (TPAA) with the server. The TPAA maintains the session states and provides a virtual view of the server to the application. A typical interaction procedure between an application A and a server S goes as follows: 1. A establishes a TCP connection with S; 2. A “logs in” to S by requesting the Associate ser- vice from S, providing authentication related infor- mation as parameters; LOGICAL NODECompatible Logical Node LOGICAL DEVICE SERVER DATACommon Data Class FCDA 1 1..n 1 1..n 1 1..n 1 1..n 1 0..n TrgOp Functional Constraint DAType 1 0..2 11 1 1 1 1..n BasicType 1* Figure 4: The data model of the IEC 61850 3. S validates the information provided by A and cre- ates a TPAA object, which provides a virtual view of S to A; 4. A requests subsequent services while S processes the requests and responses with appropriate re- sponses defined in the IEC 61850 standard; 5. A issues a Release request to S; 6. S reclaims the TPAA of A and ends the session. The virtual view of server provided by a TPAA en- forces the access control policies set forth by the server. This virtual view defines which objects in the server are visible and accessible to the application and what kinds of service of those objects are accessible from the appli- cation. The concept of virtual view is very flexible and 5
  • 7. SERVER: LOG-CONTROL-BLOCK: GetServerDirectory GetLCBValues ASSOCIATION: SetLCBValues Associate QueryLogByTime Abort QueryLogAfter Release GetLogStatusValues LOGICAL-DEVICE: GOOSE: GetLogicalDeviceDirectory SendGOOSEMessage LOGICAL-NODE: GetGoReference GetLogicalNodeDirectory GetGOOSEElementNumber GetAllDataValues GetGoCBValues DATA: SetGoCBValues GetDataValues GSSE: SetDataValues SendGSSEMessage GetDataDirectory GetGsReference GetDataDefinition GetGSSEDataOffset DATA-SET: GetGsCBValues GetDataSetValues SetGsCBValues SetDataSetValues MULTICAST-SAMPLE-VALUE-CONTROL-BLOCK: CreateDataSet SendMSVMessage DeleteDataSet GetMSVCBValues GetDataSetDirectory SetMSVCBValues Substitution: UNICAST-SAMPLE-VALUE-CONTROL-BLOCK: SetDataValues SendUSVMessage GetDataValues GetUSVCBValues SETTING-GROUP-CONTROL-BLOCK: SetUSVCBValues SelectActiveSG Control: SelectEditSG Select SetSGValues SelectWithValue ConfirmEditSGValues Cancel GetSGValues Operate GetSGCBValues CommandTermination BUFFERED-REPORT-CONTROL-BLOCK: TimeActivatedOperate Report Time synchronization: GetBRCBValues TimeSynchronization SetBRCBValues FILE transfer: UNBUFFERED-REPORT-CONTROL-BLOCK: GetFile Report SetFile GetURCBValues DeleteFile SetURCBValues GetFileAttributeValues Table 3: ACSI services the IEC 61850 standard does not place any restriction on the access control policies of the server. One possible and relatively simple access control is the world-group- owner access control for files used in many UNIX sys- tems. The ACSI interface defines an object-oriented inter- face for the applications but it does not require the inter- nal implementation to be object-oriented. In actual fact, according to our experience on simulating the IEC 61850 protocol, object-oriented approach might not be a wise choice for the internal implementation. 2.7 Reporting and logging The IEC 61850 standard provides an efficient mechanism called reporting for applications to track changes to the subscribed system objects. Instead of polling the data attribute values periodically, applications can group the interesting data attributes into a data set, and require the logical node hosting this data set report any changes to 6
  • 8. the members of this data set. Theoretically a data set can contain data objects/data attributes from different logical nodes, but data sets for reporting usually contain only the data objects/data attributes in the same logical node. The procedure of report generation and transmission is under the control of an information block called report control block (RCB). A RCB maintains the necessary in- formation to generate a report like which fields should be included in the report, on what events a report should be generated, the sequence number of the current report, whether this RCB is enabled, etc.. A typical report generation and transmission proce- dure is described as follows: 1. client application creates a data set containing all the data objects and data attributes it concerns; 2. client sets the parameters in a RCB, specifies the aforementioned data set as the source of the reports (this step is called to “subscribe to a data set”) and enables this RCB; 3. on any change to any member of the data set, the logical node tests this change against the event list of the RCB, and issues an internal event if any event in the list gets matched; 4. on receiving the internal event, the RCB stores this event for later sending; 5. if the condition of sending the report is satisfied, the logical node collects necessary data, generates the report and sends it out to the client via the associ- ation under the direction of the parameters in the RCB. Reports can be sent by either two-party application as- sociation (TPAA) or multi-party application association (MPAA). TPAA is the association that can serve only one client while MPAA can serve more than one client si- multaneously. Reports generated on the request of the Report service is sent by TPAA, whereas other reports are sent by MPAA. Reporting uses a publisher/subscriber mechanism: for every client, the server must assign an individual RCB to handle the report generation and trans- mission. Logging is a mechanism to record the device events. Logs are stored in the server and hosted by the corre- sponding logical device. Unlike reporting, every time a device event is triggered, the logical device merely saves a log entry into the log database for later inquiries. 2.8 Generic substation event Besides reporting, the IEC 61850 standard defines generic substation event (GSE) as another means for ap- plications to monitor changes to the data objects/data at- tributes. GSE is designed for fast delivering notification of system object changes. There are two kinds of GSE, generic object-oriented substation events (GOOSE) and generic substation state event (GSSE). GOOSE is used to exchange a wide range of common data while GSSE is used to convey state change information. The GSE mechanism shares a lot of similarities with reporting, with the major difference that GSE is designed for fast information exchange inside a substation while reporting is mainly used for sending notification from the server side to remote control centers or browsers. Since real-time performance is critical for GSE mes- sages, the message format and communication stack for GSE transmission is very different from those for report- ing. GSE messages are transmitted in binary format, which provides shorter message body and higher mes- sage encoding/decoding speed. In stead of using TCP or UDP as the underlying transport layer, GSSE uses its specific transport layer while GOOSE messages are sent to the Ethernet link layer directly without going through any transport layer or network layer. GSE also utilizes a publisher/subscriber mechanism to transmit the messages. This mechanism is implemented by the Ethernet multicast feature: the publisher sends the GSE message to a specific multi-cast MAC address and the subscribers pick up messages sent to this address, put them into their local buffer for the local applications to consume. 2.9 Communication network The IEC 61850 standard defines a distributed system consisting of interacting logical nodes, which are con- nected by logical connections. However, in order for this distributed system to work correctly and intelligently, there must be some intelligent components inside this network. It is not hard to see that applications play this role. An interesting question is how to integrate appli- cations into the interacting logical node network. We try to answer this question by starting from the simple ACSI server-application network. Figure 5 shows such a server-application network. Clearly, each server may serve several applications and vice versa. The dotted lines in Figure 5 refer to the com- munication channels for reports and GSE messages. Al- though there are no restrictions about the relationship be- tween report subscribers and report publishers, it is not true for GSE messages. The design of GSE has physical concerns. GSE messages are sent from one IED to an- other, thus the subscribers and the publishers should not reside in the same IED. To make things more clear, let us transform Figure 5 into Figure 6, which shows the communication between 7
  • 9. Server1 App1 Server3 Server2 App4 App5 App3 App2 Figure 5: Server-Application network Server3 LN31 LN32 Server2 LN21 LN22 Server1 LN11 LN12 App1 App2 App4 App5 App3 Figure 6: Logical node-application network Server3 LN31 LN32 Server2 LN21 LN22 Server1 LN11 LN12 Figure 7: Logical node network applications and logical nodes (we hid the communica- tion to server and logical devices). At this point, we can clearly see that logical connections between logical nodes are actually a mixture of several kinds of connec- tions: when a logical node sends a message to another logical node, it is virtually sending reports/GSE mes- sages to the relevant applications; after necessary pro- cessing of the reports/GSE messages, the applications is- sue relevant requests to the other logical node, and vice versa. Thus we can deploy the application logic to the relevant logical nodes and get Figure 7 by abstracting away the applications. Being aware of this abstraction is important for both implementation and simulation of the IEC 61850 protocol. 3 Simulating the IEC 61850 In this section, we talk about the design and implemen- tation of a simulator of the IEC 61850 standard. Due to the challenges listed in Section 2.1, simulating the entire protocol is very difficult. Since the goal of our simula- tion is to inspect possible security vulnerabilities in the protocol, we refined the protocol to a version contain- ing only data gathering/setting related ACSI services and reporting services. Furthermore we simplified the data model by abstracting various data attribute types to string and discarding the concept of functional constraint. Cur- rently, features of the IEC 61850 protocol supported by our simulation model include two-party application asso- ciation, data attribute, data object, data set, logical node, logical device, server, ACSI services, reporting and un- buffered report control block. 3.1 Design and implementation of the sim- ulator In order to inspect the IEC 61850 standard, we need a tool to simulate the protocol. Demo software of the pro- tocol exists [10]. However, they are mostly provided by the IED manufacturer and are not freely available for re- search purposes. Kostic et al. proposed an implementa- tion of ACSI [6]. The work of Kostic et al. focuses on implementing a set of application programming interface for device and application development, while we would like to build our own simulation tool for further study on the IEC 61850, especially on network security issues. Our simulator consists of about 3,500 lines of Java code. Its components are divided into three major cat- egories: the data model, internal message representation and the service model. Figure 8 shows the architecture of the simulator. 8
  • 10. ApplicationServer Association Service API Object Management Association Management Remote Service API Internal Messaging Reporting Figure 8: The IEC 61850 simulator architecture Server LD LN Data DataSet URCB DA LD LD LN Data DA DA ... ... ... ... Figure 9: The IEC 61850 simulator data model 3.1.1 Data model The internal data model in the simulator is the same as the one defined in the IEC 61850 standard. All the IEC 61850 objects are instances of the I6Object class and are organized as a tree as shown in Figure 9. I6Object class provides a collection of services to manage the ob- jects. Table 4 lists some frequently used services. Name Description addChild adds a child node removeChild removes a child node getName gets the node name getRef gets the object reference create creates a node in the tree remove removes a node from the tree lookup looks up a node in the tree list lists the specific child nodes lock locks a specific node unlock unlocks a specific node Table 4: Major services of I6Object The lock and unlock services are necessary be- cause the IEC 61850 standard allows multiple accesses to the same object simultaneously. One would resolve this problem by sequentializing all the received requests, but since reports could be generated at the time when the related data objects are being updated, synchroniza- tion mechanism is still needed. One could implement lock as locking the whole object tree, but this would lead to severe performance problems, even dead locks. Our solution is to lock the whole subtree dominated by the locked object and mark all the ancestor nodes of that object as partly locked so that these ancestor nodes can- not be locked by other Associations. Each kind of the IEC 61850 objects are implemented as a subclass of I6Object. These subclasses pro- vide templates to define the desired specialized classes. For example, in order to create a specialized logical de- vice class, one just need to derive a subclass from the LDevice class and use the declareLN method to de- clare the member logical nodes in the configure func- tion. Using the IEC 61850 data model as the internal data model has two advantages: on the one hand, there is no need to map the internal data representation to the IEC 61850 data model in such an approach; on the other hand, we can deploy the implementation of the ACSI ser- vices to the relevant object classes thus achieve a simple object-oriented approach. However, our simulation ex- perience shows such a simple internal data representation might not be a good choice because of the following two reasons: 1. The data model defined by the IEC 61850 is unnec- essarily structured as a tree. Functional constraints present another view of data attributes in a logical node, breaking the tree structure maintained by data objects. 2. Some ACSI services are not easy to deploy to the specific object classes. One example is the CreateDataSet service, which should be im- plemented by the LogicalNode class or the Association class instead of the DataSet class. To maintain the tree structure, one can implement functional constraints as implicit data sets, and redirect 9
  • 11. +createSimple() +createComplex() +createList() +getType() +toXML() +parseXML() Msg +getValue() +setValue() SimpleMsg +appendItem() +listItems() ListMsg +getAttribute() +setAttribute() ComplexMsg Figure 10: Internal message of the simulator the service requests to the appropriate object class us- ing a dispatcher in the Association class. Instead of maintaining an internal representation, we recommend an other approach: using a lightweight database system as the backend storage support. This approach provides several benefits: 1. A database system provides the most flexible and easiest way to maintain the appropriate tables and views. A database system incorporates all the nec- essary services to operate on the object tables, re- ducing the complexity of maintaining an internal data representation. 2. A database system supports exclusive object ac- cesses, so the engineer does not need to explicitly perform lock and unlock operations. 3. Database systems are usually optimized for data storage and access, thus the database system ap- proach can give comparable real-time performance against the internal data representation approach. 3.1.2 Message representation Messages are used in two cases: as internal events and as requests/responses of ACSI services. Although the IEC 61850 standard defines manufacturing message specifi- cation (MMS) as its representation format for informa- tion exchange, we would like to use another information representation format because on the one hand, MMS is relatively complicated and on the other hand, the details about the MMS standard is not freely available. Messages in our simulator are represented as at- tributed trees. There are three kinds of tree nodes (Fig- ure 10): SimpleMsg, ComplexMsg and ListMsg. A SimpleMsg node is a leaf node containing a string value, which is used to represent a value. A ComplexMsg node is a node containing a collection of named attributes, the values of which are also nodes. A Kernel Service API J-Sim Communication Interface Association Service API Figure 11: Implementation of the ACSI service ListMsg node is a node that represents a list, with each member also a node. Our message tree is virtually a sim- plified version of a XML DOM tree. Using such kind of message representation, we can easily pass the internal events and service parameters/responses among different internal objects. 3.1.3 Service model Figure 11 shows the internal architecture of the im- plementation of the ACSI services on the server side. Each active association is equipped with an instance of AssocAPI. AssocAPI provides the basic ACSI inter- face for an association instance. On receiving the appli- cation requests, the association instance invokes relevant services provided by AssocAPI to complete the tasks. AssocAPI is supported both by the underlying kernel services which provides the basic functions to complete the ACSI service requests, and by the communication utilities, which talks to J-Sim [11], a network simulator. Instead of delivering the reports using multi-party ap- plication associations, we deliver them to the applica- tions using the corresponding two-party application as- sociations. The reporting procedure is rather straight- forward: when the value of a data attribute is changed or updated, we check whether this operation satisfies the trigger condition. If the trigger condition is met, the data attribute issues an internal event to all the data sets mark- ing it as a member and those data sets will forward the internal event to the active report control blocks, which generate the reports and send them to the subscribing ap- plications. For the sake of simplification, we assume the members of a data set are all data attributes in our simu- lation. 3.2 Running the simulator One can follow the following steps to create a simulation scenario and run a simulation: Step 1 create specialized classes based on the tem- plate classes. The simulation package provides the necessary template classes from Server to DataAttr. Users just need to derive a specialized class from 10
  • 12. the appropriate template class and configure this class in the configure method as follows: class DemoRelay extends LDevice { ... protected void configure() { declareLN(new DemoXCBR(‘‘XCBR0’’)); declareLN(new DemoMMXU(‘‘MMXU0’’)); } } Step 2 create applications based on the Application class. Similar to the previous step, one needs to define his own specialized Application class: public class DemoApp1 extends Application { protected void _start() { ... } } Currently, our simulation package only supports talking to one server for each application in- stance. Enabling an application instance to talk to multiple servers remains our future work. Step 3 create the network topology in J-Sim. We shall build a network scenario to simu- late. One could easily create the require network topology in J-Sim by following the INET Tuto- rial [1]. It should be noted that only TCP based communication is supported in current version of our simulator. Step 4 bind Application instances to the J-Sim nodes. After the above steps are done, we should bind the specialized Application instances to the J-Sim network nodes: set server [java::new demo.DemoServer] mkdir demo.DemoApp1 h3/app1 connect -c h3/tcp/up@ -and h3/app1/down@ mkdir demo.DemoApp2 h4/app2 connect -c h4/tcp/up@ -and h4/app2/down@ Step 5 call createTPAA to create TPAAs and bind them to the J-Sim nodes. Then bind the TPAA instances to the J-Sim net- work nodes: cp [$server createTPAA] h1/tpaa1 connect -c h1/tcp/up@ -and h1/tpaa1/down@ cp [$server createTPAA] h2/tpaa2 connect -c h2/tcp/up@ -and h2/tpaa2/down@ Step 6 start J-Sim simulation. Finally, we can start the simulation of the IEC 61850 standard: set sim [attach_simulator .] # start the association instances run h1-2 # then the application instances run h3-4 4 Conclusions Due to its complexity and the assumed domain-specific knowledge, the IEC 61850 standard is difficult for people other than domain experts to understand and implement. We presented our understanding of the standard as well as the design and implementation of our simulation of the IEC 61850 protocol based on J-Sim. Our experience and lessons of simulating the protocol show that although the IEC 61850 adopts an object-oriented approach, imple- menters still need their own internal data representation or take the advantage of a database system. 5 Acknowledgments We would like to thank Zahid Anwar and Jianqing Zhang for their keen discussions on the IEC 61850 standard. References [1] J-sim inet tutorial, December 2003. http://www.j-sim. org/drcl.inet/inet_tutorial.html. [2] BRAND, K.-P. The standard iec 61850 as prerequisite for in- telligent applications in substations. Power Engineering Society General Meeting, 2004. IEEE (June 2004), 714–718 Vol.1. [3] DNP USERS GROUP. The distributed network protocol. Website. http://www.dnp.org/. [4] DOLEZILEK, D. Iec 61850: what you need to know about func- tionality and practical implementation. Power Systems Confer- ence: Advanced Metering, Protection, Control, Communication, and Distributed Resources, 2006. PS ’06 (March 2006), 1–17. [5] KIM, G.-S., AND LEE, H.-H. A study on iec 61850 based communication for intelligent electronic devices. Science and Technology, 2005. KORUS 2005. Proceedings. The 9th Russian- Korean International Symposium on (2005), 765–770. [6] KOSTIC, T., AND FREI, C. Modelling and using IEC 61850-7-2 (ACSI) as an API. In Power Tech 2007 Proceedings (July 2007). [7] KOSTIC, T., PREISS, O., AND FREI, C. Understanding and us- ing the iec 61850: a case for meta-modelling. Computer Stan- dards & Interfaces 27, 6 (June 2005), 679–695. 11
  • 13. [8] MCDONALD, J. Substation automation. ied integration and avail- ability of information. Power and Energy Magazine, IEEE 1, 2 (March and April 2003), 22–31. [9] MODBUS-IDA. Modbus application protocol specification v1.1b, December 2006. http://www.modbus-ida.org/. [10] SYSTEMS INTEGRATION SPECIALISTS COMPANY, I. IEC 61850 evaluation kit CD-ROM. Software. http://www.nettedautomation.com/solutions/ uca/evalkit/index.html. [11] TYAN, H. Y., AND HOU, C. J. Javasim: A component-based compositional network simulation environment. In Proceed- ings of the Western Simulation Multiconference – Communica- tion Networks And Distributed Systems Modeling And Simulation (January 2001). [12] UCA INTERNATIONAL USERS GROUP, I. Introduction to UCA R version 2.0. Tech. rep., Institute of Electrical and Elec- tronics Engineerings, Inc., November 1999. [13] UDREN, E., KUNSMAN, S., AND DOLEZILEK, D. Significant substation communication standardization developments. In 2nd Annual Western Power Delivery Automation Conference (WP- DAC) Proceedings (April 2000). 12 View publication statsView publication stats