Processing & Properties of Floor and Wall Tiles.pptx
Ccs for solar power pv plant
1. Challenges for the Design of Wind and Solar Power
Plant Grounding System for Personal Safety
Comparison of Copper and Copper Clad Steel Conductors for WPP
Grounding Application
IEEE PES 2016 General Meeting, Boston, MA, July 17-21, 2016.
Presentation by:
Andrew Cadmore , CEng MIET, Principal Electrical Design Engineer, RES Ltd
Abdou Sana, P.Eng, Ph.D, Electrical Engineering Specialist, RES-Americas
1
2. 1- The Use of bare Copper Clad Steel (CSS) conductor, instead of
bare Copper (Cu) conductor, as the directly buried bare
horizontal ground electrode conductor laid in all MV cable
trenches is evaluated based on a WPP project design exercise
2
Typical 34.5kV MV Cable Trench Cross-Section View
3. 2- Copper Clad Steel (CCS)
• Composite in which a concentric copper cladding is bonded to
a steel core to provide a strong “low cost” solution for
grounding conductors
• Available Stranded CCS conductors: 40% and 30% conductivity
relative to the same size of annealed soft-drawn copper
(relative conductivity of 100%).
• Sizing of CCS conductor should be based on an equivalent
short circuit capacity to that of annealed soft-drawn copper
3
4. 4
• Claims on the benefits of CCS conductors as an alternative to
copper conductors:
– Cost savings compared to copper
– 8-12% lighter than copper conductors
– 105-108% higher fusing current compared to copper conductors
– Highly theft resistant
– Excellent fatigue properties
– Extremely strong and rugged, higher breaking strength than copper
conductors
– CCS requires no special handling compared to Copper
– CCS is compatible with standard copper connectors either pressure,
bolted or exothermic welded
– CCS conductors exhibit high corrosion resistance as tested in various
soils conditions
5. 3- Comparative Study copper vs CCS for a typical WPP
• Analysis of the impedance profile resulting from a 3-
dimensional model of the grounding system for a large WPP
– Impedance profiles as seen from the main substation and using 3
types of conductors throughout the MV cable trenches are evaluated
and compared:
• Bare copper conductors
• Equivalent 30% conductivity CCS conductors
• Equivalent 40% conductivity CCS conductors
• Parametric analysis for each of these 3 grounding conductor
systems (Copper, CCS30% & CCS40%), with logarithmic varying
soil resistivity:
• 10 ohm.m uniform soil model (Typ. Shoreline windfarm)
• 100 ohm.m uniform soil model (Typ. low-land windfarm)
• 1,000 ohm.m uniform soil model (Typ. high-land windfarm)
• 10,000 ohm.m uniform soil model (Extreme rocky mountainous windfarm)
5
6. 6
WPP example in WA State, USA, Design-built in 2010/2011:
• 1x 230kV/34.5kVSubstation
• 83 Wind Turbines (191MW)
• 2 Met Masts
• Approx. 5.7 mi x 3.5 mi
• 10- 34.5kV Collection Circuits
All UG, 5 different MV cable
sizes
7. • Equivalent Bare Grounding Conductor installed at the base of
all MV cable trenches:
– Size based on IEEE Std 80-2000 with:
• Prevailing maximum 34.5kV fault level, seen at the main substation: 20,383 Amps.
• Fault clearing time 0.133s
• Initial Temperature : 25°C
• Final Temperature: 350°C
– Results:
• 1/0 AWG stranded copper conductor, (106kcmil)
• 30% conductivity CCS conductor: 7x #6 AWG (184kcmil)
• 40% conductivity CCS conductor: 7x #7 AWG (146kcmil)
7
8. I rms current in kA
Amm
2 minimum Conductor cross section in mm2
Akcmil minimum Conductor cross section in kcmil
Tm Maximum allowable temperature in °C
Ta Ambient temperature in °C
Tr Reference temperature for material constants in °C
αo Thermal coefficient of resistivity at 0 °C in 1/°C
αr Thermal coefficient of resistivity at reference temperature Tr in 1/°C
ρr Resistivity of the ground conductor at reference temperature Tr in μΩ-cm
Ko 1/αo or (1/αr) – Tr in °C
tc duration of current in s
TCAP: Thermal capacity per unit volume of material in J/(cm3·°C) (see table)
αr and ρr to be evaluated at the same reference temperature of Tr °C .
(Tables provides data for αr and ρr at 20 °C).
8
Amm2 I
1
TCAP10
4
tc r r
ln
K0 Tm
K0 Ta
A.kcmil I
197.4
TCAP
t.c .r .r
ln
K.0 T.m
K.0 T.a
Minimum Conductor Cross-section Area (IEEE Std 80 -2000)
9. 9
a From ASTM standards.
b Copper-clad steel rods based on 0.254 mm (0.010 in) copper thickness.
c Stainless-clad steel rod based on 0.508 mm (0.020 in) No. 304 stainless steel thickness over No. 1020
steel core.
Description Material
conductivity
(%)
αr factor at
20 °C
(1/°C)
Ko at 0 °C
(0 °C)
Fusinga
temperature
Tm (°C)
ρr 20 °C
(μΩ·cm)
TCAP thermal
capacity
[J/(cm3
·°C)]
Copper, annealed soft-
drawn
100.0 0.003 93 234 1083 1.72 3.42
Copper, commercial
hard-drawn
97.0 0.003 81 242 1084 1.78 3.42
Copper-clad steel wire 40.0 0.003 78 245 1084 4.40 3.85
Copper-clad steel wire 30.0 0.003 78 245 1084 5.86 3.85
Copper-clad steel rodb
20.0 0.003 78 245 1084 8.62 3.85
Aluminum, EC grade 61.0 0.004 03 228 657 2.86 2.56
Aluminum, 5005 alloy 53.5 0.003 53 263 652 3.22 2.60
Aluminum, 6201 alloy 52.5 0.003 47 268 654 3.28 2.60
Aluminum-clad steel
wire
20.3 0.003 60 258 657 8.48 3.58
Steel, 1020 10.8 0.001 60 605 1510 15.90 3.28
Stainless-clad steel rodc
9.8 0.001 60 605 1400 17.50 4.44
Zinc-coated steel rod 8.6 0.003 20 293 419 20.10 3.93
Stainless steel, 304 2.4 0.001 30 749 1400 72.00 4.03
15. 4- Comments on Results
• Ground grid Impedance Zg, as seen at the Main Substation
(i.e. point of fault), increases for CCS relative to copper. Max
value 140.8% for the 30% CCS conductor, in a 10 ohm.m soil.
This results also in:
– Increase of GPR, Touch & Step Potential as seen at or near the point of
fault proportional to the increase in ground electrode impedance.
– Slightly larger Hot Zones
– Increased need for crushed rock at the WTG’s located closest to the
main sub.
For most in-land WPP (100 ohm.m soils), the various ground potential
values would all have increased by approximately 124.7%.
15
16. • The % deviation in Zg as seen at the Main Substation (i.e.point
of fault), decreases with CCS compared to Copper with an
increase in soil resistivity. This means that the:
– impact of CCS conductor becomes more comparable to Copper as the
soil resistivity increases in ohm.m value.
• The % deviation in Zg as seen at the farthest WTG or Met
Mast, from the Main Substation decreases with CCS compared
to Copper with an increase in the value of soil resistivity.
– This means that for transfer potentials, CSS conductors performs
better than Copper conductors due the increase in their internal
impedance.
• The difference in electrical performance between 30%CCS and
40% CCS conductor is not significant.
16
17. 5- CONCLUSION
• Copper ground conductors offer better electrical
performance than CCS conductors.
– The difference in performance is though not so substantial (max
140.8% of increased GPR using CCS as compared to Copper during
extremely low soil resistivity conditions)
– In most cases this is manageable within the engineering design of
the windfarm grounding system.
• From an engineering design perspective, the impact of CCS
compared to Copper conductors are as follows:
– Possible need to install additional GPR control conductors, around
WTG’s, Junction Boxes or Met Masts to mitigate increased Touch &
Step Potential: Likelihood of having to install such additional
ground conductors is relatively low.
17
18. – Possible need to install crushed rock at more WTG’s, MV Junction
Boxes or Met Masts to mitigate increased Touch & Step Potential
– Possible need to undertake more detailed ground potential analysis
mitigate increased Touch & Step Potential.
– Increased likelihood that a project site will be subject to a “Hot”
Zone of Influence and an increase in the area size of that “Hot” Zone
of Influence. There is little that can be practically done to reduce the
size of the “Hot” Zone of Influence, beyond refining the desktop
design & analysis.
• The difference in electrical performance of 30% and 40%
conductivity CCS conductors is not significant,
– 40% CCS conductor product has a better protection of the inner
steel core against corrosion resulting from either soil chemistry, or
3rd party damage of the outer copper coating, and is recommended
over 30%CCS
18
19. Challenges for the Design of Wind and Solar Power
Plant Grounding System for Personal Safety
Applicability of Electrical Code (NESC/CEC) to WPP & Solar Power
Plant Grounding
IEEE PES 2016 General Meeting, Boston, MA, July 17‐21, 2016.
Presentation by:
Tracker Goree, Electrical Design Engineer, RES-Americas
Abdou Sana, P.Eng, Ph.D, Electrical Engineering Specialist, RES-Americas
1
25. Ground Impedance Calculations were done using an interconnected model both including
and excluding the bare ground conductor.
Split Factor Calculations were done for each location both including and excluding the
bare ground conductor.
The GPR was calculated as a product of the short circuit current, split factor, and ground
resistance.
GPR = I_ShC * L_f * S_f * Rg
I_ShC = Actual Short-circuit current
L_f = Load Growth Factor =110%
S_f = Split factor (calculated)
Rg = Ground grid resistance
Touch and Step voltages were calculated based on simulation plots as a percentage of
the GPR.
Vtouch = Vtouch% * GPR
Vstep = Vsep% * GPR
7
26. 8
Of the 42 locations evaluated: Roughly 50% of the locations considered were
unsafe without the use of crushed rock.
All Sites were safe when considered with the use of crushed rock.
27. This study was conducted using one median soil resistivity model with an average
of roughly 100 ohm-m.
If this resistivity is increased beyond 100 ohm-m what will be the effect?
Assumptions:
• Only the interconnected impedance was changed according to soil resistivity in the
calculation.
• Split factor and all other variables were considered to be the same for this exercise.
• Safety Criteria was held constant for this exercise.
9
28. 10
0
100
200
300
400
500
600
700
800
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Touch Voltage
Average Soil Resistivity
Average Soil Resistivity Vs Touch Voltage
With Bare GND
Conductor
Without Bare GND
Conductor
Safety Criteria
Without Crushed
Rock
Safety Criteria With
Crushed Rock
29. Main Implications of Rule for Solar and WPP
• It has been shown in this case study that if the grounding conductor is removed the
split factor, the network impedance and subsequently the GPR will increase. This
increase in GPR will consequently increase touch and step voltages. The higher the
soil resistivity is the greater this increase will be.
• This increase may motivate the need for mitigation measures in order to achieve
safety and this will have an associated cost impact.
• From an NESC applicability standpoint. Rule 354-D.2.a(3) is restrictive in enforcing
unjacketed concentric neutral or semi conducting jacket in-lieu of the trench
ground, however the study proves that under certain soil conditions (low rho and low
SC current) and/or with the use of crushed rock, the safety criteria can be met
without the trench conductor or the semi-conducting jacket or unjacketed concentric
neutral.
• For med. to high rho value soil safety can be difficult to achieve without costly
mitigation. In addition many wind turbine manufacturers local grounding or lightning
protection requirements will be difficult to meet at reasonable cost. (namely those of
IEC 61400-24).
• Further Analysis is needed to determine the effects of soil structure on this
comparison and to evaluate the economics associated with the various code
compliant solutions.
11
39. • Each remote grounding station has to be connected to the
substation by redundant paths which is either:
– a double ground conductor (bare or OHG) or
– a looped ground connection to the substation through 2 or more
circuits)
• If underground shielded cables (Concentric Neutral, tape
shield etc..) are used, the cable shield shall not be considered
a current return path (don’t count on it).
• If OHL are used, the neutral cannot be considered a sufficient
path for fault current return
• In addition, the grounding system shall exhibit a GPR < 5000V
and be safe (V_Step ≤ Safe V_Step; and V_Touch ≤ Safe
V_Touch)
21
44. Main Implications of OSC Rule 36‐302 (3)(a) for Solar & WPP
• Extraordinary cost increase especially on difficult soils
(500Ohm.m and above) up to 15,000$ per WTG
• Improved Personnel Safety ?
– Safety is achieved with standard calculations without need to apply
this Rule
– UG and OH systems layout are such that the ground conductor
cannot be severed without cutting the communication cable and
hence cannot be unnoticed. The intent of redundancy is thus
achieved through a careful and methodic trench and OHL layout.
– Even if the ground conductor is voluntarily severed without
touching the communication system, part of phase to ground
current will still flow in the concentric neutral and hence a split
factor should be allowed to be applied for the standalone cases.
– Due to inductive coupling and outer jacket insulation the split
factor component of the concentric neutral is more stable than that
of the bare ground conductor.
26
47. Project 'A' Windfarm
2
Project A Windfarm,
Ontario, Canada (2010/11), ( / )
98.9MW (43x 2.3MW turbines) project ~60km north‐east of
Thunder Bay. Project required 10.3km (49 spans) of new build
d l i it 230kV t i i li f th P i t Ofdual circuit 230kV transmission line from the new Point Of
Interconnection Switching Station (POI) to the new Windfarm
230/34.5kV Main Substation (WF Sub). RES were responsible for230/34.5kV Main Substation (WF Sub). RES were responsible for
all project electrical design works, inc. 230kV POI through to LV
terminals at base of each wind turbine.
51. Wide Range of Soil Resistivity
6
Wide Range of Soil Resistivity
Project 'A'
Range of Electrical Soil Resistivity:
From 230kV POI Switching Station to Windfarm 230/34.5kV Main Substation
100,000
g /
Windfarm Median
10,000
istivity
WF 230/34.5kV SUB
200m from SUB
400m from SUB
600m from SUB
800mfrom SUB
1,000
Electrical Soil Resi
(ohm‐m)
800m from SUB
1000m from SUB
3300m from SUB
Midway SWY/SUB
900m from SWY
1,000
790m from SWY
600m from SWY
420m from SWY
140m from SWY
60m from SWY
100
0.1 1.0 10.0 100.0
Average Electrode Spacing
(m)
POI 230kV SWY
52. Ground Electrodes
7
Ground Electrodes
b d l d d d ‘ ’ hWF Sub stand‐alone ground grid design = ‘Rg = 29.79Ω’ even with 6x 100m
vertical electrodes, reducing to ‘Zg+wf = 3.25 + j0.73Ω’ upon connection to
windfarm grounding system. WF Sub grid required to be designed stand‐alone
sufficient.
Grounding analysis software was used to model all ground electrode systems, g y g y ,
allowing full consideration of internal impedances.
RES specified installation of 2x low resistance OPGW sky wires and control ofRES specified installation of 2x low resistance OPGW sky wires, and control of
OHL pole ground electrode ‘Rtg’ values, to reduce current split factor (Sf) as
seen from both ends.
Rtg ≤95Ω ‐ except initial 7x poles out from POI Rtg ≤9Ω
53. Windfarm Sub Ground Grid
8
Windfarm Sub Ground Grid
-30
0 SOIL SURFACE
60
30
XIS(METERS)
90
ZAX
54
84
114
Y
AXIS
(M
ETE
120
-36
-6
24
TERS)
-30 0 30 60 90 120
XAXIS (METERS)
WF Sub Ground Grid – 3D View
XAXIS (METERS)
3-D View of Conductors
57. Standard v Optimised Design
12
Standard v Optimised Design
Applicable Standard and Code Requirements
If Rg Sf Ig GPR
Applicable Standard and Code Requirements
(A) (ohm) (%) (A) (V)
Ontario Electrical Safety Code (OESC) 24th Ed.: 2009 ‐ Rule 36‐304:
Standard GPR Limit
≤5,000
Ontario Electrical Safety Code (OESC) 24th Ed.: 2009 ‐ Rules 36‐304 & 2‐030:
E t d d GPR Li it P itt d d i ti ith itt OESA l
>5,000
Extended GPR Limit ‐ Permitted deviation with written OESA approval
,
IEEE 367: 1996 ‐ Clause 4.2 ‐ Possible high GPR under 'unusual circumstances' ≤25000
Calculation Methods
IEEE 80: 2000 ‐ Table C.1: 1x Transmission Line; 0x Distribution Lines
1x 7x #10 AWG (36 8mm²) Alumoweld (ACS) Shield Wire R 2 94Ω/km @ 20°C
18.20% 1,941 57,837
1x 7x #10 AWG (36.8mm²) Alumoweld (ACS) Shield Wire: Rac = 2.94Ω/km @ 20°C
IEEE 80: 2000 ‐ Table C.1: 2x Transmission Lines; 0x Distribution Lines
2x 7x #10 AWG (36.8mm²) Alumoweld (ACS) Shield Wire: Rac = 2.94Ω/km @ 20°C
10.00% 1,067 31,779
Calculated: 1x Single Circuit Transmission Line (Check against IEEE 80, Table C.1)
( ²) l ld ( ) h ld /k °
18.22% 1,943 57,88529.79
1x 7x #10 AWG (36.8mm²) Alumoweld (ACS) Shield Wire: Rac = 2.94Ω/km @ 20°C
8 % ,9 3 5 ,885
Calculated: 1x Dual Circuit Transmission Line
2x 7x #10 AWG (36.8mm²) Alumoweld (ACS) Shield Wire: Rac = 2.94Ω/km @ 20°C
13.10% 1,398 41,636
Calculated: 1x Dual Circuit Transmission Line ‐ Design approved by HONI & OESA
2x OPGW (129mm²) ACS/AA Shield Wire Rac 0 423Ω/km @ 20°C
5.82% 620 18,486
10,667
2x OPGW (129mm²) ACS/AA Shield Wire: Rac = 0.423Ω/km @ 20°C
Calculated: 1x Dual Circuit Transmission Line ‐ As‐Built approved by HONI & OESA
2x OPGW (129mm²) ACS/AA Shield Wire: Rac = 0.423Ω/km @ 20°C
21.40 6.17% 658 14,090
58. Design Validation
13
Design Validation
Following site testing of as‐built works, and using the same g g , g
grounding analysis software, RES undertook validation checks of
design calculations based on the as‐built ground electrode
resistance test data taken from the terminal substations and
each line pole. Both Design and As‐Built installation were
accepted and approved by HONI & OESAaccepted and approved by HONI & OESA.
59. Design Validation
14
Design Validation
50%20000
Project 'A'
Current Split Factor Curve ‐ 230/34.5kV Windfarm Sub
29.821.43.25 3.30
40%
45%
50%
16000
18000
20000
25%
30%
35%
10000
12000
14000
t Split Factor
(%)
Potential Rise
(volts)
10%
15%
20%
4000
6000
8000
Curren
Ground
(
0%
5%
10%
0
2000
4000
0.1 1.0 10.0 100.0
Earth Electrode Resistance seen at Windfarm Main Sub
(ohms)
OEB/HONI GPR [10.67kA] (Design) OEB/HONI GPR [10.67kA] (As‐Built) Max Actual GPR [3.16kA] (Design) Max Actual GPR [3.16kA] (As‐Built)
OESC 5000V (Design) Current Split Factor (Design) Current Split Factor (As‐Built) R Grid (Design)
R Grid (As‐Built) R Windfarm (Design) R Windfarm (As‐Built)
60. Conclusion
15
Conclusion
The grounding design criteria at Project 'A' WPP proved to be g g g j p
very challenging throughout, particularly at the 230kV terminal
substations. However, in‐depth modelling and analysis of the
230kV transmission line configuration, to accurately calculate
ground fault current split factors, demonstrated: excellent
correlation between IEEE 80 2000 Table C 1 values and analysiscorrelation between IEEE 80‐2000, Table C.1 values and analysis
results; opportunity to improve on standard split factor values
through in‐depth modelling of an enhanced OPGW conductor g p g
installation; very good validation of design values through
extensive on‐site testing prior to approval and commissioning.
All helping to provide a confident design solution, for a very
difficult grounding environment.