BUSBAR PROTECTION
Dinesh Kumar Sarda
A.Manager(MRSS)
CONTENTS
What is a bus bar?
Causes of fault
Suitable protection
Selection of CT ratios
Types of faults
Overcoming the faults
Dot convention or polarity marks
Why PS class is preferred over other protection class.
Stability ratio
Bus Bar Protection drawing of MRSS
Why is bus bar protection not in line at MRSS
Philosophy of pilot wire supervision relay
Conclusion
References
What is a bus bar?
• Bus is derived from
Latin word
“OMNIBUS”
(common for all)
• Nerve centre of the
power system
where various
circuits are
connected together.
CAUSES OF FAULT
• Breakdown of insulation because
of over voltages, foreign objects,
etc
• Weakening of insulation because
of ageing,corrosion,salty
water,etc.
Suitable Protection
• Differential protection
Why differential protection?
• Terminals of the system are near to each other.
• Hence by installing CT’s on the two sides of the
bus, comparison can be made between the
current entering it & leaving it. Any difference in
current will immediately signal an internal fault.
• The difference in current can be used to excite
the coil of a differential relay via CT secondary
and thus issue trip commands to CB on both
sides of the bus to isolate it.
Wrong method of CT ratios selection
That means the method of
selecting CT ratio on the basis of
maximum primary current seen by
an individual feeder is not correct.
Correct method of CT ratios selection
Selection of CT Ratios
CT ratios for all CT’s in bus
differential schemes is = (max out
of all feeder currents/1Aor 5A)
TYPES OF FAULTS
Faults may be broadly classified as
External Fault(through fault) &
Internal Fault.
Requirement of a unit protection is
that the differential scheme should
respond to internal faults and should
not respond to external fault.
Internal Fault
External Fault
The maloperation of bus bar differential
scheme on external faults is caused due
to non ideal behavior of CT carrying
excessive primary current, during fault
conditions.
• when due to external faults one of the CT’s get
saturated, the differential relay coil needs to be
restrained from tripping.
• We can easily accomplish this by connecting a
high resistance known as stabilizing resistance in
series with the differential relay coil
• The stabilizing resistance should be of such a
value,that under the worst case of maximum
external fault and full saturation of CT,the current
through differential coil is less than its pick up
value and at the same time it should respond to
minimum internal fault current.
CORRECTION
External & Internal Fault
Correction
DOT CONVENTION
• Dot markings are used to know the
direction of circulating current in the CT
secondary circuit.
• Rule of dot convention says that
“When current enters the dot mark on the
primary side of a CT, the current must
leave the similarly marked dot mark on the
secondary side & vice versa”.
WHY PS CLASS ONLY ?
Protection class CT’S such as 5P10,5P20 may
produce undesired difference current in the CT
secondary due to following reasons
1.Two or more CT’S of class 5P10 may have
different accuracy (in this case for 10 times the
rated current)
2.Even if the CT’S are identically manufactured,
deterioration of core properties over time may
differ & they may behave differently over time.
3. Distance of incoming side CT & outgoing side CT
may lead to difference in lead lengths, thus
imposing additional burden on CT’s, which may in
turn shift the saturation levels of the CT’s.
Owing to many other similar factors contributing to
maloperation of unit protection scheme when
conventional protection class CT’s( such as 5P10)
are employed, usage of a special protection class of
CT known as
“PS” class became popular.
FEATURES OF PS CLASS
1.Here instead of generalizing minimum
saturation level of a CT,the users have to
exactly specify the saturation level of the CT.
This is called as knee point voltage as it
appears as a human knee in CT
magnetization characteristics.
2. This specification will take into account the
maximum through fault current,the actual
lead burden,the relay burden,resistance of
the CT secondary winding & also a factor of
safety.
KNEE POINT CALCULATION
The minimum knee point voltage for a given PS class CT is
calculated by:
Vkp = K*If(s)*(Rct+Rb).
Vkp stands for knee point voltage.
If(s) stands for maximum through fault current as reflected at
the CT secondary terminals=If(s)/CT ratio.
Rct stands for CT winding secondary resistance.
Rb stands for connected burden(which includes the burden of
connecting leads & relay burden.
K stands for factor of safety (normally taken as 2).
i.e atleast upto 2 times the maximum possible through fault
current the CT would not saturate.
Stability Ratio
Ratio of max. ext. fault current for which
the scheme remains stable to the min. int.
fault current for which it operates
S = (IF,EXT,MAX)/(IF,INT,MIN)
PILOT WIRE SUPERVISION
USE OF METROSIL
• In some applications of high impedance
relays, the maximum internal fault current
can develop high voltages, that can damage
the relay insulation.
• A range of "METROSILS”(nonlinear
resistance) of 150 mm dia discs have been
developed to limit the voltage to safe levels.
• Choice of “METROSILS” depend on relay
setting, voltage & maximum internal fault
current
• Correct METROSIL selection ensures that
best protection is obtained, while
maintaining a metrosil leakage current low
enough to have negligible effect on the
accuracy of the relay at its maximum
setting voltage.
• Single disc METROSILS are suitable for
secondary internal fault current up to 50A
rms.
• METROSILS with multiple discs
connected in parallel are used for large
fault currents.
Why BUS BAR
PROTECTION
in MRSS is not in line
currently?
Conclusion
• Thus it is concluded that the bus bar
protection is an important part of the
power system, as the system voltage has
been increasing and short circuit
capacities are building up.
• So, it is not advisable to leave the bus
bars unprotected on a primary basis.
REFERENCES
• Fundamentals of power system protection
by Y.G.Paithankar & S.R.Bhide
• WWW.GOOGLE.COM

More Related Content

What's hot

Neutral grounding resistor
Neutral grounding resistorNeutral grounding resistor
Neutral grounding resistor
Nithin Kumar K S
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
moiz89
 

What's hot (20)

Distance protection scheme for transmission line using back propagation neura...
Distance protection scheme for transmission line using back propagation neura...Distance protection scheme for transmission line using back propagation neura...
Distance protection scheme for transmission line using back propagation neura...
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
24620708 feeder-protection (1)
24620708 feeder-protection (1)24620708 feeder-protection (1)
24620708 feeder-protection (1)
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
1 transmission
1 transmission1 transmission
1 transmission
 
7SS52 Distributed Bus Bar Diffrential Protection Relay
7SS52 Distributed Bus Bar Diffrential Protection Relay7SS52 Distributed Bus Bar Diffrential Protection Relay
7SS52 Distributed Bus Bar Diffrential Protection Relay
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Protection schemes and zones
Protection schemes and zonesProtection schemes and zones
Protection schemes and zones
 
Protection
ProtectionProtection
Protection
 
Neutral grounding resistor
Neutral grounding resistorNeutral grounding resistor
Neutral grounding resistor
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Designing and testing of metal oxide surge arrester for EHV line
Designing and testing of metal oxide surge arrester for EHV lineDesigning and testing of metal oxide surge arrester for EHV line
Designing and testing of metal oxide surge arrester for EHV line
 
Article
ArticleArticle
Article
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
surge diverters
surge diverterssurge diverters
surge diverters
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 

Similar to 7edbbe03 1919-4c98-b064-507ff7c76729-141210052746-conversion-gate01

Unwanted blocking of diffrential protection during converter transformer inte...
Unwanted blocking of diffrential protection during converter transformer inte...Unwanted blocking of diffrential protection during converter transformer inte...
Unwanted blocking of diffrential protection during converter transformer inte...
Power System Operation
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
Ronald Santos
 

Similar to 7edbbe03 1919-4c98-b064-507ff7c76729-141210052746-conversion-gate01 (20)

BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Busbar protection LEC 2.pptx
Busbar protection LEC 2.pptxBusbar protection LEC 2.pptx
Busbar protection LEC 2.pptx
 
Busbar protection LEC 1
Busbar protection  LEC 1Busbar protection  LEC 1
Busbar protection LEC 1
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Proposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorProposal Technique for an Static Var Compensator
Proposal Technique for an Static Var Compensator
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
s.pdf
s.pdfs.pdf
s.pdf
 
Bc36330333
Bc36330333Bc36330333
Bc36330333
 
transformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppttransformerdesignandprotection-130408132534-phpapp02.ppt
transformerdesignandprotection-130408132534-phpapp02.ppt
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Unwanted blocking of diffrential protection during converter transformer inte...
Unwanted blocking of diffrential protection during converter transformer inte...Unwanted blocking of diffrential protection during converter transformer inte...
Unwanted blocking of diffrential protection during converter transformer inte...
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 
Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)Bus ele tech_lib_short_circuit_current_calculations (1)
Bus ele tech_lib_short_circuit_current_calculations (1)
 
C0212014018
C0212014018C0212014018
C0212014018
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 

More from HAYMANOTTAKELE1 (6)

20160104 pwr-sys-fund-relay-applications
20160104 pwr-sys-fund-relay-applications20160104 pwr-sys-fund-relay-applications
20160104 pwr-sys-fund-relay-applications
 
20160104 pwr-sys-fund-relay-applications (1)
20160104 pwr-sys-fund-relay-applications (1)20160104 pwr-sys-fund-relay-applications (1)
20160104 pwr-sys-fund-relay-applications (1)
 
6843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web26843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web2
 
11 webinar-directional-overcurrent-relaying
11 webinar-directional-overcurrent-relaying11 webinar-directional-overcurrent-relaying
11 webinar-directional-overcurrent-relaying
 
29
2929
29
 
Chapter 1 4
Chapter 1 4Chapter 1 4
Chapter 1 4
 

Recently uploaded

Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 

Recently uploaded (20)

Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 

7edbbe03 1919-4c98-b064-507ff7c76729-141210052746-conversion-gate01

  • 1. BUSBAR PROTECTION Dinesh Kumar Sarda A.Manager(MRSS)
  • 2. CONTENTS What is a bus bar? Causes of fault Suitable protection Selection of CT ratios Types of faults Overcoming the faults Dot convention or polarity marks Why PS class is preferred over other protection class. Stability ratio Bus Bar Protection drawing of MRSS Why is bus bar protection not in line at MRSS Philosophy of pilot wire supervision relay Conclusion References
  • 3. What is a bus bar? • Bus is derived from Latin word “OMNIBUS” (common for all) • Nerve centre of the power system where various circuits are connected together.
  • 4. CAUSES OF FAULT • Breakdown of insulation because of over voltages, foreign objects, etc • Weakening of insulation because of ageing,corrosion,salty water,etc.
  • 5. Suitable Protection • Differential protection Why differential protection? • Terminals of the system are near to each other. • Hence by installing CT’s on the two sides of the bus, comparison can be made between the current entering it & leaving it. Any difference in current will immediately signal an internal fault. • The difference in current can be used to excite the coil of a differential relay via CT secondary and thus issue trip commands to CB on both sides of the bus to isolate it.
  • 6. Wrong method of CT ratios selection
  • 7. That means the method of selecting CT ratio on the basis of maximum primary current seen by an individual feeder is not correct.
  • 8. Correct method of CT ratios selection
  • 9. Selection of CT Ratios CT ratios for all CT’s in bus differential schemes is = (max out of all feeder currents/1Aor 5A)
  • 10. TYPES OF FAULTS Faults may be broadly classified as External Fault(through fault) & Internal Fault. Requirement of a unit protection is that the differential scheme should respond to internal faults and should not respond to external fault.
  • 13. The maloperation of bus bar differential scheme on external faults is caused due to non ideal behavior of CT carrying excessive primary current, during fault conditions.
  • 14. • when due to external faults one of the CT’s get saturated, the differential relay coil needs to be restrained from tripping. • We can easily accomplish this by connecting a high resistance known as stabilizing resistance in series with the differential relay coil • The stabilizing resistance should be of such a value,that under the worst case of maximum external fault and full saturation of CT,the current through differential coil is less than its pick up value and at the same time it should respond to minimum internal fault current. CORRECTION
  • 15. External & Internal Fault Correction
  • 16. DOT CONVENTION • Dot markings are used to know the direction of circulating current in the CT secondary circuit. • Rule of dot convention says that “When current enters the dot mark on the primary side of a CT, the current must leave the similarly marked dot mark on the secondary side & vice versa”.
  • 17. WHY PS CLASS ONLY ? Protection class CT’S such as 5P10,5P20 may produce undesired difference current in the CT secondary due to following reasons 1.Two or more CT’S of class 5P10 may have different accuracy (in this case for 10 times the rated current) 2.Even if the CT’S are identically manufactured, deterioration of core properties over time may differ & they may behave differently over time.
  • 18. 3. Distance of incoming side CT & outgoing side CT may lead to difference in lead lengths, thus imposing additional burden on CT’s, which may in turn shift the saturation levels of the CT’s. Owing to many other similar factors contributing to maloperation of unit protection scheme when conventional protection class CT’s( such as 5P10) are employed, usage of a special protection class of CT known as “PS” class became popular.
  • 19. FEATURES OF PS CLASS 1.Here instead of generalizing minimum saturation level of a CT,the users have to exactly specify the saturation level of the CT. This is called as knee point voltage as it appears as a human knee in CT magnetization characteristics. 2. This specification will take into account the maximum through fault current,the actual lead burden,the relay burden,resistance of the CT secondary winding & also a factor of safety.
  • 20. KNEE POINT CALCULATION The minimum knee point voltage for a given PS class CT is calculated by: Vkp = K*If(s)*(Rct+Rb). Vkp stands for knee point voltage. If(s) stands for maximum through fault current as reflected at the CT secondary terminals=If(s)/CT ratio. Rct stands for CT winding secondary resistance. Rb stands for connected burden(which includes the burden of connecting leads & relay burden. K stands for factor of safety (normally taken as 2). i.e atleast upto 2 times the maximum possible through fault current the CT would not saturate.
  • 21. Stability Ratio Ratio of max. ext. fault current for which the scheme remains stable to the min. int. fault current for which it operates S = (IF,EXT,MAX)/(IF,INT,MIN)
  • 22.
  • 23.
  • 24.
  • 26. USE OF METROSIL • In some applications of high impedance relays, the maximum internal fault current can develop high voltages, that can damage the relay insulation. • A range of "METROSILS”(nonlinear resistance) of 150 mm dia discs have been developed to limit the voltage to safe levels. • Choice of “METROSILS” depend on relay setting, voltage & maximum internal fault current
  • 27. • Correct METROSIL selection ensures that best protection is obtained, while maintaining a metrosil leakage current low enough to have negligible effect on the accuracy of the relay at its maximum setting voltage. • Single disc METROSILS are suitable for secondary internal fault current up to 50A rms. • METROSILS with multiple discs connected in parallel are used for large fault currents.
  • 28. Why BUS BAR PROTECTION in MRSS is not in line currently?
  • 29. Conclusion • Thus it is concluded that the bus bar protection is an important part of the power system, as the system voltage has been increasing and short circuit capacities are building up. • So, it is not advisable to leave the bus bars unprotected on a primary basis.
  • 30. REFERENCES • Fundamentals of power system protection by Y.G.Paithankar & S.R.Bhide • WWW.GOOGLE.COM