SlideShare a Scribd company logo
1 of 7
OPERATING LIMITATIONS
OBJECTIVES
(1) Explain how a generator output is limited by:
a) Rotor heating
b) Stator winding heating
c) Stability
d) Core end heating
e) Stator core heating
(2) Explain the precautions that must be taken to ensure the limitations listed above are
not exceeded and the consequences of exceeding each of these limitations.
INTRODUCTION
This lesson explains the generator thermal or heating limitations and relates these
limitations to the generator capability curves. The lesson also explains the precautions
that must be taken to ensure the limits are not exceeded and the consequences of-
exceeding the limits.
GENERATOR LIMITATIONS
Figure 1 shows the operating limitations, usually referred to as the ‘capability
curves’ for a generator. These capability curves are shown by the heavy black lines. Full
rated output of 540 MW, 24 Kv at 0.85 pf (lag) is achieved without exceeding any of the
generators limitations.
Examination of these curves will show that they define four of the five limitations
stated in the objectives:
a) Rotor heating
b) Stator winding heating
c) Stability
d) Core end heating
— 1 —
Q-P CAPABILITY CURVE WITH OP. LIMITS
•H2 has 6
times the
thermal
conductivity
of air.
•Low density
decreases
windage.
Figure 1: GENERATOR CAPABILITY CURVES
Rotor Heating Limitation
The rotors of large generators (typically above 60 MW) are hydrogen cooled. For
reliable operation, it is essential that at all times, the temperature of the rotor conductors
and insulation is not exceeded. An indication of the rotor temperature can be obtained
from the temperature of the hydrogen cooling gas as it returns to the coolers. An accurate
method rotor conductor temperature measurement is obtained from the rotor temperature
indicator. This indicator computes the temperature from the change in resistance of the
rotor winding.
Exceeding the rotor temperature will shorten the life of the insulation. Differential
expansion, due to excessive temperature differences between the rotor copper and rotor
iron components may cause cracking of the rotor copper or insulation.
— 2 —
Stator Winding Heating Limits
Figure 1 shows that when the generator is producing 800 MW at 0.85 pf lag with
520 KPa hydrogen pressure, the generator stator conductors are operating at their thermal
limit. This limit is due to the 12
R heating in the stator conductors. If the generator power
factor is altered to a value nearer 1.0, then due to the lower stator current, the generator
stator conductors would be operating well within their thermal limit. Provided the turbine
could produce the necessary power, the generator could produce about 1000 MW at 1.0
pf with 520 KPa hydrogen pressure before the stator conductor thermal limit is reached.
The temperature of the stator conductors is monitored by measuring the
temperature of coolant leaving the conductors. Exceeding the rated temperature will
shorten insulation life. Excessive differential expansion between the copper conductors
can cause cracking of the copper conductors and/or insulation.
Stability Limit
When a generator is operating at a leading power factor, the excitation and hence
the flux produced by the rotor is weak. Consequently the magnetic coupling between
rotor and stator rotating magnetic fields is also weak. If the generator is loaded under this
condition, a large load angle (rotor angle) is produced. When this load angle reaches 90°,
the generator is producing the maximum amount of power for the excitation being used
and is said to be operating at its steady state stability limit. Any further increase in load
will cause the magnetic fluxes to stretch further and the load angle to increase further. A
point is reached when the rotor is at the 180° position, see Figure 3, where there is no
magnetic coupling between the rotor and stator. When this occurs, the rotor will speed up
and the generator, instead of giving a steady output, will only give surges of power as the
rotor N pole passes the stator S pole. This effect is known as “pole slipping” and the
generator is now unstable.
Figure 2: Generator rotor at stability limit 90° Figure 3: Generator unstable
Rotor at180°.
— 3—
It is very bad operating practice to allow a generator to pole slip. The large surges
of power, from a mechanical point of view, put great strain on the generator to turbine
coupling, the bearings and foundations. From an electrical point of view the surges of
power will cause current surges and hence magnetic stresses to all load carrying
components. These surges of power will also cause the voltages to fluctuate rapidly and
cause lights to flash. Should instability occur, automatic protection trips the turbine. This
protection operates when the generators power factor becomes excessively leading.
To make sure that the generator will remain stable, it must not be operated with more
leading vars than is shown by the stability limit line.
Stator Core End Heating Limits
When a generator is operating at unity or lagging power factor, a strong flux is
produced by the rotor. Under this condition, little flux is able to leak out from the ends of
the stator core and there is no excessive heating at the core ends.
When the generator is operating at a leading power factor, the flux produced by
the rotor is weaker and more flux is able to leak out from the ends of the stator core.
When this flux leaks out front the ends of the stator core, it passes through the face of
each lamination and causes large eddy currents to flow in these laminations. These eddy
currents can cause excessive heating. To minimize heating at the ends of the core, two
techniques are employed. ‘they are:
(a) Extra cooling ducts are provided at the ends of the core. These ducts allow the
hydrogen to remove the additional heat produced in the iron.
(b) Copper screens, are employed. These screens, which are water cooled in Parsons
generators, have currents induced in them by the fluxes passing out from the end of the
core. The currents in the copper screen produce fluxes which due to Lenz’s law, oppose
the fluxes coming out of the end of the core. To a great extent, the fluxes leaking from the
ends at the core are forced to take a path which gives a better flux pattern through the iron
at the end of the core. Less core end heating results. Figure 4 shows typical curves of
relative heating of stator core ends versus power factor for a generator operating at 100%
full load MVA and 80% full load MVA.
—4—
.2 .4 .6 .8 1 .8 .6 .4 .2
Lead Lag
Figure 4: Curves of relative heating of stator core ends versus power factor
Stator Core Heating
The stator core heating limitation is not shown on Figure 1. It should be
remembered that the voltage output VT for a generator is governed by the relationship:
VT α N Φmf
Where: N is the number of turns,
Φm is the maximum value of rotor flux
f is the frequency
—5—
As the frequency and number of turns are fixed, then the voltage output is proportional to
the flux, ie, VT α Φm . The flux in a generator must not be kept at a value greater than
10% above normal for more than a few minutes. It follows then that the terminal voltage
of a generator should not be kept appreciably above its rated value for any significant
length of time. This will prevent excess heating due to eddy currents and hysterisis in the
stator iron laminations. If the flux and hence the voltage in the generator is higher than
normal, the flux in the transformers connected to the generators will also be higher than
normal. The cores of these transformers can easily be damaged due to over-fluxing.
Excessive voltages produced by the generator will also stress the insulation of all
electrical components in the generator and components connected to the generator. This
stressing of the insulation is usually a minor problem compared with the magnetic
stressing and heating of the iron.
SUMMARY
From an operational viewpoint, a generator is normally operated within its
operational area shown by Figure 1. With full power output at 0.85 pf lag, the generator
is operating at the thermal limits quoted by the manufacturer. These thermal limits
assume that the cooling water is at the maximum temperature (40°C) that can be expected
in service. If any of the thermal limits are exceeded, the life of some components, in
particular the insulation, will be reduced. As a rough estimate, the life of insulation is
halved for each 10°C rise in temperature above the design value.
Increasing gas pressure will increase the generators thermal capabilities. It will not
increase the generators stability capabilities.
Therefore, for a generator operating at its rated speed (frequency) the
(a) MW output is limited by turbine output and stator conductor heating.
(b) Mvar output (lag) is limited by the rotor heating.
(c) Mvar output (lead) is limited by stator core end heating and also by stability
considerations.
(d) Terminal voltage output is limited by the heating of the stator iron core, as distinct
from the core end heating.
(e) The maximum permissible continuous field current specified by the manufacturer.
REFERENCES
For further reading reference may be made to “Modern Power Station Practice, Volume
7, Chapter 2.
—6—
As the frequency and number of turns are fixed, then the voltage output is proportional to
the flux, ie, VT α Φm . The flux in a generator must not be kept at a value greater than
10% above normal for more than a few minutes. It follows then that the terminal voltage
of a generator should not be kept appreciably above its rated value for any significant
length of time. This will prevent excess heating due to eddy currents and hysterisis in the
stator iron laminations. If the flux and hence the voltage in the generator is higher than
normal, the flux in the transformers connected to the generators will also be higher than
normal. The cores of these transformers can easily be damaged due to over-fluxing.
Excessive voltages produced by the generator will also stress the insulation of all
electrical components in the generator and components connected to the generator. This
stressing of the insulation is usually a minor problem compared with the magnetic
stressing and heating of the iron.
SUMMARY
From an operational viewpoint, a generator is normally operated within its
operational area shown by Figure 1. With full power output at 0.85 pf lag, the generator
is operating at the thermal limits quoted by the manufacturer. These thermal limits
assume that the cooling water is at the maximum temperature (40°C) that can be expected
in service. If any of the thermal limits are exceeded, the life of some components, in
particular the insulation, will be reduced. As a rough estimate, the life of insulation is
halved for each 10°C rise in temperature above the design value.
Increasing gas pressure will increase the generators thermal capabilities. It will not
increase the generators stability capabilities.
Therefore, for a generator operating at its rated speed (frequency) the
(a) MW output is limited by turbine output and stator conductor heating.
(b) Mvar output (lag) is limited by the rotor heating.
(c) Mvar output (lead) is limited by stator core end heating and also by stability
considerations.
(d) Terminal voltage output is limited by the heating of the stator iron core, as distinct
from the core end heating.
(e) The maximum permissible continuous field current specified by the manufacturer.
REFERENCES
For further reading reference may be made to “Modern Power Station Practice, Volume
7, Chapter 2.
—6—

More Related Content

What's hot

Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 
Genrator Relay Protection & Logics
Genrator Relay Protection & LogicsGenrator Relay Protection & Logics
Genrator Relay Protection & Logics
Mahadev Kovalli
 

What's hot (20)

Excitation System & capability curve of synchronous generator
Excitation System &  capability curve of synchronous generatorExcitation System &  capability curve of synchronous generator
Excitation System & capability curve of synchronous generator
 
SWITCHGEAR AND PROTECTION, STARTING OF 3 PHASE INDUCTION MOTOR
SWITCHGEAR AND PROTECTION, STARTING OF 3 PHASE INDUCTION MOTORSWITCHGEAR AND PROTECTION, STARTING OF 3 PHASE INDUCTION MOTOR
SWITCHGEAR AND PROTECTION, STARTING OF 3 PHASE INDUCTION MOTOR
 
Seminario eficiencia energetica electrica Fluke
Seminario eficiencia energetica electrica FlukeSeminario eficiencia energetica electrica Fluke
Seminario eficiencia energetica electrica Fluke
 
Motor Test (Induction motor)
Motor Test (Induction motor)Motor Test (Induction motor)
Motor Test (Induction motor)
 
Switchgear and protection 2
Switchgear and protection 2Switchgear and protection 2
Switchgear and protection 2
 
synchronous motor for presentation
 synchronous motor for presentation synchronous motor for presentation
synchronous motor for presentation
 
Breaking,Types of Electrical Braking system, Regenerative Braking, Plugging ...
Breaking,Types of Electrical Braking system, Regenerative Braking,  Plugging ...Breaking,Types of Electrical Braking system, Regenerative Braking,  Plugging ...
Breaking,Types of Electrical Braking system, Regenerative Braking, Plugging ...
 
The squirrel-cage induction motor
The squirrel-cage induction motorThe squirrel-cage induction motor
The squirrel-cage induction motor
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordination
 
moving iron instrument
 moving iron instrument moving iron instrument
moving iron instrument
 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
 
MTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptxMTA GENERATOR PROTECTION .PPT.pptx
MTA GENERATOR PROTECTION .PPT.pptx
 
armature Winding
armature Windingarmature Winding
armature Winding
 
3 ph induction motor ppt
3 ph induction motor ppt3 ph induction motor ppt
3 ph induction motor ppt
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
MOTOR STARTER
MOTOR STARTERMOTOR STARTER
MOTOR STARTER
 
Transformer 2
Transformer 2Transformer 2
Transformer 2
 
Curvas de magnetizacion del transformador
Curvas de magnetizacion del transformadorCurvas de magnetizacion del transformador
Curvas de magnetizacion del transformador
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Genrator Relay Protection & Logics
Genrator Relay Protection & LogicsGenrator Relay Protection & Logics
Genrator Relay Protection & Logics
 

Similar to (9) Synchronous Alternator Capability Graph

Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentation
Ramendra Dhiman
 

Similar to (9) Synchronous Alternator Capability Graph (20)

(9) limitations
(9) limitations(9) limitations
(9) limitations
 
GenDesign
GenDesignGenDesign
GenDesign
 
Generator capability curve
Generator capability curve Generator capability curve
Generator capability curve
 
Design turbo generator
Design turbo generatorDesign turbo generator
Design turbo generator
 
(7) overfluxing
(7) overfluxing(7) overfluxing
(7) overfluxing
 
Equipment and Stability Constraints : System Operation
Equipment and Stability Constraints : System OperationEquipment and Stability Constraints : System Operation
Equipment and Stability Constraints : System Operation
 
Manfacturing of turbo generators at BHEL
Manfacturing of turbo generators at BHELManfacturing of turbo generators at BHEL
Manfacturing of turbo generators at BHEL
 
diesel generator
diesel generatordiesel generator
diesel generator
 
F:\Ac Generator Ppt
F:\Ac Generator PptF:\Ac Generator Ppt
F:\Ac Generator Ppt
 
Experiment 2 AC Machines
Experiment 2 AC MachinesExperiment 2 AC Machines
Experiment 2 AC Machines
 
Electrical and electronics form five notes
Electrical and electronics form five notesElectrical and electronics form five notes
Electrical and electronics form five notes
 
Cooling turbines blade system in hydraulic power plants
Cooling turbines blade  system in hydraulic power plants  Cooling turbines blade  system in hydraulic power plants
Cooling turbines blade system in hydraulic power plants
 
Electrical machines lecture notes
Electrical machines lecture notesElectrical machines lecture notes
Electrical machines lecture notes
 
welding and welding transformer
welding and welding transformerwelding and welding transformer
welding and welding transformer
 
Ac generator
Ac generatorAc generator
Ac generator
 
BHELppt
BHELpptBHELppt
BHELppt
 
Ac generator
Ac generatorAc generator
Ac generator
 
5.2.c gen basics
5.2.c gen basics5.2.c gen basics
5.2.c gen basics
 
ELEKTRA_new
ELEKTRA_newELEKTRA_new
ELEKTRA_new
 
Ramendra summer training presentation
Ramendra summer training presentationRamendra summer training presentation
Ramendra summer training presentation
 

More from Daniel Gray (8)

Electrical Theory Review
Electrical Theory ReviewElectrical Theory Review
Electrical Theory Review
 
Power factor correction formula
Power factor correction formulaPower factor correction formula
Power factor correction formula
 
Electrical power and power factor
Electrical power and power factorElectrical power and power factor
Electrical power and power factor
 
(8) loading
(8) loading(8) loading
(8) loading
 
(4) synch
(4) synch(4) synch
(4) synch
 
(10) stability
(10) stability(10) stability
(10) stability
 
(5) infinite
(5) infinite(5) infinite
(5) infinite
 
(6) finite
(6) finite(6) finite
(6) finite
 

Recently uploaded

The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
heathfieldcps1
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
heathfieldcps1
 

Recently uploaded (20)

psychiatric nursing HISTORY COLLECTION .docx
psychiatric  nursing HISTORY  COLLECTION  .docxpsychiatric  nursing HISTORY  COLLECTION  .docx
psychiatric nursing HISTORY COLLECTION .docx
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
TỔNG ÔN TẬP THI VÀO LỚP 10 MÔN TIẾNG ANH NĂM HỌC 2023 - 2024 CÓ ĐÁP ÁN (NGỮ Â...
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Key note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdfKey note speaker Neum_Admir Softic_ENG.pdf
Key note speaker Neum_Admir Softic_ENG.pdf
 
The basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptxThe basics of sentences session 3pptx.pptx
The basics of sentences session 3pptx.pptx
 
Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024
 
Food Chain and Food Web (Ecosystem) EVS, B. Pharmacy 1st Year, Sem-II
Food Chain and Food Web (Ecosystem) EVS, B. Pharmacy 1st Year, Sem-IIFood Chain and Food Web (Ecosystem) EVS, B. Pharmacy 1st Year, Sem-II
Food Chain and Food Web (Ecosystem) EVS, B. Pharmacy 1st Year, Sem-II
 
ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701ComPTIA Overview | Comptia Security+ Book SY0-701
ComPTIA Overview | Comptia Security+ Book SY0-701
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
Micro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdfMicro-Scholarship, What it is, How can it help me.pdf
Micro-Scholarship, What it is, How can it help me.pdf
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot Graph
 
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptxBasic Civil Engineering first year Notes- Chapter 4 Building.pptx
Basic Civil Engineering first year Notes- Chapter 4 Building.pptx
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
Class 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdfClass 11th Physics NEET formula sheet pdf
Class 11th Physics NEET formula sheet pdf
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...
Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...
Ecological Succession. ( ECOSYSTEM, B. Pharmacy, 1st Year, Sem-II, Environmen...
 

(9) Synchronous Alternator Capability Graph

  • 1. OPERATING LIMITATIONS OBJECTIVES (1) Explain how a generator output is limited by: a) Rotor heating b) Stator winding heating c) Stability d) Core end heating e) Stator core heating (2) Explain the precautions that must be taken to ensure the limitations listed above are not exceeded and the consequences of exceeding each of these limitations. INTRODUCTION This lesson explains the generator thermal or heating limitations and relates these limitations to the generator capability curves. The lesson also explains the precautions that must be taken to ensure the limits are not exceeded and the consequences of- exceeding the limits. GENERATOR LIMITATIONS Figure 1 shows the operating limitations, usually referred to as the ‘capability curves’ for a generator. These capability curves are shown by the heavy black lines. Full rated output of 540 MW, 24 Kv at 0.85 pf (lag) is achieved without exceeding any of the generators limitations. Examination of these curves will show that they define four of the five limitations stated in the objectives: a) Rotor heating b) Stator winding heating c) Stability d) Core end heating — 1 —
  • 2. Q-P CAPABILITY CURVE WITH OP. LIMITS •H2 has 6 times the thermal conductivity of air. •Low density decreases windage. Figure 1: GENERATOR CAPABILITY CURVES Rotor Heating Limitation The rotors of large generators (typically above 60 MW) are hydrogen cooled. For reliable operation, it is essential that at all times, the temperature of the rotor conductors and insulation is not exceeded. An indication of the rotor temperature can be obtained from the temperature of the hydrogen cooling gas as it returns to the coolers. An accurate method rotor conductor temperature measurement is obtained from the rotor temperature indicator. This indicator computes the temperature from the change in resistance of the rotor winding. Exceeding the rotor temperature will shorten the life of the insulation. Differential expansion, due to excessive temperature differences between the rotor copper and rotor iron components may cause cracking of the rotor copper or insulation. — 2 —
  • 3. Stator Winding Heating Limits Figure 1 shows that when the generator is producing 800 MW at 0.85 pf lag with 520 KPa hydrogen pressure, the generator stator conductors are operating at their thermal limit. This limit is due to the 12 R heating in the stator conductors. If the generator power factor is altered to a value nearer 1.0, then due to the lower stator current, the generator stator conductors would be operating well within their thermal limit. Provided the turbine could produce the necessary power, the generator could produce about 1000 MW at 1.0 pf with 520 KPa hydrogen pressure before the stator conductor thermal limit is reached. The temperature of the stator conductors is monitored by measuring the temperature of coolant leaving the conductors. Exceeding the rated temperature will shorten insulation life. Excessive differential expansion between the copper conductors can cause cracking of the copper conductors and/or insulation. Stability Limit When a generator is operating at a leading power factor, the excitation and hence the flux produced by the rotor is weak. Consequently the magnetic coupling between rotor and stator rotating magnetic fields is also weak. If the generator is loaded under this condition, a large load angle (rotor angle) is produced. When this load angle reaches 90°, the generator is producing the maximum amount of power for the excitation being used and is said to be operating at its steady state stability limit. Any further increase in load will cause the magnetic fluxes to stretch further and the load angle to increase further. A point is reached when the rotor is at the 180° position, see Figure 3, where there is no magnetic coupling between the rotor and stator. When this occurs, the rotor will speed up and the generator, instead of giving a steady output, will only give surges of power as the rotor N pole passes the stator S pole. This effect is known as “pole slipping” and the generator is now unstable. Figure 2: Generator rotor at stability limit 90° Figure 3: Generator unstable Rotor at180°. — 3—
  • 4. It is very bad operating practice to allow a generator to pole slip. The large surges of power, from a mechanical point of view, put great strain on the generator to turbine coupling, the bearings and foundations. From an electrical point of view the surges of power will cause current surges and hence magnetic stresses to all load carrying components. These surges of power will also cause the voltages to fluctuate rapidly and cause lights to flash. Should instability occur, automatic protection trips the turbine. This protection operates when the generators power factor becomes excessively leading. To make sure that the generator will remain stable, it must not be operated with more leading vars than is shown by the stability limit line. Stator Core End Heating Limits When a generator is operating at unity or lagging power factor, a strong flux is produced by the rotor. Under this condition, little flux is able to leak out from the ends of the stator core and there is no excessive heating at the core ends. When the generator is operating at a leading power factor, the flux produced by the rotor is weaker and more flux is able to leak out from the ends of the stator core. When this flux leaks out front the ends of the stator core, it passes through the face of each lamination and causes large eddy currents to flow in these laminations. These eddy currents can cause excessive heating. To minimize heating at the ends of the core, two techniques are employed. ‘they are: (a) Extra cooling ducts are provided at the ends of the core. These ducts allow the hydrogen to remove the additional heat produced in the iron. (b) Copper screens, are employed. These screens, which are water cooled in Parsons generators, have currents induced in them by the fluxes passing out from the end of the core. The currents in the copper screen produce fluxes which due to Lenz’s law, oppose the fluxes coming out of the end of the core. To a great extent, the fluxes leaking from the ends at the core are forced to take a path which gives a better flux pattern through the iron at the end of the core. Less core end heating results. Figure 4 shows typical curves of relative heating of stator core ends versus power factor for a generator operating at 100% full load MVA and 80% full load MVA. —4—
  • 5. .2 .4 .6 .8 1 .8 .6 .4 .2 Lead Lag Figure 4: Curves of relative heating of stator core ends versus power factor Stator Core Heating The stator core heating limitation is not shown on Figure 1. It should be remembered that the voltage output VT for a generator is governed by the relationship: VT α N Φmf Where: N is the number of turns, Φm is the maximum value of rotor flux f is the frequency —5—
  • 6. As the frequency and number of turns are fixed, then the voltage output is proportional to the flux, ie, VT α Φm . The flux in a generator must not be kept at a value greater than 10% above normal for more than a few minutes. It follows then that the terminal voltage of a generator should not be kept appreciably above its rated value for any significant length of time. This will prevent excess heating due to eddy currents and hysterisis in the stator iron laminations. If the flux and hence the voltage in the generator is higher than normal, the flux in the transformers connected to the generators will also be higher than normal. The cores of these transformers can easily be damaged due to over-fluxing. Excessive voltages produced by the generator will also stress the insulation of all electrical components in the generator and components connected to the generator. This stressing of the insulation is usually a minor problem compared with the magnetic stressing and heating of the iron. SUMMARY From an operational viewpoint, a generator is normally operated within its operational area shown by Figure 1. With full power output at 0.85 pf lag, the generator is operating at the thermal limits quoted by the manufacturer. These thermal limits assume that the cooling water is at the maximum temperature (40°C) that can be expected in service. If any of the thermal limits are exceeded, the life of some components, in particular the insulation, will be reduced. As a rough estimate, the life of insulation is halved for each 10°C rise in temperature above the design value. Increasing gas pressure will increase the generators thermal capabilities. It will not increase the generators stability capabilities. Therefore, for a generator operating at its rated speed (frequency) the (a) MW output is limited by turbine output and stator conductor heating. (b) Mvar output (lag) is limited by the rotor heating. (c) Mvar output (lead) is limited by stator core end heating and also by stability considerations. (d) Terminal voltage output is limited by the heating of the stator iron core, as distinct from the core end heating. (e) The maximum permissible continuous field current specified by the manufacturer. REFERENCES For further reading reference may be made to “Modern Power Station Practice, Volume 7, Chapter 2. —6—
  • 7. As the frequency and number of turns are fixed, then the voltage output is proportional to the flux, ie, VT α Φm . The flux in a generator must not be kept at a value greater than 10% above normal for more than a few minutes. It follows then that the terminal voltage of a generator should not be kept appreciably above its rated value for any significant length of time. This will prevent excess heating due to eddy currents and hysterisis in the stator iron laminations. If the flux and hence the voltage in the generator is higher than normal, the flux in the transformers connected to the generators will also be higher than normal. The cores of these transformers can easily be damaged due to over-fluxing. Excessive voltages produced by the generator will also stress the insulation of all electrical components in the generator and components connected to the generator. This stressing of the insulation is usually a minor problem compared with the magnetic stressing and heating of the iron. SUMMARY From an operational viewpoint, a generator is normally operated within its operational area shown by Figure 1. With full power output at 0.85 pf lag, the generator is operating at the thermal limits quoted by the manufacturer. These thermal limits assume that the cooling water is at the maximum temperature (40°C) that can be expected in service. If any of the thermal limits are exceeded, the life of some components, in particular the insulation, will be reduced. As a rough estimate, the life of insulation is halved for each 10°C rise in temperature above the design value. Increasing gas pressure will increase the generators thermal capabilities. It will not increase the generators stability capabilities. Therefore, for a generator operating at its rated speed (frequency) the (a) MW output is limited by turbine output and stator conductor heating. (b) Mvar output (lag) is limited by the rotor heating. (c) Mvar output (lead) is limited by stator core end heating and also by stability considerations. (d) Terminal voltage output is limited by the heating of the stator iron core, as distinct from the core end heating. (e) The maximum permissible continuous field current specified by the manufacturer. REFERENCES For further reading reference may be made to “Modern Power Station Practice, Volume 7, Chapter 2. —6—