OVERFLUXING
OBJECTIVES
1. Explain the two conditions which can cause over-fluxing in a generator and its
associated transformers.
2. Explain how a generator can be damaged by over-fluxing.
3. Explain how a transformer can be damaged by over-fluxing.
INTRODUCTION
It is possible to damage a generator and its associated main and auxiliary
transformers by what is known as over-fluxing. Over-fluxing occurs when a generator or
a transformer is subjected flux levels which are above the permissible limits. Over-
fluxing can occur when a generator or transformer is made to:
(a) produce rated voltage at below rated speed (frequency).
(b) produce greater than rated voltage at rated speed (frequency).
Because of the two problems outlined above, great care must be taken to ensure that
(a) a generator is at or close to operating speed before excitation is applied.
(b) a generator is not allowed to produce a voltage in excess of its rated value.
— 1 —
GENERATOR OPERATING AT RATED SPEED
When a generator rotor is rotating, prior to synchronization, at its rated speed and
has sufficient field current applied to give the rated no load voltage output, the generator
is operating at its rated point on its voltage to excitation curve, see Figure 1. Under this
condition the generator is operating normally and no overftuxing problems exist.
Figure 1: Open circuit output voltage to Field current characteristic for a generator at
100% rated speed.
—2—
GENERATOR OPERATING AT BELOW RATED SPEED
If the generator rotor speed decreases, for the generator to continue producing the
rated output voltage VT, the excitation must be increased. This is explained by the
formula given below. The increase in excitation can be done manually or by the action of
the AVR.
The output voltage VT is obtained from the formula:
VT = 4.44NΦmf Φm = rotor flux
or VT ά Φm f f = frequency
because N is constant N = number of turns in the rotor pole (remains constant )
Once a generator has been synchronized to the Grid, because the system is large,
the generator voltage and frequency are determined by the system. Under this condition,
unless the system voltage increases excessively or the frequency falls excessively, the
flux. Φm remains constant and over-fluxing cannot occur. However, when a generator is
disconnected from the grid, for example prior to synchronizing or following a trip,
problems occur when the generator is made to produce rated voltage at below rated
speed. This situation can be due to equipment malfunction or operator error.
Figure 2 shows typical output voltage to field current characteristics for a
generator operating at 100% rated speed and 80% rated speed. Note that the iron core of
the generator is now saturated or over-fluxed and that the field current has increased by a
factor of 2.5. Over-fluxing and excess rotor currents cause three problems. The
explanations of these problems follow.
—3—
Figure 2: Open circuit output voltage to field current characteristics for a generator
at 100% and 80% rated speed.
(a) Rotor Overheating. Much more field current is now required compared with that
required to produce rated voltage at rated speed. In this case, the current required is 2.5
times as much. This will cause (2.5)2
= 6.25 times the heating in the rotor. With the
cooling system operating at 80% speed, the cooling will be less effective (typically 50%)
and serious overheating may occur in the rotor.
(b) Generator Stator Damage. Figure 2 shows for the generator to produce rated voltage
at 80% rated speed, the flux must be increased in the ratio 100/80 = 1.25 times.
Consequently, the iron in the stator core is highly fluxed and almost fully saturated; it is
over-fluxed. Over-fluxing gives excessive eddy current and hysteresis heating, and thus
the iron can be overheated in the matter of minutes. It should also be appreciated that as
the magnetic fluxes increase, the mechanical forces created by the fluxes also increase.
Because of these thermal and mechanical considerations, manufacturers state that
the flux in a generator stator core must not be kept at a value greater than 10% above
normal, for more than a few minutes.
.
—4—
(c) Transformer Damage. In large installations, the generator main transformer and the
unit auxiliary transformer are directly connected to the generator. Therefore, if rated
voltage at below rated frequency is produced in the generator, this voltage is applied
directly to the transformers. The voltage, flux and frequency relationship also applies to
the transformers:
VT ά Φm f
If over-fluxing occurs in the stator of the generator, it also occurs in the
transformer cores. While a generator, from a mechanical point of view, can withstand
over-fluxing reasonably well, large transformers are more susceptible to damage from
over-fluxing. In a transformer core, the heating effects are similar to those in a generator.
However, the core is made of long thin laminations which are difficult to clamp and
support. Over-fluxing can cause the core laminations to distort or overstress the core
clamping bolts and plates, due to excessive magnetic and thermal expansive forces. This
can cause the core to become loose, leading to mechanical failure of the core.
GENERATOR OPERATION AT HIGHER THAN RATED VOLTAGE
A generator and its associated transformers can also be overfluxed if the voltage
is allowed to rise above normal, with the generator operating at rated speed. Again,
overfluxing is due to the relationship
VT ά Φm f
and if the voltage is excessive for rated frequency, the flux Φm must be excessive. The
same overfluxing problems, as stated in sections (b) and (c), will occur.
SUMMARY
To prevent generator rotor winding, generator stator core and transformer core
damage, great care must be taken to prevent overfluxing. (Some generators have relays
which measure the frequency and voltage ratio and trip the generator field breaker before
serious overfluxing occurs).
Overfluxing occurs when
(a) a generator produces rated voltage below rated speed.
(b) a generator produces above rated voltage at rated speed.
—5—
(c) Transformer Damage. In large installations, the generator main transformer and the
unit auxiliary transformer are directly connected to the generator. Therefore, if rated
voltage at below rated frequency is produced in the generator, this voltage is applied
directly to the transformers. The voltage, flux and frequency relationship also applies to
the transformers:
VT ά Φm f
If over-fluxing occurs in the stator of the generator, it also occurs in the
transformer cores. While a generator, from a mechanical point of view, can withstand
over-fluxing reasonably well, large transformers are more susceptible to damage from
over-fluxing. In a transformer core, the heating effects are similar to those in a generator.
However, the core is made of long thin laminations which are difficult to clamp and
support. Over-fluxing can cause the core laminations to distort or overstress the core
clamping bolts and plates, due to excessive magnetic and thermal expansive forces. This
can cause the core to become loose, leading to mechanical failure of the core.
GENERATOR OPERATION AT HIGHER THAN RATED VOLTAGE
A generator and its associated transformers can also be overfluxed if the voltage
is allowed to rise above normal, with the generator operating at rated speed. Again,
overfluxing is due to the relationship
VT ά Φm f
and if the voltage is excessive for rated frequency, the flux Φm must be excessive. The
same overfluxing problems, as stated in sections (b) and (c), will occur.
SUMMARY
To prevent generator rotor winding, generator stator core and transformer core
damage, great care must be taken to prevent overfluxing. (Some generators have relays
which measure the frequency and voltage ratio and trip the generator field breaker before
serious overfluxing occurs).
Overfluxing occurs when
(a) a generator produces rated voltage below rated speed.
(b) a generator produces above rated voltage at rated speed.
—5—

More Related Content

What's hot

BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEMBHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEMyash Natani
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
 
An inside view of thermal power stations and DDCMIS in power plants
An inside view of thermal power stations and DDCMIS in power plantsAn inside view of thermal power stations and DDCMIS in power plants
An inside view of thermal power stations and DDCMIS in power plantsRg Lokkesh
 
EXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptEXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptvishal laddha
 
Thermal Power Plant Simulator Hands-on Malfunctions
Thermal Power Plant Simulator Hands-on MalfunctionsThermal Power Plant Simulator Hands-on Malfunctions
Thermal Power Plant Simulator Hands-on MalfunctionsManohar Tatwawadi
 
Thermal Power Plant - Emergency situations
Thermal Power Plant   -   Emergency situations Thermal Power Plant   -   Emergency situations
Thermal Power Plant - Emergency situations Ashish Kumar Jain
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generatorMohammad Abdullah
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Manohar Tatwawadi
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relaysRoberto Costa
 
Heat rate audit in thermal power plant
Heat rate audit in thermal power plantHeat rate audit in thermal power plant
Heat rate audit in thermal power plantSHIVAJI CHOUDHURY
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Practical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansPractical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansLiving Online
 
Mini project ppt on working of steam turbine and its auxiliaries
Mini project ppt on working of steam turbine and its auxiliariesMini project ppt on working of steam turbine and its auxiliaries
Mini project ppt on working of steam turbine and its auxiliariesjyotishmathi college
 
Pulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedurePulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedureAshvani Shukla
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centresalehkhan
 
Generator cooling and sealing system 2
Generator cooling and sealing system 2Generator cooling and sealing system 2
Generator cooling and sealing system 2Mohammad Basid
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protectionNischal Popat
 

What's hot (20)

BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEMBHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
BHEL HARIDWAR,CONSTRUCTION OF TURBO GENERATOR AND EXCITATION SYSTEM
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
An inside view of thermal power stations and DDCMIS in power plants
An inside view of thermal power stations and DDCMIS in power plantsAn inside view of thermal power stations and DDCMIS in power plants
An inside view of thermal power stations and DDCMIS in power plants
 
EXCITATION SYSTEM.ppt
EXCITATION SYSTEM.pptEXCITATION SYSTEM.ppt
EXCITATION SYSTEM.ppt
 
Thermal Power Plant Simulator Hands-on Malfunctions
Thermal Power Plant Simulator Hands-on MalfunctionsThermal Power Plant Simulator Hands-on Malfunctions
Thermal Power Plant Simulator Hands-on Malfunctions
 
Thermal Power Plant - Emergency situations
Thermal Power Plant   -   Emergency situations Thermal Power Plant   -   Emergency situations
Thermal Power Plant - Emergency situations
 
Protection of three phase synchronous generator
Protection of three phase synchronous generatorProtection of three phase synchronous generator
Protection of three phase synchronous generator
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Heat rate audit in thermal power plant
Heat rate audit in thermal power plantHeat rate audit in thermal power plant
Heat rate audit in thermal power plant
 
Reactors
ReactorsReactors
Reactors
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Practical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & TechniciansPractical Boiler Control & Instrumentation for Engineers & Technicians
Practical Boiler Control & Instrumentation for Engineers & Technicians
 
Hrsg book
Hrsg bookHrsg book
Hrsg book
 
Mini project ppt on working of steam turbine and its auxiliaries
Mini project ppt on working of steam turbine and its auxiliariesMini project ppt on working of steam turbine and its auxiliaries
Mini project ppt on working of steam turbine and its auxiliaries
 
Pulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedurePulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedure
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centre
 
Generator cooling and sealing system 2
Generator cooling and sealing system 2Generator cooling and sealing system 2
Generator cooling and sealing system 2
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protection
 

Viewers also liked

Luxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley City
Luxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley CityLuxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley City
Luxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley Citymidvalleycity city
 
Master's Thesis Introduction
Master's Thesis IntroductionMaster's Thesis Introduction
Master's Thesis IntroductionEmma Goldman
 
Telling stories; inherited memories.
Telling stories; inherited memories.Telling stories; inherited memories.
Telling stories; inherited memories.Michelle Gallagher
 
The present-continuous-tense
The present-continuous-tenseThe present-continuous-tense
The present-continuous-tenseEliz Haligur
 
(9) Synchronous Alternator Capability Graph
(9) Synchronous Alternator Capability Graph(9) Synchronous Alternator Capability Graph
(9) Synchronous Alternator Capability GraphDaniel Gray
 
Political Party Stances
Political Party StancesPolitical Party Stances
Political Party Stanceshcpsgov
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformerSumeet Ratnawat
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Stores management and stock control
Stores management and stock controlStores management and stock control
Stores management and stock controlGabriel Lubale
 

Viewers also liked (14)

Luxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley City
Luxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley CityLuxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley City
Luxury Apartments, Sky Villas, Flats in Vijayawada | Mid Valley City
 
Master's Thesis Introduction
Master's Thesis IntroductionMaster's Thesis Introduction
Master's Thesis Introduction
 
Horrace Mann
Horrace MannHorrace Mann
Horrace Mann
 
Telling stories; inherited memories.
Telling stories; inherited memories.Telling stories; inherited memories.
Telling stories; inherited memories.
 
The present-continuous-tense
The present-continuous-tenseThe present-continuous-tense
The present-continuous-tense
 
(9) Synchronous Alternator Capability Graph
(9) Synchronous Alternator Capability Graph(9) Synchronous Alternator Capability Graph
(9) Synchronous Alternator Capability Graph
 
Quantifiers
QuantifiersQuantifiers
Quantifiers
 
(6) finite
(6) finite(6) finite
(6) finite
 
(5) infinite
(5) infinite(5) infinite
(5) infinite
 
Political Party Stances
Political Party StancesPolitical Party Stances
Political Party Stances
 
Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Stores management and stock control
Stores management and stock controlStores management and stock control
Stores management and stock control
 
Store management
Store managementStore management
Store management
 

Similar to (7) overfluxing

Equipment protection
Equipment protectionEquipment protection
Equipment protectionSlides Hub
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarjavid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarjavid iqbal sodagar
 
Equipment and Stability Constraints : System Operation
Equipment and Stability Constraints : System OperationEquipment and Stability Constraints : System Operation
Equipment and Stability Constraints : System OperationRidwanul Hoque
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
Generation protection - complete
Generation protection - completeGeneration protection - complete
Generation protection - completeSlides Hub
 
LECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptxLECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptxLoitaFredy
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipmentsateesh kumar
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorCS V
 
3 phase power unbalance
3 phase power unbalance3 phase power unbalance
3 phase power unbalanceWilson Pavão
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersAli Sepehri
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generatormytechinfo
 
Electrical and electronics form five notes
Electrical and electronics form five notesElectrical and electronics form five notes
Electrical and electronics form five notesRobert Benjamin
 

Similar to (7) overfluxing (20)

(9) limitations
(9) limitations(9) limitations
(9) limitations
 
Equipment protection
Equipment protectionEquipment protection
Equipment protection
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Equipment and Stability Constraints : System Operation
Equipment and Stability Constraints : System OperationEquipment and Stability Constraints : System Operation
Equipment and Stability Constraints : System Operation
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
Generation protection - complete
Generation protection - completeGeneration protection - complete
Generation protection - complete
 
LECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptxLECTURE 1 - GENERATOR PROTECTION.pptx
LECTURE 1 - GENERATOR PROTECTION.pptx
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipment
 
Turbo generator
Turbo generator Turbo generator
Turbo generator
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
3 phase power unbalance
3 phase power unbalance3 phase power unbalance
3 phase power unbalance
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit Breakers
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
Motor.ppt
Motor.pptMotor.ppt
Motor.ppt
 
Motor starter
Motor starterMotor starter
Motor starter
 
European Grid Codes
European Grid CodesEuropean Grid Codes
European Grid Codes
 
Electrical and electronics form five notes
Electrical and electronics form five notesElectrical and electronics form five notes
Electrical and electronics form five notes
 
Gymr motor starting_solutions
Gymr motor starting_solutionsGymr motor starting_solutions
Gymr motor starting_solutions
 

More from Daniel Gray

Electrical Theory Review
Electrical Theory ReviewElectrical Theory Review
Electrical Theory ReviewDaniel Gray
 
Power factor correction formula
Power factor correction formulaPower factor correction formula
Power factor correction formulaDaniel Gray
 
Electrical power and power factor
Electrical power and power factorElectrical power and power factor
Electrical power and power factorDaniel Gray
 

More from Daniel Gray (6)

Electrical Theory Review
Electrical Theory ReviewElectrical Theory Review
Electrical Theory Review
 
Power factor correction formula
Power factor correction formulaPower factor correction formula
Power factor correction formula
 
Electrical power and power factor
Electrical power and power factorElectrical power and power factor
Electrical power and power factor
 
(8) loading
(8) loading(8) loading
(8) loading
 
(4) synch
(4) synch(4) synch
(4) synch
 
(10) stability
(10) stability(10) stability
(10) stability
 

Recently uploaded

Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Mark Reed
 
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfAMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfphamnguyenenglishnb
 
Grade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptxGrade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptxChelloAnnAsuncion2
 
Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........LeaCamillePacle
 
Full Stack Web Development Course for Beginners
Full Stack Web Development Course  for BeginnersFull Stack Web Development Course  for Beginners
Full Stack Web Development Course for BeginnersSabitha Banu
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfMr Bounab Samir
 
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTiammrhaywood
 
Planning a health career 4th Quarter.pptx
Planning a health career 4th Quarter.pptxPlanning a health career 4th Quarter.pptx
Planning a health career 4th Quarter.pptxLigayaBacuel1
 
How to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPHow to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPCeline George
 
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxEPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxRaymartEstabillo3
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Celine George
 
Employee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxEmployee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxNirmalaLoungPoorunde1
 
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Quarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up FridayQuarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up FridayMakMakNepo
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Jisc
 
AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.arsicmarija21
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfSpandanaRallapalli
 

Recently uploaded (20)

Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
 
Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)Influencing policy (training slides from Fast Track Impact)
Influencing policy (training slides from Fast Track Impact)
 
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfAMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
 
Rapple "Scholarly Communications and the Sustainable Development Goals"
Rapple "Scholarly Communications and the Sustainable Development Goals"Rapple "Scholarly Communications and the Sustainable Development Goals"
Rapple "Scholarly Communications and the Sustainable Development Goals"
 
Grade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptxGrade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptx
 
Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........
 
Full Stack Web Development Course for Beginners
Full Stack Web Development Course  for BeginnersFull Stack Web Development Course  for Beginners
Full Stack Web Development Course for Beginners
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
 
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPTECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
ECONOMIC CONTEXT - LONG FORM TV DRAMA - PPT
 
Planning a health career 4th Quarter.pptx
Planning a health career 4th Quarter.pptxPlanning a health career 4th Quarter.pptx
Planning a health career 4th Quarter.pptx
 
How to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPHow to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERP
 
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxEPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17
 
Employee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptxEmployee wellbeing at the workplace.pptx
Employee wellbeing at the workplace.pptx
 
OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...
 
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Kamla Market (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
 
Quarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up FridayQuarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up Friday
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...
 
AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.AmericanHighSchoolsprezentacijaoskolama.
AmericanHighSchoolsprezentacijaoskolama.
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdf
 

(7) overfluxing

  • 1. OVERFLUXING OBJECTIVES 1. Explain the two conditions which can cause over-fluxing in a generator and its associated transformers. 2. Explain how a generator can be damaged by over-fluxing. 3. Explain how a transformer can be damaged by over-fluxing. INTRODUCTION It is possible to damage a generator and its associated main and auxiliary transformers by what is known as over-fluxing. Over-fluxing occurs when a generator or a transformer is subjected flux levels which are above the permissible limits. Over- fluxing can occur when a generator or transformer is made to: (a) produce rated voltage at below rated speed (frequency). (b) produce greater than rated voltage at rated speed (frequency). Because of the two problems outlined above, great care must be taken to ensure that (a) a generator is at or close to operating speed before excitation is applied. (b) a generator is not allowed to produce a voltage in excess of its rated value. — 1 —
  • 2. GENERATOR OPERATING AT RATED SPEED When a generator rotor is rotating, prior to synchronization, at its rated speed and has sufficient field current applied to give the rated no load voltage output, the generator is operating at its rated point on its voltage to excitation curve, see Figure 1. Under this condition the generator is operating normally and no overftuxing problems exist. Figure 1: Open circuit output voltage to Field current characteristic for a generator at 100% rated speed. —2—
  • 3. GENERATOR OPERATING AT BELOW RATED SPEED If the generator rotor speed decreases, for the generator to continue producing the rated output voltage VT, the excitation must be increased. This is explained by the formula given below. The increase in excitation can be done manually or by the action of the AVR. The output voltage VT is obtained from the formula: VT = 4.44NΦmf Φm = rotor flux or VT ά Φm f f = frequency because N is constant N = number of turns in the rotor pole (remains constant ) Once a generator has been synchronized to the Grid, because the system is large, the generator voltage and frequency are determined by the system. Under this condition, unless the system voltage increases excessively or the frequency falls excessively, the flux. Φm remains constant and over-fluxing cannot occur. However, when a generator is disconnected from the grid, for example prior to synchronizing or following a trip, problems occur when the generator is made to produce rated voltage at below rated speed. This situation can be due to equipment malfunction or operator error. Figure 2 shows typical output voltage to field current characteristics for a generator operating at 100% rated speed and 80% rated speed. Note that the iron core of the generator is now saturated or over-fluxed and that the field current has increased by a factor of 2.5. Over-fluxing and excess rotor currents cause three problems. The explanations of these problems follow. —3—
  • 4. Figure 2: Open circuit output voltage to field current characteristics for a generator at 100% and 80% rated speed. (a) Rotor Overheating. Much more field current is now required compared with that required to produce rated voltage at rated speed. In this case, the current required is 2.5 times as much. This will cause (2.5)2 = 6.25 times the heating in the rotor. With the cooling system operating at 80% speed, the cooling will be less effective (typically 50%) and serious overheating may occur in the rotor. (b) Generator Stator Damage. Figure 2 shows for the generator to produce rated voltage at 80% rated speed, the flux must be increased in the ratio 100/80 = 1.25 times. Consequently, the iron in the stator core is highly fluxed and almost fully saturated; it is over-fluxed. Over-fluxing gives excessive eddy current and hysteresis heating, and thus the iron can be overheated in the matter of minutes. It should also be appreciated that as the magnetic fluxes increase, the mechanical forces created by the fluxes also increase. Because of these thermal and mechanical considerations, manufacturers state that the flux in a generator stator core must not be kept at a value greater than 10% above normal, for more than a few minutes. . —4—
  • 5. (c) Transformer Damage. In large installations, the generator main transformer and the unit auxiliary transformer are directly connected to the generator. Therefore, if rated voltage at below rated frequency is produced in the generator, this voltage is applied directly to the transformers. The voltage, flux and frequency relationship also applies to the transformers: VT ά Φm f If over-fluxing occurs in the stator of the generator, it also occurs in the transformer cores. While a generator, from a mechanical point of view, can withstand over-fluxing reasonably well, large transformers are more susceptible to damage from over-fluxing. In a transformer core, the heating effects are similar to those in a generator. However, the core is made of long thin laminations which are difficult to clamp and support. Over-fluxing can cause the core laminations to distort or overstress the core clamping bolts and plates, due to excessive magnetic and thermal expansive forces. This can cause the core to become loose, leading to mechanical failure of the core. GENERATOR OPERATION AT HIGHER THAN RATED VOLTAGE A generator and its associated transformers can also be overfluxed if the voltage is allowed to rise above normal, with the generator operating at rated speed. Again, overfluxing is due to the relationship VT ά Φm f and if the voltage is excessive for rated frequency, the flux Φm must be excessive. The same overfluxing problems, as stated in sections (b) and (c), will occur. SUMMARY To prevent generator rotor winding, generator stator core and transformer core damage, great care must be taken to prevent overfluxing. (Some generators have relays which measure the frequency and voltage ratio and trip the generator field breaker before serious overfluxing occurs). Overfluxing occurs when (a) a generator produces rated voltage below rated speed. (b) a generator produces above rated voltage at rated speed. —5—
  • 6. (c) Transformer Damage. In large installations, the generator main transformer and the unit auxiliary transformer are directly connected to the generator. Therefore, if rated voltage at below rated frequency is produced in the generator, this voltage is applied directly to the transformers. The voltage, flux and frequency relationship also applies to the transformers: VT ά Φm f If over-fluxing occurs in the stator of the generator, it also occurs in the transformer cores. While a generator, from a mechanical point of view, can withstand over-fluxing reasonably well, large transformers are more susceptible to damage from over-fluxing. In a transformer core, the heating effects are similar to those in a generator. However, the core is made of long thin laminations which are difficult to clamp and support. Over-fluxing can cause the core laminations to distort or overstress the core clamping bolts and plates, due to excessive magnetic and thermal expansive forces. This can cause the core to become loose, leading to mechanical failure of the core. GENERATOR OPERATION AT HIGHER THAN RATED VOLTAGE A generator and its associated transformers can also be overfluxed if the voltage is allowed to rise above normal, with the generator operating at rated speed. Again, overfluxing is due to the relationship VT ά Φm f and if the voltage is excessive for rated frequency, the flux Φm must be excessive. The same overfluxing problems, as stated in sections (b) and (c), will occur. SUMMARY To prevent generator rotor winding, generator stator core and transformer core damage, great care must be taken to prevent overfluxing. (Some generators have relays which measure the frequency and voltage ratio and trip the generator field breaker before serious overfluxing occurs). Overfluxing occurs when (a) a generator produces rated voltage below rated speed. (b) a generator produces above rated voltage at rated speed. —5—