Current carrying capacities & other technical tables
1. MicCom
The Quality Cable Makers
CARRYING
CURRENT CAPACITIES
073
C U R R E N T- C A R R Y I N G
CAPACITIES
and other
TECHNICAL TABLES
MicCom
074
The Quality Cable Makers
www.miccomcables.com
2. TABLE II
7.1
7
TABLE 1
Current-carrying capacities and associated voltage drops for twin and
multicore p.v.c. insulated cables, non armoured, (copper conductors)
Current-carrying capacities and associated voltage drops for single-core p.v.c.
insulated cable, non armoured, with or without sheath (copper conductors)
Conductor operating temperature 70 0C
Conductor operating temperature 700C
Conductor
2 cable,
3 or 4 cables,
cross-sectional single-phase three-phase
area
a.c., or d.c.
a.c.
2 cable,
single-phase
a.c., or d.c.
3 or 4 cables,
three-phase
a.c.
Flat or vertical (2
cables, single-phase
a.c., or d.c., or 3 or 4
cables three-phase)
Trefoil
(3 cables
three phase)
Current Volt drop Current Volt drop Current Volt drop Current Volt drop Current Volt drop per ampere Current Volt drop
Carrying per ampere
per metre
Carrying per ampere Carrying per ampere Carrying per ampere Carrying per ampere Carrying
Capacity per metre
Capacity per metre Capacity per metre Capacity per metre Capacity per metre Capacity Single
d.c Three
phase
phase
mm2
A
mV
A
mV
A
mV
A
mV
A
mV
mV
mV
A
14
17
24
32
41
55
74
97
119
42.0
28.0
17.0
11.0
7.1
4.2
2.7
1.7
1.3
12
14
21
29
37
51
66
87
106
37.0
24.0
15.0
9.2
6.2
3.7
2.3
1.5
1.1
17
21
30
40
50
68
90
118
145
42.0
28.0
17.0
11.0
7.1
4.2
2.7
1.7
1.3
16
20
26
36
45
61
81
106
130
37.0
24.0
15.0
9.2
6.2
3.7
2.3
1.5
1.1
-
-
-
-
-
-
160
200
240
280
320
365
430
500
610
710
820
0.82
0.59
0.45
0.38
0.34
0.30
0.27
0.25
0.24
0.23
0.22
195
240
300
350
410
470
560
660
800
910
1040
170
210
260
300
350
400
480
570
680
770
880
0.80
0.59
0.42
0.34
0.29
0.25
0.22
0.19
0.17
0.16
0.15
a.c
50.0
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
500.0
630.0
145
185
230
260
-
d.c
0.97
0.71
0.56
0.48
-
0.91
0.63
0.45
0.36
-
a.c
125
160
195
220
-
0.84
0.62
0.48
0.42
-
175
220
270
310
355
405
480
560
680
800
910
d.c
0.93
0.65
0.48
0.40
0.34
0.29
0.24
0.22
0.20
0.18
0.17
0.91
0.63
0.45
0.36
0.29
0.24
0.18
0.14
0.12
0.086
0.068
0.95 0.91 0.85
0.68 0.63 0.62
0.52 0.45 0.49
0.44 0.36 0.43
0.39 0.29 0.39
0.35 0.24 0.36
0.36 0.18 0.38
0.33 0.14 0.35
0.30 0.12 0.33
0.28 0.086 0.31
0.26 0.068 0.30
One three-core
cable, with or
without protective
conductor, or one
four-core cable,
three-phase
One twin cable,
with or without
protective
conductor
single-phase
a.c., or d.c.
One three-core
cable, with or
without protective
conductor, or one
four-core cable,
three-phase
mm2
A
mV
A
mV
A
1.0
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
14
18
24
32
40
53
70
79
98
-
42.0
28.0
17.0
11.0
7.1
4.2
2.7
1.8
1.3
-
12
16
21
29
36
49
62
70
86
-
37.0
24.0
15.0
9.2
6.2
3.7
2.3
1.6
1.1
-
16
20
28
36
46
64
85
108
132
163
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
-
-
-
-
207
251
290
330
380
450
520
600
mV
42.0
28.0
17.0
11.0
7.1
4.2
2.7
1.8
1.3
0.92
a.c. d.c.
0.65 0.64
0.48 0.46
0.40 0.36
0.32 0.25
0.29 0.23
0.25 0.18
0.23 0.14
0.22 0.11
A
mV
A
13
17
24
32
40
54
71
90
115
140
37.0
24.0
15.0
9.2
6.2
3.7
2.3
1.6
1.1
0.81
114
139
172
176
215
251
287
330
392
450
520
0.57
0.42
0.34
0.29
0.24
0.20
0.18
0.17
218
265
306
348
400
474
548
632
Volt drop
per ampere
per metre
mV
A
mV
1.8
1.3
0.92
a.c. d.c.
.065 0.64
0.48 0.46
0.40 0.36
0.32 0.25
0.29 0.23
0.25 0.18
0.23 0.14
0.22 0.11
95
122
148
-flat
-cables
-only
- "
- "
- "
- "
1.6
1.1
0.81
186
227
265
302
348
413
474
548
0.57
0.42
0.34
0.29
0.24
0.20
0.18
0.17
For Ambient Temperature
For Ambient Temperature
075
One twin cable,
with or without
protective
conductor
single-phase
a.c., or d.c.
Correction Factors:
Correction Factors:
Ambient temperatures
Correction factor
One three-core
cable, with or
without protective
conductor, or
one four-core
cable, three-phase
Current Volt drop Current Volt drop
Current
Volt drop
Current Volt drop Current Volt drop Current
Carrying per ampere Carrying per ampere Carrying per ampere Carrying per ampere Carrying per ampere Carrying
Capacity per metre Capacity per metre Capacity per metre Capacity per metre Capacity per metre Capacity
mV
1.0
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
One twin cable,
with or without
Conductor
protective
cross-sectional
conductor
single-phase
area
a.c., or d.c.
250C
1.06
350C
0.94
400C
0.87
Ambient temperatures
Correction factor
450C 500C 550C 600C 650C
0.79 0.71 0.61 0.50 0.35
MicCom
400C 450C 500C 550C 600C 650C
0.87 0.79 0.71 0.61 0.50 0.35
MicCom
The Quality Cable Makers
250C 350C
1.06 0.94
The Quality Cable Makers
076
www.miccomcables.com
3. 7.2TABLE
III
7.3
Current-carrying capacities and associated voltage drops for twin and multicore
cables insulated with impregnated paper (BS 6480), lead-sheathed or
aluminium-sheathed, armoured or non-armoured, with or without serving
(copper conductor)
TABLE IV
Current-carrying capacities and associated volt drops and
masses supported, for flexible cords to BS 6500
Conductor operating temperature 800C
Normal
cross-sectional
area of
conductor*2
One three- or
One twin cable,
single-phase a.c., or d.c. four-core cable,
three-phase
Current
Carrying
Capacity
mm2
50
70
95
120
150
185
240
300
400
Volt drop per ampere
per metre
a.c.
d.c.
One twin cable,
One three- or
single-phase a.c., or d.c. four-core cable,
three-phase
Current
Current Volt drop
Carrying per ampere Carrying
Capacity per metre Capacity
Volt drop per ampere
per metre
a.c.
d.c.
Current Volt drop
Carrying per ampere
Capacity per metre
A
mV
mV
A
mV
A
mV
mV
A
mV
165
205
255
295
335
390
460
525
610
0.95
0.66
0.49
0.40
0.33
0.28
0.24
0.21
0.20
0.95
0.66
0.47
0.36
0.30
0.24
0.19
0.15
0.12
145
180
225
260
300
345
410
470
545
0.82
0.58
0.43
0.35
0.28
0.24
0.20
0.18
0.17
200
250
305
355
405
465
555
635
735
0.95
0.66
0.49
0.40
0.33
0.28
0.24
0.21
0.20
0.95
0.66
0.47
0.36
0.30
0.24
0.19
0.15
0.12
170
215
265
305
350
405
480
550
640
0.82
0.58
0.43
0.35
0.28
0.24
0.20
0.18
0.17
Normal
Maximum diameter
cross-sectional
of wires
area of conductor forming conductor
Current-carrying Volt drop per ampere per metre Maximum mass supportable
Capacity, d.c. Or
by twin flexible cord
Single-phase a.c,
(see IEE Regulation 523-32)
or three-phrase a.c.
d.c. or singlephase a.c.
mm2
0.5
0.75
1.0
1.25
1.5
2.5
4.0
mV
0.21
0.21
0.21
0.26
0.26
0.26
0.31
three-phase a.c.
mV
83
56
43
35
31
18
11
mV
72.0
48.0
37.0
29.0
26.0
16.0
9.6
A
3
6
10
13
15
20
25
Kg
2
3
5
5
5
5
5
Correction factor for ambient temperature
600C rubber and p.v.c cords
Correction Factors:
Ambient temperature
Correction factor
For Ambient Temperature
850C rubber cords having a h.o.f..r. sheath or a
heat-resisting p.v.c sheath
Ambient temperatures
Correction factor
250C 350C 400C 450C 500C 550C 600C 650C 700C 750C
1.05 0.95 0.89 0.82 0.75 0.68 0.61 0.53 0.43 0.30
Ambient temperature
Correction factor
350C
0.96
400C
0.92
450C
0.87
500C
0.71
550C
0.50
350C
To
500C
1.0
550C
600C
650C
700C
0.96
0.83
350C
To
1200C
1.0
1250C
1300C
1350C
0.85
0.74
0.60
350C
1550C
1600C
1650C
1700C
0.67
0.47
1500C rubber cords
Ambient temperature
Correction factor
0.96
1400C
1450C
0.42
Glass-fibre cords
Ambient temperature
1750C
To
1500C
077
MicCom
MicCom
The Quality Cable Makers
The Quality Cable Makers
www.miccomcables.com
078
4. 7.4
7.5
TABLE V
Current-carrying capacities and associated voltage drops for single-core
p.v.c insulated cables, non-armoured, with sheath (aluminium conductors)
Conductor operating temperature 700C
TABLE VI
Current-carrying capacities and associated voltage drops for twin and
multicore armoured p.v.c. insulated cables (aluminium conductors)
Conductor operating temperature 700C
2 cable,
Normal
cross-sectional single phase
a.c., or d.c.
area of
conductor
3 or 4 cables,
three-phase
a.c.
2 cable,
3 or 4 cables,
single phase three-phase
a.c., or d.c.
a.c.
Flat or vertical
(2 cables,
single-phase
a.c., or d.c.,
or 3 or 4 cables
three-phase)
Current Volt drop Current Volt drop Current Volt drop Current Volt drop Current
Carrying per ampere Carrying per ampere Carrying per ampere Carrying per ampere Carrying
Capacity per metre Capacity per metre Capacity per metre Capacity per metre Capacity
a.c
mm2
A
16
25
35
50
70
95
120
150
185
240
300
380
480
600
60
78
96
120
150
175
205
235
-
d.c
mV mV
4.5
2.9
2.1
1.6
1.2
0.93
0.80
0.73
-
4.5
2.8
2.0
1.5
1.0
0.75
0.60
0.49
-
A
mV
52
67
83
100
125
150
175
200
-
3.9
2.5
1.8
1.4
1.0
0.80
0.70
0.64
-
72
94
115
143
181
223
261
298
345
411
476
554
643
737
mV mV
A
4.5
2.8
2.1
1.5
1.1
0.77
0.62
0.51
0.42
0.34
0.29
0.26
0.23
0.21
4.5
2.8
2.0
1.5
1.0
0.75
0.60
0.49
0.39
0.29
0.23
0.19
0.15
0.12
A
mV
A
65
85
105
123
156
193
225
259
290
361
419
465
541
616
3.9
2.5
1.8
1.3
0.93
0.69
0.56
0.48
0.40
0.34
0.30
0.28
0.26
0.24
155
190
235
275
320
370
440
510
584
677
776
Volt drop
per ampere
per metre
1ph d.c. 3ph
mV mV mV
1.5
1.1
0.80
0.65
0.55
0.46
0.43
0.38
0.35
0.32
0.30
1.5
1.0
0.75
0.60
0.49
0.39
0.29
0.23
0.19
0.15
0.12
1.34
0.95
0.72
0.60
0.51
0.45
0.43
0.39
0.37
0.34
0.33
Trefoil
(3 cables
three-phase)
Current Volt drop
Carrying per ampere
Capacity per metre
A
mV
140
170
205
235
270
310
370
435
490
570
648
1.3
0.90
0.67
0.54
0.45
0.37
0.30
0.25
0.22
0.20
0.18
Correction Factors:
079
One three- or
four-core cable,
three-phase
One twin cable,
single-phase
a.c., or d.c.
Current
Carrying
Capacity
Volt drop per ampere
per metre
a.c.
d.c.
One twin cable,
single-phase
a.c., or d.c.
Current Volt drop per ampere
Current
Volt drop
per metre
Carrying per ampere Carrying
Capacity per metre Capacity
d.c.
a.c.
One three- or
four-core cable,
three-phase
Current Volt drop
Carrying per ampere
Capacity per metre
mm
A
mV
mV
A
mV
A
mV
mV
A
mV
16
25
35
50
70
95
120
150
185
240
300
63
83
100
124
157
185
-
4.5
2.9
2.1
1.6
1.1
0.79
-
4..5
2.9
2.0
1.5
1.0
0.77
-
55
67
88
105
138
166
195
219
257
304
347
3..9
2.5
1.8
1.3
0.93
0.68
0.54
0.45
0.37
0.30
0.25
66
87
105
130
165
195
-
4..5
2.1
2..9
1.6
1.1
0.79
-
4..3
2..9
2.0
1..5
1.0
0.77
-
58
71
93
110
145
175
205
230
270
320
365
3..9
2..5
1..8
1..3
0..93
0.68
0.54
0.45
0.37
0.30
0.25
2
Correction Factors:
For Ambient Temperature
For Ambient Temperature
Ambient temperatures
Correction factor
Normal
cross-sectional
area of
conductor*2
250C 350C
1.06 0.94
Ambient temperatures
Correction factor
400C 450C 500C 550C 600C 650C
0.87 0.79 0.71 0.61 0.50 0.35
MicCom
MicCom
The Quality Cable Makers
250C 350C 400C 450C 500C 550C 600C 650C
1.06 0.94 0.87 0.79 0.71 0.61 0.50 0.35
The Quality Cable Makers
www.miccomcables.com
080
5. 7.6
TABLE VII
TABLE VIII
7.7
Current-carrying capacities and associated voltage drops for twin and
multicore armoured p.v.c. insulated cables (copper conductors)
0
Conductor operating temperature 70 C
LAY RATIOS FOR ALUMINIUM STANDARD CONDUCTOR
Conductor
crosssectional
area
One twin cable,
single-phase
a.c., or d.c.
Current
Carrying
Capacity
Volt drop per ampere
per metre
One three- or
four-core cable,
three-phase
One twin cable,
single-phase
a.c., or d.c.
Current
Current Volt drop
Carrying per ampere Carrying
Capacity per metre Capacity
Volt drop per ampere
per metre
One three- or
four-core cable,
three-phase
Current Volt drop
Carrying per ampere
Capacity per metre
mm2
A
mV
A
mV
A
mV
A
20
29
37
48
66
86
115
142
168
29.0
18.0
12.0
7.4
4.3
2.7
1.8
1.3
0.92
18
24
31
41
56
73
97
119
147
25.0
16.0
9.6
6.3
3.8
2.3
1.6
1.1
0.81
50
69
90
121
149
180
7.3
4.3
2.7
1.8
1.3
0.92
42
58
77
102
125
155
209
257
295
337
390
461
523
589
180
219
257
295
333
399
451
523
0.57
0.42
0.34
0.29
0.24
0.20
0.18
0.17
220
270
310
355
410
485
550
620
190
230
270
310
350
420
475
550
Number of
wires in
Conductor
0.57
0.42
0.34
0.29
0.24
0.20
0.18
0.17
a.c.
d.c.
0.65
0.48
0.40
0.32
0.29
0.25
0.23
0.22
0.64
0.46
0.36
0.25
0.23
0.18
0.14
0.11
a.c.
0.64
0.46
0.36
0.25
0.23
0.18
0.14
0.11
3
5
6
7
8
9
10
11
6 wire layer 12 wire layer 18-wire layer 24- wire layer 30 wire layer
min
max
min
max
min
max
min
max
min
max
7
10
14
-
-
-
-
-
-
-
-
19
10
16
10
14
-
-
-
-
-
-
37
10
17
10
16
10
14
-
-
-
-
61
10
17
10
16
10
15
10
14
-
-
91
d.c.
0.65
0.48
0.40
0.32
0.29
0.25
0.23
0.22
4
Lay ratio
6.3
3.8
2.3
1.6
1.1
1.81
70.0
95.0
120.0
150.0
185.0
240.0
300.0
400.0
2
mV
1.5
2.5
4.0
6.0
10.0
16.0
25.0
35.0
50.0
1
10
17
10
16
10
15
10
14
10
13
Correction Factors:
For Ambient Temperature
Ambient temperatures
Correction factor
081
250C 350C 400C 450C 500C 550C 600C 650C
1.06 0.94 0.87 0.79 0.71 0.61 0.50 0.35
MicCom
MicCom
The Quality Cable Makers
The Quality Cable Makers
082
www.miccomcables.com
7. 7.10
TABLE XI
7.11
Test Method Property under test
A, B
,B
C. 1
C.1
C.2, C.3
D. 1, D.2,)
D,3_)
E.1, E.2
C.4
Minimum tensile strength (N/mm2)
Minimum elongation at break (%)
Properties after ageing in air
o
7 days at 80 + 2 C
Tensile strength
Minimum value (N/mm2)
Minimum variation from unaged
Value (%)
Elongation at break
Minimum Value (%)
Maximum variation from unaged value (%)
Loss of mass (max) (mg/cm2)
o
Elongation at break
Minimum Value (%)
Maximum variation from unaged
value (%)
Minimum insulation resistance constant
o
(K value) at 20 C
(M?KM) at 70 oC
Test
Property under test
Method
B
Minimum tensile strength (N/mm2)
Sheath
1A
2A
12.5
10
125
150
Minimum elongation at Break (%)
C.2, Loss of mass after ageing 7 days at
o
80+ 2 C
C.3
(mg/cm2)
C.1
Type of insulation or sheath
3
4
5
6
7
18.5 7.5 12.5
6
7.5
8
7.5
9
12.5
125 150
100
125
125
150
150
-
-
-
-
-
-
-
2.0
-
-
2.0
2.0
2.0
-
12.5
10
12.5
10
Elongation at break after ageing 7
o
Days at 135 +2 C
20
20
20
20
Minimum value (%)
-
65
65
-
-
-
-
Tensile strength after ageing 7 days
o
at 100 +2 C
Minimum value (N/mm2)
-
-
-
-
-
-
12.5
-
-
-
-
-
-
25
-
-
-
-
-
-
-
-
-
-
-
-
-
150
25
125
20
2.0
80 +2
50
150
20
2.0
70+2
50
Hot pressure test temperature ( C)
Maximum deformation (%) 80+2
Heat shock test
Temperature at which specimen shall not
o
crack ( C)
150+2 150+2
Non – contamination test
o
7 days at 80 +2 C
Tensile strength
Minimum value (N/mm2)
Maximum variation from unaged
value (%)
085
Requirements
Insulation
1
2
12.5
10
125
150
TABLE XII
12.5
20
10
20
125
20
2.0
80+2
50
150
20
2.0
70+2
50
Maximum variation
From unaged value (%)
Elongation at break
After ageing 7 days at 100+2oC
150+2 150+2
Minimum value (%)
Variation from Unaged value (%)
---
---
D.4
E.1
F.2
125
20
150
20
-----
-----
70
0.037
380
0.037
---
Maximum hot deformation (%)
30 65
30
65
65
40
65
Heat shock test Temperature at
o
150
100
150
120
which specimen shall not crack ( C) 150 150 150
Minimum insulation resistance
constant (K value) at 20oC
mSkm
350 0.35 180 0.0035 0.0035 0.0035 0.0035
---
MicCom
MicCom
The Quality Cable Makers
The Quality Cable Makers
086
www.miccomcables.com