C O M P O N E N T S
Power contactor
Type BMS09.08 / 18.08
2
Ue [V]
900
1800
Ith [A]
800
Ith
[A]
Ue
[V]
1800
BMS
PCC18
PCC18
BMS..08
Type A (VDC)
Type A (VDC)
Type B (VDC)
Type B (VDC)
Type A (VAC)
General information
The BMS contactor, with more than hundred thousands
units in operation worldwide, is a contactor valued by the
car builders and operators of electric traction vehicles for
its strong performance level and its extremely high reliability.
Taking advantages of its recognized features and design,
Sécheron has modernized the BMS to make a product
platform particularly well adapted to actual requirements
and standards. With its high modularity, the BMS offers
variants and options that enable our customers to find the
most appropriate version to fit their application, either as
a stand-alone contactor, dual-pole contactor or delivered
coupled with a Sécheron dedicated pre-charging contactor
type PCC18. Power contactor modules convenient to order
and easy to install are a frequent wish of our customers.
Sécheron brings the best solution with “plug & play” units
gathering line and pre-charging contactors, but also current
measurement and customised high voltage and low voltage
interfaces.
Applications
• Line contactors, assembled set of line and pre-charging contactors, main traction converter isolating contactor and other
applications for locomotives, trains, EMUs, tramways / light rail vehicles
• Contactors for fixed installations including DC power traction substations and other industrial fields
Main features
• Rated operation voltage 900 VDC or 1’800 VDC/AC
• Conventional free air thermal current up to 800 A
• Normally open and bi-directional contactor
• Heavy duty class for mechanical operations with a minimum of 2 millions operations
• Different designs of arc chutes matching installation space and operational performance requirements
• Deliverable as a single unit with Secheron’s pre-charging contactor PCC18, current measurement, high/low voltage connections
• Delivered in standard with control coil low voltage protection against surges
• Low maintenance requirements with easy access to the main contacts for replacement
• Very compact size and extremely low weight
• Suitable for ambient temperature from -40°C to +70°C
• Reference standards: IEC60077-1 /-2, IEC61373, NF-F16 101 /-102
Contactor configurations
BMSArcChutesBMSBodyPre-charging
contactor
3
Data for product selection
High voltage circuit values are indicated for each pole<
Symbol Unit BMS09.08A BMS09.08B BMS18.08A BMS18.08B PCC18
MAIN HIGH VOLTAGE CIRCUIT
Rated operational voltage Ue [VDC]
(16.7, 25, 50/60, ...400 Hz) [VAC]
900
1’800
900
-
1’800
-
1’800
1’800
Rated insulation voltage Ui [VDC]
[VAC]
2’300
2’300
2300
-
2’300
-
2’300
2’300
Conventional free air thermal current (1)
Ith [A] 800 800 N.A.
Rated operational current Ie [ADC]
and operational frequency Ie [ADC]
[AAC]
500 / C2
800 / C1
800 / C2
800/C2
-
-
500 / C2
800 / C1
-
-
800 / C1
-
N.A.
Rated short-time withstand current Icw / t [kA]/[ms] 10 / 100 10 / 100 N.A.
Peak short-time withstand current Îcw [kA] 10 10 N.A.
Maximum breaking capacity
- DC current,  = 15 ms Ibc [A]
- AC current, cos  = 0.8 (16.7, 25 & 50/60 Hz) Ibc [Arms]
3’200
4’200
6’000
-
2’300
-
6’000
-
40
100(2)
Maximum making capacity
- DC current,  = 15 ms Imc [A]
- AC current, cos  = 0.8 (16.7, 25 & 50/60 Hz) Imc [Apeak]
6’000
6’000
6’000
-
6’000
-
100
200
Rated power-frequency withstand voltage (3)
- Between main contacts (open) U50 [kVrms]
- Main circuit (closed) to earth U50 [kVrms]
7.5
9.5
7.5
9.5
7.5
9.5
(1)
At Tamb = +40°C and tested with high voltage connections with current density 1.7A/mm2
, for DC and AC voltage up to 60 Hz. For
higher frequency, please contact Sécheron.
(2)
For higher value, contact Sécheron.
(3)
At 50 Hz and during 1 minute.
LOW VOLTAGE CIRCUIT
Control circuit
Nominal voltage
- 1 pole horizontal Un [VDC]
- 1 pole vertical Un / UEF
(4)
[VDC]
- 2 poles synchronised Un / UEF
(4)
[VDC]
24, 32, 36, 48, 72, 84, 110, 220
[24 - 36], [48 - 110] / [24 - 110]
[48 - 110] / [24 - 110]
24,...220
–
–
Range of voltage [0.7 - 1.25] Un [0.7 - 1.25] Un
Nominal closing power (5) (6)
- 1 pole horizontal Pc [W]
- 1 pole vertical Pc [W]
- 2 poles synchronised Pc [W]
 37
 60
 100
<40
–
–
Nominal holding power (5)
- 1 pole horizontal Ph [W]
- 1 pole vertical Ph [W]
- 2 poles synchronised Ph [W]
 37
 4
 6
–
–
–
(4)
Control voltage UEF and supply voltage Un can be different.
(5)
At Un and Tamb = +20°C.
(6)
The maximum operating time for PCC is 10sec, maximum closing time for BMS is 500ms.
Auxiliary contacts
Type of contacts Potential free (PF)
Rated voltage [VDC] 24 to 220
Conventional thermal current Ith [A] 10
Switching categories according to EN60947 - AC-15
- DC-13
230 VAC 1.0 A
110 VDC 0.5 A
Minimum let-through current at 24 VDC (7)
[mA]  10 (silver contacts) or 4  I < 10 (gold contacts)
(7)
For a dry and clean environment.
Low voltage interface
Control circuits
Auxiliary switches
Direct on coil (faston, horizontal) or Wago terminal (vertical)
Direct on switches (screw)
Insulation
Rated power-frequency withstand voltage (8)
- LV circuit to earth U50 [kVrms] 1.5 1.5
(8)
At 50 Hz and during 1 minute.
OPERATING CONDITIONS
Installation Indoor
Altitude [m] < 1’400
Working ambient temperature Tamb [°C] - 40 to + 70
Humidity 95% at + 40°C
Pollution degree PD3A PD3
Minimum mechanical durability N Cycles 2’000’000 2’000’000
4
6270903810
10
342
83
6xØ9.3
400
HV
144
107 60
363 (1800 VDC
)
203 (900VDC
/1800 VAC
)
363 (1800 VDC
)
203 (900VDC
/1800 VAC
)
80
270
54
LV (M3 screw
83
342
70
90
10
6xØ9.3
HV
270
80
95
107
54
LV (Wago terminal)
10
400
363(1’800VDC
)
203(900VDC
/1’800VAC
)
38
13
25
==
Ø11
HV connections
62
144
10760
HV connections (BMS..08) : M10 screws
LV connections (BMS control) : faston (horizontal)
or Wago terminal (vertical)
LV connections (BMS auxiliary switches) : M3 screws
Earth connections : M6 screws
Horizontal mounting version
BMS09.08 / BMS18.08 - 1 pole - Arc chute type A
Vertical mounting version
Information for product integration
Main dimensions
Dimensions without tolerances are indicative. All dimensions are in mm. The maximum allowed flatness deviation of the support
frame is 0.5 mm.
5
370(1800VDC
)
208 (900VDC
)
371 (1800VDC
) 57
328(900VDC
)
The dimensions indicated for all versions of contactors with arc chute type A (refer to page 4) are available for contactors equiped with arc chute type B,
except for the dimensions shown on the present drawing.
DD
AA
CC
BMS09.08 / BMS18.08 - Arc chute type B
Insulation distances and Weights
Insulating distances table [mm] Arc chute removal
distance [mm]
Weight:
± 0.5 kgWith earthed wall With insulating wall
A B C D A B C D E F G 1 pole 2 poles
BMS09.08A 75 10 75 75 40 10 40 40 70 30 35 9 15
BMS18.08A 75 10 75 75 40 10 40 40 90 20 40 10 17
BMS09.08B 40 10 40 40 20 10 20 20 70 45 50 10 17
BMS18.08B 40 10 40 40 20 10 20 20 80 20 80 12 21
LV (Wago terminal)
146
73
144
107
138
164
270
27.584
83
342
70
Ø9.3
HV
60
903810
10
400 (1800 VDC
)
363 (1800 VDC
)
203 (900VDC
/1800 VAC
)
400 (1800 VDC
)
342 (900VDC
/1800 VAC
)
BMS09.08A / BMS18.08A - 2 poles
6
Un
k0
BMS closing coil
Varistor
DC
DC
+
-
C
D
Un
k1
k0
UEF
1
2
3
4
BMS closing coil
DC / DC converter
Opto-isolator
Power contactor module
On project base, Secheron designs and delivers complete Power Contactor Modules integrating BMS and PCC contactors,
but also current measurement and other components necessary to fulfill the application.
All the components are delivered mounted on a support, with implemented high voltage connections between components, and
a single low voltage interface.
This module offers the car builder simple and easy interfaces, but also simplifies its life in terms of development, logistic and
installation.
Options (subject to additional costs)
Mounting support
Pre-charging contactor
(PCC18)
Current measurement
g support
LV connector
Line contactors BMS
Diagram 1 - horizontal mounting single pole Diagram 2
Legend
: Sécheron’s scope
: Customer’s scope
: Low voltage interface
: Coil controller
Un : DC power supply
UEF : Control voltage (1)
k0 : Supply relay
k1 : Control relay
Low voltage control diagram for BMS
Applicable for the following BMS configuration: Applicable for the following BMS configurations:
(1)
Control voltage (UEF) can be different from supply voltage (Un).
7
Un
k0
Un
k0
BMS
PCC18
BMS
closing coil
Varistor
Varistor
PCC
closing coil
Un
k1
k0
UEF
1
2
3
4
+
-
5
6
+
+
-
-
DC
DC
Un
k0
BMS
PCC18
DC / DC converter
BMS
closing coil
Opto-isolator
PCC
closing coil
Varistor
Additional weight: 3 kg
244
67
318
309
177
61
HV
LV LV
WAGO terminal
on BMS
HV
M3 screws or
The drawings hereabove represent the PCC18 when mounted on any BMS..08 versions. The other dimensions of the BMS..08
indicated on page 4 and 5 remain valid.
Main dimensions
HV connections (PCC18) : M6 screw
LV connections (PCC18’s coil): M3 screws or
WAGO terminal
LV connections (PCC18 auxiliary switches): M3 screws or
faston
Earth connection : Through BMS
Integrated pre-charing contactor (PCC18)
All dimensions are in mm. The maximum allowed flatness deviation of the support frame is 0.5 mm.
Control diagram
BMS
PCC18
Applicable for the following BMS configurations: Applicable for the following BMS configurations:
Diagram 1 Diagram 2
PCC18
BMS
Un : DC power supply
UEF : Control voltage (1)
k0 : Supply relay
k1 : Control relay
: Sécheron’s scope
: Customer’s scope
: Low voltage screw terminals
: Low voltage WAGO terminals
: Coil controller
(1)
Control voltage (UEF) can be different from supply voltage (Un).
Legend
Copyright© 2014 Sécheron SA
This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the
product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the
circumstances, of the product’s maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our “General Delivery Conditions”.
SG202168BEN_B06-0914
Sécheron SA
Rue du Pré-Bouvier 25
1217 Meyrin - Geneva
CH-Switzerland
Tel: +41 22 739 41 11
Fax: +41 22 739 48 11
info@secheron.com
www.secheron.com
Place and date: Name: Signature:
Designation code (options are subject to additional costs) - Order form
Line Description Designation Standard Options
Customer’s
choice
10 Product type BMS BMS BMS
11 Rated operational voltage 900 VDC or 1800 VAC 09
1800 VDC 18
12 Rated conventional free air thermal current (1)
800 A 08 08
13 Arc chute type Type A A
Type B B
14 Number of pole 1 pole 1
2 poles 2
15 Poles mechanical synchronization (1-pole) Not applicable Z
Synchronized S
Independent I
16 Integration of Pre-Charging Contactor PCC18 No 0
Yes (2)
C
17 Control voltage 24 VDC A
32 VDC F
36 VDC B
48 VDC C
72 VDC D
84 VDC H
110 VDC E
220 VDC J
18 Auxiliary contacts BMS 1a + 1b - (switch PF) - silver type A
1a + 1b - (switch PF) - gold type C
2a + 2b - (switch PF) - silver type E
2a + 2b - (switch PF) - gold type H
3a + 3b - (switch PF) - silver type K
3a + 3b - (switch PF) - gold type M
4a + 4b - (switch PF) - silver type O
4a + 4b - (switch PF) - gold type P
19 Auxiliary contacts (PCC18) (No PCC18) Not applicable Z
1a + 1b - (switch PF) - silver type 1
1a + 1b - (switch PF) - gold type 2
2a + 2b - (switch PF) - silver type 3
2a + 2b - (switch PF) - gold type 4
20 Installation Horizontal H
Vertical (2)
V
21 Application type (Direct Current) DC D
(Alternating Current) AC A
22 Opening BMS arc chute Arc chute lever A
Screw locking S
(1)
At Tamb = +40°C and tested with high voltage connections with current density 1.7A/mm2
, for DC and AC voltage up to 60 Hz. For
higher frequency, please contact Sécheron.
(2)
PCC18 is valid for horizontal mounting only.
Some combinations may not be possible, therefore validate your configuration with Sécheron before ordering.
Designation code for ordering
• Be sure to establish the designation code from the latest version of our brochure by downloading it from the
website: www.secheron.com
• Be careful to write down the complete alphanumerical designation code with 17 characters when placing your order
• For technical reasons some variants and options indicated in the designation code might not be combined
• For other configurations not described in the brochure, please contact Secheron
The bold characters of the designation code define the device type.
Example of customer’s choice: BMS 18 08 A 1 Z 0 E A Z H D S
Line: 10 11 12 13 14 15 16 17 18 19 20 21 22
Standard
09
18
08
A
1
2
Z
S
0
A
B
C
D
E
A
Z
1
H
D
A
Options
B
I
C
F
H
J
C
E
H
K
M
O
P
2
3
4
V
A
S

More Related Content

What's hot

Control & Isolation 5
Control & Isolation 5Control & Isolation 5
Control & Isolation 5Andy Birdsall
 
Advanced motion controls avb200a100
Advanced motion controls avb200a100Advanced motion controls avb200a100
Advanced motion controls avb200a100Electromate
 
Air Circuit Breakers BT3 Series - Fuji Electric
Air Circuit Breakers BT3 Series - Fuji ElectricAir Circuit Breakers BT3 Series - Fuji Electric
Air Circuit Breakers BT3 Series - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Advanced motion controls avb250a060
Advanced motion controls avb250a060Advanced motion controls avb250a060
Advanced motion controls avb250a060Electromate
 
Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20Electromate
 
Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAUTO RECLOSER
 
Advanced motion controls s30a40
Advanced motion controls s30a40Advanced motion controls s30a40
Advanced motion controls s30a40Electromate
 
Lm 317 to 92 datasheet
Lm 317 to 92 datasheetLm 317 to 92 datasheet
Lm 317 to 92 datasheetAndy Medina
 
ABB Contactors - 4 Pole Contactors ABB AF09 AF09Z (AC DC) Contactors
ABB Contactors - 4 Pole Contactors ABB AF09 AF09Z  (AC DC) ContactorsABB Contactors - 4 Pole Contactors ABB AF09 AF09Z  (AC DC) Contactors
ABB Contactors - 4 Pole Contactors ABB AF09 AF09Z (AC DC) ContactorsThorne & Derrick International
 
Original Power Supply IC LNK616PG LNK616P LNK616 DIP-7 New
Original Power Supply IC LNK616PG LNK616P LNK616 DIP-7 NewOriginal Power Supply IC LNK616PG LNK616P LNK616 DIP-7 New
Original Power Supply IC LNK616PG LNK616P LNK616 DIP-7 NewAUTHELECTRONIC
 
Advanced motion controls avb125a200
Advanced motion controls avb125a200Advanced motion controls avb125a200
Advanced motion controls avb125a200Electromate
 
Advanced motion controls s100a40
Advanced motion controls s100a40Advanced motion controls s100a40
Advanced motion controls s100a40Electromate
 
ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...
ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...
ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...Thorne & Derrick International
 

What's hot (20)

Control & Isolation 5
Control & Isolation 5Control & Isolation 5
Control & Isolation 5
 
Cptg011 en (web)
Cptg011 en (web)Cptg011 en (web)
Cptg011 en (web)
 
Thông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LSThông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LS
 
Advanced motion controls avb200a100
Advanced motion controls avb200a100Advanced motion controls avb200a100
Advanced motion controls avb200a100
 
Air Circuit Breakers BT3 Series - Fuji Electric
Air Circuit Breakers BT3 Series - Fuji ElectricAir Circuit Breakers BT3 Series - Fuji Electric
Air Circuit Breakers BT3 Series - Fuji Electric
 
Lm358
Lm358Lm358
Lm358
 
Busbar configuarations
Busbar configuarationsBusbar configuarations
Busbar configuarations
 
000647
000647000647
000647
 
Advanced motion controls avb250a060
Advanced motion controls avb250a060Advanced motion controls avb250a060
Advanced motion controls avb250a060
 
Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20
 
Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kv
 
Advanced motion controls s30a40
Advanced motion controls s30a40Advanced motion controls s30a40
Advanced motion controls s30a40
 
Max 232
Max 232Max 232
Max 232
 
01 1 rbs2216 outdoor system proposal by delta
01 1 rbs2216 outdoor system proposal by delta01 1 rbs2216 outdoor system proposal by delta
01 1 rbs2216 outdoor system proposal by delta
 
Lm 317 to 92 datasheet
Lm 317 to 92 datasheetLm 317 to 92 datasheet
Lm 317 to 92 datasheet
 
ABB Contactors - 4 Pole Contactors ABB AF09 AF09Z (AC DC) Contactors
ABB Contactors - 4 Pole Contactors ABB AF09 AF09Z  (AC DC) ContactorsABB Contactors - 4 Pole Contactors ABB AF09 AF09Z  (AC DC) Contactors
ABB Contactors - 4 Pole Contactors ABB AF09 AF09Z (AC DC) Contactors
 
Original Power Supply IC LNK616PG LNK616P LNK616 DIP-7 New
Original Power Supply IC LNK616PG LNK616P LNK616 DIP-7 NewOriginal Power Supply IC LNK616PG LNK616P LNK616 DIP-7 New
Original Power Supply IC LNK616PG LNK616P LNK616 DIP-7 New
 
Advanced motion controls avb125a200
Advanced motion controls avb125a200Advanced motion controls avb125a200
Advanced motion controls avb125a200
 
Advanced motion controls s100a40
Advanced motion controls s100a40Advanced motion controls s100a40
Advanced motion controls s100a40
 
ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...
ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...
ABB MV Indoor Voltage Transformer : Indoor Cast Resin Voltage Transformer ABB...
 

Viewers also liked

Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...Yazid Alaoui
 
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415Patrick Volluz
 
Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...Yazid Alaoui
 
Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914Patrick Volluz
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit BreakersAmeen San
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsEnergyTech2015
 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devicesPrakash_13209
 
Free Electronics Projects Circuits and their Applications
Free Electronics Projects Circuits and their ApplicationsFree Electronics Projects Circuits and their Applications
Free Electronics Projects Circuits and their ApplicationsElectronics Hub
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 

Viewers also liked (11)

Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...
 
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
 
Presentation sap
Presentation sapPresentation sap
Presentation sap
 
Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...Culture of radical innovation and long-term performance in capital-intensive ...
Culture of radical innovation and long-term performance in capital-intensive ...
 
Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914Brochure_26-80S-ANSI _SG104309BEN_B04-0914
Brochure_26-80S-ANSI _SG104309BEN_B04-0914
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
circuit breakers
circuit breakerscircuit breakers
circuit breakers
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devices
 
Free Electronics Projects Circuits and their Applications
Free Electronics Projects Circuits and their ApplicationsFree Electronics Projects Circuits and their Applications
Free Electronics Projects Circuits and their Applications
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 

Similar to Power contactor components and specifications

Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnDien Ha The
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abbDien Ha The
 
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsThorne & Derrick International
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
Catalogue mitsubishi thiet bi dien acb dienhathe.vn
Catalogue mitsubishi thiet bi dien acb dienhathe.vnCatalogue mitsubishi thiet bi dien acb dienhathe.vn
Catalogue mitsubishi thiet bi dien acb dienhathe.vnDien Ha The
 
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vnLs catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vnDien Ha The
 
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 NewOriginal High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 NewAUTHELECTRONIC
 
SE three-phase-inverter-extended-power-datasheet
SE three-phase-inverter-extended-power-datasheetSE three-phase-inverter-extended-power-datasheet
SE three-phase-inverter-extended-power-datasheetOptimus Energy Philippines
 
Catalog ls susol vcb_e
Catalog ls susol vcb_eCatalog ls susol vcb_e
Catalog ls susol vcb_eDien Ha The
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40acElectromate
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40acElectromate
 
#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...
#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...
#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...Saikat Bhandari
 

Similar to Power contactor components and specifications (20)

Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abb
 
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
 
CWC - Contactor
CWC - ContactorCWC - Contactor
CWC - Contactor
 
Sistem breaker pro abb
Sistem breaker pro abbSistem breaker pro abb
Sistem breaker pro abb
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
Acb mitsu
Acb mitsuAcb mitsu
Acb mitsu
 
Catalogue mitsubishi thiet bi dien acb
Catalogue mitsubishi thiet bi dien acbCatalogue mitsubishi thiet bi dien acb
Catalogue mitsubishi thiet bi dien acb
 
Thông số kĩ thuật mitsubishi thiet bi dien acb
Thông số kĩ thuật mitsubishi thiet bi dien acbThông số kĩ thuật mitsubishi thiet bi dien acb
Thông số kĩ thuật mitsubishi thiet bi dien acb
 
Catalogue mitsubishi thiet bi dien acb dienhathe.vn
Catalogue mitsubishi thiet bi dien acb dienhathe.vnCatalogue mitsubishi thiet bi dien acb dienhathe.vn
Catalogue mitsubishi thiet bi dien acb dienhathe.vn
 
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vnLs catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 NewOriginal High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
Original High Voltage Isolation IC ACS710T KLA-12CB 710T SOP-16 New
 
Mcb c60 h dc
Mcb c60 h dcMcb c60 h dc
Mcb c60 h dc
 
SE three-phase-inverter-extended-power-datasheet
SE three-phase-inverter-extended-power-datasheetSE three-phase-inverter-extended-power-datasheet
SE three-phase-inverter-extended-power-datasheet
 
Catalog ls susol vcb_e
Catalog ls susol vcb_eCatalog ls susol vcb_e
Catalog ls susol vcb_e
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40ac
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40ac
 
#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...
#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...
#Solar #Design #TOOL PV System Design Calculations Report at Neotia Universit...
 

Power contactor components and specifications

  • 1. C O M P O N E N T S Power contactor Type BMS09.08 / 18.08
  • 2. 2 Ue [V] 900 1800 Ith [A] 800 Ith [A] Ue [V] 1800 BMS PCC18 PCC18 BMS..08 Type A (VDC) Type A (VDC) Type B (VDC) Type B (VDC) Type A (VAC) General information The BMS contactor, with more than hundred thousands units in operation worldwide, is a contactor valued by the car builders and operators of electric traction vehicles for its strong performance level and its extremely high reliability. Taking advantages of its recognized features and design, Sécheron has modernized the BMS to make a product platform particularly well adapted to actual requirements and standards. With its high modularity, the BMS offers variants and options that enable our customers to find the most appropriate version to fit their application, either as a stand-alone contactor, dual-pole contactor or delivered coupled with a Sécheron dedicated pre-charging contactor type PCC18. Power contactor modules convenient to order and easy to install are a frequent wish of our customers. Sécheron brings the best solution with “plug & play” units gathering line and pre-charging contactors, but also current measurement and customised high voltage and low voltage interfaces. Applications • Line contactors, assembled set of line and pre-charging contactors, main traction converter isolating contactor and other applications for locomotives, trains, EMUs, tramways / light rail vehicles • Contactors for fixed installations including DC power traction substations and other industrial fields Main features • Rated operation voltage 900 VDC or 1’800 VDC/AC • Conventional free air thermal current up to 800 A • Normally open and bi-directional contactor • Heavy duty class for mechanical operations with a minimum of 2 millions operations • Different designs of arc chutes matching installation space and operational performance requirements • Deliverable as a single unit with Secheron’s pre-charging contactor PCC18, current measurement, high/low voltage connections • Delivered in standard with control coil low voltage protection against surges • Low maintenance requirements with easy access to the main contacts for replacement • Very compact size and extremely low weight • Suitable for ambient temperature from -40°C to +70°C • Reference standards: IEC60077-1 /-2, IEC61373, NF-F16 101 /-102 Contactor configurations BMSArcChutesBMSBodyPre-charging contactor
  • 3. 3 Data for product selection High voltage circuit values are indicated for each pole< Symbol Unit BMS09.08A BMS09.08B BMS18.08A BMS18.08B PCC18 MAIN HIGH VOLTAGE CIRCUIT Rated operational voltage Ue [VDC] (16.7, 25, 50/60, ...400 Hz) [VAC] 900 1’800 900 - 1’800 - 1’800 1’800 Rated insulation voltage Ui [VDC] [VAC] 2’300 2’300 2300 - 2’300 - 2’300 2’300 Conventional free air thermal current (1) Ith [A] 800 800 N.A. Rated operational current Ie [ADC] and operational frequency Ie [ADC] [AAC] 500 / C2 800 / C1 800 / C2 800/C2 - - 500 / C2 800 / C1 - - 800 / C1 - N.A. Rated short-time withstand current Icw / t [kA]/[ms] 10 / 100 10 / 100 N.A. Peak short-time withstand current Îcw [kA] 10 10 N.A. Maximum breaking capacity - DC current,  = 15 ms Ibc [A] - AC current, cos  = 0.8 (16.7, 25 & 50/60 Hz) Ibc [Arms] 3’200 4’200 6’000 - 2’300 - 6’000 - 40 100(2) Maximum making capacity - DC current,  = 15 ms Imc [A] - AC current, cos  = 0.8 (16.7, 25 & 50/60 Hz) Imc [Apeak] 6’000 6’000 6’000 - 6’000 - 100 200 Rated power-frequency withstand voltage (3) - Between main contacts (open) U50 [kVrms] - Main circuit (closed) to earth U50 [kVrms] 7.5 9.5 7.5 9.5 7.5 9.5 (1) At Tamb = +40°C and tested with high voltage connections with current density 1.7A/mm2 , for DC and AC voltage up to 60 Hz. For higher frequency, please contact Sécheron. (2) For higher value, contact Sécheron. (3) At 50 Hz and during 1 minute. LOW VOLTAGE CIRCUIT Control circuit Nominal voltage - 1 pole horizontal Un [VDC] - 1 pole vertical Un / UEF (4) [VDC] - 2 poles synchronised Un / UEF (4) [VDC] 24, 32, 36, 48, 72, 84, 110, 220 [24 - 36], [48 - 110] / [24 - 110] [48 - 110] / [24 - 110] 24,...220 – – Range of voltage [0.7 - 1.25] Un [0.7 - 1.25] Un Nominal closing power (5) (6) - 1 pole horizontal Pc [W] - 1 pole vertical Pc [W] - 2 poles synchronised Pc [W]  37  60  100 <40 – – Nominal holding power (5) - 1 pole horizontal Ph [W] - 1 pole vertical Ph [W] - 2 poles synchronised Ph [W]  37  4  6 – – – (4) Control voltage UEF and supply voltage Un can be different. (5) At Un and Tamb = +20°C. (6) The maximum operating time for PCC is 10sec, maximum closing time for BMS is 500ms. Auxiliary contacts Type of contacts Potential free (PF) Rated voltage [VDC] 24 to 220 Conventional thermal current Ith [A] 10 Switching categories according to EN60947 - AC-15 - DC-13 230 VAC 1.0 A 110 VDC 0.5 A Minimum let-through current at 24 VDC (7) [mA]  10 (silver contacts) or 4  I < 10 (gold contacts) (7) For a dry and clean environment. Low voltage interface Control circuits Auxiliary switches Direct on coil (faston, horizontal) or Wago terminal (vertical) Direct on switches (screw) Insulation Rated power-frequency withstand voltage (8) - LV circuit to earth U50 [kVrms] 1.5 1.5 (8) At 50 Hz and during 1 minute. OPERATING CONDITIONS Installation Indoor Altitude [m] < 1’400 Working ambient temperature Tamb [°C] - 40 to + 70 Humidity 95% at + 40°C Pollution degree PD3A PD3 Minimum mechanical durability N Cycles 2’000’000 2’000’000
  • 4. 4 6270903810 10 342 83 6xØ9.3 400 HV 144 107 60 363 (1800 VDC ) 203 (900VDC /1800 VAC ) 363 (1800 VDC ) 203 (900VDC /1800 VAC ) 80 270 54 LV (M3 screw 83 342 70 90 10 6xØ9.3 HV 270 80 95 107 54 LV (Wago terminal) 10 400 363(1’800VDC ) 203(900VDC /1’800VAC ) 38 13 25 == Ø11 HV connections 62 144 10760 HV connections (BMS..08) : M10 screws LV connections (BMS control) : faston (horizontal) or Wago terminal (vertical) LV connections (BMS auxiliary switches) : M3 screws Earth connections : M6 screws Horizontal mounting version BMS09.08 / BMS18.08 - 1 pole - Arc chute type A Vertical mounting version Information for product integration Main dimensions Dimensions without tolerances are indicative. All dimensions are in mm. The maximum allowed flatness deviation of the support frame is 0.5 mm.
  • 5. 5 370(1800VDC ) 208 (900VDC ) 371 (1800VDC ) 57 328(900VDC ) The dimensions indicated for all versions of contactors with arc chute type A (refer to page 4) are available for contactors equiped with arc chute type B, except for the dimensions shown on the present drawing. DD AA CC BMS09.08 / BMS18.08 - Arc chute type B Insulation distances and Weights Insulating distances table [mm] Arc chute removal distance [mm] Weight: ± 0.5 kgWith earthed wall With insulating wall A B C D A B C D E F G 1 pole 2 poles BMS09.08A 75 10 75 75 40 10 40 40 70 30 35 9 15 BMS18.08A 75 10 75 75 40 10 40 40 90 20 40 10 17 BMS09.08B 40 10 40 40 20 10 20 20 70 45 50 10 17 BMS18.08B 40 10 40 40 20 10 20 20 80 20 80 12 21 LV (Wago terminal) 146 73 144 107 138 164 270 27.584 83 342 70 Ø9.3 HV 60 903810 10 400 (1800 VDC ) 363 (1800 VDC ) 203 (900VDC /1800 VAC ) 400 (1800 VDC ) 342 (900VDC /1800 VAC ) BMS09.08A / BMS18.08A - 2 poles
  • 6. 6 Un k0 BMS closing coil Varistor DC DC + - C D Un k1 k0 UEF 1 2 3 4 BMS closing coil DC / DC converter Opto-isolator Power contactor module On project base, Secheron designs and delivers complete Power Contactor Modules integrating BMS and PCC contactors, but also current measurement and other components necessary to fulfill the application. All the components are delivered mounted on a support, with implemented high voltage connections between components, and a single low voltage interface. This module offers the car builder simple and easy interfaces, but also simplifies its life in terms of development, logistic and installation. Options (subject to additional costs) Mounting support Pre-charging contactor (PCC18) Current measurement g support LV connector Line contactors BMS Diagram 1 - horizontal mounting single pole Diagram 2 Legend : Sécheron’s scope : Customer’s scope : Low voltage interface : Coil controller Un : DC power supply UEF : Control voltage (1) k0 : Supply relay k1 : Control relay Low voltage control diagram for BMS Applicable for the following BMS configuration: Applicable for the following BMS configurations: (1) Control voltage (UEF) can be different from supply voltage (Un).
  • 7. 7 Un k0 Un k0 BMS PCC18 BMS closing coil Varistor Varistor PCC closing coil Un k1 k0 UEF 1 2 3 4 + - 5 6 + + - - DC DC Un k0 BMS PCC18 DC / DC converter BMS closing coil Opto-isolator PCC closing coil Varistor Additional weight: 3 kg 244 67 318 309 177 61 HV LV LV WAGO terminal on BMS HV M3 screws or The drawings hereabove represent the PCC18 when mounted on any BMS..08 versions. The other dimensions of the BMS..08 indicated on page 4 and 5 remain valid. Main dimensions HV connections (PCC18) : M6 screw LV connections (PCC18’s coil): M3 screws or WAGO terminal LV connections (PCC18 auxiliary switches): M3 screws or faston Earth connection : Through BMS Integrated pre-charing contactor (PCC18) All dimensions are in mm. The maximum allowed flatness deviation of the support frame is 0.5 mm. Control diagram BMS PCC18 Applicable for the following BMS configurations: Applicable for the following BMS configurations: Diagram 1 Diagram 2 PCC18 BMS Un : DC power supply UEF : Control voltage (1) k0 : Supply relay k1 : Control relay : Sécheron’s scope : Customer’s scope : Low voltage screw terminals : Low voltage WAGO terminals : Coil controller (1) Control voltage (UEF) can be different from supply voltage (Un). Legend
  • 8. Copyright© 2014 Sécheron SA This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser’s responsibility to inform himself, no matter what the circumstances, of the product’s maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our “General Delivery Conditions”. SG202168BEN_B06-0914 Sécheron SA Rue du Pré-Bouvier 25 1217 Meyrin - Geneva CH-Switzerland Tel: +41 22 739 41 11 Fax: +41 22 739 48 11 info@secheron.com www.secheron.com Place and date: Name: Signature: Designation code (options are subject to additional costs) - Order form Line Description Designation Standard Options Customer’s choice 10 Product type BMS BMS BMS 11 Rated operational voltage 900 VDC or 1800 VAC 09 1800 VDC 18 12 Rated conventional free air thermal current (1) 800 A 08 08 13 Arc chute type Type A A Type B B 14 Number of pole 1 pole 1 2 poles 2 15 Poles mechanical synchronization (1-pole) Not applicable Z Synchronized S Independent I 16 Integration of Pre-Charging Contactor PCC18 No 0 Yes (2) C 17 Control voltage 24 VDC A 32 VDC F 36 VDC B 48 VDC C 72 VDC D 84 VDC H 110 VDC E 220 VDC J 18 Auxiliary contacts BMS 1a + 1b - (switch PF) - silver type A 1a + 1b - (switch PF) - gold type C 2a + 2b - (switch PF) - silver type E 2a + 2b - (switch PF) - gold type H 3a + 3b - (switch PF) - silver type K 3a + 3b - (switch PF) - gold type M 4a + 4b - (switch PF) - silver type O 4a + 4b - (switch PF) - gold type P 19 Auxiliary contacts (PCC18) (No PCC18) Not applicable Z 1a + 1b - (switch PF) - silver type 1 1a + 1b - (switch PF) - gold type 2 2a + 2b - (switch PF) - silver type 3 2a + 2b - (switch PF) - gold type 4 20 Installation Horizontal H Vertical (2) V 21 Application type (Direct Current) DC D (Alternating Current) AC A 22 Opening BMS arc chute Arc chute lever A Screw locking S (1) At Tamb = +40°C and tested with high voltage connections with current density 1.7A/mm2 , for DC and AC voltage up to 60 Hz. For higher frequency, please contact Sécheron. (2) PCC18 is valid for horizontal mounting only. Some combinations may not be possible, therefore validate your configuration with Sécheron before ordering. Designation code for ordering • Be sure to establish the designation code from the latest version of our brochure by downloading it from the website: www.secheron.com • Be careful to write down the complete alphanumerical designation code with 17 characters when placing your order • For technical reasons some variants and options indicated in the designation code might not be combined • For other configurations not described in the brochure, please contact Secheron The bold characters of the designation code define the device type. Example of customer’s choice: BMS 18 08 A 1 Z 0 E A Z H D S Line: 10 11 12 13 14 15 16 17 18 19 20 21 22 Standard 09 18 08 A 1 2 Z S 0 A B C D E A Z 1 H D A Options B I C F H J C E H K M O P 2 3 4 V A S