Catalogue tai sin www.thietbidienngan.com-2014

  1. 1. 1 Stranded Plain Annealed Copper Conductor ___________________________________________________ 2 PVC Cables – Single Core _________________________________________________________________ 3 PVC/ PVC Cables – 1 Core & 2 Cores _______________________________________________________ 4 PVC/ PVC Cables – 3 Cores & 4 Cores _______________________________________________________ 5 PVC/ PVC Cables – Multi Cores ____________________________________________________________ 6 PVC/ AWA/ PVC Cables – Single Core ______________________________________________________ 7 PVC/ SWA/ PVC Cables – 2 Cores, 3 Cores & 4 Cores __________________________________________ 8 PVC/ SWA/ PVC Cables - Multi Cores _______________________________________________________ 9 Flexible Cable, Circular Sheathed, Metric Unit - 2 Cores, 3 Cores & 4 Cores _________________________ 10 Flexible Cord, Twin Twisted, Imperial Unit ___________________________________________________ 11 Flexible Cable, Circular Sheathed, Imperial Unit – 1 Core, 2 Cores, 3 Cores & 4 Cores _________________ 11 XLPE/ PVC & XLPE/ AWA/ PVC Cables – Single Core _________________________________________ 12 XLPE/ PVC & XLPE/ SWA/ PVC Cables - 2 Cores, 3 Cores & 4 Cores _____________________________ 13 XLPE/ PVC & XLPE/ SWA/ PVC Cables – Multi Cores _________________________________________ 14 IN-POP & IN-POSP - Multi Cores __________________________________________________________ 15 IN-POP & IN-POSP – Single & Multi Pairs ___________________________________________________ 16 IN-PIOP & IN-PIOSP – Multi Pairs _________________________________________________________ 17 IN-EOP & IN-EOSP – Single & Multi Pairs ___________________________________________________ 18 IN-EIOP & IN-EIOSP – Multi Pairs _________________________________________________________ 19 XLPE/ CT/ AWA/ PVC Cables – Single Core _________________________________________________ 20 XLPE/ CT/ SWA/ PVC Cables – 4 Cores _____________________________________________________ 21 XLPE/ CT/ PVC Cables – 3 Cores + 3 Earth ___________________________________________________ 22 Schedule of Installation Methods of Cables ____________________________________________________ 23 Correction Factors _______________________________________________________________________ 26 Current Rating and Voltage Drop (PVC Insulated Cables) ________________________________________ 28 Current Rating and Voltage Drop (XLPE Insulated Cables) _______________________________________ 32 Current Rating and Voltage Drop (Flexible Cables) _____________________________________________ 36 Short Circuit Current for PVC Insulated & XLPE Insulated Cables _________________________________ 37 Short Circuit Ratings _____________________________________________________________________ 38 Additional Technical Information ___________________________________________________________ 39 Conversion Tables of Conductor Size ________________________________________________________ 40
  2. 2. 2 Stranded Plain Annealed Copper Conductor BS 66360 & IEC 60228 Table 1 Nominal Conductor Area No. and Diameter of Wire No. and Diameter of Conductor Maximum Conductor Resistance at 200C Nominal Weight per km of Conductor (mm2) (no./mm) (mm) (Ω/km) (kg/km) 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 7/ 0.43 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 1.29 1.59 2.01 2.55 3.12 4.05 5.10 6.42 7.56 8.90 10.70 12.60 14.21 15.75 17.64 20.25 22.68 25.65 28.80 32.76 37.05 41.60 18.1 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176 9.2 14.0 22.4 36.1 54 90.8 145 229 317 429 620 860 1086 1334 1673 2199 2759 3528 4448 5744 7346 9260 Construction Technical Data 1. Conductor : Plain Annealed Copper Conductor Stranding : Class 2 stranded circular or compacted conductors
  3. 3. 3 PVC Cables SS358 Table 2 Nominal Conductor Area No. and Diameter Of Wire Radial Thickness Of Insulation Mean Overall Diameter (Upper Limit) Approx. Weight Minimum Insulation Resistance at 700C (mm2) (no./mm) (mm) (mm) (kg/ km) (mΩ/ km) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 0.7 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 3.4 4.2 4.8 5.4 6.8 8.0 9.8 11.0 13.0 15.0 17.0 19.0 21.0 23.5 26.5 29.5 33.5 37.0 41.0 22.7 34.0 50.0 70.9 117.5 177.4 279.5 372.0 504.5 710.6 980.8 1216.0 1498.0 1874.0 2444.4 3059.5 3897.0 4940.0 6295.0 0.010 0.009 0.0077 0.0065 0.0065 0.0050 0.0050 0.0040 0.0045 0.0035 0.0035 0.0032 0.0032 0.0032 0.0032 0.0030 0.0028 0.0028 0.0025 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type C 3. Colour: Red, Yellow, Blue, Black, Green, White, or Green/ Yellow Voltage Uo/U: 450/ 750V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700C Minimum Bending Radius: 3D for D < 10mm 4D for 10mm < D < 25mm 6D for D > 25mm
  4. 4. 4 PVC/ PVC Cables IEC 60502 Table 3 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 2.8 3.0 6.3 6.7 7.6 8.2 9.2 10.2 11.9 13.1 14.8 16.6 19.2 20.8 23.0 25.4 28.7 31.7 35.3 39.5 43.2 47.7 53.0 55 70 100 125 175 240 350 460 595 810 1110 1360 1670 2070 2690 3340 4230 5290 6680 8460 10545 2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 (S) 2 x 35 (S) 2 x 50 (S) 2 x 70 (S) 2 x 95 (S) 2 x 120 (S) 2 x 150 (S) 2 x 185 (S) 2 x 240 (S) 2 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 10.4 11.2 13.1 14.2 16.1 18.2 21.8 24.0 23.0 26.0 30.0 32.0 36.0 40.0 44.0 49.0 145 180 255 285 395 590 900 1160 1260 1700 2310 2880 3520 4290 5570 6970 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type A 3. Sheath: PVC Compound Type ST1 4. Colour: Insulation: 1 Core - Black 2 Cores- Red & Black Sheath: 1 Core – Grey 2 Cores - Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700C Minimum Bending Radius: 1 Core – 8D for 1.5mm2 to 1000mm2 2 Cores – 8D for 1.5mm2 to 300mm2
  5. 5. 5 PVC/ PVC Cables IEC 60502 Table 4 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 (S) 3 x 35 (S) 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 10.9 11.8 13.8 15.0 17.1 19.3 23.2 25.7 26.0 29.0 34.0 37.0 40.0 45.0 51.2 56.0 165 210 305 370 515 740 1160 1520 1750 2435 3360 4140 5070 6330 8265 10355 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 11.7 12.8 15.0 16.4 18.6 21.2 25.6 28.4 26.0 29.0 33.0 39.0 42.5 47.0 52.0 58.2 65.0 200 255 375 455 665 930 1465 1920 1740 2320 3215 4400 5440 6675 8360 10870 13650 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type A 3. Sheath: PVC Compound Type ST1 3. Colour: Insulation: 3 Cores – Red, Yellow, Blue 4 Cores- Red , Yellow, Blue, Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700C Minimum Bending Radius: 8D for 1.5mm2 to 300mm2 PVC/ PVC Cables Table 5 No. of Nominal Conductor No. and Diameter Radial Thickness Approx. Overall Approx. Weight
  6. 6. 6 Cores Area of Wire of Insulation Diameter (mm2) (no./mm) (mm) (mm) (kg/ km) 2 3 4 5 7 10 12 19 27 37 48 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.8 9.2 10.0 10.8 11.7 14.8 15.2 17.9 21.4 24.0 27.6 109 129 154 190 240 330 385 560 770 1015 1300 2 3 4 5 7 10 12 19 27 37 48 2.5 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 10.0 10.6 11.5 12.7 13.7 17.4 18.0 21.2 25.4 28.6 33.0 148 171 218 270 340 490 560 820 1135 1560 1930 2 3 4 5 7 10 12 19 27 37 48 4 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 11.5 12.2 13.3 14.7 16.2 20.6 21.3 25.1 30.4 34.2 39.3 205 252 315 415 535 720 850 1260 1740 2300 2900 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Sheath: PVC Compound Type TM1 3. Colour: Insulation: White with Black numberings Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular Operating Temperature: Maximum 700C Minimum Bending Radius: 3D for D < 10mm 4D for 10mm < D < 25mm 6D for D > 25mm
  7. 7. 7 PVC/ AWA/ PVC Cables BS 6346 Table 6 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 50 70 95 120 150 185 240 300 400 500 630 800 1000 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 2.8 3.0 19.1 21.1 23.4 26.3 28.3 30.8 34.1 37.0 42.0 45.6 49.7 55.8 61.0 760 1010 1330 1690 2110 2450 3120 3810 4890 5990 7510 9590 11820 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Bedding: PVC Compound Type TM1 4. Armour: Aluminium Wire 5. Sheath: PVC Compound Type TM1 6. Colour: Insulation: Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700C Minimum Bending Radius: 6D for 50mm2 to 1000mm2
  8. 8. 8 PVC/ SWA/ PVC Cables BS 6346 Table 7 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 (S) 2 x 70 (S) 2 x 95 (S) 2 x 120 (S) 2 x 150 (S) 2 x 185 (S) 2 x 240 (S) 2 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 12.3 13.6 15.1 16.5 20.1 21.9 26.7 29.4 27.4 30.0 34.7 37.2 40.5 45.2 50.0 54.8 270 340 450 550 750 960 1400 1750 1990 2500 2460 4120 4890 6250 7860 9480 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 12.8 14.1 15.8 18.0 21.2 23.1 28.2 30.8 30.1 34.2 38.5 41.4 46.3 50.7 56.2 61.6 350 400 520 730 1010 1180 1760 2170 2560 3520 4640 5500 6970 8400 10550 12800 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 13.5 15.0 17.8 19.2 22.8 26.3 30.7 33.7 29.9 34.6 38.4 43.5 48.1 52.4 57.4 64.1 70.4 345 440 710 810 1130 1550 2150 2670 2510 3410 4400 5830 7400 8810 10660 13430 16330 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Bedding: PVC Compound Type TM1 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type TM1 6. Colour: Insulation: 2 Cores- Red, Black 3 Cores – Red, Yellow, Blue 4 Cores – Red, Yellow, Blue, Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700C Minimum Bending Radius: 6D for 1.5mm2 to 16mm2 8D for 25mm2 and above PVC/SWA/ PVC Cables BS 6346 Table 8 No. Nominal No. and Radial Approx. Approx.
  9. 9. 9 Of Cores Conductor Area Diameter of Wire Thickness of Insulation Overall Diameter Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 5 7 10 12 19 27 37 48 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 14.3 15.2 19.0 19.4 22.2 26.7 29.2 32.9 357 416 446 716 938 1380 1689 2048 5 7 10 12 19 27 37 48 2.5 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 16.3 18.0 21.9 22.4 26.6 30.7 34.0 39.5 465 557 878 955 1455 1885 2340 3190 5 7 10 12 19 27 37 48 4 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 19.0 20.5 26.1 26.8 30.5 37.1 40.8 46.0 750 905 1405 1530 2060 3025 3900 4800 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Bedding: PVC Compound Type TM1 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type TM1 6. Colour: Insulation:White with Black numberings Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700C Minimum Bending Radius: 6D for 1.5mm2 to 4mm2
  10. 10. 10 Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.1 Conductor Thickness of Insulation 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 0.5 0.75 1.0 1.25 1.5 2.5 4.0 16/ 0.20 24/ 0.20 32/ 0.20 40/ 0.20 30/ 0.25 50/ 0.25 56/ 0.30 0.6 0.6 0.6 0.7 0.7 0.8 0.8 6.1 6.6 6.9 7.6 7.8 9.6 11.0 55 65 75 80 90 135 135 Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.2 Conductor Thickness of Insulation 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 0.5 0.75 1.0 1.25 1.5 2.5 4.0 16/ 0.20 24/ 0.20 32/ 0.20 40/ 0.20 30/ 0.25 50/ 0.25 56/ 0.30 0.6 0.6 0.6 0.7 0.7 0.8 0.8 6.5 6.9 7.3 8.3 8.5 10.4 11.8 60 75 85 100 110 170 215 Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.3 Conductor Thickness of Insulation 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2) (no./mm) (mm) (mm) (kg/ km) 0.5 0.75 1.0 1.25 1.5 2.5 4.0 16/ 0.20 24/ 0.20 32/ 0.20 40/ 0.20 30/ 0.25 50/ 0.25 56/ 0.30 0.6 0.6 0.6 0.7 0.7 0.8 0.8 7.1 7.6 8.2 - 9.5 11.4 12.9 75 90 110 - 140 205 275 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation : PVC Compound Type TI2 3. Assembly : 2, 3 or 4 Cores are Twisted Together 4. Sheath : PVC Compound Type TM2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 5 Operating Temperature: 700
  11. 11. 11 Flexible Cord, Twin Twisted Non- Sheated, Imperial Unit BS 2004 Table 10.1 Conductor Thickness of Insulation Twin Twisted Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2) (no./in) (mm) (mm) (kg/ 100y) 0.41 0.67 1.17 14/ 0.0076 23/ 0.0076 40/ 0.0076 0.64 0.64 0.64 2.1 2.4 2.7 1.7 2.3 3.1 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation : PVC Compound Type TI1 3. Assembly : Two Cores Twisted Voltage Uo/U: 250/ 440V Conductor Stranding: Class 5 Operating Temperature: 700 Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.2 Conductor Thickness of Insulation 1 Core 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight Approx. Overall Diameter Approx. Net Weight (mm2) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y) 0.41 0.67 1.17 2.05 3.22 4.74 14/ 0.0076 23/ 0.0076 40/ 0.0076 70/ 0.0076 110/ 0.0076 162/ 0.0076 0.64 0.64 0.64 0.64 0.64 0.76 4.2 4.4 4.8 5.2 5.7 6.4 2.1 2.5 3.2 4.2 5.4 7.3 6.3 6.8 7.5 9.0 10.0 11.3 4.8 6.0 7.5 10.0 12.9 17.4 Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.3 Conductor Thickness of Insulation 3 Cores 4 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight Approx. Overall Diameter Approx. Net Weight (mm2) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y) 0.41 0.67 1.17 2.05 3.22 4.74 14/ 0.0076 23/ 0.0076 40/ 0.0076 70/ 0.0076 110/ 0.0076 162/ 0.0076 0.64 0.64 0.64 0.64 0.64 0.76 6.6 7.1 7.9 9.5 10.5 12.2 5.6 6.2 8.9 12.7 16.6 22.9 7.2 7.7 9.2 10.3 11.4 13.2 6.2 7.9 10.0 15.4 20.4 28.3 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation : PVC Compound Type TI1 3. Assembly : 1, 2, 3 or 4 Cores Twisted Togeher 4. Sheath: PVC Compound Type T6 Voltage Uo/U: 250/ 440V Conductor Stranding: Class 5 Operating Temperature: 700
  12. 12. 12 XLPE/ PVC & XLPE/ AWA/ PVC Cables IEC 60502 Table 11 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation XP XAP Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8 9.6 11.3 12.5 14.0 16.1 18.2 20.0 22.2 24.4 27.5 30.3 33.9 37.6 42.4 47.3 52.4 205 309 412 540 760 1020 1270 1560 1930 2510 3120 3970 4980 6400 8190 10265 - 10.6 11.8 13.3 15.4 17.3 19.1 21.0 23.3 26.1 28.7 32.1 35.7 40.4 45.1 50.1 - 0.9 0.9 1.25 1.25 1.25 1..6 1.60 1.60 1.6 1.6 2.0 2.0 2.0 2.5 2.5 - 16.0 17.2 19.4 21.5 23.4 25.9 27.9 30.1 33.2 35.8 40.9 44.6 49.2 55.7 61.0 - 470 581 800 960 1240 1650 1970 2390 3040 3790 4790 5880 7400 9500 11750 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 4. Armour: Aluminium Wire 5. Sheath: PVC Compound Type ST2 6. Colour: Insulation: Natural Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900C Minimum Bending Radius: Unarmoured: 8D for 16mm2 to 1000mm2 Armoured: 10D for 25mm2 to 1000mm2
  13. 13. 13 XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 12 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation XP XSP Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 (S) 2 x 70 (S) 2 x 95 (S) 2 x 120 (S) 2 x 150 (S) 2 x 185 (S) 2 x 240 (S) 2 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 10.0 10.8 11.9 13.0 14.9 17.0 20.4 22.7 21.0 24.0 26.9 29.9 33.4 37.1 45.0 50.0 130 165 210 270 390 450 820 1065 1140 1560 2130 2640 3270 4040 5150 6560 8.5 9.3 10.4 11.5 13.4 15.5 18.9 21.2 19.2 22.3 25.3 28.1 30.9 36.0 41.6 47.4 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.5 2.5 13.9 14.7 15.8 16.9 19.5 21.6 25.7 28.0 26.0 29.5 33.5 36.5 39.5 45.0 52.0 58.0 350 400 475 560 810 980 1410 1930 1880 2420 3360 3980 4730 6245 8720 9390 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 10.5 11.4 12.5 13.8 15.8 18.0 21.7 24.2 25.0 29.0 32.0 36.5 39.0 44.0 49.0 55.0 150 195 255 330 490 700 1000 1300 1600 2240 3050 3800 4640 5870 7670 9460 9.0 9.9 11.0 12.3 14.3 16.5 20.2 23.0 23.0 27.0 30.1 34.4 37.5 41.3 46.4 52.0 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 14.4 15.3 16.4 17.7 20.4 22.6 27.0 29.8 30.0 35.0 38.5 43.0 47.5 51.5 57.0 36.0 390 450 540 745 950 1250 1840 2280 2550 3500 4500 5700 6800 8200 10300 12500 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 11.3 12.3 13.6 15.0 17.2 19.7 23.9 26.6 25.0 28.5 32.0 37.0 42.0 46.0 50.0 55.0 36.0 175 225 305 405 600 870 1325 1760 1600 2200 3050 4070 5195 6350 7890 10400 12810 10.0 10.8 12.1 13.5 15.7 18.2 22.4 15.1 24.0 26.8 30.6 34.4 36.0 38.3 46.4 51.0 56.6 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 15.4 16.2 17.5 19.6 21.8 25.0 29.2 32.1 31.0 34.0 39.0 43.0 46.0 48.5 57.0 62.0 68.0 430 505 710 855 1120 1600 2160 2750 2500 3100 4400 5610 7400 8300 10400 13000 15900 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type ST2 6. Colour: Insulation: 2 Cores - Red, Black 3 Cores – Red, Yellow, Blue 4 Cores – Red, Yellow, Blue, Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900C Minimum Bending Radius: Unarmoured: 6D for 1.5mm2 to 300mm2 Armoured: 8D for 1.5mm2 to 300mm2
  14. 14. 14 XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 13 No. of Cores Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation XP XSP Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 5 7 12 19 37 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.7 0.7 0.7 0.7 0.7 11.9 12.9 16.5 19.4 25.4 214.5 235.5 391.1 522.0 981.0 10.5 11.5 15.1 17.7 23.3 0.9 0.9 1.25 1.25 1.6 15.9 16.9 21.2 23.8 30.1 493.9 560.7 903.9 1167.8 1872.0 5 7 12 19 37 2.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.7 0.7 0.7 0.7 0.7 13.1 14.1 18.4 21.4 18.4 280.4 317.5 500.0 737.0 1327.0 11.7 12.7 16.8 19.8 27.0 0.9 0.9 1.25 1.6 1.6 17.1 18.1 22.9 26.6 33.8 586.8 676.1 1095.8 1593.2 2361.0 5 7 12 19 37 4 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.7 0.7 0.7 0.7 0.7 14.5 16.0 20.6 24.1 32.2 381.6 470.0 709.0 1051.0 1989.0 13.1 14.3 18.6 22.0 30.1 1.25 1.25 1.25 1.6 1.6 19.2 20.4 24.7 28.8 36.9 823.0 906.0 1293.0 1904.0 2919.0 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type ST2 6. Colour: Insulation:White with Black numberings Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular Operating Temperature: Maximum 900C Minimum Bending Radius: Unarmoured: 6D for 1.5mm2 to 4mm2 Armoured: 8D for 1.5mm2 to 4mm2
  15. 15. 15 IN-POP & IN-POSP Cables Table 14 SIZE IN-POP IN-POSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2C x 0.5 3C x 0.5 4C x 0.5 6C x 0.5 10C x 0.5 20C x 0.5 40C x 0.5 80C x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.0 7.3 7.9 9.3 11.9 14.9 20.1 26.3 60 68 78 110 170 295 510 950 7.0 7.3 7.9 9.3 11.9 14.9 20.1 26.3 0.90 0.90 0.90 0.90 0.90 1.25 1.60 1.60 11.4 11.7 12.3 13.9 16.7 20.6 26.7 33.3 250 265 290 360 490 800 1300 2050 2C x 0.75 3C x 0.75 4C x 0.75 6C x 0.75 10C x 0.75 20C x 0.75 40C x 0.75 80C x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.3 7.7 8.3 9.9 12.7 16.0 21.7 28.5 65 78 92 128 200 355 640 1185 7.3 7.7 8.3 9.9 12.7 16.0 21.7 28.5 0.90 0.90 0.90 0.90 0.90 1.25 1.60 1.60 11.7 12.1 12.9 14.5 17.5 21.7 28.5 35.7 260 280 320 400 550 905 1500 2420 2C x 1.5 3C x 1.5 4C x 1.5 6C x 1.5 10C x 1.5 20C x 1.5 40C x 1.5 80C x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.3 8.9 9.7 11.7 14.7 18.7 24.6 33.6 90 115 140 200 315 560 1040 1970 8.3 8.9 9.7 11.7 14.7 18.7 24.6 33.6 0.90 0.90 0.90 0.90 1.25 1.60 1.60 2.00 12.9 13.5 14.3 16.3 20.4 25.3 31.6 41.8 310 360 400 515 820 1340 2090 3690 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are stranded in Reverse Layer Technique forming a Concentric Cable 4. Wrap film: Polyster Binder Tape 5. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 6. Bedding : PVC Compound Type TM1 (optional) 7. Armouring: Galvanised Steel Wire (optional) Reference standards: BS 5308 Part 2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 700C Testing Voltage: 1KV/ 1 Minute 8. Sheath: PVC Compound Type TM1 9. Colour: Insulation: Yellow with Black numberings or refer to colour code Sheath: Black
  16. 16. 16 IN-POP & IN-POSP Cables Table 15 SIZE IN-POP IN-POSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 1P x 0.5 2P(Quad) x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 60 78 185 310 430 540 780 1240 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 0.90 0.90 0.90 1.25 1.60 1.60 1.60 2.00 11.4 12.3 17.9 22.9 26.4 29.1 33.9 42.1 250 290 540 905 1270 1490 1960 3000 1P x 0.75 2P(Quad) x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.3 8.3 14.3 18.7 21.4 24.5 29.5 37.4 68 92 230 390 530 690 1010 1610 7.3 8.3 14.3 18.7 21.4 24.5 29.5 37.4 0.90 0.90 1.25 1.60 1.60 1.60 2.00 2.00 11.7 12.9 19.8 25.3 28.2 31.3 37.5 45.8 260 325 710 1170 1460 1750 2560 3550 1P x 1.5 2P(Quad) x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 90 142 330 580 860 1090 1600 2570 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 0.90 0.90 1.25 1.60 1.60 1.60 2.00 2.50 12.9 14.3 22.1 28.4 32.2 35.7 42.5 53.4 310 410 900 1510 1950 2330 3400 5320 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Wrap Film: Polyster Binder Tape 5. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 6. Bedding : PVC Compound Type TM1 (optional) 7. Armouring: Galvanised Steel Wire (optional) Reference standards: BS 5308 Part 2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 700C Testing Voltage: 1KV/ 1 Minute 8. Sheath: PVC Compound Type TM1 9. Colour: Insulation:White and Black numberings or refer to colour code Sheath: Black
  17. 17. 17 IN-POP & IN-POSP Cables Table 16 SIZE IN-PIOP IN-PIOSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2P x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.0 15.2 21.1 24.5 27.3 32.3 41.7 135 240 410 590 750 1090 1780 12.0 15.2 21.1 24.5 27.3 32.3 41.7 0.90 1.25 1.60 1.60 1.60 2.00 2.50 16.8 20.9 27.9 31.3 34.3 40.5 51.5 470 770 1320 1640 1910 2740 4400 2P x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.8 16.3 22.7 26.4 29.8 35.5 45.0 155 275 480 700 900 1310 2060 12.8 16.3 22.7 26.4 29.8 35.5 45.0 0.90 1.25 1.60 1.60 2.00 2.00 2.50 17.6 22.0 29.5 33.4 37.8 43.9 55.0 505 850 1450 1830 2430 3190 4970 2P x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 14.7 18.8 26.5 30.8 34.4 41.0 52.2 215 400 740 1060 1340 1970 3130 14.7 18.8 26.5 30.8 34.4 41.0 52.2 1.25 1.60 1.60 2.00 2.00 2.50 2.50 20.4 25.4 33.5 38.8 42.6 50.8 62.6 730 1200 1860 2660 3100 4550 6420 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Individual: Aluminium/ Polyester Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 5. Wrap Film: Polyster Binder Tape 6. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 7. Bedding : PVC Compound Type TM1 (optional) Reference standards: BS 5308 Part 2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 700C Testing Voltage: 1KV/ 1 Minute 8. Armouring: Galvanised Steel Wire (optional) 9. Sheath: PVC Compound Type TM110. Colour: 10. Colour: Insulation: White and Black numberings or refer to colour code Sheath: Black
  18. 18. 18 IN-EOP & IN-EOSP Cables Table 17 SIZE IN-EOP IN-EOSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 1P x 0.5 2P(Quad) x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 56 70 170 280 385 480 690 1080 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 0.90 0.90 0.90 1.25 1.60 1.60 1.60 2.00 11.4 12.3 17.9 22.9 26.4 29.1 33.9 42.1 230 270 500 830 1150 1360 1750 2730 1P x 0.75 2P(Quad) x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.4 8.4 14.2 18.4 21.3 24.4 29.0 37.3 68 95 230 385 540 705 995 1630 7.4 8.4 14.2 18.4 21.3 24.4 29.0 37.3 0.90 0.90 1.25 1.25 1.60 1.60 1.60 2.00 11.8 13.0 19.7 24.3 28.1 31.2 36.2 45.7 250 310 680 980 1380 1650 2150 3430 1P x 1.5 2P(Quad) x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 85 132 315 550 790 1000 1460 2340 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 0.90 0.90 1.25 1.60 1.60 1.60 2.00 2.50 12.9 14.3 22.1 28.4 32.2 35.7 42.5 53.4 290 380 840 1410 1790 2150 3100 4920 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Wrap Film: Polyster Binder Tape 5. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 6. Bedding : Polyethylene Compound Type 03 (optional) 7. Armouring: Galvanised Steel Wire (optional) Reference standards: BS 5308 Part 1 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 650C Testing Voltage: 1KV/ 1 Minute 8. Sheath: PVC Compound Type TM1 9. Colour: Insulation: White and Black numberings or refer to colour code Sheat: Black
  19. 19. 19 IN-EOP & IN-EOSP Cables Table 18 SIZE IN-EOP IN-EOSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2P x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.0 15.2 21.1 24.5 27.3 32.3 41.7 130 230 400 560 690 990 1610 12.0 15.2 21.1 24.5 27.3 32.3 41.7 0.90 1.25 1.60 1.60 1.60 2.00 2.50 16.8 20.9 27.9 31.3 34.3 40.5 51.5 430 720 1240 1530 1770 2550 4080 2P x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.8 16.3 22.7 26.4 29.8 35.5 45.0 155 285 500 720 930 1350 2130 12.8 16.3 22.7 26.4 29.8 35.5 45.0 0.90 1.25 1.60 1.60 2.00 2.00 2.50 17.6 21.9 29.4 33.2 37.8 43.8 54.9 480 800 1400 1760 2350 3060 4800 2P x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 14.7 18.8 26.5 30.8 34.4 41.0 52.2 210 380 690 990 1240 1820 2890 14.7 18.8 26.5 30.8 34.4 41.0 52.2 1.25 1.60 1.60 2.00 2.00 2.50 2.50 20.4 25.4 33.5 38.8 42.6 50.8 62.6 670 1110 1750 2460 2910 4250 6040 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: Polyethylene Compound Type 03 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Individual: Aluminium/ Polyester Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 5. Wrap Film: Polyster Binder Tape 6. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 7. Bedding : Polyethylene Compound Type 03 (optional) Reference standards: BS 5308 Part 1 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 650C Testing Voltage: 1KV/ 1 Minute 8. Armouring: Galvanised Steel Wire (optional) 9. Sheath: PVC Compound Type TM1 10. Colour: Insulation:White and Black numberings or refer to colour code Sheat: Black
  20. 20. 20 XLPE/ CT/ AWA/ PVC Cables IEC 60502 Table 19 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approximate Diameter Approx. Weight Under Screen Over Bedding Over Armour Over All (mm2) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km) 70 95 120 150 185 240 300 400 500 630 800 1000 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2. 85 127/ 3.20 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8 15.2 17.1 19.0 21.0 23.2 26.1 28.7 32.5 36.0 40.4 45.5 50.4 17.6 19.5 20.8 22.8 25.0 27.9 30.5 34.3 37.8 42.2 47.3 52.2 20.1 22.0 24.0 26.0 28.2 31.1 33.7 38.3 41..8 46.2 52.3 57.2 23.9 25.8 27.8 29.8 32.0 35.1 37.9 42.7 46.4 51.0 57.5 62.4 1400 1700 2000 2400 2800 3500 4200 5400 6500 8200 10400 13000 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Screen: Copper Tape 5. Armour: Aluminium Wire 6. Sheath: PVC Compound Type ST2 7. Colour: Insulation: Natural Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900C Minimum Bending Radius: 12D for 70mm2 to 1000mm2
  21. 21. 21 XLPE/ CT/ SWA/ PVC Cables IEC 60502 Table 20 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approximate Diameter Approx. Weight Under Screen Over Bedding Over Armour Over All (mm2) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km) 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 9.7 10.7 12.0 13.4 15.6 18.1 22.3 25.0 27.8 31.6 35.4 39.0 42.0 47.8 54.0 58.0 12.1 13.1 14.4 15.8 18.0 20.5 24.1 26.8 29.6 33.4 37.2 40.8 43.8 49.6 55.8 59.8 13.9 14.9 16.2 18.3 20.5 23.7 27.3 30.0 32.8 37.4 41.2 45.8 48.8 54.6 60.8 64.8 17.7 18.7 20.0 22.1 24.3 27.5 31.1 33.8 37.0 42.0 46.0 51.0 54.2 60.4 67.0 71.4 640 730 870 1180 1490 2070 2790 2940 3500 5000 6300 8200 9600 11500 14400 17200 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Screen: Copper Tape 5. Armour: Galvanised Steel Wire 6. Sheath: PVC Compound Type ST2 7. Colour: Insulation: Red, Yellow, Blue, Green/ Yellow Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900C Minimum Bending Radius: 12D for 1.5mm2 to 300mm2
  22. 22. 22 XLPE/ CT/ PVC Cables IEC 60502 Table 21 Nominal Conductor Area No. and Diameter of Wire Combined Earth Size Radial Thickness of Insulation Radial Thickness of Sheath Unarmoured Cable Overall Diameter Approx. Weight (mm2) (no./mm) (mm) (mm) (mm) (mm) (kg/ km) 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 4.5 (3 x 1.5) 4.5 (3 x 1.5) 4.5 (3 x 1.5) 7.5 (3 x 2.5) 12 (3 x 4) 18 (3 x 6) 30 (3 x 10) 30 (3 x 10) 30 (3 x 10) 48 (3 x 16) 48 (3 x 16) 75 (3 x 25) 75 (3 x 25) 105 (3 x 35 150 (3 x 50) 150 (3 x 50) 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.8 3.0 13.6 14.8 15.8 16.9 18.6 20.8 24.0 25.6 31.1 34.6 39.3 44.0 49.0 54.0 61.0 67.0 325 380 440 550 750 1000 1470 1890 2300 3200 4200 5400 6400 7900 10200 1230 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Screen: Copper Tape 4. Sheath: PVC Compound Type ST2 5. Colour: Insulation: Red, Yellow, Blue, Green/ Yellow (x3) Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 Operating Temperature: Maximum 900C for XLPE Maximum 1100C for XLEVA Minimum Bending Radius: 10D for unarmoured cable
  23. 23. 23 Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.1 Installation Method Examples Appropriate Reference Methoad For Determining Current- Carrying Capacity Description OPEN AND CLIPPED DIRECT: Sheathed cables clipped direct to or lying on a non- metallic surface Method 1 CABLES EMBEDDED DIRECT IN BUILDING MATERIALS: Sheathed cables embedded directly in masonry, brickwork, concrete, plaster or the like (other than thermally insulating materials) Method 1 IN CONDUIT: Single core non- sheathed cables in metallic or non- metallic conduit on a wall or ceiling Method 3 Single core non- sheathed cables in metallic or non- metallic conduit in a thermally insulating ceiling, the conduit being in contact with a thermally conductive surface on one side Method 4 Multi core cables having non- metallic sheath, in metallic or non- metallic conduit on a wall or ceiling Method 3  The wall is assumed to consist of an outer weatherproof skin, thermal insulation and an inner skin of plasterboard of wood- like material having a coefficient of heat transfer not less than 10 W/m2K. The conduit is fixed so as to be close to, but not necessarily touching, the inner skin. Heat from the cables is assumed ti escape through the inner skin only. • • • • • • •
  24. 24. 24 Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.2 Installation Method Examples Appropriate Reference Methoad For Determining Current- Carrying Capacity Description ON TRAYS: Sheathed cables on a perforated cable tray, bunched and unenclosed. A pertorated cable tray is considerd as a tray in which the holes occupy at least 30% of the surface area Method 11 IN FREE AIR, ON CLEATS, BRACKETS OR A LADDER: Sheathed single- core cables in free air (any supporting metalwork under the cables occupying less than 10% of the plan area Two of three cables vertically one above the other, minimum distance between cable surfaces equal to the overall cable diameter (De); distance from the wall not less than 0.5De Two or three cables horizontally, with spacings as above Three cables in trefoil, distance between wall and surface of nearest cable 0.5De or nearest cables 0.75De Method 12 Sheathed multicore cables on ladder or brackets, separation greater than 2De Sheathed multicore cables in free air distance between wall and cable surface not less than 0.3De Any supporting metalwork under the cables occupying less than 10% of the plan area Method 13 Cables suspended from or incorporating a catenary wire Method 12 or 13, as appropriate
  25. 25. 25 Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.3 Installation Method Examples Appropriate Reference Methoad For Determining Current- Carrying Capacity Description CABLES IN TRENCHES: Cables in enclosed trench 450mm wide by 300mm deep (minimum dimentions) including 100mm cover Two signle- core cables with surfaces sepaeerated by a minimum og one cable diameter Method 18 Use rating factors in Technical Table 3 Three single-core cables in trefoil and touching throughout Multicore cables or groups of single-core cables with surfaces separated by a minimum of 50mm Cables in enclosed trench 450mm wide by 600mm deep (minimum dimentions) including 100mm cover Single-core cables arranged in flat groups of two or three on the vertical trench wall with surfaces separated by one diameter with a minimum distance of 50mm between groups. Multicore cables installed with surfaces separated by a minimum of 75mm. All cables spaced at least 25mm from the trenched wall Method 19 Use rating factors in Technical Table 3 Cables in enclosed trench 600mm wide by 760mm deep (minimum dimentions) including 100mm cover Single-core cables arranged in groups of two or three in flat formation with the surfaces sepaerated by one diameter or in trefoil formation with cables touching Method 20 Use rating factors in Technical Table 3 Groups separated by a minimum* of 50mm either horizontally or vertically. Multi caor cables installed with surfaces separated by a minimum* of 75mm either horizontally or vertically. All cables spaced at least 25mm from the trench wall Larger spacing to be used where practicable
  26. 26. 26 Correction Factors For Groups of More than One Circuit Of Single-core Cables, or More than One Multicore Cable Technical Table 2 Reference Methods of Installation Correction Factor (C9) Number of Circuits of Multi-Core Cables 2 3 4 5 6 7 8 9 10 12 14 16 18 20 Enclosed (Method 3 or 4) or bunched and clipped direct to a non- metallic surface (Method 1) 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38 Single layer clipped to a non-metallic surface (Method 1) Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - - Spaced * 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 Single layer multi core on a perforated metal cable tray, vertical or horizontal (Method 11) Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - - Spaced * 0.91 0.89 0.88 0.87 0.87 - - - - - - - - - Single layer single core on a perforated metal cable tray, touching (Method 11) Horizontal 0.90 0.85 - - - - - - - - - - - - Vertical 0.85 - - - - - - - - - - - - - Single layer multi core touching on ladder supports 0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -  Space means a clearance between adjacent surfaces of at least one cable diameter (De). Where the horizontal clearance between adjacent cables exceeds 2 De, no correction factor need be applied. Notes: 1) The factors in the table are applicable to groups of cables all of one size. The value of current derived from application of the appropriate factors is the maximum continuous current to be carried by any of the cables in the group. 2) If, due to known operating conditions, a cable is expected to carry not more than 30% of it’s grouped rating, it may be ignored for the purposed of obtaining the rating factor for the rest of the group. For example, a group of N loaded cables would normally require a group reduction factor of Cg applied to the tabulated It. However, if M cables in the group carry loads which are not greater than 0.3Cglt amperes, the other cables can be sized by using the group rating factor corresponding to (N-M) cables. 3) Factors are given for single layer of cables and do not apply when cables are installed in more than one layer touching each other. 4) For circuits having more than one cable in parallel per phase, each set of three conductors should be considered as a circuit for the purpose of this table. Correction Factors for Cables installed in Enclosed Trenches Technical Table 3 Conductor cross- sectional area mm2 Installation Method 18 Installation Method 19 Installation Method 20 2 1-core cables, or 1 3- or 4- core cables 3 1-core cables, or 2 2-core cables 4 1-core cables, or 2 3- or 4- core cables 6 1-core cables, 4 2- core cables, or 3 3- or 4- core cables 6 1-core cables, 4 2- core cables, or 3 3- or 4- core cables 8 1-core cables, or 4 3- or 4- core cables 12 1-core cables, 8 2- core cables, or 6 3- or 4- core cables 12 1-core cables, 8 2- core cables, or 6 3- or 4- core cables 18 1-core cables, 12 2- core cables, or 9 3- or 4- core cables 24 1-core cables, 16 2- core cables, or 12 3- or 4- core cables 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 0.93 0.92 0.91 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82 0.81 0.80 0.78 0.77 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.82 0.81 0.80 0.78 0.77 0.76 0.74 0.73 0.72 0.71 0.87 0.86 0.85 0.84 0.82 0.81 0.79 0.78 0.76 0.75 0.74 0.73 0.71 0.69 0.67 0.66 0.65 0.82 0.81 0.80 0.78 0.76 0.75 0.74 0.72 0.70 0.69 0.67 0.65 0.63 0.62 0.59 0.58 0.56 0.86 0.86 0.85 0.83 0.81 0.80 0.78 0.77 0.75 0.73 0.72 0.70 0.69 0.68 0.66 0.64 0.63 0.83 0.82 0.80 0.78 0.76 0.74 0.73 0.72 0.70 0.68 0.67 0.65 0.63 0.62 0.60 0.58 0.57 0.76 0.75 0.74 0.71 0.69 0.68 0.66 0.64 0.63 0.61 0.59 0.58 0.56 0.54 0.52 0.51 0.49 0.81 0.80 0.78 0.76 0.74 0.72 0.71 0.70 0.68 0.66 0.64 0.63 0.61 0.59 0.57 0.56 0.54 0.74 0.73 0.72 0.70 0.67 0.66 0.64 0.62 0.60 0.58 0.57 0.55 0.53 0.52 0.50 0.48 0.47 0.69 0.68 0.66 0.64 0.62 0.60 0.59 0.57 0.55 0.53 0.51 0.49 0.48 0.46 0.44 0.43 0.41 The correction factors tabulated above relate to the disposition of cables illustrated in terms 18 to 20 of Technical Table 1.3 and are applicable to the current- carrying capacities for Reference Methods 12 or 13 of Technical Table 1.2. When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating temperature of any cable in the group.
  27. 27. 27 Technical Data Rating Factors for Other Temperature conditions Technical Table 4 Table A: Rating Factors for Other Ambient Air Temperature (PVC Insulated) Ambient Temperature 250C 300C 350C 400C 450C 500C 550C 600C 650C 700C Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35 - Table B: Rating Factors for Other Ground Temperature (PVC Insulated) Ambient Temperature 100C 150C 200C 250C 300C 350C 400C 450C 500C Rating Factor 1.04 1.00 0.95 0.90 0.85 0.80 0.73 0.67 0.60 Table C: Rating Factors for Other Ambient Air Temperature (XLPE Insulated) Ambient Temperature 250C 300C 350C 400C 450C 500C 550C 600C 650C 700C 750C 800C 850C Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29 Table D: Rating Factors for Other Ground Temperature (XLPE Insulated) Ambient Temperature 150C 200C 250C 300C 350C 400C 450C 500C Rating Factor 1.00 0.97 0.93 0.89 0.86 0.82 0.77 0.73 Table E: Rating factors for Other Ambient Air Temperature (PVC Insulated) Ambient Temperature 300C 350C 400C 450C 500C 550C 600C 650C 700C PVC cords, non-heat resisting 1.00 0.96 0.92 0.87 0.71 0.50 - - - PVC cords, heat resisting 1.00 - - - 1.00 0.96 0.83 0.67 0.47 Table F: Group Rating Factors for Cables Installation Group Rating Factors Numbers of Circuits 2 3 4 5 6 7 8 9 10 11 12 1 For circuits of 2 Single-core cables laid flat touching horizontal formation, laid direct in ground 0.79 0.68 0.62 0.57 0.54 0.52 0.50 0.48 0.47 0.46 0.45 2 For circuits of 3 Single-core cables in trefoil touching, laid direct in the ground 0.78 0.66 0.61 0.56 0.53 0.50 0.49 0.47 0.46 0.44 0.43 Number of Cables in a Group 2 3 4 5 6 7 8 9 10 11 12 3 For twin of multicore cables in horizontal formation, laid direct in ground Spaced 0.15m 0.87 0.78 0.74 0.70 0.68 0.66 0.64 0.63 0.62 0.61 0.60 Spaced 0.30m 0.91 0.84 0.81 0.78 0.77 0.75 0.75 0.74 0.73 0.73 0.72 Numbers of Ducts in a Group 2 3 4 5 6 7 8 9 10 11 12 4 For twin multicore cables in single-way ducts horizontal formation spaced 0.30m apart 0.93 0.88 0.85 0.83 0.82 0.81 0.80 0.79 0.79 0.78 0.78
  28. 28. 28 Current- Carrying Capacities (Amp) PVC & PVC/ PVC Cables Technical Table 5.1 Conductor cross- sectional area Reference Method 4 (Enclosed in conduit in thermally insulating wall etc) Reference Method 3 (Enclosed in conduit on a wall or in trunking etc) Reference Method 1 (‘Clipped direct’) Reference Method 11 (on a perforated cable tray horizontal of vertical) Reference Method 12 (free air) Horizontal flat spaced, Vertical flat spaced, 2 cables, single- phase ac or dc 3 or 4 cables 3- phase ac 2 cables, single- phase ac or dc 3 or 4 cables 3- phase ac 2 cables, single- phase ac or dc 3 or 4 cables 3- phase ac 2 cables, single- phase ac or dc or flat and touching 3 cables, 3-phase ac flat and touching 2 cables, single- phase ac or dc or 3 cables or trefoil 2 cables, single- phase ac or dc or 3 cables 3- phase ac 3 cables, trefoil 3-phase ac 3-phase ac mm2 Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp BS 6004 1 1.5 2.5 4 6 10 16 25 35 11 14.5 19.5 26 34 46 61 80 99 10.5 13.5 18 24 31 42 56 73 89 13.5 17.5 24 32 41 57 76 101 125 12 15.5 21 28 36 50 68 89 110 15.5 20 27 37 47 65 87 114 141 14 18 25 33 43 59 79 104 129 - - - - - - - 126 156 - - - - - - - 112 141 - - - - - - - 146 181 - - - - - - - 130 162 - - - - - - - 110 137 BS 6346 50 70 95 120 150 185 240 300 400 500 630 800 1000 119 151 182 210 240 273 320 367 - - - - - 108 136 164 188 216 245 286 328 - - - - - 151 192 232 269 300 341 400 458 546 626 720 - - 134 171 207 239 262 296 346 394 467 533 611 - - 182 234 284 330 381 436 515 594 694 792 904 1030 1154 167 214 261 303 349 400 472 545 634 723 826 943 1058 191 246 300 349 404 463 549 635 732 835 953 1086 1216 172 223 273 318 369 424 504 584 679 778 892 1020 1149 219 281 341 396 456 521 615 709 852 982 1138 1265 1420 197 254 311 362 419 480 569 659 795 920 1070 1188 1337 167 216 264 304 356 409 485 561 656 749 855 971 1079 * With or without protective conductor Note: Rating factors for ambient temperature other than 300c please refer Table A Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Meter) PVC & PVC/ PVC Cables Technical Table 5.2 Conductor Cross- sectional area 2 cables dc 2 cables- single- phase ac 3 or 4 cables- three- phase ac Reference Methods 3 & 4 (Enclosed in conduit etc in or on a wall) Reference Methods 1 & 11 (Clipped direct or on trays, touching) Reference Methods 12 (space *) Reference Methods 3 & 4 (Enclosed in conduit etc in or on a wall) Reference Methods 1, 11& 12 (in trefoil) Reference Methods 1 & 11 (flat touching) Reference Methods 12 (Flat spaced*) mm2 mV mV mV mV mV mV mV mV 1 1.5 2.5 4 6 10 16 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 38 25 15 9.5 6.4 3.8 2.4 38 25 15 9.5 6.4 3.8 2.4 38 25 15 9.5 6.4 3.8 2.4 38 25 15 9.5 6.4 3.8 2.4 r x z r x z r x z r x z r x z r x z r x z 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 1.75 1.25 0.93 0.63 0.46 0.36 0.29 0.23 0.180 0.145 0.105 0.086 0.068 0.053 0.042 1.80 1.30 0.95 0.65 0.49 0.39 0.31 0.25 0.195 0.160 0.130 0.110 0.094 - - 0.33 0.31 0.30 0.29 0.28 0.27 0.27 0.27 0.26 0.26 0.26 0.26 0.25 - - 1.80 1.30 1.00 0.72 0.56 0.47 0.41 0.37 0.33 0.31 29 0.28 0.27 - - 1.75 1.25 0.93 0.63 0.47 0.37 0.30 0.24 0.185 0.150 0.120 0.098 0.081 0.068 0.059 0.20 0.195 0.190 0.185 0.180 0.175 0.175 0.170 0.165 0.165 0.160 0.155 0.155 0.150 0.150 1.75 1.25 0.95 0.66 0.50 0.41 0.34 0.29 0.25 0.22 0.20 0.185 0.175 0.165 0.160 1.75 1.25 0.93 0.63 0.47 0.37 0.29 0.24 0.185 0.150 0.115 0.093 0.076 0.061 0.050 0.29 0.28 0.28 0.27 0.27 0.26 0.26 0.26 0.25 0.25 0.25 0.24 0.24 0.24 0.24 1.80 1.30 0.97 0.69 0.54 0.45 0.39 0.35 0.31 0.29 0.27 0.26 0.25 0.25 0.24 1.50 1.10 0.81 0.56 0.42 0.33 0.27 0.22 0.17 0.14 0.12 0.10 0.08 - - 0.29 0.27 0.26 0.25 0.24 0.23 0.23 0.23 0.23 0.23 0.22 0.22 0.22 - - 1.55 1.10 0.85 0.61 0.48 0.41 0.36 0.32 0.29 0.27 0.25 0.25 0.24 - - 1.50 1.10 0.80 0.55 0.41 0.32 0.26 0.21 0.160 0.130 0.150 0.086 0.072 0.060 0.052 0.175 0.170 0.165 0.160 0.155 0.150 0.150 0.145 0.145 0.140 0.140 0.135 0.135 0.130 0.130 1.50 1.10 0.82 0.57 0.43 0.36 0.30 0.26 0.22 0.190 0.175 0.160 0.150 0.145 0.140 1.50 1.10 0.80 0.55 0.41 0.32 0.26 0.21 0.160 0.130 0.150 0.086 0.072 0.060 0.052 0.25 0.24 0.24 0.24 0.23 0.23 0.23 0.22 0.22 0.22 0.21 0.21 0.21 0.21 0.20 1.55 1.10 0.84 0.60 0.47 0.40 0.34 0.31 0.27 0.25 0.24 0.23 0.22 0.22 0.21 1.50 1.10 0.80 0.55 0.40 0.32 0.26 0.21 0.160 0.130 0.100 0.081 0.066 0.053 0.044 0.32 0.32 0.32 0.31 0.31 0.30 0.30 0.30 0.29 0.29 0.29 0.29 0.28 0.28 0.28 1.55 1.15 0.86 0.63 0.51 0.44 0.40 0.36 0.34 0.32 0.31 0.30 0.29 0.29 0.28 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  29. 29. 29 Current- Crying Capacities (Amp) PVC/ PVC Cables Technical Table 6.1 Conductor cross- sectional area Reference Methods 4 (Enclosed in an insulated wall etc) Reference Methods 3 (Enclosed in conduit on a wall or ceiling, or in trunking) Reference Method 1 (Clipped direct) Reference Method 11 (on a perforated cable tray), or Reference Method 13 ( free air) 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac mm2 Amp Amp Amp Amp Amp Amp Amp Amp 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 11 14 18.5 25 32 43 57 75 92 110 139 167 192 219 248 291 334 - 10 13 17.5 23 29 39 52 68 83 99 125 150 172 196 223 261 298 - 13 16.5 23 30 38 52 69 90 111 133 168 201 232 258 294 344 394 470 11.5 15 20 27 34 46 62 80 99 118 149 179 206 225 255 297 339 402 15 19.5 27 36 46 63 85 112 138 168 213 258 299 344 392 461 530 634 13.5 17.5 24 32 41 57 76 96 119 144 184 223 259 299 341 403 464 557 17 22 30 40 51 70 94 119 148 180 232 282 328 379 434 514 593 715 14.5 18.5 25 34 43 60 80 101 126 153 196 238 276 319 364 430 497 597 * With or without protective conductor Note: Rating factors for ambient temperature other than 300c please refer Table A Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Meter) PVC/ PVC Cables Technical Table 6.2 Conductor cross- sectional 2-core cable ac 2-core cable single-phase ac 3 or 4-core cable 3-phase ac mm2 mV mV mV 1 1.5 2.5 4 6 10 16 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 38 25 15 9.5 6.4 3.8 2.4 r x z r x z 25 35 50 70 95 120 150 185 240 300 400 1.75 1.25 0.93 0.63 0.46 0.36 0.29 0.23 0.180 0.145 0.105 1.75 1.25 0.93 0.63 0.47 0.38 0.30 0.25 0.190 0.155 0.115 0.170 0.165 0.165 0.160 0.155 0.155 0.155 0.150 0.150 0.145 0.145 1.75 1.25 0.94 0.65 0.50 0.41 0.34 0.29 0.24 0.21 0.185 1.50 1.10 0.80 0.55 0.41 0.33 0.26 0.21 0.165 0.135 0.100 0.145 0.145 0.140 0.140 0.135 0.135 0.130 0.130 0.130 0.130 0.125 1.50 1.10 0.81 0.57 0.43 0.35 0.29 0.25 0.21 0.185 0.160 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  30. 30. 30 Current- Crying Capacities (Amp) PVC/ AWA/ PVC Cables Technical Table 7.1 Conductor cross- sectional area Reference Methods 1 (Clipped direct) Reference Methods 11 (on perforated cable tray) Reference Methods 12 (free air) Direct in ground In Single Way Ducts 2 cables single- phase ac or dc 3 or 4 cables 3-phase ac 2 cables single- phase ac flat & touching 3 or 4 cables 3-phase flat & touching 3 or 4 cables 3-phase ac 2 cables dc spaced 2 cables flat touch- ing 3 cables trefoil touch- ing 2 cables duct touch- ing 3 cables trefoil touch- ing Horizontal flat spaced Vertical flat spaced 3 cables trefoils Hori- zontal Verti- cal mm2 Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp 50 70 95 120 150 185 240 300 400 500 630 800 1000 193 245 296 342 393 447 525 594 687 763 843 919 975 179 225 269 309 352 399 465 515 575 622 669 710 737 205 259 313 360 413 469 550 624 723 805 891 976 1041 189 238 285 327 373 422 492 547 618 673 228 777 808 230 286 338 385 436 490 566 616 674 721 771 824 872 212 263 313 357 405 456 528 578 632 676 723 772 816 181 231 280 324 373 425 501 567 657 731 809 886 945 229 294 357 415 479 548 648 748 885 1035 1218 1441 1685 216 279 340 396 458 525 622 719 851 997 1174 1390 1627 238 292 349 396 443 497 571 640 708 780 856 895 939 203 248 297 337 376 423 485 542 600 660 721 756 797 216 262 308 341 375 414 463 509 545 585 632 662 703 199 241 282 311 342 375 419 459 489 523 563 587 621 Note: Rating factors for ambient temperature other than 300c please refer Table A Rating factors for ambient temperature other than 150c please refer Table B Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 7.2 Conduc- tor cross- sectional area 2 cables dc 2 cables-single-phase ac 3 or 4 cables-three-phase ac Direct in ground Single Way Ducts Reference Methods 1 & 11 (Touching) Reference Methods 12 (space*) Reference Methods 1, 11 & 12 (in trefoil touching) Reference Methods 1 & 11 (Flat touching) Reference Methods 12 (flat spaced*) 2 cables flat touch- ing 3 cables trefoil touch- ing 2 cables flat touch- ing 3 cables trefoil touch-ing mm2 mV mV mV mV mV mV mV mV mV mV r x z r x z r x z r x z r x z 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.93 0.63 0.46 0.36 0.29 0.23 0.180 0.145 0.105 0.086 0.068 0.053 0.042 0.93 0.64 0.48 0.39 0.31 0.26 0.20 0.160 0.140 0.120 0.105 0.094 0.095 0.22 0.21 0.20 0.195 0.19 0.19 0.180 0.180 0.175 0.170 0.165 0.160 0.155 0.95 0.68 0.52 0.43 0.37 0.32 0.27 0.24 0.22 0.21 0.195 0.185 0.185 0.92 0.66 0.51 0.42 0.34 0.29 0.23 0.190 0.180 0.165 0.150 0.145 0.140 0.30 0.29 0.28 0.28 0.27 0.27 0.26 0.26 0.24 0.23 0.22 0.21 0.190 0.97 0.72 0.58 0.50 0.44 0.39 0.35 0.32 0.30 0.29 0.27 0.25 0.24 0.80 0.56 0.42 0.33 0.27 0.22 0.175 0.140 0.120 0.105 0.091 0.082 0.079 0.19 0.18 0.175 0.17 0.165 0.16 0.160 0.155 0.130 0.145 0.145 0.140 0.135 0.82 0.58 0.45 0.37 0.32 0.27 0.23 0.21 0.195 0.180 0.170 0.160 0.155 0.79 0.57 0.44 0.36 0.30 0.25 0.20 0.165 0.160 0.145 0.135 0.125 0.125 0.26 0.25 0.25 0.24 0.24 0.23 0.23 0.22 0.21 0.20 0.195 0.180 0.165 0.84 0.62 0.50 0.43 0.38 0.34 0.30 0.28 0.26 0.25 0.23 0.22 0.21 0.79 0.59 0.47 0.40 0.34 0.29 0.24 0.20 0.21 0.190 0.175 0.170 0.165 0.34 0.32 0.31 0.30 0.30 0.29 0.28 0.28 0.25 0.24 0.22 0.195 0.170 0.86 0.68 0.57 0.50 0.45 0.41 0.37 0.34 0.32 0.30 0.28 0.26 0.24 0.97 0.67 0.50 0.42 0.36 0.31 0.26 0.23 0.22 0.20 0.19 - - 0.82 0.58 0.44 0.36 0.31 0.27 0.23 0.20 0.19 0.18 0.16 - - 1.00 0.76 0.61 0.54 0.48 0.44 0.40 0.37 0.34 0.32 0.30 - - 0.88 0.66 0.53 0.47 0.42 0.38 0.34 0.32 0.30 0.28 0.26 - - Note: r = conductor resistance at operating temperature; z = impedance; x = reactance
  31. 31. 31 Current- Crying Capacities (Amp) PVC/ SWA/ PVC Cables Technical Table 8.1 Conductor cross- sectional area Reference Methods 1 (Clipped direct) Reference Methods 11 (on a perforated horizontal cable tray or Reference Methods 13 (free air) Direct in Ground In Single Way Ducts 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3- phase ac or dc 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3- phase ac or dc 2 cores 3 or 4 cores 2 cores 3 or 4 cores mm2 Amp Amp Amp Amp Amp Amp Amp Amp 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 21 28 38 49 67 89 118 145 175 222 269 310 356 405 476 547 621 18 25 33 42 58 77 102 125 151 192 231 267 306 348 409 469 540 22 31 41 53 72 97 128 157 190 241 291 336 386 439 516 592 683 19 26 35 45 62 83 110 135 163 207 251 290 332 378 445 510 590 32 41 55 69 92 119 158 190 225 277 332 377 422 478 551 616 693 27 35 47 59 78 101 132 159 188 233 279 317 355 401 462 517 580 26 34 45 57 76 98 129 154 183 225 271 309 346 393 455 510 574 22 29 38 48 64 83 107 126 153 190 228 260 292 331 382 428 490 Note: Rating factors for ambient temperature other than 300c please refer Table A Rating factors for ambient temperature other than 150c please refer Table B Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 8.2 Conductor cross- sectional area 2- core cable ac 2- core cable single-phase ac 3- or 4- cable 3- phase ac Direct in Ground In Single Way Ducts 2- cores 3- or 4- cores 2 - cores 3- or 4- cores mm2 mV mV mV mV mV mV mV 1.5 2.5 4 6 10 16 29 18 11 7.3 4.4 2.8 29 18 11 7.3 4.4 2.8 25 15 9.5 6.4 3.8 2.4 29 18 11 7.3 4.4 2.8 25 15 9.5 6.4 3.8 2.4 29 18 11 7.3 4.4 2.8 25 15 9.5 6.4 3.8 2.4 r x z r x z 25 35 50 70 95 120 150 185 240 300 400 1.75 1.25 0.93 0.63 0.46 0.36 0.29 0.23 0.18 0.145 0.105 1.75 1.25 0.93 0.63 0.47 0.38 0.3 0.25 0.19 0.155 0.115 0.17 0.165 0.165 0.16 0.155 0.155 0.155 0.15 0.15 0.145 0.145 1.75 1.25 0.94 0.65 0.5 0.41 0.34 0.29 0.24 0.21 0.185 1.5 1.1 0.8 0.55 0.41 0.33 0.26 0.21 0.165 0.135 0.1 0.145 0.145 0.14 0.14 0.135 0.135 0.13 0.13 0.13 0.13 0.125 1.5 1.1 0.81 0.57 0.43 0.35 0.29 0.25 0.21 0.185 0.16 1.7 1.3 0.94 0.66 0.49 0.4 0.34 0.29 0.24 0.21 0.19 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17 1.7 1.3 0.94 0.66 0.49 0.4 0.34 0.29 0.24 0.21 0.19 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  32. 32. 32 Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 9.1 Size of Conductor Reference Methods 4 (Enclosed in an insulated wall etc) Reference Methods 3 (Enclosed in conduit on a wall or ceiling, or in trunking) Reference Method 1 (Clipped direct) Reference Method 11 (on a perforated cable tray, horizontal or vertical) Reference Method 12 ( free air) 2 cables 1-phase ac or dc 3 or 4 cables 3-phase ac 2 cables 1-phase ac or dc 3 or 4 cables 3-phase ac 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching or trefoil 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching or trefoil 3 cables trefoil 3-phase ac 1 2 3 4 5 6 7 8 9 10 mm2 A A A A A A A A A 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 18 24 33 43 58 76 100 124 149 189 228 263 300 341 400 459 - - - - - 17 23 30 39 53 70 91 111 135 170 205 235 270 306 358 410 - - - - - 22 30 40 51 71 95 126 156 189 240 290 336 375 426 500 573 683 783 900 - - 19 26 35 45 63 85 111 138 168 214 259 299 328 370 433 493 584 666 764 - - 25 34 46 59 81 109 143 176 228 293 355 413 476 545 644 743 868 990 1130 1288 1443 23 31 41 54 74 99 130 161 209 268 326 379 436 500 590 681 793 904 1033 1179 1323 - - - - - - 158 195 293 308 375 436 505 579 686 794 915 1044 1191 1358 1520 - - - - - - 140 176 215 279 341 398 461 530 630 730 849 973 1115 1275 1436 - - - - - - 138 171 209 270 330 385 445 511 606 701 820 936 1069 1214 1349 Note: Rating factors for ambient temperature other than 300c please refer Table C Rating factors for ambient temperature other than 150c please refer Table D Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 9.2 Size of Conductor 2 cables dc 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac Reference Methods 3&4 (Enclosed in conduit etc, in or on a wall) Reference Methods 1 & 11 (clipped direct or on trays touching) Reference Methods 3&4 (Enclosed in conduit etc, in or on a wall) Reference Methods 1, 11 & 12 (in trefoil) Reference Methods 1 & 11 (flat & touching) 1 2 3 4 5 6 7 mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m 1.5 2.5 4 6 10 16 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 27 16 10 6.8 4.0 2.5 27 16 10 6.8 4.0 2.5 27 16 10 6.8 4.0 2.5 r x z r x Z r x z r x z r x Z 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 1.85 1.35 0.99 0.68 0.49 0.39 0.32 0.25 0.19 0.155 0.12 0.093 0.072 0.056 0.045 1.85 1.35 1.00 0.70 0.51 0.41 0.33 0.27 0.21 0.175 0.14 0.12 0.10 - - 0.31 0.29 0.29 0.28 0.28 0.27 0.26 0.26 0.26 0.26 0.25 0.25 0.25 0.25 - 1.90 1.35 1.05 0.75 0.58 0.48 0.43 0.37 0.33 0.31 0.29 0.28 0.27 - - 1.85 1.35 0.99 0.68 0.49 0.39 0.32 0.26 0.20 0.16 0.13 0.105 0.086 0.072 0.063 0.19 0.18 0.18 0.175 0.170 0.165 0.165 0.165 0.160 0.160 0.155 0.155 0.155 0.150 0.150 1.85 1.35 1.00 0.71 0.52 0.43 0.36 0.30 0.25 0.22 0.20 0.185 0.175 0.170 0.165 1.60 1.15 0.87 0.60 0.44 0.35 0.29 0.23 0.185 0.15 0.125 0.100 0.088 - - 0.27 0.25 0.25 0.24 0.23 0.23 0.23 0.23 0.22 0.22 0.22 0.22 0.21 - - 1.65 1.15 0.90 0.65 0.50 0.42 0.37 0.32 0.29 0.27 0.25 0.24 0.23 - - 1.60 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.17 0.14 0.11 0.09 0.074 0.062 0.055 0.165 0.155 0.155 0.150 0.145 0.140 0.140 0.140 0.140 0.140 0.135 0.135 0.135 0.130 0.130 1.60 1.15 0.87 0.61 0.45 0.37 0.31 0.26 0.22 0.195 0.175 0.160 0.150 0.145 0.140 1.60 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.17 0.135 0.110 0.088 0.071 0.059 0.050 0.19 0.18 0.18 0.175 0.170 0.165 0.165 0.165 0.165 0.160 0.160 0.160 0.160 0.155 0.150 1.60 1.15 0.87 0.62 0.46 0.38 0.32 0.28 0.24 0.21 0.195 0.180 0.170 0.165 0.165 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  33. 33. 33 Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 10.1 Size of Conductor Reference Methods 4 (Enclosed in conduit and in insulated wall etc) Reference Methods 3 (Enclosed in conduit on a wall or ceiling, or in trunking) Reference Method 1 (Clipped direct) Reference Method 11 (on a perforated cable tray, or Reference Method 13 (free air) 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2 3 4 5 6 7 8 9 mm2 A A A A A A A A 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 18.5 25 33 42 57 76 99 121 145 183 220 253 290 329 386 442 - 16.5 22 30 38 51 68 89 109 130 164 197 227 259 295 346 396 - 22 30 40 51 69 91 119 146 175 221 265 305 334 384 459 532 625 19.5 26 35 44 60 50 105 128 154 194 233 268 300 340 398 455 536 24 33 45 58 80 107 138 171 209 269 328 382 441 506 599 693 803 22 30 40 52 71 96 119 147 179 229 278 322 371 424 500 576 667 26 36 49 63 86 115 149 185 225 289 352 410 473 542 641 741 865 23 32 42 54 75 100 127 158 192 246 298 346 399 456 538 621 741 Note: Rating factors for ambient temperature other than 300c please refer Table C Rating factors for ambient temperature other than 150c please refer Table D Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 10.2 Size of Conductor 2-core cable dc 2-core cable single-phase ac 3- or 4- Cable 3-phase ac 1 2 3 4 mm2 mV/A/m mV/A/m mV/A/m 1.5 2.5 4 6 10 16 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 27 16 10 6.8 4.0 2.5 r x z r x Z 25 35 50 70 95 120 150 185 240 300 400 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.120 1.85 1.35 0.99 0.67 0.50 0.40 0.32 0.26 0.20 0.16 0.13 0.16 0.155 0.155 0.150 0.150 0.145 0.145 0.145 0.140 0.140 0.140 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.6 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.175 0.140 0.115 0.14 0.135 0.135 0.130 0.130 0.130 0.125 0.125 0.125 0.120 0.120 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  34. 34. 34 Current- Crying Capacities (Amp) XLPE/ AWA/ PVC Cables Technical Table 11.1 Size of Conductor Reference Methods 1 (clipped direct) Reference Method 11 (on a perforated cable tray) Reference Method 12 ( free air) In single-way ducts Laid direct in ground 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching 3 cables 3-phase ac trefoil touching 2 cables 1-phase ac or dc ducts touching 3 cables 3-phase ac trefoil ducts touching 2 cables 1-phase ac or dc touching 3 cables 3-phase ac trefoil touching 1 2 3 4 5 6 7 8 9 10 mm2 A A A A A A A A A 50 70 95 120 150 185 240 300 400 500 630 800 1000 237 303 367 425 488 557 656 755 853 962 1082 1170 1261 220 277 333 383 437 496 579 662 717 791 861 904 961 253 322 382 449 516 587 689 792 899 1016 1146 1246 1345 232 293 352 405 462 524 612 700 767 851 935 987 1055 222 285 346 402 463 529 625 720 815 918 1027 1119 1214 255 310 365 410 445 485 550 610 640 690 750 828 919 235 280 330 370 405 440 500 550 580 620 670 735 811 257 340 405 460 510 580 670 750 830 910 1000 1117 1254 235 290 345 390 435 490 560 630 700 770 840 931 1038 Note: Rating factors for ambient temperature other than 300c please refer Table C Rating factors for ambient temperature other than 150c please refer Table D Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Per Meter) XLPE/AWA/PVC Cables Technical Table 11.2 Size of Conductor 2 cables dc 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac, touching Reference Methods 1 & 11 (touching) Reference Methods 1, 11 & 12 (in trefoil touching) Reference Methods 1 & 11 (flat & touching) In ducts In ground In ducts In ground 1 2 3 4 5 6 7 8 9 mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m r x z r x z r x z 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.115 0.093 0.073 0.056 0.045 0.99 0.68 0.51 0.41 0.33 0.27 0.21 0.17 0.145 0.125 0.105 0.09 0.092 0.21 0.20 0.195 0.190 0.185 0.185 0.180 0.175 0.170 0.170 0.165 0.160 0.155 1 0.71 0.55 0.45 0.38 0.33 0.28 0.25 0.22 0.21 0.195 0.190 0.180 0.86 0.59 0.44 0.35 0.29 0.23 0.18 0.145 0.125 0.105 0.092 0.086 0.080 0.18 0.17 0.17 0.165 0.160 0.160 0.155 0.150 0.150 0.145 0.145 0.140 0.135 0.87 0.62 0.47 0.39 0.33 0.28 0.24 0.21 0.195 0.180 0.170 0.165 0.155 0.84 0.6 0.46 0.38 0.31 0.26 0.21 0.17 0.160 0.145 0.135 0.130 0.125 0.25 0.25 0.24 0.24 0.23 0.23 0.22 0.22 0.21 0.20 0.195 0.180 0.170 0.88 0.65 0.52 0.44 0.39 0.34 0.30 0.28 0.27 0.25 0.24 0.23 0.21 1.10 0.80 0.65 0.55 0.50 0.45 0.40 0.37 0.35 0.33 0.30 0.28 0.26 0.99 0.70 0.53 0.43 0.37 0.31 0.26 0.24 0.21 0.20 0.19 0.18 0.17 0.93 0.70 0.56 0.48 0.43 0.39 0.35 0.32 0.30 0.28 0.26 0.24 0.22 0.86 0.61 0.46 0.37 0.32 0.27 0.23 0.21 0.19 0.18 0.17 0.16 0.15 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  35. 35. 35 Current- Crying Capacities (Amp) XLPE/ SWA/ PVC Cables Technical Table 12.1 Size of Conductor Reference Methods 1 (clipped direct) Reference Method 11 (on a perforated cable tray, or Reference Method 13 (free air) In single-way ducts Laid direct in ground 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2 3 4 5 6 7 8 9 mm2 A A A A A A A A 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 27 36 49 62 85 110 146 180 219 279 338 392 451 515 607 698 787 23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599 673 29 39 52 66 90 115 152 188 228 291 354 410 472 539 636 732 847 25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628 728 - - - - - 115 145 175 210 260 310 355 400 455 520 590 660 23 30 40 50 65 94 125 150 175 215 260 300 335 380 440 495 560 - - - - - 140 180 215 255 315 380 430 480 540 630 700 790 28 36 48 60 80 115 150 180 215 265 315 360 405 460 530 590 670 Note: Rating factors for ambient temperature other than 300c please refer Table C Rating factors for ambient temperature other than 150c please refer Table D Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Per Meter) XLPE/SWA/PVC Cables Technical Table 12.2 Size of Conductor 2 cables dc 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac In ducts In ground In ducts In ground 1 2 3 4 5 6 7 8 mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m 1.5 2.5 4 6 10 16 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 27 16 10 6.8 4.0 2.5 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 25 15 9.5 6.4 3.8 2.4 25 15 9.5 6.4 3.8 2.4 r x z r x z 25 35 50 70 95 120 150 185 240 300 400 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.120 1.85 1.35 0.99 0.67 0.50 0.40 0.32 0.26 0.20 0.16 0.13 0.16 0.155 0.155 0.150 0.150 0.145 0.145 0.145 0.140 0.140 0.140 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.6 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.175 0.140 0.115 0.14 0.135 0.135 0.130 0.130 0.130 0.125 0.125 0.125 0.120 0.120 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.6 1.2 0.87 0.61 0.45 0.36 0.30 0.25 0.21 0.19 0.18 1.6 1.2 0.87 0.61 0.45 0.36 0.30 0.25 0.21 0.19 0.18 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  36. 36. 36 Technical Data Flexible Cord, Imperial Sizes Technical Table 13.1 Conductor Current Rating Volt Drop PER 100FT Maximum Weigh supportable by twin flexible cord Nominal Area Construction 1 or 3 phase ac or dc dc or 1 phase ac 3 phase ac in2 No./in Amp V V lb 0.0006 0.0010 0.0017 0.0030 0.0048 0.0070 14/ 0.0076 23/ 0.0076 40/ 0.0076 70/ 0.0076 110/ 0.0076 162/ 0.0076 3 6 13 18 24 31 8.9 11 14 12 9.6 8.4 7.7 9.4 12 10 8.3 7.3 3 5 10 10 10 10 Note: Rating factors for ambient temperature other than 300c please refer Table E Technical Data Flexible Cord Metric Sizes Technical Table 13.2 Conductor Current Rating Volt Drop per 100FT Maximum Weigh supportable by twin flexible cord Nominal Area Construction 1 or 3 phase ac or dc dc or 1 phase ac 3 phase ac mm2 No./mm Amp mV/m mV/m kg 0.50 0.75 1.00 1.25 1.50 2.50 4.00 16/ 0.2 24/ 0.2 32/ 0.2 40/ 0.2 30/ 0.25 50/ 0.25 56/ 0.3 3 6 10 13 15 20 25 83 56 43 35 31 18 11 72 48 37 29 26 16 9.6 2 3 5 5 5 5 5 Note: Rating factors for ambient temperature other than 300c please refer Table E
  37. 37. 37 Allowable Short Circuit Currents For PVC Insulated Cables Technical Table 14.1 Short circuit current (KA) 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000 Conductor: Copper Insulation: PVC Curves based on formula: l = (0.115A÷ t ) Where: l – Short circuit current (KA) A- Conductor area (mm2) t – Time of short circuit (seconds) Conductor Size (mm2) Allowable Short Circuit Currents For XLPE Insulated Cables Technical Table 14.2 Short circuit current (KA) 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000 Conductor: Copper Insulation: PVC Curves based on formula: l = (0.115A÷ t ) Where: l – Short circuit current (KA) A- Conductor area (mm2) t – Time of short circuit (seconds) Conductor Size (mm2)
  38. 38. 38 Short Circuit ratings for power cables Technical Table 14.3 Cross- Sectional Area Short Circuit Rating for 1 second Short Circuit Rating for 3 seconds Another important factor for the determination of the conductor size is the maximum allowable current during a short circuit when the maximum allowable current during a short circuit when the maximum allowable conductor temperature is higher than during normal operation. The maximum permissible short circuit current of XLPE cables up to 1Kv with copper conductors can be calculated with the formula: K t S lk   Where l = Short Circuit rating (KA) S = Conductor Area (sq mm) t = Duration of Short Circuit (sec) mm2 KA KA 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.2145 0.3575 0.5720 0.8580 1.4300 2.2880 3.5750 5.0050 7.1500 10.0100 13.5850 17.1600 21.4500 26.4550 34.3200 42.9000 57.2000 71.5000 90.0900 114.4000 143.0000 0.1238 0.2064 0.3302 0.4954 0.8256 1.3210 2.0640 2.8896 4.1281 5.7793 7.8433 9.9073 12.3842 15.2738 19.8147 24.7683 33.0244 41.2805 52.0135 66.0489 82.5611 The above rating is calculated using the following formula: t S l 0.143  Where l = Short Circuit rating (KA) S = Conductor Area (sq mm) t = Duration of Short Circuit (sec) Copper Conductor Technical Table 14.3 Current in Kiloampers Duration of Short circuit in Seconds The values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 900c), and a final conductor temperature of 2500c, and it should be ensured that the accessories associated with the cable are also capable of operation at these values of fault current.
  39. 39. 39 IN-POP, IN-POSP IN-PIOP, IN-PIOSP & IN-EOP, IN-EOSP IN-EIOP, IN-EIOSP Technical Table 15 1 . Test Voltage: 1000 Vr.m.s. for 1 minute between each conductor in turn and all other connected together 2 . Maximum DC Conductor Resistance at 200c Conductor Size Multi-cores Multi-pairs 0.5 mm2 0.75 mm2 1.0 mm2 1.5 mm2 39.0 26.0 18.1 12.1 39.7 26.5 18.4 12.3 3. Minimum Insulation Resistance at 200c PE Insulated PVC Insulated Individual Conductor (between) each conductor and Remaining bunched conductors/ screen and/ or armour 5000MΩ.km 25 MΩ.km Individual Screens (between screens) 1 MΩ.km 1 MΩ.km 4. Maximum Mutual Capacitance at 1 KHz (pF/m) Cable Type Conductor Size 0.5 mm2 1.0 mm2 1.5 mm2 PE Insulated Cables without individual pair screen 75 pF/m 75 pF/m 85 pF/m PE Insulated All cables with individual pair screen, 1 and 2 pair cables collective screen 115 pF/m 115 pF/m 120 pF/m PVC Insulated Pairs 250pF/m 5. Maximum Capacitance Between Any Core or Screen PVC Insulated cables: 450 pF/m 6. Maximum Capacitance Unbalance at 1 KHz PE Insulated cables: 250pF/ 250m 7. Maximum L/R Ratio (For Adjacent Cores) Conductor Size Multi-cores 0.5 mm2 0.75 mm2 1.0 mm2 1.5 mm2 25 μH/Ω 25 μH/Ω 25 μH/Ω 40 μH/Ω Maximum Conductor Resistance Technical Table 16 Electrical Characteristics Technical Table 16 Cross Section Area (S) Conductor for Fixied Wiring Class 1 (solid), Class 2 (stranded) Conductor Resistance Temperature Correction Factors mm2 Temp0C Factor 0.50 0.75 1.00 1.50 2.50 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 36.0 24.5 18.1 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 30 35 40 45 50 55 60 65 70 75 80 85 90 0.961 0.965 0.969 0.972 0.976 0.980 0.984 0.988 0.992 0.996 1.000 1.004 1.008 1.012 1.016 1.020 1.039 1.059 1.079 1.098 1.118 1.138 1.157 1.177 1.196 1.216 1.236 1.255 1.275
  40. 40. 40 (mm2 – CM – AWG/ MCM) Technical Table 18 Cross- sectional Area Conductor Size Cross- sectional Area Conductor Size (mm2) (CM) (AWG/ MCM) (mm2) (CM) (AWG/ MCM) 0.324 0.519 0.653 0.823 *1.0 1.04 1.31 *1.5 1.65 2.08 *2.5 2.63 3.31 *4.0 4.17 5.261 *6.0 6.631 8.367 *10.0 10.55 13.3 *16.3 16.77 21.15 *25.0 26.67 33.62 *35.0 42.41 *50.0 53.49 67.43 *70.0 85.01 *95.0 640 1020 1290 1620 1974 2050 2580 2960 3260 4110 4934 5180 6530 7894 8230 10380 11841 13090 16510 19735 20820 26240 31576 33090 41740 49338 52620 66360 69073 83690 98675 105600 133100 138145 167800 187483 22 20 19 18 - 17 16 - 15 14 - 13 12 - 11 10 - 9 8 - 7 6 - 5 4 - 3 2 - 1 - 1/0 2/0 - 3/0 - 107.2 *120 127 *150 152 177 *185 203 228 *240 253 279 300 304 329 355 380 *400 405 456 *500 507 557 608 *630 633 659 709 760 *800 811 861 887 912 963 *1000 010 211600 236820 250000 296025 300000 350000 365098 400000 450000 473640 5000000 550000 592050 600000 650000 700000 750000 789400 800000 900000 986750 1000000 1000100 1000200 1243305 1250000 1300000 1400000 1500000 1578800 1600000 1700000 1750000 1800000 1900000 1973500 2000000 4/0 - -250 - 300 350 - 400 450 - 500 550 - 600 650 700 750 - 850 900 - 1000 1100 1200 - 1250 1300 1400 1500 - 1600 1700 1750 1800 1900 - 2000 Note: * British standard *127 mm2 and larger is rounded off and not actual. CM area is actual Conversion factors: mm2 x 1973.5 = CM x 0.0005067 = mm2. AWG - America Wire Gauge. A standard measurement of the size of a conductor: 4/0 & smaller. CM (Circular Mil) used to define cross-sectional areas of conductors. Area of circle 171000 inches in diameter. MCM – 1000 circular mils.

×