Dry Type Transformers
Transformers meant to be installed in a dry and air conditioned room or in a
PTI AUGIER type substation.
ELECTRICAL CHARACTERISTICS :
Power rating and type :
Single-phase : TMAI : 5 - 7.5 - 10 - 16 - 25 - 32 - 50 kVA
Three-single : TTMAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA
Three-two : TTBAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 kVA
Three-phase : TTAI : 16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200
250 - 400 - 500 - 630 kVA
Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV
Primary voltage : Every voltage compatible with insulation voltages above.
Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and
6600 V.
Secondary load voltage : 230 V - 400 V - 950 V - 3200 V - 5500 V and 6600 V.
Couplings :
Standard : Three-phase transformer : Step-down Dyn11 - Step-up YNd1– single-phase transformer :Ii0
Specific : Three-single transformer, Leblanc three-two transformer, other couplings on request.
Manufacturing specifications on request :
Inrush current transformer reduced or very reduced.
CONNEXION:
Primary and secondary connesion on copper slots, by the upper side of the transformer.
STANDARD ACCESSORIES :
Empty setting plugs : Three outputs on slots.
Two earthing switches.
Lifting lugs.
Four rollers for 10 kVA and higher power rating transformers.
NOTE :
Transformers mechanical and electrical characteristics are the same
for step-down or step-up transformers. The tranformers are not
reversible.
Step-up transfrormers are built so that inrush currents are
limited.
Single-phase transformer, TMAI type, with IP21 encolsure, fuse terminal 3200 V
and locking.
3. 3
CONSTRUCTION :
Magnetical circuits with crystal made sheet metal, oriented, with low losses.
Copper windings, vacuum impregnated of H class and applying of a fungicide varnish.
Metallic flanges.
Ironed chassis with rollers.
Wooden terminals plate bakelised.
Cooling : in natural air : NA.
Use : use in dry, air conditioned rooms, at a room temperature of -15 °C ; + 40°C.
Color : RAL 7035 gray.
STANDARDS AND TESTS : Conforms to NF C 17-200 - NF C 52-100 - IEC 60076 standards.
Other specifications on request. Routine tests U.T.E made on each transformer, specific tests on request..
Dry type transformer, naked presentation on frame
Connexion plates
Tap changer
MV side view
Dry type transformer
With IP21 enclosure
Lifting lugs
Connexion plates
LV side dismantle panel
Fixation by screw
rollers
Signaletic plate
Firm plate
LV side dismantling panel
Side panel dismantling
(cables passage)
Fixation by screw
Bakélite matter
To be screwed on request
4. 4
ELECTRICAL CHARACTERISTICS
Power rating (kVA) 25 50 100 160 200 250 400 63016 32 63 80 125 500
Copper losses
at 75°C (W)
470 800 1350 2000 2300 2800 4200 7300350 550 1000 1100 1400 5600
Iron losses (W) 180 250 450 500 550 650 900 1500100 200 250 380 450 1250
Voltage drop
(% )
at Cos = 0.83
3 3.14 3.2 3.4 3.2 3.15 3.5 3.53.3 3.07 3.4 3 3 3.5
CC tension
(%) at 75°C
3.2 3.5 4 4 4 4 4 53.4 3.4 4 3.5 4 4.5
Empty current
(%)
0.7 0.9 0.9 0.7 0.5 0.5 0.8 0.71 0.8 0.7 0.8 0.6 0.6
Three-phase dry Type Transformers
TTAI
ELECTRICAL CHARACTERISTICS :
Power rating:
16 - 25 - 32 - 50 - 63 - 80 - 100 - 125 - 160 - 200 - 250 - 400 - 500 - 630 kVA
Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV
Primary voltage : Every voltage compatible with insulation voltages above.
Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V - 5500 V and
6600 V.
Secondary load voltage : 400 V - 950 V - 3200 V - 5500 V and 6600 V.
Couplings :
Step-down Dyn11 - Step-up YNd1, other couplings on request.
CONNEXION :
Primary and secondary connexions on copper plates, by the upper side of the transformer.
STANDARD ACCESSORIES :
Voltage tapping adjustable out of voltage : +/- 2,5 % or +- 5% output on slots.
Two earthing terminals.
Lifting lugs.
Four rollers for 10 kVA and higher power rating transformers.
Naked presentation on frame : IP00.
OPTIONAL ACCESSORIES
Painted sheet metal enclosure with natural airing upwards, IP21.
Connexion on pluggable terminals 3200 V or 5500 V.
HRC fuses protection integrated above the protection envelop.
Thermal protection by thermal probe integrated to windings, one or two thresholds protection.
Tap changers +/- 2,5 % +/- 5%.
Keyhole locking of the protection envelop and or pluggable terminals.
NOTE :
Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The
tranformers are not reversible.
Step-up transfrormers are built so that inrush currents are limited.
6. 6
Single-phase Dry Type Transformers
TMAI
ELECTRICAL CHARACTERISTICS :
Power rating: 5 - 7,5 - 10 - 16 - 25 - 32 - 50 kVA
Insulation voltage : 1.1 kV - 3.6 kV - 7.2 kV
Primary voltage : Every voltage compatible with insulation voltages above.
Usually standard voltages are : 230 V - 400 V - 950 V - 3200 V.
Secondary load voltage : 230 V - 950 V - 3200 V.
Couplings :
Standard : single-phase transformer : Ii0
CONNEXION :
Primary and secondary connexions on copper plates, by the upper side of the transformer.
STANDARD ACCESSORIES :
Voltage tapping adjustable out of voltage : +/- 2,5 % ou +- 5% sorties sur plages.
Two earthing terminals.
Lifting lugs.
Four rollers for 10 kVA and higher power rating transformers.
Naked presentation on IP00 frame.
OPTIONAL ACCESSORIES
Painted sheet metal enclosure with natural airing upwards, IP21.
Connexion on pluggable terminals.
HRC fuses protection integrated above the protection envelop.
Thermal protection by thermal probe integrated to windings, one or two thresholds protection.
Tap changers +/- 2,5 % +/- 5%.
Keyhole locking of the protection envelop and or pluggable terminals.
NOTE :
Transformers mechanical and electrical characteristics are the same for step-down or step-up transformers. The
tranformers are not reversible.
Step-up transfrormers are built so that inrush currents are limited.
ELECTRICAL CHARACTERISTICS
Power rating (kVA) 5 7,5 10 16 25 32 50
Copper losses
at 75°C (W)
100 120 170 380 500 630 750
Iron losses
(W)
40 60 60 80 120 150 200
Voltage drop (% )
at Cos = 0.83
2.92 2.47 3.35 3.7 3.53 3.55 3.7
Cc tension
(%) at 75°C
2.95 2.67 3.75 3.86 3.78 4 4
Empty current
(%)
3.11 2.53 2.58 2.67 2.52 2.54 2.51