This presentation discusses circuit breaker testing using the TRAX unit and substation software. It begins with introductions and an agenda that includes fundamentals of circuit breakers, testing requirements, and a live demonstration of timing tests, coil current measurement, and contact resistance testing on a breaker simulator. The presentation provides background on circuit breaker types and basic testing procedures before demonstrating the live tests on the simulator using a single connection from the TRAX unit.
3. Send us your questions and comments during the presentation
Q&A
4. • 11am ( + 3 GMT ) ( 1 hour duration )
• 2nd July : WRM , TTR & Demag
• 6th July : SCI , FRSL & Magnatic Balance
• 13th July : Insulation Tan Delta test
• 20th July : CT Tests ( Knee point , WRM &
Ratio V & I, burden )
• Today :CB testing ( Timing , Coil current &
CRM )
Monday Weekly Webinars Live Demonstrations of Trax Tests
5. Scan QR code using Mobile Camera
Part 1
WRM
Demag
TTR
Part 2
SCI
FRSL
Magnetic Balance
6. Scan QR code using Mobile Camera
Part 3
Tan Delta
DFR
Tip Up
Part 4
Timing for CB
Coil current of CB
Contact resistance
7. Cirecuit Breakers Fundamental
Testing requirments
Live testing using TRAX220 + Substation Software
Agenda
8. Low Voltage CBs
• Below 1000V
• Will trip on own when there is too much
current
• Timing test is performed via current
injection at actual current levels
Medium/High Voltage CBs
• Greater than 1000V
• Cannot trip on own, needs external signal
to trip
• Timing test performed via time and travel
analyzer at low currents
Cirecuit Breakers Fundamental
9. 4
Typical Circuit Breaker-Single break per phase
The contact is operated by
mechanically separating the
contacts. Common insulation media
are oil, air, vacuum and SF6.
Open and close operations are
obtained by releasing energy stored
in a spring. The spring is controlled
by a coil and charged by a electrical
motor.
Connector
CB chamber where
the contact is
Operating mechanism
and control unit, auxiliary
contacts, spring.
Isolation to
earth
Connector
10. 5
Typical Circuit Breaker-Multiple breaks per phase
Grading capacitors in parallel
to divide voltage equally.
Synchronization is important.
Connector Connector
One contact can not break
400 kV under load.
CB chamber
where the
contact is
Isolation to
earth
Operating mechanism
and control unit, auxiliary
contacts, spring.
11. Gas Insulated switchgear (GIS)
Everything is inside Gas Champers
(Usually SF6 GAS)
Compact , usually Fitted indoors
Slightly Difficult for Maintenance
operations
When Energized Substation only access
through Earth links
Operating mechanism
and control unit
CB Chambers
Earth Links
12. Medium Voltage (MV) Circuit Breakers
Usually from 400 V to 40 kV
Application
Compact , usually Fitted in
Cabinets
Ability to Rack Out of Cabinets for
Maintenance
CB Chambers
Operating mechanism
and control unit
13. 10
Circuit Breaker Testing
Basic
Contact resistance
Contact timing
Travel (stroke, speed,
damping, penetration)
Operating coil current
Minimum trip voltage
Advanced (diagnostic)
Dynamic Resistance Measurement
First Trip Test (On-Line)
Special
Pressure (air blast breakers)
Vacuum check (vacuum breakers)
SF6 related Tests (Purity ,
Pressure , Etc)
Insulation Tests
14. 11
Contact Resistance
Verify low contact resistance (micro ohm).
High current for accuracy.
Test current (DC):
• Minimum 100 A (IEEE)
• IEC standard requires a current of at least 50 ADC
• +10% of rated current (recommended)
15. 12
Contact Resistance 4-wire method
>100 A
28 µΩ
Generate high current with 2
leads and measure voltage drop
with 2 separate leads.
Ability to Do Dual Ground
16. 13
Contact Timing
Close/open time also CO, O-C , O-CO
• Values are usually available in the CB manual
Breaker synchronization (phase vs. phase)
• < 1/4 cycle @ close operation (IEC62271-100)
• < 1/6 cycle @ open operation (IEC62271-100)
Phase synchronization (interrupters inside phase)
• < 1/8 cycle (IEC62271-100)
Correct timing between main & resistor
contact(PIR Contacts)
Aux contacts lead/lag time
18. 17
Trip/CloseCoil Measurement
Recording the coil currents during breaker operation
Armature time(coil Time)
Max current
Duration
Coil Resistance
Voltage During Operation
19. 18
Coil Current Trace
Mechanism
Release
Open Coil
motion Main Contacts motion
Mechanism Motion
|--------Coil Motion----------
|
Locked
Open
comma
nd
----------Auxiliary contact opened----------
|
-------------Mechanism Motion-------------
|
Detect
Coil time vs Mechanism Time
Bad Coil or Bad Mechanism
No additional clamp needed
Control module direct measures
Current
recordin
g
20. 19
Minimum Operating Voltage
Verify that the breaker operates at the minimum
voltage (IEC 60694)
• CLOSE: 85% of rated operating voltage (AC/DC)
• OPEN: 70% of rated operating voltage (DC)
• OPEN: 85% of rated operating voltage (AC)
21. 11am ( + 3 GMT ) ( 1 hour duration )
2nd July : WRM , TTR & Demag
6th July : SCI , FRSL & Magnatic
Balance
13th July : Insulation Tan Delta test
20th July : CT Tests ( Knee point , WRM
& Ratio V & I, burden )
Today :CB testing ( Timing , Coil current
& CRM )
Monday Weekly Webinars Live Demonstrations of Trax Tests
22. Scan QR code using Mobile Camera
Part 1
WRM
Demag
TTR
Part 2
SCI
FRSL
Magnetic Balance
23. Scan QR code using Mobile Camera
Part 3
Tan Delta
DFR
Tip Up
Part 4
Timing for CB
Coil current of CB
Contact resistance
25. Live Demo
We Need TRAX unit + Substation testing Software activated
Test Object
1- BRS – Breaker Simulator
- 1x break per phase
- Common mechanism
Test Conducted
1-Timing
2- Coil current
3- Contact Resistance
26. • One Connection for :
- Timing measurement
- Coil current Measurement
Connection of TRAX to CB