SlideShare a Scribd company logo
IMPROVEMENT OF POWER SYSTEM
PROTECTION BY WIDE AREA
MONITORING NETWORK
Presented By UNDERTHE GUIDANCEOF
KOLLI MANOGNA G. UJWALA
INTRODUCTION TO POWER SYSTEMS
PROTECTIUON
 Power system protection is defined as the
method of protecting the power systems from
the faults and clearing the abnormalities in
power systems to restore the operation.
 This uses some special hardware which is used
for the both primary and backup protection
 The main philosophy about protection is that no
protection of power system can prevent the flow
of fault current through the system, it only can
prevent the continuation of flowing of fault
current by quickly disconnect the short circuit
path from the system.
WIDE AREA MONITORING SYSTEMS
 TheWide Area Monitoring System (WAMS) consists of geographically
dispersed Phasor Measurement Units (PMUs) delivering
Synchrophasors, i.e., time-tagged data samples of a power system’s
sinusoidal voltage or current using a standard time signal as the
reference, to Phasor Data Concentrators (PDCs).
 These PDCs perform the desired signal handling and assembly of
synchronized Phasor measurements into snapshots.They may also
facilitate long term storage in high-resolution historical archives.The
data in each PMU are time Synchronized to Universal CoordinatedTime
(UTC), for example via Global -2- Positioning System (GPS) receivers
with an accuracy of one microsecond and stored in PDCs.The Phasors
measured simultaneously provide snapshots of the state of the
monitored nodes.
 By comparing these snapshots, not only during steady state, also the
dynamic state of critical nodes in transmission, sub-transmission and
distribution networks can be observed.
Failures in power systems
 CASCADE FAILURES
 INAPPROPRIATE OPERATION OF RELAYS
 HIDDEN FAILURES
NEED FOR WAMS IN BACKUP
PROTECTION
 The need for wide area measurements as part of
primary protection is limited, as it protects a
specific element of the power system.
 However, aspects of power system protection
that have lower requirements in terms of the
speed of response (e.g. backup protection) and
are less selective can be improved by using wide
area measurements to supervise their behavior.
 These mal operations can be attributed to either
poor relay settings or hidden failures in the
protection system.
 Novel system integrity protection schemes (SIPS)
that can deploy a wide range of far reaching actions
to prevent a cascading failure, adaptive system
protection (e.g. adaptive under frequency load
shedding), supervisory schemes that improve the
security of existing backup protection, and methods
that do not change the behavior of system
protection but do enhance our understanding of it
(e.g. alarming system operators to the risk of false
penetration of relay characteristics).
 Recent work has begun to focus not only on
developing new concepts but also on the practical
realization of these.
OBJECTIVES OF WIDE AREA
PROTECTION SCHEMES
 Avoiding inappropriate relay settings for the
prevailing system conditions.
 Managing wide area disturbances.
 Mitigating the impact of hidden failures.
 Ensuring a suitable balance between the
security and dependability of protection.
WIDE AREA PROTECTION SCHEMES
(WAPS)
 ENHANCING PROTECTIONWITHWIDEAREA
MONITORING
 ALARMINGAGAINSTTHE RISK OF RELAY
CHARACTERISTIC PENETRATION
 PREVENTING LOAD ENCROACHMENT
 ADJUSTINGTHE BALANCE BETWEENTHE SECURITYAND
DEPENDABILITYOF PROTECTION
 SUPERVISIONOF BACK-UP ZONES
 INTELLIGENT UNDER FREQUENCY LOAD SHEDDING
 ADAPTIVEOUT-OF-STEP RELAYING
 SYSTEM INTEGRITY PROTECTION SCHEMES (SIPS)
 MICROGRID PROTECTION
ENHANCING PROTECTION WITH WIDE
AREA MONITORING
 The goal of protection is to protect individual elements of
the power system from damage and to protect the security
of the power system itself. In the case of primary
equipment protection there is very little role for the use of
wide area monitoring.This is because primary protection
must reliably deliver a very fast response for any fault on
the element that it protects.
 However, the slower speed of response required for backup
protection and the fact that it protects a zone of the system
means that wide area monitoring can be a useful tool for
improving its performance.The most effective means for
ensuring that the system will survive extreme conditions
and wide area disturbances is a high degree of built in
redundancy and strength
Wide area measurements offer the potential to create supervisory
schemes for backup protection, more advanced forms of system
protection and entirely new protection concepts. Some of them are:
1. Adaptive relays that update their settings as the system state
changes.
2. Improved protection of multi terminal lines.
3. Adaptive end of line protection that monitors the remote
breaker, if it is open the under reaching Zone 1 is replaced with
an instantaneous characteristic.
4. Temporarily adapt relay settings to prevent mal operation
during cold load pickup.
5. Use the ability of digital relays to self-monitor to identify
hidden failures and use the hot swap functionality offered by
International Electro technical Commission to remove them.
6. Intelligent controlled islanding that preempts an uncontrolled
system separation by implementing an adaptive controlled
separation
ALARMING AGAINST THE RISK OF RELAY
CHARACTERISTIC PENETRATION
 The objective of this application is to detect
when the impedance observed by a relay
approaches the relay characteristic under
non-faulty conditions.This information is
then used to alarm protection engineers to a
relay setting that is potentially unsuitable.
PREVENTING LOAD ENCROACHMENT
 Heavily loaded lines may encroach on the
settings of relays and cause an incorrect and
inappropriate tripping operation during
stressed conditions and power swings.
 With the computational power of digital
relays this can be overcome by using real
time measurements of the load to prevent
load encroachment by compensating the
relay input of load current.
ADJUSTING THE BALANCE BETWEEN THE
SECURITY AND DEPENDABILITY OF PROTECTION
 Balancing the demands of dependability and security is one
of the greatest challenges during the design of protection.
 During a wide area disturbance, this preference for
dependability can result in incorrect and inappropriate
tripping operations.
 It would attractive to shift the balance of this compromise
toward security during stressed conditions, i.e. when the
conditions encountered (e.g. power swings) can increase
the likelihood of mal operations and reveal hidden failures.
 Wide area measurements could be used to detect that the
system has entered a stressed condition and then adjust
the protection philosophy to shift the balance away from
dependability and toward security.
USE OF WAM TO VARY THE BALANCEBETWEEN
DEPANDABILITY AND SECURITY
SUPERVISION OF BACK-UP ZONES
SUPERVISION OF BACK-UP ZONES
 The mal operation of zone 3 relays was identified as a significant
contributing factor to recent blackouts.The unusual load currents and
power swings observed during wide area disturbances can cause these
relays to operate undesirably. Examples of the system behavior that can
cause mal operation of a relay are shown in Fig. 3.
 The remote PMUs are installed within the protection zone of the backup
relay and monitor the current at these remote locations.
 These devices implement a simple pickup characteristic and
communicate a binary pick up signal to the backup relay.
 If the backup relay characteristic is violated but none of the remote
devices have picked up, then it can be concluded that no fault has
occurred and the backup relay operation can be blocked.
 This prevents load swings during extreme conditions from being
misinterpreted as faults and helps prevent the mal operation of backup
relays from allowing a wide area disturbance to spread through the
system.
INTELLIGENT UNDER FREQUENCY LOAD
SHEDDING
 Load shedding is the traditional last line of defense
against extreme under frequency conditions.
 Current practice is mostly for this shedding to be
delivered using a sequence of stages of shedding
that are triggered when a certain frequency
threshold is violated.
 Shedding load more quickly after a loss of in feed is
recognized as an effective means for limiting the
frequency deviation with a reduced amount of load
shedding.
 However, balancing the benefits of an increased
speed of response against the risk of unnecessary
shedding is a challenge.
Extensive research has been undertaken to create more advanced load
shedding schemes that use wide area measurements to reduce the
amount of load shed by:
1. Adapting the amount of load shed to the prevailing system conditions,
e.g. inertia.
2. Initiating the load shedding more quickly.
 Initiating the load shedding more quickly can be achieved by using
event based signals (e.g. the loss of a major interconnector or
generator) or by using more complex triggering signals (e.g. triggering
based on rate of change of frequency).
 Furthermore, the amount of load shed can be adapted to the size of
the disturbance and system inertia using wide area measurements.
 Examples of this work include the adaption of shedding based on
measurements of rate of change of frequency (RoCoF) immediately
after the disturbance.
 Quick measuring of RoCoF is very challenging. But it is easily
measured by PMUs which are adopted inWAPS.
ADAPTIVE OUT-OF-STEP RELAYING
 Out of step conditions and system separation
are key precursors to system collapse and
blackouts. As the formation of an electrical
center approaches the system will experience
extreme power swings that will further
exacerbate stressed conditions and drive the
system closer to collapse.Therefore, it is
imperative that any potential out of step
condition is quickly recognized and
prevented; this is the role of out of step relays
 A wide area protection scheme could be developed that
monitors the positive sequence voltages across the system.
These synchronized real time measurements can be used to
predict if regions of the system are approaching an out of
step condition.
 This prediction could be used to initiate a controlled
separation of the areas that are losing synchronism or, if
the prediction is available sufficiently in advance, actions
could be taken to prevent the out of step condition from
occurring and avoid system separation entirely.
 The challenge faced when developing such a scheme would
be selecting the measurement locations and developing
the algorithms for achieving robust real time coherency
determination when the coherent generator groups are
variable.
SYSTEM INTEGRITY PROTECTION
SCHEMES (SIPS)
 SIPS protect power system security from extreme contingencies or wide
area disturbances that are beyond the scope of traditional protection.
 The stages involved in the execution of a SIPS are:
1. Identification and prediction of stressed conditions,`
2. Classification of the threat to system security, ́
3. Decisions and actions,
4. Coordination, and
5. Correction.
 Examples of SIPS include: generator rejection, load rejection, under
frequency and voltage load shedding , system separation, dynamic
braking, and turbine valve control.
 SIPS is used of their ability, such as availability of real time wide area
measurements, to identify complex emerging threats to the power
system and respond to them quickly .
MICRO GRID PROTECTION
 The changes faced by distribution networks include the
connection of energy storage, electric vehicles, smart meters,
demand side participation and the connection of distributed
generation (DG).
 The protection schemes of DG is very similar to the infrastructure
of the transmission lines.
 However, the smaller angular separation across a distribution
network means that measurement of angles on the distribution
network is more demanding than it is at the transmission level.
 A particularly important enabler for these new protection
principles are microprocessor relays that can vary their settings
easily.
 WAP delivers the protection needs of future distribution systems.
CONCLUSION
 WAM offers a wide variety of opportunities for enhancing
the backup protection and system protection of modern
power systems.These enhancements can contribute to
reducing the likelihood of the mal operation of backup
relays, limiting the impact of hidden failures and creating
new tools for managing wide area disturbances.These
benefits indicate that the main role of wide area monitoring
as part of protection is improving the resilience of power
systems against stressed conditions and wide area
disturbances, not the isolation of individual faults.The well-
considered deployment of these new concepts should
reduce the frequency and intensity of blackouts and enable
more rapid service restoration
REFERENCES
[1] Phadke AG,Thorp JS, Adamiak MG (1983) A new measurement
technique for tracking voltage phasors, local system frequency,
and rate of change of frequency. IEEETrans Power Appar Syst
102(5):1025–1038.
[2] TerzijaV,Valerde G, Cai DY et al (2011)Wide-area monitoring,
protection, and control of future electric power networks. Proc
IEEE 99(1):80–93.
[3] Phadke AG (2002) Synchronized phasor measurements-a
historical overview. In: Proceedings of the IEEE PES transmission
and distribution conference and exhibition 2002: Asia Pacific, vol
1,Yokohama, Japan, 6–10 Oct 2002, pp 476–479.
[4] Phadke AG (2008)The wide world of wide-area measurement.
IEEE Power Energy Mag 6(5):52–65.
[5] Horowitz SH, Phadke AG (2006)Third zone revisited. IEEETrans
Power Deliv 21(1):23–29.
WIDE AREA PROTECTION IN POWER SYSTEMS

More Related Content

What's hot

Wide Area Monitoring System WAMS & Applications
Wide Area Monitoring System WAMS & ApplicationsWide Area Monitoring System WAMS & Applications
Wide Area Monitoring System WAMS & Applications
Power System Operation
 
Facts controller
Facts controllerFacts controller
Facts controller
Debayon Saha
 
WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)
Vikram Purohit
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
Manash Deka
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission Lines
Raja Adapa
 
Sssc
SsscSssc
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensatorbhupendra kumar
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
Mamta Bagoria
 
Firing Angle Control & Constant Current Control
Firing Angle Control & Constant Current ControlFiring Angle Control & Constant Current Control
Firing Angle Control & Constant Current Control
Kaushik Naik
 
Smart Grid & WAMS
Smart Grid & WAMSSmart Grid & WAMS
Smart Grid & WAMS
Power System Operation
 
Harmonics
HarmonicsHarmonics
Harmonics
Kartik Mali
 
Load Frequency Control of two area Power system
Load Frequency Control  of two area Power systemLoad Frequency Control  of two area Power system
Load Frequency Control of two area Power system
Animesh Sachan
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch center
ddxdharmesh
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
Nitish NIT
 
Web based power quality monitoring system
Web based power quality monitoring systemWeb based power quality monitoring system
Web based power quality monitoring system
Vikram Purohit
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
Preet_patel
 
Facts devices
Facts devicesFacts devices
Facts devices
Vinod Srivastava
 
Role of phasor measuring unit in power system
Role of phasor measuring unit in power systemRole of phasor measuring unit in power system
Role of phasor measuring unit in power system
HASEENA. M
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
jawaharramaya
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unit
SathriGiridhar
 

What's hot (20)

Wide Area Monitoring System WAMS & Applications
Wide Area Monitoring System WAMS & ApplicationsWide Area Monitoring System WAMS & Applications
Wide Area Monitoring System WAMS & Applications
 
Facts controller
Facts controllerFacts controller
Facts controller
 
WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission Lines
 
Sssc
SsscSssc
Sssc
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensator
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Firing Angle Control & Constant Current Control
Firing Angle Control & Constant Current ControlFiring Angle Control & Constant Current Control
Firing Angle Control & Constant Current Control
 
Smart Grid & WAMS
Smart Grid & WAMSSmart Grid & WAMS
Smart Grid & WAMS
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Load Frequency Control of two area Power system
Load Frequency Control  of two area Power systemLoad Frequency Control  of two area Power system
Load Frequency Control of two area Power system
 
Load dispatch center
Load dispatch centerLoad dispatch center
Load dispatch center
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Web based power quality monitoring system
Web based power quality monitoring systemWeb based power quality monitoring system
Web based power quality monitoring system
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
 
Facts devices
Facts devicesFacts devices
Facts devices
 
Role of phasor measuring unit in power system
Role of phasor measuring unit in power systemRole of phasor measuring unit in power system
Role of phasor measuring unit in power system
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unit
 

Similar to WIDE AREA PROTECTION IN POWER SYSTEMS

A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
Power System Operation
 
Technical paper 6_2
Technical paper 6_2Technical paper 6_2
Technical paper 6_2
Alaa Eladl
 
Backpropagation Neural Network Modeling for Fault Location in Transmission Li...
Backpropagation Neural Network Modeling for Fault Location in Transmission Li...Backpropagation Neural Network Modeling for Fault Location in Transmission Li...
Backpropagation Neural Network Modeling for Fault Location in Transmission Li...
ijeei-iaes
 
E011123541
E011123541E011123541
E011123541
IOSR Journals
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)theijes
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
EMERSON EDUARDO RODRIGUES
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
Mark Anthony Enoy
 
Sistem Tenaga Listrik
Sistem Tenaga Listrik Sistem Tenaga Listrik
Sistem Tenaga Listrik
MuhammadHarrisMunand2
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
IJERD Editor
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectioAminu Bugaje
 
Contigency analysis and security system taking different cases
Contigency analysis  and security system taking different casesContigency analysis  and security system taking different cases
Contigency analysis and security system taking different cases
fekadewalle
 
Elwerfelli2008
Elwerfelli2008Elwerfelli2008
Elwerfelli2008
Gene Rubira
 
Wide area protection-research_in_the_smart_grid
Wide area protection-research_in_the_smart_gridWide area protection-research_in_the_smart_grid
Wide area protection-research_in_the_smart_grid
Alaa Eladl
 
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Kashif Mehmood
 
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Oktay Yaman
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
Power System Operation
 
عرض تقديمي1.pptx
عرض تقديمي1.pptxعرض تقديمي1.pptx
عرض تقديمي1.pptx
ssuserf314411
 
A transient current based micro grid connected power system protection scheme...
A transient current based micro grid connected power system protection scheme...A transient current based micro grid connected power system protection scheme...
A transient current based micro grid connected power system protection scheme...
IJECEIAES
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
Rahul Mehra
 

Similar to WIDE AREA PROTECTION IN POWER SYSTEMS (20)

A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
 
Technical paper 6_2
Technical paper 6_2Technical paper 6_2
Technical paper 6_2
 
Backpropagation Neural Network Modeling for Fault Location in Transmission Li...
Backpropagation Neural Network Modeling for Fault Location in Transmission Li...Backpropagation Neural Network Modeling for Fault Location in Transmission Li...
Backpropagation Neural Network Modeling for Fault Location in Transmission Li...
 
E011123541
E011123541E011123541
E011123541
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
Sistem Tenaga Listrik
Sistem Tenaga Listrik Sistem Tenaga Listrik
Sistem Tenaga Listrik
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Microcontroller based transformer protectio
Microcontroller based transformer protectioMicrocontroller based transformer protectio
Microcontroller based transformer protectio
 
Contigency analysis and security system taking different cases
Contigency analysis  and security system taking different casesContigency analysis  and security system taking different cases
Contigency analysis and security system taking different cases
 
Elwerfelli2008
Elwerfelli2008Elwerfelli2008
Elwerfelli2008
 
Wide area protection-research_in_the_smart_grid
Wide area protection-research_in_the_smart_gridWide area protection-research_in_the_smart_grid
Wide area protection-research_in_the_smart_grid
 
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
Modelling and Implementation of Microprocessor Based Numerical Relay for Prot...
 
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
Chapter 3 electrical-protection_system (hat, trafo, generatör, bara koruma)
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
عرض تقديمي1.pptx
عرض تقديمي1.pptxعرض تقديمي1.pptx
عرض تقديمي1.pptx
 
A transient current based micro grid connected power system protection scheme...
A transient current based micro grid connected power system protection scheme...A transient current based micro grid connected power system protection scheme...
A transient current based micro grid connected power system protection scheme...
 
ASHUTOSH BHATT DT19EEJ008 RPC JUNE22.ppt
ASHUTOSH BHATT DT19EEJ008 RPC JUNE22.pptASHUTOSH BHATT DT19EEJ008 RPC JUNE22.ppt
ASHUTOSH BHATT DT19EEJ008 RPC JUNE22.ppt
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 

More from manogna gwen

Emitter turn off_thyristor(ETO)
Emitter turn off_thyristor(ETO)Emitter turn off_thyristor(ETO)
Emitter turn off_thyristor(ETO)
manogna gwen
 
d-q axis model for DOL starter
d-q axis model for DOL starterd-q axis model for DOL starter
d-q axis model for DOL starter
manogna gwen
 
Implementation of METRO rail using PLC and SCADA
Implementation of METRO rail using PLC and SCADAImplementation of METRO rail using PLC and SCADA
Implementation of METRO rail using PLC and SCADA
manogna gwen
 
Dual axis solar tracking systems with thermal refrigeration
Dual axis solar tracking systems with thermal refrigerationDual axis solar tracking systems with thermal refrigeration
Dual axis solar tracking systems with thermal refrigeration
manogna gwen
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
manogna gwen
 
Artificial Intelligence in Power Systems
Artificial Intelligence in Power SystemsArtificial Intelligence in Power Systems
Artificial Intelligence in Power Systems
manogna gwen
 

More from manogna gwen (6)

Emitter turn off_thyristor(ETO)
Emitter turn off_thyristor(ETO)Emitter turn off_thyristor(ETO)
Emitter turn off_thyristor(ETO)
 
d-q axis model for DOL starter
d-q axis model for DOL starterd-q axis model for DOL starter
d-q axis model for DOL starter
 
Implementation of METRO rail using PLC and SCADA
Implementation of METRO rail using PLC and SCADAImplementation of METRO rail using PLC and SCADA
Implementation of METRO rail using PLC and SCADA
 
Dual axis solar tracking systems with thermal refrigeration
Dual axis solar tracking systems with thermal refrigerationDual axis solar tracking systems with thermal refrigeration
Dual axis solar tracking systems with thermal refrigeration
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
 
Artificial Intelligence in Power Systems
Artificial Intelligence in Power SystemsArtificial Intelligence in Power Systems
Artificial Intelligence in Power Systems
 

Recently uploaded

Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
TECHNICAL TRAINING MANUAL GENERAL FAMILIARIZATION COURSE
TECHNICAL TRAINING MANUAL   GENERAL FAMILIARIZATION COURSETECHNICAL TRAINING MANUAL   GENERAL FAMILIARIZATION COURSE
TECHNICAL TRAINING MANUAL GENERAL FAMILIARIZATION COURSE
DuvanRamosGarzon1
 
Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
Intella Parts
 
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
AJAYKUMARPUND1
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
Robbie Edward Sayers
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
ssuser9bd3ba
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
fxintegritypublishin
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
Jayaprasanna4
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
MuhammadTufail242431
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
MLILAB
 
Event Management System Vb Net Project Report.pdf
Event Management System Vb Net  Project Report.pdfEvent Management System Vb Net  Project Report.pdf
Event Management System Vb Net Project Report.pdf
Kamal Acharya
 

Recently uploaded (20)

Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
TECHNICAL TRAINING MANUAL GENERAL FAMILIARIZATION COURSE
TECHNICAL TRAINING MANUAL   GENERAL FAMILIARIZATION COURSETECHNICAL TRAINING MANUAL   GENERAL FAMILIARIZATION COURSE
TECHNICAL TRAINING MANUAL GENERAL FAMILIARIZATION COURSE
 
Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
 
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
ethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.pptethical hacking-mobile hacking methods.ppt
ethical hacking-mobile hacking methods.ppt
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang,  ICLR 2024, MLILAB, KAIST AI.pdfJ.Yang,  ICLR 2024, MLILAB, KAIST AI.pdf
J.Yang, ICLR 2024, MLILAB, KAIST AI.pdf
 
Event Management System Vb Net Project Report.pdf
Event Management System Vb Net  Project Report.pdfEvent Management System Vb Net  Project Report.pdf
Event Management System Vb Net Project Report.pdf
 

WIDE AREA PROTECTION IN POWER SYSTEMS

  • 1. IMPROVEMENT OF POWER SYSTEM PROTECTION BY WIDE AREA MONITORING NETWORK Presented By UNDERTHE GUIDANCEOF KOLLI MANOGNA G. UJWALA
  • 2. INTRODUCTION TO POWER SYSTEMS PROTECTIUON  Power system protection is defined as the method of protecting the power systems from the faults and clearing the abnormalities in power systems to restore the operation.  This uses some special hardware which is used for the both primary and backup protection  The main philosophy about protection is that no protection of power system can prevent the flow of fault current through the system, it only can prevent the continuation of flowing of fault current by quickly disconnect the short circuit path from the system.
  • 3. WIDE AREA MONITORING SYSTEMS  TheWide Area Monitoring System (WAMS) consists of geographically dispersed Phasor Measurement Units (PMUs) delivering Synchrophasors, i.e., time-tagged data samples of a power system’s sinusoidal voltage or current using a standard time signal as the reference, to Phasor Data Concentrators (PDCs).  These PDCs perform the desired signal handling and assembly of synchronized Phasor measurements into snapshots.They may also facilitate long term storage in high-resolution historical archives.The data in each PMU are time Synchronized to Universal CoordinatedTime (UTC), for example via Global -2- Positioning System (GPS) receivers with an accuracy of one microsecond and stored in PDCs.The Phasors measured simultaneously provide snapshots of the state of the monitored nodes.  By comparing these snapshots, not only during steady state, also the dynamic state of critical nodes in transmission, sub-transmission and distribution networks can be observed.
  • 4. Failures in power systems  CASCADE FAILURES  INAPPROPRIATE OPERATION OF RELAYS  HIDDEN FAILURES
  • 5. NEED FOR WAMS IN BACKUP PROTECTION  The need for wide area measurements as part of primary protection is limited, as it protects a specific element of the power system.  However, aspects of power system protection that have lower requirements in terms of the speed of response (e.g. backup protection) and are less selective can be improved by using wide area measurements to supervise their behavior.  These mal operations can be attributed to either poor relay settings or hidden failures in the protection system.
  • 6.  Novel system integrity protection schemes (SIPS) that can deploy a wide range of far reaching actions to prevent a cascading failure, adaptive system protection (e.g. adaptive under frequency load shedding), supervisory schemes that improve the security of existing backup protection, and methods that do not change the behavior of system protection but do enhance our understanding of it (e.g. alarming system operators to the risk of false penetration of relay characteristics).  Recent work has begun to focus not only on developing new concepts but also on the practical realization of these.
  • 7. OBJECTIVES OF WIDE AREA PROTECTION SCHEMES  Avoiding inappropriate relay settings for the prevailing system conditions.  Managing wide area disturbances.  Mitigating the impact of hidden failures.  Ensuring a suitable balance between the security and dependability of protection.
  • 8. WIDE AREA PROTECTION SCHEMES (WAPS)  ENHANCING PROTECTIONWITHWIDEAREA MONITORING  ALARMINGAGAINSTTHE RISK OF RELAY CHARACTERISTIC PENETRATION  PREVENTING LOAD ENCROACHMENT  ADJUSTINGTHE BALANCE BETWEENTHE SECURITYAND DEPENDABILITYOF PROTECTION  SUPERVISIONOF BACK-UP ZONES  INTELLIGENT UNDER FREQUENCY LOAD SHEDDING  ADAPTIVEOUT-OF-STEP RELAYING  SYSTEM INTEGRITY PROTECTION SCHEMES (SIPS)  MICROGRID PROTECTION
  • 9. ENHANCING PROTECTION WITH WIDE AREA MONITORING  The goal of protection is to protect individual elements of the power system from damage and to protect the security of the power system itself. In the case of primary equipment protection there is very little role for the use of wide area monitoring.This is because primary protection must reliably deliver a very fast response for any fault on the element that it protects.  However, the slower speed of response required for backup protection and the fact that it protects a zone of the system means that wide area monitoring can be a useful tool for improving its performance.The most effective means for ensuring that the system will survive extreme conditions and wide area disturbances is a high degree of built in redundancy and strength
  • 10. Wide area measurements offer the potential to create supervisory schemes for backup protection, more advanced forms of system protection and entirely new protection concepts. Some of them are: 1. Adaptive relays that update their settings as the system state changes. 2. Improved protection of multi terminal lines. 3. Adaptive end of line protection that monitors the remote breaker, if it is open the under reaching Zone 1 is replaced with an instantaneous characteristic. 4. Temporarily adapt relay settings to prevent mal operation during cold load pickup. 5. Use the ability of digital relays to self-monitor to identify hidden failures and use the hot swap functionality offered by International Electro technical Commission to remove them. 6. Intelligent controlled islanding that preempts an uncontrolled system separation by implementing an adaptive controlled separation
  • 11. ALARMING AGAINST THE RISK OF RELAY CHARACTERISTIC PENETRATION  The objective of this application is to detect when the impedance observed by a relay approaches the relay characteristic under non-faulty conditions.This information is then used to alarm protection engineers to a relay setting that is potentially unsuitable.
  • 12. PREVENTING LOAD ENCROACHMENT  Heavily loaded lines may encroach on the settings of relays and cause an incorrect and inappropriate tripping operation during stressed conditions and power swings.  With the computational power of digital relays this can be overcome by using real time measurements of the load to prevent load encroachment by compensating the relay input of load current.
  • 13. ADJUSTING THE BALANCE BETWEEN THE SECURITY AND DEPENDABILITY OF PROTECTION  Balancing the demands of dependability and security is one of the greatest challenges during the design of protection.  During a wide area disturbance, this preference for dependability can result in incorrect and inappropriate tripping operations.  It would attractive to shift the balance of this compromise toward security during stressed conditions, i.e. when the conditions encountered (e.g. power swings) can increase the likelihood of mal operations and reveal hidden failures.  Wide area measurements could be used to detect that the system has entered a stressed condition and then adjust the protection philosophy to shift the balance away from dependability and toward security.
  • 14. USE OF WAM TO VARY THE BALANCEBETWEEN DEPANDABILITY AND SECURITY
  • 16. SUPERVISION OF BACK-UP ZONES  The mal operation of zone 3 relays was identified as a significant contributing factor to recent blackouts.The unusual load currents and power swings observed during wide area disturbances can cause these relays to operate undesirably. Examples of the system behavior that can cause mal operation of a relay are shown in Fig. 3.  The remote PMUs are installed within the protection zone of the backup relay and monitor the current at these remote locations.  These devices implement a simple pickup characteristic and communicate a binary pick up signal to the backup relay.  If the backup relay characteristic is violated but none of the remote devices have picked up, then it can be concluded that no fault has occurred and the backup relay operation can be blocked.  This prevents load swings during extreme conditions from being misinterpreted as faults and helps prevent the mal operation of backup relays from allowing a wide area disturbance to spread through the system.
  • 17.
  • 18. INTELLIGENT UNDER FREQUENCY LOAD SHEDDING  Load shedding is the traditional last line of defense against extreme under frequency conditions.  Current practice is mostly for this shedding to be delivered using a sequence of stages of shedding that are triggered when a certain frequency threshold is violated.  Shedding load more quickly after a loss of in feed is recognized as an effective means for limiting the frequency deviation with a reduced amount of load shedding.  However, balancing the benefits of an increased speed of response against the risk of unnecessary shedding is a challenge.
  • 19. Extensive research has been undertaken to create more advanced load shedding schemes that use wide area measurements to reduce the amount of load shed by: 1. Adapting the amount of load shed to the prevailing system conditions, e.g. inertia. 2. Initiating the load shedding more quickly.  Initiating the load shedding more quickly can be achieved by using event based signals (e.g. the loss of a major interconnector or generator) or by using more complex triggering signals (e.g. triggering based on rate of change of frequency).  Furthermore, the amount of load shed can be adapted to the size of the disturbance and system inertia using wide area measurements.  Examples of this work include the adaption of shedding based on measurements of rate of change of frequency (RoCoF) immediately after the disturbance.  Quick measuring of RoCoF is very challenging. But it is easily measured by PMUs which are adopted inWAPS.
  • 20. ADAPTIVE OUT-OF-STEP RELAYING  Out of step conditions and system separation are key precursors to system collapse and blackouts. As the formation of an electrical center approaches the system will experience extreme power swings that will further exacerbate stressed conditions and drive the system closer to collapse.Therefore, it is imperative that any potential out of step condition is quickly recognized and prevented; this is the role of out of step relays
  • 21.  A wide area protection scheme could be developed that monitors the positive sequence voltages across the system. These synchronized real time measurements can be used to predict if regions of the system are approaching an out of step condition.  This prediction could be used to initiate a controlled separation of the areas that are losing synchronism or, if the prediction is available sufficiently in advance, actions could be taken to prevent the out of step condition from occurring and avoid system separation entirely.  The challenge faced when developing such a scheme would be selecting the measurement locations and developing the algorithms for achieving robust real time coherency determination when the coherent generator groups are variable.
  • 22. SYSTEM INTEGRITY PROTECTION SCHEMES (SIPS)  SIPS protect power system security from extreme contingencies or wide area disturbances that are beyond the scope of traditional protection.  The stages involved in the execution of a SIPS are: 1. Identification and prediction of stressed conditions,` 2. Classification of the threat to system security, ́ 3. Decisions and actions, 4. Coordination, and 5. Correction.  Examples of SIPS include: generator rejection, load rejection, under frequency and voltage load shedding , system separation, dynamic braking, and turbine valve control.  SIPS is used of their ability, such as availability of real time wide area measurements, to identify complex emerging threats to the power system and respond to them quickly .
  • 23. MICRO GRID PROTECTION  The changes faced by distribution networks include the connection of energy storage, electric vehicles, smart meters, demand side participation and the connection of distributed generation (DG).  The protection schemes of DG is very similar to the infrastructure of the transmission lines.  However, the smaller angular separation across a distribution network means that measurement of angles on the distribution network is more demanding than it is at the transmission level.  A particularly important enabler for these new protection principles are microprocessor relays that can vary their settings easily.  WAP delivers the protection needs of future distribution systems.
  • 24.
  • 25.
  • 26. CONCLUSION  WAM offers a wide variety of opportunities for enhancing the backup protection and system protection of modern power systems.These enhancements can contribute to reducing the likelihood of the mal operation of backup relays, limiting the impact of hidden failures and creating new tools for managing wide area disturbances.These benefits indicate that the main role of wide area monitoring as part of protection is improving the resilience of power systems against stressed conditions and wide area disturbances, not the isolation of individual faults.The well- considered deployment of these new concepts should reduce the frequency and intensity of blackouts and enable more rapid service restoration
  • 27. REFERENCES [1] Phadke AG,Thorp JS, Adamiak MG (1983) A new measurement technique for tracking voltage phasors, local system frequency, and rate of change of frequency. IEEETrans Power Appar Syst 102(5):1025–1038. [2] TerzijaV,Valerde G, Cai DY et al (2011)Wide-area monitoring, protection, and control of future electric power networks. Proc IEEE 99(1):80–93. [3] Phadke AG (2002) Synchronized phasor measurements-a historical overview. In: Proceedings of the IEEE PES transmission and distribution conference and exhibition 2002: Asia Pacific, vol 1,Yokohama, Japan, 6–10 Oct 2002, pp 476–479. [4] Phadke AG (2008)The wide world of wide-area measurement. IEEE Power Energy Mag 6(5):52–65. [5] Horowitz SH, Phadke AG (2006)Third zone revisited. IEEETrans Power Deliv 21(1):23–29.