SlideShare a Scribd company logo
© 1993 Square D All Rights Reserved
Product Data Bulletin
Bulletin No. 0140PD9202A
March, 1994
Raleigh, NC, U.S.A.
Supersedes 0140PD9202 dated 1/93
Understanding Type 2 Coordinated Protection in
Motor Branch Circuits
Technical Overview
The new IEC (International Electrotechnical Commission) standard, publication
947 “Low Voltage Switchgear and Control, Part 4-1: Contactors and Motor Start-
ers,” has been recognized by UL (Underwriters Laboratories) and is becoming
widely accepted by designers and users of motor control in the U.S. This standard
addresses coordination between the branch circuit protective device and the motor
starter. It also provides a method to measure performance of these devices if a short
circuit occurs. This standard defines two levels of component protection in the
event of a short circuit: Type 1 and Type 2 coordination.
This Product Data Bulletin describes:
 How to conform to the new standard using motor controls built to meet
NEMA and IEC standards
 Related benefits associated with Type 2 coordination
The IEC standard for motor starters and contactors, 947-4-1, defines two levels of
protection/coordination for the motor starter (contactor and overload relay) under
short circuit conditions. Each level of protection is achieved by using a specific
combination of motor starter and short circuit protective device.
 Type 1 Coordination
Under short circuit conditions, the contactor or starter shall cause no dan-
ger to persons or installation and may not be suitable for further service
without repair and replacement of parts.
 Type 2 Coordination
Under short circuit conditions, the contactor or starter shall cause no dan-
ger to persons or installation and shall be suitable for further use. The risk
of contact welding is recognized, in which case the manufacturer shall in-
dicate the measures to be taken in regards to equipment maintenance.
Faults in electrical systems are most likely to be of a low level, which are handled
well by motor controllers built to meet Type 1 coordination standards. After the
fault is cleared, the only action necessary is to reset the circuit breaker or replace
the fuses. In situations where available fault currents are high and any period of
maintenance downtime is crucial, a higher degree of coordinated protection may
be desirable.
Many industries are dependent upon the continuous operation of a critical manu-
facturing process. In these conditions, it is especially important to understand that
Type 1 protection may not prevent damage to the motor starter components. In or-
der to ensure that high level fault or short circuit does not interrupt a critical pro-
cess, it may be prudent to consider implementation of Type 2 coordination in the
selection and application of low voltage motor controllers.
Type 2 coordination, which has no equivalent U.S. standard, does not permit damage
to the starter beyond light contact welding, easily separated by a screwdriver or several
coil operations. Type 2 coordination does not allow replacement of parts (except fus-
INTRODUCTION
TWO LEVELS OF
PROTECTION
Bulletin No. 0140PD9202A Understanding Type 2 Coordination in Motor Branch Circuits
March, 1994 Technical Overview
Page 2 © 1993 Square D All Rights Reserved
es) and requires that all parts remain in service. Beyond providing basic electrical and
fire protection, it also minimizes lost production, reduced productivity and unsched-
uled disruptions resulting from downtime needed to replace or repair a starter.
Standard industry practice in North America is to use components listed by UL
(Underwriters Laboratories), or certified by the CSA (Canadian Standard Associ-
ation) and applied according to the NEC (National Electrical Code) and CEC (Ca-
nadian Electric Code). Under most circumstances, motor starters designed to meet
the requirements of UL 508 and installed in compliance with the NEC are safe for
the operator and provide adequate protection for the components under most low
and high level short circuit conditions, However, UL, CSA and NEC testing and
application procedures are primarily oriented toward fire safety, with limited con-
cern for maintaining productivity or preventing downtime under severe short cir-
cuit conditions.
The following excerpts from UL 508 Section 58.56, “Controllers Intended for Use
on Circuits Capable of Delivering High Fault Currents,” illustrates this point.
A. There shall be no discharge of parts. Welding or complete disintegration of
contactor contacts and burnout of the current element of an overload relay
is acceptable. The controller may be inoperative at the conclusion of the test.
B. The door or cover shall not be blown open, and it shall be possible to open
the door or cover. Deformation of the enclosure is acceptable.
C. There shall be no breakage of insulating bases to the extent that the integ-
rity of the mounting of live parts is impaired.
The concept of Type 2 coordination started in Europe and has now spread to North
America because of two main reasons:
1. Components meeting IEC standards are designed for application very close
to their maximum capacity. They are physically smaller than traditional
starters built to NEMA standards used in North America. Both styles of
starters, if applied properly, will perform adequately. However, when com-
pared to starters built to NEMA standards, starters built to IEC standards
present unique problems when subjected to short circuit overcurrents. Gen-
erally, the smaller the starter, the lower its ability to withstand short circuits
and the more susceptible it is to damage from higher fault currents.
2. IEC standards for short circuit protective devices do not specify maximum
allowable let-through currents and let-through energies. The more energy
let through by the short circuit protective device, the more potential dam-
age to the starter and vice versa.
In Europe, users of motor control components requested that manufacturers specify
a particular short circuit protective device to be used for each starter size. They also
wanted to know the type of damage likely to result if a short circuit occurred.
The manufacturers conducted short circuit tests for each starter with specific short
circuit protective devices. These tests enabled them to determine what level of
damage a specific starter would experience at a given voltage and short circuit cur-
rent level. In Europe, tests were witnessed and results certified by a unbiased third
party. The exact test procedure was refined so all motor starters could be evaluated
on the same basis. The result was IEC 947-4-1, a new standard for motor starters.
NORTH AMERICAN
MARKET AND UL 508
EVOLUTION OF
TYPE 2
COORDINATION
Understanding Type 2 Coordination in Motor Branch Circuits Bulletin No. 0140PD9202A
Technical Overview March, 1994
Page 3© 1993 Square D All Rights Reserved
One solution to limit short circuit current levels is to limit the amount of available
fault current to a system installation where motor starters are installed. This is not
always practical because the upstream short circuit protection usually exists and is
costly to replace. Today, industry trends favor facilities with higher levels of avail-
able fault current, not less.
Short circuits damage motor starters due to excessive current. This damage is
caused by magnetic forces and excessive heat. Magnetic forces are manifested
through instantaneous peak let-through current (Ip) passed by the short circuit pro-
tective device. These forces can cause the contacts of the starter to blow apart and
can also break the housing of the device.
Heat is proportional to the let-through energy (I2
t) passed by the short circuit pro-
tective device during opening. Excessive heating energy may cause the starter con-
tacts to weld after magnetically blowing apart and may also cause thermal unit
burnout.
The key to Type 2 coordinated protection is to use a protective device that limits
the peak current and clears in less than 8 milliseconds, or the first half cycle.
There are three key benefits of Type 2 coordination:
1. Safety: Type 2 coordination is intended to provide safety for operating per-
sonnel, facility and the installed equipment.
2. Reduced costs: When a starter is properly protected from short circuits, all
components of the branch circuit remain intact and operational. Only fuses
may need to be replaced. Savings result from a reduction in labor required
to perform maintenance after a short circuit and in the amount of replace-
ment parts and required equipment. Savings are also realized by minimiz-
ing spoiled or lost production in a continuous process environment, such
as may occur in some food and chemical process plants.
3. Increased productivity: The manufacturing process relies on continuous
motor operation. If starters are damaged and must be repaired or replaced,
the motors are shut down and the manufacturing process stops. By imple-
menting Type 2 coordination, manufacturing processes should function
with minimum disruption from short circuits on the motor circuits.
SHORT CIRCUIT
CURRENT LEVELS
BENEFITS OF TYPE 2
COORDINATION
Bulletin No. 0140PD9202A Understanding Type 2 Coordination in Motor Branch Circuits
March, 1994 Technical Overview
Page 4 © 1993 Square D All Rights Reserved
Square D motor control products such as circuit breakers, combination motor start-
ers and motor control centers are built to meet the performance requirements of UL
508 and, when applied according to the NEC, provide satisfactory protection in
most industrial applications.
Square D has developed component selection tables. These tables offer engineers,
designers and plant electricians the opportunity to implement Type 2 coordination
protection using standard Square D motor control products.
Currently, the following product lines have been tested to Type 2 performance cri-
teria with independent certification by UL and CSA:
 Class 8536 Type S Starters, built to meet NEMA standards,
NEMA size 00 through 5
 Class 8538 Combination Starters, Fusible Disconnect Switch Type,
NEMA size 0 through 5
 Class 8998 Motor Control Centers, with Type S or D-Line Starters
 Telemecanique D-Line and F-Line Starters, built to meet IEC standards
 Telemecanique Integral 18, Integral 32 and Integral 63 Self-Protected
Starters, rated from 1 to 40 hp @ 480 VAC
The following fusible disconnect switches have been tested to the appropriate with-
stand level and can be used in Type 2 applications. They can accommodate all fuses
shown in Square D’s published Type 2 Coordination fuse selection tables.
 D10
 9421N
 9422T
IEC Publication 947, Low-Voltage Switchgear and Controlgear, Part 4: Contactors
and Motor-Starters.
IEC Publication 292-1, Appendix C: Coordination with Short-Circuit Protective
Devices.
Underwriters Laboratories Standard UL 508, Standard for Safety: Industrial Con-
trol Equipment.
SQUARE D,
TELEMECANIQUE AND
TYPE 2
COORDINATION
REFERENCES

More Related Content

What's hot

MCC Motor Control Center 4
MCC Motor Control Center 4MCC Motor Control Center 4
MCC Motor Control Center 4
Sakshi Vashist
 
Ditek DTK-120SR Data Sheet
Ditek DTK-120SR Data SheetDitek DTK-120SR Data Sheet
Ditek DTK-120SR Data Sheet
JMAC Supply
 
Project
ProjectProject
Projectmkanth
 
Why we need power-system protection? System Protection
Why we need power-system protection? System ProtectionWhy we need power-system protection? System Protection
Why we need power-system protection? System Protection
System Protection
 
Littelfuse Power Supply Solutions
Littelfuse Power Supply SolutionsLittelfuse Power Supply Solutions
Littelfuse Power Supply Solutions
Littelfuse
 
Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...
Living Online
 
MCC Motor Control Center 3
MCC Motor Control Center 3MCC Motor Control Center 3
MCC Motor Control Center 3
Sakshi Vashist
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
Power System Operation
 
Littelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse Solutions for Security Cameras and Video DoorbellsLittelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse
 
Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...
Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...
Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...
Littelfuse
 
Circuit breaker Maintenance By Mobile Agent Software Technology
Circuit breaker Maintenance By Mobile Agent Software TechnologyCircuit breaker Maintenance By Mobile Agent Software Technology
Circuit breaker Maintenance By Mobile Agent Software Technologysiddhartha muduli
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_advertsKhalid Sithari
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET Journal
 
Bhb sicam ak_eng
Bhb sicam ak_engBhb sicam ak_eng
Bhb sicam ak_eng
Trịnh Thế Vinh
 
Advanced Network Solutions for Electric Power Application
Advanced Network Solutions for Electric Power ApplicationAdvanced Network Solutions for Electric Power Application
Advanced Network Solutions for Electric Power Application
chowfei
 
Improving the reliability of feeder protection using digital relays
Improving the reliability of feeder protection using digital relaysImproving the reliability of feeder protection using digital relays
Improving the reliability of feeder protection using digital relaysByreddy Sudarshan
 
Nec emergency requirements
Nec emergency requirementsNec emergency requirements
Nec emergency requirements
michaeljmack
 
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
Harjit Birdi
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
System Protection
 

What's hot (20)

MCC Motor Control Center 4
MCC Motor Control Center 4MCC Motor Control Center 4
MCC Motor Control Center 4
 
Ditek DTK-120SR Data Sheet
Ditek DTK-120SR Data SheetDitek DTK-120SR Data Sheet
Ditek DTK-120SR Data Sheet
 
Project
ProjectProject
Project
 
Why we need power-system protection? System Protection
Why we need power-system protection? System ProtectionWhy we need power-system protection? System Protection
Why we need power-system protection? System Protection
 
Littelfuse Power Supply Solutions
Littelfuse Power Supply SolutionsLittelfuse Power Supply Solutions
Littelfuse Power Supply Solutions
 
Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...Installing, Programming & Commissioning of Power System Protection Relays and...
Installing, Programming & Commissioning of Power System Protection Relays and...
 
MCC Motor Control Center 3
MCC Motor Control Center 3MCC Motor Control Center 3
MCC Motor Control Center 3
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Littelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse Solutions for Security Cameras and Video DoorbellsLittelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse Solutions for Security Cameras and Video Doorbells
 
Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...
Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...
Littelfuse Building Automation Capabilities: Smart Locks and Window / Door Se...
 
Circuit breaker Maintenance By Mobile Agent Software Technology
Circuit breaker Maintenance By Mobile Agent Software TechnologyCircuit breaker Maintenance By Mobile Agent Software Technology
Circuit breaker Maintenance By Mobile Agent Software Technology
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
 
Bhb sicam ak_eng
Bhb sicam ak_engBhb sicam ak_eng
Bhb sicam ak_eng
 
Advanced Network Solutions for Electric Power Application
Advanced Network Solutions for Electric Power ApplicationAdvanced Network Solutions for Electric Power Application
Advanced Network Solutions for Electric Power Application
 
Improving the reliability of feeder protection using digital relays
Improving the reliability of feeder protection using digital relaysImproving the reliability of feeder protection using digital relays
Improving the reliability of feeder protection using digital relays
 
Nec emergency requirements
Nec emergency requirementsNec emergency requirements
Nec emergency requirements
 
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
NETWORK PROTECTION & AUTOMATION GUIDE, EDITION
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
128 electrical power-protection_guide
128 electrical power-protection_guide128 electrical power-protection_guide
128 electrical power-protection_guide
 

Similar to Understanding type 2 coordinated protection in motor branch circuit

Motor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.orgMotor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.org
Dien Ha The
 
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Electrical Reliability Services
 
Molded Case Circuit Breakers Technical Information
Molded Case Circuit Breakers Technical InformationMolded Case Circuit Breakers Technical Information
Molded Case Circuit Breakers Technical Information
CTY TNHH HẠO PHƯƠNG
 
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Schneider Electric
 
Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN
Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN
Factors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsFactors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsJim White
 
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
Luis Antonio González Mederos
 
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Abu Hashim
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guide
Prasad RVS
 
Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazard
IJAPEJOURNAL
 
Pd Maintenance
Pd MaintenancePd Maintenance
Pd Maintenancedwessin
 
Switchgear and Protection ...........................
Switchgear and Protection ...........................Switchgear and Protection ...........................
Switchgear and Protection ...........................
MANOJ KHARADE
 
Switchgear and Protection.................
Switchgear and Protection.................Switchgear and Protection.................
Switchgear and Protection.................
MANOJ KHARADE
 
Importance of the NERC PRC-005 Standard - Challenges and Audit Tips
Importance of the NERC PRC-005 Standard - Challenges and Audit TipsImportance of the NERC PRC-005 Standard - Challenges and Audit Tips
Importance of the NERC PRC-005 Standard - Challenges and Audit Tips
Certrec
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Mahesh Chandra Manav
 
1489 series circuit breaker guide
1489 series circuit breaker guide1489 series circuit breaker guide
1489 series circuit breaker guide
Juan Carlos Lara Quiroz
 
Littelfuse fuseology selection_guide.pdf
Littelfuse fuseology selection_guide.pdfLittelfuse fuseology selection_guide.pdf
Littelfuse fuseology selection_guide.pdf
Brit4
 

Similar to Understanding type 2 coordinated protection in motor branch circuit (20)

Motor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.orgMotor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.org
 
ms ppt.ppt
ms ppt.pptms ppt.ppt
ms ppt.ppt
 
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
 
Molded Case Circuit Breakers Technical Information
Molded Case Circuit Breakers Technical InformationMolded Case Circuit Breakers Technical Information
Molded Case Circuit Breakers Technical Information
 
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
Impact of IEC 61508 Standards on Intelligent Electrial Networks and Safety Im...
 
Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN
Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN
Bussman Medium voltage fuse-AZZAN AL BADI TRADING OMAN
 
Factors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsFactors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE Transactions
 
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
{76d7e191 801e-4032-8c0f-2e0e374a94fc} short-circuit_current_rating_wp033001_en
 
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
 
13
1313
13
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guide
 
Transformer guide
Transformer guideTransformer guide
Transformer guide
 
Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazard
 
Pd Maintenance
Pd MaintenancePd Maintenance
Pd Maintenance
 
Switchgear and Protection ...........................
Switchgear and Protection ...........................Switchgear and Protection ...........................
Switchgear and Protection ...........................
 
Switchgear and Protection.................
Switchgear and Protection.................Switchgear and Protection.................
Switchgear and Protection.................
 
Importance of the NERC PRC-005 Standard - Challenges and Audit Tips
Importance of the NERC PRC-005 Standard - Challenges and Audit TipsImportance of the NERC PRC-005 Standard - Challenges and Audit Tips
Importance of the NERC PRC-005 Standard - Challenges and Audit Tips
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
 
1489 series circuit breaker guide
1489 series circuit breaker guide1489 series circuit breaker guide
1489 series circuit breaker guide
 
Littelfuse fuseology selection_guide.pdf
Littelfuse fuseology selection_guide.pdfLittelfuse fuseology selection_guide.pdf
Littelfuse fuseology selection_guide.pdf
 

More from Bassam Gomaa

Size a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpSize a circuit breaker for a fire pump
Size a circuit breaker for a fire pump
Bassam Gomaa
 
Power management for a changing world
Power management for a changing worldPower management for a changing world
Power management for a changing world
Bassam Gomaa
 
Digital Twin In Hospitals
Digital Twin In HospitalsDigital Twin In Hospitals
Digital Twin In Hospitals
Bassam Gomaa
 
Power tag Catalogue
Power tag CataloguePower tag Catalogue
Power tag Catalogue
Bassam Gomaa
 
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building SolutionValve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Bassam Gomaa
 
Product selection guide - Ecostruxure building Solution
Product selection guide - Ecostruxure building SolutionProduct selection guide - Ecostruxure building Solution
Product selection guide - Ecostruxure building Solution
Bassam Gomaa
 
The impact of power management on building performance and energy costs
The impact of power management on building performance and energy costsThe impact of power management on building performance and energy costs
The impact of power management on building performance and energy costs
Bassam Gomaa
 
Seven steps to reduce the risk of infectious disease in hospitals
Seven steps to reduce the risk of infectious disease in hospitalsSeven steps to reduce the risk of infectious disease in hospitals
Seven steps to reduce the risk of infectious disease in hospitals
Bassam Gomaa
 
Leveraging cloud based building management systems for multi-site facilities
Leveraging cloud based building management systems for multi-site facilitiesLeveraging cloud based building management systems for multi-site facilities
Leveraging cloud based building management systems for multi-site facilities
Bassam Gomaa
 

More from Bassam Gomaa (9)

Size a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpSize a circuit breaker for a fire pump
Size a circuit breaker for a fire pump
 
Power management for a changing world
Power management for a changing worldPower management for a changing world
Power management for a changing world
 
Digital Twin In Hospitals
Digital Twin In HospitalsDigital Twin In Hospitals
Digital Twin In Hospitals
 
Power tag Catalogue
Power tag CataloguePower tag Catalogue
Power tag Catalogue
 
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building SolutionValve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
Valve and Actuator Catalog EMEA - Catalog Ecostruxure Building Solution
 
Product selection guide - Ecostruxure building Solution
Product selection guide - Ecostruxure building SolutionProduct selection guide - Ecostruxure building Solution
Product selection guide - Ecostruxure building Solution
 
The impact of power management on building performance and energy costs
The impact of power management on building performance and energy costsThe impact of power management on building performance and energy costs
The impact of power management on building performance and energy costs
 
Seven steps to reduce the risk of infectious disease in hospitals
Seven steps to reduce the risk of infectious disease in hospitalsSeven steps to reduce the risk of infectious disease in hospitals
Seven steps to reduce the risk of infectious disease in hospitals
 
Leveraging cloud based building management systems for multi-site facilities
Leveraging cloud based building management systems for multi-site facilitiesLeveraging cloud based building management systems for multi-site facilities
Leveraging cloud based building management systems for multi-site facilities
 

Recently uploaded

block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
ongomchris
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
ViniHema
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation & Control
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
Robbie Edward Sayers
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
R&R Consult
 
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdfGoverning Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
WENKENLI1
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
SupreethSP4
 

Recently uploaded (20)

block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 
space technology lecture notes on satellite
space technology lecture notes on satellitespace technology lecture notes on satellite
space technology lecture notes on satellite
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
Water Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdfWater Industry Process Automation and Control Monthly - May 2024.pdf
Water Industry Process Automation and Control Monthly - May 2024.pdf
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
HYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generationHYDROPOWER - Hydroelectric power generation
HYDROPOWER - Hydroelectric power generation
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
 
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdfGoverning Equations for Fundamental Aerodynamics_Anderson2010.pdf
Governing Equations for Fundamental Aerodynamics_Anderson2010.pdf
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Runway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptxRunway Orientation Based on the Wind Rose Diagram.pptx
Runway Orientation Based on the Wind Rose Diagram.pptx
 

Understanding type 2 coordinated protection in motor branch circuit

  • 1. © 1993 Square D All Rights Reserved Product Data Bulletin Bulletin No. 0140PD9202A March, 1994 Raleigh, NC, U.S.A. Supersedes 0140PD9202 dated 1/93 Understanding Type 2 Coordinated Protection in Motor Branch Circuits Technical Overview The new IEC (International Electrotechnical Commission) standard, publication 947 “Low Voltage Switchgear and Control, Part 4-1: Contactors and Motor Start- ers,” has been recognized by UL (Underwriters Laboratories) and is becoming widely accepted by designers and users of motor control in the U.S. This standard addresses coordination between the branch circuit protective device and the motor starter. It also provides a method to measure performance of these devices if a short circuit occurs. This standard defines two levels of component protection in the event of a short circuit: Type 1 and Type 2 coordination. This Product Data Bulletin describes: How to conform to the new standard using motor controls built to meet NEMA and IEC standards Related benefits associated with Type 2 coordination The IEC standard for motor starters and contactors, 947-4-1, defines two levels of protection/coordination for the motor starter (contactor and overload relay) under short circuit conditions. Each level of protection is achieved by using a specific combination of motor starter and short circuit protective device. Type 1 Coordination Under short circuit conditions, the contactor or starter shall cause no dan- ger to persons or installation and may not be suitable for further service without repair and replacement of parts. Type 2 Coordination Under short circuit conditions, the contactor or starter shall cause no dan- ger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall in- dicate the measures to be taken in regards to equipment maintenance. Faults in electrical systems are most likely to be of a low level, which are handled well by motor controllers built to meet Type 1 coordination standards. After the fault is cleared, the only action necessary is to reset the circuit breaker or replace the fuses. In situations where available fault currents are high and any period of maintenance downtime is crucial, a higher degree of coordinated protection may be desirable. Many industries are dependent upon the continuous operation of a critical manu- facturing process. In these conditions, it is especially important to understand that Type 1 protection may not prevent damage to the motor starter components. In or- der to ensure that high level fault or short circuit does not interrupt a critical pro- cess, it may be prudent to consider implementation of Type 2 coordination in the selection and application of low voltage motor controllers. Type 2 coordination, which has no equivalent U.S. standard, does not permit damage to the starter beyond light contact welding, easily separated by a screwdriver or several coil operations. Type 2 coordination does not allow replacement of parts (except fus- INTRODUCTION TWO LEVELS OF PROTECTION
  • 2. Bulletin No. 0140PD9202A Understanding Type 2 Coordination in Motor Branch Circuits March, 1994 Technical Overview Page 2 © 1993 Square D All Rights Reserved es) and requires that all parts remain in service. Beyond providing basic electrical and fire protection, it also minimizes lost production, reduced productivity and unsched- uled disruptions resulting from downtime needed to replace or repair a starter. Standard industry practice in North America is to use components listed by UL (Underwriters Laboratories), or certified by the CSA (Canadian Standard Associ- ation) and applied according to the NEC (National Electrical Code) and CEC (Ca- nadian Electric Code). Under most circumstances, motor starters designed to meet the requirements of UL 508 and installed in compliance with the NEC are safe for the operator and provide adequate protection for the components under most low and high level short circuit conditions, However, UL, CSA and NEC testing and application procedures are primarily oriented toward fire safety, with limited con- cern for maintaining productivity or preventing downtime under severe short cir- cuit conditions. The following excerpts from UL 508 Section 58.56, “Controllers Intended for Use on Circuits Capable of Delivering High Fault Currents,” illustrates this point. A. There shall be no discharge of parts. Welding or complete disintegration of contactor contacts and burnout of the current element of an overload relay is acceptable. The controller may be inoperative at the conclusion of the test. B. The door or cover shall not be blown open, and it shall be possible to open the door or cover. Deformation of the enclosure is acceptable. C. There shall be no breakage of insulating bases to the extent that the integ- rity of the mounting of live parts is impaired. The concept of Type 2 coordination started in Europe and has now spread to North America because of two main reasons: 1. Components meeting IEC standards are designed for application very close to their maximum capacity. They are physically smaller than traditional starters built to NEMA standards used in North America. Both styles of starters, if applied properly, will perform adequately. However, when com- pared to starters built to NEMA standards, starters built to IEC standards present unique problems when subjected to short circuit overcurrents. Gen- erally, the smaller the starter, the lower its ability to withstand short circuits and the more susceptible it is to damage from higher fault currents. 2. IEC standards for short circuit protective devices do not specify maximum allowable let-through currents and let-through energies. The more energy let through by the short circuit protective device, the more potential dam- age to the starter and vice versa. In Europe, users of motor control components requested that manufacturers specify a particular short circuit protective device to be used for each starter size. They also wanted to know the type of damage likely to result if a short circuit occurred. The manufacturers conducted short circuit tests for each starter with specific short circuit protective devices. These tests enabled them to determine what level of damage a specific starter would experience at a given voltage and short circuit cur- rent level. In Europe, tests were witnessed and results certified by a unbiased third party. The exact test procedure was refined so all motor starters could be evaluated on the same basis. The result was IEC 947-4-1, a new standard for motor starters. NORTH AMERICAN MARKET AND UL 508 EVOLUTION OF TYPE 2 COORDINATION
  • 3. Understanding Type 2 Coordination in Motor Branch Circuits Bulletin No. 0140PD9202A Technical Overview March, 1994 Page 3© 1993 Square D All Rights Reserved One solution to limit short circuit current levels is to limit the amount of available fault current to a system installation where motor starters are installed. This is not always practical because the upstream short circuit protection usually exists and is costly to replace. Today, industry trends favor facilities with higher levels of avail- able fault current, not less. Short circuits damage motor starters due to excessive current. This damage is caused by magnetic forces and excessive heat. Magnetic forces are manifested through instantaneous peak let-through current (Ip) passed by the short circuit pro- tective device. These forces can cause the contacts of the starter to blow apart and can also break the housing of the device. Heat is proportional to the let-through energy (I2 t) passed by the short circuit pro- tective device during opening. Excessive heating energy may cause the starter con- tacts to weld after magnetically blowing apart and may also cause thermal unit burnout. The key to Type 2 coordinated protection is to use a protective device that limits the peak current and clears in less than 8 milliseconds, or the first half cycle. There are three key benefits of Type 2 coordination: 1. Safety: Type 2 coordination is intended to provide safety for operating per- sonnel, facility and the installed equipment. 2. Reduced costs: When a starter is properly protected from short circuits, all components of the branch circuit remain intact and operational. Only fuses may need to be replaced. Savings result from a reduction in labor required to perform maintenance after a short circuit and in the amount of replace- ment parts and required equipment. Savings are also realized by minimiz- ing spoiled or lost production in a continuous process environment, such as may occur in some food and chemical process plants. 3. Increased productivity: The manufacturing process relies on continuous motor operation. If starters are damaged and must be repaired or replaced, the motors are shut down and the manufacturing process stops. By imple- menting Type 2 coordination, manufacturing processes should function with minimum disruption from short circuits on the motor circuits. SHORT CIRCUIT CURRENT LEVELS BENEFITS OF TYPE 2 COORDINATION
  • 4. Bulletin No. 0140PD9202A Understanding Type 2 Coordination in Motor Branch Circuits March, 1994 Technical Overview Page 4 © 1993 Square D All Rights Reserved Square D motor control products such as circuit breakers, combination motor start- ers and motor control centers are built to meet the performance requirements of UL 508 and, when applied according to the NEC, provide satisfactory protection in most industrial applications. Square D has developed component selection tables. These tables offer engineers, designers and plant electricians the opportunity to implement Type 2 coordination protection using standard Square D motor control products. Currently, the following product lines have been tested to Type 2 performance cri- teria with independent certification by UL and CSA: Class 8536 Type S Starters, built to meet NEMA standards, NEMA size 00 through 5 Class 8538 Combination Starters, Fusible Disconnect Switch Type, NEMA size 0 through 5 Class 8998 Motor Control Centers, with Type S or D-Line Starters Telemecanique D-Line and F-Line Starters, built to meet IEC standards Telemecanique Integral 18, Integral 32 and Integral 63 Self-Protected Starters, rated from 1 to 40 hp @ 480 VAC The following fusible disconnect switches have been tested to the appropriate with- stand level and can be used in Type 2 applications. They can accommodate all fuses shown in Square D’s published Type 2 Coordination fuse selection tables. D10 9421N 9422T IEC Publication 947, Low-Voltage Switchgear and Controlgear, Part 4: Contactors and Motor-Starters. IEC Publication 292-1, Appendix C: Coordination with Short-Circuit Protective Devices. Underwriters Laboratories Standard UL 508, Standard for Safety: Industrial Con- trol Equipment. SQUARE D, TELEMECANIQUE AND TYPE 2 COORDINATION REFERENCES