RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymeric and MINDpaper insulated cables from 7.2 kV up to 36 kVSystem Designer EPKT- 17C3MOH3 B21 G43
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...AKBAR TRADING
te connectivity saudi arabia
TYCO TERMINATION KIT IN ALL VOLTAGE
Raychem terminations for polymeric and MIND
paper insulated cables from 7.2 kV up to 36 kV
System Designer
케이블 종단-거-瑞侃工具包电缆终端-阿克巴交易
ชุด การเลิกจ้าง
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS)
11kV-33kV Medium Voltage Heat Shrink Cable Joints & Cable Terminations
11kV and 33kV heat shrink cable joints and cable terminations for medium voltage power cables - SPS heat shrink cable joints and cable terminations are suitable for installation at indoors and outdoors in the Middle East countries, this includes salt laden and dusty atmospheres associated with the Middle East oil, gas and petrochemical industries. Cable terminations and cable joints are suitable for XLPE and paper insulated single core and three 3 core cables of 11kV and 33kV voltages, 3 phase, 50HZ type electrical systems with highest system voltages of 12kV and 36kV. Cable joints are suitable for connecting two XLPE insulated cables of same size or dissimilar sizes and for transition between XLPE and paper insulated lead covered (PILC) medium voltage cables.
SPS High Voltage Cable Termination Kit List (Typical) - Three Core Cables
XLPE EPR HV Termination Kits
Anti-track heat shrink 3 core tubes x 3
Stress control heat shrink 3 core tubes x 3
Yellow stress relief tape for screen ends x 3
3 core heat shrink cable breakout boot x 1
Red mastic sealing tape x 1
Cable cleaning and de-greasing wipes x 3
Box, label, jointing instructions x 1
HV Termination Kits Optional Extras, 3 Core 6.6-7.2kV - Solderless Earth Kit for Copper Tape Screen Cables, Insulating Bushing Boots (Straight, Right Angled, Universal), HV Cable Glands for SWA Cable (Bolt-on Top Hat), Outdoor Armour Earthing Kit, Outdoor Stand-off Brackets + Insulators, High Voltage HV Cable Lugs (Crimp or Mechanical Shearbolt Lugs).
SPS High Voltage Heat Shrink Cable Termination Kits, 6.6-7.2kV - Testing
SPS high voltage heat shrink termination kits for 3 core HV cables (XLPE and EPR) are Tested and Certified to latest International Test Standards as outlined in Cenelec standards HD 628 S1 and 629.1 S2 : 2006 - high voltage cable termination kit testing also encompasses VDE 0278 and IEC 60502.
Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints TYCO- RA...AKBAR TRADING
Raychem heat-shrinkable joints
for screened plastic and rubber
insulated cables up to 36 kV
Raychem heat-shrinkable joints for screened plastic and rubber insulated cables
up to 36 kV
Tyco Electronics
For jointing plastic insulated cables for
up to 36 kV we offer a system based
on head-shrinkable materials which are
fast and simple to install, eliminates
shelf-life limitations even in severe
climates and permits immediate
back-filling of the trench and
re-energize.
ชุด การเลิกจ้าง
瑞侃工具包电缆终端-阿克巴交易
케이블 종단-거
TERMINAZIONE DEL CAVO - AKBAR TRADING
TERMINACIÓN DE CABLE - AKBAR TRADING
KABELABSCHLUSS
TERMINACIÓN DE CABLE
KABLO SONLANDIRMA
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...AKBAR TRADING
te connectivity saudi arabia
TYCO TERMINATION KIT IN ALL VOLTAGE
Raychem terminations for polymeric and MIND
paper insulated cables from 7.2 kV up to 36 kV
System Designer
케이블 종단-거-瑞侃工具包电缆终端-阿克巴交易
ชุด การเลิกจ้าง
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS)
11kV-33kV Medium Voltage Heat Shrink Cable Joints & Cable Terminations
11kV and 33kV heat shrink cable joints and cable terminations for medium voltage power cables - SPS heat shrink cable joints and cable terminations are suitable for installation at indoors and outdoors in the Middle East countries, this includes salt laden and dusty atmospheres associated with the Middle East oil, gas and petrochemical industries. Cable terminations and cable joints are suitable for XLPE and paper insulated single core and three 3 core cables of 11kV and 33kV voltages, 3 phase, 50HZ type electrical systems with highest system voltages of 12kV and 36kV. Cable joints are suitable for connecting two XLPE insulated cables of same size or dissimilar sizes and for transition between XLPE and paper insulated lead covered (PILC) medium voltage cables.
SPS High Voltage Cable Termination Kit List (Typical) - Three Core Cables
XLPE EPR HV Termination Kits
Anti-track heat shrink 3 core tubes x 3
Stress control heat shrink 3 core tubes x 3
Yellow stress relief tape for screen ends x 3
3 core heat shrink cable breakout boot x 1
Red mastic sealing tape x 1
Cable cleaning and de-greasing wipes x 3
Box, label, jointing instructions x 1
HV Termination Kits Optional Extras, 3 Core 6.6-7.2kV - Solderless Earth Kit for Copper Tape Screen Cables, Insulating Bushing Boots (Straight, Right Angled, Universal), HV Cable Glands for SWA Cable (Bolt-on Top Hat), Outdoor Armour Earthing Kit, Outdoor Stand-off Brackets + Insulators, High Voltage HV Cable Lugs (Crimp or Mechanical Shearbolt Lugs).
SPS High Voltage Heat Shrink Cable Termination Kits, 6.6-7.2kV - Testing
SPS high voltage heat shrink termination kits for 3 core HV cables (XLPE and EPR) are Tested and Certified to latest International Test Standards as outlined in Cenelec standards HD 628 S1 and 629.1 S2 : 2006 - high voltage cable termination kit testing also encompasses VDE 0278 and IEC 60502.
Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints TYCO- RA...AKBAR TRADING
Raychem heat-shrinkable joints
for screened plastic and rubber
insulated cables up to 36 kV
Raychem heat-shrinkable joints for screened plastic and rubber insulated cables
up to 36 kV
Tyco Electronics
For jointing plastic insulated cables for
up to 36 kV we offer a system based
on head-shrinkable materials which are
fast and simple to install, eliminates
shelf-life limitations even in severe
climates and permits immediate
back-filling of the trench and
re-energize.
ชุด การเลิกจ้าง
瑞侃工具包电缆终端-阿克巴交易
케이블 종단-거
TERMINAZIONE DEL CAVO - AKBAR TRADING
TERMINACIÓN DE CABLE - AKBAR TRADING
KABELABSCHLUSS
TERMINACIÓN DE CABLE
KABLO SONLANDIRMA
Medium Voltage Terminations- up to 42kV.| AKBAR TRADING EST.| mail@akbartradi...AKBAR TRADING
Cold Applied:
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Pre Expanded on Holdout - up to 42kV
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Push On - up to 42kV
Heat Shrinkable:
• IXSU/OXSU:
Uniterm - Terminations for Polymeric Cables - up to
42kV
Uniterm - Terminations for Polymeric Cables - up to
42kV - Selection Guide
• IXSU/OXSU - EPKT Quick Reference Guide
Heat Shrinkable Elbows:
• EPKT:
Heat Shrinkable Termination System for cables up to 36kV
Heat Shrinkable Termination Selection Guide
• RSRB:
Inline Bushing Boots
• RSRB:
Right Angle Bushing Boots
Inline & Right Angle Bushing Boot Selection Guide
Push On Elbows:
• RCAB:
Elastomeric Flexible Bushing Boot - up to 17.5kV ONLY
• RCAB:
Inline Cold Applied Boot - up to 24kV ONLY
• RICS:
Insulated Elbow Adaptors - up to 24kV
Insulated Elbow Adaptors - up to 24kV - Selection Guide
• RSES/RSSS:
Insulated Screened Elbows - 250A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 36kV
• RSTI:
Insulated Screened Elbow - Piggyback Coupling System - up to 36kV
GURO MV:
NEW
GUROFLEX Medium Voltage - Cold pour Insulating Compound
Section 4:
Energy Division
http://energy.tycoelectronics.com
Modern underground power cables are sophisticated assemblies of insulators, conductors and protective materials. Within these components are sensors, which enable cable operators to monitor conditions along the cable in real time.
The condition of the cable insulation is usually monitored through the following two main methods:
Loss tangent measurements
Partial discharge (PD) measurements
T&D are distributors for ABB Kabeldon High Voltage Cable Joints, Cable Terminations and Screened Separable Connectors for high voltage XLPE cable terminating and jointing 11kV, 24kV and 33kV. ABB HV cable connectors are premolded screened separable connectors for terminating and connecting XLPE insulated single or three core cables with copper or aluminium conductors, 11-24kV-33kV, into high voltage switchgear and transformers.
ABB connectors terminate high voltage cables with copper wire and copper tape screens, with or without aluminium (AWA) or steel wire armour (SWA) inot switchgear and transformers.
Elastimold - HV High Voltage Joints, Terminations, Loadbreak & Deadbreak Connectors.
Load Break Elbows
A load break elbow when used with a hot stick can be connected or disconnected at high voltage under load, but can only be used with up to a 250kcmil cable. At 100% insulation level, a 250kcmil is good for 345A in underground duct, so you would be de-rating your system by using a 200A elbow with a 250kcmil cable, but they are still widely used due to the flexibility given to the high voltage distribution system at the equipment. Think about it…if you had a critical application where power disruptions were extremely costly and maintenance was required on up-stream equipment in, let’s say a non critical area, this product would be great. You could disconnect the load without disturbing the critical portions, perform the maintenance and then reconnect it. Just make sure to take safety precautions, making and breaking electrical connections under load is very dangerous. The load break elbow is typically not used in man-holes, because it does not allow expansion like the dead break elbow. The construction of the load break elbow does not allow it to be connected to other elbows, but the dead break does.
Dead Break Elbows
A dead break or “hammerhead” elbow can only be disconnected when not under load, this is because you need to actually unscrew a pin to detach it. It would be pretty tough to unscrew the pin with a hot stick and the arc from the disconnected load, if under load, would be pretty substantial. A dead break elbow allows an increased current rating (up to 600A) and can be used on basically all cable types. At 100% insulation level a 750kcmil cable is rated 610A in underground duct. When would you use a 750kcmil? In most non-utility cases you would design or install sets of 500kcmil or smaller if you needed more than one 500kcmil could handle. Even from a 1200A breaker, two sets of 500kcmil per phase would be sufficient for distribution (about 1000A), if the load was even that high. Most of the time you set the relays down to the actual load in order to limit the copper used. A dead break when used in man-holes for splicing cables allows the flexibility of connecting more than two cables together as well as future expansion if required. Say another building was added that needed power, you could just connect that building to the existing array of dead break elbows. This also works great when temporary power is needed for construction or even if the circus is in town and they need medium voltage (it happens!). They can pick up power from the man-hole with the dead break elbows or from a piece of equipment with dead break elbows. I’ve heard that ships are now starting to use medium voltage shore power, I wonder what kind of connections they use.
Medium Voltage Terminations- up to 42kV.| AKBAR TRADING EST.| mail@akbartradi...AKBAR TRADING
Cold Applied:
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Pre Expanded on Holdout - up to 42kV
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Push On - up to 42kV
Heat Shrinkable:
• IXSU/OXSU:
Uniterm - Terminations for Polymeric Cables - up to
42kV
Uniterm - Terminations for Polymeric Cables - up to
42kV - Selection Guide
• IXSU/OXSU - EPKT Quick Reference Guide
Heat Shrinkable Elbows:
• EPKT:
Heat Shrinkable Termination System for cables up to 36kV
Heat Shrinkable Termination Selection Guide
• RSRB:
Inline Bushing Boots
• RSRB:
Right Angle Bushing Boots
Inline & Right Angle Bushing Boot Selection Guide
Push On Elbows:
• RCAB:
Elastomeric Flexible Bushing Boot - up to 17.5kV ONLY
• RCAB:
Inline Cold Applied Boot - up to 24kV ONLY
• RICS:
Insulated Elbow Adaptors - up to 24kV
Insulated Elbow Adaptors - up to 24kV - Selection Guide
• RSES/RSSS:
Insulated Screened Elbows - 250A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 36kV
• RSTI:
Insulated Screened Elbow - Piggyback Coupling System - up to 36kV
GURO MV:
NEW
GUROFLEX Medium Voltage - Cold pour Insulating Compound
Section 4:
Energy Division
http://energy.tycoelectronics.com
Modern underground power cables are sophisticated assemblies of insulators, conductors and protective materials. Within these components are sensors, which enable cable operators to monitor conditions along the cable in real time.
The condition of the cable insulation is usually monitored through the following two main methods:
Loss tangent measurements
Partial discharge (PD) measurements
T&D are distributors for ABB Kabeldon High Voltage Cable Joints, Cable Terminations and Screened Separable Connectors for high voltage XLPE cable terminating and jointing 11kV, 24kV and 33kV. ABB HV cable connectors are premolded screened separable connectors for terminating and connecting XLPE insulated single or three core cables with copper or aluminium conductors, 11-24kV-33kV, into high voltage switchgear and transformers.
ABB connectors terminate high voltage cables with copper wire and copper tape screens, with or without aluminium (AWA) or steel wire armour (SWA) inot switchgear and transformers.
Elastimold - HV High Voltage Joints, Terminations, Loadbreak & Deadbreak Connectors.
Load Break Elbows
A load break elbow when used with a hot stick can be connected or disconnected at high voltage under load, but can only be used with up to a 250kcmil cable. At 100% insulation level, a 250kcmil is good for 345A in underground duct, so you would be de-rating your system by using a 200A elbow with a 250kcmil cable, but they are still widely used due to the flexibility given to the high voltage distribution system at the equipment. Think about it…if you had a critical application where power disruptions were extremely costly and maintenance was required on up-stream equipment in, let’s say a non critical area, this product would be great. You could disconnect the load without disturbing the critical portions, perform the maintenance and then reconnect it. Just make sure to take safety precautions, making and breaking electrical connections under load is very dangerous. The load break elbow is typically not used in man-holes, because it does not allow expansion like the dead break elbow. The construction of the load break elbow does not allow it to be connected to other elbows, but the dead break does.
Dead Break Elbows
A dead break or “hammerhead” elbow can only be disconnected when not under load, this is because you need to actually unscrew a pin to detach it. It would be pretty tough to unscrew the pin with a hot stick and the arc from the disconnected load, if under load, would be pretty substantial. A dead break elbow allows an increased current rating (up to 600A) and can be used on basically all cable types. At 100% insulation level a 750kcmil cable is rated 610A in underground duct. When would you use a 750kcmil? In most non-utility cases you would design or install sets of 500kcmil or smaller if you needed more than one 500kcmil could handle. Even from a 1200A breaker, two sets of 500kcmil per phase would be sufficient for distribution (about 1000A), if the load was even that high. Most of the time you set the relays down to the actual load in order to limit the copper used. A dead break when used in man-holes for splicing cables allows the flexibility of connecting more than two cables together as well as future expansion if required. Say another building was added that needed power, you could just connect that building to the existing array of dead break elbows. This also works great when temporary power is needed for construction or even if the circus is in town and they need medium voltage (it happens!). They can pick up power from the man-hole with the dead break elbows or from a piece of equipment with dead break elbows. I’ve heard that ships are now starting to use medium voltage shore power, I wonder what kind of connections they use.
Cloud computing is the area which is involving at a very fast rate. With the increase in the internet speed and the decrease in the cost associated with the technology and networking, cloud computing is gaining momentum. This presentation shows the use of cloud computing from the user's point of view, that is it deals with the use of cloud rather than going to the technical implementations of it.
Ultra-Lok® Band and Buckle Systems 10
BAND-FAST™ Precut and Assembled 11
COLOR-IT™ 12
BAND-IT® Band and Buckles 13
Hand Tools for Band and Buckle 13
VALU-STRAP™ and Clips 14
Corrosion Resistant Stainless Steel Bands 15-16
Scru-Lokt Buckles 15
All Purpose Band 16
Q-Band™ and Q-Clip™ 17
Pipe Patches 17
Sign Mounting Brack-Its 18
Mounting Plates 19
BAND-IT® Bolt/Clamps 19
Signal Mounts 19
ID Tagging Systems 20-21
Tie-Lok® Ties 23
Ultra-Lok® Ties 24
Ball-Lok Ties 24
Multi-Lok Ties 24
BAND-IT® Ties 25
Engineered Applications 26
IT Series Heavy Duty Pneumatic Production Tools 27
Ultra-Lok® Clamp Systems 30
Junior® Smooth ID Clamp Systems 31
Universal Clamps 32
Center Punch Clamp Systems 33
BAND-FAST™ Open End with Center Punch Clip 33
Worm Gear Clamps 34
Scru-Seal Clamping System 34
Scru-Band Clamping System 34
Tri-Lokt® Systems 35-36
Full Flow Hose Nipples 36
Swaged Hose Nipples 37
Male Hose Nipples 36-37
Hose Menders 37
Hand Tools 38
Power Tools 39
Patents, Trademarks, Codes, Approvals 40
Definitions and Abbreviations 41
Metals Data 42-43
This presentation was made to enhance the overall experience of the school annual function. This was presented in front of the esteemed guests to give them a glimpse of the school and the science exhibition.
This slide was made by me when i was in school.
PureView Technology, the secret behind the nokia's 41 megapixel cameraPuru Agrawal
PureView technology is a patented technology that Nokia uses in some of its smartphone's cameras. This technology makes use of bigger sensors and better image processing algorithms for getting better photos, better low light performance and loss-less zoom.
AXIS Cable lugs | AKBAR TRADING EST -SAUDI ARABIA| mail@akbartrading.com
Similar to RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymeric and MINDpaper insulated cables from 7.2 kV up to 36 kVSystem Designer EPKT- 17C3MOH3 B21 G43
Abb Combiflex Lugs 1.5, Abb Combiflex Lugs 2.5 | AKBAR TRADING EST. JUBAILAKBAR TRADING
Contact sockets, silver plated (set of 100 pcs)
10 A, conductor area 0,25-1,5 mm2
20 A, conductor area 1,5-2,5 mm2
1
1
1MRK 002 136-A
1MRK 002 136-D
50 g
90 g
Contact pins, silver plated (set of 100 pcs)
10 A, conductor area 0,25-1,5 mm2
20 A, conductor area 1,5-2,5 mm2
1
1
1MRK 002 136-G
1MRK 002 136-H
60 g
120 g
400 Series Interface B Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface B bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Euromold Connectors 400 Series Interface Type C Bushing - 630Amp
* Connector Type : M16 Bolted Copper Insert
* Voltage Range : 11/12kV-33/36kV
* Current Rating : 630amps
* Specification : CENELEC EN50180 & EN50181
Euromold 430TB Elbow Connectors are used with 400 Series Interface C Bushing.
Nexans Euromold tee connectors are designed for terminating high voltage XLPE power cables into compact switchgear to make optimum use of limited installation space.
Nexans, the worldwide leader in the cable industry, has extended its well-proven range of compact high voltage (HV) connectors with two new tee-shaped connectors designed specifically for use with compact switchgear and transformers now being specified for wind turbine applications. The Nexans Euromold M430TB connector is for use with higher voltages (up to 33-36kV) and the M434TB connector is for higher currents (up to 1,250 A).
Trend Towards Compact Switchgear for Wind Turbines
The growing trend towards using ever more compact high voltage switchgear in wind turbines has resulted in smaller cable boxes, limiting the space available for connectors. Nexans has responded to this challenge by developing its new asymmetric tee-shape connectors to create a compact connection solution. This now enables two cables to be connected in the same space required for one cable using a traditional non-compact connector. As well as being ideal for all applications where space is a limiting factor, the Nexans compact connectors also enable users to increase the capacity of an existing installation.
EPDM Jacket: A Key Design Feature for Safety and Reliability
The Nexans Euromold M430TB and the M434TB are separable tee-shape bolted connectors designed to connect high voltage polymer-insulated cable to wind turbine equipment such as switchgear and transformers- they can also be used for cable to cable connections with the appropriate mating parts. A key design feature is the thick (3 mm) EPDM (Ethylene Propylene Diene Monomer) rubber conductive insulation jacket that provides a total safe to touch screen for personnel safety, this is both more reliable and longer lasting than the painted silicone rubber insulation used in many connectors.
400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
The Nexans Euromold compact version screened separable connector is suitable for high voltage HV cable termination up to 33kV. Interface Type C Euromold M16 bolted tee connectors up to 33kV are designed to connect and terminate polymeric (XLPE EPR) cables to M16 bolted 400 series equipment bushings. Nexans Euromold connectors are supplied in sets of three phases.
Nexans Euromold Kit Contents: 3 x connector housings, 3 x size sensitive cable reducers, 3 x conductor contact lug, 3 x clamping screws and 3 x insulating plugs & caps.
900 Series Interface F Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface F bushings on switchgear and transformers up to 42kV. Nexans 944TB Tee Connectors provide high voltage cable terminations using separable tee shape connectors :
Nexans 944TB/G - 12kV 2500Amp 70-80sqmm Conductors
Nexans K944TB/G - 24kV 2500Amp 16-800sqmm Conductors
Nexans M944TB/G - 36kV 2500Amp 35-800sqmm Conductors
Nexans P944TB/G - 42kV 1250Amp 50-800sqmm Conductors
Similar to RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymeric and MINDpaper insulated cables from 7.2 kV up to 36 kVSystem Designer EPKT- 17C3MOH3 B21 G43 (20)
A cold applied tape which remains plastic over a wide temperature range. It is
non-hardening and non-cracking. It is highly resistant to mineral acids, alkalis,
salts and micro-organisms and highly impermeable to water, water vapour and
gases. For the protection of buried or exposed pipes, rods, cables, valves and
metal fittings from corrosion. Waterproofing of cables and thermal insulation.
Partex identification catalogue 2017 | AKBAR TRADING EST. AKBAR TRADING
PARTEX ensure that all of products meet the same consistent high quality standard, They subject them to a series of exacting tests, both in-house and at
independent test laboratories. This ensures they meet the requirements of the releavnt International Standards, such as BS EN and UL certiication.
In our UK test laboratory they have equipment that enables us to perform mechanical force tests up to 30KN which means that they can test to destruction
our full range of cable terminations, and cable management products.
We are able to provide test reports and calibration certiicates upon request.
We can also perform a moisture content inspection on our range of Nylon products to ensure they are perfectly conditioned, strong, lexible and durable.
In line with our ISO9001 certiication we operate a strict stock rotation system to ensure that all products reach you in perfect condition.
To meet the requirements of our ISO14001 environmental standard, we strive to minimise our impact upon the environment at all stages of our business
activities.
Partex lugs and_connectors_catalogue | AKBAR TRADING EST. AKBAR TRADING
All copper tube terminals have bell mouth entry for ease of cable insertion.
All terminals have inspection holes to check cable is properly inserted before crimping.
Copper tube splices, four hole transformer fixing, long palm, right angle, blank terminals, copper pins, dissimilar copper splices and flag terminals also available on request.
Sizes above 400mm² available on request.
Other Stud sizes available on request.
MATERIAL: High conductivity copper to BS2871
PURITY: > 99.9%
COATING: Bright electro-tin plating to BS 1872
SCHNEIDER CIRCUIT BREAKER
Schneider Electric range of products in Circuit Breakers and Switches: Compact NS < 630A,Compact NS,Compact NSF/NSJ,Compact NG160,Compact
Thermal Magnetic Circuit Breaker, Miniature, Multi 9 C60N Series, 120 VAC
SCHNEIDER ELECTRIC SAUDI ARABIA
SCHNEIDER - STOCK - SAUDI ARABIA- AKBAR TRADINGI c60n circuit_breakers_schnei...AKBAR TRADING
Acti9 iC60N MCBs 2 Pole
iC60N curve B, C, D circuit breakers are multi-standard circuit breakers which combine circuit protection against short-circuit currents and circuit protection against overload currents
เบรกเกอร์,قاطع الدائرة الكهربائية, 电气断路器 , Leistungsschalter
AKBAR TRADING EST| Thomas & Betts Cable Tie TyrapAKBAR TRADING
1.1
8
Premium cable ties with steel locking barb
Characteristics
The single most distinguishing feature of the Ty-Rap
®
cable ties
from Thomas & Betts is the stainless steel locking barb, firmly
anchored inside the tie head (Fig. 1).
It is made from corrosion-proof, antimagnetic steel (Marine
Grade Type 316).
This guarantees a strong and durable locking of the tie even
under the most adverse conditions - humidity, heat, cold, etc.
and is also proof against vibration and external shock.
When applying ties with Thomas & Betts tooling, the excess
end of the tie is automatically cut off and the slight over cut
retracts into the tie, so that there is no risk of injury from
protruding sharp edges. (Fig. 3)
The low-profile design of the head allows secure tying in tight
spaces.
The edges of the head are also rounded off to offer maximum
protection from injury.
The transition from the strap to the head is gradual. This
protects the material against breaking at this most critical
point.
TY523MX - THOMAS & BETTS - Cable Tie, Ty Rap® Self Lock, Nylon| AKBAR TRADING...AKBAR TRADING
Thomas & Betts Corporation. Specifications are subject to change without notice. www.tnb.com. J3. J. Ty-Rap. ®/Ty-Fast. ®. T&B's Ty-Rap® Cable Ties
Thomas & Betts Key Products:
Ty-Rap Cable Ties
Ty-Met Cable Management Products
Cable Conduits
Cable Accessories
Akbar trading splicing_kit_raychem_te_connectivityAKBAR TRADING
RSTI-58 Separable Connection
CRSM Heat-shrinkable
Category 2 Catalog
HVBT Busbar Insulation Tape
RSTI-6952 Separable Connection
low voltage medium voltage high voltage termination
ALL RAYCHEM PRODUCTS ARE APPROVED BY SAUDI ARAMCO / SEC / SABIC / ROYAL COMMISSION.
Akbar trading splicing_kit_loadbreak_elbow_raychem_te_connectivityAKBAR TRADING
ENERGY /// HIGH VOLTAGE CABLE ACCESSORIES UP TO 245 KV
RAYCHEM
HIGH VOLTAGE
CABLE ACCESSORIES
UP TO 245 KV
Heat-Shrinkable Terminations (IHVT-H/ OHVT-H/ LHVT-H)
10
Heat-Shrinkable Terminations for DC Filter Cables (FCEV)
14
Outdoor Terminations Composite (OHVT-C)
17
Outdoor Terminations Porcelain (OHVT-P)
22
Outdoor Terminations Dry-type (OHVT-D)
27
Add-On Kits for Outdoor Terminations
Heat-Shrinkable Joints (EHVS-H)
46
One Piece Joints (EHVS-S)
48
Three Piece Joints (EHVS-T)
51
Fibre-Optic Add-On Kit for HV Cable Joints
Medium Voltage Terminations
- up to 42kV.
Cold Applied:
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Pre Expanded on Holdout - up to 42kV
• TFTI-TFTO:
Single Core Polymeric Cable Termination - Push On - up to 42kV
Heat Shrinkable:
• IXSU/OXSU:
Uniterm - Terminations for Polymeric Cables - up to 42kV
Uniterm - Terminations for Polymeric Cables - up to 42kV - Selection Guide
• IXSU/OXSU - EPKT Quick Reference Guide
Heat Shrinkable Elbows:
• EPKT:
Heat Shrinkable Termination System for cables up to 36kV
Heat Shrinkable Termination Selection Guide
• RSRB:
Inline Bushing Boots
• RSRB:
Right Angle Bushing Boots
Inline & Right Angle Bushing Boot Selection Guide
Push On Elbows:
• RCAB:
Elastomeric Flexible Bushing Boot - up to 17.5kV ONLY
• RCAB:
Inline Cold Applied Boot - up to 24kV ONLY
• RICS:
Insulated Elbow Adaptors - up to 24kV
Insulated Elbow Adaptors - up to 24kV - Selection Guide
• RSES/RSSS:
Insulated Screened Elbows - 250A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 24kV
• RSTI:
Insulated Screened Elbows - 630A - up to 36kV
• RSTI:
Insulated Screened Elbow - Piggyback Coupling System - up to 36kV
GURO MV: NEW
GUROFLEX Medium Voltage - Cold pour Insulating Compound
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) Raychem terminations for polymeric and MINDpaper insulated cables from 7.2 kV up to 36 kVSystem Designer EPKT- 17C3MOH3 B21 G43
1. Raychem terminations for polymeric and MIND
paper insulated cables from 7.2 kV up to 36 kV
System Designer
MOHD. BIN AHMED AKBAR TRADING EST.
(Electrical, Automation & Instrumentation)
Jeddah Street | P.O Box 30073 | Jubail 31951 | Kingdom of Saudi Arabia
Tel: 00966 (0) 13 3635225, 13 3618081 | Fax: 00966 (0) 13 363 3883 |
mail@akbartrading.com | www.akbartrading.com
2. Termination systems designer
This worksheet enables you to arrive at a part number for a Raychem
termination EPKT.
Choose one figure from the left-hand column of each table.
Voltage in kV
7 for 7.2 kV
17 for 12 kV & 17.5 kV
24 for 24 kV
36 for 36 kV
Size in mm2
7.2 kV 12 kV & 17.5 kV 24 kV 36 kV
A 16 - 50 16 - 25 - -
B 70 - 120 35 - 70 25 - 50 -
C 150 - 240 95 - 240 70 - 185 50 - 95
D 300 - 500 300 - 400 240 - 300 120 - 185
E 630 - 1000 500 - 800 400 - 630 240 - 500
F - 1000 800 - 1000 630 - 1000
No. of Cores
1 for single (1) core
3 for three (3) core
Dielectric of insulation type
X for PLASTIC eg. XLPE, EPDM, EPR, etc.
M for MIND non-draining paper (not applicable for draining paper cables)
Location of the termination
I for INDOOR
O for OUTDOOR
Length (only 3-core) of the terminated portion (tail)
H1 for 450 mm long
H2 for 650 mm long (min for 17.5 kV outdoor & 36 kV indoor)
H3 for 800 mm long (min for 24 kV outdoor & 36 kV outdoor)
H4 for 1200 mm long
Typical part number:
EPKT- 17C3MOH3 B21 G43
Voltage (Umax)
Cable size
Number of cores
Dielectric
Location
Length (3-core-cables)
Accessories
3. Armour Earthing
Wire armour in paper or plastic cables
can be effectively terminated to earth
by means of mechanical clamping rings.
Heat-shrinkable tubing for corrosion
protection and an insulated copper
conductor for earth connection are
also included.
The kits can be ordered separately or
with the termination by adding the
mod code to the end of the part
number.
1-core cables
Diameter Application Range (mm2
) Part Number Mod Code
Range (mm) 7.2 kV 12 kV 17.5 kV 24 kV 36 kV
21 - 32 16 - 70 16 - 70 16 - 50 16 - 50 - EAKT 1636 G 36
33 - 50 95 - 400 95 - 400 70 - 400 70 - 300 16 - 185 EAKT 1637 G 37
51 - 67 500 - 800 500 - 800 500 - 800 400 - 800 240 - 630 EAKT 1638 G 38
3-core cables
Diameter Application Range (mm2
) Part Number Mod Code
Range (mm) 7.2 kV 12 kV 17.5 kV 24 kV 36 kV
40 - 67 16 - 120 16 - 120 16 - 95 16 - 35 16 - 25 EAKT 1642 G 42
50 - 86 150 - 240 150 - 240 120 - 185 50 - 120 35 - 95 EAKT 1643 G 43
60 - 94 300 - 400 300 - 400 240 - 300 150 - 185 120 - 185 EAKT 1644 G 44
70 - 110 - - - 240 - 300 240 - 300 EAKT 1645 G 45
Cable Preparation Kit
Two types of cable preparation kits
are also available. The one for paper
cable contains cleaning solvent,
solder and binding wire.
The one for plastic cable contains
abrasive paper, string, cleaning tissues
and plastic gloves. These can only be
ordered along with terminations by
adding the mod code to the end of
the part number.
Application Mod Code
Paper cable E 01
Plastic cable E 02
4. Cable Glands
The Raychem cable gland is used with
a wide range of cable boxes designed
for compound filling where the
distance from bushing to base-plate
is a limiting factor. The gland is made
to match stud spacings to BS 2562.
It is also available with an insulating
plate for separate earthing and of
aluminium for single core applications.
These can be ordered separately as
complete kits or along with the
termination by adding the mod code
at the end of the part number.
Application Part Number Mod Code
Steel/Small/X-Type/cables up to 95 mm2
EAKT 1605 G 05
Steel/Large/Y-Type/cables up to 300 mm2
EAKT 1606 G 06
Steel/Large/Y-Type/with insulating plate EAKT 1607 G 07
Aluminium/Small/X-Type/1-core application EAKT 1608 G 08
Note:
The stud hole spacing in the small gland is 66 mm x 66 mm and in the large gland is 86 mm x 95 mm.
Solderless Earth Connection
Copper tape screens on plastic cables
can be earthed mechanically by using
Raychem's solderless earth connection
system. The kit comes complete with a
tinned copper earthing braid and a
mechanical roll spring for each phase.
These can be ordered separately as
kits or with the termination by adding
the mod code to the end of the part
number.
Diameter over Application Range (mm2
) Part Number Mod Code
Screen (mm) 7.2 kV 12 kV 17.5 kV 24 kV 36 kV
12 - 18 16 - 50 16 - 50 16 - 25 - - EAKT 1655 G 55
19 - 24 70 - 150 70 - 150 35 - 95 25 - 70 25 - 35 EAKT 1656 G 56
25 - 30 185 - 300 185 - 240 120 - 185 95 - 150 50 - 70 EAKT 1657 G 57
31 - 44 400 - 630 300 - 630 240 - 500 185 - 500 95 - 300 EAKT 1658 G 58
41 - 65 800 - 1000 800 - 1000 630 - 1000 630 - 1000 400 - 1000 EAKT 1659 G 59
Note:
Solderless earth connections are also available for lead sheaths on paper cables. For such requirements please contact your
local sales representative.
5. Boots
Insulating boots are moulded parts
which are shrunk over the connection
between the cable lug and bushing
to insulate them. They are used in
switchgear and transformers with
compound filled boxes where the
clearances are insufficient for
operation in air or to protect against
flash over due to rodents or extreme
humidity.
A full range of insulating boots are
available up to 17.5 kV. These can be
ordered separately by quoting the
part number or with the termination
by adding a mod code to the end.
Example:
EPKT-17C3MOH3-B07
This kit comes complete with straight
boots.
Application range Straight boots Right angle boots - long Right angle boots - short
Mod Code Part Number Mod Code Part Number Mod Code Part Number
10 - 35 mm2
B05 RSRB 4022 B08 RSRB 4042 B15 RSRB 4062
50 - 95 mm2
B06 RSRB 4024 B09 RSRB 4044 B16 RSRB 4064
120 - 300 mm2
B07 RSRB 4026 B10 RSRB 4046 B17 RSRB 4066
Note:
1. Long boots are 110 mm long over the bushing. The short boots are 90 mm long.
2. Insulating boot kits are also available for up to 36 kV applications.
For such requirements please refer to your local sales representative.
Support Insulators and Bracket
We also manufacture a range of
hybrid insulators. The sheds of red,
non tracking, flexible polymeric mate-
rial are mounted on a porcelain core.
Sets of three, along with a galvanised
steel T-bracket, can be ordered for
applications up to 36 kV either as
separate kits by quoting the part
number or with the termination by
adding the mod code to the end.
Reference standard IEC 60815,
IEC 60071
Part Number Mod Code Description
(pollution level IV) (pollution level III) (pollution level II) (pollution level I)
EAKT 1521 B 21 Insulator Kits 12 kV Insulator Kits 17.5 kV Insulator Kits 24 kV
EAKT 1523 B 23 Insulator Kits 17.5 kV Insulator Kits 24 kV Insulator Kits 36 kV
EAKT 1524 B 24 Insulator Kits 24 kV
Insulator Kits 36 kV
Note:
The voltage is the highest phase-to-phase voltage Umax
6. T-adapter for perpendicular connection
of the termination to SF6-insulated
switchgear
T-adapter for perpendicular connection
of termination and surge arrester to
SF6-insulated switchgear
Straight adapter for vertical connection
of the termination to SF6-insulated
switchgear
Raychem insulated adapter termination system RICS
for SF6-insulated switchgear up to 24 kV
T-adapter
The insulated adapter termination
system provides perfect sealing,
electrical insulation and an electrical
connection between Raychem termi-
nations and SF6-insulated switchgear
up to 24 kV.
Its lead-in insulator (630 A) conforms
to DIN 47636 and ANSI IEEE 386.
The cable box of the switchgear must
be provided with suitable protection
against electric shock. The insulating
adapter is compatible with all Raychem
terminations. Details of the terminations
can be found in the cable accessories
catalogue.
The insulating body, fixing bolts,
terminal stud and backplug are
supplied in a 3-phase set complete
with installation instruction. Cable
lugs and terminations are not included.
For double T-connections, the second
adapter is of special design and
includes connection plug, insulating
body, fixing bolts, terminal stud and
backplug. It can be combined with
first Raychem adapters of type
RICS-57x3-CU with M16 lugs, but not
with Raychem adapter for surge
arresters type RICS-51x9.
Straight adapter
A thick walled, heat-shrinkable
insulating sleeve provides a
hermetic seal over the cone of
the bushing and the termination.
The adapter area is smoothed
with a meltable filler strip.
Scope of supply (for three phases)
Heat-shrinkable insulating sleeving,
filler strip, small accessories and
installation instructions. Terminal
stud and lug must be enclosed.
T-adapter with surge arrester
Thick walled insulator made of high
quality elastomer with sealing face
over the termination, bushing cone
and plug.
The electrical connection is made with
a terminal stud and the cable lug of the
termination. Two cable connection is
possible. A special plug which allows
cable testing without disconnecting
the adapter is also offered. The design
of the adapter for connecting the
surge arrester is basically identical. The
elastomer insulator has an additional
lead-in duct for the surge arrester.
Details of the surge arresters can be
found in the brochure EPP 0533.
Scope of supply (for three phases)
Insulator, plug, terminal stud, small
accessories and installation instructions.
7. Raychem insulated adapter termination system RICS
for SF6-insulated switchgear up to 24 kV
Raychem RICS T-adapter
Voltage class Cable type Application range Type of indoor Part Number
(U0 / U (Um)kV (mm2
) termination
6.35 / 11 (12)kV Polymeric 1C & 3C 25 to 50 IXSU-F, POLT, EPKT, TFTI RICS 5113
70 to 150 RICS 5123
185 to 240 RICS 5133
300 RICS 5143
8.7 / 15 (17,5)kV Polymeric 1C & 3C 25 to 35 IXSU-F, POLT, EPKT, TFTI RICS 5113
50 to 95 RICS 5123
120 to 185 RICS 5133
240 to 300 RICS 5143
12.7 / 22 (24)kV Polymeric 1C & 3C 10 to 70 IXSU-F, POLT, EPKT, TFTI RICS 5123
95 to 185 RICS 5133
240 to 300 RICS 5143
6.35 / 11 (12)kV Paper (MI and MIND) 35 EPKT-45xx RICS 5113
Belted 50 to 95 RICS 5123
120 to 185 RICS 5133
240 RICS 5143
6.35 / 11 (12)kV Paper (MI and MIND) 35 to 70 EPKT RICS 5113
Screened or belted 95 to 150 RICS 5123
185 to 240 RICS 5133
300 RICS 5143
Raychem RICS T-adapter with Surge Arrester
Voltage class Cable type Application range Type of indoor Part Number
(U0 / U (Um)kV (mm2
) termination
6.35 / 11 (12)kV Polymeric 1C & 3C NA IXSU-F, POLT, EPKT, TFTI
NA
185 to 240 RICS 5139
300 RICS 5149
8.7 / 15 (17,5)kV Polymeric 1C & 3C NA IXSU-F, POLT, EPKT, TFTI
NA
120 to 185 RICS 5139
240 to 300 RICS 5149
12.7 / 22 (24)kV Polymeric 1C & 3C NA IXSU-F, POLT, EPKT, TFTI
95 to 185 RICS 5139
240 to 300 RICS 5149
6.35 / 11 (12)kV Paper (MI and MIND) NA EPKT-45xx
Belted NA
120 to 185 RICS 5139
240 RICS 5149
6.35 / 11 (12)kV Paper (MI and MIND) NA EPKT
Screened or belted NA
185 to 240 RICS 5139
300 RICS 5149
Tests
The adapters meet Cenelec HD629.1S1,
IEC 540, VDE 0278 and ANSI IEEE 386
standards, as well as the Raychem
specification PPS 3013, in addition they
were type tested together with most
switchgear. The test requirements and
results are summarised in Raychem test
reports, which are available on request.