Nexans Euromold tee connectors are designed for terminating high voltage XLPE power cables into compact switchgear to make optimum use of limited installation space.
Nexans, the worldwide leader in the cable industry, has extended its well-proven range of compact high voltage (HV) connectors with two new tee-shaped connectors designed specifically for use with compact switchgear and transformers now being specified for wind turbine applications. The Nexans Euromold M430TB connector is for use with higher voltages (up to 33-36kV) and the M434TB connector is for higher currents (up to 1,250 A).
Trend Towards Compact Switchgear for Wind Turbines
The growing trend towards using ever more compact high voltage switchgear in wind turbines has resulted in smaller cable boxes, limiting the space available for connectors. Nexans has responded to this challenge by developing its new asymmetric tee-shape connectors to create a compact connection solution. This now enables two cables to be connected in the same space required for one cable using a traditional non-compact connector. As well as being ideal for all applications where space is a limiting factor, the Nexans compact connectors also enable users to increase the capacity of an existing installation.
EPDM Jacket: A Key Design Feature for Safety and Reliability
The Nexans Euromold M430TB and the M434TB are separable tee-shape bolted connectors designed to connect high voltage polymer-insulated cable to wind turbine equipment such as switchgear and transformers- they can also be used for cable to cable connections with the appropriate mating parts. A key design feature is the thick (3 mm) EPDM (Ethylene Propylene Diene Monomer) rubber conductive insulation jacket that provides a total safe to touch screen for personnel safety, this is both more reliable and longer lasting than the painted silicone rubber insulation used in many connectors.
700 Series Interface E Elastimold Cable Connectors and Bushings connect and terminate HV cables to Interface E bushings on switchgear and transformers. Elastimold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F. Elastimold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables. 700 Series Interface E, Elastimold Bushings * Bushing Voltage Range 33kV-36kV * Bushing Current Rating 800Amps & 1250Amps * Bushing Type 5/8" Bolted Aluminium Insert Elastimold separable elbow connectors are high voltage cable terminations used to connect polymeric (XLPE or EPR insulated) power cables to HV equipment including transformers, switchgear, capacitors and motors. 700 Series Connectors - 750LR Tee Connectors & 775LR Tee Connectors 800-1250Amps 35-630sqmm Slip on cable connectors - quick to install to high voltage switchgear and transformers (oil, air and gas insulated) Touchproof cable terminations - made from conductive EPDM rubber, fully screened HV termination for safety One part cable termination - built-in stress relief, insulation and outer semi-conductive layers Maintenance friendly - readily disconnectable cable connector for high voltage maintenance work Compact cable connectors - space-saving HV cable terminations for SF6 gas insulated switchgear (GIS) EPDM rubber cable connectors - resistant to ozone, corona, chemicals, water and atmospheric pollutants Flexibility - Elastimold cable connectors are disconnectable and re-useable. Re-use of the Elastimold high voltage cable connector permits site re-location of HV electrical equipment without requiring cable re-termination. HV High Voltage Cable Connectors, Specification - Elastimold dead-break separable cable connectors suit all international high voltage bushing interfaces for the termination of HV cable into switchgear, transformers and motors. Elastimold cable connectors terminate high voltage power cables (typically 11kV, 15kV, 24kV, 33kV, 36kV up to 52kV) into SF6 GIS gas insulated switchgear including Schneider, ABB, Areva and Siemens. Elastimold cable connectors meet the requirements of ANSI/IEEE 386 & 404 and CENELEC EN50180 & EN50181 for high voltage "dead-break" cable connection, i..e connectors installed and terminated onto un-energised high voltage power cable. US specification "load-break" cable connectors for high voltage energised cable termination are available. High Voltage Cable Connectors - Elastimold cable connectors (elbow and straight types) are specified to terminate XLPE or EPR insulated high voltage power cables with copper tape or copper wire screens up to 52kV. Elastimold cable connectors are available to suit and terminate lead covered HV cables for hydro-carbon industries (oil, gas, petrochemicals) with ATEX certification for hazardous area Zones 1 and Zones 2.
400 Series Interface B Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface B bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold separable elbow connectors are designed to terminate high voltage polymeric (XLPE EPR) screened (copper wire or copper tape) cables to CENELEC Interface Type B (400amp) bushings with 14mm plug-in pins, up to 33kV.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold straight plug connectors, Nexans Euromold bushings (air, oil and gas insulated switchgear) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Euromold Connectors 400 Series Interface Type B Bushing
* Connector Type : 14mm Plug-In Pin Contact
* Voltage Range : 11/12kV-33/36kV
* Current Rating : 400amps
* Specification : CENELEC EN50180 & EN50181
Euromold 400LR Elbow Connectors are used with 400 Series Interface B Bushing.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
700 Series Interface E Elastimold Cable Connectors and Bushings connect and terminate HV cables to Interface E bushings on switchgear and transformers. Elastimold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F. Elastimold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables. 700 Series Interface E, Elastimold Bushings * Bushing Voltage Range 33kV-36kV * Bushing Current Rating 800Amps & 1250Amps * Bushing Type 5/8" Bolted Aluminium Insert Elastimold separable elbow connectors are high voltage cable terminations used to connect polymeric (XLPE or EPR insulated) power cables to HV equipment including transformers, switchgear, capacitors and motors. 700 Series Connectors - 750LR Tee Connectors & 775LR Tee Connectors 800-1250Amps 35-630sqmm Slip on cable connectors - quick to install to high voltage switchgear and transformers (oil, air and gas insulated) Touchproof cable terminations - made from conductive EPDM rubber, fully screened HV termination for safety One part cable termination - built-in stress relief, insulation and outer semi-conductive layers Maintenance friendly - readily disconnectable cable connector for high voltage maintenance work Compact cable connectors - space-saving HV cable terminations for SF6 gas insulated switchgear (GIS) EPDM rubber cable connectors - resistant to ozone, corona, chemicals, water and atmospheric pollutants Flexibility - Elastimold cable connectors are disconnectable and re-useable. Re-use of the Elastimold high voltage cable connector permits site re-location of HV electrical equipment without requiring cable re-termination. HV High Voltage Cable Connectors, Specification - Elastimold dead-break separable cable connectors suit all international high voltage bushing interfaces for the termination of HV cable into switchgear, transformers and motors. Elastimold cable connectors terminate high voltage power cables (typically 11kV, 15kV, 24kV, 33kV, 36kV up to 52kV) into SF6 GIS gas insulated switchgear including Schneider, ABB, Areva and Siemens. Elastimold cable connectors meet the requirements of ANSI/IEEE 386 & 404 and CENELEC EN50180 & EN50181 for high voltage "dead-break" cable connection, i..e connectors installed and terminated onto un-energised high voltage power cable. US specification "load-break" cable connectors for high voltage energised cable termination are available. High Voltage Cable Connectors - Elastimold cable connectors (elbow and straight types) are specified to terminate XLPE or EPR insulated high voltage power cables with copper tape or copper wire screens up to 52kV. Elastimold cable connectors are available to suit and terminate lead covered HV cables for hydro-carbon industries (oil, gas, petrochemicals) with ATEX certification for hazardous area Zones 1 and Zones 2.
400 Series Interface B Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface B bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold separable elbow connectors are designed to terminate high voltage polymeric (XLPE EPR) screened (copper wire or copper tape) cables to CENELEC Interface Type B (400amp) bushings with 14mm plug-in pins, up to 33kV.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold straight plug connectors, Nexans Euromold bushings (air, oil and gas insulated switchgear) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Euromold Connectors 400 Series Interface Type B Bushing
* Connector Type : 14mm Plug-In Pin Contact
* Voltage Range : 11/12kV-33/36kV
* Current Rating : 400amps
* Specification : CENELEC EN50180 & EN50181
Euromold 400LR Elbow Connectors are used with 400 Series Interface B Bushing.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold Connectors & Bushing Interfaces
Euromold Connectors 200 Series Interface Type A Bushing
* Connector Type : 7.9mm Plug-In Pin Contact
* Voltage Range : 11/12kV-24kV
* Current Rating : 250amps
* Specification : CENELEC EN50180 & EN50181
Euromold 158LR Elbow Connectors are used with 200 Series Interface A Bushing.
400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
The Nexans Euromold compact version screened separable connector is suitable for high voltage HV cable termination up to 33kV. Interface Type C Euromold M16 bolted tee connectors up to 33kV are designed to connect and terminate polymeric (XLPE EPR) cables to M16 bolted 400 series equipment bushings. Nexans Euromold connectors are supplied in sets of three phases.
Nexans Euromold Kit Contents: 3 x connector housings, 3 x size sensitive cable reducers, 3 x conductor contact lug, 3 x clamping screws and 3 x insulating plugs & caps.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Euromold elbow connectors, Euromold tee connectors, Euromold bushings (oil insulated) and Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series, 400TB 440TB Features :
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
T&D UK with the support of Nexans provide installation training and certification for experienced high voltage cable jointers up to 33kV.
200 Series Interface A Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface A bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
900 Series Interface F Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface F bushings on switchgear and transformers up to 42kV. Nexans 944TB Tee Connectors provide high voltage cable terminations using separable tee shape connectors :
Nexans 944TB/G - 12kV 2500Amp 70-80sqmm Conductors
Nexans K944TB/G - 24kV 2500Amp 16-800sqmm Conductors
Nexans M944TB/G - 36kV 2500Amp 35-800sqmm Conductors
Nexans P944TB/G - 42kV 1250Amp 50-800sqmm Conductors
400 Series Interface C Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold Connectors & Bushing Interfaces
Euromold Connectors 200 Series Interface Type A Bushing
* Connector Type : 7.9mm Plug-In Pin Contact
* Voltage Range : 11/12kV-24kV
* Current Rating : 250amps
* Specification : CENELEC EN50180 & EN50181
Euromold 158LR Elbow Connectors are used with 200 Series Interface A Bushing.
400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
The Nexans Euromold compact version screened separable connector is suitable for high voltage HV cable termination up to 33kV. Interface Type C Euromold M16 bolted tee connectors up to 33kV are designed to connect and terminate polymeric (XLPE EPR) cables to M16 bolted 400 series equipment bushings. Nexans Euromold connectors are supplied in sets of three phases.
Nexans Euromold Kit Contents: 3 x connector housings, 3 x size sensitive cable reducers, 3 x conductor contact lug, 3 x clamping screws and 3 x insulating plugs & caps.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Euromold elbow connectors, Euromold tee connectors, Euromold bushings (oil insulated) and Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series, 400TB 440TB Features :
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
T&D UK with the support of Nexans provide installation training and certification for experienced high voltage cable jointers up to 33kV.
200 Series Interface A Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface A bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
900 Series Interface F Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface F bushings on switchgear and transformers up to 42kV. Nexans 944TB Tee Connectors provide high voltage cable terminations using separable tee shape connectors :
Nexans 944TB/G - 12kV 2500Amp 70-80sqmm Conductors
Nexans K944TB/G - 24kV 2500Amp 16-800sqmm Conductors
Nexans M944TB/G - 36kV 2500Amp 35-800sqmm Conductors
Nexans P944TB/G - 42kV 1250Amp 50-800sqmm Conductors
400 Series Interface C Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold Connectors Interface D 600 Series
Nexans Euromold 675LR Connector
1250A 11kV Dead Break Connectors 35-800sqmm
Nexans Euromold 675LR connector suits 11kV/12kV polymeric insulated cables (XLPE EPR), rated up to 1250amps with copper or aluminium conductors 35-800sqmm.
Interface type D Nexans Euromold 5/8" bolted tee connector, for high voltage cable connecting and termination applications up to 24kV. 1250amp (copper stud) application separable connector is designed to connect polymeric (XLPE EPR) cables to a 5/8" copper, 600 series bushings.
Nexans Euromold Connectors Interface D 600 Series
Nexans Euromold 650LR Connector
800A 11kV Dead Break Connectors 35-630sqmm
Interface type D Nexans Euromold 5/8" bolted tee connector, for high voltage cable connecting and termination applications up to 24kV. 800amp (aluminium stud) application separable connector is designed to connect polymeric (XLPE EPR) cables to a 5/8" aluminium stud, 600 series bushings.
Nexans Euromold K650LR connector suits 24kV polymeric insulated cables (XLPE EPR), rated up to 800amps with copper or aluminium conductors 35-630sqmm.
Interface type D Nexans Euromold 5/8" bolted tee connector, for high voltage cable connecting and termination applications up to 24kV. 800amp (aluminium stud) application separable Nexans Euromold connector is designed to connect polymeric (XLPE EPR) cables to a 5/8" aluminium stud, 600 series bushings.
Nexans Euromold 600 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV and 24kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 600 series separable connectors include Nexans Euromold bolted tee connectors and Nexans Euromold bushings (oil and air insulated) for electrical equipment up to 24kV - 1250A. Nexans Euromold 600 series connectors are specified to terminate and connect polymeric (XLPE or EPR) screened (copper tape and wire) cables to ANSI-style Interface Type D (800amp) bushings with either copper or aluminium 5/8" bolted connection.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 200 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV and 24kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold separable elbow connectors are designed to terminate high voltage polymeric (XLPE EPR) screened (copper wire or copper tape) cables to CENELEC Interface Type A (250amp) bushings with 7.9mm plug-in pins, 11kV-24kV.
Nexans Euromold 200 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold straight plugs, Nexans Euromold bushings (air, oil and gas insulated switchgear) and Nexans Euromold surge arresters to protect 11kV-24kV electrical equipment.
Isolation Procedures for Safe Working on Electrical Systems and Equipment by the JIB | solation Procedures for Safe Working on Electrical Systems and Equipment
This chart shows the safe isolation procedure that you should use when working on electrical systems and equipment.
You'll receive a printed copy of this from your Training Provider, but it's also here as a handy reference to keep electronically.
THE RULES OF SAFE ISOLATION ARE:
Obtain permission to start work (a Permit may be required in some situations)
Identify the source(s) of supply using an approved voltage indicator or test lamp
Prove that the approved voltage indicator or test lamp is functioning correctly
Isolate the supply(s)
Secure the isolation
Prove the system/equipment is DEAD using an approved voltage indicator or test lamp
Prove that the approved voltage indicator or test lamp is functioning correctly
Put up warning signs to tell other people that the electrical installation has been isolated
Once the system/equipment is proved DEAD, work can begin
Uploaded by THORNE & DERRICK LV HV Jointing, Earthing, Substation & Electrical Eqpt | Explosive Atmosphere Experts & ATEX IECEx.
THORNE & DERRICK based in the UK are international distributors of LV, MV & HV Cable Installation, Jointing, Substation & Electrical Equipment.
Since 1985, T&D have established an international reputation based on SERVICE | INTEGRITY | TRUST.
Contact us for 3M, ABB, Alroc, AN Wallis, CATU, Cembre, Centriforce, CMP, CSD, Elastimold, Ellis Patents, Emtelle, Euromold, Filoform , Furse, Lucy Electric & Zodion, Nexans, Pfisterer, Polypipe, Prysmian, Roxtec, Sicame, WT Henley.
"𝑩𝑬𝑮𝑼𝑵 𝑾𝑰𝑻𝑯 𝑻𝑱 𝑰𝑺 𝑯𝑨𝑳𝑭 𝑫𝑶𝑵𝑬"
𝐓𝐉 𝐂𝐨𝐦𝐬 (𝐓𝐉 𝐂𝐨𝐦𝐦𝐮𝐧𝐢𝐜𝐚𝐭𝐢𝐨𝐧𝐬) is a professional event agency that includes experts in the event-organizing market in Vietnam, Korea, and ASEAN countries. We provide unlimited types of events from Music concerts, Fan meetings, and Culture festivals to Corporate events, Internal company events, Golf tournaments, MICE events, and Exhibitions.
𝐓𝐉 𝐂𝐨𝐦𝐬 provides unlimited package services including such as Event organizing, Event planning, Event production, Manpower, PR marketing, Design 2D/3D, VIP protocols, Interpreter agency, etc.
Sports events - Golf competitions/billiards competitions/company sports events: dynamic and challenging
⭐ 𝐅𝐞𝐚𝐭𝐮𝐫𝐞𝐝 𝐩𝐫𝐨𝐣𝐞𝐜𝐭𝐬:
➢ 2024 BAEKHYUN [Lonsdaleite] IN HO CHI MINH
➢ SUPER JUNIOR-L.S.S. THE SHOW : Th3ee Guys in HO CHI MINH
➢FreenBecky 1st Fan Meeting in Vietnam
➢CHILDREN ART EXHIBITION 2024: BEYOND BARRIERS
➢ WOW K-Music Festival 2023
➢ Winner [CROSS] Tour in HCM
➢ Super Show 9 in HCM with Super Junior
➢ HCMC - Gyeongsangbuk-do Culture and Tourism Festival
➢ Korean Vietnam Partnership - Fair with LG
➢ Korean President visits Samsung Electronics R&D Center
➢ Vietnam Food Expo with Lotte Wellfood
"𝐄𝐯𝐞𝐫𝐲 𝐞𝐯𝐞𝐧𝐭 𝐢𝐬 𝐚 𝐬𝐭𝐨𝐫𝐲, 𝐚 𝐬𝐩𝐞𝐜𝐢𝐚𝐥 𝐣𝐨𝐮𝐫𝐧𝐞𝐲. 𝐖𝐞 𝐚𝐥𝐰𝐚𝐲𝐬 𝐛𝐞𝐥𝐢𝐞𝐯𝐞 𝐭𝐡𝐚𝐭 𝐬𝐡𝐨𝐫𝐭𝐥𝐲 𝐲𝐨𝐮 𝐰𝐢𝐥𝐥 𝐛𝐞 𝐚 𝐩𝐚𝐫𝐭 𝐨𝐟 𝐨𝐮𝐫 𝐬𝐭𝐨𝐫𝐢𝐞𝐬."
Accpac to QuickBooks Conversion Navigating the Transition with Online Account...PaulBryant58
This article provides a comprehensive guide on how to
effectively manage the convert Accpac to QuickBooks , with a particular focus on utilizing online accounting services to streamline the process.
Buy Verified PayPal Account | Buy Google 5 Star Reviewsusawebmarket
Buy Verified PayPal Account
Looking to buy verified PayPal accounts? Discover 7 expert tips for safely purchasing a verified PayPal account in 2024. Ensure security and reliability for your transactions.
PayPal Services Features-
🟢 Email Access
🟢 Bank Added
🟢 Card Verified
🟢 Full SSN Provided
🟢 Phone Number Access
🟢 Driving License Copy
🟢 Fasted Delivery
Client Satisfaction is Our First priority. Our services is very appropriate to buy. We assume that the first-rate way to purchase our offerings is to order on the website. If you have any worry in our cooperation usually You can order us on Skype or Telegram.
24/7 Hours Reply/Please Contact
usawebmarketEmail: support@usawebmarket.com
Skype: usawebmarket
Telegram: @usawebmarket
WhatsApp: +1(218) 203-5951
USA WEB MARKET is the Best Verified PayPal, Payoneer, Cash App, Skrill, Neteller, Stripe Account and SEO, SMM Service provider.100%Satisfection granted.100% replacement Granted.
Enterprise Excellence is Inclusive Excellence.pdfKaiNexus
Enterprise excellence and inclusive excellence are closely linked, and real-world challenges have shown that both are essential to the success of any organization. To achieve enterprise excellence, organizations must focus on improving their operations and processes while creating an inclusive environment that engages everyone. In this interactive session, the facilitator will highlight commonly established business practices and how they limit our ability to engage everyone every day. More importantly, though, participants will likely gain increased awareness of what we can do differently to maximize enterprise excellence through deliberate inclusion.
What is Enterprise Excellence?
Enterprise Excellence is a holistic approach that's aimed at achieving world-class performance across all aspects of the organization.
What might I learn?
A way to engage all in creating Inclusive Excellence. Lessons from the US military and their parallels to the story of Harry Potter. How belt systems and CI teams can destroy inclusive practices. How leadership language invites people to the party. There are three things leaders can do to engage everyone every day: maximizing psychological safety to create environments where folks learn, contribute, and challenge the status quo.
Who might benefit? Anyone and everyone leading folks from the shop floor to top floor.
Dr. William Harvey is a seasoned Operations Leader with extensive experience in chemical processing, manufacturing, and operations management. At Michelman, he currently oversees multiple sites, leading teams in strategic planning and coaching/practicing continuous improvement. William is set to start his eighth year of teaching at the University of Cincinnati where he teaches marketing, finance, and management. William holds various certifications in change management, quality, leadership, operational excellence, team building, and DiSC, among others.
Putting the SPARK into Virtual Training.pptxCynthia Clay
This 60-minute webinar, sponsored by Adobe, was delivered for the Training Mag Network. It explored the five elements of SPARK: Storytelling, Purpose, Action, Relationships, and Kudos. Knowing how to tell a well-structured story is key to building long-term memory. Stating a clear purpose that doesn't take away from the discovery learning process is critical. Ensuring that people move from theory to practical application is imperative. Creating strong social learning is the key to commitment and engagement. Validating and affirming participants' comments is the way to create a positive learning environment.
[Note: This is a partial preview. To download this presentation, visit:
https://www.oeconsulting.com.sg/training-presentations]
Sustainability has become an increasingly critical topic as the world recognizes the need to protect our planet and its resources for future generations. Sustainability means meeting our current needs without compromising the ability of future generations to meet theirs. It involves long-term planning and consideration of the consequences of our actions. The goal is to create strategies that ensure the long-term viability of People, Planet, and Profit.
Leading companies such as Nike, Toyota, and Siemens are prioritizing sustainable innovation in their business models, setting an example for others to follow. In this Sustainability training presentation, you will learn key concepts, principles, and practices of sustainability applicable across industries. This training aims to create awareness and educate employees, senior executives, consultants, and other key stakeholders, including investors, policymakers, and supply chain partners, on the importance and implementation of sustainability.
LEARNING OBJECTIVES
1. Develop a comprehensive understanding of the fundamental principles and concepts that form the foundation of sustainability within corporate environments.
2. Explore the sustainability implementation model, focusing on effective measures and reporting strategies to track and communicate sustainability efforts.
3. Identify and define best practices and critical success factors essential for achieving sustainability goals within organizations.
CONTENTS
1. Introduction and Key Concepts of Sustainability
2. Principles and Practices of Sustainability
3. Measures and Reporting in Sustainability
4. Sustainability Implementation & Best Practices
To download the complete presentation, visit: https://www.oeconsulting.com.sg/training-presentations
India Orthopedic Devices Market: Unlocking Growth Secrets, Trends and Develop...Kumar Satyam
According to TechSci Research report, “India Orthopedic Devices Market -Industry Size, Share, Trends, Competition Forecast & Opportunities, 2030”, the India Orthopedic Devices Market stood at USD 1,280.54 Million in 2024 and is anticipated to grow with a CAGR of 7.84% in the forecast period, 2026-2030F. The India Orthopedic Devices Market is being driven by several factors. The most prominent ones include an increase in the elderly population, who are more prone to orthopedic conditions such as osteoporosis and arthritis. Moreover, the rise in sports injuries and road accidents are also contributing to the demand for orthopedic devices. Advances in technology and the introduction of innovative implants and prosthetics have further propelled the market growth. Additionally, government initiatives aimed at improving healthcare infrastructure and the increasing prevalence of lifestyle diseases have led to an upward trend in orthopedic surgeries, thereby fueling the market demand for these devices.
Explore our most comprehensive guide on lookback analysis at SafePaaS, covering access governance and how it can transform modern ERP audits. Browse now!
Affordable Stationery Printing Services in Jaipur | Navpack n PrintNavpack & Print
Looking for professional printing services in Jaipur? Navpack n Print offers high-quality and affordable stationery printing for all your business needs. Stand out with custom stationery designs and fast turnaround times. Contact us today for a quote!
Attending a job Interview for B1 and B2 Englsih learnersErika906060
It is a sample of an interview for a business english class for pre-intermediate and intermediate english students with emphasis on the speking ability.
Skye Residences | Extended Stay Residences Near Toronto Airportmarketingjdass
Experience unparalleled EXTENDED STAY and comfort at Skye Residences located just minutes from Toronto Airport. Discover sophisticated accommodations tailored for discerning travelers.
Website Link :
https://skyeresidences.com/
https://skyeresidences.com/about-us/
https://skyeresidences.com/gallery/
https://skyeresidences.com/rooms/
https://skyeresidences.com/near-by-attractions/
https://skyeresidences.com/commute/
https://skyeresidences.com/contact/
https://skyeresidences.com/queen-suite-with-sofa-bed/
https://skyeresidences.com/queen-suite-with-sofa-bed-and-balcony/
https://skyeresidences.com/queen-suite-with-sofa-bed-accessible/
https://skyeresidences.com/2-bedroom-deluxe-queen-suite-with-sofa-bed/
https://skyeresidences.com/2-bedroom-deluxe-king-queen-suite-with-sofa-bed/
https://skyeresidences.com/2-bedroom-deluxe-queen-suite-with-sofa-bed-accessible/
#Skye Residences Etobicoke, #Skye Residences Near Toronto Airport, #Skye Residences Toronto, #Skye Hotel Toronto, #Skye Hotel Near Toronto Airport, #Hotel Near Toronto Airport, #Near Toronto Airport Accommodation, #Suites Near Toronto Airport, #Etobicoke Suites Near Airport, #Hotel Near Toronto Pearson International Airport, #Toronto Airport Suite Rentals, #Pearson Airport Hotel Suites
Memorandum Of Association Constitution of Company.pptseri bangash
www.seribangash.com
A Memorandum of Association (MOA) is a legal document that outlines the fundamental principles and objectives upon which a company operates. It serves as the company's charter or constitution and defines the scope of its activities. Here's a detailed note on the MOA:
Contents of Memorandum of Association:
Name Clause: This clause states the name of the company, which should end with words like "Limited" or "Ltd." for a public limited company and "Private Limited" or "Pvt. Ltd." for a private limited company.
https://seribangash.com/article-of-association-is-legal-doc-of-company/
Registered Office Clause: It specifies the location where the company's registered office is situated. This office is where all official communications and notices are sent.
Objective Clause: This clause delineates the main objectives for which the company is formed. It's important to define these objectives clearly, as the company cannot undertake activities beyond those mentioned in this clause.
www.seribangash.com
Liability Clause: It outlines the extent of liability of the company's members. In the case of companies limited by shares, the liability of members is limited to the amount unpaid on their shares. For companies limited by guarantee, members' liability is limited to the amount they undertake to contribute if the company is wound up.
https://seribangash.com/promotors-is-person-conceived-formation-company/
Capital Clause: This clause specifies the authorized capital of the company, i.e., the maximum amount of share capital the company is authorized to issue. It also mentions the division of this capital into shares and their respective nominal value.
Association Clause: It simply states that the subscribers wish to form a company and agree to become members of it, in accordance with the terms of the MOA.
Importance of Memorandum of Association:
Legal Requirement: The MOA is a legal requirement for the formation of a company. It must be filed with the Registrar of Companies during the incorporation process.
Constitutional Document: It serves as the company's constitutional document, defining its scope, powers, and limitations.
Protection of Members: It protects the interests of the company's members by clearly defining the objectives and limiting their liability.
External Communication: It provides clarity to external parties, such as investors, creditors, and regulatory authorities, regarding the company's objectives and powers.
https://seribangash.com/difference-public-and-private-company-law/
Binding Authority: The company and its members are bound by the provisions of the MOA. Any action taken beyond its scope may be considered ultra vires (beyond the powers) of the company and therefore void.
Amendment of MOA:
While the MOA lays down the company's fundamental principles, it is not entirely immutable. It can be amended, but only under specific circumstances and in compliance with legal procedures. Amendments typically require shareholder
3. Nexans Network Solutions
Div. Euromold
COMPANY PRESENTATION
EUROMOLD
International standards
Euromold is the leading
European specialised designer,
manufacturer and distributor
of prefabricated cable
accessories for medium voltage
energy distribution. Euromold
provides a complete range of
accessories for underground
cables: premoulded EPDM
rubber connectors for cables
and epoxy bushings for
transformers and switchgear, as
well as a large range of coldshrinkable terminations and
joints from 12 to 42 kV.
Euromold is also the
manufacturer of electrical
components for the high
voltage accessories of the
Nexans group.
All our products meet the
International standards like
CENELEC HD 629.1, CENELEC
EN 50180, IEC 60137, IEC
60502-4… or country specifications. Official certificates,
CESI, KEMA, ATEX… prove the
conformity of our products.
Long duration tests of existing
or new products are continuously performed in our test
fields.
ISO 9001 Certificate
Since 1992, Euromold’s
commitment to quality is
demonstrated by its ISO 9001
certification.
Laboratory accreditation
Since June 2000, Euromold’s
independent ELAB laboratory
obtained the BELAC
accreditation no.144-TEST
conform with the European
standards for laboratories ISO
17025 for electrical testing of
low and medium voltage cable
accessories according to the
international standards
EN 50393, IEC 60502-4, IEC
61442 and HD 629.
08/2011
While every care is taken to ensure that the information contained
in this publication is correct, no legal responsibility can be accepted
for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold
reserves the right to alter or modify the characteristics of its products
described in this catalogue as standards and technology evolve.
1
4. SEPARABLE CONNECTORS
INTERFACE C
Table of contents
Interface C1 & C2
430TB - tee connector
484TB - tee connector
300PBM - coupling connector
430TBM-P2/P3 - dual/triple cable arrangement
804PB - coupling connector
300SA - surge arrester
800SA - surge arrester
400TR and 800TR - test rod
400TK and 400SW installation tools
Accessories
Possible arrangements
Dimensions according to
European CENELEC EN 50180
and 50181 (in mm).
Dia. 56±0.2
Dia. 46±0.2
Dia. 22 min for C1
Dia. 32 nominal for C2
M16 x 2 - 6H
0
1.5 -0.5
29
min.
90±0.2
08/2011
11
min.
Dia. 70±0.2
2
6. 430TB
INTERFACE C
TEE CONNECTOR
Application
Technical characteristics
Separable tee shape
connector (bolted type)
designed to connect polymeric
insulated cable to equipment
(transformers, switchgear,
motors, ...).
Also connects cable to cable
when using the appropriate
mating parts.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Up to 36 kV
630 A (800 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
185 mm
Design
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C interface as
described by CENELEC
EN 50180 and 50181.
5. Conductor connector.
6. Basic insulating plug (with
VD point).
7. Cable reducer.
8. Conductive rubber cap.
9. Clamping screw.
0. Earthing lead.
1
4
9
8
5
6
1
290 mm
(350 mm
for 36 kV)
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
2
3
10
Specifications and
standards
The 430TB separable connector
meets the requirements of
CENELEC HD 629.1.
7
Current Ir (A)
08/2011
Separable
connector
type
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an appropriate equipment
bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact
430TB/G
K430TB/G
M430TB/G
12
24
36
630
630
630
800
800
800
Conductor sizes (mm2)
min
max
35
35
50
300
300
240
4
7. Kit contents
The kit also comprises silicone grease, field
control mastic, installation rod, installation
instructions and crimp chart.
The complete (K)(M)430TB/G
tee connector kit comprises 3 x
the following components:
Conductor
contact TMBC-X
Table W
Ordering
part number
Voltage
(Um)
(kV)
3 x 430TB/G-11-X
3 x 430TB/G-16-X
3 x 430TB/G-18-X
min
max
12
12
12
12.0
17.0
19.0
17.5
23.5
32.6
3 x K430TB/G-11-X
3 x K430TB/G-16-X
3 x K430TB/G-18-X
24
24
24
12.0
17.0
19.0
17.5
23.5
32.6
3 x M430TB/G-11-X
3 x M430TB/G-15-X
3 x M430TB/G-19-X
3 x M430TB/G-22-X
3 x M430TB/G-25-X
3 x M430TB/G-27-X
36
36
36
36
36
36
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
Table X
35
50
70
95
120
150
185
240
300
Order: Kit MT.
For use with Alupe or
C 33-226 cables.
Please contact our
representative.
35KM-10-1
50(K)M-10-1
70(K)M-10-1
95(K)M-10-1
120(K)M-10-1
150(K)M-10-1
185(K)M-10-1
240(K)M-10-1
–
DIN
hexagonal
Deep
indent
35(K)M-10-2
50(K)M-10-2
70(K)M-10-2
95(K)M-10-2
120(K)M-10-2
150(K)M-10-2
185(K)M-10-2
240(K)M-10-2
300(K)M-10-2
Copper
conductor
Bolted
DIN
hexagonal
For use with
easy strip semi-conductive
screened cables. Order:
Field control mastic
(type MFC).
Aluminium and
copper conductor
Aluminium conductor
Conductor
sizes (mm2)
For use with
copper tape
screened cables.
Dia. over core insulation (mm)
For use with
other cable types.
Please contact our
representative.
For applications
outdoors and in
humid climate.
Order: +MWS.
120.300-12-5
Example:
The cable is 24 kV, 150 mm2
compact stranded copper with
a diameter over core insulation
of 27.5 mm.
Order 3 x
K430TB/G-18-95.240-14-5
tee connector kit.
(411CA-W
for 36 kV)
95.240-14-5
To order the tee connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Conductor
contact TBC-X
Cable reducer
430CA-W
50.150-14-5
Ordering instructions
Basic insulating
plug
(K)(M)300BIPA +
rubber cap
16.95-14-5
Connector housing
(K)(M)430BT/G
Clamping
screw
430TCS
3 x (K)(M)430TB/G-W-X
connector kit
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
When installed on an
appropriate equipment
bushing:
800 A continuously
5
8. 484TB
INTERFACE C
TEE CONNECTOR
Application
Separable tee shape
connector (bolted type)
designed to connect polymeric
insulated cable to equipment
(transformers, switchgear,
motors, ...).
Also connects cable to cable
when using the appropriate
mating parts.
Up to 42 kV
630 A (1250 A)
Technical characteristics
• The thick conductive EPDM
jacket provides a total safe to
touch screen which ensures
safety for personnel.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20.8/36 (42) kV
Design
185 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C - interface as
described by CENELEC
EN 50180 and 50181.
5. Conductor connector.
6. Basic insulating plug (with
VD point).
7. Cable reducer.
8. Conductive rubber cap.
9. Clamping screw.
0. Earthing lead.
1
4
9
8
5
6
1
2
360 mm
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
3
10
Specifications and
standards
7
The 484TB separable connector
meets the requirements of
CENELEC HD 629.1.
08/2011
Separable
connector
type
484TB/G
K484TB/G
M484TB/G
P484TB/G
Current
Ir (A)
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an
appropriate equipment bushing
min
max
12
24
36
42
630
630
630
630
1250
1250
1250
1250
50
35
35
35
630
630
630
630
Conductor sizes (mm2)
6
9. Kit contents
The complete (K)(M)(P)484TB/G
tee connector kit comprises 3x
the following components:
The kit also comprises silicone grease, field
control mastic, gloves, roll adhesive tape,
installation instructions and crimp chart.
Conductor
contact TMBC-X
Connector housing
(K)(M)(P)484BT/G
Clamping
screw
430TCS
Ordering instructions
To order the tee connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Add a 'K' for use up to 24 kV,
add an 'M' for use up to 36 kV,
add a 'P' for use up to 42 kV.
Example:
The copper wire screened cable
is 36 kV, 240 mm2 stranded
aluminium with a diameter over
core insulation of 37.0 mm.
Order 3 x
M484TB/G-32-240(K)M-12-2
tee connector kit.
(K)(M)(P)484TB/G-W-X
connector kit
Basic insulating
plug
(K)(M)(P)800BIPA
+ rubber cap
Conductor
contact TBC-X
Cable reducer
611CA-W
Table W
Dia. over core insulation (mm)
Ordering
part number
min
16.0
20.0
23.5
28.5
34.0
39.0
45.5
3 x 484TB/G-15-X
3 x 484TB/G-19-X
3 x 484TB/G-22-X
3 x 484TB/G-27-X
3 x 484TB/G-32-X
3 x 484TB/G-37-X
3 x 484TB/G-43-X
max
22.0
26.5
31.0
37.5
42.5
48.5
56.0
Table X
Conductor sizes
(mm2)
Aluminium conductor
Aluminium and
copper conductor
Copper
conductor
Bolted
DIN
hexagonal
50KM-12-1
70
70(K)M-12-2
70KM-12-1
95
95(K)M-12-2
95KM-12-1
120(K)M-12-2
120KM-12-1
150(K)M-12-2
150KM-12-1
185(K)M-12-2
185KM-12-1
240(K)M-12-2
240KM-12-1
300
300(K)M-12-2
300KM-12-1
300(K)M-11-2
400
400(K)M-12-2
400KM-12-1
400(K)M-11-2
500
500(K)M-12-2
500KM-12-1
500(K)M-11-2
630
–
630KM-12-1
630(K)M-11-2
For use with
other cable types.
Please contact our
representative.
For applications
outdoors and in
humid climate.
Order: +MWS.
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95.240-14-5
95(K)M-11-2
120(K)M-11-2
120.300-12-5
50.150-14-5
16.95-14-5
35KM-12-1
50(K)M-12-2
240
No earthing
device is
necessary.
35(K)M-12-2
50
185
Order: Kit MT.
35
150
For use with copper
wire screened cables.
Deep
indent
120
For use with
copper tape
screened cables.
DIN
hexagonal
Components can be
ordered individually.
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
When installed on an
appropriate equipment
bushing:
1250 A continuously
7
10. 300PBM
COUPLING CONNECTOR
FOR 430TB/G
Application
Technical characteristics
Separable coupling connector
(bolted type) for dual cable
arrangement. It has been
designed to be used with
430TB separable Tee connector.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Up to 36 kV
630 A (1250 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
290 mm
Design
1. Interface designed to fit
430TB connector.
2. Bus for 300PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket.
5. Conductive EPDM jacket.
6. Conductive EPDM cap.
7. Basic insulating plug (with
VD point).
8. Conductor connector
(hexagonal crimping, deep
290 mm
indent crimping or bolted).
(350 mm
9. Cable reducer.
for 36 kV)
10. Earthing lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
2
6
1
8
7
3
4
430TB
connector
300PBM
coupling
connector
5
10
9
Specifications and
standards
The 300PBM coupling
connector meets the
requirements of CENELEC
HD 629.1.
105 mm
Current Ir (A)
08/2011
Separable
connector
type
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an appropriate equipment
bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact
300PBM/G
K300PBM/G
M300PBM/G
12
24
36
630
630
630
1250
1250
1250
Conductor sizes (mm2)
min
max
35
35
50
300
300
240
8
11. Kit contents
The complete (K)(M)300PBM/G
coupling connector kit
comprises 3 x the following
components:
The kit also comprises silicone grease, field
control mastic, installation rod, installation
instructions and crimp chart.
Conductor
contact TMBC-X
3 x (K)(M)300PBM/G-W-X
coupling connector kit
Cable reducer
430CA-W
Contact rod
300PB-CR
Voltage
(Um)
(kV)
3 x 300PBM/G-11-X
3 x 300PBM/G-16-X
3 x 300PBM/G-18-X
min
max
12
12
12
12.0
17.0
19.0
17.5
23.5
32.6
3 x K300PBM/G-11-X
3 x K300PBM/G-16-X
3 x K300PBM/G-18-X
24
24
24
12.0
17.0
19.0
17.5
23.5
32.6
3 x M300PBM/G-11-X
3 x M300PBM/G-15-X
3 x M300PBM/G-19-X
3 x M300PBM/G-22-X
3 x M300PBM/G-25-X
3 x M300PBM/G-27-X
36
36
36
36
36
36
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
Table X
35
50
70
95
120
150
185
240
300
Order: Kit MT.
For use with fabric tape
(graphite) screened cables.
Order additional
semi-conductive tape
(type TSC).
35KM-10-1
50(K)M-10-1
70(K)M-10-1
95(K)M-10-1
120(K)M-10-1
150(K)M-10-1
185(K)M-10-1
240(K)M-10-1
–
DIN
hexagonal
Deep
indent
35(K)M-10-2
50(K)M-10-2
70(K)M-10-2
95(K)M-10-2
120(K)M-10-2
150(K)M-10-2
185(K)M-10-2
240(K)M-10-2
300(K)M-10-2
Copper
conductor
Bolted
DIN
hexagonal
For use with
easy strip semi-conductive
screened cables. Order:
Field control mastic
(type MFC).
Aluminium and
copper conductor
Aluminium conductor
Conductor
sizes (mm2)
For use with
copper tape
screened cables.
Dia. over core insulation (mm)
For use with copper
wire screened cables.
No earthing
device is
necessary.
For use with
other cable types.
Please contact our
representative.
120.300-12-5
Example:
The cable is 24 kV, 150 mm2
compact stranded copper with
a diameter over core insulation
of 27.5 mm.
Order 3 x
K300PBM/G-18-95.240-14-5
coupling connector kit.
Ordering
part number
95.240-14-5
To order the coupling connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Table W
50.150-14-5
Ordering instructions
(411CA-W
for 36 kV)
Conductor
contact TBC-X
16.95-14-5
Connector housing
(K)(M)300BP/G
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
For outdoor
applications.
Order: +MWS.
9
12. 430TBM-P2/P3
DUAL/TRIPLE CABLE ARRANGEMENT
FOR 430TB CONNECTOR
Application
Technical characteristics
Separable connectors (bolted
type) for dual (P2) and triple
(P3) cable arrangements.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Design
Up to 36 kV
630 A (1250 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
290 mm
1. Type C interface as
described by CENELEC
EN 50180 and 50181.
2. Bus for 300PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket.
5. Conductive EPDM jacket.
6. Conductive EPDM cap.
7. Basic insulating plug (with
VD point).
8. Conductor connector.
9. Cable reducer.
10. Earthing lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
2
1
6
8
Non-size
sensitive:
290 mm
7
3
Size
sensitive:
350 mm
4
430TBM
connector
300PBM
coupling
connector
5
10
Specifications and
standards
9
The 430TBM-P2/P3 connectors
meet the requirements of
CENELEC HD 629.1.
105 mm
Current Ir (A)
08/2011
Separable
connector
type
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an appropriate equipment
bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact
430TBM-P2/P3
K430TBM-P2/P3
M430TBM-P2/P3
12
24
36
630
630
630
1250
1250
1250
Conductor sizes (mm2)
min
max
35
35
50
300
300
240
10
13. Kit contents
The complete (K)(M)430TBM-P2
connector kit comprises 3 x the
following components:
The complete (K)(M)430TBM-P3
connector kit comprises 3 x the
following components:
395
290
300BIPA
basic
insulating
plug
300BIPA
basic
insulating
plug
300PBM
coupling
connector
300PBM
coupling
connectors
430TB tee
connector
110
430TB tee
connector
105
110
105
105
In mm.
For use with
copper tape
screened cables.
Order: Kit MT.
For use with Alupe or
C 33-226 cables.
Please contact our
representative.
min
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
W
max
11
15
19
22
25
27
Table X
Conductor
sizes (mm2)
35
50
70
95
120
150
185
240
300
For use with
other cable types.
Please contact our
representative.
Aluminium and
copper conductor
DIN
hexagonal
35KM-10-1
50(K)M-10-1
70(K)M-10-1
95(K)M-10-1
120(K)M-10-1
150(K)M-10-1
185(K)M-10-1
240(K)M-10-1
–
DIN
hexagonal
Deep
indent
35(K)M-10-2
50(K)M-10-2
70(K)M-10-2
95(K)M-10-2
120(K)M-10-2
150(K)M-10-2
185(K)M-10-2
240(K)M-10-2
300(K)M-10-2
Copper
conductor
Bolted
Aluminium conductor
For use with
easy strip semi-conductive
screened cables. Order:
Field control mastic
(type MFC).
For applications
outdoors and in
humid climate.
Order: +MWS.
120.300-12-5
Example:
The two cables are 24 kV,
150 mm2 stranded aluminium
with a diameter over core
insulation of 27.5 mm.
Order 3 x K430TBM-P2-22150(K)M-10-2.
Dia. over core
insulation (mm)
95.240-14-5
For triple cable arrangement:
3 x 430TBM-P3-W-X,
for use up to 12 kV.
Add a 'K' for use up to 24 kV:
3 x K430TBM-P3-W-X.
Add an 'M' for use up to 36 kV:
3 x M430TBM-P3-W-X.
Table W
50.150-14-5
To order the separable
connectors for dual cable
arrangement, use the tables
beside to substitute for W and
X in the formula:
3 x 430TBM-P2-W-X,
for use up to 12 kV.
Add a 'K' for use up to 24 kV:
3 x K430TBM-P2-W-X.
Add an 'M' for use up to 36 kV:
3 x M430TBM-P2-W-X.
1. From table W: select the
symbol which gives the best
centring of your core insulation
diameter.
2. From table X: according to
your conductor size and type,
select the designation which
completes the part number.
16.95-14-5
Ordering instructions
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
When installed on an
appropriate equipment
bushing:
1250 A continuously
11
14. 804PB
COUPLING CONNECTOR
FOR 484TB/G
Application
Technical characteristics
Separable coupling connector
(bolted type) for dual cable
arrangement. It has been
designed to be used with
484TB separable Tee connector.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Design
1. Interface designed to fit
484TB connector.
2. Bus for 804PB.
3. Conductor connector
(hexagonal crimping, deep
indent crimping or bolted).
4. Conductive EPDM insert.
5. Conductive EPDM jacket.
6. Insulating EPDM layer
moulded between the
insert and the jacket.
7. Cable reducer.
8. Conductive EPDM cap.
9. Basic insulating plug (with
VD point).
10. Earth lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
Up to 42 kV
630 A (1250 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20.8/36 (42) kV
290 mm
2
5
360 mm
6
484TB
connector
10
7
The 804PB coupling connector
meets the requirements of
CENELEC HD 629.1.
08/2011
804PB/G
K804PB/G
M804PB/G
P804PB/G
9
4
1
Specifications and
standards
Separable
connector
type
8
3
110 mm
Current
Ir (A)
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an
appropriate equipment bushing
min
max
12
24
36
42
630
630
630
630
1250
1250
1250
1250
50
35
35
35
630
630
630
630
Conductor sizes (mm2)
12
15. Kit contents
The complete (K)(M)(P)804PB/G
coupling connector kit
comprises 3 x the following
components:
The kit also comprises silicone grease, field
control mastic, gloves, roll adhesive tape,
installation instructions and crimp chart.
Conductor
contact TMBC-X
Connector housing
(K)(M)(P)804BP/G
Contact rod
and stud
Ordering instructions
To order the coupling connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Add a 'K' for use up to 24 kV,
add an 'M' for use up to 36 kV,
add a 'P' for use up to 42 kV.
Example:
The copper wire screened cable
is 36 kV, 240 mm2 stranded
aluminium with a diameter over
core insulation of 37.0 mm.
Order 3 x M804PB/G-32240(K)M-12-2 coupling
connector kit.
3 x (K)(M)(P)804PB/G-W-X
coupling connector kit
Conductor
contact TBC-X
Cable reducer
611CA-W
Table W
Dia. over core insulation (mm)
Ordering
part number
min
16.0
20.0
23.5
28.5
34.0
39.0
45.5
3 x 804PB/G-15-X
3 x 804PB/G-19-X
3 x 804PB/G-22-X
3 x 804PB/G-27-X
3 x 804PB/G-32-X
3 x 804PB/G-37-X
3 x 804PB/G-43-X
max
22.0
26.5
31.0
37.5
42.5
48.5
56.0
Table X
Conductor sizes
(mm2)
Aluminium conductor
Aluminium and
copper conductor
Copper
conductor
Bolted
DIN
hexagonal
50KM-12-1
70
70(K)M-12-2
70KM-12-1
95
95(K)M-12-2
95KM-12-1
120
120(K)M-12-2
120KM-12-1
150(K)M-12-2
150KM-12-1
185(K)M-12-2
185KM-12-1
240(K)M-12-2
240KM-12-1
300(K)M-12-2
300KM-12-1
300(K)M-11-2
400
400(K)M-12-2
400KM-12-1
400(K)M-11-2
500
500(K)M-12-2
500KM-12-1
500(K)M-11-2
630
–
630KM-12-1
630(K)M-11-2
For use with
other cable types.
Please contact our
representative.
For applications
outdoors and in
humid climate.
Order: +MWS.
35(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
120.300-12-5
50.150-14-5
50(K)M-11-2
95.240-14-5
16.95-14-5
35KM-12-1
50(K)M-12-2
300
No earthing
device is
necessary.
35(K)M-12-2
50
240
Order: Kit MT.
35
185
For use with copper
wire screened cables.
Deep
indent
150
For use with
copper tape
screened cables.
DIN
hexagonal
Components can be
ordered individually.
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
When installed on an
appropriate equipment
bushing:
1250 A continuously
13
16. 300SA
SURGE ARRESTER
FOR 430TB CONNECTOR
Application
Technical characteristics
Surge arrester designed to
protect 12, 24 and 36 kV
class components, including
transformers, equipment, cable
and accessories from high
voltage surges resulting from
lightning or switching.
It has been designed to be used
with the 430TB separable tee
connector.
• This surge arrester is a metal
oxide varistor surge arrester in
an elbow configuration.
• Each arrester is tested for AC
withstand, partial discharge
and critical voltage prior to
leaving the factory.
Design
Up to 36 kV
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
170 mm
Surge arrester comprising:
1. Interface designed to fit
the 430TB/G tee connector.
2. Conductive EPDM insert.
3. Conductive EPDM jacket.
4. Insulating EPDM layer
moulded between the insert
and the jacket.
5. Receptacle for contact rod.
6. Metal oxide valve elements.
7. Steel cap.
8. Earth connection.
9. Earth lead.
105 mm
Dia.
75 mm
1
5
2
3
L2
L1
Specifications and
standards
9
4
6
The 300SA surge arresters meet
the test requirements of IEC
60099-4.
Dia.
65 mm
7
8
08/2011
Surge
arrester
type
Nominal
discharge
current
In (kA)
Rated
voltage
Ur (kV)
Max. continuous
operating
voltage
Uc (kV)
L1
L2
300SA-10-15N
300SA-10-18N
300SA-10-22N
300SA-10-24N
300SA-10-30N
300SA-10-36N
300SA-10-45N
10
10
10
10
10
10
10
15
18
22
24
30
36
45
12.0
14.4
17.6
19.2
24.0
28.8
36.0
250
250
250
350
350
350
450
290
290
290
390
390
390
490
Dimensions
(mm)
14
17. Typical application and
dimensions
Ordering instructions
To order the surge arrester,
specify the surge arrester type,
as described on previous page.
290 mm
180 mm
Example:
For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 300SA-10-30N surge
arrester.
107 mm
Type 300SA
surge arrester
Type 430TB
tee connector
Technical data
Surge
arrester
type
Steep current
residual
voltage @ 10 kA
[1/20 µs] (kV)
300SA-10-15N
300SA-10-18N
300SA-10-22N
300SA-10-24N
300SA-10-30N
300SA-10-36N
300SA-10-45N
48.1
58.1
70.1
77.0
97.0
115.9
144.1
Lightning current
residual voltage
[8/20 µs] (kV)
Switching impulse
residual voltage
[36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
39.7
48.0
57.9
63.6
80.1
95.7
119.0
43.2
52.2
63.0
69.2
87.2
104.2
129.5
48.4
58.5
70.6
77.6
97.7
116.8
145.1
30.5
36.8
44.4
48.8
61.5
73.5
91.3
32.5
39.2
47.3
52.0
65.5
78.3
97.3
High current
impulse
withstand
(kA)
100
100
100
100
100
100
100
15
18. 800SA
SURGE ARRESTER
FOR 484TB CONNECTOR
Application
Technical characteristics
Surge arrester designed to
protect 12, 24, 36 and 42 kV
class components, including
transformers, equipment, cable
and accessories from high
voltage surges resulting from
lightning or switching.
It has been designed to be used
with the 484TB separable tee
connector.
• This surge arrester is a metal
oxide varistor surge arrester in
an elbow configuration.
• Each arrester is tested for AC
withstand, partial discharge
and critical voltage prior to
leaving the factory.
Design
Up to 42kV
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20.8/36 (42) kV
170 mm
Surge arrester comprising:
1. Interface designed
to fit he 484TB
t
tee connector.
2. Conductive EPDM insert.
3. Conductive EPDM jacket.
4. Insulating EPDM layer
moulded between the insert
and the jacket.
5. Receptacle for contact rod.
6. Metal oxide valve elements.
7. Steel cap.
8. Earth connection.
9. Earth lead.
105 mm
Dia.
75 mm
1
5
2
L2
3
L1
9
4
Specifications and
standards
6
The 800SA surge arresters meet
the test requirements of IEC
60099-4.
Dia.
65 mm
7
8
08/2011
Surge
arrester
type
Nominal
discharge
current
In (kA)
Rated
voltage
Ur (kV)
Max. continuous
operating
voltage
Uc (kV)
L1
L2
800SA-10-15N
800SA-10-18N
800SA-10-22N
800SA-10-24N
800SA-10-30N
800SA-10-36N
800SA-10-45N
10
10
10
10
10
10
10
15
18
22
24
30
36
45
12.0
14.4
17.6
19.2
24.0
28.8
36.0
250
250
250
350
350
350
450
290
290
290
390
390
390
490
Dimensions
(mm)
16
19. Typical application and
dimensions
Ordering instructions
To order the surge arrester,
specify the surge arrester type,
as described on previous page.
290 mm
180 mm
Example:
For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 800SA-10-30N surge
arrester.
110 mm
Type 800SA
surge arrester
Type
484TB
tee
connector
Technical data
Surge
arrester
type
Steep current
residual
voltage @ 10 kA
[1/20 µs] (kV)
800SA-10-15N
800SA-10-18N
800SA-10-22N
800SA-10-24N
800SA-10-30N
800SA-10-36N
800SA-10-45N
48.1
58.1
70.1
77.0
97.0
115.9
144.1
Lightning current
residual voltage
[8/20 µs] (kV)
Switching impulse
residual voltage
[36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
39.7
48.0
57.9
63.6
80.1
95.7
119.0
43.2
52.2
63.0
69.2
87.2
104.2
129.5
48.4
58.5
70.6
77.6
97.7
116.8
145.1
30.5
36.8
44.4
48.8
61.5
73.5
91.3
32.5
39.2
47.3
52.0
65.5
78.3
97.3
High current
impulse
withstand
(kA)
100
100
100
100
100
100
100
17
20. 400TR and 800TR
INTERFACE C
TEST RODS
Application
• The test rod can be used for:
- cable fault location
- cable testing
- phasing checks, etc.
• Connections may be made
with a cable lug, a 4 mm
plug or spring clips.
Technical characteristics
• The 400TR test rod can be
used with 430TB connectors.
• The 800TR is for use with the
484TB.
400TR
Design
1. nsulating shroud.
I
2. Threaded rod for test
connection.
3. Two nuts M12.
4. Insulation.
5. Copper test rod stem.
6. Wing nut.
An insulating shroud is
provided to allow the
application of test voltages
when bushings are closely
spaced.
1
1
M12
2
3
M12
2
40
3
480
Installation
The test rod is mounted on
to the clamping screw in
the type C interface tee and
coupling connectors. The
test cable is connected to
the threaded stem and the
insulating shroud moved to its
final position over the end of
the test rod.
800TR
480
321,5
4
288
4
5
5
Ordering instructions
Simply specify:
400TR or 800TR test rod.
In mm.
08/2011
Test rod
type
Maximum A.C.
test voltage
(50 Hz - 1 min)
Maximum D.C.
test voltage
(8 x U0 - 30 min)
Impulse voltage
(1.2 x 50 µs)
min
400TR
800TR
36 kV
36 kV
96 kV
96 kV
95 kV
95 kV
18
21. 400TK and 400SW
INSTALLATION TOOL
Application
• The 400SW box spanner
key fits on the hex nut of the
400BIPA basic insulating
plug.
• The box spanner and box
spanner key are designed
to facilitate assembly of
400TE, 400TB and 440TB
connectors.
• The 400TK box spanner is
used to install the 400TEF
clamping pin contact or
400TCS clamping screw.
400SW
400TK
Ordering instructions
08/2011
Simply specify:
- 400TK box spanner
- 400SW box spanner key
19
22. ACCESSORIES
INTERFACE C
Application
For use with connectors and
bushings with an interface C
as described by CENELEC EN
50180 and 50181.
400DR-B
Dead-end receptacle
Fits over a bushing with a type
C interface to provide 'deadend' facility.
400SOP-B
Stand-off plug
Is designed to support and
'dead-end' connectors with a
type C interface when removed
from equipment.
400GP-B
Earthing plug
Is designed to support and
earth connectors with a type C
interface when removed from
equipment.
08/2011
300GP-B
Earthing plug
Is designed to earth the 430TB
connectors when it is fixedmounted to the equipment
(maintenance earthing).
Technical characteristics
All these products, except the
earthing plugs, are tested for
AC withstand and partial
discharge prior to leaving
the factory.
Up to 36 kV
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20,8/36 (42) kV
Ordering instructions
Order
400DR-B for 12 kV,
K400DR-B for 24 kV or
M400DR-B for 36 kV
applications.
The dead-end receptacle can
be supplied with an earth lead.
Order with suffix -/G.
E.g. K400DR-B/G.
Ordering instructions
Order
400SOP-B for 12 kV,
K400SOP-B for 24 kV,
M400SOP-B for 36 kV or
P400SOP-B for 42 kV
applications.
Ordering instructions
Order
400GP-B for 12, 24, 36 or
42 kV applications.
Ordering instructions
Order
300GP-B for 12, 24, 36 or
42 kV applications.
20
23. 800GP-B
Earthing plug
Is designed to earth the 484TB
connectors when it is fixedmounted to the equipment
(maintenance earthing).
400BIPA
Basic insulating plug
Acts as a tightening nut for
the 400TB and 440TB tee
connector kits.
The plug contains a voltage
detection point.
The conductive rubber
protection cap is included.
Kit MT
Earthing kit for copper
tape screened cables
Contains a tinned copper braid
(25 mm² - L = 500 mm), a
tinned copper wire for cleating
and some water sealing mastic.
Ordering instructions
Order
800GP-B for 12, 24, 36 or
42 kV applications.
Ordering instructions
Order
400BIPA for 12 kV,
K400BIPA for 24 kV
M400BIPA for 36 kV or
P400BIPA for 42 kV
applications.
Ordering instructions
Order
Kit MT for 12 kV, 24 kV
36 kV or 42 kV applications.
21
24. POSSIBLE ARRANGEMENTS
INTERFACE C
430TB
430TBM-P2
Single cable arrangement.
Order 430TB for 12 kV,
K430TB for 24 kV or M430TB
for 36 kV applications.
Dual cable arrangement.
Order 430TBM-P2 for 12 kV,
K430TBM-P2 for 24 kV or
M430TBM-P2 for 36 kV
applications.
290
300BIPA
basic
insulating
plug
300PBM
coupling
connector
430TB tee
connector
110
105
430TBM-P3
430TBM-L3
Triple cable arrangement.
Order 430TBM-P3 for 12 kV,
K430TBM-P3 for 24 kV or
M430TBM-P3 for 36 kV
applications.
3-way connection.
Order 430TBM-L3 for 12 kV,
K430TBM-L3 for 24 kV or
M430TBM-L3 for 36 kV
applications.
425
395
300BIPA
basic
insulating
plug
300PBM
coupling
connectors
430TB tee
connector
08/2011
110
105
400BIPA
basic
insulating
plug
300BIPA
basic
insulating
plug
300PBM
coupling
connectors
430TB tee
connector
105
In mm.
22
25. 484TB
484TB-P2
Single cable arrangement.
Order 484TB for 12 kV,
K484TB for 24 kV, M484TB
for 36 kV or P484TB for 42 kV
applications.
Dual cable arrangement.
Order 484TB-P2 for 12 kV,
K484TB-P2 for 24 kV or
M484TB-P2 for 36 kV
or P484TB-P2 for 42kV
applications.
185
290
800BIPA
basic
insulating
plug
800BIPA
basic
insulating
plug
484TB tee
connector
804PB
coupling
connector
484TB tee
connector
110
110
110
484TB-P2 + 800SA
Dual cable arrangement with
surge arrester.
Order 484TB-P2+800SA for
12 kV, K484TB-P2+800SA for
24 kV, M484TB-P2+800SA for
36 kV or P484TB-P2+800SA
for 42 kV applications.
400
800BIPA
basic
insulating
plug
800SA
surge
arrester
804PB
coupling
connector
110
110
484TB tee
connector
23
26. Earthing plug on
connector
Order 300GP-B for 12 kV,
24 kV and 36 kV applications.
Order 800GP-B for 12 kV,
24 kV, 36 kV or 42 kV
applications.
800GP-B
earthing plug
484TB tee
connector
Cable and equipment
testing
800TR
test rod
insulating
schroud
484TB tee
connector
08/2011
110
In mm.
24
27.
28. Additional catalogue information on power cable accessories
is available by contacting us at the address below:
Distributed by:
Tel: +44 (0)191 490 1547
Nexans Network Solutions N.V. - Div. Euromold • Zuid III, Industrielaan 12, B-9320 Erembodegem
Fax: +44 (0)191 477 5371
Tel.: +32 (0)53 85 02 11 • Fax: +32 (0)53 83 10 13 • www.nexans.com • info.euromold@nexans.com
08/2011
a Nexans company
Email: northernsales@thorneandderrick.co.uk
Catalogue also available on CD-ROM Website: www.cablejoints.co.uk
www.thorneanderrick.co.uk