400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
The Nexans Euromold compact version screened separable connector is suitable for high voltage HV cable termination up to 33kV. Interface Type C Euromold M16 bolted tee connectors up to 33kV are designed to connect and terminate polymeric (XLPE EPR) cables to M16 bolted 400 series equipment bushings. Nexans Euromold connectors are supplied in sets of three phases.
Nexans Euromold Kit Contents: 3 x connector housings, 3 x size sensitive cable reducers, 3 x conductor contact lug, 3 x clamping screws and 3 x insulating plugs & caps.
Euromold Connectors 400 Series Interface Type B Bushing
* Connector Type : 14mm Plug-In Pin Contact
* Voltage Range : 11/12kV-33/36kV
* Current Rating : 400amps
* Specification : CENELEC EN50180 & EN50181
Euromold 400LR Elbow Connectors are used with 400 Series Interface B Bushing.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold separable elbow connectors are designed to terminate high voltage polymeric (XLPE EPR) screened (copper wire or copper tape) cables to CENELEC Interface Type B (400amp) bushings with 14mm plug-in pins, up to 33kV.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold straight plug connectors, Nexans Euromold bushings (air, oil and gas insulated switchgear) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
700 Series Interface E Elastimold Cable Connectors and Bushings connect and terminate HV cables to Interface E bushings on switchgear and transformers. Elastimold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F. Elastimold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables. 700 Series Interface E, Elastimold Bushings * Bushing Voltage Range 33kV-36kV * Bushing Current Rating 800Amps & 1250Amps * Bushing Type 5/8" Bolted Aluminium Insert Elastimold separable elbow connectors are high voltage cable terminations used to connect polymeric (XLPE or EPR insulated) power cables to HV equipment including transformers, switchgear, capacitors and motors. 700 Series Connectors - 750LR Tee Connectors & 775LR Tee Connectors 800-1250Amps 35-630sqmm Slip on cable connectors - quick to install to high voltage switchgear and transformers (oil, air and gas insulated) Touchproof cable terminations - made from conductive EPDM rubber, fully screened HV termination for safety One part cable termination - built-in stress relief, insulation and outer semi-conductive layers Maintenance friendly - readily disconnectable cable connector for high voltage maintenance work Compact cable connectors - space-saving HV cable terminations for SF6 gas insulated switchgear (GIS) EPDM rubber cable connectors - resistant to ozone, corona, chemicals, water and atmospheric pollutants Flexibility - Elastimold cable connectors are disconnectable and re-useable. Re-use of the Elastimold high voltage cable connector permits site re-location of HV electrical equipment without requiring cable re-termination. HV High Voltage Cable Connectors, Specification - Elastimold dead-break separable cable connectors suit all international high voltage bushing interfaces for the termination of HV cable into switchgear, transformers and motors. Elastimold cable connectors terminate high voltage power cables (typically 11kV, 15kV, 24kV, 33kV, 36kV up to 52kV) into SF6 GIS gas insulated switchgear including Schneider, ABB, Areva and Siemens. Elastimold cable connectors meet the requirements of ANSI/IEEE 386 & 404 and CENELEC EN50180 & EN50181 for high voltage "dead-break" cable connection, i..e connectors installed and terminated onto un-energised high voltage power cable. US specification "load-break" cable connectors for high voltage energised cable termination are available. High Voltage Cable Connectors - Elastimold cable connectors (elbow and straight types) are specified to terminate XLPE or EPR insulated high voltage power cables with copper tape or copper wire screens up to 52kV. Elastimold cable connectors are available to suit and terminate lead covered HV cables for hydro-carbon industries (oil, gas, petrochemicals) with ATEX certification for hazardous area Zones 1 and Zones 2.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
400 Series Interface B Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface B bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
The Nexans Euromold compact version screened separable connector is suitable for high voltage HV cable termination up to 33kV. Interface Type C Euromold M16 bolted tee connectors up to 33kV are designed to connect and terminate polymeric (XLPE EPR) cables to M16 bolted 400 series equipment bushings. Nexans Euromold connectors are supplied in sets of three phases.
Nexans Euromold Kit Contents: 3 x connector housings, 3 x size sensitive cable reducers, 3 x conductor contact lug, 3 x clamping screws and 3 x insulating plugs & caps.
Euromold Connectors 400 Series Interface Type B Bushing
* Connector Type : 14mm Plug-In Pin Contact
* Voltage Range : 11/12kV-33/36kV
* Current Rating : 400amps
* Specification : CENELEC EN50180 & EN50181
Euromold 400LR Elbow Connectors are used with 400 Series Interface B Bushing.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold separable elbow connectors are designed to terminate high voltage polymeric (XLPE EPR) screened (copper wire or copper tape) cables to CENELEC Interface Type B (400amp) bushings with 14mm plug-in pins, up to 33kV.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold straight plug connectors, Nexans Euromold bushings (air, oil and gas insulated switchgear) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
700 Series Interface E Elastimold Cable Connectors and Bushings connect and terminate HV cables to Interface E bushings on switchgear and transformers. Elastimold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F. Elastimold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables. 700 Series Interface E, Elastimold Bushings * Bushing Voltage Range 33kV-36kV * Bushing Current Rating 800Amps & 1250Amps * Bushing Type 5/8" Bolted Aluminium Insert Elastimold separable elbow connectors are high voltage cable terminations used to connect polymeric (XLPE or EPR insulated) power cables to HV equipment including transformers, switchgear, capacitors and motors. 700 Series Connectors - 750LR Tee Connectors & 775LR Tee Connectors 800-1250Amps 35-630sqmm Slip on cable connectors - quick to install to high voltage switchgear and transformers (oil, air and gas insulated) Touchproof cable terminations - made from conductive EPDM rubber, fully screened HV termination for safety One part cable termination - built-in stress relief, insulation and outer semi-conductive layers Maintenance friendly - readily disconnectable cable connector for high voltage maintenance work Compact cable connectors - space-saving HV cable terminations for SF6 gas insulated switchgear (GIS) EPDM rubber cable connectors - resistant to ozone, corona, chemicals, water and atmospheric pollutants Flexibility - Elastimold cable connectors are disconnectable and re-useable. Re-use of the Elastimold high voltage cable connector permits site re-location of HV electrical equipment without requiring cable re-termination. HV High Voltage Cable Connectors, Specification - Elastimold dead-break separable cable connectors suit all international high voltage bushing interfaces for the termination of HV cable into switchgear, transformers and motors. Elastimold cable connectors terminate high voltage power cables (typically 11kV, 15kV, 24kV, 33kV, 36kV up to 52kV) into SF6 GIS gas insulated switchgear including Schneider, ABB, Areva and Siemens. Elastimold cable connectors meet the requirements of ANSI/IEEE 386 & 404 and CENELEC EN50180 & EN50181 for high voltage "dead-break" cable connection, i..e connectors installed and terminated onto un-energised high voltage power cable. US specification "load-break" cable connectors for high voltage energised cable termination are available. High Voltage Cable Connectors - Elastimold cable connectors (elbow and straight types) are specified to terminate XLPE or EPR insulated high voltage power cables with copper tape or copper wire screens up to 52kV. Elastimold cable connectors are available to suit and terminate lead covered HV cables for hydro-carbon industries (oil, gas, petrochemicals) with ATEX certification for hazardous area Zones 1 and Zones 2.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
400 Series Interface B Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface B bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Euromold elbow connectors, Euromold tee connectors, Euromold bushings (oil insulated) and Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series, 400TB 440TB Features :
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
T&D UK with the support of Nexans provide installation training and certification for experienced high voltage cable jointers up to 33kV.
200 Series Interface A Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface A bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold Connectors & Bushing Interfaces
Euromold Connectors 200 Series Interface Type A Bushing
* Connector Type : 7.9mm Plug-In Pin Contact
* Voltage Range : 11/12kV-24kV
* Current Rating : 250amps
* Specification : CENELEC EN50180 & EN50181
Euromold 158LR Elbow Connectors are used with 200 Series Interface A Bushing.
Lucy Lighting Fortress Feeder Pillars, Double Door Feeder Pillars
Fortress Double Door Hinged Feeder Pillars are robust electrical enclosures providing electrical services for a variety of low voltage electrical distribution applications - the feeder pillars incorporate a high level of corrosion proofing to ensure durability and a long maintenance free life. The Fortress feeder pillar range is available in a variety of sizes to meet most applications.
Lucy Fortress Feeder Pillars - Key Features
Two or three hinged pillar doors
Long life hinges - solid stainless steel blocks on all versions
Two Lucy Lighting T key wedge locks for added security
18mm thick backboard - treated exterior grade plywood
Danger warning label fitted as standard
Earth lead connection is supplied from the feeder pillar body to the door
High quality UV resistant paint - minimum thickness of 60 microns
Door seal up to IP65
No fixed bar between doors gives totally open access
Detachable roof section from pillar
Backboard can be removed for electrical wiring
Detachable root section - finished in bitumen enriched paint
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Euromold elbow connectors, Euromold tee connectors, Euromold bushings (oil insulated) and Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series, 400TB 440TB Features :
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
T&D UK with the support of Nexans provide installation training and certification for experienced high voltage cable jointers up to 33kV.
200 Series Interface A Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface A bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
Nexans Euromold Connectors & Bushing Interfaces
Euromold Connectors 200 Series Interface Type A Bushing
* Connector Type : 7.9mm Plug-In Pin Contact
* Voltage Range : 11/12kV-24kV
* Current Rating : 250amps
* Specification : CENELEC EN50180 & EN50181
Euromold 158LR Elbow Connectors are used with 200 Series Interface A Bushing.
Lucy Lighting Fortress Feeder Pillars, Double Door Feeder Pillars
Fortress Double Door Hinged Feeder Pillars are robust electrical enclosures providing electrical services for a variety of low voltage electrical distribution applications - the feeder pillars incorporate a high level of corrosion proofing to ensure durability and a long maintenance free life. The Fortress feeder pillar range is available in a variety of sizes to meet most applications.
Lucy Fortress Feeder Pillars - Key Features
Two or three hinged pillar doors
Long life hinges - solid stainless steel blocks on all versions
Two Lucy Lighting T key wedge locks for added security
18mm thick backboard - treated exterior grade plywood
Danger warning label fitted as standard
Earth lead connection is supplied from the feeder pillar body to the door
High quality UV resistant paint - minimum thickness of 60 microns
Door seal up to IP65
No fixed bar between doors gives totally open access
Detachable roof section from pillar
Backboard can be removed for electrical wiring
Detachable root section - finished in bitumen enriched paint
3M LVI-1/2 Scotchcast Resin Cable Joints
Resin Joints - 3M Scotchcast Cable Joints Kits LV
2, 3, 4 Core Resin Cable Jointing Kits - 3M
Resin Joints - Low Voltage Underground Resin Cable Joint Kits
3M Scotchcast Resin Joint - 4 Core up to 6sqmm - LV1-1/2 Kit
Up to 25mm OD cables accomodated in cable joint shell
3M Scotchcast resin (470W) cable joints are designed to joint multi-core armoured (SWA or GSWB), polymeric (XLPE EPR) low voltage power cables - 3M cable joints provide electrical insulation and mechanical protection with either compression or mechanical connectors - 3M LVI-1 power cable joints have now replaced the 3M LA range of joints.
Prysmian Draka supplies a complete range of marine, offshore oil and gas power, control and instrumentation cables for use on oil platforms and floating oil production units (FPSO). T&D distribute an extensive range of cables from 250V to 33kV - a complete range of marine, offshore oil and gas industry cables to IEEE, UKOOA and IEC specification.
The T&D and Prysmian commercial relationshipgoes back to the previous century. T&D have distributed the Prysmian Components range of cable joints, cable glands, cable cleats and high voltage cable terminations for several decades. The new relationship will now extend T&D's portfolio to embrace Prysmian Draka Offshore Marine, Oil & Gas cables.
Prysmian Draka Marine Offshore Oil & Gas Cables - Overview
RFOU(i) 250V S1/S5 Halogen-free, mud resistant instrumentation cable
RFOU(c)250V S2/S6 Halogen-free, mud resistant instrumentation cable
BFOU(i)250V S3/S7 Halogen-free, mud and fire resistant instrumentation cable
BFOU(c)250V S4/S8 Halogen-free, mud and fire resistant instrumentation cable
RU(i) 250V S11 Halogen-free, unarmoured, mud resistant instrumentation cable
BU(i) 250V S13 Halogen-free, unarmoured, mud resistant instrumentation cable
BU(c) 250V S14 Halogen-free, unarmoured, mud resistant instrumentation cable
RFOU 0,6/1kV P1/P8 Halogen-free, mud resistant power cable
RFOU 6/10(12)kV P3/P10 Halogen-free, mud resistant HV power cable
RFOU 12/20(24)kVP19/P21 Halogen-free, mud resistant HV power cable
BFOU 0,6/1kV P5/P12 Halogen-free, mud resistant, fire resistant power cable
UX 1000V P15 Halogen-free, mud resistant insulated conductor
RU 0,6/1kV P18 Halogen-free, unarmoured, mud resistant power cable
BU 0,6/1kV P17 Halogen-free, fire resistant, unarmoured, mud resistant power cable
QFCI Fire resistant optical fibre cable, halogen-free
AICI Optical cable for industrial environments
IFLI 250V P16 Cables for living quarter and office areas, halogen-free
400 Series Interface C Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
900 Series Interface F Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface F bushings on switchgear and transformers up to 42kV. Nexans 944TB Tee Connectors provide high voltage cable terminations using separable tee shape connectors :
Nexans 944TB/G - 12kV 2500Amp 70-80sqmm Conductors
Nexans K944TB/G - 24kV 2500Amp 16-800sqmm Conductors
Nexans M944TB/G - 36kV 2500Amp 35-800sqmm Conductors
Nexans P944TB/G - 42kV 1250Amp 50-800sqmm Conductors
Nexans Euromold Connectors Interface D 600 Series
Nexans Euromold 675LR Connector
1250A 11kV Dead Break Connectors 35-800sqmm
Nexans Euromold 675LR connector suits 11kV/12kV polymeric insulated cables (XLPE EPR), rated up to 1250amps with copper or aluminium conductors 35-800sqmm.
Interface type D Nexans Euromold 5/8" bolted tee connector, for high voltage cable connecting and termination applications up to 24kV. 1250amp (copper stud) application separable connector is designed to connect polymeric (XLPE EPR) cables to a 5/8" copper, 600 series bushings.
Nexans Euromold Connectors Interface D 600 Series
Nexans Euromold 650LR Connector
800A 11kV Dead Break Connectors 35-630sqmm
Interface type D Nexans Euromold 5/8" bolted tee connector, for high voltage cable connecting and termination applications up to 24kV. 800amp (aluminium stud) application separable connector is designed to connect polymeric (XLPE EPR) cables to a 5/8" aluminium stud, 600 series bushings.
Nexans Euromold K650LR connector suits 24kV polymeric insulated cables (XLPE EPR), rated up to 800amps with copper or aluminium conductors 35-630sqmm.
Interface type D Nexans Euromold 5/8" bolted tee connector, for high voltage cable connecting and termination applications up to 24kV. 800amp (aluminium stud) application separable Nexans Euromold connector is designed to connect polymeric (XLPE EPR) cables to a 5/8" aluminium stud, 600 series bushings.
Nexans Euromold 600 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV and 24kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 600 series separable connectors include Nexans Euromold bolted tee connectors and Nexans Euromold bushings (oil and air insulated) for electrical equipment up to 24kV - 1250A. Nexans Euromold 600 series connectors are specified to terminate and connect polymeric (XLPE or EPR) screened (copper tape and wire) cables to ANSI-style Interface Type D (800amp) bushings with either copper or aluminium 5/8" bolted connection.
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 400 series screened separable connectors are EPDM pre-moulded,high voltage cable terminations for 6.6kV, 11kV, 15kV, 24kV and 33kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold 400 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold tee connectors, Nexans Euromold bushings (oil insulated) and Nexans Euromold surge arresters to protect electrical equipment up to 33kV.
Nexans Euromold Separable Elbow Connectors 400 Series
Euromold 400LB Elbow Connectors & 400TB 440TB Elbow Connectors
Connector for terminating high voltage polymeric (XLPE EPR) cables, 11-33kV
Plug in bolted tee connectors with current rating 630amps and 1250amps
Conductive EPDM jacket provides a touch safe screened termination
Suits copper wire and copper tape screened cable, 35-300sqmm
Type C 630A interface to CENELEC EN50180
Nexans Euromold 200 series screened separable connectors are EPDM pre-moulded, high voltage cable terminations for 6.6kV, 11kV, 15kV and 24kV electrical equipment including switchgear, transformers and motors.
Nexans Euromold separable elbow connectors are designed to terminate high voltage polymeric (XLPE EPR) screened (copper wire or copper tape) cables to CENELEC Interface Type A (250amp) bushings with 7.9mm plug-in pins, 11kV-24kV.
Nexans Euromold 200 series separable connectors include Nexans Euromold elbow connectors, Nexans Euromold straight plugs, Nexans Euromold bushings (air, oil and gas insulated switchgear) and Nexans Euromold surge arresters to protect 11kV-24kV electrical equipment.
Isolation Procedures for Safe Working on Electrical Systems and Equipment by the JIB | solation Procedures for Safe Working on Electrical Systems and Equipment
This chart shows the safe isolation procedure that you should use when working on electrical systems and equipment.
You'll receive a printed copy of this from your Training Provider, but it's also here as a handy reference to keep electronically.
THE RULES OF SAFE ISOLATION ARE:
Obtain permission to start work (a Permit may be required in some situations)
Identify the source(s) of supply using an approved voltage indicator or test lamp
Prove that the approved voltage indicator or test lamp is functioning correctly
Isolate the supply(s)
Secure the isolation
Prove the system/equipment is DEAD using an approved voltage indicator or test lamp
Prove that the approved voltage indicator or test lamp is functioning correctly
Put up warning signs to tell other people that the electrical installation has been isolated
Once the system/equipment is proved DEAD, work can begin
Uploaded by THORNE & DERRICK LV HV Jointing, Earthing, Substation & Electrical Eqpt | Explosive Atmosphere Experts & ATEX IECEx.
THORNE & DERRICK based in the UK are international distributors of LV, MV & HV Cable Installation, Jointing, Substation & Electrical Equipment.
Since 1985, T&D have established an international reputation based on SERVICE | INTEGRITY | TRUST.
Contact us for 3M, ABB, Alroc, AN Wallis, CATU, Cembre, Centriforce, CMP, CSD, Elastimold, Ellis Patents, Emtelle, Euromold, Filoform , Furse, Lucy Electric & Zodion, Nexans, Pfisterer, Polypipe, Prysmian, Roxtec, Sicame, WT Henley.
Dev Dives: Train smarter, not harder – active learning and UiPath LLMs for do...UiPathCommunity
💥 Speed, accuracy, and scaling – discover the superpowers of GenAI in action with UiPath Document Understanding and Communications Mining™:
See how to accelerate model training and optimize model performance with active learning
Learn about the latest enhancements to out-of-the-box document processing – with little to no training required
Get an exclusive demo of the new family of UiPath LLMs – GenAI models specialized for processing different types of documents and messages
This is a hands-on session specifically designed for automation developers and AI enthusiasts seeking to enhance their knowledge in leveraging the latest intelligent document processing capabilities offered by UiPath.
Speakers:
👨🏫 Andras Palfi, Senior Product Manager, UiPath
👩🏫 Lenka Dulovicova, Product Program Manager, UiPath
Key Trends Shaping the Future of Infrastructure.pdfCheryl Hung
Keynote at DIGIT West Expo, Glasgow on 29 May 2024.
Cheryl Hung, ochery.com
Sr Director, Infrastructure Ecosystem, Arm.
The key trends across hardware, cloud and open-source; exploring how these areas are likely to mature and develop over the short and long-term, and then considering how organisations can position themselves to adapt and thrive.
Smart TV Buyer Insights Survey 2024 by 91mobiles.pdf91mobiles
91mobiles recently conducted a Smart TV Buyer Insights Survey in which we asked over 3,000 respondents about the TV they own, aspects they look at on a new TV, and their TV buying preferences.
The Art of the Pitch: WordPress Relationships and SalesLaura Byrne
Clients don’t know what they don’t know. What web solutions are right for them? How does WordPress come into the picture? How do you make sure you understand scope and timeline? What do you do if sometime changes?
All these questions and more will be explored as we talk about matching clients’ needs with what your agency offers without pulling teeth or pulling your hair out. Practical tips, and strategies for successful relationship building that leads to closing the deal.
Essentials of Automations: Optimizing FME Workflows with ParametersSafe Software
Are you looking to streamline your workflows and boost your projects’ efficiency? Do you find yourself searching for ways to add flexibility and control over your FME workflows? If so, you’re in the right place.
Join us for an insightful dive into the world of FME parameters, a critical element in optimizing workflow efficiency. This webinar marks the beginning of our three-part “Essentials of Automation” series. This first webinar is designed to equip you with the knowledge and skills to utilize parameters effectively: enhancing the flexibility, maintainability, and user control of your FME projects.
Here’s what you’ll gain:
- Essentials of FME Parameters: Understand the pivotal role of parameters, including Reader/Writer, Transformer, User, and FME Flow categories. Discover how they are the key to unlocking automation and optimization within your workflows.
- Practical Applications in FME Form: Delve into key user parameter types including choice, connections, and file URLs. Allow users to control how a workflow runs, making your workflows more reusable. Learn to import values and deliver the best user experience for your workflows while enhancing accuracy.
- Optimization Strategies in FME Flow: Explore the creation and strategic deployment of parameters in FME Flow, including the use of deployment and geometry parameters, to maximize workflow efficiency.
- Pro Tips for Success: Gain insights on parameterizing connections and leveraging new features like Conditional Visibility for clarity and simplicity.
We’ll wrap up with a glimpse into future webinars, followed by a Q&A session to address your specific questions surrounding this topic.
Don’t miss this opportunity to elevate your FME expertise and drive your projects to new heights of efficiency.
Let's dive deeper into the world of ODC! Ricardo Alves (OutSystems) will join us to tell all about the new Data Fabric. After that, Sezen de Bruijn (OutSystems) will get into the details on how to best design a sturdy architecture within ODC.
PHP Frameworks: I want to break free (IPC Berlin 2024)Ralf Eggert
In this presentation, we examine the challenges and limitations of relying too heavily on PHP frameworks in web development. We discuss the history of PHP and its frameworks to understand how this dependence has evolved. The focus will be on providing concrete tips and strategies to reduce reliance on these frameworks, based on real-world examples and practical considerations. The goal is to equip developers with the skills and knowledge to create more flexible and future-proof web applications. We'll explore the importance of maintaining autonomy in a rapidly changing tech landscape and how to make informed decisions in PHP development.
This talk is aimed at encouraging a more independent approach to using PHP frameworks, moving towards a more flexible and future-proof approach to PHP development.
JMeter webinar - integration with InfluxDB and GrafanaRTTS
Watch this recorded webinar about real-time monitoring of application performance. See how to integrate Apache JMeter, the open-source leader in performance testing, with InfluxDB, the open-source time-series database, and Grafana, the open-source analytics and visualization application.
In this webinar, we will review the benefits of leveraging InfluxDB and Grafana when executing load tests and demonstrate how these tools are used to visualize performance metrics.
Length: 30 minutes
Session Overview
-------------------------------------------
During this webinar, we will cover the following topics while demonstrating the integrations of JMeter, InfluxDB and Grafana:
- What out-of-the-box solutions are available for real-time monitoring JMeter tests?
- What are the benefits of integrating InfluxDB and Grafana into the load testing stack?
- Which features are provided by Grafana?
- Demonstration of InfluxDB and Grafana using a practice web application
To view the webinar recording, go to:
https://www.rttsweb.com/jmeter-integration-webinar
"Impact of front-end architecture on development cost", Viktor TurskyiFwdays
I have heard many times that architecture is not important for the front-end. Also, many times I have seen how developers implement features on the front-end just following the standard rules for a framework and think that this is enough to successfully launch the project, and then the project fails. How to prevent this and what approach to choose? I have launched dozens of complex projects and during the talk we will analyze which approaches have worked for me and which have not.
Search and Society: Reimagining Information Access for Radical FuturesBhaskar Mitra
The field of Information retrieval (IR) is currently undergoing a transformative shift, at least partly due to the emerging applications of generative AI to information access. In this talk, we will deliberate on the sociotechnical implications of generative AI for information access. We will argue that there is both a critical necessity and an exciting opportunity for the IR community to re-center our research agendas on societal needs while dismantling the artificial separation between the work on fairness, accountability, transparency, and ethics in IR and the rest of IR research. Instead of adopting a reactionary strategy of trying to mitigate potential social harms from emerging technologies, the community should aim to proactively set the research agenda for the kinds of systems we should build inspired by diverse explicitly stated sociotechnical imaginaries. The sociotechnical imaginaries that underpin the design and development of information access technologies needs to be explicitly articulated, and we need to develop theories of change in context of these diverse perspectives. Our guiding future imaginaries must be informed by other academic fields, such as democratic theory and critical theory, and should be co-developed with social science scholars, legal scholars, civil rights and social justice activists, and artists, among others.
Accelerate your Kubernetes clusters with Varnish CachingThijs Feryn
A presentation about the usage and availability of Varnish on Kubernetes. This talk explores the capabilities of Varnish caching and shows how to use the Varnish Helm chart to deploy it to Kubernetes.
This presentation was delivered at K8SUG Singapore. See https://feryn.eu/presentations/accelerate-your-kubernetes-clusters-with-varnish-caching-k8sug-singapore-28-2024 for more details.
3. Nexans Network Solutions
Div. Euromold
COMPANY PRESENTATION
EUROMOLD
International standards
Euromold is the leading
European specialised designer,
manufacturer and distributor
of prefabricated cable
accessories for medium voltage
energy distribution. Euromold
provides a complete range of
accessories for underground
cables: premoulded EPDM
rubber connectors for cables
and epoxy bushings for
transformers and switchgear, as
well as a large range of coldshrinkable terminations and
joints from 12 to 42 kV.
Euromold is also the
manufacturer of electrical
components for the high
voltage accessories of the
Nexans group.
All our products meet the
International standards like
CENELEC HD 629.1, CENELEC
EN 50180, IEC 60137, IEC
60502-4… or country specifications. Official certificates,
CESI, KEMA, ATEX… prove the
conformity of our products.
Long duration tests of existing
or new products are continuously performed in our test
fields.
ISO 9001 Certificate
Since 1992, Euromold’s
commitment to quality is
demonstrated by its ISO 9001
certification.
Laboratory accreditation
Since June 2000, Euromold’s
independent ELAB laboratory
obtained the BELAC
accreditation no.144-TEST
conform with the European
standards for laboratories ISO
17025 for electrical testing of
low and medium voltage cable
accessories according to the
international standards
EN 50393, IEC 60502-4, IEC
61442 and HD 629.
08/2011
While every care is taken to ensure that the information contained
in this publication is correct, no legal responsibility can be accepted
for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold
reserves the right to alter or modify the characteristics of its products
described in this catalogue as standards and technology evolve.
1
4. SEPARABLE CONNECTORS
INTERFACE C
Table of contents
Interface C1 & C2
430TB - tee connector
484TB - tee connector
300PBM - coupling connector
430TBM-P2/P3 - dual/triple cable arrangement
804PB - coupling connector
300SA - surge arrester
800SA - surge arrester
400TR and 800TR - test rod
400TK and 400SW installation tools
Accessories
Possible arrangements
Dimensions according to
European CENELEC EN 50180
and 50181 (in mm).
Dia. 56±0.2
Dia. 46±0.2
Dia. 22 min for C1
Dia. 32 nominal for C2
M16 x 2 - 6H
0
1.5 -0.5
29
min.
90±0.2
08/2011
11
min.
Dia. 70±0.2
2
6. 430TB
INTERFACE C
TEE CONNECTOR
Application
Technical characteristics
Separable tee shape
connector (bolted type)
designed to connect polymeric
insulated cable to equipment
(transformers, switchgear,
motors, ...).
Also connects cable to cable
when using the appropriate
mating parts.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Up to 36 kV
630 A (800 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
185 mm
Design
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C interface as
described by CENELEC
EN 50180 and 50181.
5. Conductor connector.
6. Basic insulating plug (with
VD point).
7. Cable reducer.
8. Conductive rubber cap.
9. Clamping screw.
0. Earthing lead.
1
4
9
8
5
6
1
290 mm
(350 mm
for 36 kV)
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
2
3
10
Specifications and
standards
The 430TB separable connector
meets the requirements of
CENELEC HD 629.1.
7
Current Ir (A)
08/2011
Separable
connector
type
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an appropriate equipment
bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact
430TB/G
K430TB/G
M430TB/G
12
24
36
630
630
630
800
800
800
Conductor sizes (mm2)
min
max
35
35
50
300
300
240
4
7. Kit contents
The kit also comprises silicone grease, field
control mastic, installation rod, installation
instructions and crimp chart.
The complete (K)(M)430TB/G
tee connector kit comprises 3 x
the following components:
Conductor
contact TMBC-X
Table W
Ordering
part number
Voltage
(Um)
(kV)
3 x 430TB/G-11-X
3 x 430TB/G-16-X
3 x 430TB/G-18-X
min
max
12
12
12
12.0
17.0
19.0
17.5
23.5
32.6
3 x K430TB/G-11-X
3 x K430TB/G-16-X
3 x K430TB/G-18-X
24
24
24
12.0
17.0
19.0
17.5
23.5
32.6
3 x M430TB/G-11-X
3 x M430TB/G-15-X
3 x M430TB/G-19-X
3 x M430TB/G-22-X
3 x M430TB/G-25-X
3 x M430TB/G-27-X
36
36
36
36
36
36
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
Table X
35
50
70
95
120
150
185
240
300
Order: Kit MT.
For use with Alupe or
C 33-226 cables.
Please contact our
representative.
35KM-10-1
50(K)M-10-1
70(K)M-10-1
95(K)M-10-1
120(K)M-10-1
150(K)M-10-1
185(K)M-10-1
240(K)M-10-1
–
DIN
hexagonal
Deep
indent
35(K)M-10-2
50(K)M-10-2
70(K)M-10-2
95(K)M-10-2
120(K)M-10-2
150(K)M-10-2
185(K)M-10-2
240(K)M-10-2
300(K)M-10-2
Copper
conductor
Bolted
DIN
hexagonal
For use with
easy strip semi-conductive
screened cables. Order:
Field control mastic
(type MFC).
Aluminium and
copper conductor
Aluminium conductor
Conductor
sizes (mm2)
For use with
copper tape
screened cables.
Dia. over core insulation (mm)
For use with
other cable types.
Please contact our
representative.
For applications
outdoors and in
humid climate.
Order: +MWS.
120.300-12-5
Example:
The cable is 24 kV, 150 mm2
compact stranded copper with
a diameter over core insulation
of 27.5 mm.
Order 3 x
K430TB/G-18-95.240-14-5
tee connector kit.
(411CA-W
for 36 kV)
95.240-14-5
To order the tee connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Conductor
contact TBC-X
Cable reducer
430CA-W
50.150-14-5
Ordering instructions
Basic insulating
plug
(K)(M)300BIPA +
rubber cap
16.95-14-5
Connector housing
(K)(M)430BT/G
Clamping
screw
430TCS
3 x (K)(M)430TB/G-W-X
connector kit
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
When installed on an
appropriate equipment
bushing:
800 A continuously
5
8. 484TB
INTERFACE C
TEE CONNECTOR
Application
Separable tee shape
connector (bolted type)
designed to connect polymeric
insulated cable to equipment
(transformers, switchgear,
motors, ...).
Also connects cable to cable
when using the appropriate
mating parts.
Up to 42 kV
630 A (1250 A)
Technical characteristics
• The thick conductive EPDM
jacket provides a total safe to
touch screen which ensures
safety for personnel.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20.8/36 (42) kV
Design
185 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C - interface as
described by CENELEC
EN 50180 and 50181.
5. Conductor connector.
6. Basic insulating plug (with
VD point).
7. Cable reducer.
8. Conductive rubber cap.
9. Clamping screw.
0. Earthing lead.
1
4
9
8
5
6
1
2
360 mm
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
3
10
Specifications and
standards
7
The 484TB separable connector
meets the requirements of
CENELEC HD 629.1.
08/2011
Separable
connector
type
484TB/G
K484TB/G
M484TB/G
P484TB/G
Current
Ir (A)
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an
appropriate equipment bushing
min
max
12
24
36
42
630
630
630
630
1250
1250
1250
1250
50
35
35
35
630
630
630
630
Conductor sizes (mm2)
6
9. Kit contents
The complete (K)(M)(P)484TB/G
tee connector kit comprises 3x
the following components:
The kit also comprises silicone grease, field
control mastic, gloves, roll adhesive tape,
installation instructions and crimp chart.
Conductor
contact TMBC-X
Connector housing
(K)(M)(P)484BT/G
Clamping
screw
430TCS
Ordering instructions
To order the tee connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Add a 'K' for use up to 24 kV,
add an 'M' for use up to 36 kV,
add a 'P' for use up to 42 kV.
Example:
The copper wire screened cable
is 36 kV, 240 mm2 stranded
aluminium with a diameter over
core insulation of 37.0 mm.
Order 3 x
M484TB/G-32-240(K)M-12-2
tee connector kit.
(K)(M)(P)484TB/G-W-X
connector kit
Basic insulating
plug
(K)(M)(P)800BIPA
+ rubber cap
Conductor
contact TBC-X
Cable reducer
611CA-W
Table W
Dia. over core insulation (mm)
Ordering
part number
min
16.0
20.0
23.5
28.5
34.0
39.0
45.5
3 x 484TB/G-15-X
3 x 484TB/G-19-X
3 x 484TB/G-22-X
3 x 484TB/G-27-X
3 x 484TB/G-32-X
3 x 484TB/G-37-X
3 x 484TB/G-43-X
max
22.0
26.5
31.0
37.5
42.5
48.5
56.0
Table X
Conductor sizes
(mm2)
Aluminium conductor
Aluminium and
copper conductor
Copper
conductor
Bolted
DIN
hexagonal
50KM-12-1
70
70(K)M-12-2
70KM-12-1
95
95(K)M-12-2
95KM-12-1
120(K)M-12-2
120KM-12-1
150(K)M-12-2
150KM-12-1
185(K)M-12-2
185KM-12-1
240(K)M-12-2
240KM-12-1
300
300(K)M-12-2
300KM-12-1
300(K)M-11-2
400
400(K)M-12-2
400KM-12-1
400(K)M-11-2
500
500(K)M-12-2
500KM-12-1
500(K)M-11-2
630
–
630KM-12-1
630(K)M-11-2
For use with
other cable types.
Please contact our
representative.
For applications
outdoors and in
humid climate.
Order: +MWS.
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95.240-14-5
95(K)M-11-2
120(K)M-11-2
120.300-12-5
50.150-14-5
16.95-14-5
35KM-12-1
50(K)M-12-2
240
No earthing
device is
necessary.
35(K)M-12-2
50
185
Order: Kit MT.
35
150
For use with copper
wire screened cables.
Deep
indent
120
For use with
copper tape
screened cables.
DIN
hexagonal
Components can be
ordered individually.
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
When installed on an
appropriate equipment
bushing:
1250 A continuously
7
10. 300PBM
COUPLING CONNECTOR
FOR 430TB/G
Application
Technical characteristics
Separable coupling connector
(bolted type) for dual cable
arrangement. It has been
designed to be used with
430TB separable Tee connector.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Up to 36 kV
630 A (1250 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
290 mm
Design
1. Interface designed to fit
430TB connector.
2. Bus for 300PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket.
5. Conductive EPDM jacket.
6. Conductive EPDM cap.
7. Basic insulating plug (with
VD point).
8. Conductor connector
(hexagonal crimping, deep
290 mm
indent crimping or bolted).
(350 mm
9. Cable reducer.
for 36 kV)
10. Earthing lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
2
6
1
8
7
3
4
430TB
connector
300PBM
coupling
connector
5
10
9
Specifications and
standards
The 300PBM coupling
connector meets the
requirements of CENELEC
HD 629.1.
105 mm
Current Ir (A)
08/2011
Separable
connector
type
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an appropriate equipment
bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact
300PBM/G
K300PBM/G
M300PBM/G
12
24
36
630
630
630
1250
1250
1250
Conductor sizes (mm2)
min
max
35
35
50
300
300
240
8
11. Kit contents
The complete (K)(M)300PBM/G
coupling connector kit
comprises 3 x the following
components:
The kit also comprises silicone grease, field
control mastic, installation rod, installation
instructions and crimp chart.
Conductor
contact TMBC-X
3 x (K)(M)300PBM/G-W-X
coupling connector kit
Cable reducer
430CA-W
Contact rod
300PB-CR
Voltage
(Um)
(kV)
3 x 300PBM/G-11-X
3 x 300PBM/G-16-X
3 x 300PBM/G-18-X
min
max
12
12
12
12.0
17.0
19.0
17.5
23.5
32.6
3 x K300PBM/G-11-X
3 x K300PBM/G-16-X
3 x K300PBM/G-18-X
24
24
24
12.0
17.0
19.0
17.5
23.5
32.6
3 x M300PBM/G-11-X
3 x M300PBM/G-15-X
3 x M300PBM/G-19-X
3 x M300PBM/G-22-X
3 x M300PBM/G-25-X
3 x M300PBM/G-27-X
36
36
36
36
36
36
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
Table X
35
50
70
95
120
150
185
240
300
Order: Kit MT.
For use with fabric tape
(graphite) screened cables.
Order additional
semi-conductive tape
(type TSC).
35KM-10-1
50(K)M-10-1
70(K)M-10-1
95(K)M-10-1
120(K)M-10-1
150(K)M-10-1
185(K)M-10-1
240(K)M-10-1
–
DIN
hexagonal
Deep
indent
35(K)M-10-2
50(K)M-10-2
70(K)M-10-2
95(K)M-10-2
120(K)M-10-2
150(K)M-10-2
185(K)M-10-2
240(K)M-10-2
300(K)M-10-2
Copper
conductor
Bolted
DIN
hexagonal
For use with
easy strip semi-conductive
screened cables. Order:
Field control mastic
(type MFC).
Aluminium and
copper conductor
Aluminium conductor
Conductor
sizes (mm2)
For use with
copper tape
screened cables.
Dia. over core insulation (mm)
For use with copper
wire screened cables.
No earthing
device is
necessary.
For use with
other cable types.
Please contact our
representative.
120.300-12-5
Example:
The cable is 24 kV, 150 mm2
compact stranded copper with
a diameter over core insulation
of 27.5 mm.
Order 3 x
K300PBM/G-18-95.240-14-5
coupling connector kit.
Ordering
part number
95.240-14-5
To order the coupling connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Table W
50.150-14-5
Ordering instructions
(411CA-W
for 36 kV)
Conductor
contact TBC-X
16.95-14-5
Connector housing
(K)(M)300BP/G
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
For outdoor
applications.
Order: +MWS.
9
12. 430TBM-P2/P3
DUAL/TRIPLE CABLE ARRANGEMENT
FOR 430TB CONNECTOR
Application
Technical characteristics
Separable connectors (bolted
type) for dual (P2) and triple
(P3) cable arrangements.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Design
Up to 36 kV
630 A (1250 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
290 mm
1. Type C interface as
described by CENELEC
EN 50180 and 50181.
2. Bus for 300PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket.
5. Conductive EPDM jacket.
6. Conductive EPDM cap.
7. Basic insulating plug (with
VD point).
8. Conductor connector.
9. Cable reducer.
10. Earthing lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
2
1
6
8
Non-size
sensitive:
290 mm
7
3
Size
sensitive:
350 mm
4
430TBM
connector
300PBM
coupling
connector
5
10
Specifications and
standards
9
The 430TBM-P2/P3 connectors
meet the requirements of
CENELEC HD 629.1.
105 mm
Current Ir (A)
08/2011
Separable
connector
type
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an appropriate equipment
bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact
430TBM-P2/P3
K430TBM-P2/P3
M430TBM-P2/P3
12
24
36
630
630
630
1250
1250
1250
Conductor sizes (mm2)
min
max
35
35
50
300
300
240
10
13. Kit contents
The complete (K)(M)430TBM-P2
connector kit comprises 3 x the
following components:
The complete (K)(M)430TBM-P3
connector kit comprises 3 x the
following components:
395
290
300BIPA
basic
insulating
plug
300BIPA
basic
insulating
plug
300PBM
coupling
connector
300PBM
coupling
connectors
430TB tee
connector
110
430TB tee
connector
105
110
105
105
In mm.
For use with
copper tape
screened cables.
Order: Kit MT.
For use with Alupe or
C 33-226 cables.
Please contact our
representative.
min
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
W
max
11
15
19
22
25
27
Table X
Conductor
sizes (mm2)
35
50
70
95
120
150
185
240
300
For use with
other cable types.
Please contact our
representative.
Aluminium and
copper conductor
DIN
hexagonal
35KM-10-1
50(K)M-10-1
70(K)M-10-1
95(K)M-10-1
120(K)M-10-1
150(K)M-10-1
185(K)M-10-1
240(K)M-10-1
–
DIN
hexagonal
Deep
indent
35(K)M-10-2
50(K)M-10-2
70(K)M-10-2
95(K)M-10-2
120(K)M-10-2
150(K)M-10-2
185(K)M-10-2
240(K)M-10-2
300(K)M-10-2
Copper
conductor
Bolted
Aluminium conductor
For use with
easy strip semi-conductive
screened cables. Order:
Field control mastic
(type MFC).
For applications
outdoors and in
humid climate.
Order: +MWS.
120.300-12-5
Example:
The two cables are 24 kV,
150 mm2 stranded aluminium
with a diameter over core
insulation of 27.5 mm.
Order 3 x K430TBM-P2-22150(K)M-10-2.
Dia. over core
insulation (mm)
95.240-14-5
For triple cable arrangement:
3 x 430TBM-P3-W-X,
for use up to 12 kV.
Add a 'K' for use up to 24 kV:
3 x K430TBM-P3-W-X.
Add an 'M' for use up to 36 kV:
3 x M430TBM-P3-W-X.
Table W
50.150-14-5
To order the separable
connectors for dual cable
arrangement, use the tables
beside to substitute for W and
X in the formula:
3 x 430TBM-P2-W-X,
for use up to 12 kV.
Add a 'K' for use up to 24 kV:
3 x K430TBM-P2-W-X.
Add an 'M' for use up to 36 kV:
3 x M430TBM-P2-W-X.
1. From table W: select the
symbol which gives the best
centring of your core insulation
diameter.
2. From table X: according to
your conductor size and type,
select the designation which
completes the part number.
16.95-14-5
Ordering instructions
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
When installed on an
appropriate equipment
bushing:
1250 A continuously
11
14. 804PB
COUPLING CONNECTOR
FOR 484TB/G
Application
Technical characteristics
Separable coupling connector
(bolted type) for dual cable
arrangement. It has been
designed to be used with
484TB separable Tee connector.
• A thick conductive EPDM
jacket provides a total safe to
touch screen.
• Each separable connector is
tested for AC withstand and
partial discharge prior to
leaving the factory.
Design
1. Interface designed to fit
484TB connector.
2. Bus for 804PB.
3. Conductor connector
(hexagonal crimping, deep
indent crimping or bolted).
4. Conductive EPDM insert.
5. Conductive EPDM jacket.
6. Insulating EPDM layer
moulded between the
insert and the jacket.
7. Cable reducer.
8. Conductive EPDM cap.
9. Basic insulating plug (with
VD point).
10. Earth lead.
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector.
Up to 42 kV
630 A (1250 A)
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20.8/36 (42) kV
290 mm
2
5
360 mm
6
484TB
connector
10
7
The 804PB coupling connector
meets the requirements of
CENELEC HD 629.1.
08/2011
804PB/G
K804PB/G
M804PB/G
P804PB/G
9
4
1
Specifications and
standards
Separable
connector
type
8
3
110 mm
Current
Ir (A)
Voltage
Um
(kV)
Current
Ir
(A)
When installed on an
appropriate equipment bushing
min
max
12
24
36
42
630
630
630
630
1250
1250
1250
1250
50
35
35
35
630
630
630
630
Conductor sizes (mm2)
12
15. Kit contents
The complete (K)(M)(P)804PB/G
coupling connector kit
comprises 3 x the following
components:
The kit also comprises silicone grease, field
control mastic, gloves, roll adhesive tape,
installation instructions and crimp chart.
Conductor
contact TMBC-X
Connector housing
(K)(M)(P)804BP/G
Contact rod
and stud
Ordering instructions
To order the coupling connector,
select the ordering part number
which gives you the best
centring of your core insulation diameter and substitute X
using table X, according to your
conductor size and type.
Add a 'K' for use up to 24 kV,
add an 'M' for use up to 36 kV,
add a 'P' for use up to 42 kV.
Example:
The copper wire screened cable
is 36 kV, 240 mm2 stranded
aluminium with a diameter over
core insulation of 37.0 mm.
Order 3 x M804PB/G-32240(K)M-12-2 coupling
connector kit.
3 x (K)(M)(P)804PB/G-W-X
coupling connector kit
Conductor
contact TBC-X
Cable reducer
611CA-W
Table W
Dia. over core insulation (mm)
Ordering
part number
min
16.0
20.0
23.5
28.5
34.0
39.0
45.5
3 x 804PB/G-15-X
3 x 804PB/G-19-X
3 x 804PB/G-22-X
3 x 804PB/G-27-X
3 x 804PB/G-32-X
3 x 804PB/G-37-X
3 x 804PB/G-43-X
max
22.0
26.5
31.0
37.5
42.5
48.5
56.0
Table X
Conductor sizes
(mm2)
Aluminium conductor
Aluminium and
copper conductor
Copper
conductor
Bolted
DIN
hexagonal
50KM-12-1
70
70(K)M-12-2
70KM-12-1
95
95(K)M-12-2
95KM-12-1
120
120(K)M-12-2
120KM-12-1
150(K)M-12-2
150KM-12-1
185(K)M-12-2
185KM-12-1
240(K)M-12-2
240KM-12-1
300(K)M-12-2
300KM-12-1
300(K)M-11-2
400
400(K)M-12-2
400KM-12-1
400(K)M-11-2
500
500(K)M-12-2
500KM-12-1
500(K)M-11-2
630
–
630KM-12-1
630(K)M-11-2
For use with
other cable types.
Please contact our
representative.
For applications
outdoors and in
humid climate.
Order: +MWS.
35(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
120.300-12-5
50.150-14-5
50(K)M-11-2
95.240-14-5
16.95-14-5
35KM-12-1
50(K)M-12-2
300
No earthing
device is
necessary.
35(K)M-12-2
50
240
Order: Kit MT.
35
185
For use with copper
wire screened cables.
Deep
indent
150
For use with
copper tape
screened cables.
DIN
hexagonal
Components can be
ordered individually.
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
When installed on an
appropriate equipment
bushing:
1250 A continuously
13
16. 300SA
SURGE ARRESTER
FOR 430TB CONNECTOR
Application
Technical characteristics
Surge arrester designed to
protect 12, 24 and 36 kV
class components, including
transformers, equipment, cable
and accessories from high
voltage surges resulting from
lightning or switching.
It has been designed to be used
with the 430TB separable tee
connector.
• This surge arrester is a metal
oxide varistor surge arrester in
an elbow configuration.
• Each arrester is tested for AC
withstand, partial discharge
and critical voltage prior to
leaving the factory.
Design
Up to 36 kV
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
170 mm
Surge arrester comprising:
1. Interface designed to fit
the 430TB/G tee connector.
2. Conductive EPDM insert.
3. Conductive EPDM jacket.
4. Insulating EPDM layer
moulded between the insert
and the jacket.
5. Receptacle for contact rod.
6. Metal oxide valve elements.
7. Steel cap.
8. Earth connection.
9. Earth lead.
105 mm
Dia.
75 mm
1
5
2
3
L2
L1
Specifications and
standards
9
4
6
The 300SA surge arresters meet
the test requirements of IEC
60099-4.
Dia.
65 mm
7
8
08/2011
Surge
arrester
type
Nominal
discharge
current
In (kA)
Rated
voltage
Ur (kV)
Max. continuous
operating
voltage
Uc (kV)
L1
L2
300SA-10-15N
300SA-10-18N
300SA-10-22N
300SA-10-24N
300SA-10-30N
300SA-10-36N
300SA-10-45N
10
10
10
10
10
10
10
15
18
22
24
30
36
45
12.0
14.4
17.6
19.2
24.0
28.8
36.0
250
250
250
350
350
350
450
290
290
290
390
390
390
490
Dimensions
(mm)
14
17. Typical application and
dimensions
Ordering instructions
To order the surge arrester,
specify the surge arrester type,
as described on previous page.
290 mm
180 mm
Example:
For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 300SA-10-30N surge
arrester.
107 mm
Type 300SA
surge arrester
Type 430TB
tee connector
Technical data
Surge
arrester
type
Steep current
residual
voltage @ 10 kA
[1/20 µs] (kV)
300SA-10-15N
300SA-10-18N
300SA-10-22N
300SA-10-24N
300SA-10-30N
300SA-10-36N
300SA-10-45N
48.1
58.1
70.1
77.0
97.0
115.9
144.1
Lightning current
residual voltage
[8/20 µs] (kV)
Switching impulse
residual voltage
[36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
39.7
48.0
57.9
63.6
80.1
95.7
119.0
43.2
52.2
63.0
69.2
87.2
104.2
129.5
48.4
58.5
70.6
77.6
97.7
116.8
145.1
30.5
36.8
44.4
48.8
61.5
73.5
91.3
32.5
39.2
47.3
52.0
65.5
78.3
97.3
High current
impulse
withstand
(kA)
100
100
100
100
100
100
100
15
18. 800SA
SURGE ARRESTER
FOR 484TB CONNECTOR
Application
Technical characteristics
Surge arrester designed to
protect 12, 24, 36 and 42 kV
class components, including
transformers, equipment, cable
and accessories from high
voltage surges resulting from
lightning or switching.
It has been designed to be used
with the 484TB separable tee
connector.
• This surge arrester is a metal
oxide varistor surge arrester in
an elbow configuration.
• Each arrester is tested for AC
withstand, partial discharge
and critical voltage prior to
leaving the factory.
Design
Up to 42kV
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20.8/36 (42) kV
170 mm
Surge arrester comprising:
1. Interface designed
to fit he 484TB
t
tee connector.
2. Conductive EPDM insert.
3. Conductive EPDM jacket.
4. Insulating EPDM layer
moulded between the insert
and the jacket.
5. Receptacle for contact rod.
6. Metal oxide valve elements.
7. Steel cap.
8. Earth connection.
9. Earth lead.
105 mm
Dia.
75 mm
1
5
2
L2
3
L1
9
4
Specifications and
standards
6
The 800SA surge arresters meet
the test requirements of IEC
60099-4.
Dia.
65 mm
7
8
08/2011
Surge
arrester
type
Nominal
discharge
current
In (kA)
Rated
voltage
Ur (kV)
Max. continuous
operating
voltage
Uc (kV)
L1
L2
800SA-10-15N
800SA-10-18N
800SA-10-22N
800SA-10-24N
800SA-10-30N
800SA-10-36N
800SA-10-45N
10
10
10
10
10
10
10
15
18
22
24
30
36
45
12.0
14.4
17.6
19.2
24.0
28.8
36.0
250
250
250
350
350
350
450
290
290
290
390
390
390
490
Dimensions
(mm)
16
19. Typical application and
dimensions
Ordering instructions
To order the surge arrester,
specify the surge arrester type,
as described on previous page.
290 mm
180 mm
Example:
For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 800SA-10-30N surge
arrester.
110 mm
Type 800SA
surge arrester
Type
484TB
tee
connector
Technical data
Surge
arrester
type
Steep current
residual
voltage @ 10 kA
[1/20 µs] (kV)
800SA-10-15N
800SA-10-18N
800SA-10-22N
800SA-10-24N
800SA-10-30N
800SA-10-36N
800SA-10-45N
48.1
58.1
70.1
77.0
97.0
115.9
144.1
Lightning current
residual voltage
[8/20 µs] (kV)
Switching impulse
residual voltage
[36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
39.7
48.0
57.9
63.6
80.1
95.7
119.0
43.2
52.2
63.0
69.2
87.2
104.2
129.5
48.4
58.5
70.6
77.6
97.7
116.8
145.1
30.5
36.8
44.4
48.8
61.5
73.5
91.3
32.5
39.2
47.3
52.0
65.5
78.3
97.3
High current
impulse
withstand
(kA)
100
100
100
100
100
100
100
17
20. 400TR and 800TR
INTERFACE C
TEST RODS
Application
• The test rod can be used for:
- cable fault location
- cable testing
- phasing checks, etc.
• Connections may be made
with a cable lug, a 4 mm
plug or spring clips.
Technical characteristics
• The 400TR test rod can be
used with 430TB connectors.
• The 800TR is for use with the
484TB.
400TR
Design
1. nsulating shroud.
I
2. Threaded rod for test
connection.
3. Two nuts M12.
4. Insulation.
5. Copper test rod stem.
6. Wing nut.
An insulating shroud is
provided to allow the
application of test voltages
when bushings are closely
spaced.
1
1
M12
2
3
M12
2
40
3
480
Installation
The test rod is mounted on
to the clamping screw in
the type C interface tee and
coupling connectors. The
test cable is connected to
the threaded stem and the
insulating shroud moved to its
final position over the end of
the test rod.
800TR
480
321,5
4
288
4
5
5
Ordering instructions
Simply specify:
400TR or 800TR test rod.
In mm.
08/2011
Test rod
type
Maximum A.C.
test voltage
(50 Hz - 1 min)
Maximum D.C.
test voltage
(8 x U0 - 30 min)
Impulse voltage
(1.2 x 50 µs)
min
400TR
800TR
36 kV
36 kV
96 kV
96 kV
95 kV
95 kV
18
21. 400TK and 400SW
INSTALLATION TOOL
Application
• The 400SW box spanner
key fits on the hex nut of the
400BIPA basic insulating
plug.
• The box spanner and box
spanner key are designed
to facilitate assembly of
400TE, 400TB and 440TB
connectors.
• The 400TK box spanner is
used to install the 400TEF
clamping pin contact or
400TCS clamping screw.
400SW
400TK
Ordering instructions
08/2011
Simply specify:
- 400TK box spanner
- 400SW box spanner key
19
22. ACCESSORIES
INTERFACE C
Application
For use with connectors and
bushings with an interface C
as described by CENELEC EN
50180 and 50181.
400DR-B
Dead-end receptacle
Fits over a bushing with a type
C interface to provide 'deadend' facility.
400SOP-B
Stand-off plug
Is designed to support and
'dead-end' connectors with a
type C interface when removed
from equipment.
400GP-B
Earthing plug
Is designed to support and
earth connectors with a type C
interface when removed from
equipment.
08/2011
300GP-B
Earthing plug
Is designed to earth the 430TB
connectors when it is fixedmounted to the equipment
(maintenance earthing).
Technical characteristics
All these products, except the
earthing plugs, are tested for
AC withstand and partial
discharge prior to leaving
the factory.
Up to 36 kV
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
20,8/36 (42) kV
Ordering instructions
Order
400DR-B for 12 kV,
K400DR-B for 24 kV or
M400DR-B for 36 kV
applications.
The dead-end receptacle can
be supplied with an earth lead.
Order with suffix -/G.
E.g. K400DR-B/G.
Ordering instructions
Order
400SOP-B for 12 kV,
K400SOP-B for 24 kV,
M400SOP-B for 36 kV or
P400SOP-B for 42 kV
applications.
Ordering instructions
Order
400GP-B for 12, 24, 36 or
42 kV applications.
Ordering instructions
Order
300GP-B for 12, 24, 36 or
42 kV applications.
20
23. 800GP-B
Earthing plug
Is designed to earth the 484TB
connectors when it is fixedmounted to the equipment
(maintenance earthing).
400BIPA
Basic insulating plug
Acts as a tightening nut for
the 400TB and 440TB tee
connector kits.
The plug contains a voltage
detection point.
The conductive rubber
protection cap is included.
Kit MT
Earthing kit for copper
tape screened cables
Contains a tinned copper braid
(25 mm² - L = 500 mm), a
tinned copper wire for cleating
and some water sealing mastic.
Ordering instructions
Order
800GP-B for 12, 24, 36 or
42 kV applications.
Ordering instructions
Order
400BIPA for 12 kV,
K400BIPA for 24 kV
M400BIPA for 36 kV or
P400BIPA for 42 kV
applications.
Ordering instructions
Order
Kit MT for 12 kV, 24 kV
36 kV or 42 kV applications.
21
24. POSSIBLE ARRANGEMENTS
INTERFACE C
430TB
430TBM-P2
Single cable arrangement.
Order 430TB for 12 kV,
K430TB for 24 kV or M430TB
for 36 kV applications.
Dual cable arrangement.
Order 430TBM-P2 for 12 kV,
K430TBM-P2 for 24 kV or
M430TBM-P2 for 36 kV
applications.
290
300BIPA
basic
insulating
plug
300PBM
coupling
connector
430TB tee
connector
110
105
430TBM-P3
430TBM-L3
Triple cable arrangement.
Order 430TBM-P3 for 12 kV,
K430TBM-P3 for 24 kV or
M430TBM-P3 for 36 kV
applications.
3-way connection.
Order 430TBM-L3 for 12 kV,
K430TBM-L3 for 24 kV or
M430TBM-L3 for 36 kV
applications.
425
395
300BIPA
basic
insulating
plug
300PBM
coupling
connectors
430TB tee
connector
08/2011
110
105
400BIPA
basic
insulating
plug
300BIPA
basic
insulating
plug
300PBM
coupling
connectors
430TB tee
connector
105
In mm.
22
25. 484TB
484TB-P2
Single cable arrangement.
Order 484TB for 12 kV,
K484TB for 24 kV, M484TB
for 36 kV or P484TB for 42 kV
applications.
Dual cable arrangement.
Order 484TB-P2 for 12 kV,
K484TB-P2 for 24 kV or
M484TB-P2 for 36 kV
or P484TB-P2 for 42kV
applications.
185
290
800BIPA
basic
insulating
plug
800BIPA
basic
insulating
plug
484TB tee
connector
804PB
coupling
connector
484TB tee
connector
110
110
110
484TB-P2 + 800SA
Dual cable arrangement with
surge arrester.
Order 484TB-P2+800SA for
12 kV, K484TB-P2+800SA for
24 kV, M484TB-P2+800SA for
36 kV or P484TB-P2+800SA
for 42 kV applications.
400
800BIPA
basic
insulating
plug
800SA
surge
arrester
804PB
coupling
connector
110
110
484TB tee
connector
23
26. Earthing plug on
connector
Order 300GP-B for 12 kV,
24 kV and 36 kV applications.
Order 800GP-B for 12 kV,
24 kV, 36 kV or 42 kV
applications.
800GP-B
earthing plug
484TB tee
connector
Cable and equipment
testing
800TR
test rod
insulating
schroud
484TB tee
connector
08/2011
110
In mm.
24
27.
28. Additional catalogue information on power cable accessories
is available by contacting us at the address below:
Distributed by:
Tel: +44 (0)191 490 1547
Nexans Network Solutions N.V. - Div. Euromold • Zuid III, Industrielaan 12, B-9320 Erembodegem
Fax: +44 (0)191 477 5371
Tel.: +32 (0)53 85 02 11 • Fax: +32 (0)53 83 10 13 • www.nexans.com • info.euromold@nexans.com
08/2011
a Nexans company
Email: northernsales@thorneandderrick.co.uk
Catalogue also available on CD-ROM Website: www.cablejoints.co.uk
www.thorneanderrick.co.uk