MAGNETIC OIL LEVEL
GAUGE IN THE
CONSERVATOR TANK OF
THE TRANSFORMER
• BY
• JULIUS ALOWONLE
•
JULIUSALOWONLE
MAGNETIC OIL GAUGE
JULIUSALOWONLE
INTRODUCTION
Magnetic oil level gauge (MOG) or A liquid level indicator is
provided to aid in the systematic inspection of the transformer
under load. It consists of a float-arm inside the tank, an
indicating pointer and a magnetic coupling between the two
across a liquid-tight separation. The gauge may be furnished
with SPDT (Single Pole Double Throw) alarm contacts to give a
remote annunciation of low liquid level.
Magnetic oil level gauge-This is a mechanical device used to
indicate the position of transformer insulating oil level in the
conservator tank of a transformer.
JULIUSALOWONLE
MAINLY PARTS
These parts are
• A float.
• Bevel gear arrangement (magnetic coupled linked to the pointer ).
• An indicating dial ( pointer movement by magnetic field )
incorporate with mercury switch.
JULIUSALOWONLE
OPERATION PRINCIPLES
•Float Bevel gear Indicating dial Mercury switch
• (Alarm)
Movement Gear rotation Movement
by oil level (magnetic coupled) by pointer
expansion
JULIUSALOWONLE
CONSTRUCTION
•A ball or drum type float is attached to the bevel gear which is
magnetically coupled with the pointer. The movement of the
float is associate with the rotation of the bevel gear and the
pointer due to the rise and fall of the insulation oil in the
transformer conservator tank.
•The magnetic field between the bevel gear and the pointer
initiate the rotation of the pointer (clockwise or anti-clockwise)
•along the dial.
•The dial has a scale from EMPTY, ¼, ½, ¾, and FULL.
•The prescribed oil level at either 30 oC or 35 oC ambient
temperature may also be indicated on the dial (filling level).
•The mercury switch is fixed with the pointer which when rotates
,the alignment of the mercury switch also changes to energized
an alarm during empty indication.
JULIUSALOWONLE
WORKING PRINCIPLE
Electrical power transformer is incorporated with conservator
tank for expansion and reduction of insulation oil due to
temperature rise and fall during it working time.
Power transformer s are provided with a magnetic oil level
gauge. In the conservator tank, a light weight hollow ball or
drum floats attached to the bevel gear arm. The position of the
float goes up and down depending on the level of oil in the
conservator tank. The bevel gear rotates and transmitted to the
pointer outside the conservator tank , as this pointer is
magnetically coupled with the bevel gear. The pointer is also
incorporate with a mercury switch. When the pointer reaches
empty on the dial of MOG, this switch closes and actuate an
alarm for attention for topping up oil in the power transformer
JULIUSALOWONLE
MAGNETIC OIL LEVEL GAUGE
JULIUSALOWONLE
WHY TEMPERATURE DEGREE
INDICATOR SHOWN ON MOG ?
• The oil levels are generally indicated on the MOG dial as
‘Empty’, 1/4, 1/2, 3/4 and ‘Full’. But in between these levels
usually 300C temperature indication is also shown. This is
because oil level in the conservator tank changes according to
the ambient temperature. The hotter the temperature, the
more will be the oil level in the conservator tank due to
expansion and vice versa. So, as the oil level depends on the
ambient temperature, we must have an indication to what
level the oil is to be filled at a certain temperature. This is why
the level is indicated in temperature degrees so that when
the ambient temperature is same as the temperature
indicated on that MOG dial, the oil level should reach that
mark to ensure that the Transformer has sufficient oil level in
the conservator.
JULIUSALOWONLE
ADVANTAGES
• Continuous oil level monitoring – with ease in reading at men
height.
• Magnetic couplings ensures a reliable movement transmission
between float arm and pointer avoiding leakages through
conservator wall.
• Initiate alarm at EMPTY oil level.
• Adjustable value settings for switches at ambient
temperature.
• No printings neither stickers on the view glass: temperature
indication is directly marked on the plate behind the view
glass.
• Modern technology MOG are equipped with data
downloading device.
JULIUSALOWONLE
LIMITATIONS
• MOG is not incorporated with tripping relay.
• MOG is used only for measuring oil level in the conservator
tank.
• It is not a fault detecting device.
• MOG may loss is reading vision on aging transformer due
weather changes.
JULIUSALOWONLE
REFERENCES
• PRINCIPLE OF POWER SYSTEM BY V.K. MEHTA.
• 33/11KV, 3X15MVA INJECTION SUBSTATION OGUDU, IKEJA
ELECTRIC LAGOS.
• www.electrical4u.com
• www.wikipedia.org
JULIUSALOWONLE

More Related Content

What's hot

RELAY
RELAYRELAY
Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"
Harshit Srivastava
 
Presentation of Manufacturing Of Distribution Transformer (Prodip)
Presentation of Manufacturing Of Distribution Transformer (Prodip)Presentation of Manufacturing Of Distribution Transformer (Prodip)
Presentation of Manufacturing Of Distribution Transformer (Prodip)
Prodip Das Durjoy
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
Power System Operation
 
Transformer Oil Testing.pptx
Transformer Oil Testing.pptxTransformer Oil Testing.pptx
Transformer Oil Testing.pptx
MADHUSMITA MOHANTY
 
Protective relay
Protective relay Protective relay
Protective relay
Uday Wankar
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
Dr. Selvarasu Ranganathan
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
Induction Motor Speed Control Drive, Design and Implementation
Induction Motor Speed Control Drive, Design and ImplementationInduction Motor Speed Control Drive, Design and Implementation
Induction Motor Speed Control Drive, Design and Implementation
Nasrullah Khan
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
Indiran K
 
Faults in Power System
Faults in Power SystemFaults in Power System
Faults in Power System
Avijit Adhikary
 
Breaker Operation & Maintenance
Breaker Operation & MaintenanceBreaker Operation & Maintenance
Breaker Operation & Maintenance
Sheikh Nazmul Islam
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
Vincent Wedelich, PE MBA
 
What is a buchholz relay
What is a buchholz relayWhat is a buchholz relay
What is a buchholz relay
Dr.Raja Masood Larik
 
CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...
CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...
CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...
Prasant Kumar
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
jawaharramaya
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
Adnan Sayed
 
Three phase transformer ( vector groups)
Three phase  transformer ( vector groups)Three phase  transformer ( vector groups)
Three phase transformer ( vector groups)
Dr.Raja Masood Larik
 

What's hot (20)

RELAY
RELAYRELAY
RELAY
 
Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"
 
Presentation of Manufacturing Of Distribution Transformer (Prodip)
Presentation of Manufacturing Of Distribution Transformer (Prodip)Presentation of Manufacturing Of Distribution Transformer (Prodip)
Presentation of Manufacturing Of Distribution Transformer (Prodip)
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
Transformer Oil Testing.pptx
Transformer Oil Testing.pptxTransformer Oil Testing.pptx
Transformer Oil Testing.pptx
 
Protective relay
Protective relay Protective relay
Protective relay
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Induction Motor Speed Control Drive, Design and Implementation
Induction Motor Speed Control Drive, Design and ImplementationInduction Motor Speed Control Drive, Design and Implementation
Induction Motor Speed Control Drive, Design and Implementation
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
 
Lightning arresters
Lightning arrestersLightning arresters
Lightning arresters
 
Faults in Power System
Faults in Power SystemFaults in Power System
Faults in Power System
 
Breaker Operation & Maintenance
Breaker Operation & MaintenanceBreaker Operation & Maintenance
Breaker Operation & Maintenance
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
75181713.pdf
75181713.pdf75181713.pdf
75181713.pdf
 
What is a buchholz relay
What is a buchholz relayWhat is a buchholz relay
What is a buchholz relay
 
CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...
CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...
CONDUCTION & BREAKDOWN IN LIQUID DIELECTRICS|HIGH VOLTAGE ENGINEERING|ELECTRI...
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Three phase transformer ( vector groups)
Three phase  transformer ( vector groups)Three phase  transformer ( vector groups)
Three phase transformer ( vector groups)
 

Similar to MAGNETIC GAUGE IN THE CONSERVATOR TANK OF THE

DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
Jobin Abraham
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection system
Sachin Pyasi
 
Day 07 Governor and Ignition System
Day 07 Governor and Ignition SystemDay 07 Governor and Ignition System
Day 07 Governor and Ignition System
Suyog Khose
 
On off controller
On off controllerOn off controller
On off controller
SayanSarkar55
 
Variable Valve Timing
Variable Valve TimingVariable Valve Timing
Variable Valve Timing
Sourav Bagchi
 
Inspection and Testing of various electrical equipment
Inspection and Testing of various electrical equipmentInspection and Testing of various electrical equipment
Inspection and Testing of various electrical equipment
AkankshaSharma570781
 
Seal Oil System.pptx
Seal Oil System.pptxSeal Oil System.pptx
Seal Oil System.pptx
SaravananKumar264695
 
TURBINE_GOVERNING KWU.pdf
TURBINE_GOVERNING KWU.pdfTURBINE_GOVERNING KWU.pdf
TURBINE_GOVERNING KWU.pdf
SaravananKumar264695
 
Governing system
Governing systemGoverning system
Governing system
Ashish Kumar Jain
 
STEAM TURBINES Governing System & TROUBLE SHOOTING
STEAM TURBINES Governing System & TROUBLE SHOOTINGSTEAM TURBINES Governing System & TROUBLE SHOOTING
STEAM TURBINES Governing System & TROUBLE SHOOTING
Ashish Kumar Jain
 
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptxMOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
KBR-AMCDE
 
Converter c8000
Converter c8000Converter c8000
Converter c8000
Gustavo De Haro
 
Transformer
TransformerTransformer
Transformer
karthickaashi
 
buchholz relay on transformer
buchholz relay on transformerbuchholz relay on transformer
buchholz relay on transformer
AbhishekLalkiya
 
Oil filled transformer accessories - copy
Oil  filled  transformer   accessories - copyOil  filled  transformer   accessories - copy
Oil filled transformer accessories - copy
ayyadurai SHANMUGAM
 
Torque converter operation & maintenance
Torque converter operation & maintenanceTorque converter operation & maintenance
Torque converter operation & maintenance
Prem Baboo
 
applictions of actuators
applictions of actuatorsapplictions of actuators
applictions of actuators
Yasir Hashmi
 
Diesel fuel 4_d5_stepiii
Diesel fuel 4_d5_stepiiiDiesel fuel 4_d5_stepiii
Diesel fuel 4_d5_stepiii
Atilio Marchisio
 
Handout.pptx
Handout.pptxHandout.pptx
Handout.pptx
DitaGGemechu
 

Similar to MAGNETIC GAUGE IN THE CONSERVATOR TANK OF THE (20)

DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
DESIGN OF DC MACHINES AND TRANSFORMER. various protective and indicative inst...
 
Governing and protection system
Governing and protection systemGoverning and protection system
Governing and protection system
 
Day 07 Governor and Ignition System
Day 07 Governor and Ignition SystemDay 07 Governor and Ignition System
Day 07 Governor and Ignition System
 
On off controller
On off controllerOn off controller
On off controller
 
Variable Valve Timing
Variable Valve TimingVariable Valve Timing
Variable Valve Timing
 
Inspection and Testing of various electrical equipment
Inspection and Testing of various electrical equipmentInspection and Testing of various electrical equipment
Inspection and Testing of various electrical equipment
 
Seal Oil System.pptx
Seal Oil System.pptxSeal Oil System.pptx
Seal Oil System.pptx
 
Symetro Presentation
Symetro PresentationSymetro Presentation
Symetro Presentation
 
TURBINE_GOVERNING KWU.pdf
TURBINE_GOVERNING KWU.pdfTURBINE_GOVERNING KWU.pdf
TURBINE_GOVERNING KWU.pdf
 
Governing system
Governing systemGoverning system
Governing system
 
STEAM TURBINES Governing System & TROUBLE SHOOTING
STEAM TURBINES Governing System & TROUBLE SHOOTINGSTEAM TURBINES Governing System & TROUBLE SHOOTING
STEAM TURBINES Governing System & TROUBLE SHOOTING
 
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptxMOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
MOTORISED VALVE ACTUATORS_SANTHIRAJ001.pptx
 
Converter c8000
Converter c8000Converter c8000
Converter c8000
 
Transformer
TransformerTransformer
Transformer
 
buchholz relay on transformer
buchholz relay on transformerbuchholz relay on transformer
buchholz relay on transformer
 
Oil filled transformer accessories - copy
Oil  filled  transformer   accessories - copyOil  filled  transformer   accessories - copy
Oil filled transformer accessories - copy
 
Torque converter operation & maintenance
Torque converter operation & maintenanceTorque converter operation & maintenance
Torque converter operation & maintenance
 
applictions of actuators
applictions of actuatorsapplictions of actuators
applictions of actuators
 
Diesel fuel 4_d5_stepiii
Diesel fuel 4_d5_stepiiiDiesel fuel 4_d5_stepiii
Diesel fuel 4_d5_stepiii
 
Handout.pptx
Handout.pptxHandout.pptx
Handout.pptx
 

MAGNETIC GAUGE IN THE CONSERVATOR TANK OF THE

  • 1. MAGNETIC OIL LEVEL GAUGE IN THE CONSERVATOR TANK OF THE TRANSFORMER • BY • JULIUS ALOWONLE • JULIUSALOWONLE
  • 3. INTRODUCTION Magnetic oil level gauge (MOG) or A liquid level indicator is provided to aid in the systematic inspection of the transformer under load. It consists of a float-arm inside the tank, an indicating pointer and a magnetic coupling between the two across a liquid-tight separation. The gauge may be furnished with SPDT (Single Pole Double Throw) alarm contacts to give a remote annunciation of low liquid level. Magnetic oil level gauge-This is a mechanical device used to indicate the position of transformer insulating oil level in the conservator tank of a transformer. JULIUSALOWONLE
  • 4. MAINLY PARTS These parts are • A float. • Bevel gear arrangement (magnetic coupled linked to the pointer ). • An indicating dial ( pointer movement by magnetic field ) incorporate with mercury switch. JULIUSALOWONLE
  • 5. OPERATION PRINCIPLES •Float Bevel gear Indicating dial Mercury switch • (Alarm) Movement Gear rotation Movement by oil level (magnetic coupled) by pointer expansion JULIUSALOWONLE
  • 6. CONSTRUCTION •A ball or drum type float is attached to the bevel gear which is magnetically coupled with the pointer. The movement of the float is associate with the rotation of the bevel gear and the pointer due to the rise and fall of the insulation oil in the transformer conservator tank. •The magnetic field between the bevel gear and the pointer initiate the rotation of the pointer (clockwise or anti-clockwise) •along the dial. •The dial has a scale from EMPTY, ¼, ½, ¾, and FULL. •The prescribed oil level at either 30 oC or 35 oC ambient temperature may also be indicated on the dial (filling level). •The mercury switch is fixed with the pointer which when rotates ,the alignment of the mercury switch also changes to energized an alarm during empty indication. JULIUSALOWONLE
  • 7. WORKING PRINCIPLE Electrical power transformer is incorporated with conservator tank for expansion and reduction of insulation oil due to temperature rise and fall during it working time. Power transformer s are provided with a magnetic oil level gauge. In the conservator tank, a light weight hollow ball or drum floats attached to the bevel gear arm. The position of the float goes up and down depending on the level of oil in the conservator tank. The bevel gear rotates and transmitted to the pointer outside the conservator tank , as this pointer is magnetically coupled with the bevel gear. The pointer is also incorporate with a mercury switch. When the pointer reaches empty on the dial of MOG, this switch closes and actuate an alarm for attention for topping up oil in the power transformer JULIUSALOWONLE
  • 8. MAGNETIC OIL LEVEL GAUGE JULIUSALOWONLE
  • 9. WHY TEMPERATURE DEGREE INDICATOR SHOWN ON MOG ? • The oil levels are generally indicated on the MOG dial as ‘Empty’, 1/4, 1/2, 3/4 and ‘Full’. But in between these levels usually 300C temperature indication is also shown. This is because oil level in the conservator tank changes according to the ambient temperature. The hotter the temperature, the more will be the oil level in the conservator tank due to expansion and vice versa. So, as the oil level depends on the ambient temperature, we must have an indication to what level the oil is to be filled at a certain temperature. This is why the level is indicated in temperature degrees so that when the ambient temperature is same as the temperature indicated on that MOG dial, the oil level should reach that mark to ensure that the Transformer has sufficient oil level in the conservator. JULIUSALOWONLE
  • 10. ADVANTAGES • Continuous oil level monitoring – with ease in reading at men height. • Magnetic couplings ensures a reliable movement transmission between float arm and pointer avoiding leakages through conservator wall. • Initiate alarm at EMPTY oil level. • Adjustable value settings for switches at ambient temperature. • No printings neither stickers on the view glass: temperature indication is directly marked on the plate behind the view glass. • Modern technology MOG are equipped with data downloading device. JULIUSALOWONLE
  • 11. LIMITATIONS • MOG is not incorporated with tripping relay. • MOG is used only for measuring oil level in the conservator tank. • It is not a fault detecting device. • MOG may loss is reading vision on aging transformer due weather changes. JULIUSALOWONLE
  • 12. REFERENCES • PRINCIPLE OF POWER SYSTEM BY V.K. MEHTA. • 33/11KV, 3X15MVA INJECTION SUBSTATION OGUDU, IKEJA ELECTRIC LAGOS. • www.electrical4u.com • www.wikipedia.org JULIUSALOWONLE