Insulator string Questions
1. I n a 6 unit suspension insulator string, the capacitance between each link and pin and earth is
   0.1 of the self capacitance of each unit. Determine the voltage across the lowest unit as a
   percentage of the total voltage and also the string efficiency.                   [58.29%]



2. Find the voltage distribution and string efficiency of a three unit suspension insulator string of a
   three unit suspension insulator string if the capacitances of the link pins to earth and to the line
   are respectively 20% and 10% of the self capacitance of each unit. If a guard ring increases the
   capacitance to the line of lower link pin to 35% of the self capacitance of each unit, find the
   redistribution of voltage and string efficiency.

                    [0.31V, 0.303V, 0.387V, 86.13%; 0.3299V, 0.328887V, 0.34123V, 97.68%]



3. Each conductor of a three phase overhead line is suspendedfrom a cross armof a steel tower by
   a string of 4 suspension insulators. The voltage across the second unit is 14.2kV and across the
   third 20kV. Find the voltage between the conductors and the string efficiency.

                                                                               [131.79kV, 62.78%]



4. In a string of three insulator units, the capacitance of each unit is C, from each conductor to
   ground is C/3, and from each connector to the line conductor is C/5. Calculate the voltage across
   each unit as a % of the total voltage. To what value the capacitance between the connector of
   the bottom unit and the line has to be increased by a guard ring to make the voltage across it
   equal to that across the next higher unit?                  [31.5%, 28.3%, 40.196%; 0.6833C]

Insulator String

  • 1.
    Insulator string Questions 1.I n a 6 unit suspension insulator string, the capacitance between each link and pin and earth is 0.1 of the self capacitance of each unit. Determine the voltage across the lowest unit as a percentage of the total voltage and also the string efficiency. [58.29%] 2. Find the voltage distribution and string efficiency of a three unit suspension insulator string of a three unit suspension insulator string if the capacitances of the link pins to earth and to the line are respectively 20% and 10% of the self capacitance of each unit. If a guard ring increases the capacitance to the line of lower link pin to 35% of the self capacitance of each unit, find the redistribution of voltage and string efficiency. [0.31V, 0.303V, 0.387V, 86.13%; 0.3299V, 0.328887V, 0.34123V, 97.68%] 3. Each conductor of a three phase overhead line is suspendedfrom a cross armof a steel tower by a string of 4 suspension insulators. The voltage across the second unit is 14.2kV and across the third 20kV. Find the voltage between the conductors and the string efficiency. [131.79kV, 62.78%] 4. In a string of three insulator units, the capacitance of each unit is C, from each conductor to ground is C/3, and from each connector to the line conductor is C/5. Calculate the voltage across each unit as a % of the total voltage. To what value the capacitance between the connector of the bottom unit and the line has to be increased by a guard ring to make the voltage across it equal to that across the next higher unit? [31.5%, 28.3%, 40.196%; 0.6833C]