Prepared by Joshua Burroughs & Jeff
Carrara
IEEE PES
Highgate
Converter
Overview
2
2
Highgate Converter
Abstract
• Introduction to HVDC
• Background on Highgate
• Operation and Control schemes of Highgate
3
3
Why Use HVDC?
• Fast and accurate control of power transfer not dependent
on system angles
• Interconnection between asynchronous systems
– Frequency and Voltage independent
• Provides isolation from system disturbances in other
system
• To transmit large bulk power over a long distance
– Losses proportional to current squared
– AC systems also have reactive power & losses
– Long AC systems use series capacitors to automatically compensate
vars
• This can cause sub-synchronous resonance which can harm machines
• Line breakers need to have higher ratings for transient recovery voltage
– DC terminals also have real and reactive power losses but they occur
only at the injection points and can be more easily compensated
– Loss savings for and Cost savings DC vs. AC line losses occurs at
long distances
4
4
• AC is converted into DC (Rectifier Side)
• DC is then converted into AC (Inverter Side)
• Both use controlled electronic switches (Thyristors) to
allow current to flow in a controlled fashion
– Thyristors turn on (allow current flow) occurs due to a gate pulse and
can be delayed but naturally turn-off when current tries to reverse
• By adjusting firing delay angles of the Thyristors, we can
control the magnitude of DC voltage of the rectifier and
inverter.
– The difference of the DC voltages impacts the magnitude of current
and power flow Idc=(Vrect-Vinv)/Rdc Pdc=Vdc*Idc
– The polarity (which side is higher) controls the direction of power flow
– The converter transformers determine magnitude of the voltage on
the dc side and therefore the maximum possible DC voltage
• Harmonics are produced because of the 12-pulse current
steps compared to sinusoidal currents
Basic Principle
5
5
• 6 pulse, 10° firing angle (15° offset, thyristor off delay)
• 6 pulse, 40° firing angle, lower DC (and MW)
• 12 Pulse, 10° firing angle
Basic Principle
Waveform examples – Rectifier (AC to DC)
6
6
• Monopolar HVDC connections
• No DC Transmission Line (just a bus)
• Both converters are located at the same site
• Utilize 12-pulse converter units on both the Rectifier
and Inverter sides
• Valves can be located in one Valve hall – Option
Smoothing Reactor reduces negative sequence
coupling
Back-to-Back Converters
7
7
• What are the reasons HVDC is utilized?
– Direct accurate Control of power transfer
– Interconnections between Asynchronous systems
– Provides isolation from system disturbances
– Transmission of Bulk power of Long Distances
– No restrictions on cable length while AC Cables must be less than
~40 km
• The terms Rectifier & Inverter refer to what functions?
– A Rectifier converts AC to DC
– An Inverter converts DC to AC
– Either converter can be either rectifier or inverter
• Firing Angle has what impact on the DC and Power Flow?
– Adjusting the firing delay angle adjusts the magnitude of the DC
voltage
– Magnitude and polarity of the DC voltage affects the magnitude and
direction of Power flow
HVDC Review
8
8
Background
of the Highgate Converter
• 225 MW BTB Interconnection between Hydro Quebec and
VELCO (both 60 Hz but Asynchronous)
• Commissioned in 1985
• Recognized as the fastest constructed HVDC Substation
from Drawing Board to Commissioning
• Continuous Capacity of 225 MW rated (up to 40°C)
• Limited to 218 MW due to HQ System until fall of 2014
• North AC bus is connected to the HQ System (120kV)
• South AC bus is connected to the VELCO system (115kV)
9
9
Basic Ratings of the Converter
• Continuous Capacity of 225 MW rated (up to 40°C)
– North to South
– Requires transformer cooling fans and pumps
– Requires 4 cooling towers in-service
• 5th tower added for redundancy, does not increase power transfer rating
• Maximum Direct Voltage - 56 kV
• Minimum Direct Voltage - 32.5 kV (20 MW)
• Maximum Direct Continuous Current - 4061 A
• Continuous Capacity of 170 MW rated (up to 40°C)
– South to North (System not converter constraint)
10
10
Cooling System
• 2 closed loop systems
separated by dual heat
exchangers
• Fine water (De-ionized, Pure
Water) cools the valves
• Raw water (Propylene
Glycol/water) mixture cools the
fine water
• Redundancy in the controls
• Redundancy of pumps, motors
and fans and heat exchangers.
11
11
Harmonic Filter Banks and
additional Capacitor Banks
• Symmetric filter configuration each
side (North & South)
• 2 – 11th/13th filter (22 / 20 MVAR)
• 1 – HP 25th filter (22 / 20 MVAR)
• 1 – 3rd/27th filter (11 / 10 MVAR)
• Provides harmonic filtering and
VAR support for the converters
• 3 – 20 (22) MVAR
• 1 – 10 (11) MVAR
• Extra VAR support is needed to
avoid drawing vars from the ac
systems on both sides (helps
maintain voltage)
12
12
Power Control Mode
Keeps DC power equal to the Power Order given by the
operator
• The power order is given by the Operator
• DC Current is controlled to keep ordered power constant
Idc = Pdc/Vdc
• The power order is set in MW (20 to 225 MW)
• The power ramp rate is set in MW/min (1 to 30 MW/min)
• Power modulations are available if enabled
13
13
Current Control Mode
Operates to maintain constant current regardless of the DC
Voltage fluctuations
• The current order is entered by the operator
• The current order is set in A (360 to 4050 A)
• The ramp rate is set in A/min (1 to 500 A/min)
• Power modulations are available if enabled
Note VELCO only uses Current control under test mode
14
14
• The facility was commissioned when and to connect who?
– The facility was commissioned in 1985 to bring power from Hydro
Quebec into VELCO’s system
• What are critical components for achieving the full rating?
– At least 4 out of the 5 radiator towers
– Transformer fans and pumps available
• Does the outdoor cooling liquid in the Radiators enter the
valve hall to cool the Thyristors?
– No, the cooling system has 2 loops, Raw water (Propylene
Glycol/water) between the radiators and the heat exchanger & Fine
water (De-ionized, Pure Water) between the heat exchangers and
the valves
• What are the 2 functions the Filter shunt Capacitor banks
perform?
– The filter capacitors absorb harmonics and provide VAR/Voltage
support. The regular capacitors are primarily for VAR/Voltage
support.
Highgate Converter Initial Review
15
15
Starting the Converter
Permissions / Steps
• At least 1 of redundant protection and control systems available/healthy for each
system.
• Tap changer starts in tap position 31 (highest ratio - lowest dc side voltage)
• AC busses initially isolated by breakers
• Valve hall grounds need to be removed
• Once energized with breakers:
• Tap changers move to regulate dc side transformer voltage to starting condition
• Minimum filters must be available
• Thyristors still blocked but available to de-block
• Converter Ramp Order and Power Order values cannot be changed yet
• The converter firing pulses will be Deblocked (i.e. released) – starts at 20 MW
• Minimum filters needed for filter performance are automatically connected at
deblock
16
16
Starting the Converter
Ramp and Filter/Capacitor Switching
• System operator selects Ramp Order & Power Order
• Automatic AC voltage on both sides to a setpoint is provided
by adjusting converter var absorption. This can be increased
at low power by lowering the dc voltage reference and by
firing angle control and by switching in and out
filters/capacitor banks
• Additional minimum filters will close at 35 & 120 MW
• Capacitor banks will connect
or disconnect automatically
to maintain desired voltages
17
17
Stopping the Converter
• Emergency Stop
– Block thyristor firing pulses
– Trip & lockout main breakers
• Normal Stop
– Ramp down
• System operator selects ramp order
• and power order of 20 MW
• With ramp, filters will open at 100 & 25 MW or with voltage control
• Other capacitors will open with voltage control
– Issue Block Command
• Blocks thyristors
• Trips minimum filters
– Operator may manually open main breakers
18
18
Changing of Power Direction
• Automatic Sequence
– Ramp to Min Power Order
– Block Converters (The minimum filters remain connected)
– Reverse Rectifier/Inverter designations
– Restart the Converters. Due to different firing angles the dc
voltage is reversed, current flows in same direction
– Ramp to new Power Order
19
19
Runbacks
• Power Modulated Voltage Controller (PMVC) Runbacks
– Utilizes a PID Function to constrain DC power transfer if the AC
systems cannot maintain voltage above a set-point DC transfer is
controlled so AC voltage does not go too low (maximizes energy
throughput)
• Voltage Runbacks
– When enabled and voltage below set-point for a given time:
– Quick MW ramp down until voltage is acceptable or MW minimum
met
• Frequency Limiter Runbacks (North only)
– When enabled and outside frequency band:
– Ramp speed proportional to frequency deviation
20
20
• What are some of the required starting conditions of the
converter?
– At least 1 of redundant protection and control systems available/healthy for each system.
– Transformer Tap changer in position 31 (highest ratio - lowest LV or DC voltage)
– AC busses initially isolated by breakers
– Valve hall grounds need to be removed
– Once transformers are energized with breakers:
– Tap changers move to regulate LV/dc to starting value, HV must remain within band
– Minimum filters available
– Thyristors available to de-block
• What are the 3 runback schemes?
– Power Modulated Voltage Control
– Voltage Runbacks
– Frequency Runbacks
Highgate Converter 2nd Review
21
21
Temporary Blocking
• Special Control Sequences to allow the converter to ride
through faults on North & South lines
• There are no Operator inputs or adjustments to the North
or South Temporary block sequences
• Separate Temporary Block sequences are provided on
the North side and the South sides
22
22
Temporary Blocking
initiation & actions
Initiated by a serious voltage drop for a given time
• Retards firing angle of the rectifier to reduce DC Current toward zero
• Blocks the faulted-side converter with Bypass Pair
• Opens faulted-side Main Breakers, but leaves filters and shunts
connected
• Switches the control mode of the unfaulted-side DC converter to AC
overvoltage control mode
• Deblocks the faulted-side converter as an Inverter the unfaulted-side as
a Rectifier (if not already that way)
• After dc voltage is established, fires a bypass on the faulted-side side
and circulates current through bypass pairs in the faulted-side as
needed to control overvoltage as the unfaulted-side AC Bus to 1.1 pu
• Maintains the above condition until the faulted-side AC voltage recovers
• If not recovered within a given timeframe , the converter will trip
23
23
Temporary Blocking
Recovery
• If the ac voltage recovers, the dc system will automatically be
restored back to pre-fault power order
– Firing angle of the unfaulted-side converter is retarded to bring DC
current to zero and the converter is blocked
– The faulted-side Main breakers are re-closed
– Power direction is restored to the pre-fault state (rectifier/inverter
designations during temporary block may need to be reversed)
– The pole controls rapidly restore the pre-fault power by adjusting firing
angles (no ramping)
24
24
Other than voltage other initiating signals may include:
• Transfer trip signals from other substation protection systems
• Status indications from other substations for low system strength
determination
Likewise both voltage recovery and removal of any other initiating
condition need to occur to allow recovery from temporary block
condition
There are some conditions where due to harmonics the system may
not be able to restore previous conditions and will instead trip if those
conditions are determined by the control system
Temporary Blocking
additional initiation
25
25
Offline Capacitor Bank Switching
• Used when Converter offline for extended
outage
• Request for using the capacitor banks for
addition MVAR support to the system
• Allows the use of five of the capacitor banks
• (3) 20 MVAR banks and (2) 10 MVAR banks for a total of 80 MVARs,
26
26
Mode of operation/switching:
– Verify that the Converter is stopped
– Open the Main breaker
– Place the Filter control to Manual
– Open the converter Transformer high-side disconnect
• Need person on site to confirm disconnect is open
– Enable the Cap bank control
– Close the Main breaker
– Dispatch the desired cap/filter banks
Offline Capacitor Bank Switching
27
27
Offline Capacitor Bank Protections
• If voltage is above High voltage limit
– Sequential tripping of capacitor banks
– Stops when below High voltage limit
• If voltage is above Very-High voltage limit
– Faster sequential tripping of capacitor banks
– Reverts to slower sequential tripping (High voltage
mode) when below Very-high voltage limit
28
28
• Does the converter trip during a line fault?
– Generally not unless the ac voltage stays low for a long time. Trick question, some
breakers will at least trip temporarily but the system will resume where it left off if the ac
voltages recover in time. Otherwise the system will trip if the AC system voltage remains
low or some other protection conditions exist
• Other than voltage what other initiating conditions may cause a
temporary block?
– Transfer trip from other substations
– Status from other substations that in combination can be determined to be a low short
circuit condition
• Can the north & south capacitor banks be used when the
converter is offline?
– Only the capacitors on one side have been set up in the control
system for independent ac bus voltage control while offline
Highgate Converter Final Review
29
29

More Related Content

Similar to HVDC

Power electronics and its applications.pptx
Power electronics and its applications.pptxPower electronics and its applications.pptx
Power electronics and its applications.pptx
SHIVANICHAUUHAN1
 
Grid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgd
Grid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgdGrid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgd
Grid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgd
suresh386785
 
Application of power electronics in hvdc copy
Application of power electronics in hvdc   copyApplication of power electronics in hvdc   copy
Application of power electronics in hvdc copy
SARAVANAN A
 
High Reliability and Efficiency Single phase Transformerless Inverter for Gri...
High Reliability and Efficiency Single phase Transformerless Inverter for Gri...High Reliability and Efficiency Single phase Transformerless Inverter for Gri...
High Reliability and Efficiency Single phase Transformerless Inverter for Gri...
Anoop kumar Niravuparambil
 
powersupply-120904002231-phpapp02.pdf
powersupply-120904002231-phpapp02.pdfpowersupply-120904002231-phpapp02.pdf
powersupply-120904002231-phpapp02.pdf
HebaEng
 

Similar to HVDC (20)

Voltage Regulation
Voltage RegulationVoltage Regulation
Voltage Regulation
 
PowerSwitches.ppt
PowerSwitches.pptPowerSwitches.ppt
PowerSwitches.ppt
 
Chapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdfChapter 1 Introduction to power Electronic Devices.pdf
Chapter 1 Introduction to power Electronic Devices.pdf
 
Principles Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPrinciples Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC Schemes
 
HVDC transmission system and its components
HVDC transmission system and its componentsHVDC transmission system and its components
HVDC transmission system and its components
 
Hvdc transmission
Hvdc transmissionHvdc transmission
Hvdc transmission
 
Analysis of HVDC Converters.pptx
Analysis of HVDC Converters.pptxAnalysis of HVDC Converters.pptx
Analysis of HVDC Converters.pptx
 
T&D_Unit V.pdf
T&D_Unit V.pdfT&D_Unit V.pdf
T&D_Unit V.pdf
 
Power electronics and its applications.pptx
Power electronics and its applications.pptxPower electronics and its applications.pptx
Power electronics and its applications.pptx
 
Grid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgd
Grid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgdGrid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgd
Grid.pptxdfsdgfsdfghdfcdfsdgdsfghgbnfghdfgd
 
Application of power electronics in hvdc
Application of power electronics in hvdcApplication of power electronics in hvdc
Application of power electronics in hvdc
 
Hvdc ppt with animated videos
Hvdc ppt with animated videosHvdc ppt with animated videos
Hvdc ppt with animated videos
 
Application of power electronics in hvdc copy
Application of power electronics in hvdc   copyApplication of power electronics in hvdc   copy
Application of power electronics in hvdc copy
 
Basics of hvdc
Basics of hvdc Basics of hvdc
Basics of hvdc
 
BASIC ELECTRO MECHANICAL ARRANGEMENTS.pptx
BASIC ELECTRO MECHANICAL ARRANGEMENTS.pptxBASIC ELECTRO MECHANICAL ARRANGEMENTS.pptx
BASIC ELECTRO MECHANICAL ARRANGEMENTS.pptx
 
High Reliability and Efficiency Single phase Transformerless Inverter for Gri...
High Reliability and Efficiency Single phase Transformerless Inverter for Gri...High Reliability and Efficiency Single phase Transformerless Inverter for Gri...
High Reliability and Efficiency Single phase Transformerless Inverter for Gri...
 
Psoc voltage control 2018
Psoc voltage control 2018Psoc voltage control 2018
Psoc voltage control 2018
 
powersupply-120904002231-phpapp02.pdf
powersupply-120904002231-phpapp02.pdfpowersupply-120904002231-phpapp02.pdf
powersupply-120904002231-phpapp02.pdf
 
VSC based HVDC system
VSC based HVDC systemVSC based HVDC system
VSC based HVDC system
 
various types of transformers.
various types of transformers.various types of transformers.
various types of transformers.
 

Recently uploaded

Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
Kamal Acharya
 
ONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdf
ONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdfONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdf
ONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdf
Kamal Acharya
 

Recently uploaded (20)

KIT-601 Lecture Notes-UNIT-5.pdf Frame Works and Visualization
KIT-601 Lecture Notes-UNIT-5.pdf Frame Works and VisualizationKIT-601 Lecture Notes-UNIT-5.pdf Frame Works and Visualization
KIT-601 Lecture Notes-UNIT-5.pdf Frame Works and Visualization
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
 
Top 13 Famous Civil Engineering Scientist
Top 13 Famous Civil Engineering ScientistTop 13 Famous Civil Engineering Scientist
Top 13 Famous Civil Engineering Scientist
 
2024 DevOps Pro Europe - Growing at the edge
2024 DevOps Pro Europe - Growing at the edge2024 DevOps Pro Europe - Growing at the edge
2024 DevOps Pro Europe - Growing at the edge
 
Arduino based vehicle speed tracker project
Arduino based vehicle speed tracker projectArduino based vehicle speed tracker project
Arduino based vehicle speed tracker project
 
Furniture showroom management system project.pdf
Furniture showroom management system project.pdfFurniture showroom management system project.pdf
Furniture showroom management system project.pdf
 
NO1 Pandit Amil Baba In Bahawalpur, Sargodha, Sialkot, Sheikhupura, Rahim Yar...
NO1 Pandit Amil Baba In Bahawalpur, Sargodha, Sialkot, Sheikhupura, Rahim Yar...NO1 Pandit Amil Baba In Bahawalpur, Sargodha, Sialkot, Sheikhupura, Rahim Yar...
NO1 Pandit Amil Baba In Bahawalpur, Sargodha, Sialkot, Sheikhupura, Rahim Yar...
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
 
ONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdf
ONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdfONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdf
ONLINE VEHICLE RENTAL SYSTEM PROJECT REPORT.pdf
 
Construction method of steel structure space frame .pptx
Construction method of steel structure space frame .pptxConstruction method of steel structure space frame .pptx
Construction method of steel structure space frame .pptx
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Event Management System Vb Net Project Report.pdf
Event Management System Vb Net  Project Report.pdfEvent Management System Vb Net  Project Report.pdf
Event Management System Vb Net Project Report.pdf
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
fundamentals of drawing and isometric and orthographic projection
fundamentals of drawing and isometric and orthographic projectionfundamentals of drawing and isometric and orthographic projection
fundamentals of drawing and isometric and orthographic projection
 
A case study of cinema management system project report..pdf
A case study of cinema management system project report..pdfA case study of cinema management system project report..pdf
A case study of cinema management system project report..pdf
 
BRAKING SYSTEM IN INDIAN RAILWAY AutoCAD DRAWING
BRAKING SYSTEM IN INDIAN RAILWAY AutoCAD DRAWINGBRAKING SYSTEM IN INDIAN RAILWAY AutoCAD DRAWING
BRAKING SYSTEM IN INDIAN RAILWAY AutoCAD DRAWING
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
 

HVDC

  • 1. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Overview
  • 2. 2 2 Highgate Converter Abstract • Introduction to HVDC • Background on Highgate • Operation and Control schemes of Highgate
  • 3. 3 3 Why Use HVDC? • Fast and accurate control of power transfer not dependent on system angles • Interconnection between asynchronous systems – Frequency and Voltage independent • Provides isolation from system disturbances in other system • To transmit large bulk power over a long distance – Losses proportional to current squared – AC systems also have reactive power & losses – Long AC systems use series capacitors to automatically compensate vars • This can cause sub-synchronous resonance which can harm machines • Line breakers need to have higher ratings for transient recovery voltage – DC terminals also have real and reactive power losses but they occur only at the injection points and can be more easily compensated – Loss savings for and Cost savings DC vs. AC line losses occurs at long distances
  • 4. 4 4 • AC is converted into DC (Rectifier Side) • DC is then converted into AC (Inverter Side) • Both use controlled electronic switches (Thyristors) to allow current to flow in a controlled fashion – Thyristors turn on (allow current flow) occurs due to a gate pulse and can be delayed but naturally turn-off when current tries to reverse • By adjusting firing delay angles of the Thyristors, we can control the magnitude of DC voltage of the rectifier and inverter. – The difference of the DC voltages impacts the magnitude of current and power flow Idc=(Vrect-Vinv)/Rdc Pdc=Vdc*Idc – The polarity (which side is higher) controls the direction of power flow – The converter transformers determine magnitude of the voltage on the dc side and therefore the maximum possible DC voltage • Harmonics are produced because of the 12-pulse current steps compared to sinusoidal currents Basic Principle
  • 5. 5 5 • 6 pulse, 10° firing angle (15° offset, thyristor off delay) • 6 pulse, 40° firing angle, lower DC (and MW) • 12 Pulse, 10° firing angle Basic Principle Waveform examples – Rectifier (AC to DC)
  • 6. 6 6 • Monopolar HVDC connections • No DC Transmission Line (just a bus) • Both converters are located at the same site • Utilize 12-pulse converter units on both the Rectifier and Inverter sides • Valves can be located in one Valve hall – Option Smoothing Reactor reduces negative sequence coupling Back-to-Back Converters
  • 7. 7 7 • What are the reasons HVDC is utilized? – Direct accurate Control of power transfer – Interconnections between Asynchronous systems – Provides isolation from system disturbances – Transmission of Bulk power of Long Distances – No restrictions on cable length while AC Cables must be less than ~40 km • The terms Rectifier & Inverter refer to what functions? – A Rectifier converts AC to DC – An Inverter converts DC to AC – Either converter can be either rectifier or inverter • Firing Angle has what impact on the DC and Power Flow? – Adjusting the firing delay angle adjusts the magnitude of the DC voltage – Magnitude and polarity of the DC voltage affects the magnitude and direction of Power flow HVDC Review
  • 8. 8 8 Background of the Highgate Converter • 225 MW BTB Interconnection between Hydro Quebec and VELCO (both 60 Hz but Asynchronous) • Commissioned in 1985 • Recognized as the fastest constructed HVDC Substation from Drawing Board to Commissioning • Continuous Capacity of 225 MW rated (up to 40°C) • Limited to 218 MW due to HQ System until fall of 2014 • North AC bus is connected to the HQ System (120kV) • South AC bus is connected to the VELCO system (115kV)
  • 9. 9 9 Basic Ratings of the Converter • Continuous Capacity of 225 MW rated (up to 40°C) – North to South – Requires transformer cooling fans and pumps – Requires 4 cooling towers in-service • 5th tower added for redundancy, does not increase power transfer rating • Maximum Direct Voltage - 56 kV • Minimum Direct Voltage - 32.5 kV (20 MW) • Maximum Direct Continuous Current - 4061 A • Continuous Capacity of 170 MW rated (up to 40°C) – South to North (System not converter constraint)
  • 10. 10 10 Cooling System • 2 closed loop systems separated by dual heat exchangers • Fine water (De-ionized, Pure Water) cools the valves • Raw water (Propylene Glycol/water) mixture cools the fine water • Redundancy in the controls • Redundancy of pumps, motors and fans and heat exchangers.
  • 11. 11 11 Harmonic Filter Banks and additional Capacitor Banks • Symmetric filter configuration each side (North & South) • 2 – 11th/13th filter (22 / 20 MVAR) • 1 – HP 25th filter (22 / 20 MVAR) • 1 – 3rd/27th filter (11 / 10 MVAR) • Provides harmonic filtering and VAR support for the converters • 3 – 20 (22) MVAR • 1 – 10 (11) MVAR • Extra VAR support is needed to avoid drawing vars from the ac systems on both sides (helps maintain voltage)
  • 12. 12 12 Power Control Mode Keeps DC power equal to the Power Order given by the operator • The power order is given by the Operator • DC Current is controlled to keep ordered power constant Idc = Pdc/Vdc • The power order is set in MW (20 to 225 MW) • The power ramp rate is set in MW/min (1 to 30 MW/min) • Power modulations are available if enabled
  • 13. 13 13 Current Control Mode Operates to maintain constant current regardless of the DC Voltage fluctuations • The current order is entered by the operator • The current order is set in A (360 to 4050 A) • The ramp rate is set in A/min (1 to 500 A/min) • Power modulations are available if enabled Note VELCO only uses Current control under test mode
  • 14. 14 14 • The facility was commissioned when and to connect who? – The facility was commissioned in 1985 to bring power from Hydro Quebec into VELCO’s system • What are critical components for achieving the full rating? – At least 4 out of the 5 radiator towers – Transformer fans and pumps available • Does the outdoor cooling liquid in the Radiators enter the valve hall to cool the Thyristors? – No, the cooling system has 2 loops, Raw water (Propylene Glycol/water) between the radiators and the heat exchanger & Fine water (De-ionized, Pure Water) between the heat exchangers and the valves • What are the 2 functions the Filter shunt Capacitor banks perform? – The filter capacitors absorb harmonics and provide VAR/Voltage support. The regular capacitors are primarily for VAR/Voltage support. Highgate Converter Initial Review
  • 15. 15 15 Starting the Converter Permissions / Steps • At least 1 of redundant protection and control systems available/healthy for each system. • Tap changer starts in tap position 31 (highest ratio - lowest dc side voltage) • AC busses initially isolated by breakers • Valve hall grounds need to be removed • Once energized with breakers: • Tap changers move to regulate dc side transformer voltage to starting condition • Minimum filters must be available • Thyristors still blocked but available to de-block • Converter Ramp Order and Power Order values cannot be changed yet • The converter firing pulses will be Deblocked (i.e. released) – starts at 20 MW • Minimum filters needed for filter performance are automatically connected at deblock
  • 16. 16 16 Starting the Converter Ramp and Filter/Capacitor Switching • System operator selects Ramp Order & Power Order • Automatic AC voltage on both sides to a setpoint is provided by adjusting converter var absorption. This can be increased at low power by lowering the dc voltage reference and by firing angle control and by switching in and out filters/capacitor banks • Additional minimum filters will close at 35 & 120 MW • Capacitor banks will connect or disconnect automatically to maintain desired voltages
  • 17. 17 17 Stopping the Converter • Emergency Stop – Block thyristor firing pulses – Trip & lockout main breakers • Normal Stop – Ramp down • System operator selects ramp order • and power order of 20 MW • With ramp, filters will open at 100 & 25 MW or with voltage control • Other capacitors will open with voltage control – Issue Block Command • Blocks thyristors • Trips minimum filters – Operator may manually open main breakers
  • 18. 18 18 Changing of Power Direction • Automatic Sequence – Ramp to Min Power Order – Block Converters (The minimum filters remain connected) – Reverse Rectifier/Inverter designations – Restart the Converters. Due to different firing angles the dc voltage is reversed, current flows in same direction – Ramp to new Power Order
  • 19. 19 19 Runbacks • Power Modulated Voltage Controller (PMVC) Runbacks – Utilizes a PID Function to constrain DC power transfer if the AC systems cannot maintain voltage above a set-point DC transfer is controlled so AC voltage does not go too low (maximizes energy throughput) • Voltage Runbacks – When enabled and voltage below set-point for a given time: – Quick MW ramp down until voltage is acceptable or MW minimum met • Frequency Limiter Runbacks (North only) – When enabled and outside frequency band: – Ramp speed proportional to frequency deviation
  • 20. 20 20 • What are some of the required starting conditions of the converter? – At least 1 of redundant protection and control systems available/healthy for each system. – Transformer Tap changer in position 31 (highest ratio - lowest LV or DC voltage) – AC busses initially isolated by breakers – Valve hall grounds need to be removed – Once transformers are energized with breakers: – Tap changers move to regulate LV/dc to starting value, HV must remain within band – Minimum filters available – Thyristors available to de-block • What are the 3 runback schemes? – Power Modulated Voltage Control – Voltage Runbacks – Frequency Runbacks Highgate Converter 2nd Review
  • 21. 21 21 Temporary Blocking • Special Control Sequences to allow the converter to ride through faults on North & South lines • There are no Operator inputs or adjustments to the North or South Temporary block sequences • Separate Temporary Block sequences are provided on the North side and the South sides
  • 22. 22 22 Temporary Blocking initiation & actions Initiated by a serious voltage drop for a given time • Retards firing angle of the rectifier to reduce DC Current toward zero • Blocks the faulted-side converter with Bypass Pair • Opens faulted-side Main Breakers, but leaves filters and shunts connected • Switches the control mode of the unfaulted-side DC converter to AC overvoltage control mode • Deblocks the faulted-side converter as an Inverter the unfaulted-side as a Rectifier (if not already that way) • After dc voltage is established, fires a bypass on the faulted-side side and circulates current through bypass pairs in the faulted-side as needed to control overvoltage as the unfaulted-side AC Bus to 1.1 pu • Maintains the above condition until the faulted-side AC voltage recovers • If not recovered within a given timeframe , the converter will trip
  • 23. 23 23 Temporary Blocking Recovery • If the ac voltage recovers, the dc system will automatically be restored back to pre-fault power order – Firing angle of the unfaulted-side converter is retarded to bring DC current to zero and the converter is blocked – The faulted-side Main breakers are re-closed – Power direction is restored to the pre-fault state (rectifier/inverter designations during temporary block may need to be reversed) – The pole controls rapidly restore the pre-fault power by adjusting firing angles (no ramping)
  • 24. 24 24 Other than voltage other initiating signals may include: • Transfer trip signals from other substation protection systems • Status indications from other substations for low system strength determination Likewise both voltage recovery and removal of any other initiating condition need to occur to allow recovery from temporary block condition There are some conditions where due to harmonics the system may not be able to restore previous conditions and will instead trip if those conditions are determined by the control system Temporary Blocking additional initiation
  • 25. 25 25 Offline Capacitor Bank Switching • Used when Converter offline for extended outage • Request for using the capacitor banks for addition MVAR support to the system • Allows the use of five of the capacitor banks • (3) 20 MVAR banks and (2) 10 MVAR banks for a total of 80 MVARs,
  • 26. 26 26 Mode of operation/switching: – Verify that the Converter is stopped – Open the Main breaker – Place the Filter control to Manual – Open the converter Transformer high-side disconnect • Need person on site to confirm disconnect is open – Enable the Cap bank control – Close the Main breaker – Dispatch the desired cap/filter banks Offline Capacitor Bank Switching
  • 27. 27 27 Offline Capacitor Bank Protections • If voltage is above High voltage limit – Sequential tripping of capacitor banks – Stops when below High voltage limit • If voltage is above Very-High voltage limit – Faster sequential tripping of capacitor banks – Reverts to slower sequential tripping (High voltage mode) when below Very-high voltage limit
  • 28. 28 28 • Does the converter trip during a line fault? – Generally not unless the ac voltage stays low for a long time. Trick question, some breakers will at least trip temporarily but the system will resume where it left off if the ac voltages recover in time. Otherwise the system will trip if the AC system voltage remains low or some other protection conditions exist • Other than voltage what other initiating conditions may cause a temporary block? – Transfer trip from other substations – Status from other substations that in combination can be determined to be a low short circuit condition • Can the north & south capacitor banks be used when the converter is offline? – Only the capacitors on one side have been set up in the control system for independent ac bus voltage control while offline Highgate Converter Final Review
  • 29. 29 29