SlideShare a Scribd company logo
Bowthorpe EMP
Distribution Metal Oxide Surge Arrester
DAH Series (IEEE) Heavy Duty
Energy Division
Sealing:
All arrester cores are encapsulated in silicone insulating
housing. A permanent chemical bond connects the
arrester core and the non-tracking silicone housing. This
invisible interface prevents moisture from entering during
severe thermal fluctuations due to normal climatic and
energy absorption events.
Polymer housing:
Non-tracking and hydrophobic silicone insulating material
is used for DA arrester housings. The DA surge arrester
series is available with standard or extra leakage distance.
The housing material has proven performance in long
term TERT and UV aging tests and proven resistance
to flammability.
Integrated design:
Manufacturing integrates all components in a single
piece. There are no glued interfaces. The design is void
and gap free ensuring peak performance under the
harshest conditions.
Reliable and consistent GLD
The robust ground lead disconnect (GLD) offers
operational reliability and consistency. It was designed
to operate in event of arrester failure, removing ground
connection and fault from line. It can be shipped and
stored restriction free.
Safe mode of failure:
Our high energy arresters are tested in accordance with
the short circuit mode of failure test in IEEE C62.11, (2005).
This testing has proven the DAH’s safe and predictable
failure characteristics.
Quality:
The DAH series arrester is manufactured to international
quality standards in Tyco Electronics production facilities.
We perform 100% routine testing on arresters:
1) Visual inspection
2) Reference voltage test
3) Power loss test
4) Partial discharge test
Tyco Electronics’ Bowthorpe EMP
business group pioneered the
development of polymeric com-
posite housed surge arresters in
the early 1980’s and since then has
proven service experience across
the globe, operating in the world’s
toughest environments. DA Series
surge arresters provide active over
voltage protection that contributes
directly to improved reliability of
your system, reducing lost minutes
and protecting expensive assets.
Tyco Electronics Bowthorpe EMP
DA silicone surge arresters have
been designed and tested to meet
customers’ demand for reliability
and improved operational perfor-
mance. DA development was based
on 30 years of experience in arrester
design and manufacturing within the
Tyco Electronics Energy Division.
The DAH series is qualified to the latest
revision of IEEE C62.11, (2005) and all
reports are independently certified.
Summary of Heavy Duty Arrester (DAH) series technical characteristics
Ur (kV) 3.5 – 36
In (kA) 10
High current impulse (kA) 100
Arrester type Heavy duty
Long duration current (A /µs) 250 / 2000
10s TOV (kV) 1.4 * MCOV
High current short circuit (kA) 21
Arrester technology ZnO gapless Mold in place
2
DAH Series
Qualification testing:
The following IEEE C62.11, (2005) design type tests have
been carried out on the DA series arresters:
1) Arrester insulation withstand tests
2) Discharge-voltage characteristics
3) Accelerated aging procedure
4) Accelerated aging tests of external polymeric
insulating systems
5) Accelerated aging of the polymer housing with
exposure to salt fog (rotating wheel)
6) Contamination test
7) Distribution class surge arrester seal integrity design test
8) Partial Discharge tests
9) High-current short-duration withstand test
10)Low-current long-duration withstand test
11) Duty-cycle tests
12) TOV tests
13) Short-circuit test for polymer housed distribution
arresters
14)Distribution arrester disconnector tests
15) Mechanical tests
The silicone insulating material has been designed and
optimized for arrester application. The following additional
testing was performed in the qualification of the silicone:
1) Tracking and Erosion
2) UV testing
3) Thermal endurance
4) Dielectric testing
5) Flammability testing.
6) Long term water immersion testing
Production and Quality:
All Tyco Electronics arrester production facilities have
implemented QC and QA procedures according to
international standards to ensure test programs that
guarantee quality conforming products. 100% of all
varistors are tested and stamped with unique varistor
residual and reference voltage. The following tests are
performed on varistors:
1) Residual voltage
2) Reference voltage
3) Leakage current
4) Physical examination to screen damaged varistors
5) LOT test: High current impulse test
6) LOT test: Aging test
At the end of the arrester assembly process, the following
mandatory IEEE tests are completed on every arrester:
1) Visual inspection
2) Reference voltage test
3) Power loss test
4) Partial discharge testing
DAH Series
3
Birdcap
Aluminum fittings
Silicone rubber
housing
Mold in Place
ZnO varistors
Glass filled
epoxy laminate
Bracket
GLD
Ground clamp
Surge arrester name plate
DAH Series
Application:
Designed and optimized to protect distribution assets including transformers
and cable-end terminations from lightning and switching surge related over-
voltages.
Generic technical data:
DAH series 3.5 - 36 kV
Rated discharge current (8/20µs): 10 kA
Heavy Duty Arrester IEEE C62.11, (2005)
Operating duty impulse withstand current (4/10µs): 100 kA
Long duration current impulse (2000µs): 250 A
10 second TOV, (kV) 1.4 * MCOV
Mechanical data
Cantilever 258 ft.-lbs
Tension 450 Ibf
Torque 36.9 ft.-lbs
Bowthorpe EMP DAH series surge
arrester benefits:
Tested in accordance with
IEEE 62.11, 2005
Direct molded housing to prevent
moisture ingress
Low residual voltages
High-energy handling
Safe non-shattering short circuit
behavior to higher current levels
Maintenance free
Hydrophobic silicone housing:
(Tracking and erosion resistant)
Excellent cantilever and tensile
performance
Quality design and manufacturing
meeting international standards
Uw = TOV withstand voltage; Ur = Rated voltage
Temporary over-voltage curve (TOV)
Time (s)
0.1
1.48
1.44
1.40
1.36
1.32
1.28
1.24
100010010
Uw/MCOV
1 10000
4
DAH TOV
Sample product marking, DAH-30F
DAH series arrester standard electrical data:
DAH Series
Residual voltage in kV when tested to the following test waveforms
Ur MCOV Front of Lightning (8/20µs) Switching
Part Number kV kV wave
1.5kA 3kA 5kA 10kA 20kA 40kA 500A
DAH-04 3.5 2.95 11.1 8.9 9.4 9.8 10.5 11.6 12.6 8.3
DAH-06 6.0 5.10 19.1 15.3 16.1 16.9 18.0 19.9 21.6 14.2
DAH-09 9.0 7.65 28.6 22.9 24.2 25.3 27.0 29.9 32.4 21.3
DAH-10 10.0 8.40 31.8 25.5 26.8 28.1 30.0 33.2 36.0 23.6
DAH-12 12.0 10.2 38.1 30.5 32.2 33.7 36.0 39.8 43.2 28.4
DAH-15 15.0 12.7 47.7 38.2 40.3 42.1 45.1 49.8 54.0 35.5
DAH-18 18.0 15.3 57.2 45.8 48.3 50.6 54.1 59.7 64.8 42.5
DAH-21 21.0 17.0 66.7 53.5 56.4 59.0 63.1 69.7 75.6 49.6
DAH-24 24.0 19.5 76.3 61.1 64.4 67.4 72.1 79.6 86.4 56.7
DAH-27 27.0 22.0 85.8 68.7 72.5 75.8 81.1 89.6 97.2 63.8
DAH-30 30.0 24.2 95.3 76.4 80.5 84.3 90.1 99.5 108.0 70.9
DAH-36 36.0 29.0 114.4 91.6 96.6 101.1 108.1 119.4 129.6 85.1
Housing Leakage Flash over Dry 10s Wet Height Weight
code distance lightning withstand
(1.2 / 50)
inches inches kV kV inches lb
A 12.95 5.98 150 45 5.79 2.64
B 15.9 6.97 170 55 6.77 2.97
C 21.77 8.94 199 74 8.74 3.96
E 27.64 10.9 219 86 10.7 4.84
F 30.55 11.89 253 95 11.72 5.72
G 36.42 13.86 254 115 13.7 6.45
DAH series arrester standard housing parameters:
Housing code: A B C E F G
Ur Leakage: 12.95 15.9 21.77 27.64 30.55 36.42
3.5 ● ■
6 ● ■
9 ● ■
10 ● ■ ■
12 ● ■ ■
15 ● ■ ■
18 ● ■ ■
21 ● ■ ■
24 ● ■
27 ● ■
30 ● ■
36 ● ■
● standard housing ■ optional housing
Housing and Ur compatibility:
2in
4.1in
5
L
6
DAH Series Arrester Ordering Information:
Z Z Z - Y Y M - 1 2 3 4 5 6 - P
Naming convention cross reference:
ZZZ = series type: DAH for 10kA, heavy duty arrester
YY = Ur
M = Housing code (see page 5)
Packaging
I Individual Packing
S 3 Pack
B Bulk Packing
Line lead accessories
Bxxxxx
Birdcap with
F accessory
Exxxxx
Birdcap with
M accessory
Fxxxxx
1.7” stud
for lug
connection
Hxxxxx
Cap screw &
spring washer
Mxxxxx
1.7” stud
for line lead
connection
Oxxxxx
No stud. No
accessories
1
Line lead options
x0xxxx No line lead wire
x1xxxx 18” No. 6 AWG copper line lead with one 3/8” lug
x2xxxx 36” No. 6 AWG copper line lead with one 3/8” lug
x3xxxx 36” No. 6 AWG copper line lead with no lug
x4xxxx 18” No. 4 AWG copper line lead with one 3/8” lug
x5xxxx 36” No. 4 AWG copper line lead with one 3/8” lug
x6xxxx 36” No. 4 AWG copper line lead with no lug
x8xxxx 36” No. 6 AWG copper line lead with two 3/8” lugs
2
Ground lead accessories:
xxDxxx
Disconnect +
M accessory
xxExxx
Disconnect +
F accessory
xxFxxx
1.7” stud
for lug
connection
xxHxxx
3/8”*1”
Cap screw &
spring washer
xxMxxx
1.7” stud
for line lead
connection
xxOxxx
No stud. No
accessories
3
Additional accessories are available upon request
Ground lead options
xxx0xx No Ground Lead Wire
xxx1xx 18” No. 6 AWG Copper Ground Lead with one 3/8” lug
xxx2xx 36” No. 6 AWG Copper Ground Lead with one 3/8” lug
xxx3xx 36” No. 6 AWG Copper Ground Lead with no lug
xxx4xx 18” No. 4 AWG Copper Ground Lead with one 3/8” lug
xxx5xx 36” No. 4 AWG Copper Ground Lead with one 3/8” lug
xxx6xx 36” No. 4 AWG Copper Ground Lead with no lug
xxx8xx 36” No. 6 AWG Copper Ground Lead with two 3/8” lugs
xxx9xx 12” No. 6 AWG Copper Ground strap
4
xxxxBx
Insulating
bracket
xxxxNx
No mounting
accessories
xxxxPx Ped-
estal mount-
ing base
xxxxx0
No option
xxxxx1
NEMA cross
arm bracket
Mounting bracket options:Mounting brackets:5 6
Transformer
mounting
bracket
xxxxx5
Transformer
mounting
bracket
14.5”
xxxxx2
8.7”
xxxxx3
11”
xxxxx4
12.25”
Clearance for
Ø 3/8”
Clearance for
Ø 0.5”
6”
8”
1.7”
3/8”
3/4”max
Mxxxxx & xxMxxxx:
Stainless steel line lead connection,
(up to diameter 0.63”)
Fxxxxx & xxFxxxx:
Stainless steel lug connection
7
DAH Series Arrester Accessories
1.7”
3/8”
xxxxAx:
Galvanized steel Straight 2hole
mounting metal bracket
2”
For additional accessory options,
please contact your Tyco Electronics
Energy sales engineer.
Oxxxxx & xxOxxx
No accessories
3/4”
3/8”
Hxxxxx & xxHxxx
Cap screw connection
1/4”
2.76”
1.38”
Ø 2.5”
Bxxxxx & Exxxxx:
Tracking and erosion resistant
bird protection cover
xxDxxx and xxExxx:
ground lead disconnect
1.1”3/8”
8
DAH Series Arrester Accessories
xxxxx1:
Galvanized steel NEMA cross arm mounting bracket
For additional accessory options,
please contact your Tyco Electronics
Energy sales engineer.
1/2”
Ø 0.562”
8.7”
XXXXX2:
Galvanized transformer mounting bracket 8.7”
2.5”
XXXXX3:
Galvanized transformer mounting bracket 11”
XXXXX4:
Galvanized transformer mounting bracket 12.25”
XXXXX5:
Galvanized transformer mounting bracket 14.5”
5.7”
1.687”
1.5” 1/2”
Ø 0.562”
11”
2.5”
7”
1.687”
1.5”
1/2”
Ø 0.562”
12.5”
2.5”
7”
1.687”
1.5” 1/2”
Ø 0.562”
14.5”
12.875”
2.187”
1.5”
2.187”1.562”1.562”
1.25”
3”
4.125-5.15”
2.7-4.75”
8.7”
4.5”
0.342”
2.25”
9
DAH Series Arrester Accessories
6.85”
5.09”
Clearance for
1/2”
Clearance for
1/2”
7.95”
6.2”
xxxxBx:
Insulating brackets
12kV < Ur <= 24kV
Ur > 24kV
5.75”
4”
Clearance
for 1/2”
Ur <= 12kV
Note:
xxxxBx can only be used with either
xxDxxx or xxExxx accessory.
10
Other Bowthorpe EMP Distribution Surge Arrester Products
Hydrophobic siliconeTypical application Tracking and erosion test
Class 2 OCP series arrester
Tyco Electronics Bowthorpe EMP
OCP2 surge arresters are used in
overhead line to cable junction
and substation protection applica-
tions. These arresters are manufac-
tured using high energy and low
residual voltage ZnO varistors, which
display excellent thermal and current
handling characteristics, delivering
optimal protection.
Generic technical data:
OCP2 series 3-41kV Uc
Rated discharge current (8/20µs): 10kA
Line discharge class 2 according to IEC 60099-4
Operating duty impulse withstand current (4/10µs): 100kA
Long duration current impulse (2000µs): 530A
High current short circuit: (pre-failing method) 40kA
(Safe non-shattering failure mode)
Energy 2 Long duration impulses: 6.0kJ/kVUc
with CLXTypical application without CLX
Protection for covered
conductor systems
Tyco Electronics Bowthorpe
EMP CLX protection for covered
conductor systems is designed for
lightning protection in overhead
lines with covered conductors to
prevent conductor breakage.
Generic technical data:
CLX / MORE series 11-33kV systems
Rated discharge current (8/20µs): 10kA
Operating duty impulse withstand current (4/10µs): 65kA
Long duration current impulse (1000µs): 250A
High current short circuit: (pre-failing method) 25kA
Energy 2 Long duration impulses: 2.9kJ/kVUc
Type Application Rating [kA] Line Continuous
discharge voltage [kV]
class from to
MV arresters for outdoor application
DAR Outdoor riser pole arrester 10 Riser 3.5 36
HDA Outdoor high pollution application 10 1 3 41
OCP2 Outdoor Cable and substation protection 10 2 3 41
Arresters for protection systems
CLX Protection of covered conductor systems 10 1 3 36
MV arresters for indoor application
RDA Protection of gas insulated switchgear 10 1 3 26
SPA Protection of air insulated switchgear 10 1 3 36
MPA Motor protection 10 1 3 6
CPA Cable sheath protection 10 1 3 6
RSTI-SA Screened separable surge arrester 5, 10 n.a. 12 24
LV arresters
LVA Transformer secondary protection 10 n.a. 0,28 0,441
Arresters for railway application
HE60 DC railway protection 10 n.a. 1 6
11
Tyco Electronics Energy Division total commitment to quality
Even the best technology must be backed up by a thorough and consistent
quality assurance program. At Tyco Electronics, we subject every product to
an extensive quality control regimen. At every production stage, beginning with
the raw materials and continuing through to the packaged product, the QC lab
tests all physical and electrical characteristics which can influence performance.
By means of lot numbers, the Quality Assurance Program ensures traceability
all the way to details of the compound batch test reports. Quality assurance
at Tyco Electronics is not static, but a constantly improving process directed
toward our goal of complete customer satisfaction. Tyco Electronics Energy
Division arrester manufacturing sites are accredited to international quality
standards. Our vendor routine tests and internal incoming inspection confirm
performance of all critical components used in the assembly of our arresters.
Tyco Electronics Arrester Overview
Energy Division – innovative and economical solutions for the electrical power industry: cable accessories, connectors &
fittings, insulators & insulation, surge arresters, switching equipment, lighting controls, power measurement and control.
Other Products Available from Tyco Electronics Energy Division
Asset protection
Low-voltage surge arresters
Insulation enhancement systems for substations and
overhead. Designed to prevent unplanned outages due to
accidental bridging and to help upgrade insulation levels
at critical points in systems.
LV arresters are used to provide protection for LV
overhead lines, consumer in-house supplies, distribution
transformers and other appliances.
Metal oxide varistor, distribution arresters for indoor and
outdoor applications for protection of overhead lines, DC
locomotives and switchgear applications.
Porcelain and polymeric series parallel and single column
constructed arresters for protection of transmission
systems up to 550 kV.
Insulators and insulating components/housings providing
reliable solutions for power utilities and railway customers
with installations in high pollution environments and
applications up to 400 kV.
Insulators for applications up to system voltages of 132 kV.
This range of insulators offers a cost-effective solution for
low and medium polluted environments.
Medium-voltage surge arresters
High-voltage surge arresters
Polymeric insulators
Porcelain insulators
While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalog, Tyco Electronics cannot assure
that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current.
Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained
herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics’ only obligations are those stated in Tyco Electronics’
Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not
limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its
intended application. In case of any potential ambiguities or questions, please don’t hesitate to contact us for clarification. Bowthorpe EMP, TE (Logo) and Tyco Electronics are trademarks.
Tyco Electronics Corporation
8000 Purfoy Road
Fuquay Varina, NC 27526-9349
Tel: 800.327.6996
Fax: 800.527.8350
E-mail: naenergy@tycoelectronics.com
www.tycoelectronics.com
Copyright 2009 Tyco Electronics Corporation
All rights reserved
9-1773455-6 E367 12/09

More Related Content

What's hot

Catalog terminal idec beeteco
Catalog terminal idec beetecoCatalog terminal idec beeteco
Catalog terminal idec beeteco
CTY TNHH HẠO PHƯƠNG
 
CMP B327-20 Zen Insulated Brass Cable Gland 12.5-20.9mm
CMP B327-20 Zen Insulated Brass Cable Gland  12.5-20.9mmCMP B327-20 Zen Insulated Brass Cable Gland  12.5-20.9mm
CMP B327-20 Zen Insulated Brass Cable Gland 12.5-20.9mm
Thorne & Derrick International
 
Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags?
Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags? Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags?
Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags?
pinkinator
 
Insulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman CatalogueInsulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman Catalogue
nuhasoman
 
Abtech ZAG1 Aluminium Electrical Enclosure & Junction Box
Abtech ZAG1 Aluminium Electrical Enclosure & Junction BoxAbtech ZAG1 Aluminium Electrical Enclosure & Junction Box
Abtech ZAG1 Aluminium Electrical Enclosure & Junction Box
Thorne & Derrick International
 
Catalogue tai sin www.thietbidienngan.com-2014
Catalogue tai sin  www.thietbidienngan.com-2014Catalogue tai sin  www.thietbidienngan.com-2014
Catalogue tai sin www.thietbidienngan.com-2014
Ngan TNHH
 
Siemon cat6 a cable data sheet upload
Siemon cat6 a cable data sheet  uploadSiemon cat6 a cable data sheet  upload
Siemon cat6 a cable data sheet upload
TDKSolutionsLimited
 
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...Thorne & Derrick International
 
3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...
3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...
3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...
Thorne & Derrick International
 
QT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV Cables
QT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV CablesQT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV Cables
QT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV Cables
Thorne & Derrick International
 
CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables
CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed CablesCMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables
CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed CablesThorne & Derrick International
 
Nuhas Oman LLC brochure
Nuhas Oman LLC  brochureNuhas Oman LLC  brochure
Nuhas Oman LLC brochure
Nuhas Oman LLC
 

What's hot (13)

Catalog terminal idec beeteco
Catalog terminal idec beetecoCatalog terminal idec beeteco
Catalog terminal idec beeteco
 
CMP B327-20 Zen Insulated Brass Cable Gland 12.5-20.9mm
CMP B327-20 Zen Insulated Brass Cable Gland  12.5-20.9mmCMP B327-20 Zen Insulated Brass Cable Gland  12.5-20.9mm
CMP B327-20 Zen Insulated Brass Cable Gland 12.5-20.9mm
 
Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags?
Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags? Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags?
Trouble Finding 3M* Dri-Shield* Static Shielding Moisture Barrier Bags?
 
Insulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman CatalogueInsulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman Catalogue
 
Abtech ZAG1 Aluminium Electrical Enclosure & Junction Box
Abtech ZAG1 Aluminium Electrical Enclosure & Junction BoxAbtech ZAG1 Aluminium Electrical Enclosure & Junction Box
Abtech ZAG1 Aluminium Electrical Enclosure & Junction Box
 
Catalogue tai sin www.thietbidienngan.com-2014
Catalogue tai sin  www.thietbidienngan.com-2014Catalogue tai sin  www.thietbidienngan.com-2014
Catalogue tai sin www.thietbidienngan.com-2014
 
Nb cat
Nb catNb cat
Nb cat
 
Siemon cat6 a cable data sheet upload
Siemon cat6 a cable data sheet  uploadSiemon cat6 a cable data sheet  upload
Siemon cat6 a cable data sheet upload
 
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...
CMP E1FX Hazardous Area Flameproof ATEX Cable Glands for Wire Braided Cables ...
 
3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...
3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...
3M Medium Voltage Cable Terminations, 5kV–46kV, 2013 Electrical Product Catal...
 
QT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV Cables
QT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV CablesQT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV Cables
QT111 Cold Shrink Silicone Rubber 3M Cable Terminations For MV HV Cables
 
CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables
CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed CablesCMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables
CMP E2FW Hazardous Area Flameproof ATEX Cable Glands for Lead Sheathed Cables
 
Nuhas Oman LLC brochure
Nuhas Oman LLC  brochureNuhas Oman LLC  brochure
Nuhas Oman LLC brochure
 

Viewers also liked

Nexans Euromold 156SA Surge Arrester 12-24kV
Nexans Euromold 156SA Surge Arrester 12-24kVNexans Euromold 156SA Surge Arrester 12-24kV
Nexans Euromold 156SA Surge Arrester 12-24kV
Thorne & Derrick International
 
surge diverters
surge diverterssurge diverters
surge diverters
nehakardam
 
surge arrester
surge arrestersurge arrester
surge arrester
shubham kumar
 
Designing and testing of metal oxide surge arrester for EHV line
Designing and testing of metal oxide surge arrester for EHV lineDesigning and testing of metal oxide surge arrester for EHV line
Designing and testing of metal oxide surge arrester for EHV line
Rohit Khare
 
Surge arrester
Surge arresterSurge arrester
Surge arrester
pratikguptateddy
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
Gilberto Mejía
 
Matek 1 minggu 8-9
Matek 1   minggu 8-9Matek 1   minggu 8-9
Matek 1 minggu 8-9
Iwan Pranoto
 
NCA Grocery Prices Survey August 2010
NCA Grocery Prices Survey August 2010NCA Grocery Prices Survey August 2010
NCA Grocery Prices Survey August 2010
National Consumer Agency
 
Matek 1 - Minggu 3
Matek 1 - Minggu 3Matek 1 - Minggu 3
Matek 1 - Minggu 3
Iwan Pranoto
 
Week 6b
Week 6bWeek 6b
Week 6b
Iwan Pranoto
 
Kalkulus 2A minggu 7
Kalkulus 2A   minggu 7Kalkulus 2A   minggu 7
Kalkulus 2A minggu 7
Iwan Pranoto
 
NCA market research on consumers and transport
NCA market research on consumers and transportNCA market research on consumers and transport
NCA market research on consumers and transport
National Consumer Agency
 
Cgsm 4 pillars_of_marketing
Cgsm 4 pillars_of_marketingCgsm 4 pillars_of_marketing
Cgsm 4 pillars_of_marketinggwells9694
 
Bahan untuk Diskusi "Temani Aku Bunda"
Bahan untuk Diskusi "Temani Aku Bunda"Bahan untuk Diskusi "Temani Aku Bunda"
Bahan untuk Diskusi "Temani Aku Bunda"
Iwan Pranoto
 
Kalkulus 1A minggu 5
Kalkulus 1A   minggu 5Kalkulus 1A   minggu 5
Kalkulus 1A minggu 5
Iwan Pranoto
 
Connection Center - Outreach Commission
Connection Center - Outreach CommissionConnection Center - Outreach Commission
Connection Center - Outreach CommissionSt. Lukes UMC
 
Kalkulus 2 a minggu 5a
Kalkulus 2 a minggu 5aKalkulus 2 a minggu 5a
Kalkulus 2 a minggu 5a
Iwan Pranoto
 
Kalkulus 1A – minggu 2
Kalkulus 1A – minggu 2Kalkulus 1A – minggu 2
Kalkulus 1A – minggu 2
Iwan Pranoto
 
AHRI Article on HR 2.0
AHRI Article on HR 2.0AHRI Article on HR 2.0
AHRI Article on HR 2.0
gxdoyle
 

Viewers also liked (20)

Nexans Euromold 156SA Surge Arrester 12-24kV
Nexans Euromold 156SA Surge Arrester 12-24kVNexans Euromold 156SA Surge Arrester 12-24kV
Nexans Euromold 156SA Surge Arrester 12-24kV
 
surge diverters
surge diverterssurge diverters
surge diverters
 
surge arrester
surge arrestersurge arrester
surge arrester
 
Designing and testing of metal oxide surge arrester for EHV line
Designing and testing of metal oxide surge arrester for EHV lineDesigning and testing of metal oxide surge arrester for EHV line
Designing and testing of metal oxide surge arrester for EHV line
 
Surge arrester
Surge arresterSurge arrester
Surge arrester
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
 
Imvu
ImvuImvu
Imvu
 
Matek 1 minggu 8-9
Matek 1   minggu 8-9Matek 1   minggu 8-9
Matek 1 minggu 8-9
 
NCA Grocery Prices Survey August 2010
NCA Grocery Prices Survey August 2010NCA Grocery Prices Survey August 2010
NCA Grocery Prices Survey August 2010
 
Matek 1 - Minggu 3
Matek 1 - Minggu 3Matek 1 - Minggu 3
Matek 1 - Minggu 3
 
Week 6b
Week 6bWeek 6b
Week 6b
 
Kalkulus 2A minggu 7
Kalkulus 2A   minggu 7Kalkulus 2A   minggu 7
Kalkulus 2A minggu 7
 
NCA market research on consumers and transport
NCA market research on consumers and transportNCA market research on consumers and transport
NCA market research on consumers and transport
 
Cgsm 4 pillars_of_marketing
Cgsm 4 pillars_of_marketingCgsm 4 pillars_of_marketing
Cgsm 4 pillars_of_marketing
 
Bahan untuk Diskusi "Temani Aku Bunda"
Bahan untuk Diskusi "Temani Aku Bunda"Bahan untuk Diskusi "Temani Aku Bunda"
Bahan untuk Diskusi "Temani Aku Bunda"
 
Kalkulus 1A minggu 5
Kalkulus 1A   minggu 5Kalkulus 1A   minggu 5
Kalkulus 1A minggu 5
 
Connection Center - Outreach Commission
Connection Center - Outreach CommissionConnection Center - Outreach Commission
Connection Center - Outreach Commission
 
Kalkulus 2 a minggu 5a
Kalkulus 2 a minggu 5aKalkulus 2 a minggu 5a
Kalkulus 2 a minggu 5a
 
Kalkulus 1A – minggu 2
Kalkulus 1A – minggu 2Kalkulus 1A – minggu 2
Kalkulus 1A – minggu 2
 
AHRI Article on HR 2.0
AHRI Article on HR 2.0AHRI Article on HR 2.0
AHRI Article on HR 2.0
 

Similar to E367 dah heavy duty

Craig & Derricott Switch Disconnectors Catalogue
Craig & Derricott Switch Disconnectors CatalogueCraig & Derricott Switch Disconnectors Catalogue
Craig & Derricott Switch Disconnectors Catalogue
Thorne & Derrick International
 
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable TerminationsNexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Thorne & Derrick International
 
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingEuromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Thorne & Derrick International
 
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CNexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Thorne & Derrick International
 
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
Thorne & Derrick International
 
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVNexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Thorne & Derrick International
 
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Thorne & Derrick International
 
Acome Hypercell 2002 cable catalogue - kaapelikatalogi
Acome Hypercell 2002 cable catalogue - kaapelikatalogiAcome Hypercell 2002 cable catalogue - kaapelikatalogi
Acome Hypercell 2002 cable catalogue - kaapelikatalogi
Aerial Oy
 
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Thorne & Derrick International
 
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Thorne & Derrick International
 
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Thorne & Derrick International
 
Rubber insulated cable
Rubber insulated cableRubber insulated cable
Rubber insulated cable
辉 李
 
CMP E2FW130 - ATEX Cable Gland - 114.2-123.3mm
CMP E2FW130 - ATEX Cable Gland - 114.2-123.3mmCMP E2FW130 - ATEX Cable Gland - 114.2-123.3mm
CMP E2FW130 - ATEX Cable Gland - 114.2-123.3mm
Thorne & Derrick International
 
OVM250 Stay Cable System.ppt
OVM250 Stay Cable System.pptOVM250 Stay Cable System.ppt
OVM250 Stay Cable System.ppt
SaritaJoshi5
 
Prysmian KCA472 E1FW Flameproof Bicon Gland Kit
Prysmian KCA472 E1FW Flameproof Bicon Gland KitPrysmian KCA472 E1FW Flameproof Bicon Gland Kit
Prysmian KCA472 E1FW Flameproof Bicon Gland Kit
Thorne & Derrick International
 
Prysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SS
Prysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SSPrysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SS
Prysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SS
Thorne & Derrick International
 
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Thorne & Derrick International
 
Nexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface ENexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface E
Thorne & Derrick International
 
LS Cast Resin Transformer Catalogue
LS Cast Resin Transformer CatalogueLS Cast Resin Transformer Catalogue
LS Cast Resin Transformer Catalogue
hairxoawn
 
Mecatraction - Railway Connections, Crimps & Crimping Tools
Mecatraction - Railway Connections, Crimps & Crimping ToolsMecatraction - Railway Connections, Crimps & Crimping Tools
Mecatraction - Railway Connections, Crimps & Crimping Tools
Thorne & Derrick International
 

Similar to E367 dah heavy duty (20)

Craig & Derricott Switch Disconnectors Catalogue
Craig & Derricott Switch Disconnectors CatalogueCraig & Derricott Switch Disconnectors Catalogue
Craig & Derricott Switch Disconnectors Catalogue
 
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable TerminationsNexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
Nexans AFNP36 33kV Slip-On Outdoor High Voltage Cable Terminations
 
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C BushingEuromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
Euromold Connectors 400 Series Elbows 430TB - Interface Type C Bushing
 
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface CNexans MV Medium Voltage Compact Separable Connectors - Interface C
Nexans MV Medium Voltage Compact Separable Connectors - Interface C
 
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV400 Series Interface C Compact Nexans Euromold Cable Connectors HV
400 Series Interface C Compact Nexans Euromold Cable Connectors HV
 
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HVNexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
Nexans Euromold Connectors 400 Series Interface C Compact Cable Connectors HV
 
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
Nexans Euromold - Medium Voltage Compact Separable Connectors Interface C.
 
Acome Hypercell 2002 cable catalogue - kaapelikatalogi
Acome Hypercell 2002 cable catalogue - kaapelikatalogiAcome Hypercell 2002 cable catalogue - kaapelikatalogi
Acome Hypercell 2002 cable catalogue - kaapelikatalogi
 
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
Heat Shrink Cable Joints & Cable Terminations LV HV, 6.6kV 11kV 33kV - SPS Ca...
 
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
 
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
 
Rubber insulated cable
Rubber insulated cableRubber insulated cable
Rubber insulated cable
 
CMP E2FW130 - ATEX Cable Gland - 114.2-123.3mm
CMP E2FW130 - ATEX Cable Gland - 114.2-123.3mmCMP E2FW130 - ATEX Cable Gland - 114.2-123.3mm
CMP E2FW130 - ATEX Cable Gland - 114.2-123.3mm
 
OVM250 Stay Cable System.ppt
OVM250 Stay Cable System.pptOVM250 Stay Cable System.ppt
OVM250 Stay Cable System.ppt
 
Prysmian KCA472 E1FW Flameproof Bicon Gland Kit
Prysmian KCA472 E1FW Flameproof Bicon Gland KitPrysmian KCA472 E1FW Flameproof Bicon Gland Kit
Prysmian KCA472 E1FW Flameproof Bicon Gland Kit
 
Prysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SS
Prysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SSPrysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SS
Prysmian KCA472-71 Flameproof (ATEX) Cable Gland - E1FW 20SS
 
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
Nexans Euromold Interface E 5/8" 700 Series Cable Connectors
 
Nexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface ENexans Euromold MV Separable Connectors & Bushings - Interface E
Nexans Euromold MV Separable Connectors & Bushings - Interface E
 
LS Cast Resin Transformer Catalogue
LS Cast Resin Transformer CatalogueLS Cast Resin Transformer Catalogue
LS Cast Resin Transformer Catalogue
 
Mecatraction - Railway Connections, Crimps & Crimping Tools
Mecatraction - Railway Connections, Crimps & Crimping ToolsMecatraction - Railway Connections, Crimps & Crimping Tools
Mecatraction - Railway Connections, Crimps & Crimping Tools
 

Recently uploaded

一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
ydteq
 
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdfBPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
MIGUELANGEL966976
 
Water billing management system project report.pdf
Water billing management system project report.pdfWater billing management system project report.pdf
Water billing management system project report.pdf
Kamal Acharya
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024
Rahul
 
ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...
ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...
ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...
Mukeshwaran Balu
 
bank management system in java and mysql report1.pdf
bank management system in java and mysql report1.pdfbank management system in java and mysql report1.pdf
bank management system in java and mysql report1.pdf
Divyam548318
 
Unbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptxUnbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptx
ChristineTorrepenida1
 
一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理
一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理
一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理
dxobcob
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
Modelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdfModelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdf
camseq
 
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming PipelinesHarnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
Christina Lin
 
[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf
[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf
[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf
awadeshbabu
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
Fundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptxFundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptx
manasideore6
 
Tutorial for 16S rRNA Gene Analysis with QIIME2.pdf
Tutorial for 16S rRNA Gene Analysis with QIIME2.pdfTutorial for 16S rRNA Gene Analysis with QIIME2.pdf
Tutorial for 16S rRNA Gene Analysis with QIIME2.pdf
aqil azizi
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
SyedAbiiAzazi1
 
PROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.ppt
PROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.pptPROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.ppt
PROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.ppt
bhadouriyakaku
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
thanhdowork
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
Dr Ramhari Poudyal
 

Recently uploaded (20)

一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
 
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdfBPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
 
Water billing management system project report.pdf
Water billing management system project report.pdfWater billing management system project report.pdf
Water billing management system project report.pdf
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024ACEP Magazine edition 4th launched on 05.06.2024
ACEP Magazine edition 4th launched on 05.06.2024
 
ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...
ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...
ACRP 4-09 Risk Assessment Method to Support Modification of Airfield Separat...
 
bank management system in java and mysql report1.pdf
bank management system in java and mysql report1.pdfbank management system in java and mysql report1.pdf
bank management system in java and mysql report1.pdf
 
Unbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptxUnbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptx
 
一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理
一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理
一比一原版(Otago毕业证)奥塔哥大学毕业证成绩单如何办理
 
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
Modelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdfModelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdf
 
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming PipelinesHarnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
 
[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf
[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf
[JPP-1] - (JEE 3.0) - Kinematics 1D - 14th May..pdf
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
Fundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptxFundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptx
 
Tutorial for 16S rRNA Gene Analysis with QIIME2.pdf
Tutorial for 16S rRNA Gene Analysis with QIIME2.pdfTutorial for 16S rRNA Gene Analysis with QIIME2.pdf
Tutorial for 16S rRNA Gene Analysis with QIIME2.pdf
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
 
PROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.ppt
PROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.pptPROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.ppt
PROJECT FORMAT FOR EVS AMITY UNIVERSITY GWALIOR.ppt
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
 

E367 dah heavy duty

  • 1. Bowthorpe EMP Distribution Metal Oxide Surge Arrester DAH Series (IEEE) Heavy Duty Energy Division
  • 2. Sealing: All arrester cores are encapsulated in silicone insulating housing. A permanent chemical bond connects the arrester core and the non-tracking silicone housing. This invisible interface prevents moisture from entering during severe thermal fluctuations due to normal climatic and energy absorption events. Polymer housing: Non-tracking and hydrophobic silicone insulating material is used for DA arrester housings. The DA surge arrester series is available with standard or extra leakage distance. The housing material has proven performance in long term TERT and UV aging tests and proven resistance to flammability. Integrated design: Manufacturing integrates all components in a single piece. There are no glued interfaces. The design is void and gap free ensuring peak performance under the harshest conditions. Reliable and consistent GLD The robust ground lead disconnect (GLD) offers operational reliability and consistency. It was designed to operate in event of arrester failure, removing ground connection and fault from line. It can be shipped and stored restriction free. Safe mode of failure: Our high energy arresters are tested in accordance with the short circuit mode of failure test in IEEE C62.11, (2005). This testing has proven the DAH’s safe and predictable failure characteristics. Quality: The DAH series arrester is manufactured to international quality standards in Tyco Electronics production facilities. We perform 100% routine testing on arresters: 1) Visual inspection 2) Reference voltage test 3) Power loss test 4) Partial discharge test Tyco Electronics’ Bowthorpe EMP business group pioneered the development of polymeric com- posite housed surge arresters in the early 1980’s and since then has proven service experience across the globe, operating in the world’s toughest environments. DA Series surge arresters provide active over voltage protection that contributes directly to improved reliability of your system, reducing lost minutes and protecting expensive assets. Tyco Electronics Bowthorpe EMP DA silicone surge arresters have been designed and tested to meet customers’ demand for reliability and improved operational perfor- mance. DA development was based on 30 years of experience in arrester design and manufacturing within the Tyco Electronics Energy Division. The DAH series is qualified to the latest revision of IEEE C62.11, (2005) and all reports are independently certified. Summary of Heavy Duty Arrester (DAH) series technical characteristics Ur (kV) 3.5 – 36 In (kA) 10 High current impulse (kA) 100 Arrester type Heavy duty Long duration current (A /µs) 250 / 2000 10s TOV (kV) 1.4 * MCOV High current short circuit (kA) 21 Arrester technology ZnO gapless Mold in place 2 DAH Series
  • 3. Qualification testing: The following IEEE C62.11, (2005) design type tests have been carried out on the DA series arresters: 1) Arrester insulation withstand tests 2) Discharge-voltage characteristics 3) Accelerated aging procedure 4) Accelerated aging tests of external polymeric insulating systems 5) Accelerated aging of the polymer housing with exposure to salt fog (rotating wheel) 6) Contamination test 7) Distribution class surge arrester seal integrity design test 8) Partial Discharge tests 9) High-current short-duration withstand test 10)Low-current long-duration withstand test 11) Duty-cycle tests 12) TOV tests 13) Short-circuit test for polymer housed distribution arresters 14)Distribution arrester disconnector tests 15) Mechanical tests The silicone insulating material has been designed and optimized for arrester application. The following additional testing was performed in the qualification of the silicone: 1) Tracking and Erosion 2) UV testing 3) Thermal endurance 4) Dielectric testing 5) Flammability testing. 6) Long term water immersion testing Production and Quality: All Tyco Electronics arrester production facilities have implemented QC and QA procedures according to international standards to ensure test programs that guarantee quality conforming products. 100% of all varistors are tested and stamped with unique varistor residual and reference voltage. The following tests are performed on varistors: 1) Residual voltage 2) Reference voltage 3) Leakage current 4) Physical examination to screen damaged varistors 5) LOT test: High current impulse test 6) LOT test: Aging test At the end of the arrester assembly process, the following mandatory IEEE tests are completed on every arrester: 1) Visual inspection 2) Reference voltage test 3) Power loss test 4) Partial discharge testing DAH Series 3 Birdcap Aluminum fittings Silicone rubber housing Mold in Place ZnO varistors Glass filled epoxy laminate Bracket GLD Ground clamp Surge arrester name plate
  • 4. DAH Series Application: Designed and optimized to protect distribution assets including transformers and cable-end terminations from lightning and switching surge related over- voltages. Generic technical data: DAH series 3.5 - 36 kV Rated discharge current (8/20µs): 10 kA Heavy Duty Arrester IEEE C62.11, (2005) Operating duty impulse withstand current (4/10µs): 100 kA Long duration current impulse (2000µs): 250 A 10 second TOV, (kV) 1.4 * MCOV Mechanical data Cantilever 258 ft.-lbs Tension 450 Ibf Torque 36.9 ft.-lbs Bowthorpe EMP DAH series surge arrester benefits: Tested in accordance with IEEE 62.11, 2005 Direct molded housing to prevent moisture ingress Low residual voltages High-energy handling Safe non-shattering short circuit behavior to higher current levels Maintenance free Hydrophobic silicone housing: (Tracking and erosion resistant) Excellent cantilever and tensile performance Quality design and manufacturing meeting international standards Uw = TOV withstand voltage; Ur = Rated voltage Temporary over-voltage curve (TOV) Time (s) 0.1 1.48 1.44 1.40 1.36 1.32 1.28 1.24 100010010 Uw/MCOV 1 10000 4 DAH TOV Sample product marking, DAH-30F
  • 5. DAH series arrester standard electrical data: DAH Series Residual voltage in kV when tested to the following test waveforms Ur MCOV Front of Lightning (8/20µs) Switching Part Number kV kV wave 1.5kA 3kA 5kA 10kA 20kA 40kA 500A DAH-04 3.5 2.95 11.1 8.9 9.4 9.8 10.5 11.6 12.6 8.3 DAH-06 6.0 5.10 19.1 15.3 16.1 16.9 18.0 19.9 21.6 14.2 DAH-09 9.0 7.65 28.6 22.9 24.2 25.3 27.0 29.9 32.4 21.3 DAH-10 10.0 8.40 31.8 25.5 26.8 28.1 30.0 33.2 36.0 23.6 DAH-12 12.0 10.2 38.1 30.5 32.2 33.7 36.0 39.8 43.2 28.4 DAH-15 15.0 12.7 47.7 38.2 40.3 42.1 45.1 49.8 54.0 35.5 DAH-18 18.0 15.3 57.2 45.8 48.3 50.6 54.1 59.7 64.8 42.5 DAH-21 21.0 17.0 66.7 53.5 56.4 59.0 63.1 69.7 75.6 49.6 DAH-24 24.0 19.5 76.3 61.1 64.4 67.4 72.1 79.6 86.4 56.7 DAH-27 27.0 22.0 85.8 68.7 72.5 75.8 81.1 89.6 97.2 63.8 DAH-30 30.0 24.2 95.3 76.4 80.5 84.3 90.1 99.5 108.0 70.9 DAH-36 36.0 29.0 114.4 91.6 96.6 101.1 108.1 119.4 129.6 85.1 Housing Leakage Flash over Dry 10s Wet Height Weight code distance lightning withstand (1.2 / 50) inches inches kV kV inches lb A 12.95 5.98 150 45 5.79 2.64 B 15.9 6.97 170 55 6.77 2.97 C 21.77 8.94 199 74 8.74 3.96 E 27.64 10.9 219 86 10.7 4.84 F 30.55 11.89 253 95 11.72 5.72 G 36.42 13.86 254 115 13.7 6.45 DAH series arrester standard housing parameters: Housing code: A B C E F G Ur Leakage: 12.95 15.9 21.77 27.64 30.55 36.42 3.5 ● ■ 6 ● ■ 9 ● ■ 10 ● ■ ■ 12 ● ■ ■ 15 ● ■ ■ 18 ● ■ ■ 21 ● ■ ■ 24 ● ■ 27 ● ■ 30 ● ■ 36 ● ■ ● standard housing ■ optional housing Housing and Ur compatibility: 2in 4.1in 5 L
  • 6. 6 DAH Series Arrester Ordering Information: Z Z Z - Y Y M - 1 2 3 4 5 6 - P Naming convention cross reference: ZZZ = series type: DAH for 10kA, heavy duty arrester YY = Ur M = Housing code (see page 5) Packaging I Individual Packing S 3 Pack B Bulk Packing Line lead accessories Bxxxxx Birdcap with F accessory Exxxxx Birdcap with M accessory Fxxxxx 1.7” stud for lug connection Hxxxxx Cap screw & spring washer Mxxxxx 1.7” stud for line lead connection Oxxxxx No stud. No accessories 1 Line lead options x0xxxx No line lead wire x1xxxx 18” No. 6 AWG copper line lead with one 3/8” lug x2xxxx 36” No. 6 AWG copper line lead with one 3/8” lug x3xxxx 36” No. 6 AWG copper line lead with no lug x4xxxx 18” No. 4 AWG copper line lead with one 3/8” lug x5xxxx 36” No. 4 AWG copper line lead with one 3/8” lug x6xxxx 36” No. 4 AWG copper line lead with no lug x8xxxx 36” No. 6 AWG copper line lead with two 3/8” lugs 2 Ground lead accessories: xxDxxx Disconnect + M accessory xxExxx Disconnect + F accessory xxFxxx 1.7” stud for lug connection xxHxxx 3/8”*1” Cap screw & spring washer xxMxxx 1.7” stud for line lead connection xxOxxx No stud. No accessories 3 Additional accessories are available upon request Ground lead options xxx0xx No Ground Lead Wire xxx1xx 18” No. 6 AWG Copper Ground Lead with one 3/8” lug xxx2xx 36” No. 6 AWG Copper Ground Lead with one 3/8” lug xxx3xx 36” No. 6 AWG Copper Ground Lead with no lug xxx4xx 18” No. 4 AWG Copper Ground Lead with one 3/8” lug xxx5xx 36” No. 4 AWG Copper Ground Lead with one 3/8” lug xxx6xx 36” No. 4 AWG Copper Ground Lead with no lug xxx8xx 36” No. 6 AWG Copper Ground Lead with two 3/8” lugs xxx9xx 12” No. 6 AWG Copper Ground strap 4 xxxxBx Insulating bracket xxxxNx No mounting accessories xxxxPx Ped- estal mount- ing base xxxxx0 No option xxxxx1 NEMA cross arm bracket Mounting bracket options:Mounting brackets:5 6 Transformer mounting bracket xxxxx5 Transformer mounting bracket 14.5” xxxxx2 8.7” xxxxx3 11” xxxxx4 12.25”
  • 7. Clearance for Ø 3/8” Clearance for Ø 0.5” 6” 8” 1.7” 3/8” 3/4”max Mxxxxx & xxMxxxx: Stainless steel line lead connection, (up to diameter 0.63”) Fxxxxx & xxFxxxx: Stainless steel lug connection 7 DAH Series Arrester Accessories 1.7” 3/8” xxxxAx: Galvanized steel Straight 2hole mounting metal bracket 2” For additional accessory options, please contact your Tyco Electronics Energy sales engineer. Oxxxxx & xxOxxx No accessories 3/4” 3/8” Hxxxxx & xxHxxx Cap screw connection 1/4” 2.76” 1.38” Ø 2.5” Bxxxxx & Exxxxx: Tracking and erosion resistant bird protection cover xxDxxx and xxExxx: ground lead disconnect 1.1”3/8”
  • 8. 8 DAH Series Arrester Accessories xxxxx1: Galvanized steel NEMA cross arm mounting bracket For additional accessory options, please contact your Tyco Electronics Energy sales engineer. 1/2” Ø 0.562” 8.7” XXXXX2: Galvanized transformer mounting bracket 8.7” 2.5” XXXXX3: Galvanized transformer mounting bracket 11” XXXXX4: Galvanized transformer mounting bracket 12.25” XXXXX5: Galvanized transformer mounting bracket 14.5” 5.7” 1.687” 1.5” 1/2” Ø 0.562” 11” 2.5” 7” 1.687” 1.5” 1/2” Ø 0.562” 12.5” 2.5” 7” 1.687” 1.5” 1/2” Ø 0.562” 14.5” 12.875” 2.187” 1.5” 2.187”1.562”1.562” 1.25” 3” 4.125-5.15” 2.7-4.75” 8.7” 4.5” 0.342” 2.25”
  • 9. 9 DAH Series Arrester Accessories 6.85” 5.09” Clearance for 1/2” Clearance for 1/2” 7.95” 6.2” xxxxBx: Insulating brackets 12kV < Ur <= 24kV Ur > 24kV 5.75” 4” Clearance for 1/2” Ur <= 12kV Note: xxxxBx can only be used with either xxDxxx or xxExxx accessory.
  • 10. 10 Other Bowthorpe EMP Distribution Surge Arrester Products Hydrophobic siliconeTypical application Tracking and erosion test Class 2 OCP series arrester Tyco Electronics Bowthorpe EMP OCP2 surge arresters are used in overhead line to cable junction and substation protection applica- tions. These arresters are manufac- tured using high energy and low residual voltage ZnO varistors, which display excellent thermal and current handling characteristics, delivering optimal protection. Generic technical data: OCP2 series 3-41kV Uc Rated discharge current (8/20µs): 10kA Line discharge class 2 according to IEC 60099-4 Operating duty impulse withstand current (4/10µs): 100kA Long duration current impulse (2000µs): 530A High current short circuit: (pre-failing method) 40kA (Safe non-shattering failure mode) Energy 2 Long duration impulses: 6.0kJ/kVUc with CLXTypical application without CLX Protection for covered conductor systems Tyco Electronics Bowthorpe EMP CLX protection for covered conductor systems is designed for lightning protection in overhead lines with covered conductors to prevent conductor breakage. Generic technical data: CLX / MORE series 11-33kV systems Rated discharge current (8/20µs): 10kA Operating duty impulse withstand current (4/10µs): 65kA Long duration current impulse (1000µs): 250A High current short circuit: (pre-failing method) 25kA Energy 2 Long duration impulses: 2.9kJ/kVUc
  • 11. Type Application Rating [kA] Line Continuous discharge voltage [kV] class from to MV arresters for outdoor application DAR Outdoor riser pole arrester 10 Riser 3.5 36 HDA Outdoor high pollution application 10 1 3 41 OCP2 Outdoor Cable and substation protection 10 2 3 41 Arresters for protection systems CLX Protection of covered conductor systems 10 1 3 36 MV arresters for indoor application RDA Protection of gas insulated switchgear 10 1 3 26 SPA Protection of air insulated switchgear 10 1 3 36 MPA Motor protection 10 1 3 6 CPA Cable sheath protection 10 1 3 6 RSTI-SA Screened separable surge arrester 5, 10 n.a. 12 24 LV arresters LVA Transformer secondary protection 10 n.a. 0,28 0,441 Arresters for railway application HE60 DC railway protection 10 n.a. 1 6 11 Tyco Electronics Energy Division total commitment to quality Even the best technology must be backed up by a thorough and consistent quality assurance program. At Tyco Electronics, we subject every product to an extensive quality control regimen. At every production stage, beginning with the raw materials and continuing through to the packaged product, the QC lab tests all physical and electrical characteristics which can influence performance. By means of lot numbers, the Quality Assurance Program ensures traceability all the way to details of the compound batch test reports. Quality assurance at Tyco Electronics is not static, but a constantly improving process directed toward our goal of complete customer satisfaction. Tyco Electronics Energy Division arrester manufacturing sites are accredited to international quality standards. Our vendor routine tests and internal incoming inspection confirm performance of all critical components used in the assembly of our arresters. Tyco Electronics Arrester Overview
  • 12. Energy Division – innovative and economical solutions for the electrical power industry: cable accessories, connectors & fittings, insulators & insulation, surge arresters, switching equipment, lighting controls, power measurement and control. Other Products Available from Tyco Electronics Energy Division Asset protection Low-voltage surge arresters Insulation enhancement systems for substations and overhead. Designed to prevent unplanned outages due to accidental bridging and to help upgrade insulation levels at critical points in systems. LV arresters are used to provide protection for LV overhead lines, consumer in-house supplies, distribution transformers and other appliances. Metal oxide varistor, distribution arresters for indoor and outdoor applications for protection of overhead lines, DC locomotives and switchgear applications. Porcelain and polymeric series parallel and single column constructed arresters for protection of transmission systems up to 550 kV. Insulators and insulating components/housings providing reliable solutions for power utilities and railway customers with installations in high pollution environments and applications up to 400 kV. Insulators for applications up to system voltages of 132 kV. This range of insulators offers a cost-effective solution for low and medium polluted environments. Medium-voltage surge arresters High-voltage surge arresters Polymeric insulators Porcelain insulators While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalog, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics’ only obligations are those stated in Tyco Electronics’ Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. In case of any potential ambiguities or questions, please don’t hesitate to contact us for clarification. Bowthorpe EMP, TE (Logo) and Tyco Electronics are trademarks. Tyco Electronics Corporation 8000 Purfoy Road Fuquay Varina, NC 27526-9349 Tel: 800.327.6996 Fax: 800.527.8350 E-mail: naenergy@tycoelectronics.com www.tycoelectronics.com Copyright 2009 Tyco Electronics Corporation All rights reserved 9-1773455-6 E367 12/09