Stranded Plain Annealed Copper Conductor ___________________________________________________ 2
PVC Cables – Single Core _________________________________________________________________ 3
PVC/ PVC Cables – 1 Core & 2 Cores _______________________________________________________ 4
PVC/ PVC Cables – 3 Cores & 4 Cores _______________________________________________________ 5
PVC/ PVC Cables – Multi Cores ____________________________________________________________ 6
PVC/ AWA/ PVC Cables – Single Core ______________________________________________________ 7
PVC/ SWA/ PVC Cables – 2 Cores, 3 Cores & 4 Cores __________________________________________ 8
PVC/ SWA/ PVC Cables - Multi Cores_______________________________________________________ 9
Flexible Cable, Circular Sheathed, Metric Unit - 2 Cores, 3 Cores & 4 Cores _________________________ 10
Flexible Cord, Twin Twisted, Imperial Unit ___________________________________________________ 11
Flexible Cable, Circular Sheathed, Imperial Unit – 1 Core, 2 Cores, 3 Cores & 4 Cores _________________ 11
XLPE/ PVC & XLPE/ AWA/ PVC Cables – Single Core _________________________________________ 12
XLPE/ PVC & XLPE/ SWA/ PVC Cables - 2 Cores, 3 Cores & 4 Cores _____________________________ 13
XLPE/ PVC & XLPE/ SWA/ PVC Cables – Multi Cores _________________________________________ 14
IN-POP & IN-POSP - Multi Cores __________________________________________________________ 15
IN-POP & IN-POSP – Single & Multi Pairs ___________________________________________________ 16
IN-PIOP & IN-PIOSP – Multi Pairs _________________________________________________________ 17
IN-EOP & IN-EOSP – Single & Multi Pairs ___________________________________________________ 18
IN-EIOP & IN-EIOSP – Multi Pairs _________________________________________________________ 19
XLPE/ CT/ AWA/ PVC Cables – Single Core _________________________________________________ 20
XLPE/ CT/ SWA/ PVC Cables – 4 Cores _____________________________________________________ 21
XLPE/ CT/ PVC Cables – 3 Cores + 3 Earth ___________________________________________________ 22
Schedule of Installation Methods of Cables ____________________________________________________ 23
Correction Factors _______________________________________________________________________ 26
Current Rating and Voltage Drop (PVC Insulated Cables) ________________________________________ 28
Current Rating and Voltage Drop (XLPE Insulated Cables) _______________________________________ 32
Current Rating and Voltage Drop (Flexible Cables) _____________________________________________ 36
Short Circuit Current for PVC Insulated & XLPE Insulated Cables _________________________________ 37
Short Circuit Ratings _____________________________________________________________________ 38
Additional Technical Information ___________________________________________________________ 39
Conversion Tables of Conductor Size ________________________________________________________ 40
2
Stranded Plain Annealed Copper Conductor BS 66360 & IEC 60228 Table 1
Nominal
Conductor
Area
No. and
Diameter
of Wire
No. and
Diameter
of Conductor
Maximum
Conductor
Resistance at 200
C
Nominal Weight
per km
of Conductor
(mm2
) (no./mm) (mm) (Ω/km) (kg/km)
1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
7/ 0.43
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
61/ 2.85
61/ 3.20
127/ 2.52
127/ 2.85
127/ 3.20
1.29
1.59
2.01
2.55
3.12
4.05
5.10
6.42
7.56
8.90
10.70
12.60
14.21
15.75
17.64
20.25
22.68
25.65
28.80
32.76
37.05
41.60
18.1
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
9.2
14.0
22.4
36.1
54
90.8
145
229
317
429
620
860
1086
1334
1673
2199
2759
3528
4448
5744
7346
9260
Construction Technical Data
1. Conductor : Plain Annealed Copper Conductor Stranding : Class 2 stranded circular or compacted conductors
3
PVC Cables SS358 Table 2
Nominal
Conductor
Area
No. and Diameter
Of
Wire
Radial Thickness
Of
Insulation
Mean Overall
Diameter
(Upper Limit)
Approx.
Weight
Minimum Insulation
Resistance
at 700
C
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mΩ/ km)
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
61/ 2.85
61/ 3.20
127/ 2.52
0.7
0.8
0.8
0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
3.4
4.2
4.8
5.4
6.8
8.0
9.8
11.0
13.0
15.0
17.0
19.0
21.0
23.5
26.5
29.5
33.5
37.0
41.0
22.7
34.0
50.0
70.9
117.5
177.4
279.5
372.0
504.5
710.6
980.8
1216.0
1498.0
1874.0
2444.4
3059.5
3897.0
4940.0
6295.0
0.010
0.009
0.0077
0.0065
0.0065
0.0050
0.0050
0.0040
0.0045
0.0035
0.0035
0.0032
0.0032
0.0032
0.0032
0.0030
0.0028
0.0028
0.0025
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type C
3. Colour: Red, Yellow, Blue, Black, Green,
White, or Green/ Yellow
Voltage Uo/U: 450/ 750V
Conductor Stranding: Class 2 stranded circular or compacted
conductors
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 3D for D < 10mm
4D for 10mm < D < 25mm
6D for D > 25mm
4
PVC/ PVC Cables IEC 60502 Table 3
Nominal
Conductor
Area
No. and Diameter
of
Wire
Radial Thickness
of
Insulation
Approx.
Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
61/ 2.85
61/ 3.20
127/ 2.52
127/ 2.85
127/ 3.20
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
2.8
3.0
6.3
6.7
7.6
8.2
9.2
10.2
11.9
13.1
14.8
16.6
19.2
20.8
23.0
25.4
28.7
31.7
35.3
39.5
43.2
47.7
53.0
55
70
100
125
175
240
350
460
595
810
1110
1360
1670
2070
2690
3340
4230
5290
6680
8460
10545
2 x 1.5
2 x 2.5
2 x 4
2 x 6
2 x 10
2 x 16
2 x 25 (S)
2 x 35 (S)
2 x 50 (S)
2 x 70 (S)
2 x 95 (S)
2 x 120 (S)
2 x 150 (S)
2 x 185 (S)
2 x 240 (S)
2 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
10.4
11.2
13.1
14.2
16.1
18.2
21.8
24.0
23.0
26.0
30.0
32.0
36.0
40.0
44.0
49.0
145
180
255
285
395
590
900
1160
1260
1700
2310
2880
3520
4290
5570
6970
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type A
3. Sheath: PVC Compound Type ST1
4. Colour: Insulation: 1 Core - Black
2 Cores- Red & Black
Sheath: 1 Core – Grey
2 Cores - Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 1 Core –
8D for 1.5mm2
to 1000mm2
2 Cores –
8D for 1.5mm2
to 300mm2
5
PVC/ PVC Cables IEC 60502 Table 4
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Approx.
Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
3 x 1.5
3 x 2.5
3 x 4
3 x 6
3 x 10
3 x 16
3 x 25 (S)
3 x 35 (S)
3 x 50 (S)
3 x 70 (S)
3 x 95 (S)
3 x 120 (S)
3 x 150 (S)
3 x 185 (S)
3 x 240 (S)
3 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
10.9
11.8
13.8
15.0
17.1
19.3
23.2
25.7
26.0
29.0
34.0
37.0
40.0
45.0
51.2
56.0
165
210
305
370
515
740
1160
1520
1750
2435
3360
4140
5070
6330
8265
10355
4 x 1.5
4 x 2.5
4 x 4
4 x 6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 35 (S)
4 x 50 (S)
4 x 70 (S)
4 x 95 (S)
4 x 120 (S)
4 x 150 (S)
4 x 185 (S)
4 x 240 (S)
4 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.8
0.8
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
11.7
12.8
15.0
16.4
18.6
21.2
25.6
28.4
26.0
29.0
33.0
39.0
42.5
47.0
52.0
58.2
65.0
200
255
375
455
665
930
1465
1920
1740
2320
3215
4400
5440
6675
8360
10870
13650
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type A
3. Sheath: PVC Compound Type ST1
3. Colour: Insulation: 3 Cores – Red, Yellow, Blue
4 Cores- Red , Yellow, Blue,
Black
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 8D for 1.5mm2
to 300mm2
PVC/ PVC Cables Table 5
No.
of
Nominal
Conductor
No. and
Diameter
Radial
Thickness
Approx.
Overall
Approx.
Weight
6
Cores Area of Wire of Insulation Diameter
(mm2
) (no./mm) (mm) (mm) (kg/ km)
2
3
4
5
7
10
12
19
27
37
48
1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
8.8
9.2
10.0
10.8
11.7
14.8
15.2
17.9
21.4
24.0
27.6
109
129
154
190
240
330
385
560
770
1015
1300
2
3
4
5
7
10
12
19
27
37
48
2.5
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
10.0
10.6
11.5
12.7
13.7
17.4
18.0
21.2
25.4
28.6
33.0
148
171
218
270
340
490
560
820
1135
1560
1930
2
3
4
5
7
10
12
19
27
37
48
4
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
11.5
12.2
13.3
14.7
16.2
20.6
21.3
25.1
30.4
34.2
39.3
205
252
315
415
535
720
850
1260
1740
2300
2900
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Sheath: PVC Compound Type TM1
3. Colour: Insulation: White with Black numberings
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 3D for D < 10mm
4D for 10mm < D < 25mm
6D for D > 25mm
7
PVC/ AWA/ PVC Cables BS 6346 Table 6
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Approx.
Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
50
70
95
120
150
185
240
300
400
500
630
800
1000
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
61/ 2.85
61/ 3.20
127/ 2.52
127/ 2.85
127/ 3.20
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
2.8
2.8
2.8
3.0
19.1
21.1
23.4
26.3
28.3
30.8
34.1
37.0
42.0
45.6
49.7
55.8
61.0
760
1010
1330
1690
2110
2450
3120
3810
4890
5990
7510
9590
11820
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Bedding: PVC Compound Type TM1
4. Armour: Aluminium Wire
5. Sheath: PVC Compound Type TM1
6. Colour: Insulation: Black
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 6D for 50mm2
to 1000mm2
8
PVC/ SWA/ PVC Cables BS 6346 Table 7
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Approx.
Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
2 x 1.5
2 x 2.5
2 x 4
2 x 6
2 x 10
2 x 16
2 x 25
2 x 35
2 x 50 (S)
2 x 70 (S)
2 x 95 (S)
2 x 120 (S)
2 x 150 (S)
2 x 185 (S)
2 x 240 (S)
2 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.6
0.7
0.8
0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
12.3
13.6
15.1
16.5
20.1
21.9
26.7
29.4
27.4
30.0
34.7
37.2
40.5
45.2
50.0
54.8
270
340
450
550
750
960
1400
1750
1990
2500
2460
4120
4890
6250
7860
9480
3 x 1.5
3 x 2.5
3 x 4
3 x 6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50 (S)
3 x 70 (S)
3 x 95 (S)
3 x 120 (S)
3 x 150 (S)
3 x 185 (S)
3 x 240 (S)
3 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.6
0.7
0.8
0.8
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
12.8
14.1
15.8
18.0
21.2
23.1
28.2
30.8
30.1
34.2
38.5
41.4
46.3
50.7
56.2
61.6
350
400
520
730
1010
1180
1760
2170
2560
3520
4640
5500
6970
8400
10550
12800
4 x 1.5
4 x 2.5
4 x 4
4 x 6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 35 (S)
4 x 50 (S)
4 x 70 (S)
4 x 95 (S)
4 x 120 (S)
4 x 150 (S)
4 x 185 (S)
4 x 240 (S)
4 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.6
0.7
0.8
0.8
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
13.5
15.0
17.8
19.2
22.8
26.3
30.7
33.7
29.9
34.6
38.4
43.5
48.1
52.4
57.4
64.1
70.4
345
440
710
810
1130
1550
2150
2670
2510
3410
4400
5830
7400
8810
10660
13430
16330
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Bedding: PVC Compound Type TM1 or Lapped PVC Tape
4. Armour: Galvanised Steel Wire
5. Sheath: PVC Compound Type TM1
6. Colour: Insulation: 2 Cores- Red, Black
3 Cores – Red, Yellow, Blue
4 Cores – Red, Yellow, Blue, Black
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 6D for 1.5mm2
to 16mm2
8D for 25mm2
and above
PVC/SWA/ PVC Cables BS 6346 Table 8
No. Nominal No. and Radial Approx. Approx.
9
Of
Cores
Conductor
Area
Diameter
of Wire
Thickness
of Insulation
Overall Diameter Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
5
7
10
12
19
27
37
48
1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
14.3
15.2
19.0
19.4
22.2
26.7
29.2
32.9
357
416
446
716
938
1380
1689
2048
5
7
10
12
19
27
37
48
2.5
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
7/ 0.67
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
16.3
18.0
21.9
22.4
26.6
30.7
34.0
39.5
465
557
878
955
1455
1885
2340
3190
5
7
10
12
19
27
37
48
4
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
7/ 0.85
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
19.0
20.5
26.1
26.8
30.5
37.1
40.8
46.0
750
905
1405
1530
2060
3025
3900
4800
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Bedding: PVC Compound Type TM1
or Lapped PVC Tape
4. Armour: Galvanised Steel Wire
5. Sheath: PVC Compound Type TM1
6. Colour: Insulation:White with Black numberings
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 700
C
Minimum Bending Radius: 6D for 1.5mm2
to 4mm2
10
Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.1
Conductor Thickness
of
Insulation
2 Cores
Nominal
Area
Construction
Approx.
Overall Diameter
Approx.
Net Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
0.5
0.75
1.0
1.25
1.5
2.5
4.0
16/ 0.20
24/ 0.20
32/ 0.20
40/ 0.20
30/ 0.25
50/ 0.25
56/ 0.30
0.6
0.6
0.6
0.7
0.7
0.8
0.8
6.1
6.6
6.9
7.6
7.8
9.6
11.0
55
65
75
80
90
135
135
Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.2
Conductor Thickness
of
Insulation
2 Cores
Nominal
Area
Construction
Approx.
Overall Diameter
Approx.
Net Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
0.5
0.75
1.0
1.25
1.5
2.5
4.0
16/ 0.20
24/ 0.20
32/ 0.20
40/ 0.20
30/ 0.25
50/ 0.25
56/ 0.30
0.6
0.6
0.6
0.7
0.7
0.8
0.8
6.5
6.9
7.3
8.3
8.5
10.4
11.8
60
75
85
100
110
170
215
Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.3
Conductor Thickness
of
Insulation
2 Cores
Nominal
Area
Construction
Approx.
Overall Diameter
Approx.
Net Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km)
0.5
0.75
1.0
1.25
1.5
2.5
4.0
16/ 0.20
24/ 0.20
32/ 0.20
40/ 0.20
30/ 0.25
50/ 0.25
56/ 0.30
0.6
0.6
0.6
0.7
0.7
0.8
0.8
7.1
7.6
8.2
-
9.5
11.4
12.9
75
90
110
-
140
205
275
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation : PVC Compound Type TI2
3. Assembly : 2, 3 or 4 Cores are Twisted Together
4. Sheath : PVC Compound Type TM2
Voltage Uo/U: 300/ 500V
Conductor Stranding: Class 5
Operating Temperature: 700
11
Flexible Cord, Twin Twisted Non- Sheated, Imperial Unit BS 2004 Table 10.1
Conductor Thickness
of
Insulation
Twin Twisted
Nominal
Area
Construction
Approx.
Overall Diameter
Approx.
Net Weight
(mm2
) (no./in) (mm) (mm) (kg/ 100y)
0.41
0.67
1.17
14/ 0.0076
23/ 0.0076
40/ 0.0076
0.64
0.64
0.64
2.1
2.4
2.7
1.7
2.3
3.1
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation : PVC Compound Type TI1
3. Assembly : Two Cores Twisted
Voltage Uo/U: 250/ 440V
Conductor Stranding: Class 5
Operating Temperature: 700
Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.2
Conductor Thickness
of
Insulation
1 Core 2 Cores
Nominal
Area
Construction
Approx.
Overall Diameter
Approx.
Net Weight
Approx.
Overall Diameter
Approx.
Net Weight
(mm2
) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y)
0.41
0.67
1.17
2.05
3.22
4.74
14/ 0.0076
23/ 0.0076
40/ 0.0076
70/ 0.0076
110/ 0.0076
162/ 0.0076
0.64
0.64
0.64
0.64
0.64
0.76
4.2
4.4
4.8
5.2
5.7
6.4
2.1
2.5
3.2
4.2
5.4
7.3
6.3
6.8
7.5
9.0
10.0
11.3
4.8
6.0
7.5
10.0
12.9
17.4
Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.3
Conductor Thickness
of
Insulation
3 Cores 4 Cores
Nominal
Area
Construction
Approx.
Overall Diameter
Approx.
Net Weight
Approx.
Overall Diameter
Approx.
Net Weight
(mm2
) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y)
0.41
0.67
1.17
2.05
3.22
4.74
14/ 0.0076
23/ 0.0076
40/ 0.0076
70/ 0.0076
110/ 0.0076
162/ 0.0076
0.64
0.64
0.64
0.64
0.64
0.76
6.6
7.1
7.9
9.5
10.5
12.2
5.6
6.2
8.9
12.7
16.6
22.9
7.2
7.7
9.2
10.3
11.4
13.2
6.2
7.9
10.0
15.4
20.4
28.3
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation : PVC Compound Type TI1
3. Assembly : 1, 2, 3 or 4 Cores Twisted Togeher
4. Sheath: PVC Compound Type T6
Voltage Uo/U: 250/ 440V
Conductor Stranding: Class 5
Operating Temperature: 700
12
XLPE/ PVC & XLPE/ AWA/ PVC Cables IEC 60502 Table 11
Nominal
Conductor
Area
No. and
Diameter
of
Wire
Radial
Thickness
of Insulation
XP XAP
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
61/ 2.85
61/ 3.20
127/ 2.52
127/ 2.85
127/ 3.20
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
2.6
2.8
9.6
11.3
12.5
14.0
16.1
18.2
20.0
22.2
24.4
27.5
30.3
33.9
37.6
42.4
47.3
52.4
205
309
412
540
760
1020
1270
1560
1930
2510
3120
3970
4980
6400
8190
10265
-
10.6
11.8
13.3
15.4
17.3
19.1
21.0
23.3
26.1
28.7
32.1
35.7
40.4
45.1
50.1
-
0.9
0.9
1.25
1.25
1.25
1..6
1.60
1.60
1.6
1.6
2.0
2.0
2.0
2.5
2.5
-
16.0
17.2
19.4
21.5
23.4
25.9
27.9
30.1
33.2
35.8
40.9
44.6
49.2
55.7
61.0
-
470
581
800
960
1240
1650
1970
2390
3040
3790
4790
5880
7400
9500
11750
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: XLPE Compound
3. Bedding: PVC Compound Type ST2
4. Armour: Aluminium Wire
5. Sheath: PVC Compound Type ST2
6. Colour: Insulation: Natural
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or compacted
conductors
Operating Temperature: Maximum 900
C
Minimum Bending Radius: Unarmoured:
8D for 16mm2
to 1000mm2
Armoured:
10D for 25mm2
to 1000mm2
13
XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 12
Nominal
Conductor
Area
No. and
Diameter
of
Wire
Radial
Thickness
of Insulation
XP XSP
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
2 x 1.5
2 x 2.5
2 x 4
2 x 6
2 x 10
2 x 16
2 x 25
2 x 35
2 x 50 (S)
2 x 70 (S)
2 x 95 (S)
2 x 120 (S)
2 x 150 (S)
2 x 185 (S)
2 x 240 (S)
2 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
10.0
10.8
11.9
13.0
14.9
17.0
20.4
22.7
21.0
24.0
26.9
29.9
33.4
37.1
45.0
50.0
130
165
210
270
390
450
820
1065
1140
1560
2130
2640
3270
4040
5150
6560
8.5
9.3
10.4
11.5
13.4
15.5
18.9
21.2
19.2
22.3
25.3
28.1
30.9
36.0
41.6
47.4
0.9
0.9
0.9
0.9
1.25
1.25
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.5
2.5
13.9
14.7
15.8
16.9
19.5
21.6
25.7
28.0
26.0
29.5
33.5
36.5
39.5
45.0
52.0
58.0
350
400
475
560
810
980
1410
1930
1880
2420
3360
3980
4730
6245
8720
9390
3 x 1.5
3 x 2.5
3 x 4
3 x 6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50 (S)
3 x 70 (S)
3 x 95 (S)
3 x 120 (S)
3 x 150 (S)
3 x 185 (S)
3 x 240 (S)
3 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
10.5
11.4
12.5
13.8
15.8
18.0
21.7
24.2
25.0
29.0
32.0
36.5
39.0
44.0
49.0
55.0
150
195
255
330
490
700
1000
1300
1600
2240
3050
3800
4640
5870
7670
9460
9.0
9.9
11.0
12.3
14.3
16.5
20.2
23.0
23.0
27.0
30.1
34.4
37.5
41.3
46.4
52.0
0.9
0.9
0.9
0.9
1.25
1.25
1.6
1.6
1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5
14.4
15.3
16.4
17.7
20.4
22.6
27.0
29.8
30.0
35.0
38.5
43.0
47.5
51.5
57.0
36.0
390
450
540
745
950
1250
1840
2280
2550
3500
4500
5700
6800
8200
10300
12500
4 x 1.5
4 x 2.5
4 x 4
4 x 6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 35 (S)
4 x 50 (S)
4 x 70 (S)
4 x 95 (S)
4 x 120 (S)
4 x 150 (S)
4 x 185 (S)
4 x 240 (S)
4 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
11.3
12.3
13.6
15.0
17.2
19.7
23.9
26.6
25.0
28.5
32.0
37.0
42.0
46.0
50.0
55.0
36.0
175
225
305
405
600
870
1325
1760
1600
2200
3050
4070
5195
6350
7890
10400
12810
10.0
10.8
12.1
13.5
15.7
18.2
22.4
15.1
24.0
26.8
30.6
34.4
36.0
38.3
46.4
51.0
56.6
0.9
0.9
0.9
1.25
1.25
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.5
2.5
2.5
2.5
2.5
15.4
16.2
17.5
19.6
21.8
25.0
29.2
32.1
31.0
34.0
39.0
43.0
46.0
48.5
57.0
62.0
68.0
430
505
710
855
1120
1600
2160
2750
2500
3100
4400
5610
7400
8300
10400
13000
15900
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: XLPE Compound
3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape
4. Armour: Galvanised Steel Wire
5. Sheath: PVC Compound Type ST2
6. Colour: Insulation: 2 Cores - Red, Black
3 Cores – Red, Yellow, Blue
4 Cores – Red, Yellow, Blue, Black
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 900
C
Minimum Bending Radius: Unarmoured:
6D for 1.5mm2
to 300mm2
Armoured:
8D for 1.5mm2
to 300mm2
14
XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 13
No.
of
Cores
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
XP XSP
Cable
Overall
Diameter
Approx.
Weight
Diameter
Under
Armour
Armour
Wire
Diameter
Cable
Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
5
7
12
19
37
1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.7
0.7
0.7
0.7
0.7
11.9
12.9
16.5
19.4
25.4
214.5
235.5
391.1
522.0
981.0
10.5
11.5
15.1
17.7
23.3
0.9
0.9
1.25
1.25
1.6
15.9
16.9
21.2
23.8
30.1
493.9
560.7
903.9
1167.8
1872.0
5
7
12
19
37
2.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.7
0.7
0.7
0.7
0.7
13.1
14.1
18.4
21.4
18.4
280.4
317.5
500.0
737.0
1327.0
11.7
12.7
16.8
19.8
27.0
0.9
0.9
1.25
1.6
1.6
17.1
18.1
22.9
26.6
33.8
586.8
676.1
1095.8
1593.2
2361.0
5
7
12
19
37
4
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.7
0.7
0.7
0.7
0.7
14.5
16.0
20.6
24.1
32.2
381.6
470.0
709.0
1051.0
1989.0
13.1
14.3
18.6
22.0
30.1
1.25
1.25
1.25
1.6
1.6
19.2
20.4
24.7
28.8
36.9
823.0
906.0
1293.0
1904.0
2919.0
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: XLPE Compound
3. Bedding: PVC Compound Type ST2 or
Lapped PVC Tape
4. Armour: Galvanised Steel Wire
5. Sheath: PVC Compound Type ST2
6. Colour: Insulation:White with Black numberings
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular
Operating Temperature: Maximum 900
C
Minimum Bending Radius: Unarmoured:
6D for 1.5mm2
to 4mm2
Armoured:
8D for 1.5mm2
to 4mm2
15
IN-POP & IN-POSP Cables Table 14
SIZE IN-POP IN-POSP
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Unarmoured Armoured
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
2C x 0.5
3C x 0.5
4C x 0.5
6C x 0.5
10C x 0.5
20C x 0.5
40C x 0.5
80C x 0.5
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
7.0
7.3
7.9
9.3
11.9
14.9
20.1
26.3
60
68
78
110
170
295
510
950
7.0
7.3
7.9
9.3
11.9
14.9
20.1
26.3
0.90
0.90
0.90
0.90
0.90
1.25
1.60
1.60
11.4
11.7
12.3
13.9
16.7
20.6
26.7
33.3
250
265
290
360
490
800
1300
2050
2C x 0.75
3C x 0.75
4C x 0.75
6C x 0.75
10C x 0.75
20C x 0.75
40C x 0.75
80C x 0.75
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
7.3
7.7
8.3
9.9
12.7
16.0
21.7
28.5
65
78
92
128
200
355
640
1185
7.3
7.7
8.3
9.9
12.7
16.0
21.7
28.5
0.90
0.90
0.90
0.90
0.90
1.25
1.60
1.60
11.7
12.1
12.9
14.5
17.5
21.7
28.5
35.7
260
280
320
400
550
905
1500
2420
2C x 1.5
3C x 1.5
4C x 1.5
6C x 1.5
10C x 1.5
20C x 1.5
40C x 1.5
80C x 1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
8.3
8.9
9.7
11.7
14.7
18.7
24.6
33.6
90
115
140
200
315
560
1040
1970
8.3
8.9
9.7
11.7
14.7
18.7
24.6
33.6
0.90
0.90
0.90
0.90
1.25
1.60
1.60
2.00
12.9
13.5
14.3
16.3
20.4
25.3
31.6
41.8
310
360
400
515
820
1340
2090
3690
Pair configurations are available upon request
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Lay Up: Cores are stranded in Reverse Layer
Technique forming a Concentric Cable
4. Wrap film: Polyster Binder Tape
5. Collective: Aluminium/ Polyster Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
6. Bedding : PVC Compound Type TM1
(optional)
7. Armouring: Galvanised Steel Wire
(optional)
Reference standards: BS 5308 Part 2
Voltage Uo/U: 300/ 500V
Conductor Stranding: Class 2 and 5
Operating Temperature: 700
C
Testing Voltage: 1KV/ 1 Minute
8. Sheath: PVC Compound Type TM1
9. Colour: Insulation: Yellow with Black numberings
or refer to colour code
Sheath: Black
16
IN-POP & IN-POSP Cables Table 15
SIZE IN-POP IN-POSP
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Unarmoured Armoured
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
1P x 0.5
2P(Quad) x 0.5
5P x 0.5
10P x 0.5
15P x 0.5
20P x 0.5
30P x 0.5
50P x 0.5
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
7.0
7.9
13.1
17.2
19.8
22.3
26.9
33.9
60
78
185
310
430
540
780
1240
7.0
7.9
13.1
17.2
19.8
22.3
26.9
33.9
0.90
0.90
0.90
1.25
1.60
1.60
1.60
2.00
11.4
12.3
17.9
22.9
26.4
29.1
33.9
42.1
250
290
540
905
1270
1490
1960
3000
1P x 0.75
2P(Quad) x 0.75
5P x 0.75
10P x 0.75
15P x 0.75
20P x 0.75
30P x 0.75
50P x 0.75
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
7.3
8.3
14.3
18.7
21.4
24.5
29.5
37.4
68
92
230
390
530
690
1010
1610
7.3
8.3
14.3
18.7
21.4
24.5
29.5
37.4
0.90
0.90
1.25
1.60
1.60
1.60
2.00
2.00
11.7
12.9
19.8
25.3
28.2
31.3
37.5
45.8
260
325
710
1170
1460
1750
2560
3550
1P x 1.5
2P(Quad) x 1.5
5P x 1.5
10P x 1.5
15P x 1.5
20P x 1.5
30P x 1.5
50P x 1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
8.3
9.7
16.4
21.6
25.2
28.5
34.3
43.6
90
142
330
580
860
1090
1600
2570
8.3
9.7
16.4
21.6
25.2
28.5
34.3
43.6
0.90
0.90
1.25
1.60
1.60
1.60
2.00
2.50
12.9
14.3
22.1
28.4
32.2
35.7
42.5
53.4
310
410
900
1510
1950
2330
3400
5320
Pair configurations are available upon request
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Lay Up: Cores are paired, pairs are twisted in
Reverse Layer Technique forming a
Concentric Cable
4. Wrap Film: Polyster Binder Tape
5. Collective: Aluminium/ Polyster Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
6. Bedding : PVC Compound Type TM1
(optional)
7. Armouring: Galvanised Steel Wire
(optional)
Reference standards: BS 5308 Part 2
Voltage Uo/U: 300/ 500V
Conductor Stranding: Class 2 and 5
Operating Temperature: 700
C
Testing Voltage: 1KV/ 1 Minute
8. Sheath: PVC Compound Type TM1
9. Colour: Insulation:White and Black numberings
or refer to colour code
Sheath: Black
17
IN-POP & IN-POSP Cables Table 16
SIZE IN-PIOP IN-PIOSP
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Unarmoured Armoured
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
2P x 0.5
5P x 0.5
10P x 0.5
15P x 0.5
20P x 0.5
30P x 0.5
50P x 0.5
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
12.0
15.2
21.1
24.5
27.3
32.3
41.7
135
240
410
590
750
1090
1780
12.0
15.2
21.1
24.5
27.3
32.3
41.7
0.90
1.25
1.60
1.60
1.60
2.00
2.50
16.8
20.9
27.9
31.3
34.3
40.5
51.5
470
770
1320
1640
1910
2740
4400
2P x 0.75
5P x 0.75
10P x 0.75
15P x 0.75
20P x 0.75
30P x 0.75
50P x 0.75
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
12.8
16.3
22.7
26.4
29.8
35.5
45.0
155
275
480
700
900
1310
2060
12.8
16.3
22.7
26.4
29.8
35.5
45.0
0.90
1.25
1.60
1.60
2.00
2.00
2.50
17.6
22.0
29.5
33.4
37.8
43.9
55.0
505
850
1450
1830
2430
3190
4970
2P x 1.5
5P x 1.5
10P x 1.5
15P x 1.5
20P x 1.5
30P x 1.5
50P x 1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
14.7
18.8
26.5
30.8
34.4
41.0
52.2
215
400
740
1060
1340
1970
3130
14.7
18.8
26.5
30.8
34.4
41.0
52.2
1.25
1.60
1.60
2.00
2.00
2.50
2.50
20.4
25.4
33.5
38.8
42.6
50.8
62.6
730
1200
1860
2660
3100
4550
6420
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Lay Up: Cores are paired, pairs are twisted in Reverse
Layer Technique forming a
Concentric Cable
4. Individual: Aluminium/ Polyester Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
5. Wrap Film: Polyster Binder Tape
6. Collective: Aluminium/ Polyster Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
7. Bedding : PVC Compound Type TM1
(optional)
Reference standards: BS 5308 Part 2
Voltage Uo/U: 300/ 500V
Conductor Stranding: Class 2 and 5
Operating Temperature: 700
C
Testing Voltage: 1KV/ 1 Minute
8. Armouring: Galvanised Steel Wire
(optional)
9. Sheath: PVC Compound Type TM110. Colour:
10. Colour: Insulation: White and Black numberings
or refer to colour code
Sheath: Black
18
IN-EOP & IN-EOSP Cables Table 17
SIZE IN-EOP IN-EOSP
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Unarmoured Armoured
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
1P x 0.5
2P(Quad) x 0.5
5P x 0.5
10P x 0.5
15P x 0.5
20P x 0.5
30P x 0.5
50P x 0.5
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
7.0
7.9
13.1
17.2
19.8
22.3
26.9
33.9
56
70
170
280
385
480
690
1080
7.0
7.9
13.1
17.2
19.8
22.3
26.9
33.9
0.90
0.90
0.90
1.25
1.60
1.60
1.60
2.00
11.4
12.3
17.9
22.9
26.4
29.1
33.9
42.1
230
270
500
830
1150
1360
1750
2730
1P x 0.75
2P(Quad) x 0.75
5P x 0.75
10P x 0.75
15P x 0.75
20P x 0.75
30P x 0.75
50P x 0.75
7/ 0.43
7/ 0.43
7/ 0.43
7/ 0.43
7/ 0.43
7/ 0.43
7/ 0.43
7/ 0.43
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
7.4
8.4
14.2
18.4
21.3
24.4
29.0
37.3
68
95
230
385
540
705
995
1630
7.4
8.4
14.2
18.4
21.3
24.4
29.0
37.3
0.90
0.90
1.25
1.25
1.60
1.60
1.60
2.00
11.8
13.0
19.7
24.3
28.1
31.2
36.2
45.7
250
310
680
980
1380
1650
2150
3430
1P x 1.5
2P(Quad) x 1.5
5P x 1.5
10P x 1.5
15P x 1.5
20P x 1.5
30P x 1.5
50P x 1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
8.3
9.7
16.4
21.6
25.2
28.5
34.3
43.6
85
132
315
550
790
1000
1460
2340
8.3
9.7
16.4
21.6
25.2
28.5
34.3
43.6
0.90
0.90
1.25
1.60
1.60
1.60
2.00
2.50
12.9
14.3
22.1
28.4
32.2
35.7
42.5
53.4
290
380
840
1410
1790
2150
3100
4920
Pair configurations are available upon request
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: PVC Compound Type TI1
3. Lay Up: Cores are paired, pairs are twisted in Reverse
Layer Technique forming a Concentric Cable
4. Wrap Film: Polyster Binder Tape
5. Collective: Aluminium/ Polyster Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
6. Bedding : Polyethylene Compound Type 03
(optional)
7. Armouring: Galvanised Steel Wire
(optional)
Reference standards: BS 5308 Part 1
Voltage Uo/U: 300/ 500V
Conductor Stranding: Class 2 and 5
Operating Temperature: 650
C
Testing Voltage: 1KV/ 1 Minute
8. Sheath: PVC Compound Type TM1
9. Colour: Insulation: White and Black numberings
or refer to colour code
Sheat: Black
19
IN-EOP & IN-EOSP Cables Table 18
SIZE IN-EOP IN-EOSP
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Unarmoured Armoured
Cable Overall
Diameter
Approx.
Weight
Diameter
Under Armour
Armour Wire
Diameter
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km)
2P x 0.5
5P x 0.5
10P x 0.5
15P x 0.5
20P x 0.5
30P x 0.5
50P x 0.5
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
16/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
12.0
15.2
21.1
24.5
27.3
32.3
41.7
130
230
400
560
690
990
1610
12.0
15.2
21.1
24.5
27.3
32.3
41.7
0.90
1.25
1.60
1.60
1.60
2.00
2.50
16.8
20.9
27.9
31.3
34.3
40.5
51.5
430
720
1240
1530
1770
2550
4080
2P x 0.75
5P x 0.75
10P x 0.75
15P x 0.75
20P x 0.75
30P x 0.75
50P x 0.75
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
24/ 0.2
0.6
0.6
0.6
0.6
0.6
0.6
0.6
12.8
16.3
22.7
26.4
29.8
35.5
45.0
155
285
500
720
930
1350
2130
12.8
16.3
22.7
26.4
29.8
35.5
45.0
0.90
1.25
1.60
1.60
2.00
2.00
2.50
17.6
21.9
29.4
33.2
37.8
43.8
54.9
480
800
1400
1760
2350
3060
4800
2P x 1.5
5P x 1.5
10P x 1.5
15P x 1.5
20P x 1.5
30P x 1.5
50P x 1.5
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
7/ 0.53
0.6
0.6
0.6
0.6
0.6
0.6
0.6
14.7
18.8
26.5
30.8
34.4
41.0
52.2
210
380
690
990
1240
1820
2890
14.7
18.8
26.5
30.8
34.4
41.0
52.2
1.25
1.60
1.60
2.00
2.00
2.50
2.50
20.4
25.4
33.5
38.8
42.6
50.8
62.6
670
1110
1750
2460
2910
4250
6040
Pair configurations are available upon request
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: Polyethylene Compound Type 03
3. Lay Up: Cores are paired, pairs are twisted in
Reverse Layer Technique forming
a Concentric Cable
4. Individual: Aluminium/ Polyester Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
5. Wrap Film: Polyster Binder Tape
6. Collective: Aluminium/ Polyster Tape, with a Tinned
Screen Copper Drain Wire 0.5mm2
(7/ 0.3mm)
7. Bedding : Polyethylene Compound Type 03
(optional)
Reference standards: BS 5308 Part 1
Voltage Uo/U: 300/ 500V
Conductor Stranding: Class 2 and 5
Operating Temperature: 650
C
Testing Voltage: 1KV/ 1 Minute
8. Armouring: Galvanised Steel Wire
(optional)
9. Sheath: PVC Compound Type TM1
10. Colour: Insulation:White and Black numberings
or refer to colour code
Sheat: Black
20
XLPE/ CT/ AWA/ PVC Cables IEC 60502 Table 19
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Approximate Diameter
Approx.
Weight
Under
Screen
Over
Bedding
Over
Armour
Over
All
(mm2
) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km)
70
95
120
150
185
240
300
400
500
630
800
1000
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
61/ 2.85
61/ 3.20
127/ 2.52
127/ 2. 85
127/ 3.20
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
2.6
2.8
15.2
17.1
19.0
21.0
23.2
26.1
28.7
32.5
36.0
40.4
45.5
50.4
17.6
19.5
20.8
22.8
25.0
27.9
30.5
34.3
37.8
42.2
47.3
52.2
20.1
22.0
24.0
26.0
28.2
31.1
33.7
38.3
41..8
46.2
52.3
57.2
23.9
25.8
27.8
29.8
32.0
35.1
37.9
42.7
46.4
51.0
57.5
62.4
1400
1700
2000
2400
2800
3500
4200
5400
6500
8200
10400
13000
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: XLPE Compound
3. Bedding: PVC Compound Type ST2 or
Lapped PVC Tape
4. Screen: Copper Tape
5. Armour: Aluminium Wire
6. Sheath: PVC Compound Type ST2
7. Colour: Insulation: Natural
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 900
C
Minimum Bending Radius: 12D for 70mm2
to 1000mm2
21
XLPE/ CT/ SWA/ PVC Cables IEC 60502 Table 20
Nominal
Conductor
Area
No. and
Diameter
of Wire
Radial
Thickness
of Insulation
Approximate Diameter
Approx.
Weight
Under
Screen
Over
Bedding
Over
Armour
Over
All
(mm2
) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km)
4 x 1.5
4 x 2.5
4 x 4
4 x 6
4 x 10
4 x 16
4 x 25
4 x 35 (S)
4 x 50 (S)
4 x 70 (S)
4 x 95 (S)
4 x 120 (S)
4 x 150 (S)
4 x 185 (S)
4 x 240 (S)
4 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
9.7
10.7
12.0
13.4
15.6
18.1
22.3
25.0
27.8
31.6
35.4
39.0
42.0
47.8
54.0
58.0
12.1
13.1
14.4
15.8
18.0
20.5
24.1
26.8
29.6
33.4
37.2
40.8
43.8
49.6
55.8
59.8
13.9
14.9
16.2
18.3
20.5
23.7
27.3
30.0
32.8
37.4
41.2
45.8
48.8
54.6
60.8
64.8
17.7
18.7
20.0
22.1
24.3
27.5
31.1
33.8
37.0
42.0
46.0
51.0
54.2
60.4
67.0
71.4
640
730
870
1180
1490
2070
2790
2940
3500
5000
6300
8200
9600
11500
14400
17200
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: XLPE Compound
3. Bedding: PVC Compound Type ST2 or
Lapped PVC Tape
4. Screen: Copper Tape
5. Armour: Galvanised Steel Wire
6. Sheath: PVC Compound Type ST2
7. Colour: Insulation: Red, Yellow, Blue, Green/ Yellow
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2 stranded circular or
compacted conductors
Operating Temperature: Maximum 900
C
Minimum Bending Radius: 12D for 1.5mm2
to 300mm2
22
XLPE/ CT/ PVC Cables IEC 60502 Table 21
Nominal
Conductor
Area
No. and
Diameter
of Wire
Combined
Earth
Size
Radial
Thickness
of Insulation
Radial
Thickness
of Sheath
Unarmoured
Cable Overall
Diameter
Approx.
Weight
(mm2
) (no./mm) (mm) (mm) (mm) (mm) (kg/ km)
3 x 1.5
3 x 2.5
3 x 4
3 x 6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50 (S)
3 x 70 (S)
3 x 95 (S)
3 x 120 (S)
3 x 150 (S)
3 x 185 (S)
3 x 240 (S)
3 x 300 (S)
7/ 0.53
7/ 0.67
7/ 0.85
7/ 1.04
7/ 1.35
7/ 1.70
7/ 2.14
7/ 2.52
19/ 1.78
19/ 2.14
19/ 2.52
37/ 2.03
37/ 2.25
37/ 2.52
61/ 2.25
61/ 2.52
4.5 (3 x 1.5)
4.5 (3 x 1.5)
4.5 (3 x 1.5)
7.5 (3 x 2.5)
12 (3 x 4)
18 (3 x 6)
30 (3 x 10)
30 (3 x 10)
30 (3 x 10)
48 (3 x 16)
48 (3 x 16)
75 (3 x 25)
75 (3 x 25)
105 (3 x 35
150 (3 x 50)
150 (3 x 50)
0.7
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.2
2.3
2.5
2.6
2.8
3.0
13.6
14.8
15.8
16.9
18.6
20.8
24.0
25.6
31.1
34.6
39.3
44.0
49.0
54.0
61.0
67.0
325
380
440
550
750
1000
1470
1890
2300
3200
4200
5400
6400
7900
10200
1230
Construction Technical Data
1. Conductor : Plain Annealed Copper
2. Insulation: XLPE Compound
3. Screen: Copper Tape
4. Sheath: PVC Compound Type ST2
5. Colour: Insulation: Red, Yellow, Blue,
Green/ Yellow (x3)
Sheath: Black
Voltage Uo/U: 600/ 1000V
Conductor Stranding: Class 2
Operating Temperature: Maximum 900
C for XLPE
Maximum 1100
C for XLEVA
Minimum Bending Radius: 10D for unarmoured cable
23
Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.1
Installation Method
Examples
Appropriate Reference Methoad For
Determining Current- Carrying Capacity
Description
OPEN AND CLIPPED DIRECT:
Sheathed cables clipped direct to or lying on
a non- metallic surface
Method 1
CABLES EMBEDDED DIRECT IN BUILDING MATERIALS:
Sheathed cables embedded directly in
masonry, brickwork, concrete, plaster or the
like (other than thermally insulating
materials)
Method 1
IN CONDUIT:
Single core non- sheathed cables in metallic
or non- metallic conduit on a wall or ceiling
Method 3
Single core non- sheathed cables in
metallic or non- metallic conduit in a
thermally insulating ceiling, the conduit
being in contact with a thermally conductive
surface on one side
Method 4
Multi core cables having non- metallic
sheath, in metallic or non- metallic conduit
on a wall or ceiling
Method 3
 The wall is assumed to consist of an outer weatherproof skin, thermal insulation and an inner skin of plasterboard of wood- like material
having a coefficient of heat transfer not less than 10 W/m2
K. The conduit is fixed so as to be close to, but not necessarily touching, the
inner skin. Heat from the cables is assumed ti escape through the inner skin only.
•
•
•
•
•
•
•
24
Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.2
Installation Method
Examples
Appropriate Reference Methoad For
Determining Current- Carrying Capacity
Description
ON TRAYS:
Sheathed cables on a perforated cable tray,
bunched and unenclosed. A pertorated cable
tray is considerd as a tray in which the holes
occupy at least 30% of the surface area
Method 11
IN FREE AIR, ON CLEATS, BRACKETS OR A LADDER:
Sheathed single- core cables in free air (any
supporting metalwork under the cables
occupying less than 10% of the plan area
Two of three cables vertically one above the
other, minimum distance between cable
surfaces equal to the overall cable diameter
(De); distance from the wall not less than
0.5De
Two or three cables horizontally, with
spacings as above
Three cables in trefoil, distance between
wall and surface of nearest cable 0.5De or
nearest cables 0.75De
Method 12
Sheathed multicore cables on ladder or
brackets, separation greater than 2De
Sheathed multicore cables in free air
distance between wall and cable surface not
less than 0.3De
Any supporting metalwork under the cables
occupying less than 10% of the plan area
Method 13
Cables suspended from or incorporating a
catenary wire Method 12 or 13,
as appropriate
25
Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.3
Installation Method
Examples
Appropriate Reference Methoad For
Determining Current- Carrying
Capacity
Description
CABLES IN TRENCHES:
Cables in enclosed trench
450mm wide by 300mm deep
(minimum dimentions)
including 100mm cover
Two signle- core cables
with surfaces
sepaeerated by a
minimum og one cable
diameter
Method 18
Use rating factors
in Technical Table 3
Three single-core
cables in trefoil and
touching throughout
Multicore cables or
groups of single-core
cables with surfaces
separated by a
minimum of 50mm
Cables in enclosed trench
450mm wide by 600mm deep
(minimum dimentions)
including 100mm cover
Single-core cables arranged
in flat groups of two or three
on the vertical trench wall
with surfaces separated by
one diameter with a
minimum distance of 50mm
between groups. Multicore
cables installed with surfaces
separated by a minimum of
75mm. All cables spaced at
least 25mm from the
trenched wall
Method 19
Use rating factors
in Technical Table 3
Cables in enclosed trench
600mm wide by 760mm deep
(minimum dimentions)
including 100mm cover
Single-core cables arranged
in groups of two or three in
flat formation with the
surfaces sepaerated by one
diameter or in trefoil
formation with cables
touching
Method 20
Use rating factors
in Technical Table 3
Groups separated by a
minimum* of 50mm either
horizontally or vertically.
Multi caor cables installed
with surfaces separated by a
minimum* of 75mm either
horizontally or vertically. All
cables spaced at least 25mm
from the trench wall
Larger spacing to be used where practicable
26
Correction Factors For Groups of More than One Circuit Of Single-core Cables, or More than One Multicore Cable Technical Table 2
Reference Methods
of Installation
Correction Factor (C9)
Number of Circuits of Multi-Core Cables
2 3 4 5 6 7 8 9 10 12 14 16 18 20
Enclosed (Method 3 or 4) or
bunched and clipped direct to a
non- metallic surface (Method 1)
0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38
Single layer clipped
to a non-metallic
surface (Method 1)
Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - -
Spaced * 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Single layer multi
core on a perforated
metal cable tray,
vertical or
horizontal
(Method 11)
Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - -
Spaced * 0.91 0.89 0.88 0.87 0.87 - - - - - - - - -
Single layer single
core on a perforated
metal cable tray,
touching (Method 11)
Horizontal 0.90 0.85 - - - - - - - - - - - -
Vertical 0.85 - - - - - - - - - - - - -
Single layer multi core touching on
ladder supports
0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -
 Space means a clearance between adjacent surfaces of at least one cable diameter (De). Where the horizontal clearance between adjacent cables exceeds 2 De, no
correction factor need be applied.
Notes:
1) The factors in the table are applicable to groups of cables all of one size. The value of current derived from application of the appropriate factors is the
maximum continuous current to be carried by any of the cables in the group.
2) If, due to known operating conditions, a cable is expected to carry not more than 30% of it’s grouped rating, it may be ignored for the purposed of
obtaining the rating factor for the rest of the group.
For example, a group of N loaded cables would normally require a group reduction factor of Cg applied to the tabulated It. However, if M cables in the
group carry loads which are not greater than 0.3Cglt amperes, the other cables can be sized by using the group rating factor corresponding to (N-M)
cables.
3) Factors are given for single layer of cables and do not apply when cables are installed in more than one layer touching each other.
4) For circuits having more than one cable in parallel per phase, each set of three conductors should be considered as a circuit for the purpose of this table.
Correction Factors for Cables installed in Enclosed Trenches Technical Table 3
Conductor
cross-
sectional
area
mm2
Installation Method 18 Installation Method 19 Installation Method 20
2
1-core
cables, or 1
3- or
4- core
cables
3
1-core
cables,
or 2
2-core
cables
4
1-core
cables, or 2
3- or
4- core
cables
6
1-core
cables,
4
2- core
cables, or 3
3- or
4- core
cables
6
1-core
cables,
4
2- core
cables, or 3
3- or
4- core
cables
8
1-core
cables, or 4
3- or
4- core
cables
12
1-core
cables,
8
2- core
cables, or 6
3- or
4- core
cables
12
1-core
cables,
8
2- core
cables, or 6
3- or
4- core
cables
18
1-core
cables,
12
2- core
cables, or 9
3- or
4- core
cables
24
1-core
cables,
16
2- core
cables, or
12
3- or
4- core
cables
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
0.93
0.92
0.91
0.91
0.90
0.89
0.88
0.87
0.86
0.85
0.84
0.83
0.82
0.81
0.80
0.78
0.77
0.90
0.89
0.88
0.87
0.86
0.85
0.84
0.82
0.81
0.80
0.78
0.77
0.76
0.74
0.73
0.72
0.71
0.87
0.86
0.85
0.84
0.82
0.81
0.79
0.78
0.76
0.75
0.74
0.73
0.71
0.69
0.67
0.66
0.65
0.82
0.81
0.80
0.78
0.76
0.75
0.74
0.72
0.70
0.69
0.67
0.65
0.63
0.62
0.59
0.58
0.56
0.86
0.86
0.85
0.83
0.81
0.80
0.78
0.77
0.75
0.73
0.72
0.70
0.69
0.68
0.66
0.64
0.63
0.83
0.82
0.80
0.78
0.76
0.74
0.73
0.72
0.70
0.68
0.67
0.65
0.63
0.62
0.60
0.58
0.57
0.76
0.75
0.74
0.71
0.69
0.68
0.66
0.64
0.63
0.61
0.59
0.58
0.56
0.54
0.52
0.51
0.49
0.81
0.80
0.78
0.76
0.74
0.72
0.71
0.70
0.68
0.66
0.64
0.63
0.61
0.59
0.57
0.56
0.54
0.74
0.73
0.72
0.70
0.67
0.66
0.64
0.62
0.60
0.58
0.57
0.55
0.53
0.52
0.50
0.48
0.47
0.69
0.68
0.66
0.64
0.62
0.60
0.59
0.57
0.55
0.53
0.51
0.49
0.48
0.46
0.44
0.43
0.41
The correction factors tabulated above relate to the disposition of cables illustrated in terms 18 to 20 of Technical Table 1.3 and are applicable to the
current- carrying capacities for Reference Methods 12 or 13 of Technical Table 1.2.
When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating temperature
of any cable in the group.
27
Technical Data Rating Factors for Other Temperature conditions Technical Table 4
Table A: Rating Factors for Other Ambient Air Temperature (PVC Insulated)
Ambient
Temperature
250
C 300
C 350
C 400
C 450
C 500
C 550
C 600
C 650
C 700
C
Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35 -
Table B: Rating Factors for Other Ground Temperature (PVC Insulated)
Ambient Temperature 100
C 150
C 200
C 250
C 300
C 350
C 400
C 450
C 500
C
Rating Factor 1.04 1.00 0.95 0.90 0.85 0.80 0.73 0.67 0.60
Table C: Rating Factors for Other Ambient Air Temperature (XLPE Insulated)
Ambient
Temperature
250
C 300
C 350
C 400
C 450
C 500
C 550
C 600
C 650
C 700
C 750
C 800
C 850
C
Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29
Table D: Rating Factors for Other Ground Temperature (XLPE Insulated)
Ambient Temperature 150
C 200
C 250
C 300
C 350
C 400
C 450
C 500
C
Rating Factor 1.00 0.97 0.93 0.89 0.86 0.82 0.77 0.73
Table E: Rating factors for Other Ambient Air Temperature (PVC Insulated)
Ambient Temperature 300
C 350
C 400
C 450
C 500
C 550
C 600
C 650
C 700
C
PVC cords, non-heat
resisting 1.00
0.96 0.92
0.87
0.71 0.50 - - -
PVC cords, heat resisting
1.00 - - - 1.00 0.96 0.83 0.67 0.47
Table F: Group Rating Factors for Cables Installation
Group Rating Factors Numbers of Circuits
2 3 4 5 6 7 8 9 10 11 12
1
For circuits of 2 Single-core
cables laid flat touching
horizontal formation, laid direct
in ground
0.79
0.68
0.62 0.57 0.54 0.52 0.50 0.48 0.47 0.46 0.45
2
For circuits of 3 Single-core
cables in trefoil touching, laid
direct in the ground
0.78 0.66 0.61 0.56 0.53 0.50 0.49 0.47 0.46 0.44 0.43
Number of Cables in a Group
2 3 4 5 6 7 8 9 10 11 12
3
For twin of
multicore
cables in
horizontal
formation, laid
direct in ground
Spaced
0.15m
0.87 0.78 0.74 0.70 0.68 0.66 0.64 0.63 0.62 0.61 0.60
Spaced
0.30m
0.91 0.84 0.81 0.78 0.77 0.75 0.75 0.74 0.73 0.73 0.72
Numbers of Ducts in a Group
2 3 4 5 6 7 8 9 10 11 12
4
For twin multicore cables in
single-way ducts horizontal
formation spaced 0.30m apart
0.93 0.88 0.85 0.83 0.82 0.81 0.80 0.79 0.79 0.78 0.78
28
Current- Carrying Capacities (Amp) PVC & PVC/ PVC Cables Technical Table 5.1
Conductor
cross-
sectional
area
Reference Method 4
(Enclosed in conduit in
thermally insulating
wall etc)
Reference Method 3
(Enclosed in conduit on
a wall or in trunking
etc)
Reference Method 1
(‘Clipped direct’)
Reference Method 11
(on a perforated cable
tray horizontal of
vertical)
Reference Method 12 (free air)
Horizontal
flat spaced,
Vertical
flat spaced,
2 cables,
single-
phase
ac or dc
3 or 4
cables
3- phase
ac
2 cables,
single-
phase
ac or dc
3 or 4
cables
3- phase
ac
2 cables,
single-
phase
ac or dc
3 or 4
cables
3- phase
ac
2 cables,
single-
phase
ac or dc
or flat and
touching
3 cables,
3-phase
ac
flat and
touching
2 cables,
single- phase
ac or dc or
3 cables
or
trefoil
2 cables,
single-
phase
ac or dc
or
3 cables
3- phase
ac
3 cables,
trefoil
3-phase
ac
3-phase
ac
mm2
Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp
BS
6004
1
1.5
2.5
4
6
10
16
25
35
11
14.5
19.5
26
34
46
61
80
99
10.5
13.5
18
24
31
42
56
73
89
13.5
17.5
24
32
41
57
76
101
125
12
15.5
21
28
36
50
68
89
110
15.5
20
27
37
47
65
87
114
141
14
18
25
33
43
59
79
104
129
-
-
-
-
-
-
-
126
156
-
-
-
-
-
-
-
112
141
-
-
-
-
-
-
-
146
181
-
-
-
-
-
-
-
130
162
-
-
-
-
-
-
-
110
137
BS
6346
50
70
95
120
150
185
240
300
400
500
630
800
1000
119
151
182
210
240
273
320
367
-
-
-
-
-
108
136
164
188
216
245
286
328
-
-
-
-
-
151
192
232
269
300
341
400
458
546
626
720
-
-
134
171
207
239
262
296
346
394
467
533
611
-
-
182
234
284
330
381
436
515
594
694
792
904
1030
1154
167
214
261
303
349
400
472
545
634
723
826
943
1058
191
246
300
349
404
463
549
635
732
835
953
1086
1216
172
223
273
318
369
424
504
584
679
778
892
1020
1149
219
281
341
396
456
521
615
709
852
982
1138
1265
1420
197
254
311
362
419
480
569
659
795
920
1070
1188
1337
167
216
264
304
356
409
485
561
656
749
855
971
1079
* With or without protective conductor
Note: Rating factors for ambient temperature other than 300
c please refer Table A
Group Rating Factor please refer to Table 2
Voltage Drop (Per Amp Meter) PVC & PVC/ PVC Cables Technical Table 5.2
Conductor
Cross-
sectional
area
2
cables
dc
2 cables- single- phase ac 3 or 4 cables- three- phase ac
Reference Methods
3 & 4 (Enclosed in
conduit etc in or on
a wall)
Reference Methods 1
& 11 (Clipped direct
or on trays, touching)
Reference Methods
12
(space *)
Reference Methods
3 & 4 (Enclosed in
conduit etc in or on
a wall)
Reference Methods
1, 11& 12
(in trefoil)
Reference Methods
1 & 11 (flat
touching)
Reference Methods
12
(Flat spaced*)
mm2
mV mV mV mV mV mV mV mV
1
1.5
2.5
4
6
10
16
44
29
18
11
7.3
4.4
2.8
44
29
18
11
7.3
4.4
2.8
44
29
18
11
7.3
4.4
2.8
44
29
18
11
7.3
4.4
2.8
38
25
15
9.5
6.4
3.8
2.4
38
25
15
9.5
6.4
3.8
2.4
38
25
15
9.5
6.4
3.8
2.4
38
25
15
9.5
6.4
3.8
2.4
r x z r x z r x z r x z r x z r x z r x z
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.75
1.25
0.93
0.63
0.46
0.36
0.29
0.23
0.180
0.145
0.105
0.086
0.068
0.053
0.042
1.80
1.30
0.95
0.65
0.49
0.39
0.31
0.25
0.195
0.160
0.130
0.110
0.094
-
-
0.33
0.31
0.30
0.29
0.28
0.27
0.27
0.27
0.26
0.26
0.26
0.26
0.25
-
-
1.80
1.30
1.00
0.72
0.56
0.47
0.41
0.37
0.33
0.31
29
0.28
0.27
-
-
1.75
1.25
0.93
0.63
0.47
0.37
0.30
0.24
0.185
0.150
0.120
0.098
0.081
0.068
0.059
0.20
0.195
0.190
0.185
0.180
0.175
0.175
0.170
0.165
0.165
0.160
0.155
0.155
0.150
0.150
1.75
1.25
0.95
0.66
0.50
0.41
0.34
0.29
0.25
0.22
0.20
0.185
0.175
0.165
0.160
1.75
1.25
0.93
0.63
0.47
0.37
0.29
0.24
0.185
0.150
0.115
0.093
0.076
0.061
0.050
0.29
0.28
0.28
0.27
0.27
0.26
0.26
0.26
0.25
0.25
0.25
0.24
0.24
0.24
0.24
1.80
1.30
0.97
0.69
0.54
0.45
0.39
0.35
0.31
0.29
0.27
0.26
0.25
0.25
0.24
1.50
1.10
0.81
0.56
0.42
0.33
0.27
0.22
0.17
0.14
0.12
0.10
0.08
-
-
0.29
0.27
0.26
0.25
0.24
0.23
0.23
0.23
0.23
0.23
0.22
0.22
0.22
-
-
1.55
1.10
0.85
0.61
0.48
0.41
0.36
0.32
0.29
0.27
0.25
0.25
0.24
-
-
1.50
1.10
0.80
0.55
0.41
0.32
0.26
0.21
0.160
0.130
0.150
0.086
0.072
0.060
0.052
0.175
0.170
0.165
0.160
0.155
0.150
0.150
0.145
0.145
0.140
0.140
0.135
0.135
0.130
0.130
1.50
1.10
0.82
0.57
0.43
0.36
0.30
0.26
0.22
0.190
0.175
0.160
0.150
0.145
0.140
1.50
1.10
0.80
0.55
0.41
0.32
0.26
0.21
0.160
0.130
0.150
0.086
0.072
0.060
0.052
0.25
0.24
0.24
0.24
0.23
0.23
0.23
0.22
0.22
0.22
0.21
0.21
0.21
0.21
0.20
1.55
1.10
0.84
0.60
0.47
0.40
0.34
0.31
0.27
0.25
0.24
0.23
0.22
0.22
0.21
1.50
1.10
0.80
0.55
0.40
0.32
0.26
0.21
0.160
0.130
0.100
0.081
0.066
0.053
0.044
0.32
0.32
0.32
0.31
0.31
0.30
0.30
0.30
0.29
0.29
0.29
0.29
0.28
0.28
0.28
1.55
1.15
0.86
0.63
0.51
0.44
0.40
0.36
0.34
0.32
0.31
0.30
0.29
0.29
0.28
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
29
Current- Crying Capacities (Amp) PVC/ PVC Cables Technical Table 6.1
Conductor
cross- sectional
area
Reference Methods 4
(Enclosed in an
insulated wall etc)
Reference Methods 3
(Enclosed in conduit on a wall
or ceiling, or in trunking)
Reference Method 1
(Clipped direct)
Reference Method 11
(on a perforated cable tray), or
Reference Method 13 ( free air)
1
2-core cable*
single-phase
ac or dc
1
2-core cable*
or 1
4-core cable
3-phase ac
1
2-core cable*
single-phase
ac or dc
1
2-core cable*
or 1
4-core cable
3-phase ac
1
2-core cable*
single-phase
ac or dc
1
2-core cable*
or 1
4-core cable
3-phase ac
1
2-core cable*
single-phase
ac or dc
1
2-core cable*
or 1
4-core cable
3-phase ac
mm2
Amp Amp Amp Amp Amp Amp Amp Amp
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
11
14
18.5
25
32
43
57
75
92
110
139
167
192
219
248
291
334
-
10
13
17.5
23
29
39
52
68
83
99
125
150
172
196
223
261
298
-
13
16.5
23
30
38
52
69
90
111
133
168
201
232
258
294
344
394
470
11.5
15
20
27
34
46
62
80
99
118
149
179
206
225
255
297
339
402
15
19.5
27
36
46
63
85
112
138
168
213
258
299
344
392
461
530
634
13.5
17.5
24
32
41
57
76
96
119
144
184
223
259
299
341
403
464
557
17
22
30
40
51
70
94
119
148
180
232
282
328
379
434
514
593
715
14.5
18.5
25
34
43
60
80
101
126
153
196
238
276
319
364
430
497
597
* With or without protective conductor
Note: Rating factors for ambient temperature other than 300
c please refer Table A
Group Rating Factor please refer to Table 2
Voltage Drop (Per Amp Meter) PVC/ PVC Cables Technical Table 6.2
Conductor
cross- sectional 2-core cable ac
2-core cable
single-phase ac
3 or 4-core cable
3-phase ac
mm2
mV mV mV
1
1.5
2.5
4
6
10
16
44
29
18
11
7.3
4.4
2.8
44
29
18
11
7.3
4.4
2.8
38
25
15
9.5
6.4
3.8
2.4
r x z r x z
25
35
50
70
95
120
150
185
240
300
400
1.75
1.25
0.93
0.63
0.46
0.36
0.29
0.23
0.180
0.145
0.105
1.75
1.25
0.93
0.63
0.47
0.38
0.30
0.25
0.190
0.155
0.115
0.170
0.165
0.165
0.160
0.155
0.155
0.155
0.150
0.150
0.145
0.145
1.75
1.25
0.94
0.65
0.50
0.41
0.34
0.29
0.24
0.21
0.185
1.50
1.10
0.80
0.55
0.41
0.33
0.26
0.21
0.165
0.135
0.100
0.145
0.145
0.140
0.140
0.135
0.135
0.130
0.130
0.130
0.130
0.125
1.50
1.10
0.81
0.57
0.43
0.35
0.29
0.25
0.21
0.185
0.160
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
30
Current- Crying Capacities (Amp) PVC/ AWA/ PVC Cables Technical Table 7.1
Conductor
cross-
sectional
area
Reference Methods 1
(Clipped direct)
Reference Methods 11
(on perforated cable
tray)
Reference Methods 12 (free air) Direct in
ground
In Single Way
Ducts
2 cables
single-
phase
ac or dc
3 or 4
cables
3-phase
ac
2 cables
single-
phase
ac flat &
touching
3 or 4
cables
3-phase
flat &
touching
3 or 4 cables
3-phase ac
2 cables dc
spaced
2
cables
flat
touch-
ing
3
cables
trefoil
touch-
ing
2
cables
duct
touch-
ing
3
cables
trefoil
touch-
ing
Horizontal
flat
spaced
Vertical
flat
spaced
3 cables
trefoils
Hori-
zontal
Verti-
cal
mm2
Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp
50
70
95
120
150
185
240
300
400
500
630
800
1000
193
245
296
342
393
447
525
594
687
763
843
919
975
179
225
269
309
352
399
465
515
575
622
669
710
737
205
259
313
360
413
469
550
624
723
805
891
976
1041
189
238
285
327
373
422
492
547
618
673
228
777
808
230
286
338
385
436
490
566
616
674
721
771
824
872
212
263
313
357
405
456
528
578
632
676
723
772
816
181
231
280
324
373
425
501
567
657
731
809
886
945
229
294
357
415
479
548
648
748
885
1035
1218
1441
1685
216
279
340
396
458
525
622
719
851
997
1174
1390
1627
238
292
349
396
443
497
571
640
708
780
856
895
939
203
248
297
337
376
423
485
542
600
660
721
756
797
216
262
308
341
375
414
463
509
545
585
632
662
703
199
241
282
311
342
375
419
459
489
523
563
587
621
Note: Rating factors for ambient temperature other than 300
c please refer Table A
Rating factors for ambient temperature other than 150
c please refer Table B
Group Rating Factor please refer to Table F & Table 2
Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 7.2
Conduc-
tor
cross-
sectional
area
2
cable
s dc
2 cables-single-phase ac 3 or 4 cables-three-phase ac Direct in ground
Single Way
Ducts
Reference
Methods 1 & 11
(Touching)
Reference
Methods 12
(space*)
Reference
Methods 1, 11 &
12 (in trefoil
touching)
Reference
Methods 1 & 11
(Flat touching)
Reference
Methods 12
(flat spaced*)
2
cables
flat
touch-
ing
3 cables
trefoil
touch-
ing
2 cables
flat
touch-
ing
3
cable
s
trefoi
l
touch
-ing
mm2
mV mV mV mV mV mV mV mV mV mV
r x z r x z r x z r x z r x z
50
70
95
120
150
185
240
300
400
500
630
800
1000
0.93
0.63
0.46
0.36
0.29
0.23
0.180
0.145
0.105
0.086
0.068
0.053
0.042
0.93
0.64
0.48
0.39
0.31
0.26
0.20
0.160
0.140
0.120
0.105
0.094
0.095
0.22
0.21
0.20
0.195
0.19
0.19
0.180
0.180
0.175
0.170
0.165
0.160
0.155
0.95
0.68
0.52
0.43
0.37
0.32
0.27
0.24
0.22
0.21
0.195
0.185
0.185
0.92
0.66
0.51
0.42
0.34
0.29
0.23
0.190
0.180
0.165
0.150
0.145
0.140
0.30
0.29
0.28
0.28
0.27
0.27
0.26
0.26
0.24
0.23
0.22
0.21
0.190
0.97
0.72
0.58
0.50
0.44
0.39
0.35
0.32
0.30
0.29
0.27
0.25
0.24
0.80
0.56
0.42
0.33
0.27
0.22
0.175
0.140
0.120
0.105
0.091
0.082
0.079
0.19
0.18
0.175
0.17
0.165
0.16
0.160
0.155
0.130
0.145
0.145
0.140
0.135
0.82
0.58
0.45
0.37
0.32
0.27
0.23
0.21
0.195
0.180
0.170
0.160
0.155
0.79
0.57
0.44
0.36
0.30
0.25
0.20
0.165
0.160
0.145
0.135
0.125
0.125
0.26
0.25
0.25
0.24
0.24
0.23
0.23
0.22
0.21
0.20
0.195
0.180
0.165
0.84
0.62
0.50
0.43
0.38
0.34
0.30
0.28
0.26
0.25
0.23
0.22
0.21
0.79
0.59
0.47
0.40
0.34
0.29
0.24
0.20
0.21
0.190
0.175
0.170
0.165
0.34
0.32
0.31
0.30
0.30
0.29
0.28
0.28
0.25
0.24
0.22
0.195
0.170
0.86
0.68
0.57
0.50
0.45
0.41
0.37
0.34
0.32
0.30
0.28
0.26
0.24
0.97
0.67
0.50
0.42
0.36
0.31
0.26
0.23
0.22
0.20
0.19
-
-
0.82
0.58
0.44
0.36
0.31
0.27
0.23
0.20
0.19
0.18
0.16
-
-
1.00
0.76
0.61
0.54
0.48
0.44
0.40
0.37
0.34
0.32
0.30
-
-
0.88
0.66
0.53
0.47
0.42
0.38
0.34
0.32
0.30
0.28
0.26
-
-
Note: r = conductor resistance at operating temperature; z = impedance; x = reactance
31
Current- Crying Capacities (Amp) PVC/ SWA/ PVC Cables Technical Table 8.1
Conductor
cross- sectional
area
Reference Methods 1
(Clipped direct)
Reference Methods 11
(on a perforated horizontal cable
tray or Reference Methods 13
(free air) Direct in Ground In Single Way Ducts
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3- phase ac
or dc
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3- phase ac
or dc 2 cores 3 or 4 cores 2 cores 3 or 4 cores
mm2
Amp Amp Amp Amp Amp Amp Amp Amp
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
21
28
38
49
67
89
118
145
175
222
269
310
356
405
476
547
621
18
25
33
42
58
77
102
125
151
192
231
267
306
348
409
469
540
22
31
41
53
72
97
128
157
190
241
291
336
386
439
516
592
683
19
26
35
45
62
83
110
135
163
207
251
290
332
378
445
510
590
32
41
55
69
92
119
158
190
225
277
332
377
422
478
551
616
693
27
35
47
59
78
101
132
159
188
233
279
317
355
401
462
517
580
26
34
45
57
76
98
129
154
183
225
271
309
346
393
455
510
574
22
29
38
48
64
83
107
126
153
190
228
260
292
331
382
428
490
Note: Rating factors for ambient temperature other than 300
c please refer Table A
Rating factors for ambient temperature other than 150
c please refer Table B
Group Rating Factor please refer to Table F & Table 2
Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 8.2
Conductor
cross- sectional
area 2- core cable ac 2- core cable single-phase ac
3- or 4-
cable 3- phase ac
Direct in Ground
In Single
Way Ducts
2- cores
3- or 4-
cores
2 -
cores
3- or 4-
cores
mm2
mV mV mV mV mV mV mV
1.5
2.5
4
6
10
16
29
18
11
7.3
4.4
2.8
29
18
11
7.3
4.4
2.8
25
15
9.5
6.4
3.8
2.4
29
18
11
7.3
4.4
2.8
25
15
9.5
6.4
3.8
2.4
29
18
11
7.3
4.4
2.8
25
15
9.5
6.4
3.8
2.4
r x z r x z
25
35
50
70
95
120
150
185
240
300
400
1.75
1.25
0.93
0.63
0.46
0.36
0.29
0.23
0.18
0.145
0.105
1.75
1.25
0.93
0.63
0.47
0.38
0.3
0.25
0.19
0.155
0.115
0.17
0.165
0.165
0.16
0.155
0.155
0.155
0.15
0.15
0.145
0.145
1.75
1.25
0.94
0.65
0.5
0.41
0.34
0.29
0.24
0.21
0.185
1.5
1.1
0.8
0.55
0.41
0.33
0.26
0.21
0.165
0.135
0.1
0.145
0.145
0.14
0.14
0.135
0.135
0.13
0.13
0.13
0.13
0.125
1.5
1.1
0.81
0.57
0.43
0.35
0.29
0.25
0.21
0.185
0.16
1.7
1.3
0.94
0.66
0.49
0.4
0.34
0.29
0.24
0.21
0.19
1.5
1.1
0.82
0.57
0.42
0.35
0.29
0.25
0.21
0.18
0.17
1.7
1.3
0.94
0.66
0.49
0.4
0.34
0.29
0.24
0.21
0.19
1.5
1.1
0.82
0.57
0.42
0.35
0.29
0.25
0.21
0.18
0.17
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
32
Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 9.1
Size of
Conductor
Reference Methods 4
(Enclosed in an
insulated wall etc)
Reference Methods 3
(Enclosed in conduit on a wall
or ceiling, or in trunking)
Reference Method 1
(Clipped direct)
Reference Method
11 (on a perforated
cable tray,
horizontal or
vertical)
Reference
Method 12
( free air)
2 cables
1-phase
ac or dc
3 or 4
cables
3-phase ac
2 cables
1-phase
ac or dc
3 or 4
cables
3-phase ac
2 cables
1-phase
ac or dc flat &
touching
3 or 4
cables
3-phase ac flat
& touching or
trefoil
2 cables
1-phase
ac or dc
flat &
touching
3 or 4
cables
3-phase
ac flat &
touching
or
trefoil
3 cables
trefoil
3-phase ac
1 2 3 4 5 6 7 8 9 10
mm2
A A A A A A A A A
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
18
24
33
43
58
76
100
124
149
189
228
263
300
341
400
459
-
-
-
-
-
17
23
30
39
53
70
91
111
135
170
205
235
270
306
358
410
-
-
-
-
-
22
30
40
51
71
95
126
156
189
240
290
336
375
426
500
573
683
783
900
-
-
19
26
35
45
63
85
111
138
168
214
259
299
328
370
433
493
584
666
764
-
-
25
34
46
59
81
109
143
176
228
293
355
413
476
545
644
743
868
990
1130
1288
1443
23
31
41
54
74
99
130
161
209
268
326
379
436
500
590
681
793
904
1033
1179
1323
-
-
-
-
-
-
158
195
293
308
375
436
505
579
686
794
915
1044
1191
1358
1520
-
-
-
-
-
-
140
176
215
279
341
398
461
530
630
730
849
973
1115
1275
1436
-
-
-
-
-
-
138
171
209
270
330
385
445
511
606
701
820
936
1069
1214
1349
Note: Rating factors for ambient temperature other than 300
c please refer Table C
Rating factors for ambient temperature other than 150
c please refer Table D
Group Rating Factor please refer to Table 2
Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 9.2
Size of
Conductor
2 cables
dc
2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac
Reference Methods 3&4
(Enclosed in conduit
etc, in or on a wall)
Reference Methods 1 &
11 (clipped direct or on
trays touching)
Reference Methods 3&4
(Enclosed in conduit etc,
in or on a wall)
Reference Methods
1, 11 & 12
(in trefoil)
Reference Methods
1 & 11
(flat & touching)
1 2 3 4 5 6 7
mm2
mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5
2.5
4
6
10
16
31
19
12
7.9
4.7
2.9
31
19
12
7.9
4.7
2.9
31
19
12
7.9
4.7
2.9
27
16
10
6.8
4.0
2.5
27
16
10
6.8
4.0
2.5
27
16
10
6.8
4.0
2.5
r x z r x Z r x z r x z r x Z
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.85
1.35
0.99
0.68
0.49
0.39
0.32
0.25
0.19
0.155
0.12
0.093
0.072
0.056
0.045
1.85
1.35
1.00
0.70
0.51
0.41
0.33
0.27
0.21
0.175
0.14
0.12
0.10
-
-
0.31
0.29
0.29
0.28
0.28
0.27
0.26
0.26
0.26
0.26
0.25
0.25
0.25
0.25
-
1.90
1.35
1.05
0.75
0.58
0.48
0.43
0.37
0.33
0.31
0.29
0.28
0.27
-
-
1.85
1.35
0.99
0.68
0.49
0.39
0.32
0.26
0.20
0.16
0.13
0.105
0.086
0.072
0.063
0.19
0.18
0.18
0.175
0.170
0.165
0.165
0.165
0.160
0.160
0.155
0.155
0.155
0.150
0.150
1.85
1.35
1.00
0.71
0.52
0.43
0.36
0.30
0.25
0.22
0.20
0.185
0.175
0.170
0.165
1.60
1.15
0.87
0.60
0.44
0.35
0.29
0.23
0.185
0.15
0.125
0.100
0.088
-
-
0.27
0.25
0.25
0.24
0.23
0.23
0.23
0.23
0.22
0.22
0.22
0.22
0.21
-
-
1.65
1.15
0.90
0.65
0.50
0.42
0.37
0.32
0.29
0.27
0.25
0.24
0.23
-
-
1.60
1.15
0.86
0.59
0.43
0.34
0.28
0.22
0.17
0.14
0.11
0.09
0.074
0.062
0.055
0.165
0.155
0.155
0.150
0.145
0.140
0.140
0.140
0.140
0.140
0.135
0.135
0.135
0.130
0.130
1.60
1.15
0.87
0.61
0.45
0.37
0.31
0.26
0.22
0.195
0.175
0.160
0.150
0.145
0.140
1.60
1.15
0.86
0.59
0.43
0.34
0.28
0.22
0.17
0.135
0.110
0.088
0.071
0.059
0.050
0.19
0.18
0.18
0.175
0.170
0.165
0.165
0.165
0.165
0.160
0.160
0.160
0.160
0.155
0.150
1.60
1.15
0.87
0.62
0.46
0.38
0.32
0.28
0.24
0.21
0.195
0.180
0.170
0.165
0.165
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
33
Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 10.1
Size of
Conductor
Reference Methods 4
(Enclosed in conduit and in
insulated wall etc)
Reference Methods 3
(Enclosed in conduit on a wall
or ceiling, or in trunking)
Reference Method 1
(Clipped direct)
Reference Method 11 (on a
perforated cable tray, or
Reference Method 13 (free air)
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1 2 3 4 5 6 7 8 9
mm2
A A A A A A A A
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
18.5
25
33
42
57
76
99
121
145
183
220
253
290
329
386
442
-
16.5
22
30
38
51
68
89
109
130
164
197
227
259
295
346
396
-
22
30
40
51
69
91
119
146
175
221
265
305
334
384
459
532
625
19.5
26
35
44
60
50
105
128
154
194
233
268
300
340
398
455
536
24
33
45
58
80
107
138
171
209
269
328
382
441
506
599
693
803
22
30
40
52
71
96
119
147
179
229
278
322
371
424
500
576
667
26
36
49
63
86
115
149
185
225
289
352
410
473
542
641
741
865
23
32
42
54
75
100
127
158
192
246
298
346
399
456
538
621
741
Note: Rating factors for ambient temperature other than 300
c please refer Table C
Rating factors for ambient temperature other than 150
c please refer Table D
Group Rating Factor please refer to Table 2
Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 10.2
Size of Conductor 2-core cable dc
2-core cable
single-phase ac
3- or 4-
Cable
3-phase ac
1 2 3 4
mm2
mV/A/m mV/A/m mV/A/m
1.5
2.5
4
6
10
16
31
19
12
7.9
4.7
2.9
31
19
12
7.9
4.7
2.9
27
16
10
6.8
4.0
2.5
r x z r x Z
25
35
50
70
95
120
150
185
240
300
400
1.85
1.35
0.98
0.67
0.49
0.39
0.31
0.25
0.195
0.155
0.120
1.85
1.35
0.99
0.67
0.50
0.40
0.32
0.26
0.20
0.16
0.13
0.16
0.155
0.155
0.150
0.150
0.145
0.145
0.145
0.140
0.140
0.140
1.9
1.35
1.00
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.19
1.6
1.15
0.86
0.59
0.43
0.34
0.28
0.22
0.175
0.140
0.115
0.14
0.135
0.135
0.130
0.130
0.130
0.125
0.125
0.125
0.120
0.120
1.65
1.15
0.87
0.60
0.45
0.37
0.30
0.26
0.21
0.185
0.165
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
34
Current- Crying Capacities (Amp) XLPE/ AWA/ PVC Cables Technical Table 11.1
Size of
Conductor
Reference Methods 1
(clipped direct)
Reference Method 11
(on a perforated cable tray)
Reference
Method 12
( free air) In single-way ducts Laid direct in ground
2 cables
1-phase
ac or dc
flat &
touching
3 or 4
cables
3-phase ac
flat &
touching
2 cables
1-phase
ac or dc
flat &
touching
3 or 4
cables
3-phase ac
flat &
touching
3 cables
3-phase ac
trefoil
touching
2 cables
1-phase
ac or dc
ducts
touching
3 cables
3-phase
ac
trefoil
ducts
touching
2 cables
1-phase
ac or dc
touching
3 cables
3-phase ac
trefoil
touching
1 2 3 4 5 6 7 8 9 10
mm2
A A A A A A A A A
50
70
95
120
150
185
240
300
400
500
630
800
1000
237
303
367
425
488
557
656
755
853
962
1082
1170
1261
220
277
333
383
437
496
579
662
717
791
861
904
961
253
322
382
449
516
587
689
792
899
1016
1146
1246
1345
232
293
352
405
462
524
612
700
767
851
935
987
1055
222
285
346
402
463
529
625
720
815
918
1027
1119
1214
255
310
365
410
445
485
550
610
640
690
750
828
919
235
280
330
370
405
440
500
550
580
620
670
735
811
257
340
405
460
510
580
670
750
830
910
1000
1117
1254
235
290
345
390
435
490
560
630
700
770
840
931
1038
Note: Rating factors for ambient temperature other than 300
c please refer Table C
Rating factors for ambient temperature other than 150
c please refer Table D
Group Rating Factor please refer to Table F & Table 2
Voltage Drop (Per Amp Per Meter) XLPE/AWA/PVC Cables Technical Table 11.2
Size of
Conductor
2 cables
dc
2 Cables,
1-phase ac
3 or 4 Cables,
3-phase ac
2 Cables,
1-phase ac
3 or 4 Cables, 3-phase
ac, touching
Reference Methods 1 &
11 (touching)
Reference Methods 1, 11
& 12 (in trefoil touching)
Reference Methods 1 &
11 (flat & touching)
In
ducts
In
ground
In
ducts
In
ground
1 2 3 4 5 6 7 8 9
mm2
mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
r x z r x z r x z
50
70
95
120
150
185
240
300
400
500
630
800
1000
0.98
0.67
0.49
0.39
0.31
0.25
0.195
0.155
0.115
0.093
0.073
0.056
0.045
0.99
0.68
0.51
0.41
0.33
0.27
0.21
0.17
0.145
0.125
0.105
0.09
0.092
0.21
0.20
0.195
0.190
0.185
0.185
0.180
0.175
0.170
0.170
0.165
0.160
0.155
1
0.71
0.55
0.45
0.38
0.33
0.28
0.25
0.22
0.21
0.195
0.190
0.180
0.86
0.59
0.44
0.35
0.29
0.23
0.18
0.145
0.125
0.105
0.092
0.086
0.080
0.18
0.17
0.17
0.165
0.160
0.160
0.155
0.150
0.150
0.145
0.145
0.140
0.135
0.87
0.62
0.47
0.39
0.33
0.28
0.24
0.21
0.195
0.180
0.170
0.165
0.155
0.84
0.6
0.46
0.38
0.31
0.26
0.21
0.17
0.160
0.145
0.135
0.130
0.125
0.25
0.25
0.24
0.24
0.23
0.23
0.22
0.22
0.21
0.20
0.195
0.180
0.170
0.88
0.65
0.52
0.44
0.39
0.34
0.30
0.28
0.27
0.25
0.24
0.23
0.21
1.10
0.80
0.65
0.55
0.50
0.45
0.40
0.37
0.35
0.33
0.30
0.28
0.26
0.99
0.70
0.53
0.43
0.37
0.31
0.26
0.24
0.21
0.20
0.19
0.18
0.17
0.93
0.70
0.56
0.48
0.43
0.39
0.35
0.32
0.30
0.28
0.26
0.24
0.22
0.86
0.61
0.46
0.37
0.32
0.27
0.23
0.21
0.19
0.18
0.17
0.16
0.15
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
35
Current- Crying Capacities (Amp) XLPE/ SWA/ PVC Cables Technical Table 12.1
Size of
Conductor
Reference Methods 1
(clipped direct)
Reference Method 11 (on a
perforated cable tray, or
Reference Method 13 (free air) In single-way ducts Laid direct in ground
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1
2-core cable
single-phase
ac or dc
1
3- or 4-
cable
3-phase ac
1 2 3 4 5 6 7 8 9
mm2
A A A A A A A A
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
27
36
49
62
85
110
146
180
219
279
338
392
451
515
607
698
787
23
31
42
53
73
94
124
154
187
238
289
335
386
441
520
599
673
29
39
52
66
90
115
152
188
228
291
354
410
472
539
636
732
847
25
33
44
56
78
99
131
162
197
251
304
353
406
463
546
628
728
-
-
-
-
-
115
145
175
210
260
310
355
400
455
520
590
660
23
30
40
50
65
94
125
150
175
215
260
300
335
380
440
495
560
-
-
-
-
-
140
180
215
255
315
380
430
480
540
630
700
790
28
36
48
60
80
115
150
180
215
265
315
360
405
460
530
590
670
Note: Rating factors for ambient temperature other than 300
c please refer Table C
Rating factors for ambient temperature other than 150
c please refer Table D
Group Rating Factor please refer to Table F & Table 2
Voltage Drop (Per Amp Per Meter) XLPE/SWA/PVC Cables Technical Table 12.2
Size of
Conductor
2 cables
dc
2 Cables,
1-phase ac
3 or 4 Cables,
3-phase ac
2 Cables,
1-phase ac
3 or 4 Cables,
3-phase ac
In
ducts
In
ground
In
ducts
In
ground
1 2 3 4 5 6 7 8
mm2
mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5
2.5
4
6
10
16
31
19
12
7.9
4.7
2.9
31
19
12
7.9
4.7
2.9
27
16
10
6.8
4.0
2.5
31
19
12
7.9
4.7
2.9
31
19
12
7.9
4.7
2.9
25
15
9.5
6.4
3.8
2.4
25
15
9.5
6.4
3.8
2.4
r x z r x z
25
35
50
70
95
120
150
185
240
300
400
1.85
1.35
0.98
0.67
0.49
0.39
0.31
0.25
0.195
0.155
0.120
1.85
1.35
0.99
0.67
0.50
0.40
0.32
0.26
0.20
0.16
0.13
0.16
0.155
0.155
0.150
0.150
0.145
0.145
0.145
0.140
0.140
0.140
1.9
1.35
1.00
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.19
1.6
1.15
0.86
0.59
0.43
0.34
0.28
0.22
0.175
0.140
0.115
0.14
0.135
0.135
0.130
0.130
0.130
0.125
0.125
0.125
0.120
0.120
1.65
1.15
0.87
0.60
0.45
0.37
0.30
0.26
0.21
0.185
0.165
1.9
1.35
1.00
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.19
1.9
1.35
1.00
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.19
1.6
1.2
0.87
0.61
0.45
0.36
0.30
0.25
0.21
0.19
0.18
1.6
1.2
0.87
0.61
0.45
0.36
0.30
0.25
0.21
0.19
0.18
Note: r = conductor resistance at operating temperature
z = impedance, x = reactance
36
Technical Data Flexible Cord, Imperial Sizes Technical Table 13.1
Conductor Current Rating Volt Drop PER 100FT
Maximum Weigh
supportable by twin
flexible cord
Nominal
Area Construction
1 or 3 phase
ac or dc
dc or
1 phase ac 3 phase ac
in2
No./in Amp V V lb
0.0006
0.0010
0.0017
0.0030
0.0048
0.0070
14/ 0.0076
23/ 0.0076
40/ 0.0076
70/ 0.0076
110/ 0.0076
162/ 0.0076
3
6
13
18
24
31
8.9
11
14
12
9.6
8.4
7.7
9.4
12
10
8.3
7.3
3
5
10
10
10
10
Note: Rating factors for ambient temperature other than 300
c please refer Table E
Technical Data Flexible Cord Metric Sizes Technical Table 13.2
Conductor Current Rating Volt Drop per 100FT
Maximum Weigh
supportable by twin
flexible cord
Nominal
Area Construction
1 or 3 phase
ac or dc
dc or
1 phase ac 3 phase ac
mm2
No./mm Amp mV/m mV/m kg
0.50
0.75
1.00
1.25
1.50
2.50
4.00
16/ 0.2
24/ 0.2
32/ 0.2
40/ 0.2
30/ 0.25
50/ 0.25
56/ 0.3
3
6
10
13
15
20
25
83
56
43
35
31
18
11
72
48
37
29
26
16
9.6
2
3
5
5
5
5
5
Note: Rating factors for ambient temperature other than 300
c please refer Table E
37
Allowable Short Circuit Currents For PVC Insulated Cables Technical Table
14.1
Short
circuit
current
(KA)
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000
Conductor: Copper
Insulation: PVC
Curves based on formula:
l = (0.115A÷ t )
Where:
l – Short circuit current (KA)
A- Conductor area (mm2
)
t – Time of short circuit
(seconds)
Conductor Size (mm2
)
Allowable Short Circuit Currents For XLPE Insulated Cables Technical Table 14.2
Short
circuit
current
(KA)
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000
Conductor: Copper
Insulation: PVC
Curves based on formula:
l = (0.115A÷ t )
Where:
l – Short circuit current (KA)
A- Conductor area (mm2
)
t – Time of short circuit (seconds)
Conductor Size (mm2
)
38
Short Circuit ratings for power cables Technical Table 14.3
Cross- Sectional
Area
Short Circuit
Rating
for 1 second
Short Circuit
Rating
for 3 seconds
Another important factor for the determination of the conductor size is the maximum
allowable current during a short circuit when the maximum allowable current during
a short circuit when the maximum allowable conductor temperature is higher than
during normal operation.
The maximum permissible short circuit current of XLPE cables up to 1Kv with
copper conductors can be calculated with the formula:
K
t
S
lk 

Where l = Short Circuit rating (KA)
S = Conductor Area (sq mm)
t = Duration of Short Circuit (sec)
mm2
KA KA
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
0.2145
0.3575
0.5720
0.8580
1.4300
2.2880
3.5750
5.0050
7.1500
10.0100
13.5850
17.1600
21.4500
26.4550
34.3200
42.9000
57.2000
71.5000
90.0900
114.4000
143.0000
0.1238
0.2064
0.3302
0.4954
0.8256
1.3210
2.0640
2.8896
4.1281
5.7793
7.8433
9.9073
12.3842
15.2738
19.8147
24.7683
33.0244
41.2805
52.0135
66.0489
82.5611
The above rating is calculated using the following formula:
t
S
l
143
.
0

Where l = Short Circuit rating (KA)
S = Conductor Area (sq mm)
t = Duration of Short Circuit (sec)
Copper Conductor Technical Table 14.3
Current
in
Kiloampers
Duration of Short circuit in Seconds
The values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 900
c), and a final conductor
temperature of 2500
c, and it should be ensured that the accessories associated with the cable are also capable of operation at these values of fault current.
39
IN-POP, IN-POSP IN-PIOP, IN-PIOSP & IN-EOP, IN-EOSP IN-EIOP, IN-EIOSP Technical Table 15
1 . Test Voltage: 1000 Vr.m.s. for 1 minute between each conductor in turn and all other connected together
2 . Maximum DC Conductor Resistance at 200
c
Conductor Size Multi-cores Multi-pairs
0.5 mm2
0.75 mm2
1.0 mm2
1.5 mm2
39.0
26.0
18.1
12.1
39.7
26.5
18.4
12.3
3. Minimum Insulation Resistance at 200
c
PE Insulated PVC Insulated
Individual Conductor (between) each conductor and
Remaining bunched conductors/ screen and/ or armour
5000MΩ.km 25 MΩ.km
Individual Screens (between screens) 1 MΩ.km 1 MΩ.km
4. Maximum Mutual Capacitance at 1 KHz (pF/m)
Cable Type Conductor Size 0.5 mm2
1.0 mm2
1.5 mm2
PE Insulated Cables without individual pair screen 75 pF/m 75 pF/m 85 pF/m
PE Insulated All cables with individual pair screen, 1 and 2 pair cables collective screen 115 pF/m 115 pF/m 120 pF/m
PVC Insulated Pairs 250pF/m
5. Maximum Capacitance Between Any Core or Screen
PVC Insulated cables: 450 pF/m
6. Maximum Capacitance Unbalance at 1 KHz
PE Insulated cables: 250pF/ 250m
7. Maximum L/R Ratio (For Adjacent Cores)
Conductor Size Multi-cores
0.5 mm2
0.75 mm2
1.0 mm2
1.5 mm2
25 µH/Ω
25 µH/Ω
25 µH/Ω
40 µH/Ω
Maximum Conductor Resistance Technical Table 16 Electrical Characteristics Technical Table 16
Cross Section Area (S)
Conductor for Fixied Wiring Class 1
(solid), Class 2 (stranded)
Conductor Resistance Temperature Correction Factors
mm2
Temp0
C Factor
0.50
0.75
1.00
1.50
2.50
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
36.0
24.5
18.1
12.1
7.41
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
30
35
40
45
50
55
60
65
70
75
80
85
90
0.961
0.965
0.969
0.972
0.976
0.980
0.984
0.988
0.992
0.996
1.000
1.004
1.008
1.012
1.016
1.020
1.039
1.059
1.079
1.098
1.118
1.138
1.157
1.177
1.196
1.216
1.236
1.255
1.275
40
(mm2
– CM – AWG/ MCM) Technical Table 18
Cross- sectional Area Conductor Size Cross- sectional Area Conductor Size
(mm2
) (CM) (AWG/ MCM) (mm2
) (CM) (AWG/ MCM)
0.324
0.519
0.653
0.823
*1.0
1.04
1.31
*1.5
1.65
2.08
*2.5
2.63
3.31
*4.0
4.17
5.261
*6.0
6.631
8.367
*10.0
10.55
13.3
*16.3
16.77
21.15
*25.0
26.67
33.62
*35.0
42.41
*50.0
53.49
67.43
*70.0
85.01
*95.0
640
1020
1290
1620
1974
2050
2580
2960
3260
4110
4934
5180
6530
7894
8230
10380
11841
13090
16510
19735
20820
26240
31576
33090
41740
49338
52620
66360
69073
83690
98675
105600
133100
138145
167800
187483
22
20
19
18
-
17
16
-
15
14
-
13
12
-
11
10
-
9
8
-
7
6
-
5
4
-
3
2
-
1
-
1/0
2/0
-
3/0
-
107.2
*120
127
*150
152
177
*185
203
228
*240
253
279
300
304
329
355
380
*400
405
456
*500
507
557
608
*630
633
659
709
760
*800
811
861
887
912
963
*1000
010
211600
236820
250000
296025
300000
350000
365098
400000
450000
473640
5000000
550000
592050
600000
650000
700000
750000
789400
800000
900000
986750
1000000
1000100
1000200
1243305
1250000
1300000
1400000
1500000
1578800
1600000
1700000
1750000
1800000
1900000
1973500
2000000
4/0
-
-250
-
300
350
-
400
450
-
500
550
-
600
650
700
750
-
850
900
-
1000
1100
1200
-
1250
1300
1400
1500
-
1600
1700
1750
1800
1900
-
2000
Note: * British standard
*127 mm2
and larger is rounded off and not actual. CM area is actual
Conversion factors: mm2
x 1973.5 = CM x 0.0005067 = mm2.
AWG - America Wire Gauge. A standard measurement of the size of a conductor: 4/0 & smaller.
CM (Circular Mil) used to define cross-sectional areas of conductors. Area of circle 171000 inches in diameter. MCM – 1000 circular mils.

More Related Content

What's hot

TPI - Example Report.
TPI - Example Report.TPI - Example Report.
TPI - Example Report.
Ryan Gillespie
 
Basic electrical system
Basic electrical systemBasic electrical system
Basic electrical system
MLCalver
 
Types of cables
Types of cables Types of cables
Types of cables
Nisarg Amin
 
Symbols & Nomenclature Used By Electrical Engineer In A Construction
Symbols & Nomenclature Used By Electrical Engineer In A ConstructionSymbols & Nomenclature Used By Electrical Engineer In A Construction
Symbols & Nomenclature Used By Electrical Engineer In A Construction
Hafiz JUNAID
 
wiring Part 3: wires & cables
wiring Part 3: wires & cableswiring Part 3: wires & cables
wiring Part 3: wires & cables
vigyanashram
 
ASME SEC IX PPT.pdf
ASME SEC IX PPT.pdfASME SEC IX PPT.pdf
ASME SEC IX PPT.pdf
PKNanavati
 
Selection of filler wire
Selection of filler wireSelection of filler wire
Selection of filler wire
Imran Jamil
 
Types of cables
Types of cables   Types of cables
Types of cables
Preetshah1212
 
61769477 welding-inspection-cswip-gud
61769477 welding-inspection-cswip-gud61769477 welding-inspection-cswip-gud
61769477 welding-inspection-cswip-gud
Jithu John
 
cswip-3-1-new-book
 cswip-3-1-new-book cswip-3-1-new-book
cswip-3-1-new-book
Rohit Jaiswal
 
Api 5 l 44 ed psl 1 & psl 2
Api 5 l 44 ed psl 1 & psl 2Api 5 l 44 ed psl 1 & psl 2
Api 5 l 44 ed psl 1 & psl 2
Henry Hutabarat
 
Cable
CableCable
Presentation on cables
Presentation on cablesPresentation on cables
Presentation on cables
FaizanAli244
 
Raiway applications rolling stock rules for installation of wire harness
Raiway applications rolling stock rules for installation of wire harnessRaiway applications rolling stock rules for installation of wire harness
Raiway applications rolling stock rules for installation of wire harness
Hamdi Tosun
 
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
maharshi solanki
 
QC Welding Inspector Interview Question & Answers.pdf
QC Welding Inspector Interview Question & Answers.pdfQC Welding Inspector Interview Question & Answers.pdf
QC Welding Inspector Interview Question & Answers.pdf
University of Sarajevo, Manufacturing Technology:
 
Tcc final fernandopolastrini_2016_ee-
Tcc final fernandopolastrini_2016_ee-Tcc final fernandopolastrini_2016_ee-
Tcc final fernandopolastrini_2016_ee-
Dyego Torres
 

What's hot (17)

TPI - Example Report.
TPI - Example Report.TPI - Example Report.
TPI - Example Report.
 
Basic electrical system
Basic electrical systemBasic electrical system
Basic electrical system
 
Types of cables
Types of cables Types of cables
Types of cables
 
Symbols & Nomenclature Used By Electrical Engineer In A Construction
Symbols & Nomenclature Used By Electrical Engineer In A ConstructionSymbols & Nomenclature Used By Electrical Engineer In A Construction
Symbols & Nomenclature Used By Electrical Engineer In A Construction
 
wiring Part 3: wires & cables
wiring Part 3: wires & cableswiring Part 3: wires & cables
wiring Part 3: wires & cables
 
ASME SEC IX PPT.pdf
ASME SEC IX PPT.pdfASME SEC IX PPT.pdf
ASME SEC IX PPT.pdf
 
Selection of filler wire
Selection of filler wireSelection of filler wire
Selection of filler wire
 
Types of cables
Types of cables   Types of cables
Types of cables
 
61769477 welding-inspection-cswip-gud
61769477 welding-inspection-cswip-gud61769477 welding-inspection-cswip-gud
61769477 welding-inspection-cswip-gud
 
cswip-3-1-new-book
 cswip-3-1-new-book cswip-3-1-new-book
cswip-3-1-new-book
 
Api 5 l 44 ed psl 1 & psl 2
Api 5 l 44 ed psl 1 & psl 2Api 5 l 44 ed psl 1 & psl 2
Api 5 l 44 ed psl 1 & psl 2
 
Cable
CableCable
Cable
 
Presentation on cables
Presentation on cablesPresentation on cables
Presentation on cables
 
Raiway applications rolling stock rules for installation of wire harness
Raiway applications rolling stock rules for installation of wire harnessRaiway applications rolling stock rules for installation of wire harness
Raiway applications rolling stock rules for installation of wire harness
 
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...Electrical Wiring:Types of wires and Cables and the circuit control on domest...
Electrical Wiring:Types of wires and Cables and the circuit control on domest...
 
QC Welding Inspector Interview Question & Answers.pdf
QC Welding Inspector Interview Question & Answers.pdfQC Welding Inspector Interview Question & Answers.pdf
QC Welding Inspector Interview Question & Answers.pdf
 
Tcc final fernandopolastrini_2016_ee-
Tcc final fernandopolastrini_2016_ee-Tcc final fernandopolastrini_2016_ee-
Tcc final fernandopolastrini_2016_ee-
 

Viewers also liked

Wire Strand Chart
Wire Strand ChartWire Strand Chart
Wire Strand Chart
MaryArmenta
 
Shyam cable catalogue
Shyam cable catalogueShyam cable catalogue
Shyam cable catalogue
uibsamit87
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IEC
Joe Khan
 
Power Control Cables - Nuhas Oman Catalogue
Power Control Cables - Nuhas Oman CataloguePower Control Cables - Nuhas Oman Catalogue
Power Control Cables - Nuhas Oman Catalogue
nuhasoman
 
Awg to mm2 conversion table
Awg to mm2 conversion tableAwg to mm2 conversion table
Awg to mm2 conversion table
vineethkrishnaraj
 
Xlpe land cable systems 2 gm5007gb rev 5
Xlpe land cable systems 2 gm5007gb rev 5Xlpe land cable systems 2 gm5007gb rev 5
Xlpe land cable systems 2 gm5007gb rev 5
Tien Nguyen
 
Current carrying capacities & other technical tables
Current carrying capacities & other technical tablesCurrent carrying capacities & other technical tables
Current carrying capacities & other technical tables
asif raza
 
Cable Mgr cable tray Introduction
Cable Mgr cable tray Introduction Cable Mgr cable tray Introduction
Cable Mgr cable tray Introduction
Gabriel Vasquez
 
Catalog (eastern cables)_book
Catalog (eastern cables)_bookCatalog (eastern cables)_book
Catalog (eastern cables)_book
Engr Nizam Mfa
 
XLPE Land Cable System
XLPE Land Cable SystemXLPE Land Cable System
XLPE Land Cable System
Beny Indrawan S
 
LS Circuit Breaker Catalogue
LS Circuit Breaker CatalogueLS Circuit Breaker Catalogue
LS Circuit Breaker Catalogue
hairxoawn
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
Vijay Kumar
 
Insulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman CatalogueInsulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman Catalogue
nuhasoman
 

Viewers also liked (13)

Wire Strand Chart
Wire Strand ChartWire Strand Chart
Wire Strand Chart
 
Shyam cable catalogue
Shyam cable catalogueShyam cable catalogue
Shyam cable catalogue
 
cable ampacity calculations- IEC
cable ampacity calculations- IECcable ampacity calculations- IEC
cable ampacity calculations- IEC
 
Power Control Cables - Nuhas Oman Catalogue
Power Control Cables - Nuhas Oman CataloguePower Control Cables - Nuhas Oman Catalogue
Power Control Cables - Nuhas Oman Catalogue
 
Awg to mm2 conversion table
Awg to mm2 conversion tableAwg to mm2 conversion table
Awg to mm2 conversion table
 
Xlpe land cable systems 2 gm5007gb rev 5
Xlpe land cable systems 2 gm5007gb rev 5Xlpe land cable systems 2 gm5007gb rev 5
Xlpe land cable systems 2 gm5007gb rev 5
 
Current carrying capacities & other technical tables
Current carrying capacities & other technical tablesCurrent carrying capacities & other technical tables
Current carrying capacities & other technical tables
 
Cable Mgr cable tray Introduction
Cable Mgr cable tray Introduction Cable Mgr cable tray Introduction
Cable Mgr cable tray Introduction
 
Catalog (eastern cables)_book
Catalog (eastern cables)_bookCatalog (eastern cables)_book
Catalog (eastern cables)_book
 
XLPE Land Cable System
XLPE Land Cable SystemXLPE Land Cable System
XLPE Land Cable System
 
LS Circuit Breaker Catalogue
LS Circuit Breaker CatalogueLS Circuit Breaker Catalogue
LS Circuit Breaker Catalogue
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
 
Insulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman CatalogueInsulated Wiring Cables - Nuhas Oman Catalogue
Insulated Wiring Cables - Nuhas Oman Catalogue
 

More from Ngan TNHH

Philips tnhh kimxuan- www.thietbidienkimxuan.com
Philips tnhh kimxuan- www.thietbidienkimxuan.comPhilips tnhh kimxuan- www.thietbidienkimxuan.com
Philips tnhh kimxuan- www.thietbidienkimxuan.com
Ngan TNHH
 
catalogue rang dong - 2014
catalogue rang dong - 2014catalogue rang dong - 2014
catalogue rang dong - 2014
Ngan TNHH
 
Mang paragon 15 09-2014
Mang paragon 15 09-2014Mang paragon 15 09-2014
Mang paragon 15 09-2014
Ngan TNHH
 
Day lucky 04 09-14
Day lucky 04 09-14Day lucky 04 09-14
Day lucky 04 09-14
Ngan TNHH
 
Hp pro 400_mfp_m425_cf280
Hp pro 400_mfp_m425_cf280Hp pro 400_mfp_m425_cf280
Hp pro 400_mfp_m425_cf280
Ngan TNHH
 
bongdenGe _2014
bongdenGe _2014bongdenGe _2014
bongdenGe _2014
Ngan TNHH
 
Bang gia sino o cam cong tac va phu kien s66-s68-s19
Bang gia sino o cam cong tac va phu kien s66-s68-s19Bang gia sino o cam cong tac va phu kien s66-s68-s19
Bang gia sino o cam cong tac va phu kien s66-s68-s19
Ngan TNHH
 
Bang gia sino o cam cong tac va phu kien s18 s9 s98
Bang gia sino o cam cong tac va phu kien s18 s9 s98Bang gia sino o cam cong tac va phu kien s18 s9 s98
Bang gia sino o cam cong tac va phu kien s18 s9 s98
Ngan TNHH
 
Bang gia sino day dien thoai-www.thietbidienngan.com-2014
Bang gia sino day dien thoai-www.thietbidienngan.com-2014Bang gia sino day dien thoai-www.thietbidienngan.com-2014
Bang gia sino day dien thoai-www.thietbidienngan.com-2014
Ngan TNHH
 
banggiathietbidiencomet-www.thietbidienngan.com
banggiathietbidiencomet-www.thietbidienngan.combanggiathietbidiencomet-www.thietbidienngan.com
banggiathietbidiencomet-www.thietbidienngan.com
Ngan TNHH
 
Pricelist comet - 2014-www.thietbidienngan.com
Pricelist comet - 2014-www.thietbidienngan.comPricelist comet - 2014-www.thietbidienngan.com
Pricelist comet - 2014-www.thietbidienngan.com
Ngan TNHH
 
Banggiathietbidien ac 2014_www.thietbidienngan
Banggiathietbidien ac 2014_www.thietbidiennganBanggiathietbidien ac 2014_www.thietbidienngan
Banggiathietbidien ac 2014_www.thietbidienngan
Ngan TNHH
 
Cataloge -thietbidien ongze-www.thietbidienngan.com
Cataloge -thietbidien ongze-www.thietbidienngan.comCataloge -thietbidien ongze-www.thietbidienngan.com
Cataloge -thietbidien ongze-www.thietbidienngan.com
Ngan TNHH
 
Bang giabanle dienquang-2-t09_2014-www.thietbidienngan.com
Bang giabanle dienquang-2-t09_2014-www.thietbidienngan.comBang giabanle dienquang-2-t09_2014-www.thietbidienngan.com
Bang giabanle dienquang-2-t09_2014-www.thietbidienngan.com
Ngan TNHH
 
Bang gia hdv 2014 www.thietbidienngan.com
Bang gia hdv 2014 www.thietbidienngan.com Bang gia hdv 2014 www.thietbidienngan.com
Bang gia hdv 2014 www.thietbidienngan.com
Ngan TNHH
 
Bang gia schneider_dealer_T09_2014-www.thietbidienngan.com
Bang gia schneider_dealer_T09_2014-www.thietbidienngan.comBang gia schneider_dealer_T09_2014-www.thietbidienngan.com
Bang gia schneider_dealer_T09_2014-www.thietbidienngan.com
Ngan TNHH
 
Bang gia panasonic 2014- thietbidienngan.com
Bang gia panasonic 2014- thietbidienngan.comBang gia panasonic 2014- thietbidienngan.com
Bang gia panasonic 2014- thietbidienngan.com
Ngan TNHH
 
9.2 lv-mv cable-tnhh kimxuan
9.2 lv-mv cable-tnhh kimxuan9.2 lv-mv cable-tnhh kimxuan
9.2 lv-mv cable-tnhh kimxuan
Ngan TNHH
 
Telecom cable ls cable & system- tnhhkimxuan
Telecom cable ls cable & system- tnhhkimxuanTelecom cable ls cable & system- tnhhkimxuan
Telecom cable ls cable & system- tnhhkimxuan
Ngan TNHH
 
Ls busduct -tnhh kimxuan
Ls busduct -tnhh kimxuanLs busduct -tnhh kimxuan
Ls busduct -tnhh kimxuan
Ngan TNHH
 

More from Ngan TNHH (20)

Philips tnhh kimxuan- www.thietbidienkimxuan.com
Philips tnhh kimxuan- www.thietbidienkimxuan.comPhilips tnhh kimxuan- www.thietbidienkimxuan.com
Philips tnhh kimxuan- www.thietbidienkimxuan.com
 
catalogue rang dong - 2014
catalogue rang dong - 2014catalogue rang dong - 2014
catalogue rang dong - 2014
 
Mang paragon 15 09-2014
Mang paragon 15 09-2014Mang paragon 15 09-2014
Mang paragon 15 09-2014
 
Day lucky 04 09-14
Day lucky 04 09-14Day lucky 04 09-14
Day lucky 04 09-14
 
Hp pro 400_mfp_m425_cf280
Hp pro 400_mfp_m425_cf280Hp pro 400_mfp_m425_cf280
Hp pro 400_mfp_m425_cf280
 
bongdenGe _2014
bongdenGe _2014bongdenGe _2014
bongdenGe _2014
 
Bang gia sino o cam cong tac va phu kien s66-s68-s19
Bang gia sino o cam cong tac va phu kien s66-s68-s19Bang gia sino o cam cong tac va phu kien s66-s68-s19
Bang gia sino o cam cong tac va phu kien s66-s68-s19
 
Bang gia sino o cam cong tac va phu kien s18 s9 s98
Bang gia sino o cam cong tac va phu kien s18 s9 s98Bang gia sino o cam cong tac va phu kien s18 s9 s98
Bang gia sino o cam cong tac va phu kien s18 s9 s98
 
Bang gia sino day dien thoai-www.thietbidienngan.com-2014
Bang gia sino day dien thoai-www.thietbidienngan.com-2014Bang gia sino day dien thoai-www.thietbidienngan.com-2014
Bang gia sino day dien thoai-www.thietbidienngan.com-2014
 
banggiathietbidiencomet-www.thietbidienngan.com
banggiathietbidiencomet-www.thietbidienngan.combanggiathietbidiencomet-www.thietbidienngan.com
banggiathietbidiencomet-www.thietbidienngan.com
 
Pricelist comet - 2014-www.thietbidienngan.com
Pricelist comet - 2014-www.thietbidienngan.comPricelist comet - 2014-www.thietbidienngan.com
Pricelist comet - 2014-www.thietbidienngan.com
 
Banggiathietbidien ac 2014_www.thietbidienngan
Banggiathietbidien ac 2014_www.thietbidiennganBanggiathietbidien ac 2014_www.thietbidienngan
Banggiathietbidien ac 2014_www.thietbidienngan
 
Cataloge -thietbidien ongze-www.thietbidienngan.com
Cataloge -thietbidien ongze-www.thietbidienngan.comCataloge -thietbidien ongze-www.thietbidienngan.com
Cataloge -thietbidien ongze-www.thietbidienngan.com
 
Bang giabanle dienquang-2-t09_2014-www.thietbidienngan.com
Bang giabanle dienquang-2-t09_2014-www.thietbidienngan.comBang giabanle dienquang-2-t09_2014-www.thietbidienngan.com
Bang giabanle dienquang-2-t09_2014-www.thietbidienngan.com
 
Bang gia hdv 2014 www.thietbidienngan.com
Bang gia hdv 2014 www.thietbidienngan.com Bang gia hdv 2014 www.thietbidienngan.com
Bang gia hdv 2014 www.thietbidienngan.com
 
Bang gia schneider_dealer_T09_2014-www.thietbidienngan.com
Bang gia schneider_dealer_T09_2014-www.thietbidienngan.comBang gia schneider_dealer_T09_2014-www.thietbidienngan.com
Bang gia schneider_dealer_T09_2014-www.thietbidienngan.com
 
Bang gia panasonic 2014- thietbidienngan.com
Bang gia panasonic 2014- thietbidienngan.comBang gia panasonic 2014- thietbidienngan.com
Bang gia panasonic 2014- thietbidienngan.com
 
9.2 lv-mv cable-tnhh kimxuan
9.2 lv-mv cable-tnhh kimxuan9.2 lv-mv cable-tnhh kimxuan
9.2 lv-mv cable-tnhh kimxuan
 
Telecom cable ls cable & system- tnhhkimxuan
Telecom cable ls cable & system- tnhhkimxuanTelecom cable ls cable & system- tnhhkimxuan
Telecom cable ls cable & system- tnhhkimxuan
 
Ls busduct -tnhh kimxuan
Ls busduct -tnhh kimxuanLs busduct -tnhh kimxuan
Ls busduct -tnhh kimxuan
 

Catalogue tai sin www.thietbidienngan.com-2014

  • 1. 1 Stranded Plain Annealed Copper Conductor ___________________________________________________ 2 PVC Cables – Single Core _________________________________________________________________ 3 PVC/ PVC Cables – 1 Core & 2 Cores _______________________________________________________ 4 PVC/ PVC Cables – 3 Cores & 4 Cores _______________________________________________________ 5 PVC/ PVC Cables – Multi Cores ____________________________________________________________ 6 PVC/ AWA/ PVC Cables – Single Core ______________________________________________________ 7 PVC/ SWA/ PVC Cables – 2 Cores, 3 Cores & 4 Cores __________________________________________ 8 PVC/ SWA/ PVC Cables - Multi Cores_______________________________________________________ 9 Flexible Cable, Circular Sheathed, Metric Unit - 2 Cores, 3 Cores & 4 Cores _________________________ 10 Flexible Cord, Twin Twisted, Imperial Unit ___________________________________________________ 11 Flexible Cable, Circular Sheathed, Imperial Unit – 1 Core, 2 Cores, 3 Cores & 4 Cores _________________ 11 XLPE/ PVC & XLPE/ AWA/ PVC Cables – Single Core _________________________________________ 12 XLPE/ PVC & XLPE/ SWA/ PVC Cables - 2 Cores, 3 Cores & 4 Cores _____________________________ 13 XLPE/ PVC & XLPE/ SWA/ PVC Cables – Multi Cores _________________________________________ 14 IN-POP & IN-POSP - Multi Cores __________________________________________________________ 15 IN-POP & IN-POSP – Single & Multi Pairs ___________________________________________________ 16 IN-PIOP & IN-PIOSP – Multi Pairs _________________________________________________________ 17 IN-EOP & IN-EOSP – Single & Multi Pairs ___________________________________________________ 18 IN-EIOP & IN-EIOSP – Multi Pairs _________________________________________________________ 19 XLPE/ CT/ AWA/ PVC Cables – Single Core _________________________________________________ 20 XLPE/ CT/ SWA/ PVC Cables – 4 Cores _____________________________________________________ 21 XLPE/ CT/ PVC Cables – 3 Cores + 3 Earth ___________________________________________________ 22 Schedule of Installation Methods of Cables ____________________________________________________ 23 Correction Factors _______________________________________________________________________ 26 Current Rating and Voltage Drop (PVC Insulated Cables) ________________________________________ 28 Current Rating and Voltage Drop (XLPE Insulated Cables) _______________________________________ 32 Current Rating and Voltage Drop (Flexible Cables) _____________________________________________ 36 Short Circuit Current for PVC Insulated & XLPE Insulated Cables _________________________________ 37 Short Circuit Ratings _____________________________________________________________________ 38 Additional Technical Information ___________________________________________________________ 39 Conversion Tables of Conductor Size ________________________________________________________ 40
  • 2. 2 Stranded Plain Annealed Copper Conductor BS 66360 & IEC 60228 Table 1 Nominal Conductor Area No. and Diameter of Wire No. and Diameter of Conductor Maximum Conductor Resistance at 200 C Nominal Weight per km of Conductor (mm2 ) (no./mm) (mm) (Ω/km) (kg/km) 1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 7/ 0.43 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 1.29 1.59 2.01 2.55 3.12 4.05 5.10 6.42 7.56 8.90 10.70 12.60 14.21 15.75 17.64 20.25 22.68 25.65 28.80 32.76 37.05 41.60 18.1 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176 9.2 14.0 22.4 36.1 54 90.8 145 229 317 429 620 860 1086 1334 1673 2199 2759 3528 4448 5744 7346 9260 Construction Technical Data 1. Conductor : Plain Annealed Copper Conductor Stranding : Class 2 stranded circular or compacted conductors
  • 3. 3 PVC Cables SS358 Table 2 Nominal Conductor Area No. and Diameter Of Wire Radial Thickness Of Insulation Mean Overall Diameter (Upper Limit) Approx. Weight Minimum Insulation Resistance at 700 C (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mΩ/ km) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 0.7 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 3.4 4.2 4.8 5.4 6.8 8.0 9.8 11.0 13.0 15.0 17.0 19.0 21.0 23.5 26.5 29.5 33.5 37.0 41.0 22.7 34.0 50.0 70.9 117.5 177.4 279.5 372.0 504.5 710.6 980.8 1216.0 1498.0 1874.0 2444.4 3059.5 3897.0 4940.0 6295.0 0.010 0.009 0.0077 0.0065 0.0065 0.0050 0.0050 0.0040 0.0045 0.0035 0.0035 0.0032 0.0032 0.0032 0.0032 0.0030 0.0028 0.0028 0.0025 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type C 3. Colour: Red, Yellow, Blue, Black, Green, White, or Green/ Yellow Voltage Uo/U: 450/ 750V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700 C Minimum Bending Radius: 3D for D < 10mm 4D for 10mm < D < 25mm 6D for D > 25mm
  • 4. 4 PVC/ PVC Cables IEC 60502 Table 3 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 2.8 3.0 6.3 6.7 7.6 8.2 9.2 10.2 11.9 13.1 14.8 16.6 19.2 20.8 23.0 25.4 28.7 31.7 35.3 39.5 43.2 47.7 53.0 55 70 100 125 175 240 350 460 595 810 1110 1360 1670 2070 2690 3340 4230 5290 6680 8460 10545 2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 (S) 2 x 35 (S) 2 x 50 (S) 2 x 70 (S) 2 x 95 (S) 2 x 120 (S) 2 x 150 (S) 2 x 185 (S) 2 x 240 (S) 2 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 10.4 11.2 13.1 14.2 16.1 18.2 21.8 24.0 23.0 26.0 30.0 32.0 36.0 40.0 44.0 49.0 145 180 255 285 395 590 900 1160 1260 1700 2310 2880 3520 4290 5570 6970 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type A 3. Sheath: PVC Compound Type ST1 4. Colour: Insulation: 1 Core - Black 2 Cores- Red & Black Sheath: 1 Core – Grey 2 Cores - Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700 C Minimum Bending Radius: 1 Core – 8D for 1.5mm2 to 1000mm2 2 Cores – 8D for 1.5mm2 to 300mm2
  • 5. 5 PVC/ PVC Cables IEC 60502 Table 4 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 (S) 3 x 35 (S) 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 10.9 11.8 13.8 15.0 17.1 19.3 23.2 25.7 26.0 29.0 34.0 37.0 40.0 45.0 51.2 56.0 165 210 305 370 515 740 1160 1520 1750 2435 3360 4140 5070 6330 8265 10355 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 11.7 12.8 15.0 16.4 18.6 21.2 25.6 28.4 26.0 29.0 33.0 39.0 42.5 47.0 52.0 58.2 65.0 200 255 375 455 665 930 1465 1920 1740 2320 3215 4400 5440 6675 8360 10870 13650 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type A 3. Sheath: PVC Compound Type ST1 3. Colour: Insulation: 3 Cores – Red, Yellow, Blue 4 Cores- Red , Yellow, Blue, Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700 C Minimum Bending Radius: 8D for 1.5mm2 to 300mm2 PVC/ PVC Cables Table 5 No. of Nominal Conductor No. and Diameter Radial Thickness Approx. Overall Approx. Weight
  • 6. 6 Cores Area of Wire of Insulation Diameter (mm2 ) (no./mm) (mm) (mm) (kg/ km) 2 3 4 5 7 10 12 19 27 37 48 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.8 9.2 10.0 10.8 11.7 14.8 15.2 17.9 21.4 24.0 27.6 109 129 154 190 240 330 385 560 770 1015 1300 2 3 4 5 7 10 12 19 27 37 48 2.5 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 10.0 10.6 11.5 12.7 13.7 17.4 18.0 21.2 25.4 28.6 33.0 148 171 218 270 340 490 560 820 1135 1560 1930 2 3 4 5 7 10 12 19 27 37 48 4 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 11.5 12.2 13.3 14.7 16.2 20.6 21.3 25.1 30.4 34.2 39.3 205 252 315 415 535 720 850 1260 1740 2300 2900 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Sheath: PVC Compound Type TM1 3. Colour: Insulation: White with Black numberings Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular Operating Temperature: Maximum 700 C Minimum Bending Radius: 3D for D < 10mm 4D for 10mm < D < 25mm 6D for D > 25mm
  • 7. 7 PVC/ AWA/ PVC Cables BS 6346 Table 6 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 50 70 95 120 150 185 240 300 400 500 630 800 1000 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 2.8 3.0 19.1 21.1 23.4 26.3 28.3 30.8 34.1 37.0 42.0 45.6 49.7 55.8 61.0 760 1010 1330 1690 2110 2450 3120 3810 4890 5990 7510 9590 11820 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Bedding: PVC Compound Type TM1 4. Armour: Aluminium Wire 5. Sheath: PVC Compound Type TM1 6. Colour: Insulation: Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700 C Minimum Bending Radius: 6D for 50mm2 to 1000mm2
  • 8. 8 PVC/ SWA/ PVC Cables BS 6346 Table 7 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approx. Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 (S) 2 x 70 (S) 2 x 95 (S) 2 x 120 (S) 2 x 150 (S) 2 x 185 (S) 2 x 240 (S) 2 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 12.3 13.6 15.1 16.5 20.1 21.9 26.7 29.4 27.4 30.0 34.7 37.2 40.5 45.2 50.0 54.8 270 340 450 550 750 960 1400 1750 1990 2500 2460 4120 4890 6250 7860 9480 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 12.8 14.1 15.8 18.0 21.2 23.1 28.2 30.8 30.1 34.2 38.5 41.4 46.3 50.7 56.2 61.6 350 400 520 730 1010 1180 1760 2170 2560 3520 4640 5500 6970 8400 10550 12800 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 13.5 15.0 17.8 19.2 22.8 26.3 30.7 33.7 29.9 34.6 38.4 43.5 48.1 52.4 57.4 64.1 70.4 345 440 710 810 1130 1550 2150 2670 2510 3410 4400 5830 7400 8810 10660 13430 16330 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Bedding: PVC Compound Type TM1 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type TM1 6. Colour: Insulation: 2 Cores- Red, Black 3 Cores – Red, Yellow, Blue 4 Cores – Red, Yellow, Blue, Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700 C Minimum Bending Radius: 6D for 1.5mm2 to 16mm2 8D for 25mm2 and above PVC/SWA/ PVC Cables BS 6346 Table 8 No. Nominal No. and Radial Approx. Approx.
  • 9. 9 Of Cores Conductor Area Diameter of Wire Thickness of Insulation Overall Diameter Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 5 7 10 12 19 27 37 48 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 14.3 15.2 19.0 19.4 22.2 26.7 29.2 32.9 357 416 446 716 938 1380 1689 2048 5 7 10 12 19 27 37 48 2.5 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 7/ 0.67 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 16.3 18.0 21.9 22.4 26.6 30.7 34.0 39.5 465 557 878 955 1455 1885 2340 3190 5 7 10 12 19 27 37 48 4 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 7/ 0.85 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 19.0 20.5 26.1 26.8 30.5 37.1 40.8 46.0 750 905 1405 1530 2060 3025 3900 4800 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Bedding: PVC Compound Type TM1 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type TM1 6. Colour: Insulation:White with Black numberings Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 700 C Minimum Bending Radius: 6D for 1.5mm2 to 4mm2
  • 10. 10 Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.1 Conductor Thickness of Insulation 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 0.5 0.75 1.0 1.25 1.5 2.5 4.0 16/ 0.20 24/ 0.20 32/ 0.20 40/ 0.20 30/ 0.25 50/ 0.25 56/ 0.30 0.6 0.6 0.6 0.7 0.7 0.8 0.8 6.1 6.6 6.9 7.6 7.8 9.6 11.0 55 65 75 80 90 135 135 Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.2 Conductor Thickness of Insulation 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 0.5 0.75 1.0 1.25 1.5 2.5 4.0 16/ 0.20 24/ 0.20 32/ 0.20 40/ 0.20 30/ 0.25 50/ 0.25 56/ 0.30 0.6 0.6 0.6 0.7 0.7 0.8 0.8 6.5 6.9 7.3 8.3 8.5 10.4 11.8 60 75 85 100 110 170 215 Flexible Cable, Circular Sheathed, Metric Unit BS 6500 Table 9.3 Conductor Thickness of Insulation 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) 0.5 0.75 1.0 1.25 1.5 2.5 4.0 16/ 0.20 24/ 0.20 32/ 0.20 40/ 0.20 30/ 0.25 50/ 0.25 56/ 0.30 0.6 0.6 0.6 0.7 0.7 0.8 0.8 7.1 7.6 8.2 - 9.5 11.4 12.9 75 90 110 - 140 205 275 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation : PVC Compound Type TI2 3. Assembly : 2, 3 or 4 Cores are Twisted Together 4. Sheath : PVC Compound Type TM2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 5 Operating Temperature: 700
  • 11. 11 Flexible Cord, Twin Twisted Non- Sheated, Imperial Unit BS 2004 Table 10.1 Conductor Thickness of Insulation Twin Twisted Nominal Area Construction Approx. Overall Diameter Approx. Net Weight (mm2 ) (no./in) (mm) (mm) (kg/ 100y) 0.41 0.67 1.17 14/ 0.0076 23/ 0.0076 40/ 0.0076 0.64 0.64 0.64 2.1 2.4 2.7 1.7 2.3 3.1 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation : PVC Compound Type TI1 3. Assembly : Two Cores Twisted Voltage Uo/U: 250/ 440V Conductor Stranding: Class 5 Operating Temperature: 700 Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.2 Conductor Thickness of Insulation 1 Core 2 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight Approx. Overall Diameter Approx. Net Weight (mm2 ) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y) 0.41 0.67 1.17 2.05 3.22 4.74 14/ 0.0076 23/ 0.0076 40/ 0.0076 70/ 0.0076 110/ 0.0076 162/ 0.0076 0.64 0.64 0.64 0.64 0.64 0.76 4.2 4.4 4.8 5.2 5.7 6.4 2.1 2.5 3.2 4.2 5.4 7.3 6.3 6.8 7.5 9.0 10.0 11.3 4.8 6.0 7.5 10.0 12.9 17.4 Flexible Cable, Circular Sheathed, Imperial Unit BS 2004 Table 10.3 Conductor Thickness of Insulation 3 Cores 4 Cores Nominal Area Construction Approx. Overall Diameter Approx. Net Weight Approx. Overall Diameter Approx. Net Weight (mm2 ) (mm) (mm) (mm) (kg/ 100y) (mm) (kg/ 100y) 0.41 0.67 1.17 2.05 3.22 4.74 14/ 0.0076 23/ 0.0076 40/ 0.0076 70/ 0.0076 110/ 0.0076 162/ 0.0076 0.64 0.64 0.64 0.64 0.64 0.76 6.6 7.1 7.9 9.5 10.5 12.2 5.6 6.2 8.9 12.7 16.6 22.9 7.2 7.7 9.2 10.3 11.4 13.2 6.2 7.9 10.0 15.4 20.4 28.3 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation : PVC Compound Type TI1 3. Assembly : 1, 2, 3 or 4 Cores Twisted Togeher 4. Sheath: PVC Compound Type T6 Voltage Uo/U: 250/ 440V Conductor Stranding: Class 5 Operating Temperature: 700
  • 12. 12 XLPE/ PVC & XLPE/ AWA/ PVC Cables IEC 60502 Table 11 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation XP XAP Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2.85 127/ 3.20 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8 9.6 11.3 12.5 14.0 16.1 18.2 20.0 22.2 24.4 27.5 30.3 33.9 37.6 42.4 47.3 52.4 205 309 412 540 760 1020 1270 1560 1930 2510 3120 3970 4980 6400 8190 10265 - 10.6 11.8 13.3 15.4 17.3 19.1 21.0 23.3 26.1 28.7 32.1 35.7 40.4 45.1 50.1 - 0.9 0.9 1.25 1.25 1.25 1..6 1.60 1.60 1.6 1.6 2.0 2.0 2.0 2.5 2.5 - 16.0 17.2 19.4 21.5 23.4 25.9 27.9 30.1 33.2 35.8 40.9 44.6 49.2 55.7 61.0 - 470 581 800 960 1240 1650 1970 2390 3040 3790 4790 5880 7400 9500 11750 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 4. Armour: Aluminium Wire 5. Sheath: PVC Compound Type ST2 6. Colour: Insulation: Natural Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900 C Minimum Bending Radius: Unarmoured: 8D for 16mm2 to 1000mm2 Armoured: 10D for 25mm2 to 1000mm2
  • 13. 13 XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 12 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation XP XSP Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 2 x 35 2 x 50 (S) 2 x 70 (S) 2 x 95 (S) 2 x 120 (S) 2 x 150 (S) 2 x 185 (S) 2 x 240 (S) 2 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 10.0 10.8 11.9 13.0 14.9 17.0 20.4 22.7 21.0 24.0 26.9 29.9 33.4 37.1 45.0 50.0 130 165 210 270 390 450 820 1065 1140 1560 2130 2640 3270 4040 5150 6560 8.5 9.3 10.4 11.5 13.4 15.5 18.9 21.2 19.2 22.3 25.3 28.1 30.9 36.0 41.6 47.4 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.5 2.5 13.9 14.7 15.8 16.9 19.5 21.6 25.7 28.0 26.0 29.5 33.5 36.5 39.5 45.0 52.0 58.0 350 400 475 560 810 980 1410 1930 1880 2420 3360 3980 4730 6245 8720 9390 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 10.5 11.4 12.5 13.8 15.8 18.0 21.7 24.2 25.0 29.0 32.0 36.5 39.0 44.0 49.0 55.0 150 195 255 330 490 700 1000 1300 1600 2240 3050 3800 4640 5870 7670 9460 9.0 9.9 11.0 12.3 14.3 16.5 20.2 23.0 23.0 27.0 30.1 34.4 37.5 41.3 46.4 52.0 0.9 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 2.0 2.0 2.0 2.5 2.5 2.5 2.5 14.4 15.3 16.4 17.7 20.4 22.6 27.0 29.8 30.0 35.0 38.5 43.0 47.5 51.5 57.0 36.0 390 450 540 745 950 1250 1840 2280 2550 3500 4500 5700 6800 8200 10300 12500 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 11.3 12.3 13.6 15.0 17.2 19.7 23.9 26.6 25.0 28.5 32.0 37.0 42.0 46.0 50.0 55.0 36.0 175 225 305 405 600 870 1325 1760 1600 2200 3050 4070 5195 6350 7890 10400 12810 10.0 10.8 12.1 13.5 15.7 18.2 22.4 15.1 24.0 26.8 30.6 34.4 36.0 38.3 46.4 51.0 56.6 0.9 0.9 0.9 1.25 1.25 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 15.4 16.2 17.5 19.6 21.8 25.0 29.2 32.1 31.0 34.0 39.0 43.0 46.0 48.5 57.0 62.0 68.0 430 505 710 855 1120 1600 2160 2750 2500 3100 4400 5610 7400 8300 10400 13000 15900 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type ST2 6. Colour: Insulation: 2 Cores - Red, Black 3 Cores – Red, Yellow, Blue 4 Cores – Red, Yellow, Blue, Black Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900 C Minimum Bending Radius: Unarmoured: 6D for 1.5mm2 to 300mm2 Armoured: 8D for 1.5mm2 to 300mm2
  • 14. 14 XLPE/ PVC & XLPE/ SWA/ PVC Cables IEC 60502 Table 13 No. of Cores Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation XP XSP Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 5 7 12 19 37 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.7 0.7 0.7 0.7 0.7 11.9 12.9 16.5 19.4 25.4 214.5 235.5 391.1 522.0 981.0 10.5 11.5 15.1 17.7 23.3 0.9 0.9 1.25 1.25 1.6 15.9 16.9 21.2 23.8 30.1 493.9 560.7 903.9 1167.8 1872.0 5 7 12 19 37 2.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.7 0.7 0.7 0.7 0.7 13.1 14.1 18.4 21.4 18.4 280.4 317.5 500.0 737.0 1327.0 11.7 12.7 16.8 19.8 27.0 0.9 0.9 1.25 1.6 1.6 17.1 18.1 22.9 26.6 33.8 586.8 676.1 1095.8 1593.2 2361.0 5 7 12 19 37 4 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.7 0.7 0.7 0.7 0.7 14.5 16.0 20.6 24.1 32.2 381.6 470.0 709.0 1051.0 1989.0 13.1 14.3 18.6 22.0 30.1 1.25 1.25 1.25 1.6 1.6 19.2 20.4 24.7 28.8 36.9 823.0 906.0 1293.0 1904.0 2919.0 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Armour: Galvanised Steel Wire 5. Sheath: PVC Compound Type ST2 6. Colour: Insulation:White with Black numberings Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular Operating Temperature: Maximum 900 C Minimum Bending Radius: Unarmoured: 6D for 1.5mm2 to 4mm2 Armoured: 8D for 1.5mm2 to 4mm2
  • 15. 15 IN-POP & IN-POSP Cables Table 14 SIZE IN-POP IN-POSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2C x 0.5 3C x 0.5 4C x 0.5 6C x 0.5 10C x 0.5 20C x 0.5 40C x 0.5 80C x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.0 7.3 7.9 9.3 11.9 14.9 20.1 26.3 60 68 78 110 170 295 510 950 7.0 7.3 7.9 9.3 11.9 14.9 20.1 26.3 0.90 0.90 0.90 0.90 0.90 1.25 1.60 1.60 11.4 11.7 12.3 13.9 16.7 20.6 26.7 33.3 250 265 290 360 490 800 1300 2050 2C x 0.75 3C x 0.75 4C x 0.75 6C x 0.75 10C x 0.75 20C x 0.75 40C x 0.75 80C x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.3 7.7 8.3 9.9 12.7 16.0 21.7 28.5 65 78 92 128 200 355 640 1185 7.3 7.7 8.3 9.9 12.7 16.0 21.7 28.5 0.90 0.90 0.90 0.90 0.90 1.25 1.60 1.60 11.7 12.1 12.9 14.5 17.5 21.7 28.5 35.7 260 280 320 400 550 905 1500 2420 2C x 1.5 3C x 1.5 4C x 1.5 6C x 1.5 10C x 1.5 20C x 1.5 40C x 1.5 80C x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.3 8.9 9.7 11.7 14.7 18.7 24.6 33.6 90 115 140 200 315 560 1040 1970 8.3 8.9 9.7 11.7 14.7 18.7 24.6 33.6 0.90 0.90 0.90 0.90 1.25 1.60 1.60 2.00 12.9 13.5 14.3 16.3 20.4 25.3 31.6 41.8 310 360 400 515 820 1340 2090 3690 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are stranded in Reverse Layer Technique forming a Concentric Cable 4. Wrap film: Polyster Binder Tape 5. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 6. Bedding : PVC Compound Type TM1 (optional) 7. Armouring: Galvanised Steel Wire (optional) Reference standards: BS 5308 Part 2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 700 C Testing Voltage: 1KV/ 1 Minute 8. Sheath: PVC Compound Type TM1 9. Colour: Insulation: Yellow with Black numberings or refer to colour code Sheath: Black
  • 16. 16 IN-POP & IN-POSP Cables Table 15 SIZE IN-POP IN-POSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 1P x 0.5 2P(Quad) x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 60 78 185 310 430 540 780 1240 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 0.90 0.90 0.90 1.25 1.60 1.60 1.60 2.00 11.4 12.3 17.9 22.9 26.4 29.1 33.9 42.1 250 290 540 905 1270 1490 1960 3000 1P x 0.75 2P(Quad) x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.3 8.3 14.3 18.7 21.4 24.5 29.5 37.4 68 92 230 390 530 690 1010 1610 7.3 8.3 14.3 18.7 21.4 24.5 29.5 37.4 0.90 0.90 1.25 1.60 1.60 1.60 2.00 2.00 11.7 12.9 19.8 25.3 28.2 31.3 37.5 45.8 260 325 710 1170 1460 1750 2560 3550 1P x 1.5 2P(Quad) x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 90 142 330 580 860 1090 1600 2570 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 0.90 0.90 1.25 1.60 1.60 1.60 2.00 2.50 12.9 14.3 22.1 28.4 32.2 35.7 42.5 53.4 310 410 900 1510 1950 2330 3400 5320 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Wrap Film: Polyster Binder Tape 5. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 6. Bedding : PVC Compound Type TM1 (optional) 7. Armouring: Galvanised Steel Wire (optional) Reference standards: BS 5308 Part 2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 700 C Testing Voltage: 1KV/ 1 Minute 8. Sheath: PVC Compound Type TM1 9. Colour: Insulation:White and Black numberings or refer to colour code Sheath: Black
  • 17. 17 IN-POP & IN-POSP Cables Table 16 SIZE IN-PIOP IN-PIOSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2P x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.0 15.2 21.1 24.5 27.3 32.3 41.7 135 240 410 590 750 1090 1780 12.0 15.2 21.1 24.5 27.3 32.3 41.7 0.90 1.25 1.60 1.60 1.60 2.00 2.50 16.8 20.9 27.9 31.3 34.3 40.5 51.5 470 770 1320 1640 1910 2740 4400 2P x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.8 16.3 22.7 26.4 29.8 35.5 45.0 155 275 480 700 900 1310 2060 12.8 16.3 22.7 26.4 29.8 35.5 45.0 0.90 1.25 1.60 1.60 2.00 2.00 2.50 17.6 22.0 29.5 33.4 37.8 43.9 55.0 505 850 1450 1830 2430 3190 4970 2P x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 14.7 18.8 26.5 30.8 34.4 41.0 52.2 215 400 740 1060 1340 1970 3130 14.7 18.8 26.5 30.8 34.4 41.0 52.2 1.25 1.60 1.60 2.00 2.00 2.50 2.50 20.4 25.4 33.5 38.8 42.6 50.8 62.6 730 1200 1860 2660 3100 4550 6420 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Individual: Aluminium/ Polyester Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 5. Wrap Film: Polyster Binder Tape 6. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 7. Bedding : PVC Compound Type TM1 (optional) Reference standards: BS 5308 Part 2 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 700 C Testing Voltage: 1KV/ 1 Minute 8. Armouring: Galvanised Steel Wire (optional) 9. Sheath: PVC Compound Type TM110. Colour: 10. Colour: Insulation: White and Black numberings or refer to colour code Sheath: Black
  • 18. 18 IN-EOP & IN-EOSP Cables Table 17 SIZE IN-EOP IN-EOSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 1P x 0.5 2P(Quad) x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 56 70 170 280 385 480 690 1080 7.0 7.9 13.1 17.2 19.8 22.3 26.9 33.9 0.90 0.90 0.90 1.25 1.60 1.60 1.60 2.00 11.4 12.3 17.9 22.9 26.4 29.1 33.9 42.1 230 270 500 830 1150 1360 1750 2730 1P x 0.75 2P(Quad) x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 7/ 0.43 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 7.4 8.4 14.2 18.4 21.3 24.4 29.0 37.3 68 95 230 385 540 705 995 1630 7.4 8.4 14.2 18.4 21.3 24.4 29.0 37.3 0.90 0.90 1.25 1.25 1.60 1.60 1.60 2.00 11.8 13.0 19.7 24.3 28.1 31.2 36.2 45.7 250 310 680 980 1380 1650 2150 3430 1P x 1.5 2P(Quad) x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 85 132 315 550 790 1000 1460 2340 8.3 9.7 16.4 21.6 25.2 28.5 34.3 43.6 0.90 0.90 1.25 1.60 1.60 1.60 2.00 2.50 12.9 14.3 22.1 28.4 32.2 35.7 42.5 53.4 290 380 840 1410 1790 2150 3100 4920 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: PVC Compound Type TI1 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Wrap Film: Polyster Binder Tape 5. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 6. Bedding : Polyethylene Compound Type 03 (optional) 7. Armouring: Galvanised Steel Wire (optional) Reference standards: BS 5308 Part 1 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 650 C Testing Voltage: 1KV/ 1 Minute 8. Sheath: PVC Compound Type TM1 9. Colour: Insulation: White and Black numberings or refer to colour code Sheat: Black
  • 19. 19 IN-EOP & IN-EOSP Cables Table 18 SIZE IN-EOP IN-EOSP Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Unarmoured Armoured Cable Overall Diameter Approx. Weight Diameter Under Armour Armour Wire Diameter Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (kg/ km) (mm) (mm) (mm) (kg/ km) 2P x 0.5 5P x 0.5 10P x 0.5 15P x 0.5 20P x 0.5 30P x 0.5 50P x 0.5 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 16/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.0 15.2 21.1 24.5 27.3 32.3 41.7 130 230 400 560 690 990 1610 12.0 15.2 21.1 24.5 27.3 32.3 41.7 0.90 1.25 1.60 1.60 1.60 2.00 2.50 16.8 20.9 27.9 31.3 34.3 40.5 51.5 430 720 1240 1530 1770 2550 4080 2P x 0.75 5P x 0.75 10P x 0.75 15P x 0.75 20P x 0.75 30P x 0.75 50P x 0.75 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 24/ 0.2 0.6 0.6 0.6 0.6 0.6 0.6 0.6 12.8 16.3 22.7 26.4 29.8 35.5 45.0 155 285 500 720 930 1350 2130 12.8 16.3 22.7 26.4 29.8 35.5 45.0 0.90 1.25 1.60 1.60 2.00 2.00 2.50 17.6 21.9 29.4 33.2 37.8 43.8 54.9 480 800 1400 1760 2350 3060 4800 2P x 1.5 5P x 1.5 10P x 1.5 15P x 1.5 20P x 1.5 30P x 1.5 50P x 1.5 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 7/ 0.53 0.6 0.6 0.6 0.6 0.6 0.6 0.6 14.7 18.8 26.5 30.8 34.4 41.0 52.2 210 380 690 990 1240 1820 2890 14.7 18.8 26.5 30.8 34.4 41.0 52.2 1.25 1.60 1.60 2.00 2.00 2.50 2.50 20.4 25.4 33.5 38.8 42.6 50.8 62.6 670 1110 1750 2460 2910 4250 6040 Pair configurations are available upon request Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: Polyethylene Compound Type 03 3. Lay Up: Cores are paired, pairs are twisted in Reverse Layer Technique forming a Concentric Cable 4. Individual: Aluminium/ Polyester Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 5. Wrap Film: Polyster Binder Tape 6. Collective: Aluminium/ Polyster Tape, with a Tinned Screen Copper Drain Wire 0.5mm2 (7/ 0.3mm) 7. Bedding : Polyethylene Compound Type 03 (optional) Reference standards: BS 5308 Part 1 Voltage Uo/U: 300/ 500V Conductor Stranding: Class 2 and 5 Operating Temperature: 650 C Testing Voltage: 1KV/ 1 Minute 8. Armouring: Galvanised Steel Wire (optional) 9. Sheath: PVC Compound Type TM1 10. Colour: Insulation:White and Black numberings or refer to colour code Sheat: Black
  • 20. 20 XLPE/ CT/ AWA/ PVC Cables IEC 60502 Table 19 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approximate Diameter Approx. Weight Under Screen Over Bedding Over Armour Over All (mm2 ) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km) 70 95 120 150 185 240 300 400 500 630 800 1000 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 61/ 2.85 61/ 3.20 127/ 2.52 127/ 2. 85 127/ 3.20 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4 2.6 2.8 15.2 17.1 19.0 21.0 23.2 26.1 28.7 32.5 36.0 40.4 45.5 50.4 17.6 19.5 20.8 22.8 25.0 27.9 30.5 34.3 37.8 42.2 47.3 52.2 20.1 22.0 24.0 26.0 28.2 31.1 33.7 38.3 41..8 46.2 52.3 57.2 23.9 25.8 27.8 29.8 32.0 35.1 37.9 42.7 46.4 51.0 57.5 62.4 1400 1700 2000 2400 2800 3500 4200 5400 6500 8200 10400 13000 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Screen: Copper Tape 5. Armour: Aluminium Wire 6. Sheath: PVC Compound Type ST2 7. Colour: Insulation: Natural Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900 C Minimum Bending Radius: 12D for 70mm2 to 1000mm2
  • 21. 21 XLPE/ CT/ SWA/ PVC Cables IEC 60502 Table 20 Nominal Conductor Area No. and Diameter of Wire Radial Thickness of Insulation Approximate Diameter Approx. Weight Under Screen Over Bedding Over Armour Over All (mm2 ) (no./mm) (mm) (mm) (mm) (mm) (mm) (kg/ km) 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 4 x 35 (S) 4 x 50 (S) 4 x 70 (S) 4 x 95 (S) 4 x 120 (S) 4 x 150 (S) 4 x 185 (S) 4 x 240 (S) 4 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 9.7 10.7 12.0 13.4 15.6 18.1 22.3 25.0 27.8 31.6 35.4 39.0 42.0 47.8 54.0 58.0 12.1 13.1 14.4 15.8 18.0 20.5 24.1 26.8 29.6 33.4 37.2 40.8 43.8 49.6 55.8 59.8 13.9 14.9 16.2 18.3 20.5 23.7 27.3 30.0 32.8 37.4 41.2 45.8 48.8 54.6 60.8 64.8 17.7 18.7 20.0 22.1 24.3 27.5 31.1 33.8 37.0 42.0 46.0 51.0 54.2 60.4 67.0 71.4 640 730 870 1180 1490 2070 2790 2940 3500 5000 6300 8200 9600 11500 14400 17200 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Bedding: PVC Compound Type ST2 or Lapped PVC Tape 4. Screen: Copper Tape 5. Armour: Galvanised Steel Wire 6. Sheath: PVC Compound Type ST2 7. Colour: Insulation: Red, Yellow, Blue, Green/ Yellow Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 stranded circular or compacted conductors Operating Temperature: Maximum 900 C Minimum Bending Radius: 12D for 1.5mm2 to 300mm2
  • 22. 22 XLPE/ CT/ PVC Cables IEC 60502 Table 21 Nominal Conductor Area No. and Diameter of Wire Combined Earth Size Radial Thickness of Insulation Radial Thickness of Sheath Unarmoured Cable Overall Diameter Approx. Weight (mm2 ) (no./mm) (mm) (mm) (mm) (mm) (kg/ km) 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 3 x 35 3 x 50 (S) 3 x 70 (S) 3 x 95 (S) 3 x 120 (S) 3 x 150 (S) 3 x 185 (S) 3 x 240 (S) 3 x 300 (S) 7/ 0.53 7/ 0.67 7/ 0.85 7/ 1.04 7/ 1.35 7/ 1.70 7/ 2.14 7/ 2.52 19/ 1.78 19/ 2.14 19/ 2.52 37/ 2.03 37/ 2.25 37/ 2.52 61/ 2.25 61/ 2.52 4.5 (3 x 1.5) 4.5 (3 x 1.5) 4.5 (3 x 1.5) 7.5 (3 x 2.5) 12 (3 x 4) 18 (3 x 6) 30 (3 x 10) 30 (3 x 10) 30 (3 x 10) 48 (3 x 16) 48 (3 x 16) 75 (3 x 25) 75 (3 x 25) 105 (3 x 35 150 (3 x 50) 150 (3 x 50) 0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.8 3.0 13.6 14.8 15.8 16.9 18.6 20.8 24.0 25.6 31.1 34.6 39.3 44.0 49.0 54.0 61.0 67.0 325 380 440 550 750 1000 1470 1890 2300 3200 4200 5400 6400 7900 10200 1230 Construction Technical Data 1. Conductor : Plain Annealed Copper 2. Insulation: XLPE Compound 3. Screen: Copper Tape 4. Sheath: PVC Compound Type ST2 5. Colour: Insulation: Red, Yellow, Blue, Green/ Yellow (x3) Sheath: Black Voltage Uo/U: 600/ 1000V Conductor Stranding: Class 2 Operating Temperature: Maximum 900 C for XLPE Maximum 1100 C for XLEVA Minimum Bending Radius: 10D for unarmoured cable
  • 23. 23 Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.1 Installation Method Examples Appropriate Reference Methoad For Determining Current- Carrying Capacity Description OPEN AND CLIPPED DIRECT: Sheathed cables clipped direct to or lying on a non- metallic surface Method 1 CABLES EMBEDDED DIRECT IN BUILDING MATERIALS: Sheathed cables embedded directly in masonry, brickwork, concrete, plaster or the like (other than thermally insulating materials) Method 1 IN CONDUIT: Single core non- sheathed cables in metallic or non- metallic conduit on a wall or ceiling Method 3 Single core non- sheathed cables in metallic or non- metallic conduit in a thermally insulating ceiling, the conduit being in contact with a thermally conductive surface on one side Method 4 Multi core cables having non- metallic sheath, in metallic or non- metallic conduit on a wall or ceiling Method 3  The wall is assumed to consist of an outer weatherproof skin, thermal insulation and an inner skin of plasterboard of wood- like material having a coefficient of heat transfer not less than 10 W/m2 K. The conduit is fixed so as to be close to, but not necessarily touching, the inner skin. Heat from the cables is assumed ti escape through the inner skin only. • • • • • • •
  • 24. 24 Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.2 Installation Method Examples Appropriate Reference Methoad For Determining Current- Carrying Capacity Description ON TRAYS: Sheathed cables on a perforated cable tray, bunched and unenclosed. A pertorated cable tray is considerd as a tray in which the holes occupy at least 30% of the surface area Method 11 IN FREE AIR, ON CLEATS, BRACKETS OR A LADDER: Sheathed single- core cables in free air (any supporting metalwork under the cables occupying less than 10% of the plan area Two of three cables vertically one above the other, minimum distance between cable surfaces equal to the overall cable diameter (De); distance from the wall not less than 0.5De Two or three cables horizontally, with spacings as above Three cables in trefoil, distance between wall and surface of nearest cable 0.5De or nearest cables 0.75De Method 12 Sheathed multicore cables on ladder or brackets, separation greater than 2De Sheathed multicore cables in free air distance between wall and cable surface not less than 0.3De Any supporting metalwork under the cables occupying less than 10% of the plan area Method 13 Cables suspended from or incorporating a catenary wire Method 12 or 13, as appropriate
  • 25. 25 Schedule of Installation Methods of Cables (Including Reference Method) Technical Table 1.3 Installation Method Examples Appropriate Reference Methoad For Determining Current- Carrying Capacity Description CABLES IN TRENCHES: Cables in enclosed trench 450mm wide by 300mm deep (minimum dimentions) including 100mm cover Two signle- core cables with surfaces sepaeerated by a minimum og one cable diameter Method 18 Use rating factors in Technical Table 3 Three single-core cables in trefoil and touching throughout Multicore cables or groups of single-core cables with surfaces separated by a minimum of 50mm Cables in enclosed trench 450mm wide by 600mm deep (minimum dimentions) including 100mm cover Single-core cables arranged in flat groups of two or three on the vertical trench wall with surfaces separated by one diameter with a minimum distance of 50mm between groups. Multicore cables installed with surfaces separated by a minimum of 75mm. All cables spaced at least 25mm from the trenched wall Method 19 Use rating factors in Technical Table 3 Cables in enclosed trench 600mm wide by 760mm deep (minimum dimentions) including 100mm cover Single-core cables arranged in groups of two or three in flat formation with the surfaces sepaerated by one diameter or in trefoil formation with cables touching Method 20 Use rating factors in Technical Table 3 Groups separated by a minimum* of 50mm either horizontally or vertically. Multi caor cables installed with surfaces separated by a minimum* of 75mm either horizontally or vertically. All cables spaced at least 25mm from the trench wall Larger spacing to be used where practicable
  • 26. 26 Correction Factors For Groups of More than One Circuit Of Single-core Cables, or More than One Multicore Cable Technical Table 2 Reference Methods of Installation Correction Factor (C9) Number of Circuits of Multi-Core Cables 2 3 4 5 6 7 8 9 10 12 14 16 18 20 Enclosed (Method 3 or 4) or bunched and clipped direct to a non- metallic surface (Method 1) 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38 Single layer clipped to a non-metallic surface (Method 1) Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - - Spaced * 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 Single layer multi core on a perforated metal cable tray, vertical or horizontal (Method 11) Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - - Spaced * 0.91 0.89 0.88 0.87 0.87 - - - - - - - - - Single layer single core on a perforated metal cable tray, touching (Method 11) Horizontal 0.90 0.85 - - - - - - - - - - - - Vertical 0.85 - - - - - - - - - - - - - Single layer multi core touching on ladder supports 0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -  Space means a clearance between adjacent surfaces of at least one cable diameter (De). Where the horizontal clearance between adjacent cables exceeds 2 De, no correction factor need be applied. Notes: 1) The factors in the table are applicable to groups of cables all of one size. The value of current derived from application of the appropriate factors is the maximum continuous current to be carried by any of the cables in the group. 2) If, due to known operating conditions, a cable is expected to carry not more than 30% of it’s grouped rating, it may be ignored for the purposed of obtaining the rating factor for the rest of the group. For example, a group of N loaded cables would normally require a group reduction factor of Cg applied to the tabulated It. However, if M cables in the group carry loads which are not greater than 0.3Cglt amperes, the other cables can be sized by using the group rating factor corresponding to (N-M) cables. 3) Factors are given for single layer of cables and do not apply when cables are installed in more than one layer touching each other. 4) For circuits having more than one cable in parallel per phase, each set of three conductors should be considered as a circuit for the purpose of this table. Correction Factors for Cables installed in Enclosed Trenches Technical Table 3 Conductor cross- sectional area mm2 Installation Method 18 Installation Method 19 Installation Method 20 2 1-core cables, or 1 3- or 4- core cables 3 1-core cables, or 2 2-core cables 4 1-core cables, or 2 3- or 4- core cables 6 1-core cables, 4 2- core cables, or 3 3- or 4- core cables 6 1-core cables, 4 2- core cables, or 3 3- or 4- core cables 8 1-core cables, or 4 3- or 4- core cables 12 1-core cables, 8 2- core cables, or 6 3- or 4- core cables 12 1-core cables, 8 2- core cables, or 6 3- or 4- core cables 18 1-core cables, 12 2- core cables, or 9 3- or 4- core cables 24 1-core cables, 16 2- core cables, or 12 3- or 4- core cables 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 0.93 0.92 0.91 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82 0.81 0.80 0.78 0.77 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.82 0.81 0.80 0.78 0.77 0.76 0.74 0.73 0.72 0.71 0.87 0.86 0.85 0.84 0.82 0.81 0.79 0.78 0.76 0.75 0.74 0.73 0.71 0.69 0.67 0.66 0.65 0.82 0.81 0.80 0.78 0.76 0.75 0.74 0.72 0.70 0.69 0.67 0.65 0.63 0.62 0.59 0.58 0.56 0.86 0.86 0.85 0.83 0.81 0.80 0.78 0.77 0.75 0.73 0.72 0.70 0.69 0.68 0.66 0.64 0.63 0.83 0.82 0.80 0.78 0.76 0.74 0.73 0.72 0.70 0.68 0.67 0.65 0.63 0.62 0.60 0.58 0.57 0.76 0.75 0.74 0.71 0.69 0.68 0.66 0.64 0.63 0.61 0.59 0.58 0.56 0.54 0.52 0.51 0.49 0.81 0.80 0.78 0.76 0.74 0.72 0.71 0.70 0.68 0.66 0.64 0.63 0.61 0.59 0.57 0.56 0.54 0.74 0.73 0.72 0.70 0.67 0.66 0.64 0.62 0.60 0.58 0.57 0.55 0.53 0.52 0.50 0.48 0.47 0.69 0.68 0.66 0.64 0.62 0.60 0.59 0.57 0.55 0.53 0.51 0.49 0.48 0.46 0.44 0.43 0.41 The correction factors tabulated above relate to the disposition of cables illustrated in terms 18 to 20 of Technical Table 1.3 and are applicable to the current- carrying capacities for Reference Methods 12 or 13 of Technical Table 1.2. When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating temperature of any cable in the group.
  • 27. 27 Technical Data Rating Factors for Other Temperature conditions Technical Table 4 Table A: Rating Factors for Other Ambient Air Temperature (PVC Insulated) Ambient Temperature 250 C 300 C 350 C 400 C 450 C 500 C 550 C 600 C 650 C 700 C Rating Factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50 0.35 - Table B: Rating Factors for Other Ground Temperature (PVC Insulated) Ambient Temperature 100 C 150 C 200 C 250 C 300 C 350 C 400 C 450 C 500 C Rating Factor 1.04 1.00 0.95 0.90 0.85 0.80 0.73 0.67 0.60 Table C: Rating Factors for Other Ambient Air Temperature (XLPE Insulated) Ambient Temperature 250 C 300 C 350 C 400 C 450 C 500 C 550 C 600 C 650 C 700 C 750 C 800 C 850 C Rating Factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29 Table D: Rating Factors for Other Ground Temperature (XLPE Insulated) Ambient Temperature 150 C 200 C 250 C 300 C 350 C 400 C 450 C 500 C Rating Factor 1.00 0.97 0.93 0.89 0.86 0.82 0.77 0.73 Table E: Rating factors for Other Ambient Air Temperature (PVC Insulated) Ambient Temperature 300 C 350 C 400 C 450 C 500 C 550 C 600 C 650 C 700 C PVC cords, non-heat resisting 1.00 0.96 0.92 0.87 0.71 0.50 - - - PVC cords, heat resisting 1.00 - - - 1.00 0.96 0.83 0.67 0.47 Table F: Group Rating Factors for Cables Installation Group Rating Factors Numbers of Circuits 2 3 4 5 6 7 8 9 10 11 12 1 For circuits of 2 Single-core cables laid flat touching horizontal formation, laid direct in ground 0.79 0.68 0.62 0.57 0.54 0.52 0.50 0.48 0.47 0.46 0.45 2 For circuits of 3 Single-core cables in trefoil touching, laid direct in the ground 0.78 0.66 0.61 0.56 0.53 0.50 0.49 0.47 0.46 0.44 0.43 Number of Cables in a Group 2 3 4 5 6 7 8 9 10 11 12 3 For twin of multicore cables in horizontal formation, laid direct in ground Spaced 0.15m 0.87 0.78 0.74 0.70 0.68 0.66 0.64 0.63 0.62 0.61 0.60 Spaced 0.30m 0.91 0.84 0.81 0.78 0.77 0.75 0.75 0.74 0.73 0.73 0.72 Numbers of Ducts in a Group 2 3 4 5 6 7 8 9 10 11 12 4 For twin multicore cables in single-way ducts horizontal formation spaced 0.30m apart 0.93 0.88 0.85 0.83 0.82 0.81 0.80 0.79 0.79 0.78 0.78
  • 28. 28 Current- Carrying Capacities (Amp) PVC & PVC/ PVC Cables Technical Table 5.1 Conductor cross- sectional area Reference Method 4 (Enclosed in conduit in thermally insulating wall etc) Reference Method 3 (Enclosed in conduit on a wall or in trunking etc) Reference Method 1 (‘Clipped direct’) Reference Method 11 (on a perforated cable tray horizontal of vertical) Reference Method 12 (free air) Horizontal flat spaced, Vertical flat spaced, 2 cables, single- phase ac or dc 3 or 4 cables 3- phase ac 2 cables, single- phase ac or dc 3 or 4 cables 3- phase ac 2 cables, single- phase ac or dc 3 or 4 cables 3- phase ac 2 cables, single- phase ac or dc or flat and touching 3 cables, 3-phase ac flat and touching 2 cables, single- phase ac or dc or 3 cables or trefoil 2 cables, single- phase ac or dc or 3 cables 3- phase ac 3 cables, trefoil 3-phase ac 3-phase ac mm2 Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp BS 6004 1 1.5 2.5 4 6 10 16 25 35 11 14.5 19.5 26 34 46 61 80 99 10.5 13.5 18 24 31 42 56 73 89 13.5 17.5 24 32 41 57 76 101 125 12 15.5 21 28 36 50 68 89 110 15.5 20 27 37 47 65 87 114 141 14 18 25 33 43 59 79 104 129 - - - - - - - 126 156 - - - - - - - 112 141 - - - - - - - 146 181 - - - - - - - 130 162 - - - - - - - 110 137 BS 6346 50 70 95 120 150 185 240 300 400 500 630 800 1000 119 151 182 210 240 273 320 367 - - - - - 108 136 164 188 216 245 286 328 - - - - - 151 192 232 269 300 341 400 458 546 626 720 - - 134 171 207 239 262 296 346 394 467 533 611 - - 182 234 284 330 381 436 515 594 694 792 904 1030 1154 167 214 261 303 349 400 472 545 634 723 826 943 1058 191 246 300 349 404 463 549 635 732 835 953 1086 1216 172 223 273 318 369 424 504 584 679 778 892 1020 1149 219 281 341 396 456 521 615 709 852 982 1138 1265 1420 197 254 311 362 419 480 569 659 795 920 1070 1188 1337 167 216 264 304 356 409 485 561 656 749 855 971 1079 * With or without protective conductor Note: Rating factors for ambient temperature other than 300 c please refer Table A Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Meter) PVC & PVC/ PVC Cables Technical Table 5.2 Conductor Cross- sectional area 2 cables dc 2 cables- single- phase ac 3 or 4 cables- three- phase ac Reference Methods 3 & 4 (Enclosed in conduit etc in or on a wall) Reference Methods 1 & 11 (Clipped direct or on trays, touching) Reference Methods 12 (space *) Reference Methods 3 & 4 (Enclosed in conduit etc in or on a wall) Reference Methods 1, 11& 12 (in trefoil) Reference Methods 1 & 11 (flat touching) Reference Methods 12 (Flat spaced*) mm2 mV mV mV mV mV mV mV mV 1 1.5 2.5 4 6 10 16 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 38 25 15 9.5 6.4 3.8 2.4 38 25 15 9.5 6.4 3.8 2.4 38 25 15 9.5 6.4 3.8 2.4 38 25 15 9.5 6.4 3.8 2.4 r x z r x z r x z r x z r x z r x z r x z 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 1.75 1.25 0.93 0.63 0.46 0.36 0.29 0.23 0.180 0.145 0.105 0.086 0.068 0.053 0.042 1.80 1.30 0.95 0.65 0.49 0.39 0.31 0.25 0.195 0.160 0.130 0.110 0.094 - - 0.33 0.31 0.30 0.29 0.28 0.27 0.27 0.27 0.26 0.26 0.26 0.26 0.25 - - 1.80 1.30 1.00 0.72 0.56 0.47 0.41 0.37 0.33 0.31 29 0.28 0.27 - - 1.75 1.25 0.93 0.63 0.47 0.37 0.30 0.24 0.185 0.150 0.120 0.098 0.081 0.068 0.059 0.20 0.195 0.190 0.185 0.180 0.175 0.175 0.170 0.165 0.165 0.160 0.155 0.155 0.150 0.150 1.75 1.25 0.95 0.66 0.50 0.41 0.34 0.29 0.25 0.22 0.20 0.185 0.175 0.165 0.160 1.75 1.25 0.93 0.63 0.47 0.37 0.29 0.24 0.185 0.150 0.115 0.093 0.076 0.061 0.050 0.29 0.28 0.28 0.27 0.27 0.26 0.26 0.26 0.25 0.25 0.25 0.24 0.24 0.24 0.24 1.80 1.30 0.97 0.69 0.54 0.45 0.39 0.35 0.31 0.29 0.27 0.26 0.25 0.25 0.24 1.50 1.10 0.81 0.56 0.42 0.33 0.27 0.22 0.17 0.14 0.12 0.10 0.08 - - 0.29 0.27 0.26 0.25 0.24 0.23 0.23 0.23 0.23 0.23 0.22 0.22 0.22 - - 1.55 1.10 0.85 0.61 0.48 0.41 0.36 0.32 0.29 0.27 0.25 0.25 0.24 - - 1.50 1.10 0.80 0.55 0.41 0.32 0.26 0.21 0.160 0.130 0.150 0.086 0.072 0.060 0.052 0.175 0.170 0.165 0.160 0.155 0.150 0.150 0.145 0.145 0.140 0.140 0.135 0.135 0.130 0.130 1.50 1.10 0.82 0.57 0.43 0.36 0.30 0.26 0.22 0.190 0.175 0.160 0.150 0.145 0.140 1.50 1.10 0.80 0.55 0.41 0.32 0.26 0.21 0.160 0.130 0.150 0.086 0.072 0.060 0.052 0.25 0.24 0.24 0.24 0.23 0.23 0.23 0.22 0.22 0.22 0.21 0.21 0.21 0.21 0.20 1.55 1.10 0.84 0.60 0.47 0.40 0.34 0.31 0.27 0.25 0.24 0.23 0.22 0.22 0.21 1.50 1.10 0.80 0.55 0.40 0.32 0.26 0.21 0.160 0.130 0.100 0.081 0.066 0.053 0.044 0.32 0.32 0.32 0.31 0.31 0.30 0.30 0.30 0.29 0.29 0.29 0.29 0.28 0.28 0.28 1.55 1.15 0.86 0.63 0.51 0.44 0.40 0.36 0.34 0.32 0.31 0.30 0.29 0.29 0.28 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 29. 29 Current- Crying Capacities (Amp) PVC/ PVC Cables Technical Table 6.1 Conductor cross- sectional area Reference Methods 4 (Enclosed in an insulated wall etc) Reference Methods 3 (Enclosed in conduit on a wall or ceiling, or in trunking) Reference Method 1 (Clipped direct) Reference Method 11 (on a perforated cable tray), or Reference Method 13 ( free air) 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac 1 2-core cable* single-phase ac or dc 1 2-core cable* or 1 4-core cable 3-phase ac mm2 Amp Amp Amp Amp Amp Amp Amp Amp 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 11 14 18.5 25 32 43 57 75 92 110 139 167 192 219 248 291 334 - 10 13 17.5 23 29 39 52 68 83 99 125 150 172 196 223 261 298 - 13 16.5 23 30 38 52 69 90 111 133 168 201 232 258 294 344 394 470 11.5 15 20 27 34 46 62 80 99 118 149 179 206 225 255 297 339 402 15 19.5 27 36 46 63 85 112 138 168 213 258 299 344 392 461 530 634 13.5 17.5 24 32 41 57 76 96 119 144 184 223 259 299 341 403 464 557 17 22 30 40 51 70 94 119 148 180 232 282 328 379 434 514 593 715 14.5 18.5 25 34 43 60 80 101 126 153 196 238 276 319 364 430 497 597 * With or without protective conductor Note: Rating factors for ambient temperature other than 300 c please refer Table A Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Meter) PVC/ PVC Cables Technical Table 6.2 Conductor cross- sectional 2-core cable ac 2-core cable single-phase ac 3 or 4-core cable 3-phase ac mm2 mV mV mV 1 1.5 2.5 4 6 10 16 44 29 18 11 7.3 4.4 2.8 44 29 18 11 7.3 4.4 2.8 38 25 15 9.5 6.4 3.8 2.4 r x z r x z 25 35 50 70 95 120 150 185 240 300 400 1.75 1.25 0.93 0.63 0.46 0.36 0.29 0.23 0.180 0.145 0.105 1.75 1.25 0.93 0.63 0.47 0.38 0.30 0.25 0.190 0.155 0.115 0.170 0.165 0.165 0.160 0.155 0.155 0.155 0.150 0.150 0.145 0.145 1.75 1.25 0.94 0.65 0.50 0.41 0.34 0.29 0.24 0.21 0.185 1.50 1.10 0.80 0.55 0.41 0.33 0.26 0.21 0.165 0.135 0.100 0.145 0.145 0.140 0.140 0.135 0.135 0.130 0.130 0.130 0.130 0.125 1.50 1.10 0.81 0.57 0.43 0.35 0.29 0.25 0.21 0.185 0.160 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 30. 30 Current- Crying Capacities (Amp) PVC/ AWA/ PVC Cables Technical Table 7.1 Conductor cross- sectional area Reference Methods 1 (Clipped direct) Reference Methods 11 (on perforated cable tray) Reference Methods 12 (free air) Direct in ground In Single Way Ducts 2 cables single- phase ac or dc 3 or 4 cables 3-phase ac 2 cables single- phase ac flat & touching 3 or 4 cables 3-phase flat & touching 3 or 4 cables 3-phase ac 2 cables dc spaced 2 cables flat touch- ing 3 cables trefoil touch- ing 2 cables duct touch- ing 3 cables trefoil touch- ing Horizontal flat spaced Vertical flat spaced 3 cables trefoils Hori- zontal Verti- cal mm2 Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp Amp 50 70 95 120 150 185 240 300 400 500 630 800 1000 193 245 296 342 393 447 525 594 687 763 843 919 975 179 225 269 309 352 399 465 515 575 622 669 710 737 205 259 313 360 413 469 550 624 723 805 891 976 1041 189 238 285 327 373 422 492 547 618 673 228 777 808 230 286 338 385 436 490 566 616 674 721 771 824 872 212 263 313 357 405 456 528 578 632 676 723 772 816 181 231 280 324 373 425 501 567 657 731 809 886 945 229 294 357 415 479 548 648 748 885 1035 1218 1441 1685 216 279 340 396 458 525 622 719 851 997 1174 1390 1627 238 292 349 396 443 497 571 640 708 780 856 895 939 203 248 297 337 376 423 485 542 600 660 721 756 797 216 262 308 341 375 414 463 509 545 585 632 662 703 199 241 282 311 342 375 419 459 489 523 563 587 621 Note: Rating factors for ambient temperature other than 300 c please refer Table A Rating factors for ambient temperature other than 150 c please refer Table B Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 7.2 Conduc- tor cross- sectional area 2 cable s dc 2 cables-single-phase ac 3 or 4 cables-three-phase ac Direct in ground Single Way Ducts Reference Methods 1 & 11 (Touching) Reference Methods 12 (space*) Reference Methods 1, 11 & 12 (in trefoil touching) Reference Methods 1 & 11 (Flat touching) Reference Methods 12 (flat spaced*) 2 cables flat touch- ing 3 cables trefoil touch- ing 2 cables flat touch- ing 3 cable s trefoi l touch -ing mm2 mV mV mV mV mV mV mV mV mV mV r x z r x z r x z r x z r x z 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.93 0.63 0.46 0.36 0.29 0.23 0.180 0.145 0.105 0.086 0.068 0.053 0.042 0.93 0.64 0.48 0.39 0.31 0.26 0.20 0.160 0.140 0.120 0.105 0.094 0.095 0.22 0.21 0.20 0.195 0.19 0.19 0.180 0.180 0.175 0.170 0.165 0.160 0.155 0.95 0.68 0.52 0.43 0.37 0.32 0.27 0.24 0.22 0.21 0.195 0.185 0.185 0.92 0.66 0.51 0.42 0.34 0.29 0.23 0.190 0.180 0.165 0.150 0.145 0.140 0.30 0.29 0.28 0.28 0.27 0.27 0.26 0.26 0.24 0.23 0.22 0.21 0.190 0.97 0.72 0.58 0.50 0.44 0.39 0.35 0.32 0.30 0.29 0.27 0.25 0.24 0.80 0.56 0.42 0.33 0.27 0.22 0.175 0.140 0.120 0.105 0.091 0.082 0.079 0.19 0.18 0.175 0.17 0.165 0.16 0.160 0.155 0.130 0.145 0.145 0.140 0.135 0.82 0.58 0.45 0.37 0.32 0.27 0.23 0.21 0.195 0.180 0.170 0.160 0.155 0.79 0.57 0.44 0.36 0.30 0.25 0.20 0.165 0.160 0.145 0.135 0.125 0.125 0.26 0.25 0.25 0.24 0.24 0.23 0.23 0.22 0.21 0.20 0.195 0.180 0.165 0.84 0.62 0.50 0.43 0.38 0.34 0.30 0.28 0.26 0.25 0.23 0.22 0.21 0.79 0.59 0.47 0.40 0.34 0.29 0.24 0.20 0.21 0.190 0.175 0.170 0.165 0.34 0.32 0.31 0.30 0.30 0.29 0.28 0.28 0.25 0.24 0.22 0.195 0.170 0.86 0.68 0.57 0.50 0.45 0.41 0.37 0.34 0.32 0.30 0.28 0.26 0.24 0.97 0.67 0.50 0.42 0.36 0.31 0.26 0.23 0.22 0.20 0.19 - - 0.82 0.58 0.44 0.36 0.31 0.27 0.23 0.20 0.19 0.18 0.16 - - 1.00 0.76 0.61 0.54 0.48 0.44 0.40 0.37 0.34 0.32 0.30 - - 0.88 0.66 0.53 0.47 0.42 0.38 0.34 0.32 0.30 0.28 0.26 - - Note: r = conductor resistance at operating temperature; z = impedance; x = reactance
  • 31. 31 Current- Crying Capacities (Amp) PVC/ SWA/ PVC Cables Technical Table 8.1 Conductor cross- sectional area Reference Methods 1 (Clipped direct) Reference Methods 11 (on a perforated horizontal cable tray or Reference Methods 13 (free air) Direct in Ground In Single Way Ducts 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3- phase ac or dc 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3- phase ac or dc 2 cores 3 or 4 cores 2 cores 3 or 4 cores mm2 Amp Amp Amp Amp Amp Amp Amp Amp 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 21 28 38 49 67 89 118 145 175 222 269 310 356 405 476 547 621 18 25 33 42 58 77 102 125 151 192 231 267 306 348 409 469 540 22 31 41 53 72 97 128 157 190 241 291 336 386 439 516 592 683 19 26 35 45 62 83 110 135 163 207 251 290 332 378 445 510 590 32 41 55 69 92 119 158 190 225 277 332 377 422 478 551 616 693 27 35 47 59 78 101 132 159 188 233 279 317 355 401 462 517 580 26 34 45 57 76 98 129 154 183 225 271 309 346 393 455 510 574 22 29 38 48 64 83 107 126 153 190 228 260 292 331 382 428 490 Note: Rating factors for ambient temperature other than 300 c please refer Table A Rating factors for ambient temperature other than 150 c please refer Table B Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Meter) PVC/AWA/ PVC Cables Technical Table 8.2 Conductor cross- sectional area 2- core cable ac 2- core cable single-phase ac 3- or 4- cable 3- phase ac Direct in Ground In Single Way Ducts 2- cores 3- or 4- cores 2 - cores 3- or 4- cores mm2 mV mV mV mV mV mV mV 1.5 2.5 4 6 10 16 29 18 11 7.3 4.4 2.8 29 18 11 7.3 4.4 2.8 25 15 9.5 6.4 3.8 2.4 29 18 11 7.3 4.4 2.8 25 15 9.5 6.4 3.8 2.4 29 18 11 7.3 4.4 2.8 25 15 9.5 6.4 3.8 2.4 r x z r x z 25 35 50 70 95 120 150 185 240 300 400 1.75 1.25 0.93 0.63 0.46 0.36 0.29 0.23 0.18 0.145 0.105 1.75 1.25 0.93 0.63 0.47 0.38 0.3 0.25 0.19 0.155 0.115 0.17 0.165 0.165 0.16 0.155 0.155 0.155 0.15 0.15 0.145 0.145 1.75 1.25 0.94 0.65 0.5 0.41 0.34 0.29 0.24 0.21 0.185 1.5 1.1 0.8 0.55 0.41 0.33 0.26 0.21 0.165 0.135 0.1 0.145 0.145 0.14 0.14 0.135 0.135 0.13 0.13 0.13 0.13 0.125 1.5 1.1 0.81 0.57 0.43 0.35 0.29 0.25 0.21 0.185 0.16 1.7 1.3 0.94 0.66 0.49 0.4 0.34 0.29 0.24 0.21 0.19 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17 1.7 1.3 0.94 0.66 0.49 0.4 0.34 0.29 0.24 0.21 0.19 1.5 1.1 0.82 0.57 0.42 0.35 0.29 0.25 0.21 0.18 0.17 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 32. 32 Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 9.1 Size of Conductor Reference Methods 4 (Enclosed in an insulated wall etc) Reference Methods 3 (Enclosed in conduit on a wall or ceiling, or in trunking) Reference Method 1 (Clipped direct) Reference Method 11 (on a perforated cable tray, horizontal or vertical) Reference Method 12 ( free air) 2 cables 1-phase ac or dc 3 or 4 cables 3-phase ac 2 cables 1-phase ac or dc 3 or 4 cables 3-phase ac 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching or trefoil 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching or trefoil 3 cables trefoil 3-phase ac 1 2 3 4 5 6 7 8 9 10 mm2 A A A A A A A A A 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 18 24 33 43 58 76 100 124 149 189 228 263 300 341 400 459 - - - - - 17 23 30 39 53 70 91 111 135 170 205 235 270 306 358 410 - - - - - 22 30 40 51 71 95 126 156 189 240 290 336 375 426 500 573 683 783 900 - - 19 26 35 45 63 85 111 138 168 214 259 299 328 370 433 493 584 666 764 - - 25 34 46 59 81 109 143 176 228 293 355 413 476 545 644 743 868 990 1130 1288 1443 23 31 41 54 74 99 130 161 209 268 326 379 436 500 590 681 793 904 1033 1179 1323 - - - - - - 158 195 293 308 375 436 505 579 686 794 915 1044 1191 1358 1520 - - - - - - 140 176 215 279 341 398 461 530 630 730 849 973 1115 1275 1436 - - - - - - 138 171 209 270 330 385 445 511 606 701 820 936 1069 1214 1349 Note: Rating factors for ambient temperature other than 300 c please refer Table C Rating factors for ambient temperature other than 150 c please refer Table D Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 9.2 Size of Conductor 2 cables dc 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac Reference Methods 3&4 (Enclosed in conduit etc, in or on a wall) Reference Methods 1 & 11 (clipped direct or on trays touching) Reference Methods 3&4 (Enclosed in conduit etc, in or on a wall) Reference Methods 1, 11 & 12 (in trefoil) Reference Methods 1 & 11 (flat & touching) 1 2 3 4 5 6 7 mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m 1.5 2.5 4 6 10 16 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 27 16 10 6.8 4.0 2.5 27 16 10 6.8 4.0 2.5 27 16 10 6.8 4.0 2.5 r x z r x Z r x z r x z r x Z 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 1.85 1.35 0.99 0.68 0.49 0.39 0.32 0.25 0.19 0.155 0.12 0.093 0.072 0.056 0.045 1.85 1.35 1.00 0.70 0.51 0.41 0.33 0.27 0.21 0.175 0.14 0.12 0.10 - - 0.31 0.29 0.29 0.28 0.28 0.27 0.26 0.26 0.26 0.26 0.25 0.25 0.25 0.25 - 1.90 1.35 1.05 0.75 0.58 0.48 0.43 0.37 0.33 0.31 0.29 0.28 0.27 - - 1.85 1.35 0.99 0.68 0.49 0.39 0.32 0.26 0.20 0.16 0.13 0.105 0.086 0.072 0.063 0.19 0.18 0.18 0.175 0.170 0.165 0.165 0.165 0.160 0.160 0.155 0.155 0.155 0.150 0.150 1.85 1.35 1.00 0.71 0.52 0.43 0.36 0.30 0.25 0.22 0.20 0.185 0.175 0.170 0.165 1.60 1.15 0.87 0.60 0.44 0.35 0.29 0.23 0.185 0.15 0.125 0.100 0.088 - - 0.27 0.25 0.25 0.24 0.23 0.23 0.23 0.23 0.22 0.22 0.22 0.22 0.21 - - 1.65 1.15 0.90 0.65 0.50 0.42 0.37 0.32 0.29 0.27 0.25 0.24 0.23 - - 1.60 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.17 0.14 0.11 0.09 0.074 0.062 0.055 0.165 0.155 0.155 0.150 0.145 0.140 0.140 0.140 0.140 0.140 0.135 0.135 0.135 0.130 0.130 1.60 1.15 0.87 0.61 0.45 0.37 0.31 0.26 0.22 0.195 0.175 0.160 0.150 0.145 0.140 1.60 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.17 0.135 0.110 0.088 0.071 0.059 0.050 0.19 0.18 0.18 0.175 0.170 0.165 0.165 0.165 0.165 0.160 0.160 0.160 0.160 0.155 0.150 1.60 1.15 0.87 0.62 0.46 0.38 0.32 0.28 0.24 0.21 0.195 0.180 0.170 0.165 0.165 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 33. 33 Current- Crying Capacities (Amp) XLPE/ PVC Cables Technical Table 10.1 Size of Conductor Reference Methods 4 (Enclosed in conduit and in insulated wall etc) Reference Methods 3 (Enclosed in conduit on a wall or ceiling, or in trunking) Reference Method 1 (Clipped direct) Reference Method 11 (on a perforated cable tray, or Reference Method 13 (free air) 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2 3 4 5 6 7 8 9 mm2 A A A A A A A A 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 18.5 25 33 42 57 76 99 121 145 183 220 253 290 329 386 442 - 16.5 22 30 38 51 68 89 109 130 164 197 227 259 295 346 396 - 22 30 40 51 69 91 119 146 175 221 265 305 334 384 459 532 625 19.5 26 35 44 60 50 105 128 154 194 233 268 300 340 398 455 536 24 33 45 58 80 107 138 171 209 269 328 382 441 506 599 693 803 22 30 40 52 71 96 119 147 179 229 278 322 371 424 500 576 667 26 36 49 63 86 115 149 185 225 289 352 410 473 542 641 741 865 23 32 42 54 75 100 127 158 192 246 298 346 399 456 538 621 741 Note: Rating factors for ambient temperature other than 300 c please refer Table C Rating factors for ambient temperature other than 150 c please refer Table D Group Rating Factor please refer to Table 2 Voltage Drop (Per Amp Per Meter) XLPE/ PVC Cables Technical Table 10.2 Size of Conductor 2-core cable dc 2-core cable single-phase ac 3- or 4- Cable 3-phase ac 1 2 3 4 mm2 mV/A/m mV/A/m mV/A/m 1.5 2.5 4 6 10 16 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 27 16 10 6.8 4.0 2.5 r x z r x Z 25 35 50 70 95 120 150 185 240 300 400 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.120 1.85 1.35 0.99 0.67 0.50 0.40 0.32 0.26 0.20 0.16 0.13 0.16 0.155 0.155 0.150 0.150 0.145 0.145 0.145 0.140 0.140 0.140 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.6 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.175 0.140 0.115 0.14 0.135 0.135 0.130 0.130 0.130 0.125 0.125 0.125 0.120 0.120 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 34. 34 Current- Crying Capacities (Amp) XLPE/ AWA/ PVC Cables Technical Table 11.1 Size of Conductor Reference Methods 1 (clipped direct) Reference Method 11 (on a perforated cable tray) Reference Method 12 ( free air) In single-way ducts Laid direct in ground 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching 2 cables 1-phase ac or dc flat & touching 3 or 4 cables 3-phase ac flat & touching 3 cables 3-phase ac trefoil touching 2 cables 1-phase ac or dc ducts touching 3 cables 3-phase ac trefoil ducts touching 2 cables 1-phase ac or dc touching 3 cables 3-phase ac trefoil touching 1 2 3 4 5 6 7 8 9 10 mm2 A A A A A A A A A 50 70 95 120 150 185 240 300 400 500 630 800 1000 237 303 367 425 488 557 656 755 853 962 1082 1170 1261 220 277 333 383 437 496 579 662 717 791 861 904 961 253 322 382 449 516 587 689 792 899 1016 1146 1246 1345 232 293 352 405 462 524 612 700 767 851 935 987 1055 222 285 346 402 463 529 625 720 815 918 1027 1119 1214 255 310 365 410 445 485 550 610 640 690 750 828 919 235 280 330 370 405 440 500 550 580 620 670 735 811 257 340 405 460 510 580 670 750 830 910 1000 1117 1254 235 290 345 390 435 490 560 630 700 770 840 931 1038 Note: Rating factors for ambient temperature other than 300 c please refer Table C Rating factors for ambient temperature other than 150 c please refer Table D Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Per Meter) XLPE/AWA/PVC Cables Technical Table 11.2 Size of Conductor 2 cables dc 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac, touching Reference Methods 1 & 11 (touching) Reference Methods 1, 11 & 12 (in trefoil touching) Reference Methods 1 & 11 (flat & touching) In ducts In ground In ducts In ground 1 2 3 4 5 6 7 8 9 mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m r x z r x z r x z 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.115 0.093 0.073 0.056 0.045 0.99 0.68 0.51 0.41 0.33 0.27 0.21 0.17 0.145 0.125 0.105 0.09 0.092 0.21 0.20 0.195 0.190 0.185 0.185 0.180 0.175 0.170 0.170 0.165 0.160 0.155 1 0.71 0.55 0.45 0.38 0.33 0.28 0.25 0.22 0.21 0.195 0.190 0.180 0.86 0.59 0.44 0.35 0.29 0.23 0.18 0.145 0.125 0.105 0.092 0.086 0.080 0.18 0.17 0.17 0.165 0.160 0.160 0.155 0.150 0.150 0.145 0.145 0.140 0.135 0.87 0.62 0.47 0.39 0.33 0.28 0.24 0.21 0.195 0.180 0.170 0.165 0.155 0.84 0.6 0.46 0.38 0.31 0.26 0.21 0.17 0.160 0.145 0.135 0.130 0.125 0.25 0.25 0.24 0.24 0.23 0.23 0.22 0.22 0.21 0.20 0.195 0.180 0.170 0.88 0.65 0.52 0.44 0.39 0.34 0.30 0.28 0.27 0.25 0.24 0.23 0.21 1.10 0.80 0.65 0.55 0.50 0.45 0.40 0.37 0.35 0.33 0.30 0.28 0.26 0.99 0.70 0.53 0.43 0.37 0.31 0.26 0.24 0.21 0.20 0.19 0.18 0.17 0.93 0.70 0.56 0.48 0.43 0.39 0.35 0.32 0.30 0.28 0.26 0.24 0.22 0.86 0.61 0.46 0.37 0.32 0.27 0.23 0.21 0.19 0.18 0.17 0.16 0.15 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 35. 35 Current- Crying Capacities (Amp) XLPE/ SWA/ PVC Cables Technical Table 12.1 Size of Conductor Reference Methods 1 (clipped direct) Reference Method 11 (on a perforated cable tray, or Reference Method 13 (free air) In single-way ducts Laid direct in ground 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2-core cable single-phase ac or dc 1 3- or 4- cable 3-phase ac 1 2 3 4 5 6 7 8 9 mm2 A A A A A A A A 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 27 36 49 62 85 110 146 180 219 279 338 392 451 515 607 698 787 23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599 673 29 39 52 66 90 115 152 188 228 291 354 410 472 539 636 732 847 25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628 728 - - - - - 115 145 175 210 260 310 355 400 455 520 590 660 23 30 40 50 65 94 125 150 175 215 260 300 335 380 440 495 560 - - - - - 140 180 215 255 315 380 430 480 540 630 700 790 28 36 48 60 80 115 150 180 215 265 315 360 405 460 530 590 670 Note: Rating factors for ambient temperature other than 300 c please refer Table C Rating factors for ambient temperature other than 150 c please refer Table D Group Rating Factor please refer to Table F & Table 2 Voltage Drop (Per Amp Per Meter) XLPE/SWA/PVC Cables Technical Table 12.2 Size of Conductor 2 cables dc 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac 2 Cables, 1-phase ac 3 or 4 Cables, 3-phase ac In ducts In ground In ducts In ground 1 2 3 4 5 6 7 8 mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m 1.5 2.5 4 6 10 16 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 27 16 10 6.8 4.0 2.5 31 19 12 7.9 4.7 2.9 31 19 12 7.9 4.7 2.9 25 15 9.5 6.4 3.8 2.4 25 15 9.5 6.4 3.8 2.4 r x z r x z 25 35 50 70 95 120 150 185 240 300 400 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.120 1.85 1.35 0.99 0.67 0.50 0.40 0.32 0.26 0.20 0.16 0.13 0.16 0.155 0.155 0.150 0.150 0.145 0.145 0.145 0.140 0.140 0.140 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.6 1.15 0.86 0.59 0.43 0.34 0.28 0.22 0.175 0.140 0.115 0.14 0.135 0.135 0.130 0.130 0.130 0.125 0.125 0.125 0.120 0.120 1.65 1.15 0.87 0.60 0.45 0.37 0.30 0.26 0.21 0.185 0.165 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.9 1.35 1.00 0.69 0.52 0.42 0.35 0.29 0.24 0.21 0.19 1.6 1.2 0.87 0.61 0.45 0.36 0.30 0.25 0.21 0.19 0.18 1.6 1.2 0.87 0.61 0.45 0.36 0.30 0.25 0.21 0.19 0.18 Note: r = conductor resistance at operating temperature z = impedance, x = reactance
  • 36. 36 Technical Data Flexible Cord, Imperial Sizes Technical Table 13.1 Conductor Current Rating Volt Drop PER 100FT Maximum Weigh supportable by twin flexible cord Nominal Area Construction 1 or 3 phase ac or dc dc or 1 phase ac 3 phase ac in2 No./in Amp V V lb 0.0006 0.0010 0.0017 0.0030 0.0048 0.0070 14/ 0.0076 23/ 0.0076 40/ 0.0076 70/ 0.0076 110/ 0.0076 162/ 0.0076 3 6 13 18 24 31 8.9 11 14 12 9.6 8.4 7.7 9.4 12 10 8.3 7.3 3 5 10 10 10 10 Note: Rating factors for ambient temperature other than 300 c please refer Table E Technical Data Flexible Cord Metric Sizes Technical Table 13.2 Conductor Current Rating Volt Drop per 100FT Maximum Weigh supportable by twin flexible cord Nominal Area Construction 1 or 3 phase ac or dc dc or 1 phase ac 3 phase ac mm2 No./mm Amp mV/m mV/m kg 0.50 0.75 1.00 1.25 1.50 2.50 4.00 16/ 0.2 24/ 0.2 32/ 0.2 40/ 0.2 30/ 0.25 50/ 0.25 56/ 0.3 3 6 10 13 15 20 25 83 56 43 35 31 18 11 72 48 37 29 26 16 9.6 2 3 5 5 5 5 5 Note: Rating factors for ambient temperature other than 300 c please refer Table E
  • 37. 37 Allowable Short Circuit Currents For PVC Insulated Cables Technical Table 14.1 Short circuit current (KA) 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000 Conductor: Copper Insulation: PVC Curves based on formula: l = (0.115A÷ t ) Where: l – Short circuit current (KA) A- Conductor area (mm2 ) t – Time of short circuit (seconds) Conductor Size (mm2 ) Allowable Short Circuit Currents For XLPE Insulated Cables Technical Table 14.2 Short circuit current (KA) 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0 1.0 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 10000 Conductor: Copper Insulation: PVC Curves based on formula: l = (0.115A÷ t ) Where: l – Short circuit current (KA) A- Conductor area (mm2 ) t – Time of short circuit (seconds) Conductor Size (mm2 )
  • 38. 38 Short Circuit ratings for power cables Technical Table 14.3 Cross- Sectional Area Short Circuit Rating for 1 second Short Circuit Rating for 3 seconds Another important factor for the determination of the conductor size is the maximum allowable current during a short circuit when the maximum allowable current during a short circuit when the maximum allowable conductor temperature is higher than during normal operation. The maximum permissible short circuit current of XLPE cables up to 1Kv with copper conductors can be calculated with the formula: K t S lk   Where l = Short Circuit rating (KA) S = Conductor Area (sq mm) t = Duration of Short Circuit (sec) mm2 KA KA 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.2145 0.3575 0.5720 0.8580 1.4300 2.2880 3.5750 5.0050 7.1500 10.0100 13.5850 17.1600 21.4500 26.4550 34.3200 42.9000 57.2000 71.5000 90.0900 114.4000 143.0000 0.1238 0.2064 0.3302 0.4954 0.8256 1.3210 2.0640 2.8896 4.1281 5.7793 7.8433 9.9073 12.3842 15.2738 19.8147 24.7683 33.0244 41.2805 52.0135 66.0489 82.5611 The above rating is calculated using the following formula: t S l 143 . 0  Where l = Short Circuit rating (KA) S = Conductor Area (sq mm) t = Duration of Short Circuit (sec) Copper Conductor Technical Table 14.3 Current in Kiloampers Duration of Short circuit in Seconds The values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 900 c), and a final conductor temperature of 2500 c, and it should be ensured that the accessories associated with the cable are also capable of operation at these values of fault current.
  • 39. 39 IN-POP, IN-POSP IN-PIOP, IN-PIOSP & IN-EOP, IN-EOSP IN-EIOP, IN-EIOSP Technical Table 15 1 . Test Voltage: 1000 Vr.m.s. for 1 minute between each conductor in turn and all other connected together 2 . Maximum DC Conductor Resistance at 200 c Conductor Size Multi-cores Multi-pairs 0.5 mm2 0.75 mm2 1.0 mm2 1.5 mm2 39.0 26.0 18.1 12.1 39.7 26.5 18.4 12.3 3. Minimum Insulation Resistance at 200 c PE Insulated PVC Insulated Individual Conductor (between) each conductor and Remaining bunched conductors/ screen and/ or armour 5000MΩ.km 25 MΩ.km Individual Screens (between screens) 1 MΩ.km 1 MΩ.km 4. Maximum Mutual Capacitance at 1 KHz (pF/m) Cable Type Conductor Size 0.5 mm2 1.0 mm2 1.5 mm2 PE Insulated Cables without individual pair screen 75 pF/m 75 pF/m 85 pF/m PE Insulated All cables with individual pair screen, 1 and 2 pair cables collective screen 115 pF/m 115 pF/m 120 pF/m PVC Insulated Pairs 250pF/m 5. Maximum Capacitance Between Any Core or Screen PVC Insulated cables: 450 pF/m 6. Maximum Capacitance Unbalance at 1 KHz PE Insulated cables: 250pF/ 250m 7. Maximum L/R Ratio (For Adjacent Cores) Conductor Size Multi-cores 0.5 mm2 0.75 mm2 1.0 mm2 1.5 mm2 25 µH/Ω 25 µH/Ω 25 µH/Ω 40 µH/Ω Maximum Conductor Resistance Technical Table 16 Electrical Characteristics Technical Table 16 Cross Section Area (S) Conductor for Fixied Wiring Class 1 (solid), Class 2 (stranded) Conductor Resistance Temperature Correction Factors mm2 Temp0 C Factor 0.50 0.75 1.00 1.50 2.50 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 36.0 24.5 18.1 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 30 35 40 45 50 55 60 65 70 75 80 85 90 0.961 0.965 0.969 0.972 0.976 0.980 0.984 0.988 0.992 0.996 1.000 1.004 1.008 1.012 1.016 1.020 1.039 1.059 1.079 1.098 1.118 1.138 1.157 1.177 1.196 1.216 1.236 1.255 1.275
  • 40. 40 (mm2 – CM – AWG/ MCM) Technical Table 18 Cross- sectional Area Conductor Size Cross- sectional Area Conductor Size (mm2 ) (CM) (AWG/ MCM) (mm2 ) (CM) (AWG/ MCM) 0.324 0.519 0.653 0.823 *1.0 1.04 1.31 *1.5 1.65 2.08 *2.5 2.63 3.31 *4.0 4.17 5.261 *6.0 6.631 8.367 *10.0 10.55 13.3 *16.3 16.77 21.15 *25.0 26.67 33.62 *35.0 42.41 *50.0 53.49 67.43 *70.0 85.01 *95.0 640 1020 1290 1620 1974 2050 2580 2960 3260 4110 4934 5180 6530 7894 8230 10380 11841 13090 16510 19735 20820 26240 31576 33090 41740 49338 52620 66360 69073 83690 98675 105600 133100 138145 167800 187483 22 20 19 18 - 17 16 - 15 14 - 13 12 - 11 10 - 9 8 - 7 6 - 5 4 - 3 2 - 1 - 1/0 2/0 - 3/0 - 107.2 *120 127 *150 152 177 *185 203 228 *240 253 279 300 304 329 355 380 *400 405 456 *500 507 557 608 *630 633 659 709 760 *800 811 861 887 912 963 *1000 010 211600 236820 250000 296025 300000 350000 365098 400000 450000 473640 5000000 550000 592050 600000 650000 700000 750000 789400 800000 900000 986750 1000000 1000100 1000200 1243305 1250000 1300000 1400000 1500000 1578800 1600000 1700000 1750000 1800000 1900000 1973500 2000000 4/0 - -250 - 300 350 - 400 450 - 500 550 - 600 650 700 750 - 850 900 - 1000 1100 1200 - 1250 1300 1400 1500 - 1600 1700 1750 1800 1900 - 2000 Note: * British standard *127 mm2 and larger is rounded off and not actual. CM area is actual Conversion factors: mm2 x 1973.5 = CM x 0.0005067 = mm2. AWG - America Wire Gauge. A standard measurement of the size of a conductor: 4/0 & smaller. CM (Circular Mil) used to define cross-sectional areas of conductors. Area of circle 171000 inches in diameter. MCM – 1000 circular mils.