2. Introduction
▪ Spread foundations supporting two or more columns are classified as combined
footings or combined bases.
▪ Combined footings can become a necessity for two reasons
▪ Instances where two columns are so closely spaced such that designing isolated pad footings
under each column will result in a base overlap.
▪ Instances where the external columns are very close to a property line such that
constructing isolated pad bases is impossible without a projection beyond the line.
2
3. Principles
▪ The design of combined bases can be done using two approach, the flexibility method
and the conventional rigid method. The latter is most common method.
▪ The conventional rigid approach makes two assumptions:
▪ The base is infinitely rigid and therefore the deflection of the footing does not influence the
pressure distribution.
▪ The footing is proportioned such that the resultant of all applied loads pass through the
centroid of the base.
▪ The design of combined bases in principle is the same procedure as for an isolated
pad foundation.
3
4. Steps for Design
▪ Determine the required size of the combined base using the permissible bearing
stress and the critical loading at the serviceability limit state.
▪ Proportion the footing for uniform pressure distribution by finding the point of
application of the resultant of the column loads and adjusting the geometry of the
footing appropriately.
▪ Determine the bearing pressures associated with the critical loading arrangement at
the ultimate limit state.
▪ Assume a suitable thickness for the footing, h and effective depth, d and verify
punching shear at both column faces
▪ Analyze the footing in the longitudinal and transverse direction.
▪ In the longitudinal/transverse direction, the footing is idealized as an inverted overhanging
beam subjected to the earth pressure at the ultimate limit state.
▪ Design the bending reinforcement in the longitudinal/transverse direction
▪ Verify shear at the critical sections including punching shear at the basic control
perimeter 2d from the column face.
▪ Verify detailing requirements
4
5. Worked Example
A combined footing is required in a proposed facility for two closely spaced
column. Design the footing completely using a presumed bearing capacity of
180kN/m2 using C20/25 concrete and reinforcing steel of 410Mpa bars. The design
data is presented as follows:
Table 1.0 Design Data
Figure 1.0: Column Layout
5
Column Size Gk (kN) Qk (kN)
C1 275x275 365 185
C2 300x300 525 290
15. Solution Cont’d
▪ Punching Shear at Basic Control Perimeter 2.0d from column face
Punching at the basic control perimeter is not a critical check in combined bases, hence
the check is ignored in this example, however a check can be carried out using the same
procedures outlined in the design of isolated pad bases for each column.
▪ Transverse shear
The maximum shear force is used to carry out the check. By Inspection, this occurs in the
longitudinal direction.
▪ N:B The design shear force is taken at 1.0d from the supports.
𝑉𝐸𝑑 = 353.6 − 𝑝 1.0d = 353.6 − 226.24 × 0.442 = 253.6𝑘𝑁
𝑣 𝐸𝑑 =
𝑉 𝐸𝑑
𝑏𝑑
=
253.6×103
1000×442
= 0.57Mpa
15
16. Solution Cont’d
▪ Transverse shear Cont’d
𝑣 𝑅𝑑,𝑐 = 0.12𝑘(100𝜌𝑓𝑐𝑘)1/3
≥ 0.035𝑘3/2
𝑓𝑐𝑘
𝜌 =
𝐴 𝑠
𝑏𝑑
=
1340
1000×442
= 0.0030 ; 𝑘 = 1 +
200
𝑑
= 1 +
200
442
= 1.67 < 2
𝑣 𝑅𝑑,𝑐 = 0.12 × 1.67(100 × 0.0030 × 20)1/3 ≥ 0.035 × 1.67
3
2 20 = 0.36𝑀𝑝𝑎
𝑆𝑖𝑛𝑐𝑒 (𝑣 𝐸𝑑 = 0.57𝑀𝑝𝑎) > (𝑣 𝑅𝑑,𝑐= 0.42𝑀𝑝𝑎) 𝑁𝑜𝑡 𝑜𝑘
The section is not adequate in shear, hence the section depth can be increased to 600mm,
or reinforcement increased, or concrete grade increased and then redesigned.
16
18. Quiz
A combined footing is required in a proposed facility for two closely spaced
column. Design the footing completely using a presumed bearing capacity of
150kN/m2 using C30/37 concrete and reinforcing steel of 460Mpa bars. The design
data is presented as follows:
Table 1.0 Design Data
Figure 1.0: Column Layout
18
Column Size Gk (kN) Qk (kN)
C1 275x275 365 185
C2 300x300 525 290