The new PowerVUE™ design utilizes the same rugged Hagan actuator and frame construction, combined with the accuracy and reliability of the Fisher FieldVUE DVC6000 Digital Valve Controller. The pneumatic power positioner remains the most reliable and cost-effective method of actuation. Torque ranges are from 400 ft-lbs to 4,600 ft.-lbs.
The EL2200 series of electromagnetic flowmeters represent the state of the art for the accurate measurement for water cycle and process applications. This new generation flowmeter utilizes an innovative structure to route the electromagnetic signal generated by the electrodes, providing a flowmeter with an extremely wide measurement range. The new EL Series meters are capable of a measurement range up to 1000:1.
Magnetic flow meter for industrial process measurementCTi Controltech
Enhanced signal conditioning circuitry provides excellent noise and spike immunity
High stable and repeatable output with ±0.5% of rate accuracy
Minimum process fluid conductivity requirement of 10μS/cm provides maximum applicability
Electrode Status Diagnostic function diagnoses empty pipe condition or electrode scaling
Available in wafer of flanged designs
Both Integral and Remote configurations are available for maximum flexibility
Cameron's CamCor™ PRO Series Coriolis flow meter features high-accuracy, shallow bow-shaped dual sensor tubes and is ideal for oilfield production applications. This industrial process-grade Coriolis flow meter offers high performance for accuracy, repeatability, wide flow range, low pressure loss, and safe design.
Azbil North America recently added the AX series of multivariable vortex flowmeters for industrial process measurement and control to their product offering. The instrument combines temperature, pressure and velocity measurement in a single instrument to provide accurate mass flow measurement of gases, liquids and steam.
Rotork RI Wireless is a revolutionary concept for wireless valve monitoring and diagnostics in the process industry. The field proven solution transmits real-time position indication to the control room and enables predictive maintenance for actuated valves, delivering capital and operating expenditure reduction, increased safety and increased productivity.
FLUXUS® measures flow non-intrusively using ultrasonic technology. The ultrasonic transducers are simply clamped on to the outside of the pipe and are never in contact with the liquid – pipe work is not necessary.
Clamp-on technology provides for maximum flexibility and the sophisticated electronics of FLUXUS® ensure the highest
possible accuracy and reliability. The measuring system, consisting of the transmitter, the transducers and the VARIOFIX mounting fixture, can be configured to meet individual requirements.
The FLUXUS® flowmeter series includes a variety of transmitters
and transducers: from basic models for standard applications up to robust measurement solutions for offshore use or for hazardous areas.
The EL2200 series of electromagnetic flowmeters represent the state of the art for the accurate measurement for water cycle and process applications. This new generation flowmeter utilizes an innovative structure to route the electromagnetic signal generated by the electrodes, providing a flowmeter with an extremely wide measurement range. The new EL Series meters are capable of a measurement range up to 1000:1.
Magnetic flow meter for industrial process measurementCTi Controltech
Enhanced signal conditioning circuitry provides excellent noise and spike immunity
High stable and repeatable output with ±0.5% of rate accuracy
Minimum process fluid conductivity requirement of 10μS/cm provides maximum applicability
Electrode Status Diagnostic function diagnoses empty pipe condition or electrode scaling
Available in wafer of flanged designs
Both Integral and Remote configurations are available for maximum flexibility
Cameron's CamCor™ PRO Series Coriolis flow meter features high-accuracy, shallow bow-shaped dual sensor tubes and is ideal for oilfield production applications. This industrial process-grade Coriolis flow meter offers high performance for accuracy, repeatability, wide flow range, low pressure loss, and safe design.
Azbil North America recently added the AX series of multivariable vortex flowmeters for industrial process measurement and control to their product offering. The instrument combines temperature, pressure and velocity measurement in a single instrument to provide accurate mass flow measurement of gases, liquids and steam.
Rotork RI Wireless is a revolutionary concept for wireless valve monitoring and diagnostics in the process industry. The field proven solution transmits real-time position indication to the control room and enables predictive maintenance for actuated valves, delivering capital and operating expenditure reduction, increased safety and increased productivity.
FLUXUS® measures flow non-intrusively using ultrasonic technology. The ultrasonic transducers are simply clamped on to the outside of the pipe and are never in contact with the liquid – pipe work is not necessary.
Clamp-on technology provides for maximum flexibility and the sophisticated electronics of FLUXUS® ensure the highest
possible accuracy and reliability. The measuring system, consisting of the transmitter, the transducers and the VARIOFIX mounting fixture, can be configured to meet individual requirements.
The FLUXUS® flowmeter series includes a variety of transmitters
and transducers: from basic models for standard applications up to robust measurement solutions for offshore use or for hazardous areas.
Inline and Insertion models of the Azbil Multivariable Vortex Mass Flow Meters employ three sensing elements in a single meter; a vortex shedding velocity sensor, an RTD temperature sensor, and a solid state pressure transducer. This unique combination allows accurate mass flow measurements of gases, liquids and steam.
Yokogawa manufactures several variants of sanitary pressure transmitters for industrial applications in food, pharma, and other industries. Leading edge measurement technology.
Foxboro Magnetic Flowmeter for Chemical and Process IndustriesSwanson Flo
Based on Faraday’s law of induction, Foxboro magnetic meters are a reliable ow measurement solution with a lower cost of ownership and maintenance, as well as eld-proven stability to maximize the availability of ow measurement.
With a wide range of liners and electrodes, the 9700A owtube is ideal for the Chemical and Process industries. In combination with the IMT30A, IMT31A and IMT33A transmitters, Foxboro offers an innovative solution designed to meet the demands for all chemical applications such as:
• Clean liquids
• Mixing of chemicals
• Demanding applications including corrosive, abrasive liquids • Rapid variation of the pH value
• For slurries and pastes with high solids content
• Drilling applications, mining slurries with large particles
The Brooks® Ar-MiteTM is a reliable, low flow metal tube flowmeter with 316L stainless steel wetted parts. The magnetically coupled indicator provides a highly reliable method of indication. This model is a practical and economical approach to low flow rate indication for high pressure and difficult to handle fluids. Optional accessories include 4-20 mA output, Needle Valve, Flow Controllers and Alarms.
The robust mechanical design of the M2CP is evident in its ductile iron gear case, bronze worm gear, and heat-treated alloy steel worm. Add the flexibility of modular control packages, plus an international sales & support network, and the result is an actuator to count on for the long term.
Digital valve positioner for industrial process control valvesCTi Controltech
The Flowserve Logix 3200 Digital HART® positioner utilizes state-of-the-art piezo technology to provide superior performance and reliability. The Logix 3200 can be easily configured using the local buttons, HART handheld, and SoftTools software.
Local status LED's
Local DIP Switches/Calibration Buttons
Auto Tuning with dynamic gain selection
Utilizes HART 5
Simple calibration via local interface
The AX Series of Vortex inline flowmeters measure flows of liquid, gas, and steam by measuring the rate at which vortices are alternately shed from a bluff body; this rate has been shown to be directly proportional to the flow velocity.
As flow passes a bluff body in the stream, vortices create pressure differentials which are measured by a piezoelectric crystal sensor, which converts these pulses into electrical signals. The meter uses an all-welded sensor design to create a strong unit and minimize potential leakage.
The AX Series can be configured to measure anything from simple volumetric flow of liquids and saturated steam up through multivariable measurements, including mass flow rate, pressure, temperature and density of liquids and steam.
Insertion style vortex meters measure fl ow by detecting the local velocity at a strategically located position within the pipe. Using local velocity, calculated by measuring the rate at which vortices are alternately shed from a bluff body within the sensor, the AX2300 uses parameters such as fluid type, pipe size, and Reynolds number to calculate accurate measurements.
Catalog biến tần Frenic eHVAC - beeteco.com
Chuyên cung cấp các thiết bị: Đèn báo nút nhấn, Relay, Timer, Contactor, MCCB ELCB, Biến tần, Van, Thiết bị cảm biến, phụ kiện tủ điện, .... Từ các thương hiệu hàng đầu trên thế giới.
www.beeteco.com @ Công ty TNHH TM KT ASTER
Địa chỉ : Số 7/31 KDC Thương Mại Sóng Thần, KP. Nhị Đồng 1, P. Dĩ An, Tx. Dĩ An, Tỉnh Bình Dương
FB: www.facebook.com/beeteco
Email: contact@beeteco.com
Tel: 0650 3617 012
Hotline: 0909.41.61.43
Pulp and paper applications create a notoriously harsh, high moisture and chemical-laden environment; coupled with extreme vibration in many of the processes. The following document outlines an array of level, pressure, and position applications and solutions for the pulp & paper industry.
GE Oil & Gas offers, under their Becker brand name, segmented valve rotary control valves known throughout the world for quality and durability. Becker valves have a proven track record, installed in a variety of process industries and applications. Segmented ball rotary valves offer dependability and a unique combination of high capacity and turndown capability.
Electrical test equipment for high and low voltage systems. Phasing rods, ammeter for overhead powerlines on
systems up to 36kV. Hubungi PT. Siwali Swantika, Jakarta Office : 021-45850618 atau Surabaya Office : 031-8421264
Making the best instrument selection for a flow measurement application should include an assessment of what the operators really need in order to safely and effectively run the process or perform the task related to the measurement of fluid flow.
Industry needs muscle to control process valves, dampers and feed mechanisms accurately and in response to a demand signal. Emerson’s Rosemount Analytical pneumatic power positioners have been satisfying these exacting control requirements for many years in countless applications – from steel mills to refineries – where positioning speed and accuracy are taken for granted.
Fuji tu dong hoa renic ehvaccatalog-dienhathe.orgDien Ha The
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.vn
Inline and Insertion models of the Azbil Multivariable Vortex Mass Flow Meters employ three sensing elements in a single meter; a vortex shedding velocity sensor, an RTD temperature sensor, and a solid state pressure transducer. This unique combination allows accurate mass flow measurements of gases, liquids and steam.
Yokogawa manufactures several variants of sanitary pressure transmitters for industrial applications in food, pharma, and other industries. Leading edge measurement technology.
Foxboro Magnetic Flowmeter for Chemical and Process IndustriesSwanson Flo
Based on Faraday’s law of induction, Foxboro magnetic meters are a reliable ow measurement solution with a lower cost of ownership and maintenance, as well as eld-proven stability to maximize the availability of ow measurement.
With a wide range of liners and electrodes, the 9700A owtube is ideal for the Chemical and Process industries. In combination with the IMT30A, IMT31A and IMT33A transmitters, Foxboro offers an innovative solution designed to meet the demands for all chemical applications such as:
• Clean liquids
• Mixing of chemicals
• Demanding applications including corrosive, abrasive liquids • Rapid variation of the pH value
• For slurries and pastes with high solids content
• Drilling applications, mining slurries with large particles
The Brooks® Ar-MiteTM is a reliable, low flow metal tube flowmeter with 316L stainless steel wetted parts. The magnetically coupled indicator provides a highly reliable method of indication. This model is a practical and economical approach to low flow rate indication for high pressure and difficult to handle fluids. Optional accessories include 4-20 mA output, Needle Valve, Flow Controllers and Alarms.
The robust mechanical design of the M2CP is evident in its ductile iron gear case, bronze worm gear, and heat-treated alloy steel worm. Add the flexibility of modular control packages, plus an international sales & support network, and the result is an actuator to count on for the long term.
Digital valve positioner for industrial process control valvesCTi Controltech
The Flowserve Logix 3200 Digital HART® positioner utilizes state-of-the-art piezo technology to provide superior performance and reliability. The Logix 3200 can be easily configured using the local buttons, HART handheld, and SoftTools software.
Local status LED's
Local DIP Switches/Calibration Buttons
Auto Tuning with dynamic gain selection
Utilizes HART 5
Simple calibration via local interface
The AX Series of Vortex inline flowmeters measure flows of liquid, gas, and steam by measuring the rate at which vortices are alternately shed from a bluff body; this rate has been shown to be directly proportional to the flow velocity.
As flow passes a bluff body in the stream, vortices create pressure differentials which are measured by a piezoelectric crystal sensor, which converts these pulses into electrical signals. The meter uses an all-welded sensor design to create a strong unit and minimize potential leakage.
The AX Series can be configured to measure anything from simple volumetric flow of liquids and saturated steam up through multivariable measurements, including mass flow rate, pressure, temperature and density of liquids and steam.
Insertion style vortex meters measure fl ow by detecting the local velocity at a strategically located position within the pipe. Using local velocity, calculated by measuring the rate at which vortices are alternately shed from a bluff body within the sensor, the AX2300 uses parameters such as fluid type, pipe size, and Reynolds number to calculate accurate measurements.
Catalog biến tần Frenic eHVAC - beeteco.com
Chuyên cung cấp các thiết bị: Đèn báo nút nhấn, Relay, Timer, Contactor, MCCB ELCB, Biến tần, Van, Thiết bị cảm biến, phụ kiện tủ điện, .... Từ các thương hiệu hàng đầu trên thế giới.
www.beeteco.com @ Công ty TNHH TM KT ASTER
Địa chỉ : Số 7/31 KDC Thương Mại Sóng Thần, KP. Nhị Đồng 1, P. Dĩ An, Tx. Dĩ An, Tỉnh Bình Dương
FB: www.facebook.com/beeteco
Email: contact@beeteco.com
Tel: 0650 3617 012
Hotline: 0909.41.61.43
Pulp and paper applications create a notoriously harsh, high moisture and chemical-laden environment; coupled with extreme vibration in many of the processes. The following document outlines an array of level, pressure, and position applications and solutions for the pulp & paper industry.
GE Oil & Gas offers, under their Becker brand name, segmented valve rotary control valves known throughout the world for quality and durability. Becker valves have a proven track record, installed in a variety of process industries and applications. Segmented ball rotary valves offer dependability and a unique combination of high capacity and turndown capability.
Electrical test equipment for high and low voltage systems. Phasing rods, ammeter for overhead powerlines on
systems up to 36kV. Hubungi PT. Siwali Swantika, Jakarta Office : 021-45850618 atau Surabaya Office : 031-8421264
Making the best instrument selection for a flow measurement application should include an assessment of what the operators really need in order to safely and effectively run the process or perform the task related to the measurement of fluid flow.
Industry needs muscle to control process valves, dampers and feed mechanisms accurately and in response to a demand signal. Emerson’s Rosemount Analytical pneumatic power positioners have been satisfying these exacting control requirements for many years in countless applications – from steel mills to refineries – where positioning speed and accuracy are taken for granted.
Fuji tu dong hoa renic ehvaccatalog-dienhathe.orgDien Ha The
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.vn
Electric Control Valve Actuators for Industrial Process ApplicationsCTi Controltech
The Rotork CVA line of electric process control actuators offers a highly accurate and responsive method of automating control valves, without the complexity and cost of a pneumatic supply. With an increased focus on production costs and efficiency, accurate control of product through the pipeline is paramount. With resolution figures better than 0.1% and the ability to eliminate position overshoot, the Rotork CVA models help to maximize product quality and plant capacity.
Siemens Terminal Box Controller (APOGEE Automation System )CONTROLS & SYSTEMS
In This PPT we are discussed about complete details of that product (Use,Operation, Technical details, Dimensions, Wiring, and etc..)
Please Support us and Follow our other Sites
https://www.instagram.com/controlsandsystems.offical
https://twitter.com/ControlsSystems
https://automationtechplc2.blogspot.com
https://humidificationcontrol.blogspot.com
https://controlsandsystems.business.site
www.controls.systemsdm@gmail.com
If you enjoyed this article, share it with your friends and colleagues
Vlt® hvac drives a complete range of advanced solutionsDanfoss India
Setting new standards, the modular VLT HVAC Drive integrates seamlessly with HVAC systems at the lowest cost of ownership in the market. Danfoss’ extensive experience in advanced variable frequency drive technology for HVAC applications has produced an unmatched product offering. The VLT HVAC Drive is suited for a range of needs, from simple follower operation to intelligent standalone control. From “drive only” to complete package solutions, the VLT HVAC Drive is so economical, flexible and user-friendly that it makes HVAC operation pure child’s play.Setting new standards, the modular VLT HVAC Drive integrates seamlessly with HVAC systems at the lowest cost of ownership in the market. Danfoss’ extensive experience in advanced variable frequency drive technology for HVAC applications has produced an unmatched product offering. The VLT HVAC Drive is suited for a range of needs, from simple follower operation to intelligent standalone control. From “drive only” to complete package solutions, the VLT HVAC Drive is so economical, flexible and user-friendly that it makes HVAC operation pure child’s play. For more info, visit http://www.danfoss.in/
THE WORLD’S FIRST RIFT DRIVEN® ELECTRIC ACTUATOR
For Part Turn & Multi-Turn Applications
The SmartAct®-1 electric valve actuator is the world’s first RIFT DRIVEN® product .
Its revolutionary British design has a single glass reinforced polypropylene housing that contains the RIFT motor system and gearbox. The SmartAct®-1 can be configured to produce a range of output torques up to 100Nm.
Smart, state of the art electronics provide accurate, reliable and repeatable performance characteristics and enables a comprehensive list of standard and optional features to be
offered. Optional extra cost features include failsafe and/ or modulating functionality; speed control and fieldbus communications are available to customer order.
At a time where energy consumption is becoming increasingly important to the world, the SmartAct®-1 actuator takes full advantage of the dramatic reduction in energy that the RIFT DRIVEN® system provides. This creates an electric actuator with the lowest energy usage figures available in the world market.
Standard:
- Universal power supply 12-300V
- Anti-condensation heater
- Over-torque protection
- Torque range 40, 60, 80, 100Nm
- SO5211 / EN15714-2 compliant
- Weatherproof
- Local controls
- 2 x M20 x 1.5 Cable entries
Options:
- Failsafe
- Modulating
- Fieldbus communications
- Speed control
- Data logging
- Torque profiling
- Solenoid Function
- 2 x 1/2” NPT Cable entries
- Of-Grid and Timer Facility
- Multi-Turn Function
MADE IN BRITAIN
The SmartAct®-1 electric actuator was conceived, designed, prototyped, and is being manufactured in Britain.
TH E RIFT DRIVEN® ADVANTAGE
RIFT is a new British innovation; significantly enhancing the motor characteristics resulting in a powerful, light, and yet energy efficient motor driven product.
HUGELY ENERGY EFFICIENT
A RIFT DRIVEN® product contains the RIFT technology that will transform motor driven systems in the future. They show weight and energy savings of over 75% compared to traditional motor driven systems.
In actuator comparison tests the SACO valve actuator is in fact over 90% more energy efficient than the market leading electric actuators it was compared with.
PID CONTROL
Combining PID control with a 10 bit magnetic electronic position sensing system, the SACO S m a r t a c t - 1 actuator gives very accurate positioning and timing capabilities. Part Turn or Multi-Turn applications can be configured with accuracy up to at least ¼ of a degree on most valves.
OPTIONAL SOLENOID FUNCTION
A huge advantage of the SACO actuator is that it is capable of very fast cycle times. This allows it to be used as a direct acting solenoid. Fitted to a full bore ball valve it eliminates the difficulties traditional solenoids face when used with dirty media.
Catalog Biến tần Frenic ACE Mini (Fuji Electric) - Beeteco.comBeeteco
Catalog Biến tần Frenic ACE Mini
Beeteco.com là trang mua sắm trực tuyến thiết bị điện - Tự động hóa uy tín tại Việt Nam.
Chuyên cung cấp các thiết bị: Đèn báo nút nhấn, Relay, Timer, Contactor, MCCB ELCB, Biến tần, Van, Thiết bị cảm biến, phụ kiện tủ điện, .... Từ các thương hiệu hàng đầu trên thế giới.
www.beeteco.com @ Công ty TNHH TM KT ASTER
Số 7 Đại Lộ Độc Lập, KCN Sóng Thần 1, P. Dĩ An, Tx. Dĩ An, Bình Dương
www.facebook.com/beeteco
Tel: 0650 3617 012
DĐ: 0904 676 925
RUGGED MONITORING’s R501 is the most versatile and advanced multi-channel monitoring solution. Designed to seamlessly integrate into diverse industries, the R501 stands as a testament to our commitment to innovation and reliability in electrical asset monitoring.
Fuji tu dong hoa catalog frenic-multi-dienhathe.orgDien Ha The
Khoa Học - Kỹ Thuật & Giải Trí: http://phongvan.org
Tài Liệu Khoa Học Kỹ Thuật: http://tailieukythuat.info
Thiết bị Điện Công Nghiệp - Điện Hạ Thế: http://dienhathe.vn
EL-FLOW Prestige is the next generation of Bronkhorst Mass Flow Meters / Controllers for gases. Nearly all core components have been redesigned and many improvements and innovations have been incorporated. With this new series Bronkhorst introduced the “Differential Temperature Balancing” technology, ensuring a superb sensor stability.
Durable, efficient and easy to operate, we've worked together very closely with our rental fleet customers to develop the new FG Wilson PRO range of rental generator sets.
Siemens ,
Catalog Thiết Bị Điện Siemens , Catalog Thiết Tự Động
Catalog Phụ Kiện Siemens , Catalog Phụ Kiện,
Catalog Siemens , Catalog,
https://www.dienhathe.com,
Chi tiết các sản phẩm khác của Siemens tại https://dienhathe.com
Xem thêm các Catalog khác của Siemens tại https://dienhathe.info
Để nhận báo giá sản phẩm Siemens vui lòng gọi: 0907.764.966
Similar to Damper Drive Actuator With Fieldbus Communications (20)
PID is short for "proportional plus integral and derivative control", the three actions used in managing a control loop. Process loop controllers use one, two or all three of these to optimally control the process system. PID control is used in a wide variety of applications in industrial control and process system management.
Courtesy of Eurotherm. Eurotherm offers a wide range of single & multi-loop PID controllers.
Smokeless Flares
Smokeless flares incinerate flammable hazardous vent gas with the assistance of supplemental high-velocity air or steam to prevent the formation of soot or smoke. Excessive injection of air or steam reduces combustion efficiency, resulting in the release of hazardous VOC gases. Meanwhile, inadequate injection of air or steam results in the formation of undesirable soot and smoke. Although modern flares are designed for high flow rates associated with an emergency condition, they most commonly operate at high-turn-down, low-flow rates, making it challenging for the flare to operate at optimal combustion efficiency.
Pilot Monitor
Flammable vent gases are ignited by a pilot flame when released into the atmosphere by refineries, natural gas processing plants, and petrochemical plants. The proper incineration of these gases is a critical safety and environmental concern. Therefore, it is essential to confirm that the pilot is lit at all times. Monitoring via a thermocouple is common, however, failures frequently occur and replacements can require costly process shutdowns. Remote sensing IR technology (PM) is the superior alternative.
Flame Intensity Monitors
Williamson Flame Intensity Monitors (FI) are the single-wavelength sensors of choice for a variety of flare applications where the more sophisticated dual-wavelength flare products are not appropriate or are not required.
Some materials can be difficult or near impossible to measure with precision using single-wavelength or ratio pyrometers because of their complex emissivity characteristics. These types of materials are called non-greybody materials and their emissivity varies with wavelength.
Multi-wavelength pyrometers use application specific algorithms to characterize infrared energy and emissivity across the measured wavelengths to accurately calculate both the actual temperature and emissivity of these complex non-greybody materials.
The 3000 series gives you high accuracy, fast response time and low temperature drift – without compromise. All 6 mm devices can be mounted on a standard DIN rail or power rail with no air gap separation.
Bronkhorst has over 35 years experience in designing and manufacturing precise and reliable measurement and control equipment and the widest range of mass flow and pressure meters and controllers available on the market.
Bronkhorst offers innovative solutions for many different applications across a great many different markets, and has a particular strong wealth of knowledge and reputation within the plastics and rubber market.
The Coriolis measuring principle refers to the effect that a moving mass has on a body in a rotating frame of reference. The moving mass exerts an apparent force on the body, causing a deformation. This force is called the Coriolis force. It does not act directly on the body, but on the motion of the body. This principle is used in Coriolis flowmeters.
AP Tech is a manufacturer of gas handling components – primarily pressure regulators and valves. AP Tech’s competitive advantage are products that deliver specialty gases for high purity through ultra high purity applications. Starting from the source vessel to point of use and into the process tool or equipment itself, AP Tech products are known to deliver gases with uncompromising quality, performance and reliability.
The L100 Bubble-Tube Level System is a fully self contained instrument, requiring only connections to air or gas supply, dip tube and electrical power source to provide precise level indication. Because only the stationary dip tube and the purge gas come in contact with the liquid, this system is ideal for applications involving hazardous locations or liquids which are highly corrosive, viscous, hot, (molten metal), explosive, slurry type or foodstuff.
For applications where rapid transition from open to closed positions is warranted, the Mark 76 is a solid choice. Designed with a short stroke and straight through fluid path, the Mark 76 also incorporates other features to assure good service for process operations using on/off control.
Tek-Trol provides process measurement and control products for Flow, Level, Temperature and Pressure measurement and Control Valves and Analyzers systems for the Process, Power and Oil and Gas Industries.
Each ReFlexIO unit allows you to connect (2) Analog Inputs and (2) Digital Inputs which are wirelessly transferred to (2) Analog Outputs and (2) Digital Outputs on the other end. The 2 ReFlexIO 'paired' units work bi-directionally, so it's possible, for example, to turn on a relay (digital input to digital output on the other end) and get a signal back (digital input to sense replay closure returned to digital output on the original sending unit) to turn on a light telling you that the relay is indeed on.
The T2750 PAC hardware provides high-performance control with cost-effective redundancy options in a versatile modular system. Powerful instruments, the control units, and the I/O system form the basis of a complete distributed control and recording environment. This environment is capable of continuous analog, logic, sequential control, batch management, secure data recording at point of measurement, and setpoint programming.
The T2550 PAC is a high performance solution offering extremely cost effective redundancy options - making high availability viable for more of your process.
The control unit and I/O system form the basis of a complete distributed control and recording environment capable of continuous analog, logic and sequential control combined with secure data recording at point of measurement - all designed to maximize Return on Investment (ROI) from your process.
ControlAir Inc. is a leading manufacturer of precision air pressure regulators, I/P transducers, E/P transducers, P/I transducers, valve positioners, air relays, volume boosters, air filter regulators and frictionless diaphragm air cylinders.
The LowFlow JRDL Series line of diaphragm sensed, high pressure regulators have the ability to handle very high pressures and very low flows. These valves are typically used in research and sampling systems for general, corrosive and specialty gas and liquid service. Typical applications include gas chromatography and flame ionization detectors, as well as other industrial controls.
The Model TCL measures total chlorine in water, and is ideal for seawater chlorine analysis applications. The system consists of a sample conditioning unit, a sensor, and transmitter
Advanced Cooling Technologies, manufacturer of specialized heat transfer equipment including heat pipes and industrial enclosure coolers, collaborated with a local children's science museum to produce a hands on learning exhibit. The exhibit illustrates principals of heat transfer.
The Mark 86 Ambient Temperature Regulator is designed to control steam-tracing lines based on ambient temperatures. Steam tracing lines are commonly used to protect outdoor instrumentation, pipelines, and tanks from freezing. The Mark 86 allows steam to flow through the tracer lines only when it is needed and remains closed when the ambient temperature rises above a predetermined set point.
For efficient control of combustion and drying processes
Simultaneous or as individual measurement: the GM35 gas analyzer measures CO2, H2O and CO, or N2O, as well temperature and pressure – and it does this reliably, quickly, and economically. As an in-situ gas analyzer, the GM35 detects these gas components directly in the gas stream without gas sampling. Reliability, precision, and short response time of the GM35 offer a key advantage for efficient control loops in all CO and CO2-generating processes.
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)MdTanvirMahtab2
This presentation is about the working procedure of Shahjalal Fertilizer Company Limited (SFCL). A Govt. owned Company of Bangladesh Chemical Industries Corporation under Ministry of Industries.
Using recycled concrete aggregates (RCA) for pavements is crucial to achieving sustainability. Implementing RCA for new pavement can minimize carbon footprint, conserve natural resources, reduce harmful emissions, and lower life cycle costs. Compared to natural aggregate (NA), RCA pavement has fewer comprehensive studies and sustainability assessments.
HEAP SORT ILLUSTRATED WITH HEAPIFY, BUILD HEAP FOR DYNAMIC ARRAYS.
Heap sort is a comparison-based sorting technique based on Binary Heap data structure. It is similar to the selection sort where we first find the minimum element and place the minimum element at the beginning. Repeat the same process for the remaining elements.
Welcome to WIPAC Monthly the magazine brought to you by the LinkedIn Group Water Industry Process Automation & Control.
In this month's edition, along with this month's industry news to celebrate the 13 years since the group was created we have articles including
A case study of the used of Advanced Process Control at the Wastewater Treatment works at Lleida in Spain
A look back on an article on smart wastewater networks in order to see how the industry has measured up in the interim around the adoption of Digital Transformation in the Water Industry.
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdffxintegritypublishin
Advancements in technology unveil a myriad of electrical and electronic breakthroughs geared towards efficiently harnessing limited resources to meet human energy demands. The optimization of hybrid solar PV panels and pumped hydro energy supply systems plays a pivotal role in utilizing natural resources effectively. This initiative not only benefits humanity but also fosters environmental sustainability. The study investigated the design optimization of these hybrid systems, focusing on understanding solar radiation patterns, identifying geographical influences on solar radiation, formulating a mathematical model for system optimization, and determining the optimal configuration of PV panels and pumped hydro storage. Through a comparative analysis approach and eight weeks of data collection, the study addressed key research questions related to solar radiation patterns and optimal system design. The findings highlighted regions with heightened solar radiation levels, showcasing substantial potential for power generation and emphasizing the system's efficiency. Optimizing system design significantly boosted power generation, promoted renewable energy utilization, and enhanced energy storage capacity. The study underscored the benefits of optimizing hybrid solar PV panels and pumped hydro energy supply systems for sustainable energy usage. Optimizing the design of solar PV panels and pumped hydro energy supply systems as examined across diverse climatic conditions in a developing country, not only enhances power generation but also improves the integration of renewable energy sources and boosts energy storage capacities, particularly beneficial for less economically prosperous regions. Additionally, the study provides valuable insights for advancing energy research in economically viable areas. Recommendations included conducting site-specific assessments, utilizing advanced modeling tools, implementing regular maintenance protocols, and enhancing communication among system components.
Forklift Classes Overview by Intella PartsIntella Parts
Discover the different forklift classes and their specific applications. Learn how to choose the right forklift for your needs to ensure safety, efficiency, and compliance in your operations.
For more technical information, visit our website https://intellaparts.com
6th International Conference on Machine Learning & Applications (CMLA 2024)ClaraZara1
6th International Conference on Machine Learning & Applications (CMLA 2024) will provide an excellent international forum for sharing knowledge and results in theory, methodology and applications of on Machine Learning & Applications.
6th International Conference on Machine Learning & Applications (CMLA 2024)
Damper Drive Actuator With Fieldbus Communications
1. Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Fan/Damper Actuators with Optional
FoundationTM fieldbus Communications
n Combines the power and reliability of the
Hagan Pneumatic Drive with the accuracy and
features of the Fisher DVC5000/6000 Digital
Valve Controller
n Integral I/P: FOUNDATION™ fieldbus input or
4-20mA HART® input
n Reliable, closed loop positioning
n Double acting piston – no vanes
n Optional “fail-in-place” upon loss of plant air
n Manual operator
n ValveLink Diagnostics/AMS
n Suitable for hazardous area service;
explosion-proof, flameproof or intrinsically safe
Product description
Hagan Pneumatic Power Positioners have defined the standard
of excellence in fan and damper actuation for more than 70
years.
These actuators convert the linear motion from a pneumatic
piston into an 80° rotation of a drive arm. With few moving
parts, the pneumatic power positioner remains the simplest,
most reliable and most cost-effective method of actuation.
Torque ranges are offered from 400 ft-lbs to 4,600 ft.-lbs.
The PowerVUE design uses the same rugged Hagan actua-
tor and frame construction, combined with the accuracy and
reliability of the Fisher FieldVUE DVC5000/6000 Digital Valve
Controller.
The DVC5000 controller, using the HART or FOUNDATION
fieldbus communications protocols, gives easy access to
information that is critical to process operation.
The controller uses feedback from the actuator travel position
to diagnose not only the instrument, but the actuator as well.
The information from the DVC5000/6000 can be integrated
into control systems or be received for a single loop.
These instruments use two-wire loop power for low-cost
replacement of existing instruments. The two-wire design
avoids cost of separate power and signal wiring.
Self-diagnostic capabilities allow you to check fan/damper
actuator performance in place. You can compare the present
signature (load, friction, etc.) against stored signatures to
discover performance changes before they cause problems.
Field maintenance of these instruments is easy. Repair consists
of quick replacement of a single master module without
disconnecting wires or tubing. Troubleshooting of the master
module is fast and easy in the instrument shop.
Applications
Fan/Damper actuation for:
n Utilities
n Steel mills
n Refineries
n Pulp and paper
n Wastewater (aeration blowers)
Hile Controls of Alabama, Inc.
800-536-0269
www.hilealabama.com
2. 2 www.EmersonProcess.com
Theory of operation
Traditional positioners use a mechanical force/balance concept,
whereby a pneumatic input signal forces a diaphragm down,
actuating a valve which ports air into one side of a piston and
vents the other side. A feedback spring provides a
counterbalancing force as the actuator approaches setpoint.
Mechanical positioners have worked well for many years, but
are subject to sticking as mechanical components become
soiled, resulting in a situation where the actuator “hunts” for
the proper position. The process variable is always above or
below setpoint, providing poor control that costs significant
money and causes excessive wear on the actuator/linkage/
dampers system.
The FieldVUE DVC5000/6000 Digital Valve Controller directly
receives a 4-20 mA or fieldbus input signal. An independent
feedback transducer provides an actuator position input,
ensuring that the PowerVUE drive always moves to the setpoint
demanded by the control system. Fieldbus versions of the
DVC5000/6000 also offer PID loop control capability.
Options
Air Lock - mechanically locks the drive in place upon the loss of
plant air.
Manual Operator - handwheel/lever arm permits manual
adjustment of drive.
Limit Switches - proof of position for purge/lightoff conditions
may be accomplished by traditional mechanical microswitches.
Electric Position Transmitter - provides a 4-20 mA feedback
signal representing actuator position. (HART versions only.)
Digital communications
4-20mA HART versions:
All operator information for setup and diagnostics is transmit-
ted digitally via HART communications. A Rosemount 375
Hand-held or similar communicator may be used or a laptop
computer with ValveLink Software. Emerson’s AMS offers the
ValveLink software as an optional “snap-on” application.
Instruments may be accessed individually or multiplexed
through an “interchange” unit, providing continuous access to
any number of Emerson’s instruments.
FOUNDATION fieldbus versions:
All operator interface is via the host computer console.
A hand-held device is available.
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Valvelink advanced
diagnostics
In addition to the standard features, advanced diagnos-
tic features provide additional capabilities to diagnose
problems with the DVC5000, the actuator, and even in
the damper/ linkage systems. Actuator can be tested
as it is put into service, and this data compared to an “as
found” condition after years in service. Maintenance
can be scheduled based upon actual need vs. traditional
“time in service” criteria.
3. 3www.EmersonProcess.com
Performance Curves
Set of characteristic curves for a typical air-operated power
cylinder. Piston displacement and time are plotted for suddenly
applied full-range positioning inputs to the cylinder. The linear
sections of the curves correspond to steady speed.
Note: Stall torques are specified for all models. Emerson recommends that a 60% factor be applied to ensure fast control response.
Rosemount Analytical power positioners are not recommended for reversing loads or heavy mass loads.
A typical cylinder-thrust vs. speed characteristic. The curve of
relative horsepower output is also shown.
Typical
arrangement
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
4. 4 www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Features
n Digitally-controlled positioner system with HART® or
FOUNDATION™ fieldbus communications
n Repeatability better than ±0.5%
n Direct 4-20 mA signal input – integral I/P
n Characterizable
n Reverse or direct acting
n Standard rotation – counterclockwise
Accessories
Clevis and pin are included P/N 174469
Air filter/regulator included P/N 4505C21G03
Options
n Mechanical air lock upon loss of plant air supply
n 4-20 mA position feedback signal – 4-20 mA
HART versions only
n Manual lock
n Limit switches
n Minimum limit stop
4 X 5 torque type floor mounted
features, accessories and options
5. 5www.EmersonProcess.com
Specifications1
Actuator
Repeatability
±0.5% of full stroke or better
No load full stroke time
3 sec.
Stall torque
400 ft.-lbs. (542 N•m) with 100 psig (689 kPa gage) air supply
Maximum friction load
50% of control torque.
Maximum weight load
140 ft.-lbs. (189 N•m)
Maximum allowable cylinder air pressure
100 psig (689 kPa gage)
Power air consumption
10 scfm steady state.
Stroke length
5 in. (127 mm), 80° rotation.
Physical characteristics
Weight
80 lbs. (36 kg) typical
Air supply and signal air input fittings
1/4 inch NPT female connections
Environmental requirements actuator
Ambient temperature
Without heater:
40° to 122°F (4,44° to 50°C), 140°F
(60°C) with increased maintenance
With heater
-10° to 122°F (-23,3° to 50°C) 140°F (60°C) with increased
maintenance
4 X 5 torque type floor mounted
specifications1
Relative humidity
Operable up to 100% RH
Electronics
See DVC5000/6000 specifications
Pneumatic
Operating air supply pressure
45 to 100 psig (310 to 689 kPa gage)
Recommended air supply pressure
100 psig (689 kPa gage)
Electrical Optional heater power consumption
150 watts
Signal requirements
Control signal inputs
4-20 mA signal with HART® or FOUNDATION™ fieldbus
1
Specifications are subject to change without notification. Our policy is
one of continuous improvement, and we reserve the right to change
specifications.
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
6. 6 www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Model Product Description
PVD 405 PowerVUE Drive – 4 x 5 Torque Type Floor Mount
Basic Assembly Type and Connection Material
01 Standard brass assembly
02 Manual lock brass assemblyProbe Length
03 Mechanical air lock brass assembly
04 Standard stainless assembly
05 Manual lock stainless assembly
06 Mechanical air lock stainless assembly
Digital Valve Controller
00 None
01 HART®
02 Fieldbus with basic control suite
03 Fieldbus without basic control suite
04 Other DVC style selected
Limit Switches
01 None
02 2 Std. limit switch – SPDT
EPT
01 None
02 Digital EPT and 2 limit contacts (HART®
versions only)
Heater Option
01 None
02 Heater/thermostat 115V 150 watt (not for use in hazardous areas)
Option Notes
General Notes PowerVUE Drive – 4 x 5 Torque Type Floor Mount
43/95 kg/lb shipping weight
Base price includes air filter-regulator. Style 4505C21G03, clevis style 174469 and IB-102-204
Level 2 Option: 00
Digital Valve Controller (DVC 5000/6000) may be supplied by others but no performance guarantees for
accuracy or speed of responses are provided. Warranty for DVC 5000/6000 will be the responsibility o
the provider
Level 2 Option: 02, 03
DVC 5000 Options: flameproof cable gland: 1/2” NPT (aluminum), EExd IIC; cable entry adaptor (brass):
1/2” NPT M20 x 1.5 ISO, 1/2” NPT, PG 13.5
Level 2 Option: 03
Order as separate line item from addendum price list
Level 2 Option: 03
Standard arrangement calls for Model DVC 5020F-216, certified to FM as intrinsically safe and Division II.
Other certifications available. Advanced diagnostics provided.
Level 2 Option: 01
Standard arrangement calls for Model DVC 5020-116G60, certified to FM as intrinsically safe and
Division II. Other certifications available. Advanced diagnostics provided
Level 2 Option: 02
Standard arrangement calls for Model DVC 5020F-216, certified to FM as intrinsically safe and Division II.
Other certifications available. Advanced diagnostics provided
Level 4 Option: 02
Utilizes Moore Industries Site Programmable HART Alarm. Default configuration: 1 analog output
representing actuator travel; 3 customer selectable position contacts; 1 contact for field device failure
Moore HART SPA may be configured in an intrinsically safe arrangement through an IS barrier..
Accessories
1101588-002ENG Tag SS (engraved)
Ordering information
PVD 405 PowerVUE Drive – 4 x 5 Torque Type Floor Mount
7. 7www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Features
n Digitally-controlled positioner system with HART® or
FOUNDATION™ fieldbus communications
n Repeatability better than ±0.5%
n Direct 4-20 mA signal input – integral I/P
n Characterizable
n Reverse or direct acting
n Standard rotation – counterclockwise
Accessories
Clevis and pin are included P/N 274472
Air filter/regulator included P/N 274472
Options
n Mechanical air lock upon loss of plant air supply
n 4-20 mA position feedback signal – 4-20 mA
HART versions only
n Heater and thermostat
n Limit switches
n Manual operator
6 X 10 torque type floor mounted
features, accessories and options
Dimensions in inches with
millimeters in parentheses.
Drawings are for reference purposes only and Emerson does
not warrant the accuracy of the dimensions herein.
8. 8 www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Model Product Description
PVD 610 PowerVUE Drive – 6 x 10 Torque Type Floor Mount
Assembly Type & Connection Material
01 Manual lock, brass fittings, polymer tubing assembly
02 Manual and mechanical air lock, brass fittings, polymer tubing assemblyProbe Length
03 Manual lock, SS fittings, SS tubing assembly
04 Manual lock and mechanical air lock, SS fittings, SS tubing assembly
DVC 6000 Controller Style
00 None required
01 HART®
02 Fieldbus with basic control suite
03 Fieldbus without basic control suite
04 Other DVC style selected
Limit Switches and Position Retransmission
01 No limit switches
02 2 mechanical limit switches SPDT
03 Digital electronic position transmitter & 2 limit contacts, HART®
version only
Heater
01 None
02 Heater/Therostat 115 VAC 150 watt (not for use in hazardous area)
Option Notes
General Notes PowerVue Drive – 6 x 10 Torque Type Floor Mount
125/275 kg/lb shipping weight
Base price includes air filter-regulator. Style 4505C21G03, clevis style 174469 and IB-102-204
Level 2 Option: 04
Designate other DVC 6000 model number as a note on order.
Level 2 Option: 00
Digital Valve Controller (DVC 6000) may be supplied by others but no performance guarantees for accuracy or
speed of responses are provided. Warranty for DVC 6000 will be the responsibility of the provider.
Level 2 Option: 02, 03
DVC 6000 Options: flameproof cable gland: 1/2” NPT (aluminum), EExd IIC; cable entry adaptor (brass): 1/2” NPT
M20 x 1.5 ISO, 1/2” NPT, PG 13.5
Level 2 Option: 03
order as separate line item from addendum price list.
Level 2 Option: 02
Standard arrangement calls for Model FSDVC6020F-105/G160B/CSA, certified to CSA as intrinsically safe and
Division II. Other certifications available. Advanced diagnostics provided.
Level 2 Option: 01
Standard arrangement calls for Model FSDVC6030F-107/G160B/CSA, certified to CSA as intrinsically safe and
Division II. Other certifications available. HC HART communications. Advanced Diagnostics option available for
additional price.
Accessories
1101588-002ENG Tag SS (engraved)
Ordering information
PVD 610 PowerVUE Drive – 6 x 10 Torque Type Floor Mount
9. 9www.EmersonProcess.com
Model Product Description
PVD814 PowerVUE Drive – 8 x 14 Torque Type Floor Mount
Assembly Type & Connection Material
01 Standard brass assembly
02 Standard stainless assembly
03 Mechanical air lock brass assembly
04 Mechanical air lock stainless assembly
Digital Valve Controller
00 None
01 HART®
02 Fieldbus with basic control suite
03 Fieldbus without basic control suite
04 Other DVC style selected
Limit Switches
01 None
02 2 Std. limit switch – SPDT
Electronic Position Transmitter
01 None
02 Digital electronic position transmitter & 2 limit contacts (HART®
versions only)
Heater Optionr
01 None
02 Heater/thermostat 115VAC 150 watt (not for use in hazardous areas)
Option Notes
General Notes PowerVue Drive – 8 x 14 Torque Type Floor Mount
249/550 kg/lb shipping weight
Base price includes air filter-regulator. Style 4505C21G03, clevis style 174469 and IB-102-204
Level 2 Option: 04
Designate other DVC 5000 model number as a note on order.
Level 2 Option: 00
Digital Valve Controller (DVC 5000/6000) may be supplied by others but no performance guarantees
for accuracy or speed of responses are provided. Warranty for DVC 5000/6000 will be the responsibility of the provider.
Level 2 Option: 02, 03
DVC 5000 Options: flameproof cable gland: 1/2” NPT (aluminum), EExd IIC; cable entry adaptor (brass): 1/2” NPT
M20 x 1.5 ISO, 1/2” NPT, PG 13.5
Level 2 Option: 03
order as separate line item from addendum price list.
Level 2 Option: 01
Standard arrangement calls for Model DVC5020-116G60, certified to FM as intrinsically safe and Division II.
Other certifications available. Advanced diagnostics provided.
Level 2 Option: 02
Standard arrangement calls for Model DVC5020F-216, certified to FM as intrinsically safe and Division II. Other
certifications available. HC HART communications. Advanced diagnostics provided.
Level 4 Option: 02
Utilizes Moore Industries Site Programmable HART Alarm. Default configuration: 1 analog output representing
actuator travel; 3 customer selectable position contacts; 1 contact for field device failure. Moore HART SPA may
be configured in an intrinsically safe arrangement through an IS barrier.
DVC 5000 Options: flameproof cable gland: 1/2” NPT (aluminum), EExd IIC; cable entry adaptor (brass): 1/2” NPT
M20 x 1.5 ISO, 1/2” NPT, PG 13.5
Accessories
1101588-002ENG Tag SS (engraved)
Ordering information
PVD814 PowerVUE Drive – 8 x 14 Torque Type Floor Mount
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
10. 10 www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
DVC6000 series
Specifications1
Available configurations
DVC6010
Sliding stem applications
DVC6020
Rotary applications and long-stroke sliding-stem applications
DVC6030
Quarter-turn rotary applications
Input signal1
Analog Input Signal
4-20 mA dc, nominal; split ranging available
Minimum Voltage Available at Instrument Terminals
11 VDC for analog control (see instrument instruction manual
for details)
Minimum Control Current
4.0 mA
Minimum Current without Microprocessor Restart
3.5 mA
Maximum Voltage
30 VDC
Overcurrent Protection
Input circuitry limits current to prevent internal damage
Reverse Polarity Protection
No damage occurs from reversal of loop output
Output signal1
Ranges
Pneumatic signal as required by the actuator, up to 95% of
supply pressure
Minimum Span
6 psig (0.4 bar)
Maximum Span
140 psig (9.5 bar)
Action
Double, single direct, and single reverse
Supply pressure
Minimum and Recommended
5 psig (0.3 bar) higher than maximum actuator requirements
Maximum
150 psig (10.2 bar) or maximum pressure rating of the
actuator, whichever is lower
Steady-state air consumption1 2 3
At 20 psig (1.4 bar) supply pressure
Less than 11 scfh (0.3 normal m3/hr.)
At 100 psig (6.9 bar) supply pressure
Less than 45 scfh (1.2 normal m3/hr.)
Xi Temp. limits as measured inside the electronics housing
-20° to 70°C (-4° to 158°F)
Maximum output capacity2 3
At 20 psig (1.4 bar) supply pressure
465 scfh (12.5 normal m3/hr.)
At 100 psig (6.9 bar) supply pressure
1570 scfh (42.1 normal m3/hr.)
Independent linearity1
±0.5% of output span
Electrical classification
Hazardous Area
FM, CSA, CENELEC
Other approvals are pending from certifying agencies
Electrical Housing
Designed to meet NEMA 4X, IEC 529 IP 65
Connections
Supply Pressure
1/4-inch NPT female and integral pad for mounting
67 CFR regulator
Output Pressure
1/4-inch NPT female
Tubing
3/8-inch metal, recommended
Vent (pipe-away)
1/4-inch NPT female
Electrical
1/2-inch NPT female conduit connection,
M20 adaptor optional
11. 11www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
DVC6000 series
Specifications1
continued
Operating ambient temperature limits
(standard)
-40° to 85°C (-40° to 185°F)
Construction materials
Housing, module base and terminal box
ANSI B360.0 low copper aluminum alloy
Cover
Valox
Elastomers
Nitrile (standard), or Fluorelastomer (optional)
Stem travel
DVC6010
0 to 102 mm (8-1/8 inches) maximum
0 to 19 mm (3/4 inches) minimum
DVC6020
0 to 22 inches
Shaft rotation (DVC6020 and
DVC6030)
0 to 90 degrees maximum.
Mounting
Designed for direct actuator mounting. For weatherproof
housing capability, the instrument must be mounted upright to
allow the vent to drain.
Weight
3.5 kg (7.7 lbs.)
Options
Supply and output pressure gauges or tire valves
Integrally mounted filter regulator
1
These terms are defined in ISA Standard S51.1-1979
2
Normal m3/hr. – Normal cubic meters per hour at 0°C and 1.01325 bar, absolute; Scfh-Standard cubic feet per hour at 80°F and 14.7 psia
3
Values at 1.4 bar (20 psig) based on a single-acting relay; values at 6.8 bar (100 psig) based on double-acting relay.
Emerson Process Management has satisfied all obligations coming from the European legislation to harmonize the product requirements in Europe.
The PowerVUE actuator is a subcomponent of an actuating system, including user-provided items such as linkages, bearings, and dampers. The user
must ensure that the entire actuating system is in conformity with the provisions of the European Machinery Directive EC Machinery Directive
89/392/EEC, as amended by directive 91/368/EEC and Directive 93/44/EEC.
12. 12 www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Step #1 – remove existing positioning system
Step #2 – install PowerVue DVC5000
components
PowerVue field retrofit kits
for existing hagan power
positioners
Description
An existing Hagan torque-type power positioner can be
retrofitted with the PowerVUE system in a few hours.
The PowerVUE system eliminates most maintenance
requirements associated with mechanical “force balance”
positioning systems, based on pilot valves.
The Hagan PowerVUE retrofit package includes all mounting
brackets, hardware, and pneumatic tubing needed to upgrade
an existing Hagan Pneumatic Power Positioner. No drilling or
tapping of holes is required. (The positioning system mounts
directly to the frame, eliminating the need for connecting
linkages.)
Note: Retrofit kits are not offered for the Hagan
thrust-type units, or the Econotorque Models.
Features
n Digitally-controlled positioner system
n Factory designed mounting
n Direct 4-20 mA signal input – integral I/P
n Characterizable
n Air lock upon loss of plant air supply
n Reverse or direct acting
n ValveLink diagnostics
Options
n 4-20 mA position feedback signal
n 2 position limit contacts available
Field Retrofit Kits are available for the 4 x 5 and 8 x 14
torque-type models:
PP405TR 4” x 5” Cylinder
452167 8” x 14” Cylinder
457696 8” x 14” Cylinder
452593 8” x 14” Cylinder
443700 8” x 14” Cylinder
457031 8” x 14” Cylinder
Ease of retrofit
(4 x 5 Unit Pictured)
13. 13www.EmersonProcess.com
Product Data Sheet
PDS 102-222.A01
PowerVUE™
November 2011
Model Product Description
PVD 468R PowerVUE Drive – Retrofit Kit 4x5 or 8x14
Model
00 4x5
01 8x14
03 6x10
Digital Valve Controller
00 None required
01 HART®
02 FieldBus with basic control suite
03 FieldBus without basic control suite
04 Other DVC style selected, see addendum
Electronic Position Transmitter
00 None required
01 Digital electronic position transmitter & 2 limit contacts, HART® version only (4)
Option Notes
General Notes PowerVue Drive – Retrofit Kit 4x5 or 8x14
“Base price includes air filter/regular style: 4505C21G03; clevis style: 174469
Instruction manual IB 102-204.
“Performance specifications may vary from the published specifications, depending
on the age of the existing Hagan fan/damper actuator and the quality of the DVC
5000/6000 installation. Setup and calibration of DVC 5000 is responsibility of
others. Fairchild reversing relay is included with or without selection of DVC 5000.”
Level 1 Option: 02
Some drilling and tapping required. Existing covers may be modified in the field or a
precut back cover can be selected, P/N 4851B28G01.
Level 2 Option: 04
Designate other DVC 5020/6020 model number as a note on order.
Level 2 Option: 00
Digital Valve Control (DVC 5000/6000) may be supplied by others, but no
performance guarantees for accuracy or speed of response are provided.
Warranty for DVC 5000/6000 will be the responsibility of the provider. Tubing is
provided, but is not precut or preformed.
Level 2 Option: 02, 03
DVC 5000 Options: flameproof cable gland: 1/2” NPT (aluminum), EExd IIC, cable
entry adaptor (brass): 1/2” NPT M20 x 1.5 ISO, 1/2” NPT, PG 13.5.
Level 2 Option: 03
Order as separate line item from addendum price list.
Level 2 Option: 01
Standard arrangement calls for Model DVC5020-116G60, certified to FM as intrinsically safe,
and Division II. Other certifications available. Advanced diagnostics provided.
Level 2 Option: 02
Standard arrangement calls for model DVC5020F-216, certified to FM as intrinsically safe,
and Division II. Other certifications available. Advanced diagnostics provided.
Option Notes
1101588-002ENG Tag SS (engraved)
Ordering information
PVD 468R PowerVUE Drive – Retrofit Kit 4x5 or 8x14