Yokogawa manufactures several variants of sanitary pressure transmitters for industrial applications in food, pharma, and other industries. Leading edge measurement technology.
2.
GS 530SCBS-01E January 1, 2017-00
This product is only available in North America.
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the
lower and upper range limits of the capsule.
Integral Display (LCD Display)
5-digit numerical display, 6-digit unit display and bar
graph. The display is configurable to display one or up
to three of the following variable: pressure in %,
scaled pressure, measured pressure.
Local Parameter Setting
Parameter configuration without a HHC offers quick
and easy setup of parameters. Parameters that can
be set include Tag Number, Unit of Measure, LRV,
URV, Damping, Output Mode, Display, and Re-range
by applying actual pressure (LRV and URV).
Response Time (All Capsules)
100 msec
When software damping is set to zero and includes
dead time of 45 msec (nominal)
Self-Diagnostics
CPU failure, hardware failure, configuration error,
process alarm for pressure or capsule temperature.
User-configurable process high/low alarm for
pressure also available.
Signal Characterizer
User-configurable 10-segment signal characterizer for
the 4 to 20 mA output.
HART PROTOCOL DIGITAL OUPUT
Two wire 4 to 20 mA DC with digital communications,
HART FSK protocol superimposed on the 4 to 20 mA
signal.
FEATURES
• Remote Ranging and Monitoring Functions
Ranges can be remotely set and monitored through
HART communication.
• On-line Communication
Analog signal output and HART digital communication
do not interfere with one another making on-line
communication possible.
• Enhanced Burst Mode and Event Notification
(HART 7)
Advanced burst mode includes the variety of
transmission settings by specifying burst variables,
update period, and message trigger mode. Event
notification function gives you an alert signal based on
the status change in preset values and self-
diagnostics.
• Long Tag Supporting Up to 32 Characters
(HART 7)
Long tag secures better asset management with
abundant digits available for device tag numbers.
• Self-Diagnostics
Pressure input outside the range limit, excessive
ambient temperature, incorrect span setting etc. can
be diagnosed through HART communication.
• HART Protocol Revision Selectable
HART protocol revision can be selected from HART 5
or HART 7 when ordering. The protocol revision can
be changed in the field by the user.
2
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
3.
GS 530SCBS-01E January 1, 2017-00
This product is only available in North America.
□NORMAL OPERATING CONDITIONS
(Optional features option codes may affect
limits)
Ambient Temperature Limits
-40⁰F to +185⁰F
-22⁰F to +176⁰F (with Integral Display)
Process Temperature Limits
-40⁰F to +248⁰F
Ambient Humidity Limits
0 to 100% RH
Maximum over Pressure
Supply & Load Requirements
(Output Signal code D and J. Optional features
may affect electrical requirements)
With 24 V DC supply, up to 550Ω load can be used.
See graph below.
Figure1. Relationship between power supply
Voltage and external load resistance.
(Output signal code J)
Supply Voltage
For 4 to 20 mA HART Protocol
10.5 to 42 VDC for general use and flameproof type.
10.5 to 32 VDC for Lightning Protector (option code
code /A).
10.5 to 30 VDC for intrinsically safe, type n, non-
incendive or non-sparking type.
Minimum voltage limited at 16.6 VDC for
communication.
Load for 4 to 20 mA HART Protocol
0 to 1290 Ω for operation
250 to 600 Ω for digital communication
Communication Requirements
Load Capacitance
0.22µF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10kΩ or more at 2.4 kHz
EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in industrial
locations)
EN61326-2-3
Safety Requirement Standard
EN61010-1, EN61010-2-030
Altitude of installation site: Max 2,000 meters
above sea level.
Installation category: I (Anticipation transient
overvoltage 330 V)
Pollution degree: 2
Indoor / Outdoor use
3
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
4.
GS 530SCBS-01E January 1, 2017-00
This product is only available in North America.
□PHYSICAL SPECIFICATIONS
Wetted Parts Materials
All wetted parts material is 316 Stainless Steel
Non-wetted Parts Material
Amplifier Housing
Amplifier Housing code 1: Low copper cast
aluminum alloy with polyurethane, deep sea moss
green paint (Munsell 0.6GY3.1/2.0)
Code /X2: Upgraded painting process to increase
corrosion resistance in sanitary applications.
(Available on Amplifier Housing code 1)
Atmospheric Reference Pipe
Polypropylene
Cover O-rings
Buna-N
Name plate and tag
316 Stainless Steel
Fill Fluid
DC200 Silicone and Neobee M20
Degrees of Protection
NEMA 4x (IP66/IP67); IP69K
Weight
Amplifier Housing code 1: 3.2 lbs.
Note: Transmitter only, weight does not include
mounting bracket (If supplied).
Clean in Place (CIP) / Sanitize in Place (SIP)
The EJA530E (Gauge) Sanitary Pressure
Transmitters feature a 3A compliant sanitary Cherry
Burrell ‘I’ Line process connection with an upper
process temperature limit of 400⁰F.
< Related Instruments>
YHC5150X HART Communicator:
GS 01R01A30-01EN-A
FieldMate Device Management:
GS 01R01A01-01E
<Reference>
4
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
5.
This product is only available in North America.
GS 530SCBS-01E January 1, 2017-00
▪ MODEL AND SUFFIX CODES
The “>” mark indicates the most typical selection for each specification.
▪ OPTIONAL SPECIFICATIONS
*1: Lower limit of ambient temperature: -15°C (+5°F).
*2: Indicates the unit of MWP on the name plate of the housing.
Example Model Code: EJA530E-JASWN-012EN/X2/HC/SCCN/D1
5
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
6.
This product is only available in North America. GS 530SCBS-01E January 1, 2017-00
▪ DIMENSIONS
Model EJA530E S-Series
▪ TERMINAL CONFIGURATION
6
Unit: mm (approx. inch)
95 (3.74) 110 (4.33)
Open to Atmosphere
Ground terminal
Zero adjustment (LPS)
Conduit connection
Integral indicator
(Optional)
193.4(7.62)
• With sanitary process connections code SCCN
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
7.
GS 530SCBS-01E January 1, 2017-01
This product is only available in North America.
▪ ORDERING INFORMATION
Specify the following when ordering:
1. Model, suffix codes, and option codes
2. Calibration range and units
a. Calibration range can be specified
with values up to 5 digits (excluding
any decimal point) for low and high
range limits within the value of
-32000 to +32000
b. Specify only one unit from table
“Factory Settings” when shipped
3. Display scale and units (for transmitters with
integral indicator). Specify either 0 to 100%
or engineering unit scale. For engineering
unit scale, range limit for the low and high
limits can be up to 5 digits (excluding any
decimal point) and must be within -32000 to
+32000
4. Specify HART 5 or HART 7
5. Tag No (if required): Can specify up to 22
characters that will be engraved on the tag
plate fixed to the amplifier housing.
6. Software Tag (if required): Up to 32
characters can be specified. First 8
characters are set as “Tag” and Up to 32
characters are set as “Long Tag”.
▪ FACTORY SETTING AT SHIPMENT
7
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
8.
GS 530SCBS-01E January 1, 2017-01
This product is only available in North America.
This Page Blank
8
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
10.
GS 530STSS-01E January 1, 2017-00
This product is only available in North America.
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the
lower and upper range limits of the capsule.
Integral Display (LCD Display)
5-digit numerical display, 6-digit unit display and bar
graph. The display is configurable to display one or up
to three of the following variable: pressure in %,
scaled pressure, measured pressure.
Local Parameter Setting
Parameter configuration without a HHC offers quick
and easy setup of parameters. Parameters that can
be set include Tag Number, Unit of Measure, LRV,
URV, Damping, Output Mode, Display, and Re-range
by applying actual pressure (LRV and URV).
Response Time (All Capsules)
100 msec
When software damping is set to zero and includes
dead time of 45 msec (nominal)
Self-Diagnostics
CPU failure, hardware failure, configuration error,
process alarm for pressure or capsule temperature.
User-configurable process high/low alarm for
pressure also available.
Signal Characterizer
User-configurable 10-segment signal characterizer for
the 4 to 20 mA output.
HART PROTOCOL DIGITAL OUPUT
Two wire 4 to 20 mA DC with digital communications,
HART FSK protocol superimposed on the 4 to 20 mA
signal.
FEATURES
• Remote Ranging and Monitoring Functions
Ranges can be remotely set and monitored through
HART communication.
• On-line Communication
Analog signal output and HART digital communication
do not interfere with one another making on-line
communication possible.
• Enhanced Burst Mode and Event Notification
(HART 7)
Advanced burst mode includes the variety of
transmission settings by specifying burst variables,
update period, and message trigger mode. Event
notification function gives you an alert signal based on
the status change in preset values and self-
diagnostics.
• Long Tag Supporting Up to 32 Characters
(HART 7)
Long tag secures better asset management with
abundant digits available for device tag numbers.
• Self-Diagnostics
Pressure input outside the range limit, excessive
ambient temperature, incorrect span setting etc. can
be diagnosed through HART communication.
• HART Protocol Revision Selectable
HART protocol revision can be selected from HART 5
or HART 7 when ordering. The protocol revision can
be changed in the field by the user.
2
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
11.
GS 530STSS-01E January 1, 2017-00
This product is only available in North America.
□NORMAL OPERATING CONDITIONS
(Optional features option codes may affect
limits)
Ambient Temperature Limits
-40⁰F to +185⁰F
-22⁰F to +176⁰F (with Integral Display)
Process Temperature Limits
-40⁰F to +248⁰F
Ambient Humidity Limits
0 to 100% RH
Maximum over Pressure
Supply & Load Requirements
(Output Signal code D and J. Optional features
may affect electrical requirements)
With 24 V DC supply, up to 550Ω load can be used.
See graph below.
Figure1. Relationship between power supply
Voltage and external load resistance.
(Output signal code J)
Supply Voltage
For 4 to 20 mA HART Protocol
10.5 to 42 VDC for general use and flameproof type.
10.5 to 32 VDC for Lightning Protector (option code
code /A).
10.5 to 30 VDC for intrinsically safe, type n, non-
incendive or non-sparking type.
Minimum voltage limited at 16.6 VDC for
communication.
Load for 4 to 20 mA HART Protocol
0 to 1290 Ω for operation
250 to 600 Ω for digital communication
Communication Requirements
Load Capacitance
0.22µF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10kΩ or more at 2.4 kHz
EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in industrial
locations)
EN61326-2-3
Safety Requirement Standard
EN61010-1, EN61010-2-030
Altitude of installation site: Max 2,000 meters
above sea level.
Installation category: I (Anticipation transient
overvoltage 330 V)
Pollution degree: 2
Indoor / Outdoor use
3
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
12.
GS 530STSS-01E January 1, 2017-00
This product is only available in North America.
□PHYSICAL SPECIFICATIONS
Wetted Parts Materials
All wetted parts material is 316 Stainless Steel
Non-wetted Parts Material
Amplifier Housing
Amplifier Housing code 1: Low copper cast
aluminum alloy with polyurethane, deep sea moss
green paint (Munsell 0.6GY3.1/2.0)
Code /X2: Upgraded painting process to increase
corrosion resistance in sanitary applications.
(Available on Amplifier Housing code 1)
Atmospheric Reference Pipe
Polypropylene
Cover O-rings
Buna-N
Name plate and tag
316 Stainless Steel
Fill Fluid
DC200 Silicone and Neobee M20
Degrees of Protection
NEMA 4x (IP66/IP67); IP69K
Weight
Amplifier Housing code 1: 5.2 lbs.
Note: Transmitter only, weight does not include
mounting bracket (If supplied).
Clean in Place (CIP) / Sanitize in Place (SIP)
The EJA530E (Gauge) Sanitary Pressure
Transmitters feature a 3A compliant sanitary Tank
Spud process connection with an upper process
temperature limit of 400⁰F.
< Related Instruments>
YHC5150X HART Communicator:
GS 01R01A30-01EN-A
FieldMate Device Management:
GS 01R01A01-01E
<Reference>
4
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
13.
This product is only available in North America.
GS 530STSS-01E January 1, 2017-00
▪ MODEL AND SUFFIX CODES
The “>” mark indicates the most typical selection for each specification.
▪ OPTIONAL SPECIFICATIONS
*1: Lower limit of ambient temperature: -15°C (+5°F).
*2: Indicates the unit of MWP on the name plate of the housing.
Example Model Code: EJA530E-JASWN-012EN/X2/HC/SSDN/D1
5
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
14.
This product is only available in North America. GS 530STSS-01E January 1, 2017-00
▪ DIMENSIONS
Model EJA530E S-Series
6
• With sanitary process connections code SSDN Unit: mm (approx. inch)
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
15.
GS 530STSS-01E January 1, 2017-01
This product is only available in North America.
▪ TERMINAL CONFIGURATION
Unit: mm (approx. inch)
7
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
16.
GS 530STSS-01E January 1, 2017-01
This product is only available in North America.
▪ ORDERING INFORMATION
Specify the following when ordering:
1. Model, suffix codes, and option codes
2. Calibration range and units
a. Calibration range can be specified
with values up to 5 digits (excluding
any decimal point) for low and high
range limits within the value of
-32000 to +32000
b. Specify only one unit from table
“Factory Settings” when shipped
3. Display scale and units (for transmitters with
integral indicator). Specify either 0 to 100%
or engineering unit scale. For engineering
unit scale, range limit for the low and high
limits can be up to 5 digits (excluding any
decimal point) and must be within -32000 to
+32000
4. Specify HART 5 or HART 7
5. Tag No (if required): Can specify up to 22
characters that will be engraved on the tag
plate fixed to the amplifier housing.
6. Software Tag (if required): Up to 32
characters can be specified. First 8
characters are set as “Tag” and Up to 32
characters are set as “Long Tag”.
▪ FACTORY SETTING AT SHIPMENT
8
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
18. GS 530STCS-01E-Y February 1, 2017-00
This product is only available in North America.
Local Parameter Setting
Parameter configuration without a HHC offers quick
and easy setup of parameters. Parameters that can
be set include Tag Number, Unit of Measure, LRV,
URV, Damping, Output Mode, Display, and Re-range
by applying actual pressure (LRV and URV).
(Available on Amplifier Housing code 1 and Integral
Indicator code E)
Response Time (All Capsules)
100 msec
When software damping is set to zero and includes a
dead time of 45 msec (nominal)
Self-Diagnostics
CPU failure, hardware failure, configuration error,
process alarm for pressure or capsule temperature. A
user-configurable process high/low alarm for pressure
is also available.
Signal Characterizer
User-configurable 10-segment signal characterizer for
the 4 to 20 mA output.
HART PROTOCOL DIGITAL OUPUT
Two wire 4 to 20 mA DC with digital communications,
HART FSK protocol superimposed on the 4 to 20 mA
signal.
FEATURES
• Remote Ranging and Monitoring Functions
Ranges can be remotely set and monitored through
HART communication.
• On-line Communication
Analog signal output and HART digital communication
do not interfere with one another, making on-line
communication possible.
• Enhanced Burst Mode and Event Notification
(HART 7)
Advanced burst mode includes a variety of
transmission settings by specifying burst variables,
update period, and message trigger mode. The event
notification function gives users an alert signal based
on the status change in preset values and
self-diagnostics.
• Long Tag Supporting Up to 32 Characters
(HART 7)
Long tag secures better asset management with
abundant digits available for device tag numbers.
• Self-Diagnostics
Pressure input outside the range limit, excessive
ambient temperature, incorrect span setting, etc. can
be diagnosed through HART communication.
• HART Protocol Revision Selectable
HART protocol revision can be selected from HART 5
or HART 7 when ordering. The protocol revision can
be changed in the field by the user.
□NORMAL OPERATING CONDITIONS
Ambient Temperature Limits
-40⁰F to +185⁰F
-22⁰F to +176⁰F (with Integral Display)
Process Temperature Limits
-40⁰F to +248⁰F
Ambient Humidity Limits
0 to 100% RH
Maximum over Pressure
□Supply & Load Requirements
Supply Voltage for 4 to 20 mA HART Protocol
10.5 to 42 VDC.
Minimum voltage limited at 16.6 VDC for
communication.
Load for 4 to 20 mA HART Protocol
0 to 1290 Ω for operation
250 to 600 Ω for digital communication
Figure1. Relationship between power supply
voltage and external load resistance.
2
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
19. GS 530STCS-01E-Y February 1, 2017-00
This product is only available in North America.
□Communication Requirements
Load Capacitance
0.22µF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10kΩ or more at 2.4 kHz
□EMC Conformity Standards
(Amplifier Housing code 1)
EN61326-1 Class A, Table 2 (For use in industrial
locations)
EN61326-2-3
□Safety Requirement Standard
EN61010-1, EN61010-2-030
Altitude of installation site: Max 2,000 meters
above sea level.
Installation category: I (Anticipation transient
overvoltage 330 V)
Pollution degree: 2
Indoor / Outdoor use
□PHYSICAL SPECIFICATIONS
Integral Display (LCD Display)
5-digit numerical display, 6-digit unit display and bar
graph. The LCD display is configurable to display one
to three of the following variables: pressure in %,
scaled pressure, or measured pressure.
Wetted Parts Materials
All wetted parts material is 316 Stainless Steel
Non-wetted Parts Material
Amplifier Housing
Amplifier Housing code 1: Low copper cast
aluminum alloy with polyurethane, deep sea moss
green paint (Munsell 0.6GY3.1/2.0)
Amplifier Housing Coating code /X2: Upgraded
painting process to increase corrosion resistance in
sanitary applications.
Atmospheric Reference Pipe
Polypropylene
Cover O-rings
Buna-N
Name plate and tag
316 Stainless Steel
Fill Fluid
DC200 Silicone and Neobee M20
Degrees of Protection
NEMA 4x (IP66/IP67); IP69K
Weight
Amplifier Housing code 1: 3.2 lbs.
Note: Transmitter only, weight does not include any
mounting bracket.
Clean in Place (CIP) / Sanitize in Place (SIP)
The EJA530E (Gauge) Sanitary Pressure
Transmitters feature a 3A compliant sanitary Tri-
clamp process connection with an upper process
temperature limit of 400⁰F.
<Related Instruments>
YHC5150X HART Communicator:
GS 01R01A30-01EN-A
FieldMate Device Management:
GS 01R01A01-01E
<Reference>
3
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
20. This product is only available in North America.
GS 530STCS-01E-Y February 1, 2017-00
▪ MODEL AND SUFFIX CODES
The “>” mark indicates the most typical selection for each specification.
▪ OPTIONAL SPECIFICATIONS
*1: Not Used
*2: Not Used.
*3: Indicates the unit of MWP on the name plate of the housing.
Example Model Code: EJA530E-JASWN-012EN/X2/HC/STCN/D1
4
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
21. This product is only available in North America. GS 530STCS-01E-Y February 1, 2017-00
▪ DIMENSIONS
Model EJA530E S-Series
5
Unit: mm (approx. inch)
95 (3.74) 110 (4.33)
Open to Atmosphere
Ground terminal
Zero adjustment (LPS)
Conduit connection
Integral indicator
(Optional)
158(6.22)
• With sanitary process connections code STCN
-Amplifier Housing Code 1
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
22. GS 530STCS-01E-Y February 1, 2017-01
This product is only available in North America.
▪ TERMINAL CONFIGURATION
▪ ORDERING INFORMATION
Specify the following when ordering:
1. Model, suffix codes, and option codes
2. Calibration range and units
a. Calibration range can be specified
with values up to 5 digits (excluding
any decimal point) for low and high
range limits within the value of
-32000 to +32000
b. Specify only one unit from table
“Factory Settings” when shipped
3. Display scale and units (for transmitters with
integral indicator). Specify either 0 to 100%
or engineering unit scale. For engineering
unit scale, range limit for the low and high
limits can be up to 5 digits (excluding any
decimal point) and must be within -32000 to
+32000
4. Specify HART 5 or HART 7
5. Tag No (if required): Can specify up to 22
characters that will be engraved on the tag
plate fixed to the amplifier housing.
6. Software Tag (if required): Up to 32
characters can be specified. First 8
characters are set as “Tag” and Up to 32
characters are set as “Long Tag”.
▪ FACTORY SETTING AT SHIPMENT
6
• Terminal wiring for 4 to 20mA output
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749
ARJAY AUTOMATION | WWW.ARJAYNET.COM | (800) 761-1749