International Journal of Engineering Research and Development
e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com
Volume 3, Issue 2 (August 2012), PP. 21-34


LabVIEW Based Transient Stability Analysis of A Multi-Machine
  System When Equipped With Hybrid Power Flow Controller
                                            Lini Mathew1, S.Chatterji2
                                        1
                                         Associate Professor, NITTTR, Chandigarh.
                                             2
                                               Professor, NITTTR, Chandigarh.



Abstract - The high cost of the Voltage Source Converters (VSC) based FACTS controllers such as STATCOM, SSSC
and UPFC is found to be the major hindrance to their widespread use. The classical controllers such as SVC and TCSC
are important because of their simple construction, ease of use and low installation cost. Over the years, environmental,
right-of-way and cost problems have delayed construction of generation facilities as well as new transmission lines. Better
utilization of existing power systems and control equipment has thus become imperative. Novel and cost effective FACTS
topologies therefore, need to be built upon existing equipment which makes use of static converters. The control
performance of such topologies therefore, needs to be analyzed. Such controllers have been envisaged to be Hybrid Power
Flow Controllers (HPFC). In the present work, the authors have made an attempt to simulate HPFC in terms of transfer
function models. This simulated model has been tested by incorporating it in a Multi- Machine system. LabVIEW
software has been employed for this purpose. Results obtained are encouraging and indicate that the dynamic
performance of the power system has quite a bit improved with the HPFC.

Keywords – SVC, TCSC, SSSC, STATCOM, HPFC, Multi- Machine system

                                              I.       INTRODUCTION
          The considerable price of VSC based FACTS Controllers, such as STATCOM, SSSC, UPFC etc, remain as the
major impediment to their widespread use. The existing classical equipment such as switched capacitors and SVC used for
voltage support and switched series capacitors and TCSC used for line impedance control have to be replaced whenever
system upgrades or performance improvements are planned. These compensators are installed in many applications, in order
to mitigate critical contingency conditions and while improvements in their performance would be worth considering, and
their complete replacement is prohibitive. Several distinct models such as transfer function models have been proposed to
represent SVC, TCSC,SSSC and STATCOM [1-8]. Concept of Hybrid Power Flow Controller (HPFC) has been proposed
by Bebic et al. [9,10] but no model has been simulated so far and no stability studies carried out till date.

                             II.      HYBRID POWER FLOW CONTROLLER
           The Hybrid Power Flow Controller (HPFC) employs two equally rated series connected voltage sourced
converters to upgrade the functionality of the existing switched capacitors or Static VAR Compensators (SVC). Since, static
converters are used together with passive devices the power flow controller can be considered as a hybrid controller, and is
therefore named Hybrid Power Flow Controller (HPFC). The functions of switched capacitors and the SVC can be changed
from reactive power support to the generalized power flow control by making use of appropriate converter control – the
functionality commonly associated with UPFC. The key benefit of the new topology is that it fully utilizes the existing
equipment and thereby the required ratings of the additional converters are substantially lower as compared to the ratings of
the comparable UPFC [9].
           The converters can exchange active power through a common dc circuit. A block diagram view of the envisioned
typical HPFC controller is shown in Figure 1. The HPFC configuration is installed on a transmission line that connects two
electrical areas on a Single Machine Infinite Bus (SMIB) System. Central to the HPFC topology is the shunt connected
source of reactive power denoted by BM and represents the controllable shunt connected variable capacitance. This is
equivalent to a typical SVC or any other functional equivalents of SVC such as STATCOM, a synchronous condenser or
even a mechanically switched capacitor bank. The two voltage sourced converters VSC x and VSCY, are connected to the
transmission line by means of coupling transformers. The converters provide controllable voltages at the terminals of the
high voltage side of the transformers. The converters share a common dc circuit coupling each others’ dc terminals. The dc
circuit permits exchange of active power between the converters [10]. HPFC can thus be regarded as the functional
equivalent of UPFC.




                                                            21
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller




                                                                    CDC
                                          VSCX                                     VSCY


                   VS          V1                                                                V2               VR
                                                             VM

          ~

                                                                  BM                                       HPFC



                                        Fig.1. SMIB Power System Equipped with an HPFC

          Two novel hybrid power flow controller (HPFC) topologies were proposed recently for FACTS. The first one
consists of a shunt connected controllable source of reactive power, and the two series connected voltage sourced converters
– one on each side of the shunt device. A simplified single-phase equivalent of the circuit corresponding to Fig.1 is shown in
Fig.2.


                                                                       VD
                                          PX                           C           PY

                                                              CDC

                                     PX, QX                                             PY, QY



                                               VX                             VY
              VS                V1                          VM                             V2                VR
                         ZS                                                                       ZR
                                               ~                             ~

                        IS                                                                            IR
                                                                  IM


                                                                  BM




                              Fig.2 Simplified Single-Phase Equivalent Circuit of the System

           The flow of active power through the line and the amounts of reactive power supplied to each line segment can be
simultaneously and independently controlled by controlling the magnitudes and angles of voltages supplied by the converters.
Control of the shunt connected reactive element is coordinated with the control of converters in order to supply the bulk of
the total required reactive power.
           The hybrid power flow controller is installed on a transmission path, so that, it is dividing the path into two
transmission line segments. This is shown in Fig.1. The line to neutral voltage at the point of connection of the hybrid power
flow controller with one line segment has been denoted by V1. The voltage at the point of connection of the other line
segment to the HPFC has been denoted by V2. The three-phase transmission line segments are carrying three-phase
alternating currents denoted by IS and IR as shown in Fig.2. The voltage sources VX and VY represent the high voltage
equivalents of the voltages generated by the voltage source converters VSC X and VSCY respectively. BM represents the
controllable shunt connected variable susceptance. Active and reactive powers of converters have been denoted by PX, QX,
PY, and QY respectively.



                                                             22
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

         Switching functions have been approximated by their fundamental frequency components neglecting the
harmonics. HPFC can be modeled by transforming the three-phase voltages and currents to dqo variables using Park’s
transformation. This is given by [11]:

Vdqo = T Vabc                                                                             (1)

where T =           cos     cos ( - 120)      cos ( + 120)
                    -sin    -sin ( - 120)     -sin ( + 120)


          The two voltage source converters connected in series have been represented by controllable voltage sources VX
and VY . On the other hand, VM is the voltage at the point where the variable susceptance is connected. LR, LS, RR, RS are the
inductances and resistances of transmission line of both sides of HPFC. P X is the real power exchange of the converter VSCX,
with the dc link and PY is the real power exchange of the converter VSCY, with the dc link. It is obvious that at any instant
of time,
                    PX = PY,
The shunt connected variable susceptance or capacitance has been modeled by means of the differential equations given
below:
BM dVMd                                                                                            (2)
        + BMVMq = IMd = ISd _ IRd
    dt

BM dVMq                                                                                              (3)
        + BMVMd = IMq = ISq _                  IRq
    dt

Model of the series converter VSCX and the line segment on the sending end is given by:

     dI Sd                                                                                         (4)
LS         + LS I Sq + R S I Sd + VXd + VMd = VSd
       dt

     dI Sq
LS             + L S I Sq + R R I Sq + VXq + VMq = VSq                                              (5)
        dt
The differential equations describing the dynamics of the series converter VSCY and the line segment on the receiving end is
given by:

       dI Rd
LR           + R R I Rd + VRd = VMd + VYd + L R I Rq                                               (6)
         dt

       dI Rq
LR             + R R IRq + VRq = VMq + VYq + LR IRd                                                 (7)
        dt

The differential equation describing the dynamics of V dc is given by:

       dVdc    1
C dc        =     (PX _ PY )                                                               (8)
        dt    Vdc

         The dc circuit permits the exchange of active power between the converters. HPFC can be used to independently
and simultaneously control the flow of active power through the line and the amounts of reactive power exchanged with the
sending end and receiving end [12]. HPFC can thus be regarded as the functional equivalent of UPFC. The influence of
HPFC on power system stability, mainly transient stability has been investigated in the following sections.

             III.     MODELLING OF A MULTI-MACHINE SYSTEM USING LABVIEW
          The popular Western System Coordinated Council (WSCC) 3-machines 9-bus practical power system with loads
assumed to be represented by constant impedance model and all the three machines are operated with constant mechanical
power input and with constant excitation has been considered as the test case. Fig.3 shows the WSCC 3-machines, 9-bus
system. WSCC system is widely used and found very frequently in the relevant literature [13-14]. The base MVA of the
system is 100, and system frequency is 60 Hz. The other data are given in Table 1 [4]. All time constants are in seconds. The
disturbance, for the power system under study, initiating the transient has been considered as a three-phase fault occurring
near bus number 7 at the end of the line 5-7.




                                                              23
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

                                                                                           Load C                    230kV
                                    230kV
             18kV                                                                                                              j0.0586    13.8kV
                         j0.0625
                                           0.0085 + j0.072                            0.0119 + j0.1008
        2                                                                                                                                          3

                           18/230                                                                                            230/13.8
                     2                                                                                                                    3
                                                                                  8




                                              0.032 + j0.161




                                                                                                    0.039 + j0.170
                                       7                                                                                 9




                                                                      5                                                             6
                                             0.010 + j0.085




                                                                                                    0.017 + j0.092
                           Load A                                                                                              Load B



                                                                           230kV
                                                                                                                               4



                                                                16.5/230                  j0.0576


                                                                 16.5kV                        1



                                                                                  1


                                                                Fig.3 WSCC 3-Machines, 9-Bus System

                                                       Table 1 Generator-Data
            Specifications                     Generator 1            Generator 2                                                  Generator 3
            Rated MVA                       247.5                 192.0                                                         128.0
            kV                             16.5                   18.0                                                          13.8
            H(s)                           23.64                  6.4                                                           3.01
            Power factor                   1.0                    0.85                                                          0.85
            Type                           Hydro                  Steam                                                         Steam
            Speed                          180 r/min.             3600 r/min.                                                   3600 r/min.
            Xd                             0.1460                 0.8958                                                        1.3125
            Xd’                            0.0608                                     0.1198                                    0.1813
            Xq                             0.0969                                     0.8645                                    1.2578
            Xq’                            0.0969                                     0.1969                                    0.25
            Xl (leakage)                   0.0336                                     0.0521                                    0.0742
            Tdo                            8.96                                       6.00                                      5.89
            Tqo’                           0                                          0.535                                     0.600
            Stored energy at rated         2364 MWs                                   640 MWs                                   301 MWs
            speed

          The resultant reduced Y matrices of the system before, and during the fault conditions are worked out and are
given as YRpf and YRdf respectively.

Reduced Y matrix for the network in the pre-fault condition is given by:
                         0.8455 - j2.9883                      0.2871+ j1.5129 0.2096 + j1.2256
            YRpf =       0.2871+ j1.5129                       0.4200 - j2.7239       0.2133 + j1.0879                                                 (9)
                         0.2096 + j1.2256 0.2133 + j1.0879                            0.2770 - j2.3681

Reduced Y matrix for the network during-fault condition is similarly, given by:




                                                                                  24
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

          0.6568 - j3.8160          0        0.0701+ j0.6306
YRdf =            0            0 - j5.4855           0                                                      (10)
          0.0701+ j0.6306           0        0.1740 - j2.7959

           The WSCC 3-machines 9-bus system has been modelled using LabVIEW and considered as the test case for the
transient stability enhancement investigations carried out in the following sections.
           LabVIEW is a very powerful and flexible tool. It is basically a software package having provision of environment
for graphical development. LabVIEW enables simulation of instrumentation schemes and their analyses. LabVIEW has
features regarding built-in virtual instrument modules and can thus, provide a graphical environment for simulation. It can
produce a visual representation of the system. The software has a huge potential for analyzing system performance and can
be used in simulation techniques effectively.
           LabVIEW consists of a variety of tools for analysis including built-in-functions and add-on-toolkits. LabVIEW
now has several toolkits and modules in the areas of control and simulation, signal processing, system identification,
mathematics etc. The LabVIEW Control and Simulations Toolkit (Module) contains a block diagram based environment for
simulation of linear and non-linear continuous-time and discrete-time dynamic systems. Many simulation algorithms such as
various Runge-Kutta methods are available. The mathematical model to be simulated must be represented in a simulation
loop which is similar to an ordinary while loop in LabVIEW. The mathematical models of the SMIB Electrical power
systems with and without incorporating the different FACTS controllers have been simulated, using the LabVIEW Control
and Simulation Toolkit.

      IV.       MODELLING OF MULTI-MACHINE SYSTEM EQUIPPED WITH HPFC1
          The topology of HPFC proposed by Bebic et al [9] as shown in Fig.1 have been simulated using LabVIEW
software. Two configurations of HPFC have been modeled and simulated using LabVIEW. The control performance of these
topologies has been investigated and analyzed. These are discussed in the following sections:
The first configuration of HPFC, termed as HPFC1, has been simulated as a combination of two VSCs in series and one
shunt capacitor. The middle shunt element has been substituted by a presumably existing switched capacitor or SVC, with
the two half-sized series converters. The transfer function models for the series converters and the SVC have been combined
together to form the LabVIEW model of HPFC1. The LabVIEW based model of HPFC1, which is a combination of series
converters or SSSC and SVC, has been simulated as shown in Fig.4. The HPFC model simulated as shown in Fig.4 has been
implemented in the MM system as shown in Fig.5.




                                        Fig.4. LabVIEW Based Model of HPFC1




                                                            25
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller




                      Fig.5 LabVIEW Based Model of MM Power System Equipped with HPFC1

          The controller consists of amplification block, a wash-out block with low pass filters and stages of lead-lag blocks.
The parameters of the HPFC are as under:
Measurement time constant, Tm = 2,                           Gain of voltage regulator block, KR = 0.2,
Time constant of voltage regulator block, TR = 0.7,          Thyristor dead time, Td = 0.0016,
Thyristor firing delay time, Tb = 1                          Controller gain, K=15,
Wash-out time constant, Tw=10,
Lead-lag time constant of different stages: T1s=0.3          T2s=0.5 Tss=3.5

           In order to analyze the ability of the controller to stabilize the system under study, the disturbance initiating the
transient has been considered as a three-phase fault occurring near bus no.7 at the end of the line 5-7.
           Fig.5 shows the LabVIEW based model of Multi-Machine system equipped with HPFC1. The main objective of
transient stability simulation of power system is to investigate and analyze the stability of a power system over a time period
from few seconds to several tens of seconds, plotting the response of generator rotor-angle with time. Values of damping
constant of machine1 (D1), machine2 (D2) and machine3 (D3) have been varied and system stability has been investigated by
plotting relative angular positions versus time curves. While varying the values of damping constant D 1, D2 and D3, they are
kept equal at each instant. Fig.6 shows the variation of relative angular positions with time for the 3 machines 9-bus system
equipped with HPFC1 corresponding to the damping constant values D 1 = D2 = D3 = 10.




                                                              26
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller




                                                       (a)        del 12




                                                       (b)        del 23




                                                       (c)        del 31

       Fig. 6 Variation of Relative Angular Positions: del 12, del 23 and del 31, with Time, for D1= D2= D3=10
                                        in case of MM System Equipped with HPFC1

           Table 2 indicates the steady state stable values, the time taken to attain stability, the maximum value of overshoot
and the value of rise-time of relative angular positions: del12, del23 and del31 when the values of damping constant D1, D2,
D3 are varied. As the values of damping constant are increased, the oscillations start reducing, the time taken to attain
stability and the maximum value of overshoot reduce.

  Table 2 Steady State Stable Values, Value of Time Taken to Attain Stability, Maximum Value of Overshoot and
   Value of Rise Time of Relative Angular Positions: del 12, del 23 and del 31, with Varying Values of Damping
                   Constant D1, D2 and D3 for a 3 Machines 9 Bus System Equipped with HPFC1
  Value of      Stable Value of     Value of Time Taken to        Maximum Value of             Value of Rise Time
  Damping      Relative Angular          Attain Stability              Overshoot                    (seconds)
  Constants        Positions                (seconds)                  (degrees)
  (D1=D2=          (degrees)
    D3)     del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31
     0                                                        unstable
     1       System goes on diverging, not attaining a steady First swing is not the maximum overshoot, subsequent
                                  state                                    oscillations also goes diverging
     2       System goes on diverging, not attaining a steady    1.49    1.42       2.4       4.9       4.8     4.8
                                  state
     3       2.0     1.32    2.75     21.5      22       21       1.4    1.33      2.23       4.7       4.6     4.7
     4       1.6     1.13    2.25     19.5      20      19.5     1.34    1.27       2.1       4.6       4.5     4.5

                                                             27
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

       5       1.4     1.0       1.9       17       18      17.5      1.28      1.21   1.99     4.5       4.4       4.4
       8       1.06    0.81     1.39      15.5      16      15.5      1.16      1.09   1.75     4.4       4.3       4.3
       10      0.95    0.75      1.2      14.5     14.5      15       1.10      1.03   1.63     4.3       4.2       4.3
       15      0.79    0.67     0.97       13      13.5      13       0.99      0.92   1.41     4.2       4.1       4.2
       20      0.72    0.63     0.85      13.5     12.5      13       0.91      0.84   1.25     4.2       4.1       4.2
       25      0.68    0.6      0.78      10.5      11       11       0.86      0.78   1.13     4.2       4.2       4.2
       30      0.65    0.58     0.73       10       11      10.5      0.8       0.74   1.04     4.3       4.2       4.3
       35      0.63    0.57     0.69      8.5       10       9.5      0.76      0.71   0.97     4.3       4.3       4.3
       40      0.61    0.56     0.67      8.5        9        9       0.74      0.69   0.92     4.4       4.3       4.4
       45      0.59    0.56     0.65      8.5        9       9.5      0.71      0.66   0.88     4.4       4.3       4.4
       50      0.59    0.55     0.64       8        8.5      8.5      0.69      0.65   0.84     4.5       4.4       4.5

       V.        MODELLING OF MULTI-MACHINE SYSTEM EQUIPPED WITH HPFC2
          The previous configuration of HPFC, termed as HPFC1, employed transfer function models of SVC and series
converters (SSSC). It is apparent that the functional equivalents of an SVC, such as a mechanically switched compensator
bank, or a STATCOM or a synchronous condenser can be successfully employed.
          The investigator envisaged to design another model using the above principle by replacing the SVC with a
STATCOM. The transfer function models for the series converters and the STATCOM have been combined together to form
the LabVIEW model of HPFC2.
          The LabVIEW based model of HPFC2, which is a combination of series converters or SSSC and STATCOM, has
been simulated as shown in Fig.7.




                                          Fig.7 LabVIEW based Model of HPFC2

The parameters of HPFC2 are as under:
Controller gain, K=15,
Wash-out time constant, Tw=10,
Lead-lag time constant of different stages: T1s=0.3T2s=0.5       Tss=3.5
AC and DC voltage stabilizer gains, KC = 3.91, Kφ = 51.4,
Lead-lag damping stabilizer time constants, T1C = 0.305s, T2C = 0.5s,
Lead-lag damping stabilizer time constants, T1φ = 0.008s, T2φ = 0.5s,
AC voltage PI controller gains, KP,ac = 5.959,     KI,ac = -31.87
DC voltage PI controller gains, KP,dc = 2.916,                KI,dc = -92.27,
KF = 1.0, TF = 0.25s.

          The second configuration of HPFC termed as HPFC2 has been simulated and the LabVIEW based model of
HPFC2 is shown in Fig.7. The LabVIEW based model of 3-Machine 9 bus WSCC system equipped with HPFC2 is almost
similar to as shown in Fig.5. Values of damping constant of machine1 (D1), machine2 (D2) and machine3 (D3) have been
varied and system stability has been investigated. Fig.8 shows the variation of relative angular positions with time for the 3
machines 9-bus system equipped with HPFC2 corresponding to the damping constant values D 1, D2, D3 equal to 10. The
system attains stability faster when the damping constant is increased. The oscillations die out completely. This is clearly
seen in Fig.8. For a damping constant value equal to 0, the system becomes unstable. The system behaves almost different
when the value of damping constant equal to 1 or 2. The system oscillations die out but the system do not attain a stable
value. The stable value goes on increasing.

                                                               28
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller




                                                      (a)         del 12




                                                      (b)         del 23




                                                      (c)         del 31

        Fig. 8 Variation of Relative Angular Positions: del 12, del 23 and del 31, with Time, for D 1= D2= D3=10
                                     In case of MM System Equipped with HPFC2

           The steady state stable values, the time taken to attain stability, the maximum value of overshoot and the value of
rise-time of relative angular positions: del12, del23 and del31 for varying values of damping constants D 1, D2, D3, have been
observed and the values are similar to those in Table 2. It is observed that the steady state stable values, the time taken to
attain stability, and the maximum value of overshoot of relative angular positions: del12, del23 and del31 decreases when
the values of damping constant D1, D2, D3 are increased.

                 VI.        MODELLING OF A THIRD CONFIGURATION OF HPFC
          Out of the two HPFC topologies proposed by Bebic etal, the first one is a shown in Fig.1. The second topology is a
dual of the first. This topology can be obtained by following a simple circuit transformation of the one shown in Fig.1. This
topology is shown in Fig.9(a) and (b). In Fig.9(a) voltage sources V X and VY represent the high voltage equivalents of
voltages generated by the voltage source converters VSCX and VSCY respectively. It is assumed that the shunt connected
variable susceptance BM is replaced by a shunt connected current source IM as shown in Fig.9(a). It is also assumed that the
current source is split into two half-value currents IM1 and IM2. The two voltage sources are assumed to be combined into one
as VX – VY as shown in Fig.9(b). Finally let the series connected voltage source be regarded as a variable reactance and the
shunt connected current sources as shunt connected voltage source converters. As in the case of the original circuit, the
converters couple each other’s dc terminals, and hence, are able to exchange active power between each other. This
topological variation of the HPFC can be used to improve the performance of the series capacitors by connecting shunt
connected voltage source converters. Both topologies make combined use of passive components and converters and can
therefore be regarded as hybrid devices. The above discussed topology can be envisioned in an SMIB power system as
shown in Fig.10.


                                                             29
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

                                               VX                           VY
                               V1                                                         V2

                                               ~                            ~
                       IS                                                                           IR


                                                                   IM




                                                              (a)

                                                         VX - VY
                               V1                                                        V2

                                                              ~
                      IS                                                                        IR



                                                  IM1                           IM2




                                                           (b)
                            Fig.9 HPFC – Circuit Transformations (a) Equivalent of the First
                                  Topology, (b) Rearranged Equivalent

                 Vt                                                                            Vb
                                                         XM

         ~




                                       VSCX                              VSCY
                                                              CDC
                                                                                               HPFC2




                 Fig.10 SMIB Power System Equipped with an HPFC (Second Topology)


          The second topology of HPFC, shown in Fig.10, can be simulated as a combination of two VSCs connected in
shunt with one series connected capacitor. The middle series element has been substituted by a presumably existing switched
capacitor or TCSC, with the two half-sized shunt converters. This configuration is termed as HPFC3. The transfer function
models of the shunt converters and the TCSC have been combined together to form the LabVIEW based model of HPFC3.
The HPFC3 which is a combination of shunt converters or STATCOM and TCSC have been simulated and the LabVIEW
based model of HPFC3 is as shown in Fig.11.




                                                                    30
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller




                                    Fig.11 LabVIEW based Model of the HPFC3
The parameters of HPFC3 are as under:
Block gain, K = 20,
Wash out block time constant, Tw = 0.1,
Lead-lag block time constants, T1 = 0.4 and T2 = 0.5,
Nominal reactance of the fixed series capacitor, Xc = 0.01,
Reactance of the inductor connected in parallel to the capacitor, X p = 0.75.
AC and DC voltage stabilizer gains, KC = 3.91, Kφ = 51.4,
Lead-lag damping stabilizer time constants, T1C = 0.305s, T2C = 0.5s,
Lead-lag damping stabilizer time constants, T1φ = 0.008s, T2φ = 0.5s,
AC voltage PI controller gains, KP,ac = 5.959,               KI,ac = -31.87
DC voltage PI controller gains, KP,dc = 2.916,               KI,dc = -92.27,
     KF = 1.0,                          TF = 0.25s.

           The model of HPFC3 simulated as shown in Fig.11, has been incorporated in a 3-Machine 9 bus WSCC system
and has been investigated for transient stability enhancements. Values of damping constant of machine1 (D 1), machine2 (D2)
and machine3 (D3) have been varied and system stability has been investigated. Fig.12 shows the variation of relative
angular positions with time for the 3 machines 9-bus system equipped with HPFC3 corresponding to the damping constant
values D1, D2, D3 equal to 10. The steady state stable values, the time taken to attain stability, the maximum value of
overshoot and the value of rise-time of relative angular positions: del12, del23 and del31 for varying values of damping
constants D1, D2, D3, have been tabulated in Table 3.
           It is observed that the system behaves almost in the similar manner with all the three configurations of HPFC. This
is established by comparing Tables 2 and 3.
           It is clearly observed that Fig.8 is very much similar to Fig.12. It is also seen that the values in Tables 2 and 3 are
almost the same. The performance characteristics of HPFC1, HPFC2 and HPFC3 are very much similar and all the three
configurations of HPFC can be implemented as a FACTS controller in a multi-machine system. A comparative chart
comparing the values of time taken to attain stability of the 3 machines 9 bus system when equipped with any of the three
configurations HPFC1, HPFC2 and HPFC3 has been prepared and is shown in Table 4.




                                                        (a)         del 12


                                                               31
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller




                                                 (b)         del 23




                                                 (c)         del 31

Fig.12 Variation of Relative Angular Positions: del 12, del 23 and del 31, with Time, for D1= D2= D3=10 in case of
                                      MM System Equipped with HPFC3

Table 3 Steady State Stable Values, Value of Time Taken to Attain Stability, Maximum Value of Overshoot and
 Value of Rise Time of Relative Angular Positions: del 12, del 23 and del 31, with Varying Values of Damping
                Constant D1, D2 and D3 for a 3 Machines 9 Bus System Equipped with HPFC3
 Value of      Stable Value of      Value of Time Taken to     Maximum Value of          Value of Rise Time
 Damping      Relative Angular         Attain Stability             Overshoot                (seconds)
 Constants        Positions                (seconds)                (degrees)
(D1=D2=           (degrees)
D3)        del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31


     0                                                      unstable
     1      System goes on diverging, oscillations die out but       First swing is not the maximum overshoot,
                         the value is diverging                          subsequent peaks are also diverging
     2      System goes on diverging, oscillations die out but    3.4        2.2      1.8     4.7      4.6    4.7
                         the value is diverging
     3       3.2    1.8     1.75       39       38       37       3.2        2.0      1.7     4.5      4.6    4.6
     4       2.3    1.4      1.4       29       30       27       3.0        1.9      1.7     4.5      4.5    4.5
     5       1.9    1.3      1.2       25       26       27       2.9        1.7      1.6     4.5      4.4    4.5
     8      1.35 0.96       0.88       19       18       19      2.46       1.54     1.44     4.4      4.4    4.4
     10     1.15 0.86        0.8       13      13.5     12.5     2.26       1.43     1.35     4.4      4.4    4.4
     15     0.93 0.74       0.68       11      11.5     11.5      1.9       1.21     1.19     4.5      4.4    4.5
     20     0.81 0.68       0.63        9       9.5       9      1.64       1.08     1.07     4.6      4.6    4.6
     25     0.75 0.64       0.61       8.5      8.5       9      1.45       0.97     0.99     4.7      4.7    4.8
     30     0.71 0.62       0.59       8.5       9       8.5     1.32        0.9     0.92     5.0      5.0    5.0
     35     0.68    0.6     0.57        8       8.5       8      1.21       0.85     0.87     5.3      5.3    5.3
     40     0.65 0.58       0.56        8       8.5       8      1.14       0.81     0.83     5.9      5.9    5.9
     45      0.6   0.57     0.54        8       8.5       8      0.88       0.69     0.69     6.3      6.3    6.3
     50     0.58 0.56       0.55        8        8        8      0.86       0.68     0.65     6.4      6.3    6.4




                                                        32
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

   Table 4 Comparative Chart Combining Values of Time Taken to Attain Stability of Relative Angular Positions:
del 12, del 23 and del 31, for HPFC1, HPFC2 and HPFC3 with Varying Values of Damping Constants
D1, D2 and D3 for a 3 Machines 9 Bus System
       Value of                 HPFC1                            HPFC2                            HPFC3
       Damping       del 12      del 23      del 31   del 12      del 23      del 31   del 12      del 23      del 31
      Constants
     (D1=D2= D3)
           0                    unstable                         unstable                         unstable
           1         Oscillations die out, but stable Oscillations die out, but stable Oscillations die out, but stable
           2            value goes on increasing        value goes on increasing         value goes on increasing
           3           21.5        22           21      33          35           32      39          38           37
           4           19.5        20          19.5     28          28           24      29          30           27
           5            17         18          17.5     22          22           20      25          26           27
           8           15.5        16          15.5     15          15           13      19          18           19
          10           14.5       14.5          15      13          13           12      13         13.5         12.5
          15            13        13.5          13      11          11           10      11         11.5         11.5
          20           13.5       12.5          13       9           9            9       9          9.5           9
          25           10.5        11           11       8           8            8      8.5         8.5           9
          30            10         11          10.5      7           7            7      8.5          9           8.5
          35            8.5        10           9.5      7           7            7       8          8.5           8
          40            8.5         9            9       6           6            6       8          8.5           8
          45            8.5         9           9.5      6           6            6       8          8.5           8
          50             8         8.5          8.5      6           6            6       8           8            8

           It is clearly seen that the system behaves almost in the same manner. For a value of damping constant equal to 0,
the system becomes unstable. When the damping constant is increased to 1 or 2, the system oscillations die out but it does
not attain a constant stable value. The stable value goes on increasing. For increasing values of damping constant, the
settling time improves considerably. This shows that HPFC is effective in improving stability.

                                                VII.           CONCLUSION
           The goal of transient stability simulation of power systems is to analyze the stability of a power system. A power
system is deemed to be stable if the rotational speeds of the generators return to their normal values in a quick and stable
manner after a sudden fault. Three configurations of HPFC viz. HPFC1, HPFC2 and HPFC3 have been modeled and
simulated using LabVIEW and the control performance of these controllers when incorporated in a 3 machines, 9 bus system,
in terms of transient stability enhancement, has been investigated and analyzed in the present work. The transfer function
models for the series converters, SVC, TCSC and the STATCOM have been employed to form the LabVIEW models of
HPFC1, HPFC2 and HPFC3. Variations of the relative angular positions of generators with time has thus been plotted and
the steady-state stable-values, time taken to attain stability, the maximum value of overshoot and the rise-time have been
found out in each case and tabulated for comparison purposes. It is clearly observed from the comparative analysis that the
dynamic performance of the power system has quite a bit improved with the HPFC. All the three HPFC configurations
behave almost in the similar manner. The value of time taken to attain stability starts reducing drastically with increase in the
value of damping constant. It is also observed that the maximum value of overshoot decreases and the value of rise-time
increases slightly with the increase in the value of damping constant. It is evident from the simulation results that all the
three configurations can be utilised effectively as a controller in the system for damping out system oscillations.
           Encouraging results have been obtained which shows that HPFC is very effective in improving stability. Another
major benefit of the new topology ie. HPFC is, that it is capable of fully utilizing the existing equipment (switched
capacitors or SVC) and thereby the required ratings of the additional converters are substantially lower as compared to the
ratings of the comparable UPFC model.

                                                     REFERENCES
[1].      Masood T., Edris A.A, Aggarwal RK, Qureshi.S.A., Khan.A.J., Yacob.Y.A, “Static VAR Compensator (SVC)
          Modeling and Analysis Techniques by MATLAB”, Power System Conference PSC 2006, pp.1-7, 2006.
[2].      Lee.S.Y, Bhattacharya.S, Lejonberg.T, Hammad.A, Lefebvre.S, “Detailed Modeling of Static VAR Compensators
          using the Electromagnetic Transients Program (EMTP)”, IEEE Transactions On Power Delivery, Vol. 7. No. 2, pp.
          836-847, 1992.
[3].      Juncheng.G, Luyuan.T, Jun.G, Zhonghong.W., “ Mathematical Model for Describing Characteristics of TCSC”,
          Proceedings of the International Conference Power System Technology PowerCon 2002, Vol.3, pp.1498-1502,
          2002.
[4].      Patel.R, Mahajan.V, Pant.V, “Modelling of TCSC Controller for Transient Stability Enhancement”, International
          Journal of Emerging Electric Power Systems, Vol.7, Issue.1, Article.6, pp. 1-17, 2006.
[5].      Taheri.H, Shahabi.S, Taheri.Sh, Gholami.A, “Application of Synchronous Static Series Compensator (SSSC) on
          Enhancement of Voltage Stability and Power Oscillation Damping”, Proceedings of the IEEE Region 8
          Conference, EUROCON 2009, pp.533-539, 2009.


                                                              33
Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller

[6].     Panda.S, “Modelling, Simulation and Optimal Tuning of SSSC-based Controller in a Multi-Machine Power
         System”, World Journal of Modelling and Simulation, Vol.6, No.2, pp. 110-121, 2010.
[7].     Abido.M.A, Weindl.Ch, Herold.G, “Analysis and Assessment of STATCOM based Damping Stabilizers for Power
         System Stability Enhancement”, Science Direct Journal of Electric Power Systems Research, Vol.73, No.2,
         pp.177-185, Feb. 2005.
[8].     Fawzi.A.R.A.J., “Analysis of Damping Torque and Synchronising Torque Contributed by STATCOM Considering
         Two Different Damping Schemes”, International Journal of Emerging Electric Power Systems, Vol.12, Issue 2,
         Article 3, 2011.
[9].     Bebic.J.Z., “The Hybrid Power Flow Controller - Introduction to HPFC”, 2007, Available at
         http://www.hpfc.ca/hpfc.html
[10].    Bebic.J.Z., Lehn.P.W., Iravani.M.R., “The Hybrid Power Flow Controller - A New Concept for Flexible AC
         Transmission”, Proceedings of the IEEE Power Engineering Society General Meeting, pp.1-7, 2006.
[11].    Rakesh Babu.G., Bhargav.K.V., Rambabu, “Real and Reactive Power Control of HPFC with Adaptive Back
         Stepping Control”, International Journal of Engineering Science and Technology, Vol.3, No.5, May 2011.
[12].    Sood.V.K., Sivadas.S.D., “Simulation of Hybrid Power Flow Controller”, Proceedings of the Joint International
         Conference on Power Electronics, Drives and Energy Systems (PEDES) & Power India, pp.1-5, December 2010.
[13].    Jyothsna.T.R, Vaisakh.K, “Improving Multi-Machine Transient Stability Using a Non- Linear Power System
         Stabilizer under Different Operating Conditions”, Fifteenth National Power Systems Conference (NPSC), pp.101-
         106, December, 2008.
[14].    Patel.R, Bhatti T. S Kothari D. P, “MATLAB/ Simulink based Transient Stability Analysis of a Multi-Machine
         Power System”, International Journal of Electrical Engineering Education, Vol. 39, Issue 4, pp 320-336, October,
         2002




                                                          34

More Related Content

What's hot

SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...
SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...
SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...Journal For Research
 
HARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTER
HARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTERHARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTER
HARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTERJournal For Research
 
Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING CONSTANT VOLTAGE AND CURREN...
Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING  CONSTANT VOLTAGE AND CURREN...Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING  CONSTANT VOLTAGE AND CURREN...
Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING CONSTANT VOLTAGE AND CURREN...Pandu Sandi Pratama
 
A Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTS
A Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTSA Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTS
A Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTSIJMER
 
Multi Carrier based Multilevel Inverter with Minimal Harmonic Distortion
Multi Carrier based Multilevel Inverter with Minimal Harmonic DistortionMulti Carrier based Multilevel Inverter with Minimal Harmonic Distortion
Multi Carrier based Multilevel Inverter with Minimal Harmonic DistortionIJPEDS-IAES
 
2 twofold mode series echoing dc dc converter for ample load
2 twofold mode series echoing dc dc converter for ample load2 twofold mode series echoing dc dc converter for ample load
2 twofold mode series echoing dc dc converter for ample loadchelliah paramasivan
 
Space Vector Modulation Strategy for NPC Converter
Space Vector Modulation Strategy for NPC ConverterSpace Vector Modulation Strategy for NPC Converter
Space Vector Modulation Strategy for NPC ConverterIRJET Journal
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...
Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...
Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...IAES-IJPEDS
 
BOOST DERIVED HYBRID CONVERTER
BOOST DERIVED HYBRID CONVERTERBOOST DERIVED HYBRID CONVERTER
BOOST DERIVED HYBRID CONVERTERDebasis Mohanty
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...
Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...
Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...IJPEDS-IAES
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
SINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADS
SINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADSSINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADS
SINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADSelelijjournal
 

What's hot (19)

SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...
SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...
SIMULATION ANALYSIS OF CLOSED LOOP DUAL INDUCTOR CURRENT-FED PUSH-PULL CONVER...
 
HARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTER
HARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTERHARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTER
HARMONIC ANALYSIS OF THREE LEVEL DIODE CLAMPED INVERTER
 
J026055062
J026055062J026055062
J026055062
 
Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING CONSTANT VOLTAGE AND CURREN...
Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING  CONSTANT VOLTAGE AND CURREN...Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING  CONSTANT VOLTAGE AND CURREN...
Isae 2011 A HYBRID CONTROLLER DESIGN FOR KEEPING CONSTANT VOLTAGE AND CURREN...
 
Selective Harmonic Elimination Based on Newton-raphson Method for Cascaded H-...
Selective Harmonic Elimination Based on Newton-raphson Method for Cascaded H-...Selective Harmonic Elimination Based on Newton-raphson Method for Cascaded H-...
Selective Harmonic Elimination Based on Newton-raphson Method for Cascaded H-...
 
A Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTS
A Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTSA Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTS
A Novel Three-Phase Three-Leg AC/AC Converter Using Nine IGBTS
 
Multi Carrier based Multilevel Inverter with Minimal Harmonic Distortion
Multi Carrier based Multilevel Inverter with Minimal Harmonic DistortionMulti Carrier based Multilevel Inverter with Minimal Harmonic Distortion
Multi Carrier based Multilevel Inverter with Minimal Harmonic Distortion
 
2 twofold mode series echoing dc dc converter for ample load
2 twofold mode series echoing dc dc converter for ample load2 twofold mode series echoing dc dc converter for ample load
2 twofold mode series echoing dc dc converter for ample load
 
Space Vector Modulation Strategy for NPC Converter
Space Vector Modulation Strategy for NPC ConverterSpace Vector Modulation Strategy for NPC Converter
Space Vector Modulation Strategy for NPC Converter
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Js3217191723
Js3217191723Js3217191723
Js3217191723
 
Kb2517721780
Kb2517721780Kb2517721780
Kb2517721780
 
Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...
Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...
Asymmetrical Cascaded Multi Level Inverter using Control Freedom Pulse width ...
 
BOOST DERIVED HYBRID CONVERTER
BOOST DERIVED HYBRID CONVERTERBOOST DERIVED HYBRID CONVERTER
BOOST DERIVED HYBRID CONVERTER
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...
Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...
Simulation and dSPACE Based Implementation of Various PWM Strategies for a Ne...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
1
11
1
 
SINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADS
SINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADSSINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADS
SINGLE PHASE SYMMETRICAL MULTILEVEL INVERTER DESIGN FOR VARIOUS LOADS
 

Similar to IJERD (www.ijerd.com) International Journal of Engineering Research and Development IJERD : hard copy of journal, Call for Papers 2012, publishing of journal, journal of science and technology, research paper publishing, where to publish research paper,

VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGESVSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGESIJERD Editor
 
Flexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question BankFlexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question BankSanthosh Kumar
 
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...IJERA Editor
 
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerAugmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerIJERA Editor
 
Fd2427822788
Fd2427822788Fd2427822788
Fd2427822788IJMER
 
journalism research
journalism researchjournalism research
journalism researchrikaseorika
 
Power quality improvement using fuzzy logic controller based unified power fl...
Power quality improvement using fuzzy logic controller based unified power fl...Power quality improvement using fuzzy logic controller based unified power fl...
Power quality improvement using fuzzy logic controller based unified power fl...nooriasukmaningtyas
 
Power flow control in parallel transmission lines based on UPFC
Power flow control in parallel transmission lines based on UPFCPower flow control in parallel transmission lines based on UPFC
Power flow control in parallel transmission lines based on UPFCjournalBEEI
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1JayakalyanReddy
 
Simulation Of Interline Power Flow Controller in Power Transmission System
 Simulation Of Interline Power Flow Controller in Power Transmission System Simulation Of Interline Power Flow Controller in Power Transmission System
Simulation Of Interline Power Flow Controller in Power Transmission Systemijsrd.com
 
Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...
Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...
Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...IDES Editor
 
IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...
IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...
IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...IRJET Journal
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 
REACTIVE POWER COMPENSATION ppt.pptx
REACTIVE POWER COMPENSATION  ppt.pptxREACTIVE POWER COMPENSATION  ppt.pptx
REACTIVE POWER COMPENSATION ppt.pptxAryan630616
 

Similar to IJERD (www.ijerd.com) International Journal of Engineering Research and Development IJERD : hard copy of journal, Call for Papers 2012, publishing of journal, journal of science and technology, research paper publishing, where to publish research paper, (20)

H04945260
H04945260H04945260
H04945260
 
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGESVSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
VSC BASED HVDC SYTEM DESIGN AND PROTECTION AGAINST OVER VOLTAGES
 
Flexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question BankFlexible Ac Transmission Systems 2Mark Materials and Question Bank
Flexible Ac Transmission Systems 2Mark Materials and Question Bank
 
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
 
upfc
upfcupfc
upfc
 
International Journal of Engineering Inventions (IJEI)
International Journal of Engineering Inventions (IJEI)International Journal of Engineering Inventions (IJEI)
International Journal of Engineering Inventions (IJEI)
 
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow ControllerAugmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
Augmentation of Real & Reactive Power in Grid by Unified Power Flow Controller
 
Fd2427822788
Fd2427822788Fd2427822788
Fd2427822788
 
journalism research
journalism researchjournalism research
journalism research
 
Power quality improvement using fuzzy logic controller based unified power fl...
Power quality improvement using fuzzy logic controller based unified power fl...Power quality improvement using fuzzy logic controller based unified power fl...
Power quality improvement using fuzzy logic controller based unified power fl...
 
Power flow control in parallel transmission lines based on UPFC
Power flow control in parallel transmission lines based on UPFCPower flow control in parallel transmission lines based on UPFC
Power flow control in parallel transmission lines based on UPFC
 
Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1Unified Power Flow Controller(upfc)1
Unified Power Flow Controller(upfc)1
 
Simulation Of Interline Power Flow Controller in Power Transmission System
 Simulation Of Interline Power Flow Controller in Power Transmission System Simulation Of Interline Power Flow Controller in Power Transmission System
Simulation Of Interline Power Flow Controller in Power Transmission System
 
It2415351540
It2415351540It2415351540
It2415351540
 
Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...
Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...
Design and Analysis of Adaptive Neural Controller for Voltage Source Converte...
 
IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...
IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...
IMPROVEMENT OF POWER QUALITY BY USING MULTICONVERTER UNIFIED POWER QUALITY CO...
 
Eb25778783
Eb25778783Eb25778783
Eb25778783
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
A1102010106
A1102010106A1102010106
A1102010106
 
REACTIVE POWER COMPENSATION ppt.pptx
REACTIVE POWER COMPENSATION  ppt.pptxREACTIVE POWER COMPENSATION  ppt.pptx
REACTIVE POWER COMPENSATION ppt.pptx
 

More from IJERD Editor

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksIJERD Editor
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEIJERD Editor
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...IJERD Editor
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’IJERD Editor
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignIJERD Editor
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationIJERD Editor
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...IJERD Editor
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRIJERD Editor
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingIJERD Editor
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string valueIJERD Editor
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...IJERD Editor
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeIJERD Editor
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...IJERD Editor
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraIJERD Editor
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...IJERD Editor
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...IJERD Editor
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingIJERD Editor
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...IJERD Editor
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart GridIJERD Editor
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderIJERD Editor
 

More from IJERD Editor (20)

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACE
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding Design
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and Verification
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive Manufacturing
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string value
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF Dxing
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart Grid
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powder
 

Recently uploaded

Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...lizamodels9
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...lizamodels9
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024christinemoorman
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Serviceritikaroy0888
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfpollardmorgan
 
Non Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxNon Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxAbhayThakur200703
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...lizamodels9
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,noida100girls
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Neil Kimberley
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...anilsa9823
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsApsara Of India
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 

Recently uploaded (20)

Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
Lowrate Call Girls In Sector 18 Noida ❤️8860477959 Escorts 100% Genuine Servi...
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
 
Non Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxNon Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptx
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
 
KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 

IJERD (www.ijerd.com) International Journal of Engineering Research and Development IJERD : hard copy of journal, Call for Papers 2012, publishing of journal, journal of science and technology, research paper publishing, where to publish research paper,

  • 1. International Journal of Engineering Research and Development e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com Volume 3, Issue 2 (August 2012), PP. 21-34 LabVIEW Based Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller Lini Mathew1, S.Chatterji2 1 Associate Professor, NITTTR, Chandigarh. 2 Professor, NITTTR, Chandigarh. Abstract - The high cost of the Voltage Source Converters (VSC) based FACTS controllers such as STATCOM, SSSC and UPFC is found to be the major hindrance to their widespread use. The classical controllers such as SVC and TCSC are important because of their simple construction, ease of use and low installation cost. Over the years, environmental, right-of-way and cost problems have delayed construction of generation facilities as well as new transmission lines. Better utilization of existing power systems and control equipment has thus become imperative. Novel and cost effective FACTS topologies therefore, need to be built upon existing equipment which makes use of static converters. The control performance of such topologies therefore, needs to be analyzed. Such controllers have been envisaged to be Hybrid Power Flow Controllers (HPFC). In the present work, the authors have made an attempt to simulate HPFC in terms of transfer function models. This simulated model has been tested by incorporating it in a Multi- Machine system. LabVIEW software has been employed for this purpose. Results obtained are encouraging and indicate that the dynamic performance of the power system has quite a bit improved with the HPFC. Keywords – SVC, TCSC, SSSC, STATCOM, HPFC, Multi- Machine system I. INTRODUCTION The considerable price of VSC based FACTS Controllers, such as STATCOM, SSSC, UPFC etc, remain as the major impediment to their widespread use. The existing classical equipment such as switched capacitors and SVC used for voltage support and switched series capacitors and TCSC used for line impedance control have to be replaced whenever system upgrades or performance improvements are planned. These compensators are installed in many applications, in order to mitigate critical contingency conditions and while improvements in their performance would be worth considering, and their complete replacement is prohibitive. Several distinct models such as transfer function models have been proposed to represent SVC, TCSC,SSSC and STATCOM [1-8]. Concept of Hybrid Power Flow Controller (HPFC) has been proposed by Bebic et al. [9,10] but no model has been simulated so far and no stability studies carried out till date. II. HYBRID POWER FLOW CONTROLLER The Hybrid Power Flow Controller (HPFC) employs two equally rated series connected voltage sourced converters to upgrade the functionality of the existing switched capacitors or Static VAR Compensators (SVC). Since, static converters are used together with passive devices the power flow controller can be considered as a hybrid controller, and is therefore named Hybrid Power Flow Controller (HPFC). The functions of switched capacitors and the SVC can be changed from reactive power support to the generalized power flow control by making use of appropriate converter control – the functionality commonly associated with UPFC. The key benefit of the new topology is that it fully utilizes the existing equipment and thereby the required ratings of the additional converters are substantially lower as compared to the ratings of the comparable UPFC [9]. The converters can exchange active power through a common dc circuit. A block diagram view of the envisioned typical HPFC controller is shown in Figure 1. The HPFC configuration is installed on a transmission line that connects two electrical areas on a Single Machine Infinite Bus (SMIB) System. Central to the HPFC topology is the shunt connected source of reactive power denoted by BM and represents the controllable shunt connected variable capacitance. This is equivalent to a typical SVC or any other functional equivalents of SVC such as STATCOM, a synchronous condenser or even a mechanically switched capacitor bank. The two voltage sourced converters VSC x and VSCY, are connected to the transmission line by means of coupling transformers. The converters provide controllable voltages at the terminals of the high voltage side of the transformers. The converters share a common dc circuit coupling each others’ dc terminals. The dc circuit permits exchange of active power between the converters [10]. HPFC can thus be regarded as the functional equivalent of UPFC. 21
  • 2. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller CDC VSCX VSCY VS V1 V2 VR VM ~ BM HPFC Fig.1. SMIB Power System Equipped with an HPFC Two novel hybrid power flow controller (HPFC) topologies were proposed recently for FACTS. The first one consists of a shunt connected controllable source of reactive power, and the two series connected voltage sourced converters – one on each side of the shunt device. A simplified single-phase equivalent of the circuit corresponding to Fig.1 is shown in Fig.2. VD PX C PY CDC PX, QX PY, QY VX VY VS V1 VM V2 VR ZS ZR ~ ~ IS IR IM BM Fig.2 Simplified Single-Phase Equivalent Circuit of the System The flow of active power through the line and the amounts of reactive power supplied to each line segment can be simultaneously and independently controlled by controlling the magnitudes and angles of voltages supplied by the converters. Control of the shunt connected reactive element is coordinated with the control of converters in order to supply the bulk of the total required reactive power. The hybrid power flow controller is installed on a transmission path, so that, it is dividing the path into two transmission line segments. This is shown in Fig.1. The line to neutral voltage at the point of connection of the hybrid power flow controller with one line segment has been denoted by V1. The voltage at the point of connection of the other line segment to the HPFC has been denoted by V2. The three-phase transmission line segments are carrying three-phase alternating currents denoted by IS and IR as shown in Fig.2. The voltage sources VX and VY represent the high voltage equivalents of the voltages generated by the voltage source converters VSC X and VSCY respectively. BM represents the controllable shunt connected variable susceptance. Active and reactive powers of converters have been denoted by PX, QX, PY, and QY respectively. 22
  • 3. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller Switching functions have been approximated by their fundamental frequency components neglecting the harmonics. HPFC can be modeled by transforming the three-phase voltages and currents to dqo variables using Park’s transformation. This is given by [11]: Vdqo = T Vabc (1) where T = cos  cos ( - 120) cos ( + 120) -sin  -sin ( - 120) -sin ( + 120) The two voltage source converters connected in series have been represented by controllable voltage sources VX and VY . On the other hand, VM is the voltage at the point where the variable susceptance is connected. LR, LS, RR, RS are the inductances and resistances of transmission line of both sides of HPFC. P X is the real power exchange of the converter VSCX, with the dc link and PY is the real power exchange of the converter VSCY, with the dc link. It is obvious that at any instant of time, PX = PY, The shunt connected variable susceptance or capacitance has been modeled by means of the differential equations given below: BM dVMd (2) + BMVMq = IMd = ISd _ IRd  dt BM dVMq (3) + BMVMd = IMq = ISq _ IRq  dt Model of the series converter VSCX and the line segment on the sending end is given by: dI Sd (4) LS + LS I Sq + R S I Sd + VXd + VMd = VSd dt dI Sq LS + L S I Sq + R R I Sq + VXq + VMq = VSq (5) dt The differential equations describing the dynamics of the series converter VSCY and the line segment on the receiving end is given by: dI Rd LR + R R I Rd + VRd = VMd + VYd + L R I Rq (6) dt dI Rq LR + R R IRq + VRq = VMq + VYq + LR IRd (7) dt The differential equation describing the dynamics of V dc is given by: dVdc 1 C dc = (PX _ PY ) (8) dt Vdc The dc circuit permits the exchange of active power between the converters. HPFC can be used to independently and simultaneously control the flow of active power through the line and the amounts of reactive power exchanged with the sending end and receiving end [12]. HPFC can thus be regarded as the functional equivalent of UPFC. The influence of HPFC on power system stability, mainly transient stability has been investigated in the following sections. III. MODELLING OF A MULTI-MACHINE SYSTEM USING LABVIEW The popular Western System Coordinated Council (WSCC) 3-machines 9-bus practical power system with loads assumed to be represented by constant impedance model and all the three machines are operated with constant mechanical power input and with constant excitation has been considered as the test case. Fig.3 shows the WSCC 3-machines, 9-bus system. WSCC system is widely used and found very frequently in the relevant literature [13-14]. The base MVA of the system is 100, and system frequency is 60 Hz. The other data are given in Table 1 [4]. All time constants are in seconds. The disturbance, for the power system under study, initiating the transient has been considered as a three-phase fault occurring near bus number 7 at the end of the line 5-7. 23
  • 4. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller Load C 230kV 230kV 18kV j0.0586 13.8kV j0.0625 0.0085 + j0.072 0.0119 + j0.1008 2 3 18/230 230/13.8 2 3 8 0.032 + j0.161 0.039 + j0.170 7 9 5 6 0.010 + j0.085 0.017 + j0.092 Load A Load B 230kV 4 16.5/230 j0.0576 16.5kV 1 1 Fig.3 WSCC 3-Machines, 9-Bus System Table 1 Generator-Data Specifications Generator 1 Generator 2 Generator 3 Rated MVA 247.5 192.0 128.0 kV 16.5 18.0 13.8 H(s) 23.64 6.4 3.01 Power factor 1.0 0.85 0.85 Type Hydro Steam Steam Speed 180 r/min. 3600 r/min. 3600 r/min. Xd 0.1460 0.8958 1.3125 Xd’ 0.0608 0.1198 0.1813 Xq 0.0969 0.8645 1.2578 Xq’ 0.0969 0.1969 0.25 Xl (leakage) 0.0336 0.0521 0.0742 Tdo 8.96 6.00 5.89 Tqo’ 0 0.535 0.600 Stored energy at rated 2364 MWs 640 MWs 301 MWs speed The resultant reduced Y matrices of the system before, and during the fault conditions are worked out and are given as YRpf and YRdf respectively. Reduced Y matrix for the network in the pre-fault condition is given by: 0.8455 - j2.9883 0.2871+ j1.5129 0.2096 + j1.2256 YRpf = 0.2871+ j1.5129 0.4200 - j2.7239 0.2133 + j1.0879 (9) 0.2096 + j1.2256 0.2133 + j1.0879 0.2770 - j2.3681 Reduced Y matrix for the network during-fault condition is similarly, given by: 24
  • 5. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller 0.6568 - j3.8160 0 0.0701+ j0.6306 YRdf = 0 0 - j5.4855 0 (10) 0.0701+ j0.6306 0 0.1740 - j2.7959 The WSCC 3-machines 9-bus system has been modelled using LabVIEW and considered as the test case for the transient stability enhancement investigations carried out in the following sections. LabVIEW is a very powerful and flexible tool. It is basically a software package having provision of environment for graphical development. LabVIEW enables simulation of instrumentation schemes and their analyses. LabVIEW has features regarding built-in virtual instrument modules and can thus, provide a graphical environment for simulation. It can produce a visual representation of the system. The software has a huge potential for analyzing system performance and can be used in simulation techniques effectively. LabVIEW consists of a variety of tools for analysis including built-in-functions and add-on-toolkits. LabVIEW now has several toolkits and modules in the areas of control and simulation, signal processing, system identification, mathematics etc. The LabVIEW Control and Simulations Toolkit (Module) contains a block diagram based environment for simulation of linear and non-linear continuous-time and discrete-time dynamic systems. Many simulation algorithms such as various Runge-Kutta methods are available. The mathematical model to be simulated must be represented in a simulation loop which is similar to an ordinary while loop in LabVIEW. The mathematical models of the SMIB Electrical power systems with and without incorporating the different FACTS controllers have been simulated, using the LabVIEW Control and Simulation Toolkit. IV. MODELLING OF MULTI-MACHINE SYSTEM EQUIPPED WITH HPFC1 The topology of HPFC proposed by Bebic et al [9] as shown in Fig.1 have been simulated using LabVIEW software. Two configurations of HPFC have been modeled and simulated using LabVIEW. The control performance of these topologies has been investigated and analyzed. These are discussed in the following sections: The first configuration of HPFC, termed as HPFC1, has been simulated as a combination of two VSCs in series and one shunt capacitor. The middle shunt element has been substituted by a presumably existing switched capacitor or SVC, with the two half-sized series converters. The transfer function models for the series converters and the SVC have been combined together to form the LabVIEW model of HPFC1. The LabVIEW based model of HPFC1, which is a combination of series converters or SSSC and SVC, has been simulated as shown in Fig.4. The HPFC model simulated as shown in Fig.4 has been implemented in the MM system as shown in Fig.5. Fig.4. LabVIEW Based Model of HPFC1 25
  • 6. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller Fig.5 LabVIEW Based Model of MM Power System Equipped with HPFC1 The controller consists of amplification block, a wash-out block with low pass filters and stages of lead-lag blocks. The parameters of the HPFC are as under: Measurement time constant, Tm = 2, Gain of voltage regulator block, KR = 0.2, Time constant of voltage regulator block, TR = 0.7, Thyristor dead time, Td = 0.0016, Thyristor firing delay time, Tb = 1 Controller gain, K=15, Wash-out time constant, Tw=10, Lead-lag time constant of different stages: T1s=0.3 T2s=0.5 Tss=3.5 In order to analyze the ability of the controller to stabilize the system under study, the disturbance initiating the transient has been considered as a three-phase fault occurring near bus no.7 at the end of the line 5-7. Fig.5 shows the LabVIEW based model of Multi-Machine system equipped with HPFC1. The main objective of transient stability simulation of power system is to investigate and analyze the stability of a power system over a time period from few seconds to several tens of seconds, plotting the response of generator rotor-angle with time. Values of damping constant of machine1 (D1), machine2 (D2) and machine3 (D3) have been varied and system stability has been investigated by plotting relative angular positions versus time curves. While varying the values of damping constant D 1, D2 and D3, they are kept equal at each instant. Fig.6 shows the variation of relative angular positions with time for the 3 machines 9-bus system equipped with HPFC1 corresponding to the damping constant values D 1 = D2 = D3 = 10. 26
  • 7. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller (a) del 12 (b) del 23 (c) del 31 Fig. 6 Variation of Relative Angular Positions: del 12, del 23 and del 31, with Time, for D1= D2= D3=10 in case of MM System Equipped with HPFC1 Table 2 indicates the steady state stable values, the time taken to attain stability, the maximum value of overshoot and the value of rise-time of relative angular positions: del12, del23 and del31 when the values of damping constant D1, D2, D3 are varied. As the values of damping constant are increased, the oscillations start reducing, the time taken to attain stability and the maximum value of overshoot reduce. Table 2 Steady State Stable Values, Value of Time Taken to Attain Stability, Maximum Value of Overshoot and Value of Rise Time of Relative Angular Positions: del 12, del 23 and del 31, with Varying Values of Damping Constant D1, D2 and D3 for a 3 Machines 9 Bus System Equipped with HPFC1 Value of Stable Value of Value of Time Taken to Maximum Value of Value of Rise Time Damping Relative Angular Attain Stability Overshoot (seconds) Constants Positions (seconds) (degrees) (D1=D2= (degrees) D3) del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 0 unstable 1 System goes on diverging, not attaining a steady First swing is not the maximum overshoot, subsequent state oscillations also goes diverging 2 System goes on diverging, not attaining a steady 1.49 1.42 2.4 4.9 4.8 4.8 state 3 2.0 1.32 2.75 21.5 22 21 1.4 1.33 2.23 4.7 4.6 4.7 4 1.6 1.13 2.25 19.5 20 19.5 1.34 1.27 2.1 4.6 4.5 4.5 27
  • 8. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller 5 1.4 1.0 1.9 17 18 17.5 1.28 1.21 1.99 4.5 4.4 4.4 8 1.06 0.81 1.39 15.5 16 15.5 1.16 1.09 1.75 4.4 4.3 4.3 10 0.95 0.75 1.2 14.5 14.5 15 1.10 1.03 1.63 4.3 4.2 4.3 15 0.79 0.67 0.97 13 13.5 13 0.99 0.92 1.41 4.2 4.1 4.2 20 0.72 0.63 0.85 13.5 12.5 13 0.91 0.84 1.25 4.2 4.1 4.2 25 0.68 0.6 0.78 10.5 11 11 0.86 0.78 1.13 4.2 4.2 4.2 30 0.65 0.58 0.73 10 11 10.5 0.8 0.74 1.04 4.3 4.2 4.3 35 0.63 0.57 0.69 8.5 10 9.5 0.76 0.71 0.97 4.3 4.3 4.3 40 0.61 0.56 0.67 8.5 9 9 0.74 0.69 0.92 4.4 4.3 4.4 45 0.59 0.56 0.65 8.5 9 9.5 0.71 0.66 0.88 4.4 4.3 4.4 50 0.59 0.55 0.64 8 8.5 8.5 0.69 0.65 0.84 4.5 4.4 4.5 V. MODELLING OF MULTI-MACHINE SYSTEM EQUIPPED WITH HPFC2 The previous configuration of HPFC, termed as HPFC1, employed transfer function models of SVC and series converters (SSSC). It is apparent that the functional equivalents of an SVC, such as a mechanically switched compensator bank, or a STATCOM or a synchronous condenser can be successfully employed. The investigator envisaged to design another model using the above principle by replacing the SVC with a STATCOM. The transfer function models for the series converters and the STATCOM have been combined together to form the LabVIEW model of HPFC2. The LabVIEW based model of HPFC2, which is a combination of series converters or SSSC and STATCOM, has been simulated as shown in Fig.7. Fig.7 LabVIEW based Model of HPFC2 The parameters of HPFC2 are as under: Controller gain, K=15, Wash-out time constant, Tw=10, Lead-lag time constant of different stages: T1s=0.3T2s=0.5 Tss=3.5 AC and DC voltage stabilizer gains, KC = 3.91, Kφ = 51.4, Lead-lag damping stabilizer time constants, T1C = 0.305s, T2C = 0.5s, Lead-lag damping stabilizer time constants, T1φ = 0.008s, T2φ = 0.5s, AC voltage PI controller gains, KP,ac = 5.959, KI,ac = -31.87 DC voltage PI controller gains, KP,dc = 2.916, KI,dc = -92.27, KF = 1.0, TF = 0.25s. The second configuration of HPFC termed as HPFC2 has been simulated and the LabVIEW based model of HPFC2 is shown in Fig.7. The LabVIEW based model of 3-Machine 9 bus WSCC system equipped with HPFC2 is almost similar to as shown in Fig.5. Values of damping constant of machine1 (D1), machine2 (D2) and machine3 (D3) have been varied and system stability has been investigated. Fig.8 shows the variation of relative angular positions with time for the 3 machines 9-bus system equipped with HPFC2 corresponding to the damping constant values D 1, D2, D3 equal to 10. The system attains stability faster when the damping constant is increased. The oscillations die out completely. This is clearly seen in Fig.8. For a damping constant value equal to 0, the system becomes unstable. The system behaves almost different when the value of damping constant equal to 1 or 2. The system oscillations die out but the system do not attain a stable value. The stable value goes on increasing. 28
  • 9. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller (a) del 12 (b) del 23 (c) del 31 Fig. 8 Variation of Relative Angular Positions: del 12, del 23 and del 31, with Time, for D 1= D2= D3=10 In case of MM System Equipped with HPFC2 The steady state stable values, the time taken to attain stability, the maximum value of overshoot and the value of rise-time of relative angular positions: del12, del23 and del31 for varying values of damping constants D 1, D2, D3, have been observed and the values are similar to those in Table 2. It is observed that the steady state stable values, the time taken to attain stability, and the maximum value of overshoot of relative angular positions: del12, del23 and del31 decreases when the values of damping constant D1, D2, D3 are increased. VI. MODELLING OF A THIRD CONFIGURATION OF HPFC Out of the two HPFC topologies proposed by Bebic etal, the first one is a shown in Fig.1. The second topology is a dual of the first. This topology can be obtained by following a simple circuit transformation of the one shown in Fig.1. This topology is shown in Fig.9(a) and (b). In Fig.9(a) voltage sources V X and VY represent the high voltage equivalents of voltages generated by the voltage source converters VSCX and VSCY respectively. It is assumed that the shunt connected variable susceptance BM is replaced by a shunt connected current source IM as shown in Fig.9(a). It is also assumed that the current source is split into two half-value currents IM1 and IM2. The two voltage sources are assumed to be combined into one as VX – VY as shown in Fig.9(b). Finally let the series connected voltage source be regarded as a variable reactance and the shunt connected current sources as shunt connected voltage source converters. As in the case of the original circuit, the converters couple each other’s dc terminals, and hence, are able to exchange active power between each other. This topological variation of the HPFC can be used to improve the performance of the series capacitors by connecting shunt connected voltage source converters. Both topologies make combined use of passive components and converters and can therefore be regarded as hybrid devices. The above discussed topology can be envisioned in an SMIB power system as shown in Fig.10. 29
  • 10. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller VX VY V1 V2 ~ ~ IS IR  IM (a) VX - VY V1 V2 ~ IS IR  IM1  IM2 (b) Fig.9 HPFC – Circuit Transformations (a) Equivalent of the First Topology, (b) Rearranged Equivalent Vt Vb XM ~ VSCX VSCY CDC HPFC2 Fig.10 SMIB Power System Equipped with an HPFC (Second Topology) The second topology of HPFC, shown in Fig.10, can be simulated as a combination of two VSCs connected in shunt with one series connected capacitor. The middle series element has been substituted by a presumably existing switched capacitor or TCSC, with the two half-sized shunt converters. This configuration is termed as HPFC3. The transfer function models of the shunt converters and the TCSC have been combined together to form the LabVIEW based model of HPFC3. The HPFC3 which is a combination of shunt converters or STATCOM and TCSC have been simulated and the LabVIEW based model of HPFC3 is as shown in Fig.11. 30
  • 11. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller Fig.11 LabVIEW based Model of the HPFC3 The parameters of HPFC3 are as under: Block gain, K = 20, Wash out block time constant, Tw = 0.1, Lead-lag block time constants, T1 = 0.4 and T2 = 0.5, Nominal reactance of the fixed series capacitor, Xc = 0.01, Reactance of the inductor connected in parallel to the capacitor, X p = 0.75. AC and DC voltage stabilizer gains, KC = 3.91, Kφ = 51.4, Lead-lag damping stabilizer time constants, T1C = 0.305s, T2C = 0.5s, Lead-lag damping stabilizer time constants, T1φ = 0.008s, T2φ = 0.5s, AC voltage PI controller gains, KP,ac = 5.959, KI,ac = -31.87 DC voltage PI controller gains, KP,dc = 2.916, KI,dc = -92.27, KF = 1.0, TF = 0.25s. The model of HPFC3 simulated as shown in Fig.11, has been incorporated in a 3-Machine 9 bus WSCC system and has been investigated for transient stability enhancements. Values of damping constant of machine1 (D 1), machine2 (D2) and machine3 (D3) have been varied and system stability has been investigated. Fig.12 shows the variation of relative angular positions with time for the 3 machines 9-bus system equipped with HPFC3 corresponding to the damping constant values D1, D2, D3 equal to 10. The steady state stable values, the time taken to attain stability, the maximum value of overshoot and the value of rise-time of relative angular positions: del12, del23 and del31 for varying values of damping constants D1, D2, D3, have been tabulated in Table 3. It is observed that the system behaves almost in the similar manner with all the three configurations of HPFC. This is established by comparing Tables 2 and 3. It is clearly observed that Fig.8 is very much similar to Fig.12. It is also seen that the values in Tables 2 and 3 are almost the same. The performance characteristics of HPFC1, HPFC2 and HPFC3 are very much similar and all the three configurations of HPFC can be implemented as a FACTS controller in a multi-machine system. A comparative chart comparing the values of time taken to attain stability of the 3 machines 9 bus system when equipped with any of the three configurations HPFC1, HPFC2 and HPFC3 has been prepared and is shown in Table 4. (a) del 12 31
  • 12. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller (b) del 23 (c) del 31 Fig.12 Variation of Relative Angular Positions: del 12, del 23 and del 31, with Time, for D1= D2= D3=10 in case of MM System Equipped with HPFC3 Table 3 Steady State Stable Values, Value of Time Taken to Attain Stability, Maximum Value of Overshoot and Value of Rise Time of Relative Angular Positions: del 12, del 23 and del 31, with Varying Values of Damping Constant D1, D2 and D3 for a 3 Machines 9 Bus System Equipped with HPFC3 Value of Stable Value of Value of Time Taken to Maximum Value of Value of Rise Time Damping Relative Angular Attain Stability Overshoot (seconds) Constants Positions (seconds) (degrees) (D1=D2= (degrees) D3) del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 0 unstable 1 System goes on diverging, oscillations die out but First swing is not the maximum overshoot, the value is diverging subsequent peaks are also diverging 2 System goes on diverging, oscillations die out but 3.4 2.2 1.8 4.7 4.6 4.7 the value is diverging 3 3.2 1.8 1.75 39 38 37 3.2 2.0 1.7 4.5 4.6 4.6 4 2.3 1.4 1.4 29 30 27 3.0 1.9 1.7 4.5 4.5 4.5 5 1.9 1.3 1.2 25 26 27 2.9 1.7 1.6 4.5 4.4 4.5 8 1.35 0.96 0.88 19 18 19 2.46 1.54 1.44 4.4 4.4 4.4 10 1.15 0.86 0.8 13 13.5 12.5 2.26 1.43 1.35 4.4 4.4 4.4 15 0.93 0.74 0.68 11 11.5 11.5 1.9 1.21 1.19 4.5 4.4 4.5 20 0.81 0.68 0.63 9 9.5 9 1.64 1.08 1.07 4.6 4.6 4.6 25 0.75 0.64 0.61 8.5 8.5 9 1.45 0.97 0.99 4.7 4.7 4.8 30 0.71 0.62 0.59 8.5 9 8.5 1.32 0.9 0.92 5.0 5.0 5.0 35 0.68 0.6 0.57 8 8.5 8 1.21 0.85 0.87 5.3 5.3 5.3 40 0.65 0.58 0.56 8 8.5 8 1.14 0.81 0.83 5.9 5.9 5.9 45 0.6 0.57 0.54 8 8.5 8 0.88 0.69 0.69 6.3 6.3 6.3 50 0.58 0.56 0.55 8 8 8 0.86 0.68 0.65 6.4 6.3 6.4 32
  • 13. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller Table 4 Comparative Chart Combining Values of Time Taken to Attain Stability of Relative Angular Positions: del 12, del 23 and del 31, for HPFC1, HPFC2 and HPFC3 with Varying Values of Damping Constants D1, D2 and D3 for a 3 Machines 9 Bus System Value of HPFC1 HPFC2 HPFC3 Damping del 12 del 23 del 31 del 12 del 23 del 31 del 12 del 23 del 31 Constants (D1=D2= D3) 0 unstable unstable unstable 1 Oscillations die out, but stable Oscillations die out, but stable Oscillations die out, but stable 2 value goes on increasing value goes on increasing value goes on increasing 3 21.5 22 21 33 35 32 39 38 37 4 19.5 20 19.5 28 28 24 29 30 27 5 17 18 17.5 22 22 20 25 26 27 8 15.5 16 15.5 15 15 13 19 18 19 10 14.5 14.5 15 13 13 12 13 13.5 12.5 15 13 13.5 13 11 11 10 11 11.5 11.5 20 13.5 12.5 13 9 9 9 9 9.5 9 25 10.5 11 11 8 8 8 8.5 8.5 9 30 10 11 10.5 7 7 7 8.5 9 8.5 35 8.5 10 9.5 7 7 7 8 8.5 8 40 8.5 9 9 6 6 6 8 8.5 8 45 8.5 9 9.5 6 6 6 8 8.5 8 50 8 8.5 8.5 6 6 6 8 8 8 It is clearly seen that the system behaves almost in the same manner. For a value of damping constant equal to 0, the system becomes unstable. When the damping constant is increased to 1 or 2, the system oscillations die out but it does not attain a constant stable value. The stable value goes on increasing. For increasing values of damping constant, the settling time improves considerably. This shows that HPFC is effective in improving stability. VII. CONCLUSION The goal of transient stability simulation of power systems is to analyze the stability of a power system. A power system is deemed to be stable if the rotational speeds of the generators return to their normal values in a quick and stable manner after a sudden fault. Three configurations of HPFC viz. HPFC1, HPFC2 and HPFC3 have been modeled and simulated using LabVIEW and the control performance of these controllers when incorporated in a 3 machines, 9 bus system, in terms of transient stability enhancement, has been investigated and analyzed in the present work. The transfer function models for the series converters, SVC, TCSC and the STATCOM have been employed to form the LabVIEW models of HPFC1, HPFC2 and HPFC3. Variations of the relative angular positions of generators with time has thus been plotted and the steady-state stable-values, time taken to attain stability, the maximum value of overshoot and the rise-time have been found out in each case and tabulated for comparison purposes. It is clearly observed from the comparative analysis that the dynamic performance of the power system has quite a bit improved with the HPFC. All the three HPFC configurations behave almost in the similar manner. The value of time taken to attain stability starts reducing drastically with increase in the value of damping constant. It is also observed that the maximum value of overshoot decreases and the value of rise-time increases slightly with the increase in the value of damping constant. It is evident from the simulation results that all the three configurations can be utilised effectively as a controller in the system for damping out system oscillations. Encouraging results have been obtained which shows that HPFC is very effective in improving stability. Another major benefit of the new topology ie. HPFC is, that it is capable of fully utilizing the existing equipment (switched capacitors or SVC) and thereby the required ratings of the additional converters are substantially lower as compared to the ratings of the comparable UPFC model. REFERENCES [1]. Masood T., Edris A.A, Aggarwal RK, Qureshi.S.A., Khan.A.J., Yacob.Y.A, “Static VAR Compensator (SVC) Modeling and Analysis Techniques by MATLAB”, Power System Conference PSC 2006, pp.1-7, 2006. [2]. Lee.S.Y, Bhattacharya.S, Lejonberg.T, Hammad.A, Lefebvre.S, “Detailed Modeling of Static VAR Compensators using the Electromagnetic Transients Program (EMTP)”, IEEE Transactions On Power Delivery, Vol. 7. No. 2, pp. 836-847, 1992. [3]. Juncheng.G, Luyuan.T, Jun.G, Zhonghong.W., “ Mathematical Model for Describing Characteristics of TCSC”, Proceedings of the International Conference Power System Technology PowerCon 2002, Vol.3, pp.1498-1502, 2002. [4]. Patel.R, Mahajan.V, Pant.V, “Modelling of TCSC Controller for Transient Stability Enhancement”, International Journal of Emerging Electric Power Systems, Vol.7, Issue.1, Article.6, pp. 1-17, 2006. [5]. Taheri.H, Shahabi.S, Taheri.Sh, Gholami.A, “Application of Synchronous Static Series Compensator (SSSC) on Enhancement of Voltage Stability and Power Oscillation Damping”, Proceedings of the IEEE Region 8 Conference, EUROCON 2009, pp.533-539, 2009. 33
  • 14. Transient Stability Analysis of A Multi-Machine System When Equipped With Hybrid Power Flow Controller [6]. Panda.S, “Modelling, Simulation and Optimal Tuning of SSSC-based Controller in a Multi-Machine Power System”, World Journal of Modelling and Simulation, Vol.6, No.2, pp. 110-121, 2010. [7]. Abido.M.A, Weindl.Ch, Herold.G, “Analysis and Assessment of STATCOM based Damping Stabilizers for Power System Stability Enhancement”, Science Direct Journal of Electric Power Systems Research, Vol.73, No.2, pp.177-185, Feb. 2005. [8]. Fawzi.A.R.A.J., “Analysis of Damping Torque and Synchronising Torque Contributed by STATCOM Considering Two Different Damping Schemes”, International Journal of Emerging Electric Power Systems, Vol.12, Issue 2, Article 3, 2011. [9]. Bebic.J.Z., “The Hybrid Power Flow Controller - Introduction to HPFC”, 2007, Available at http://www.hpfc.ca/hpfc.html [10]. Bebic.J.Z., Lehn.P.W., Iravani.M.R., “The Hybrid Power Flow Controller - A New Concept for Flexible AC Transmission”, Proceedings of the IEEE Power Engineering Society General Meeting, pp.1-7, 2006. [11]. Rakesh Babu.G., Bhargav.K.V., Rambabu, “Real and Reactive Power Control of HPFC with Adaptive Back Stepping Control”, International Journal of Engineering Science and Technology, Vol.3, No.5, May 2011. [12]. Sood.V.K., Sivadas.S.D., “Simulation of Hybrid Power Flow Controller”, Proceedings of the Joint International Conference on Power Electronics, Drives and Energy Systems (PEDES) & Power India, pp.1-5, December 2010. [13]. Jyothsna.T.R, Vaisakh.K, “Improving Multi-Machine Transient Stability Using a Non- Linear Power System Stabilizer under Different Operating Conditions”, Fifteenth National Power Systems Conference (NPSC), pp.101- 106, December, 2008. [14]. Patel.R, Bhatti T. S Kothari D. P, “MATLAB/ Simulink based Transient Stability Analysis of a Multi-Machine Power System”, International Journal of Electrical Engineering Education, Vol. 39, Issue 4, pp 320-336, October, 2002 34