SlideShare a Scribd company logo
ASHRAE 90.1, Lowest Energy, First and Life Cost

Future of Pumping




      Cover image should be high
      quality
      and cover this shaded area
Agenda

• Review ASHRAE 90.1 – 2010 requirements
  relating to balancing & pumping
• Review traditional pump selection against ASHRAE 90.1
• Introduce Design Envelope IVS concept
  for selections to meet ASHRAE 90.1
• Inherent added values in Design Envelope pumping units
• Sensorless control
• Energy savings in plumbing booster systems


       Where standard is referenced
       Black is the standard
       Red is the Armstrong solution




Brazil Visit 2012
ASHRAE Standard 90.1 - 2010

• Energy Standard for Buildings
• Purpose: To provide minimum
  requirements for energy-efficient
  design of buildings
• Does not apply to single family
  dwellings; multi-family structures of 3-
  stories or less
• Most North American Building Codes
  have adopted ASHRAE 90.1 standards




Brazil Visit 2012
6.7.2.3.3 System Balancing

• All HVAC systems shall be balanced
• Written balancing report provided to owner for conditioned
  areas exceeding 5,000ft² (500m²)
• “Hydronic Systems shall be Proportionately Balanced in a manner
  to first minimize throttling losses”




Brazil Visit 2012
6.7.2.3.3 System Balancing

“Then the pump impeller shall
 be trimmed or [max] speed
 adjusted to meet design flow
 conditions”




Brazil Visit 2012
Balancing : Industrial Practices

Manual balancing / conventional controls valves



                                  Advantage :
                                  - lower first cost
                                  - Ashrae 90.1 conformance

                                  Disadvantages
                                  - System must be properly balanced
                                  - Adjustment may be needed to ensure flow on
                                  legs closest to the pump




                                                          6
 Brazil Visit 2012
Balancing : Industrial Practices
    Dynamic balancing : Flow limiter

                                       Advantages:
                                       -No balancing commissioning required



                                       Disadvantages:
                                       1.Higher pump head required
                                       2.Higher initial valve cost
                                       3.No function at partial load
                                       4.Does not meet ASHRAE 90.1
                                       5.Tendency to clog
                                       6.Confusing to install




                                                            7
Brazil Visit 2012
Balancing : Industrial Practices

Dynamic : PIBCV : pressure independent balancing & control valve



                                     Advantages :
                                     - easy selection and commissioning
                                     - Flow required to space is maintained
                                     reducing hunting and energy



                                     Disadvantages
                                     - Must ensure valve is bought from a
                                     quality supplier and characteristics are
                                     as advertised
                                     - higher first cost
                                     - higher pump head can be required
                                     -ASHRAE 90.1 proportional balancing is
                                     not met


                                                        8
 Brazil Visit 2012
Armstrong Solution : manual balancing + variable speed
pumping
                     7℃


                     >12℃




                 Obtain designed comfort at min. energy consumption
                 Chiller : operating at right flow and temp.
                 Pumping : running at right flow
                 BMS : modulating with proper valve authority

                     Valves can be eliminated on constant flow circuits using
                     Sensorless control.
                                                                                37℃   32℃

                                            12℃

                                              7℃

                                                                                9
 Brazil Visit 2012
System Balancing

If conventional control valves are used,

Armstrong recommends

• Control valves are properly selected
• Manual balancing valves proportional balanced
• Design Envelope IVS CHW/Heating variable flow pumps are
  controlled by either sensor in the system for parallel or sensor-
  less control for duty/standby
• For constant flow circuit valves can be eliminated using sensorless
  control




                                                      10
 Brazil Visit 2012
6.7.2.3.3 System Balancing

• “Then the pump impeller shall be trimmed or [max] speed
 adjusted to meet design flow conditions”

• Armstrong – suggests all pumps should have integrated controls!
   • Eliminate throttling in constant flow applications
              • 15% energy reduction
   • Variable Flow
              • 75% energy savings available
   • Optimized impeller trim at factory level
        • Smaller electrics




Brazil Visit 2012
Why have Throttling ability in Variable Flow System?
Head/Press re




                              Speed 1                              • Ideal is Throttle
                                                                    AVAILABLE if system
         u




                                                                    is outside pump
                                                                    operation
                                                                      • Reducing speed will
                                                    System              not achieve this
                        Speed 2                     Resistance     • Use on all pumps
                                                A



                                        D                  B     A = Design Point
                                            C                    B = Actual Site Duty Point
                                                                 C = Reduced Speed without
                                                                  throttling
                                                                 D = Reduced Speed with Throttling
                                                          Flow

          Brazil Visit 2012
Pumps - Lowest Installed Cost
 Flo-Trex Valve

                            •   Multi Function

                            •   Drip tight Shut off Valve

                            •   Non-Slam Check Valve

                            •   Flow Throttling Valve

                            •   Straight also Available

                            •   Sizes up to 350mm

                            •   Grooved ends




  Brazil Visit 2012
Suction Guide and Flotrex Savings


                    Suction guides and Flotrex save components and 30 % in installed costs!




    • 1. “Y” Strainer
    • 2 . Suction long radius elbow
    • 3. Discharge long radius elbow
    • 4 . Discharge check valve
    • 5 . Discharge globe valve
    • 6 . Suction spool piece


Brazil Visit 2012
6.5.4 Hydronic System Design and Control



• 6.5.4.1 Hydronic Variable Flow Systems
• HVAC pumping systems having a total pump system power
 exceeding 10hp (7.5kW) that include control valves designed
 to modulate or step open and close as a function of load, shall
 be designed for variable fluid flow; and shall be capable of
 reducing pump flow rates to 50% or less of the design flow
 rate

• 3 way valves not acceptable




Brazil Visit 2012
6.5.4 Hydronic System Design and Control



• 6.5.4.1 Hydronic Variable Flow Systems
• … Individual chilled water pumps serving variable flow systems
 having motors exceeding 5hp (3.7kW) shall have controls
 and / or devices (Such as variable speed control) that will
 result in pump motor demand of no more than 30% of design
 wattage at 50% of design water flow …

• Armstrong – 2010 at 5hp (3.7kW) vs 2001 at 50hp (37kW)
• All pumps 1hp (0.75kw) and over should have integrated controls




Brazil Visit 2012
6.5.4 Hydronic System Design and Control



• 6.5.4.1 Hydronic Variable Flow Systems
• … The controls or devices shall be controlled as a function of
 desired flow or to maintain a minimum required differential
 pressure.

• Differential pressure shall be measured at or near the most
 remote heat exchanger or the heat exchanger requiring the
 greatest differential pressure. The differential set-point shall
 be no more than 110% of that required to achieve design flow
 through the heat exchanger.




Brazil Visit 2012
Traditional constant speed pump selection


                  Series 4300
                  8x8x10                                                                 •Selection to left of BEP
            120

                      10.19
                                    50
            100                           71
                                                      83
                                                                                         •1250gpm at 70ft
                      9.30
             80
                                                                                         •79.1% eff
Head (ft)




                      8.00                             BEP
             60
                                                                        71
                                                                                         •27.9 bhp

             40
                                                                             40 hp
                                                                                         •40 hp installed
                                                                     30 hp
             20                     System curve


             0
                  0           0.5         1         1.5          2           2.5     3
                                                   Flow (1,000 usgpm)




  Brazil Visit 2012
Variable Speed Operating Curve – 28ft min press


                        Series 4300
                        8x8x10 @ 9.3 in

                  120
                                                                                                    Minimum Pressure set
                  100       1848
                                               50
                                                              40 hp                                 at 40% design head
                            1760 rpm                68
                                                         75
                   80                                         80
                                                                      82
      Head (ft)




                                                                           80
                   60
                                                                                75
                   Operating curve
                                                                                     68
                   40
                                                                                      30 hp
  Feedback                                   System curve
sensor
  set-point                 528
                        0              0.5          1              1.5           2            2.5
                                                         Flow (1,000 usgpm)




        Brazil Visit 2012
Traditional selection at 50% flow


                  Series 4300
                  8x8x10 @ 9.3 in

            120
                                                                                            •625gpm at 38.5ft
            100       1848 rpm
                                       50
                                            68
                                                      40 hp
                                                                                            •67.1%eff
                                                 75
             80                                       80
                                                              82                            •9.06bhp
Head (ft)




                                                                   80
             60
                                                                        75
             Operating curve
                      1240                                                   68
             40
                                                                              30 hp
                      1012
            20
                                   System curve
                             System curve
                      528
                  0              0.5        1              1.5           2            2.5
                                                 Flow (1,000 usgpm)




  Brazil Visit 2012
Traditional Pump Selection Energy Savings




 Traditional selection    Operating point at
 (left of BEP):           50% design flow:
                                               67.5%
      1250gpm at 70ft      625gpm at 38.5ft    ENERGY SAVINGS

       79.1% efficiency     67.1% efficiency   Below ASHRAE
                                               90.1
               27.9 bhp        9.06 bhp        requirements!




Brazil Visit 2012
Design Envelope IVS Pump Selection


                  Series 4300
                  Design Envelope 0611-040.0
                  Integrated Intelligent Variable Speed with Sensorles Control
            160
                      63.0 Hz      57
                                                                                                       •Selection to right of BEP
            140                           68     77
                                                       82

            120
                      58.6 Hz                                 84
                                                                   85                                  •1250gpm at 70ft
                                                                        84
                                                                             82
            100                                                                    77                  •68.1% efficiency
Head (ft)




                                                                                        68
             80
                                                                                                       •32.5bhp
             60                                                                               40 hp

            40
            Control curve                                                                                 BEP
                      27.9 Hz
            20
                                               System curve
                      18.0 Hz

                  0        0.2      0.4        0.6      0.8         1        1.2        1.4      1.6
                                                      Flow (1,000 usgpm)




  Brazil Visit 2012
Design Envelope IVS Selection at 50% Flow


                  Series 4300
                  Design Envelope 0611-040.0
                  Integrated Intelligent Variable Speed with Sensorles Control
            160
                      63.0 Hz      57
                                                                                                       •625gpm at 38.5ft
            140                           68     77
                                                       82

            120
                                                              84
                                                                   85                                  •83.2% efficiency
                                                                        84
                                                                             82
            100                                                                    77                  •7.31bhp
Head (ft)




                                                                                        68
             80

             60                                                                               40 hp
                      36.9 Hz

            40
            Control curve
            20        20.7 Hz
                                         System curve
                                 System curve
                      18.0 Hz

                  0        0.2      0.4        0.6      0.8         1        1.2        1.4      1.6
                                                      Flow (1,000 usgpm)




  Brazil Visit 2012
Design Envelope IVS Pump Selection
Energy Savings



 Design Envelope IVS      Operating point at
 selection:               50% design flow:
                                               77.5%
      1250gpm at 70ft      625gpm at 38.5ft    ENERGY SAVINGS

       68.1% efficiency     83.2% efficiency   Exceeds
                                               ASHRAE 90.1
                32.5bhp         7.31bhp        requirements!




Brazil Visit 2012
Design Envelope IVS Selection Software




Brazil Visit 2012
Cross-hairs Pin Envelopes for Design Conditions




Brazil Visit 2012
Variable Speed Pump Selection – 1250gpm at 70ft




 •Lowest operating cost with eye on price

 •#1 rank must repay lower price difference within 3-years

 •0810-030.0 has $982 lower price than 0611-040.0

 •Improved operating cost of 0611-040.0 pays off price
   difference in 22-months at $010/kWh


Brazil Visit 2012
Design Envelope IVS Pumping Units

                        • Lowest pump operating costs
                        • True plug & play
                        • Integrated controls to
                          350hp/250kW
                        • Stand alone controls to
                          1250hp/900kW
                        • Outdoor capable to
                          125hp/90kW
                        • Pumps controlled by
                          • Armstrong IPS controls
                          • BMS system
                          • Sensorless mode
                          • Remote Sensors




Brazil Visit 2012
Design Envelope IVS Pumping Suite

4300                   4302          4380          4382




Indoors
Integrated to 350hp       to 100hp      to 7.5hp      to 7.5hp
Standalone 400-1250hp

Outdoors
Integrated to 125hp       to 100hp      to 7.5hp      to 7.5hp



   Brazil Visit 2012
Design Envelope IVS Advantages
vs. Wall Mounted VFD




                       VS.




Brazil Visit 2012
Design Envelope IVS Advantages
Selections Save Energy and Cost
             Wall-mounted                            Design Envelope IVS
                                        4” pump                                 3” pump




             Traditional pump with design point to   Design Envelope IVS pump with
             the left of BEP                         design point to the right of BEP
 Design point                                  72%                                  68%

 Average load                                  68%                                  74%

Envelope selection often smaller and in a typical example saved
7% in pump cost and 9% in energy costs
Brazil Visit 2012
Optimized capacity and motor power

• Impeller trim is optimized to the motor power                    53.5 lps @ 27 m
                                                                   18.5 kW vs. 22 kW traditional
• Electronic load limiting                                         Savings in smaller
                                                                   motor & controls
                                                                   Motor/integrated
                                                                   controls = $460 or 9%
                                                                   Power wiring = $50

                                 BEP                               Harmonics = 16.6% reduction

                             A

                                                C         30 kW
                                                                  A  B Design Envelope
                                           B      22 kW                  pump (18.5 kW)
                                       15 kW   18.5 kW

                                                                  A  C Traditional pump (22 kW)




  Brazil Visit 2012
Design Envelope IVS Advantages
Sensorless Savings and Superior Control


                                      No pressure sensors   •   Saving 49% more
                                      necessary                 energy than a
                    Design Envelope
                                                                sensor in the
                    IVS pumps                                   mechanical room
                                                            •   Cost savings of
                                                                $2000 in
                                                                installation, wiring,
                                                                and sensor costs
                                                            •    Simplified
                                                                commissioning
                                                                alone is estimated
                                                                to save $600 per
                                                                pump

Mechanical room

Brazil Visit 2012
Design Envelope IVS Advantages
Flow Meter Savings and Superior Control

• Ability for digital flow readout (in Sensorless mode)
  and communication to BMS
• Future capabilities:
   • Digital flow readout in all control modes
   • Min./max. settings for pump flow output

                    Readout
                    accuracy
                    +/- 5%




                                 =


Brazil Visit 2012
Design Envelope IVS advantages
Wiring VFD mounting bracket savings
                                      Potential wiring savings —with 30
                                      kW motor and controls, the
                                      savings is estimated to be $340
                                      per pump.




Brazil Visit 2012
Design Envelope IVS Advantages
Pump Starting


    •     Provides a gentle ramp up or down in speed to
          eliminate the surges, mechanically, electrically, and
          hydraulically, caused by starting a motor
    •     Monitors and protects the motor and cables




Brazil Visit 2012
Design Envelope IVS Advantages
Motor Starting Currents




                           Design
                           Envelope IVS




Brazil Visit 2012
Design Envelope IVS Advantages
Motor Starters



  22kw, 460V        Cost     Peak Amp Draw   Demand charge
  starter                    (35.1 A)        ($5.60 per kW per 30 days)

  DOL               $99      245.7A          $633
  Star/Delta        $1,587   140.4A          $362
  Soft Start        $1,155   98.3A           $253
  VFD               $2,835   35.1A           $90


 $543 savings per month vs. constant speed DOL starting




Brazil Visit 2012
Design Envelope IVS Advantages
 Harmonic Distortion

                5HP
                                         • Design Envelope IVS pump
                                           controls include built-in DC line
                                           reactors (equivalent to 5% AC line
                                           reactors)

                                         • Other drives often need external
                                           AC reactors (for 30 HP estimated
                                           cost is $440): Mitsubishi, Hitachi,
                                           Lenze/AC Tech, Yaskawa*,
                                           Schneider, Eaton*, Siemens
125HP
                                         * Some models only




             External AC line reactors

  Brazil Visit 2012
Design Envelope IVS Advantages
Emission and Immunity Requirements


• Design Envelope IVS pumping unit controls
   include RFI filters to ensure compliance to low
   emission and immunity requirements EN61800-3
   to the 1st environment class CI (EN55011
   unrestricted sales class B).
• Wall-mounted drives often do not include these
   and must be provided as an extra.




Brazil Visit 2012
Design Envelope IVS Advantages
Reflected Wave Voltage

• If distance between the motor and the control is long, a
 standing wave can form between the motor and control
• These waves can increase voltage at the motor terminals
 causing the motor insulation and bearings to fail prematurely
• Locating the control with the motor will minimize this problem




Brazil Visit 2012
Design Envelope IVS Advantages
Envelope Selection Reduces Risk and Cost

Savings on re-selections
Recent project $25,000 during construction alone




                         C                         A – Original design
                                                   B – 2nd design
                                    B              C – Final design
                         A




Brazil Visit 2012
Design Envelope IVS Advantages
Energy Metering Capability
•       Use the Integrated Controls as an energy meter for energy
        measurement verification




                        kWh
                        readout




    Brazil Visit 2012
Design Envelope IVS – Values & Benefits
Wall Space Savings




      No room
        on wall
    for multiple
           VFDs




Brazil Visit 2012
Design Envelope IVS Advantages to First Cost Savings
Example: 1000 USgpm at 90 ft
Selection: 4300 0611-030.0 Design Envelope IVS
                                                 First cost savings
 1) Selections save energy and cost                         $1,230
 2) Impeller trim saves energy and cost                          ---
 3) Superior control (eliminate DP sensor)                  $2,700
 4) Smaller size motor and control                            $930
 5) Wiring VFD mounting bracket savings                       $340
 6) Harmonic distortion                                       $440
 7) Emission and immunity requirements
 8) Reflected wave voltage                                             Savings
 9) Envelope selection reduces risk and cost                  $500     equal
 10) Energy metering capability
 11) Saves Wall space
                                                              $100
                                                                 ---
                                                                       75%
                                                                       of pump
 Cost to contractor of IVS pump = $8,350          Total   $6,240       cost
 Only 3) above includes Sensorless control

Brazil Visit 2012
Further Design Envelope pumping value
vs. end suction pump
                              •   First cost savings
                              •   Pipe savings
                              •   Floor Space savings
                              •   Maintenance Savings
                              •   Savings on reselection




                        VS.




Brazil Visit 2012
End suction pump installation



                                •   Coupling re-alignment
                                •   Grouting
                                •   Inertia pad
                                •   Concrete base
                                •   Flex connectors




Brazil Visit 2012
Design Envelope – values & benefits
First cost savings

                    3 pump system              3 pump system VIL
                    Horizontal Split Case      0611-030.0
                    150x120x300




                                                                             Savings
 Installation                      $19,572                    $8,327
 cost                                                                    $11,245
                                                                                (=57%)
 Floor space                    105.7 sq. ft               44.2 sq. ft
                                                                           $9,225
                                                                         ($150 / sq. ft)

Brazil Visit 2012
Design Envelope – values & benefits
Floor space savings




Brazil Visit 2012
Design Envelope – values & benefits
Pipe savings (Glendale Arena, Phoenix)

                                                              Less pipe = less friction
                                                              loss
                                                              resulting in operating cost
                                                              savings:
                                                              $6,600
                                                              (est. from TDH reduction)




                                                                  Savings
  Piping                   $225,975             $128,960
  cost                                                        $97,015
                                                                    (= 43%)
  Length                     2751 ft              1723 ft
  of pipe           (2751/100=27.51x     (1723/100=17.23x      1028 ft
                      3’tdh=82.53’tdh)     3’tdh=51.69’tdh)

Brazil Visit 2012
Design Envelope – values & benefits
Maintenance savings (Edmonton Airport)




$8200 annual savings
due to faster mechanical seal changes


Brazil Visit 2012
Design Envelope IVS – Why You Should Use It


•   Energy savings
•   First cost savings
•   Motor / control / sizing   More than     20%
•   Pipe savings               first cost savings
•   Floor space savings
•   Maintenance savings        More than     30%
•   Wiring savings             life cycle cost savings
•   Harmonic control savings
•   Sensorless savings         on a 6” Design Envelope IVS pump
                               compared to end-suction with VFD
•   Commissioning savings      on wall (doesn’t include pipe savings)
•   Flow/energy metering
•   Savings on re-selections



Brazil Visit 2012

More Related Content

What's hot

Air heater
Air heaterAir heater
Air heater
Akhilesh Kushwaha
 
Cooling tower
Cooling towerCooling tower
Cooling tower
Ayush Singh
 
Hvac
HvacHvac
HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & Components
Umang Patel
 
Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF
John Chavez
 
vapor absorption system
vapor absorption systemvapor absorption system
vapor absorption system
Arslan Nazim
 
A.C. Duct
A.C. DuctA.C. Duct
A.C. Duct
Dhruv Shah
 
Duct sizing methods and filter types
Duct sizing methods and filter typesDuct sizing methods and filter types
Duct sizing methods and filter types
SANKA_SILVA
 
urea processes - Copy.pptx
urea processes - Copy.pptxurea processes - Copy.pptx
urea processes - Copy.pptx
ArmaanKhan92
 
Hvac psychrometry and concepts
Hvac psychrometry and conceptsHvac psychrometry and concepts
Hvac psychrometry and concepts
Aishwarya Deopujari
 
Duct design .ppt
Duct design .pptDuct design .ppt
Duct design .ppt
College
 
Q&a what is the effect of low CHW delta t on efficiency & comfort - b...
Q&a what is the effect of low CHW delta t on efficiency & comfort - b...Q&a what is the effect of low CHW delta t on efficiency & comfort - b...
Q&a what is the effect of low CHW delta t on efficiency & comfort - b...
Juma Yousef J. Saleh جمعة يوسف جمعة صالح
 
Cooling water (CW) system
Cooling water (CW) system Cooling water (CW) system
Cooling water (CW) system
Mohammad Shoeb Siddiqui
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
ijtsrd
 
01 hap4 4-space - Hourly Analysis Program - Carrier
01 hap4 4-space - Hourly Analysis Program - Carrier01 hap4 4-space - Hourly Analysis Program - Carrier
01 hap4 4-space - Hourly Analysis Program - Carrier
Monzer Salahdine
 
PRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGNPRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGN
Rakshit vadi
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginers
guestf11b52
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boiler
Kongkiert Tankayura
 
Hvac basics
Hvac basicsHvac basics
Hvac basics
Sandeep Pendem
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learn
Qaimuddin SODHO
 

What's hot (20)

Air heater
Air heaterAir heater
Air heater
 
Cooling tower
Cooling towerCooling tower
Cooling tower
 
Hvac
HvacHvac
Hvac
 
HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & Components
 
Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF
 
vapor absorption system
vapor absorption systemvapor absorption system
vapor absorption system
 
A.C. Duct
A.C. DuctA.C. Duct
A.C. Duct
 
Duct sizing methods and filter types
Duct sizing methods and filter typesDuct sizing methods and filter types
Duct sizing methods and filter types
 
urea processes - Copy.pptx
urea processes - Copy.pptxurea processes - Copy.pptx
urea processes - Copy.pptx
 
Hvac psychrometry and concepts
Hvac psychrometry and conceptsHvac psychrometry and concepts
Hvac psychrometry and concepts
 
Duct design .ppt
Duct design .pptDuct design .ppt
Duct design .ppt
 
Q&a what is the effect of low CHW delta t on efficiency & comfort - b...
Q&a what is the effect of low CHW delta t on efficiency & comfort - b...Q&a what is the effect of low CHW delta t on efficiency & comfort - b...
Q&a what is the effect of low CHW delta t on efficiency & comfort - b...
 
Cooling water (CW) system
Cooling water (CW) system Cooling water (CW) system
Cooling water (CW) system
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
 
01 hap4 4-space - Hourly Analysis Program - Carrier
01 hap4 4-space - Hourly Analysis Program - Carrier01 hap4 4-space - Hourly Analysis Program - Carrier
01 hap4 4-space - Hourly Analysis Program - Carrier
 
PRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGNPRESENTATION ON DUCT DESIGN
PRESENTATION ON DUCT DESIGN
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginers
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boiler
 
Hvac basics
Hvac basicsHvac basics
Hvac basics
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learn
 

Viewers also liked

Ashrae 90.1 and the future of pumping part 2
Ashrae 90.1 and the future of pumping part 2Ashrae 90.1 and the future of pumping part 2
Ashrae 90.1 and the future of pumping part 2
ArmstrongIntegrated
 
What is ASHRAE 90.1?
What is ASHRAE 90.1?What is ASHRAE 90.1?
What is ASHRAE 90.1?
CannonDesign
 
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th EdHeating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
aakumawa
 
Foundations of Machine Learning
Foundations of Machine LearningFoundations of Machine Learning
Foundations of Machine Learning
mahutte
 
Refrigeration Piping Handbook Dupont
Refrigeration Piping Handbook DupontRefrigeration Piping Handbook Dupont
Refrigeration Piping Handbook Dupont
Luiz Carlos Martinelli Júnior
 
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
Norrazman Zaiha Zainol
 
piping design engineering by hamed motlagh
piping design engineering by hamed motlaghpiping design engineering by hamed motlagh
piping design engineering by hamed motlagh
Hamed Motlagh
 
Theory and practice_of_foundation_design_readable
Theory and practice_of_foundation_design_readableTheory and practice_of_foundation_design_readable
Theory and practice_of_foundation_design_readable
Saeed Nassery
 
Machine Foundation Design
Machine Foundation Design Machine Foundation Design
Machine Foundation Design
VARANASI RAMA RAO
 
[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii
Luis Luis
 
Centrifugal pump lecture 1
Centrifugal pump lecture 1Centrifugal pump lecture 1
Centrifugal pump lecture 1
Rahul Singhal
 
Astronomy slideshow
Astronomy slideshowAstronomy slideshow
Astronomy slideshow
aimorales
 
Introduction to Pumps
Introduction to PumpsIntroduction to Pumps
Introduction to Pumps
mohdalaamri
 
Astronomy
AstronomyAstronomy
Cooling load calculations
Cooling load calculationsCooling load calculations
Cooling load calculations
Waleed Alyafie
 
Centrifugal pump
Centrifugal pumpCentrifugal pump
Centrifugal pump
Tarun Kumar
 
Centrifugal Pump
Centrifugal PumpCentrifugal Pump
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Varun Patel
 
Piping engineering guide
Piping engineering guidePiping engineering guide
Piping engineering guide
ram111eg
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
hvactrg1
 

Viewers also liked (20)

Ashrae 90.1 and the future of pumping part 2
Ashrae 90.1 and the future of pumping part 2Ashrae 90.1 and the future of pumping part 2
Ashrae 90.1 and the future of pumping part 2
 
What is ASHRAE 90.1?
What is ASHRAE 90.1?What is ASHRAE 90.1?
What is ASHRAE 90.1?
 
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th EdHeating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
 
Foundations of Machine Learning
Foundations of Machine LearningFoundations of Machine Learning
Foundations of Machine Learning
 
Refrigeration Piping Handbook Dupont
Refrigeration Piping Handbook DupontRefrigeration Piping Handbook Dupont
Refrigeration Piping Handbook Dupont
 
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
 
piping design engineering by hamed motlagh
piping design engineering by hamed motlaghpiping design engineering by hamed motlagh
piping design engineering by hamed motlagh
 
Theory and practice_of_foundation_design_readable
Theory and practice_of_foundation_design_readableTheory and practice_of_foundation_design_readable
Theory and practice_of_foundation_design_readable
 
Machine Foundation Design
Machine Foundation Design Machine Foundation Design
Machine Foundation Design
 
[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii
 
Centrifugal pump lecture 1
Centrifugal pump lecture 1Centrifugal pump lecture 1
Centrifugal pump lecture 1
 
Astronomy slideshow
Astronomy slideshowAstronomy slideshow
Astronomy slideshow
 
Introduction to Pumps
Introduction to PumpsIntroduction to Pumps
Introduction to Pumps
 
Astronomy
AstronomyAstronomy
Astronomy
 
Cooling load calculations
Cooling load calculationsCooling load calculations
Cooling load calculations
 
Centrifugal pump
Centrifugal pumpCentrifugal pump
Centrifugal pump
 
Centrifugal Pump
Centrifugal PumpCentrifugal Pump
Centrifugal Pump
 
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
 
Piping engineering guide
Piping engineering guidePiping engineering guide
Piping engineering guide
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 

Similar to Ashrae 90.1 and the future of pumping part 1

An introduction to Energy Saving Opportunities in Pumping Systems
An introduction to Energy Saving Opportunities in Pumping Systems An introduction to Energy Saving Opportunities in Pumping Systems
An introduction to Energy Saving Opportunities in Pumping Systems
Leonardo ENERGY
 
Adroitt Flow Control Product Catalogue
Adroitt Flow Control Product CatalogueAdroitt Flow Control Product Catalogue
Adroitt Flow Control Product Catalogue
Adroitt Flow Control Pvt Ltd
 
Varley+pump+selection+handbook
Varley+pump+selection+handbookVarley+pump+selection+handbook
Varley+pump+selection+handbook
feli2004
 
Hydro_Jetting_Machine_Catalogue.PDF
Hydro_Jetting_Machine_Catalogue.PDFHydro_Jetting_Machine_Catalogue.PDF
Hydro_Jetting_Machine_Catalogue.PDF
Pressure Jet
 
PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...
PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...
PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...
sewerjettingpumps
 
Chemical process pumps & its crucial role in today’s industry.pptx
Chemical process pumps & its crucial role in today’s industry.pptxChemical process pumps & its crucial role in today’s industry.pptx
Chemical process pumps & its crucial role in today’s industry.pptx
fluorolinedEquipment
 
Why Pulsation Control
Why Pulsation ControlWhy Pulsation Control
Why Pulsation Control
Performance Pulsation Control
 
Maintenance of Hydraulic Systems
Maintenance of Hydraulic SystemsMaintenance of Hydraulic Systems
Maintenance of Hydraulic Systems
Ricky Smith CMRP, CMRT
 
Variable frequency drives rod pump control podcast
Variable frequency drives rod pump control podcastVariable frequency drives rod pump control podcast
Variable frequency drives rod pump control podcast
Schneider Electric
 
Advanced Control of Multiple Sulfur Units
Advanced Control of Multiple Sulfur Units Advanced Control of Multiple Sulfur Units
Advanced Control of Multiple Sulfur Units
Mary Claire Simoneaux
 
Regulazur III - Optimize the costs and operation of your drinking water plant
Regulazur III - Optimize the costs and operation of your drinking water plantRegulazur III - Optimize the costs and operation of your drinking water plant
Regulazur III - Optimize the costs and operation of your drinking water plant
Degrémont
 
Fuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.org
Fuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.orgFuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.org
Fuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.org
Dien Ha The
 
Hybrid engine
Hybrid engineHybrid engine
Hybrid engine
Craig Kielb
 
Oil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptxOil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptx
ssuser355c2a
 
How to increase crude throughput in desalter applications
How to increase crude throughput in desalter applicationsHow to increase crude throughput in desalter applications
How to increase crude throughput in desalter applications
Helena Barras (Goy)
 
TCL Posiflow
TCL PosiflowTCL Posiflow
BlueScape RICE NESHAP Webinar 2-26-13
BlueScape RICE NESHAP Webinar 2-26-13BlueScape RICE NESHAP Webinar 2-26-13
BlueScape RICE NESHAP Webinar 2-26-13
BlueScape
 
Escavadeira hidraulica cat 374 dl
Escavadeira hidraulica cat 374 dlEscavadeira hidraulica cat 374 dl
Escavadeira hidraulica cat 374 dl
85283081
 
Tcom Energyfinal
Tcom EnergyfinalTcom Energyfinal
Tcom Energyfinal
guest27036c7
 
Selection of pump
Selection of pumpSelection of pump
Selection of pump
sofrani
 

Similar to Ashrae 90.1 and the future of pumping part 1 (20)

An introduction to Energy Saving Opportunities in Pumping Systems
An introduction to Energy Saving Opportunities in Pumping Systems An introduction to Energy Saving Opportunities in Pumping Systems
An introduction to Energy Saving Opportunities in Pumping Systems
 
Adroitt Flow Control Product Catalogue
Adroitt Flow Control Product CatalogueAdroitt Flow Control Product Catalogue
Adroitt Flow Control Product Catalogue
 
Varley+pump+selection+handbook
Varley+pump+selection+handbookVarley+pump+selection+handbook
Varley+pump+selection+handbook
 
Hydro_Jetting_Machine_Catalogue.PDF
Hydro_Jetting_Machine_Catalogue.PDFHydro_Jetting_Machine_Catalogue.PDF
Hydro_Jetting_Machine_Catalogue.PDF
 
PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...
PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...
PressureJet - Manufacturer Of High Pressure Hydro Test Pump, Hydro Jetting Ma...
 
Chemical process pumps & its crucial role in today’s industry.pptx
Chemical process pumps & its crucial role in today’s industry.pptxChemical process pumps & its crucial role in today’s industry.pptx
Chemical process pumps & its crucial role in today’s industry.pptx
 
Why Pulsation Control
Why Pulsation ControlWhy Pulsation Control
Why Pulsation Control
 
Maintenance of Hydraulic Systems
Maintenance of Hydraulic SystemsMaintenance of Hydraulic Systems
Maintenance of Hydraulic Systems
 
Variable frequency drives rod pump control podcast
Variable frequency drives rod pump control podcastVariable frequency drives rod pump control podcast
Variable frequency drives rod pump control podcast
 
Advanced Control of Multiple Sulfur Units
Advanced Control of Multiple Sulfur Units Advanced Control of Multiple Sulfur Units
Advanced Control of Multiple Sulfur Units
 
Regulazur III - Optimize the costs and operation of your drinking water plant
Regulazur III - Optimize the costs and operation of your drinking water plantRegulazur III - Optimize the costs and operation of your drinking water plant
Regulazur III - Optimize the costs and operation of your drinking water plant
 
Fuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.org
Fuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.orgFuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.org
Fuji tu dong hoa catalog frenic-aqua-fuji-dienhathe.org
 
Hybrid engine
Hybrid engineHybrid engine
Hybrid engine
 
Oil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptxOil field equipment the part two (2)pptx
Oil field equipment the part two (2)pptx
 
How to increase crude throughput in desalter applications
How to increase crude throughput in desalter applicationsHow to increase crude throughput in desalter applications
How to increase crude throughput in desalter applications
 
TCL Posiflow
TCL PosiflowTCL Posiflow
TCL Posiflow
 
BlueScape RICE NESHAP Webinar 2-26-13
BlueScape RICE NESHAP Webinar 2-26-13BlueScape RICE NESHAP Webinar 2-26-13
BlueScape RICE NESHAP Webinar 2-26-13
 
Escavadeira hidraulica cat 374 dl
Escavadeira hidraulica cat 374 dlEscavadeira hidraulica cat 374 dl
Escavadeira hidraulica cat 374 dl
 
Tcom Energyfinal
Tcom EnergyfinalTcom Energyfinal
Tcom Energyfinal
 
Selection of pump
Selection of pumpSelection of pump
Selection of pump
 

Ashrae 90.1 and the future of pumping part 1

  • 1. ASHRAE 90.1, Lowest Energy, First and Life Cost Future of Pumping Cover image should be high quality and cover this shaded area
  • 2. Agenda • Review ASHRAE 90.1 – 2010 requirements relating to balancing & pumping • Review traditional pump selection against ASHRAE 90.1 • Introduce Design Envelope IVS concept for selections to meet ASHRAE 90.1 • Inherent added values in Design Envelope pumping units • Sensorless control • Energy savings in plumbing booster systems Where standard is referenced Black is the standard Red is the Armstrong solution Brazil Visit 2012
  • 3. ASHRAE Standard 90.1 - 2010 • Energy Standard for Buildings • Purpose: To provide minimum requirements for energy-efficient design of buildings • Does not apply to single family dwellings; multi-family structures of 3- stories or less • Most North American Building Codes have adopted ASHRAE 90.1 standards Brazil Visit 2012
  • 4. 6.7.2.3.3 System Balancing • All HVAC systems shall be balanced • Written balancing report provided to owner for conditioned areas exceeding 5,000ft² (500m²) • “Hydronic Systems shall be Proportionately Balanced in a manner to first minimize throttling losses” Brazil Visit 2012
  • 5. 6.7.2.3.3 System Balancing “Then the pump impeller shall be trimmed or [max] speed adjusted to meet design flow conditions” Brazil Visit 2012
  • 6. Balancing : Industrial Practices Manual balancing / conventional controls valves Advantage : - lower first cost - Ashrae 90.1 conformance Disadvantages - System must be properly balanced - Adjustment may be needed to ensure flow on legs closest to the pump 6 Brazil Visit 2012
  • 7. Balancing : Industrial Practices Dynamic balancing : Flow limiter Advantages: -No balancing commissioning required Disadvantages: 1.Higher pump head required 2.Higher initial valve cost 3.No function at partial load 4.Does not meet ASHRAE 90.1 5.Tendency to clog 6.Confusing to install 7 Brazil Visit 2012
  • 8. Balancing : Industrial Practices Dynamic : PIBCV : pressure independent balancing & control valve Advantages : - easy selection and commissioning - Flow required to space is maintained reducing hunting and energy Disadvantages - Must ensure valve is bought from a quality supplier and characteristics are as advertised - higher first cost - higher pump head can be required -ASHRAE 90.1 proportional balancing is not met 8 Brazil Visit 2012
  • 9. Armstrong Solution : manual balancing + variable speed pumping 7℃ >12℃ Obtain designed comfort at min. energy consumption Chiller : operating at right flow and temp. Pumping : running at right flow BMS : modulating with proper valve authority Valves can be eliminated on constant flow circuits using Sensorless control. 37℃ 32℃ 12℃ 7℃ 9 Brazil Visit 2012
  • 10. System Balancing If conventional control valves are used, Armstrong recommends • Control valves are properly selected • Manual balancing valves proportional balanced • Design Envelope IVS CHW/Heating variable flow pumps are controlled by either sensor in the system for parallel or sensor- less control for duty/standby • For constant flow circuit valves can be eliminated using sensorless control 10 Brazil Visit 2012
  • 11. 6.7.2.3.3 System Balancing • “Then the pump impeller shall be trimmed or [max] speed adjusted to meet design flow conditions” • Armstrong – suggests all pumps should have integrated controls! • Eliminate throttling in constant flow applications • 15% energy reduction • Variable Flow • 75% energy savings available • Optimized impeller trim at factory level • Smaller electrics Brazil Visit 2012
  • 12. Why have Throttling ability in Variable Flow System? Head/Press re Speed 1 • Ideal is Throttle AVAILABLE if system u is outside pump operation • Reducing speed will System not achieve this Speed 2 Resistance • Use on all pumps A D B A = Design Point C B = Actual Site Duty Point C = Reduced Speed without throttling D = Reduced Speed with Throttling Flow Brazil Visit 2012
  • 13. Pumps - Lowest Installed Cost Flo-Trex Valve • Multi Function • Drip tight Shut off Valve • Non-Slam Check Valve • Flow Throttling Valve • Straight also Available • Sizes up to 350mm • Grooved ends Brazil Visit 2012
  • 14. Suction Guide and Flotrex Savings Suction guides and Flotrex save components and 30 % in installed costs! • 1. “Y” Strainer • 2 . Suction long radius elbow • 3. Discharge long radius elbow • 4 . Discharge check valve • 5 . Discharge globe valve • 6 . Suction spool piece Brazil Visit 2012
  • 15. 6.5.4 Hydronic System Design and Control • 6.5.4.1 Hydronic Variable Flow Systems • HVAC pumping systems having a total pump system power exceeding 10hp (7.5kW) that include control valves designed to modulate or step open and close as a function of load, shall be designed for variable fluid flow; and shall be capable of reducing pump flow rates to 50% or less of the design flow rate • 3 way valves not acceptable Brazil Visit 2012
  • 16. 6.5.4 Hydronic System Design and Control • 6.5.4.1 Hydronic Variable Flow Systems • … Individual chilled water pumps serving variable flow systems having motors exceeding 5hp (3.7kW) shall have controls and / or devices (Such as variable speed control) that will result in pump motor demand of no more than 30% of design wattage at 50% of design water flow … • Armstrong – 2010 at 5hp (3.7kW) vs 2001 at 50hp (37kW) • All pumps 1hp (0.75kw) and over should have integrated controls Brazil Visit 2012
  • 17. 6.5.4 Hydronic System Design and Control • 6.5.4.1 Hydronic Variable Flow Systems • … The controls or devices shall be controlled as a function of desired flow or to maintain a minimum required differential pressure. • Differential pressure shall be measured at or near the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure. The differential set-point shall be no more than 110% of that required to achieve design flow through the heat exchanger. Brazil Visit 2012
  • 18. Traditional constant speed pump selection Series 4300 8x8x10 •Selection to left of BEP 120 10.19 50 100 71 83 •1250gpm at 70ft 9.30 80 •79.1% eff Head (ft) 8.00 BEP 60 71 •27.9 bhp 40 40 hp •40 hp installed 30 hp 20 System curve 0 0 0.5 1 1.5 2 2.5 3 Flow (1,000 usgpm) Brazil Visit 2012
  • 19. Variable Speed Operating Curve – 28ft min press Series 4300 8x8x10 @ 9.3 in 120 Minimum Pressure set 100 1848 50 40 hp at 40% design head 1760 rpm 68 75 80 80 82 Head (ft) 80 60 75 Operating curve 68 40 30 hp Feedback System curve sensor set-point 528 0 0.5 1 1.5 2 2.5 Flow (1,000 usgpm) Brazil Visit 2012
  • 20. Traditional selection at 50% flow Series 4300 8x8x10 @ 9.3 in 120 •625gpm at 38.5ft 100 1848 rpm 50 68 40 hp •67.1%eff 75 80 80 82 •9.06bhp Head (ft) 80 60 75 Operating curve 1240 68 40 30 hp 1012 20 System curve System curve 528 0 0.5 1 1.5 2 2.5 Flow (1,000 usgpm) Brazil Visit 2012
  • 21. Traditional Pump Selection Energy Savings Traditional selection Operating point at (left of BEP): 50% design flow: 67.5% 1250gpm at 70ft 625gpm at 38.5ft ENERGY SAVINGS 79.1% efficiency 67.1% efficiency Below ASHRAE 90.1 27.9 bhp 9.06 bhp requirements! Brazil Visit 2012
  • 22. Design Envelope IVS Pump Selection Series 4300 Design Envelope 0611-040.0 Integrated Intelligent Variable Speed with Sensorles Control 160 63.0 Hz 57 •Selection to right of BEP 140 68 77 82 120 58.6 Hz 84 85 •1250gpm at 70ft 84 82 100 77 •68.1% efficiency Head (ft) 68 80 •32.5bhp 60 40 hp 40 Control curve BEP 27.9 Hz 20 System curve 18.0 Hz 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 Flow (1,000 usgpm) Brazil Visit 2012
  • 23. Design Envelope IVS Selection at 50% Flow Series 4300 Design Envelope 0611-040.0 Integrated Intelligent Variable Speed with Sensorles Control 160 63.0 Hz 57 •625gpm at 38.5ft 140 68 77 82 120 84 85 •83.2% efficiency 84 82 100 77 •7.31bhp Head (ft) 68 80 60 40 hp 36.9 Hz 40 Control curve 20 20.7 Hz System curve System curve 18.0 Hz 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 Flow (1,000 usgpm) Brazil Visit 2012
  • 24. Design Envelope IVS Pump Selection Energy Savings Design Envelope IVS Operating point at selection: 50% design flow: 77.5% 1250gpm at 70ft 625gpm at 38.5ft ENERGY SAVINGS 68.1% efficiency 83.2% efficiency Exceeds ASHRAE 90.1 32.5bhp 7.31bhp requirements! Brazil Visit 2012
  • 25. Design Envelope IVS Selection Software Brazil Visit 2012
  • 26. Cross-hairs Pin Envelopes for Design Conditions Brazil Visit 2012
  • 27. Variable Speed Pump Selection – 1250gpm at 70ft •Lowest operating cost with eye on price •#1 rank must repay lower price difference within 3-years •0810-030.0 has $982 lower price than 0611-040.0 •Improved operating cost of 0611-040.0 pays off price difference in 22-months at $010/kWh Brazil Visit 2012
  • 28. Design Envelope IVS Pumping Units • Lowest pump operating costs • True plug & play • Integrated controls to 350hp/250kW • Stand alone controls to 1250hp/900kW • Outdoor capable to 125hp/90kW • Pumps controlled by • Armstrong IPS controls • BMS system • Sensorless mode • Remote Sensors Brazil Visit 2012
  • 29. Design Envelope IVS Pumping Suite 4300 4302 4380 4382 Indoors Integrated to 350hp to 100hp to 7.5hp to 7.5hp Standalone 400-1250hp Outdoors Integrated to 125hp to 100hp to 7.5hp to 7.5hp Brazil Visit 2012
  • 30. Design Envelope IVS Advantages vs. Wall Mounted VFD VS. Brazil Visit 2012
  • 31. Design Envelope IVS Advantages Selections Save Energy and Cost Wall-mounted Design Envelope IVS 4” pump 3” pump Traditional pump with design point to Design Envelope IVS pump with the left of BEP design point to the right of BEP Design point 72% 68% Average load 68% 74% Envelope selection often smaller and in a typical example saved 7% in pump cost and 9% in energy costs Brazil Visit 2012
  • 32. Optimized capacity and motor power • Impeller trim is optimized to the motor power 53.5 lps @ 27 m 18.5 kW vs. 22 kW traditional • Electronic load limiting Savings in smaller motor & controls Motor/integrated controls = $460 or 9% Power wiring = $50 BEP Harmonics = 16.6% reduction A C 30 kW A  B Design Envelope B 22 kW pump (18.5 kW) 15 kW 18.5 kW A  C Traditional pump (22 kW) Brazil Visit 2012
  • 33. Design Envelope IVS Advantages Sensorless Savings and Superior Control No pressure sensors • Saving 49% more necessary energy than a Design Envelope sensor in the IVS pumps mechanical room • Cost savings of $2000 in installation, wiring, and sensor costs • Simplified commissioning alone is estimated to save $600 per pump Mechanical room Brazil Visit 2012
  • 34. Design Envelope IVS Advantages Flow Meter Savings and Superior Control • Ability for digital flow readout (in Sensorless mode) and communication to BMS • Future capabilities: • Digital flow readout in all control modes • Min./max. settings for pump flow output Readout accuracy +/- 5% = Brazil Visit 2012
  • 35. Design Envelope IVS advantages Wiring VFD mounting bracket savings Potential wiring savings —with 30 kW motor and controls, the savings is estimated to be $340 per pump. Brazil Visit 2012
  • 36. Design Envelope IVS Advantages Pump Starting • Provides a gentle ramp up or down in speed to eliminate the surges, mechanically, electrically, and hydraulically, caused by starting a motor • Monitors and protects the motor and cables Brazil Visit 2012
  • 37. Design Envelope IVS Advantages Motor Starting Currents Design Envelope IVS Brazil Visit 2012
  • 38. Design Envelope IVS Advantages Motor Starters 22kw, 460V Cost Peak Amp Draw Demand charge starter (35.1 A) ($5.60 per kW per 30 days) DOL $99 245.7A $633 Star/Delta $1,587 140.4A $362 Soft Start $1,155 98.3A $253 VFD $2,835 35.1A $90 $543 savings per month vs. constant speed DOL starting Brazil Visit 2012
  • 39. Design Envelope IVS Advantages Harmonic Distortion 5HP • Design Envelope IVS pump controls include built-in DC line reactors (equivalent to 5% AC line reactors) • Other drives often need external AC reactors (for 30 HP estimated cost is $440): Mitsubishi, Hitachi, Lenze/AC Tech, Yaskawa*, Schneider, Eaton*, Siemens 125HP * Some models only External AC line reactors Brazil Visit 2012
  • 40. Design Envelope IVS Advantages Emission and Immunity Requirements • Design Envelope IVS pumping unit controls include RFI filters to ensure compliance to low emission and immunity requirements EN61800-3 to the 1st environment class CI (EN55011 unrestricted sales class B). • Wall-mounted drives often do not include these and must be provided as an extra. Brazil Visit 2012
  • 41. Design Envelope IVS Advantages Reflected Wave Voltage • If distance between the motor and the control is long, a standing wave can form between the motor and control • These waves can increase voltage at the motor terminals causing the motor insulation and bearings to fail prematurely • Locating the control with the motor will minimize this problem Brazil Visit 2012
  • 42. Design Envelope IVS Advantages Envelope Selection Reduces Risk and Cost Savings on re-selections Recent project $25,000 during construction alone C A – Original design B – 2nd design B C – Final design A Brazil Visit 2012
  • 43. Design Envelope IVS Advantages Energy Metering Capability • Use the Integrated Controls as an energy meter for energy measurement verification kWh readout Brazil Visit 2012
  • 44. Design Envelope IVS – Values & Benefits Wall Space Savings No room on wall for multiple VFDs Brazil Visit 2012
  • 45. Design Envelope IVS Advantages to First Cost Savings Example: 1000 USgpm at 90 ft Selection: 4300 0611-030.0 Design Envelope IVS First cost savings 1) Selections save energy and cost $1,230 2) Impeller trim saves energy and cost --- 3) Superior control (eliminate DP sensor) $2,700 4) Smaller size motor and control $930 5) Wiring VFD mounting bracket savings $340 6) Harmonic distortion $440 7) Emission and immunity requirements 8) Reflected wave voltage Savings 9) Envelope selection reduces risk and cost $500 equal 10) Energy metering capability 11) Saves Wall space $100 --- 75% of pump Cost to contractor of IVS pump = $8,350 Total $6,240 cost Only 3) above includes Sensorless control Brazil Visit 2012
  • 46. Further Design Envelope pumping value vs. end suction pump • First cost savings • Pipe savings • Floor Space savings • Maintenance Savings • Savings on reselection VS. Brazil Visit 2012
  • 47. End suction pump installation • Coupling re-alignment • Grouting • Inertia pad • Concrete base • Flex connectors Brazil Visit 2012
  • 48. Design Envelope – values & benefits First cost savings 3 pump system 3 pump system VIL Horizontal Split Case 0611-030.0 150x120x300 Savings Installation $19,572 $8,327 cost $11,245 (=57%) Floor space 105.7 sq. ft 44.2 sq. ft $9,225 ($150 / sq. ft) Brazil Visit 2012
  • 49. Design Envelope – values & benefits Floor space savings Brazil Visit 2012
  • 50. Design Envelope – values & benefits Pipe savings (Glendale Arena, Phoenix) Less pipe = less friction loss resulting in operating cost savings: $6,600 (est. from TDH reduction) Savings Piping $225,975 $128,960 cost $97,015 (= 43%) Length 2751 ft 1723 ft of pipe (2751/100=27.51x (1723/100=17.23x 1028 ft 3’tdh=82.53’tdh) 3’tdh=51.69’tdh) Brazil Visit 2012
  • 51. Design Envelope – values & benefits Maintenance savings (Edmonton Airport) $8200 annual savings due to faster mechanical seal changes Brazil Visit 2012
  • 52. Design Envelope IVS – Why You Should Use It • Energy savings • First cost savings • Motor / control / sizing More than 20% • Pipe savings first cost savings • Floor space savings • Maintenance savings More than 30% • Wiring savings life cycle cost savings • Harmonic control savings • Sensorless savings on a 6” Design Envelope IVS pump compared to end-suction with VFD • Commissioning savings on wall (doesn’t include pipe savings) • Flow/energy metering • Savings on re-selections Brazil Visit 2012

Editor's Notes

  1. A flo-trex valve is a multi function valve that replaces an isolating valve, a non-return valve and also an elbow. The valve can also be used to throttle the pump to aid the system commissioning process. The valve has a 45 degree split and can be rotated to change an angled valve to a straight configuration or visa versa. So, now we have reviewed our installation options, lets take a look at a savings example…………….
  2. LEFT: BAYFRONT TOWERS, Tampa, FL Compact mechanical room with no space for two individual pumps and no space to mount drives on the wall. Simple single large AHU avoided using DP sensor by using sensorless design. Pumps also have auto alternating feature. Worked out of the box with only a slight adjustment to the minimum maintained pressure to accommodate the twin chillers minimum flow requirement. What is not shown in this picture is the two chillers and twin buffer capacity tanks and expansion control tank. There’s a lot of equipment in this little room! 4302 8x8x10-20 hp DualArm DE-IVS Sensorless unit we sold this past year. The DualArm IVS Sensorless pump has been in operation for almost ¾’s of a year. We took out an old water source Air Handler replacing it with a chilled water AHU, Twin Chillers, the IVS dual Arm, a buffer capacity tank, air purger and expansion tank all in the same room we took the old AHU out of…No small task. It worked right out of the box with only a slight adjustment to the minimum maintained pressure. The original set point was below the chillers minimum flow requirement. Otherwise – Flawless! RIGHT: SHOREWOOD PACKAGING, Danville, VA If no floor space, mount the pumps off the ground!! Commercial real estate cost $120/ sq ft, +50% Joe’s numbers on wall mounting?
  3. Armstrong Vertical inline pumps with Design Envelope IVS integrated controls. Series 4300 pumps are available up to 350 hp with integrated controls. Series 4380 close-coupled pumps are available up to 7.5 hp with integrated controls.
  4. Impeller trims are optimized to the motor power at the pump BEP. What exactly does that mean? It means we look for the intersection of the motor bhp line with the pump BEP and set our impeller trim to that motor. In this example, a 6x6x11.5 pump 40 hp uses an 11.50” impeller 30 hp uses a 11.44” impeller 25 hp uses a 10.78” impeller And a 20 hp uses a 10.00” impeller Any operating point in between the pre-set impeller trims is achieved by varying the speed. Why don’t we use the largest impeller?... This is the most efficient trim… This is true hydraulically. But through testing and experience, we found that the common asynchronous motor torque is not constant and at lower frequencies typically around 48Hz, the mechanical losses start to have an effect. Thus we have distinct impeller trims for each motor. Harmonics => 25/30 = 16.6% (no dollar cost per Danfoss) Total harmonic distortion reduction. *NOTE if anyone asks: impeller trims are based on water. For other fluids, the trim diameter is different.
  5. This page looks at the starting currents for an AC motor. Remember that the more abrupt and higher the current start, the greater the wire sizing, to handle the current, the greater the possibility of demand charges and the greater the threat of water hammer, and broken pipes. Direct-On-Line: or “across the line” is the oldest way to start a pump. The power required to start the pump can go as high as 700% as shown above. As the pump approaches 60Hz the current drops. Start/Delta : One method to control the current is to shift between the motor coil configurations. The Star configuration is used to start the motor. When the motor reaches close to maximum speed, say 45Hz, a relay switches the configuration from a Star to Delta. Soft-Starters : These devices can be either electric timers which monitor and limit the voltage or they can be electronic which monitors and limits the current. Since these devices only control the voltage or the current, many of them can not be used for long periods of time, and usually can not exceed 30 seconds. VFDs : Control both the frequency and the voltage simultaneously. This gives full control over the acceleration and deceleration ramps. This is the best method of starting or stopping a pump but it is also, in most applications, the most expensive.
  6. Peak amp draw = 35.1 FLA x start-up % kW = Peak amp draw x 460V / 1000 Demand charge = $/kW
  7. A long list of savings that adds up to a LCC and a true value based offering.
  8. In a 3 pump system shown here (NOTE: We don’t show the VFDs on the wall or integrated on the motor) But we eliminate the flex connectors, the concrete bases, inertia pads, no realignment of the flex coupling during commissioning. HSC versus VIL Assume 3 pump system - 6x5x12 versus 6x6x11.5 (2-duty / 1-standby) Installation cost = $19,572 vs $8,327 105.7 sf vs 44.2 sf; diff. = 61.5 sf and if we assume $150 / sf, that’s $9,225
  9. LEFT: BAYFRONT TOWERS, Tampa, FL Compact mechanical room with no space for two individual pumps and no space to mount drives on the wall. Simple single large AHU avoided using DP sensor by using sensorless design. Pumps also have auto alternating feature. Worked out of the box with only a slight adjustment to the minimum maintained pressure to accommodate the twin chillers minimum flow requirement. What is not shown in this picture is the two chillers and twin buffer capacity tanks and expansion control tank. There’s a lot of equipment in this little room! 4302 8x8x10-20 hp DualArm DE-IVS Sensorless unit we sold this past year. The DualArm IVS Sensorless pump has been in operation for almost ¾’s of a year. We took out an old water source Air Handler replacing it with a chilled water AHU, Twin Chillers, the IVS dual Arm, a buffer capacity tank, air purger and expansion tank all in the same room we took the old AHU out of…No small task. It worked right out of the box with only a slight adjustment to the minimum maintained pressure. The original set point was below the chillers minimum flow requirement. Otherwise – Flawless! RIGHT: SHOREWOOD PACKAGING, Danville, VA If no floor space, mount the pumps off the ground!! Commercial real estate cost $120/ sq ft, +50% Joe’s numbers on wall mounting?
  10. The VILs present a huge opportunity for pipe savings as they can be mounted directly to the chillers, boilers, and cooling towers. On average the pipe savings are reduced by 40-50%. Here’s an example of a plant room optimization for Glendale Arena, home of the Phoenix Coyotes. On the left are HSC. On the right the VILs are mounted directly onto the chillers saving 43% of piping. In this case, the pipe savings pretty well paid for the pumps. Ran AOL 2400 gpm @ 50 ft vs 2400 gpm @ 80 ft and looked at difference in op cost. 14477 vs 7893 = $6600.
  11. The most common replaced item on pumps is the mechanical seal. Seal changeout is much faster 30mins versus 2 hrs compared to base-mount. Also 4300 VILs don’t use bearings which dramatically reduces failures and maintenance costs.
  12. A long list of savings that adds up to a LCC and a true value based offering.