SlideShare a Scribd company logo
Further Design Envelope pumping value
vs. end suction pump
                              •   First cost savings
                              •   Pipe savings
                              •   Floor Space savings
                              •   Maintenance Savings
                              •   Savings on reselection




                        VS.




Brazil Visit 2012
End suction pump installation



                                •   Coupling re-alignment
                                •   Grouting
                                •   Inertia pad
                                •   Concrete base
                                •   Flex connectors




Brazil Visit 2012
Design Envelope – values & benefits
First cost savings

                    3 pump system              3 pump system VIL
                    Horizontal Split Case      0611-030.0
                    150x120x300




                                                                             Savings
 Installation                      $19,572                    $8,327
 cost                                                                    $11,245
                                                                                (=57%)
 Floor space                    105.7 sq. ft               44.2 sq. ft
                                                                           $9,225
                                                                         ($150 / sq. ft)

Brazil Visit 2012
Design Envelope – values & benefits
Floor space savings




Brazil Visit 2012
Design Envelope – values & benefits
Pipe savings (Glendale Arena, Phoenix)

                                                              Less pipe = less friction
                                                              loss
                                                              resulting in operating cost
                                                              savings:
                                                              $6,600
                                                              (est. from TDH reduction)




                                                                  Savings
  Piping                   $225,975             $128,960
  cost                                                        $97,015
                                                                    (= 43%)
  Length                     2751 ft              1723 ft
  of pipe           (2751/100=27.51x     (1723/100=17.23x      1028 ft
                      3’tdh=82.53’tdh)     3’tdh=51.69’tdh)

Brazil Visit 2012
Design Envelope – values & benefits
Maintenance savings (Edmonton Airport)




$8200 annual savings
due to faster mechanical seal changes


Brazil Visit 2012
Design Envelope IVS – Why You Should Use It


•   Energy savings
•   First cost savings
•   Motor / control / sizing   More than     20%
•   Pipe savings               first cost savings
•   Floor space savings
•   Maintenance savings        More than     30%
•   Wiring savings             life cycle cost savings
•   Harmonic control savings
•   Sensorless savings         on a 6” Design Envelope IVS pump
                               compared to end-suction with VFD
•   Commissioning savings      on wall (doesn’t include pipe savings)
•   Flow/energy metering
•   Savings on re-selections



Brazil Visit 2012
Legislative Compliance


•      Design Envelope IVS (DIN / IEC configuration) pumps conform to
       2013 AND 2015 requirements in Europe (MEI 0.4)
•      Motor control combination is 2017 legislation compliant
•      Constant speed circulators are generally illegal in Europe ( 20 to
       2500) beginning January 2013
•      DOE in USA has indicated it’s intension to legislate pump
       efficiency
          •     My prediction is constant speed pumping will be illegal in
                the future




    Brazil Visit 2012
Design Envelope IVS Pumping Suite

4300                   4302          4380          4382




Indoors
Integrated to 350hp       to 100hp      to 7.5hp      to 7.5hp
Standalone 400-1250hp

Outdoors
Integrated to 125hp       to 100hp      to 7.5hp      to 7.5hp



   Brazil Visit 2012
Introduction
    DualArm / Twin Pump =   2 rotating assemblies
    in     1 casing




Brazil Visit 2012
Differences from dualARM

Casings



                    Twin                   DualARM




No handles – flapper on discharge   Valve handles & locking mechanism
only                                on both suction and discharge



Brazil Visit 2012
Differences dualARM / Twin
   Functionality
                      Hydraulics          Duty-       Parallel    Oversized   Isolation   Servicing
                                          standby     operation   ports       valve
                                          operation
                      ● up to 1,300 gpm
                      ● up to 120 ft                                                        Blank
   Twin               ● up to 40 hp
                                                                                        plate
                                                                                          required

                      ● up to 1,500 gpm
                      ● up to 400 ft
dualARM               ● up to 100 hp
                                                                                        Valve
                                                                                          isolation




  Brazil Visit 2012
Differences from dualARM

Servicing
                    Twin                    DualARM




                           Blanking plate

                                            Valve isolation
                                            Use handles to lock


Brazil Visit 2012
Twin or dualARM – Which one to use?


         Feature              Twin   DualARM

         Redundancy                   
         Parallel operation           
         Critical service
         no down-time                 
         High pressure                

Brazil Visit 2012
Key values & benefits


•Redundancy
•Compact
•Installation savings




Brazil Visit 2012
Key values & benefits
Redundancy

• HVAC pump systems are
  typically designed as N+1
  (where N = number of pumps)
• The “+1” is to ensure
  redundancy
• These systems operate in duty-
  standby mode only




Brazil Visit 2012
Key values & benefits
Compact




• One of the smallest footprints in the industry compared to
  other pump configurations
• In some units, flange-to-flange is less than a single VIL

Brazil Visit 2012
Twin pump – values & benefits
Floor space savings



                      dualARM




                                       Twin
    End
    suctions


                                VILs
Brazil Visit 2012
Twin pump – values & benefits
  Floor space savings

                                                            Ratio to end suction
                           Model        Footprint (sq-ft)
                                                                   pump

                       4030 3x2.5x8
2 End suctions
                       w/ 5hp motor        25.0                  1.00

             2 VILs   4300 0308-005.0      10.9                  0.44

      dualARM         4302 0408-005.0        8.7                 0.35

             Twin     4312 0308-005.0        6.4                0.26

  Brazil Visit 2012
Twin pump – values & benefits
Installation savings

                    2 pump system              1 Design Envelope IVS
                    End Suction units          Twin pumping unit
                    3x2.5x8                      4312 0308-005.0
                                                                         No coupling re-
                                                                         alignment
                                                                         No grouting
                                                                         No inertia base
                                                                         No concrete pad
                                                                         No flex connectors

                                                                             Savings
  Installation                      $5,136                    $2,010
  cost                                                                     $3,126
                                                                                (= 61%)
  Floor space                    25.0 sq. ft                6.4 sq. ft
                                                                           $2,790
                                                                         ($150 / sq. ft)

Brazil Visit 2012
Differences from dualARM

                     Price   Footprint



      Twin          1.10     0.60
dualARM             1.50     0.80

      2 VILs        1.00     1.00




Brazil Visit 2012
Sensorless Agenda

• Traditional control with sensors
• Sensorless control
   • Introduction
   • Factory loading of program map
   • Benefits of Sensorless control over sensors
• Sensorless in action (video)
• Case study – Canada Square Building Retrofit




Brazil Visit 2012
Design Envelope – Sensorless Control




Brazil Visit 2012
Traditional Control with
Differential Pressure Sensor

Pump, VFD, and sensor to control HVAC systems




Brazil Visit 2012
Traditional Control with
Differential Pressure Sensor
                               Possible sensor locations
                               1)Mechanical room
                               2)Remote load
                               3)Other




Brazil Visit 2012
Sensor Location – In Mechanical Room
(Variable Flow Secondary)




  Local
  Differential
  Pressure sensor

  (In Mech Room)




Brazil Visit 2012
Sensor Location – In Mechanical Room




                                       Supply
                                       Return




                    Sensor

Brazil Visit 2012
Sensor Location – In Mechanical Room
                                                                                 Cooling coils
                                                                                 (Typical)
        Head




                    Design Speed

            B       50% Load Speed
                                              A
                Operating Curve
                                                                         with DP sensor
Min. Head




                                                                          Pumps




                                  System                      A   Design Point

                                                              B   Minimum Head
                     50% Load Flow     Design Flow

  Minimum Head equates to sensor setting across the pump in traditional system
Brazil Visit 2012
Sensor Location – Remote Load




  Remote
  Differential
  Pressure sensor
  (Most remote
  load)




Brazil Visit 2012
Sensor location – Remote load
                                                                                   Cooling coils
                                                                                   (Typical)

                                                                             with DP sensor
       Head




                          Design Speed

                                                 A



                50% Load Speed urve  ve
                              l C ur
                                C
                           tro
                         nting
                                                                             Pumps
            B          Coa
                       er
                     Op
Min. Head




                                     System                     A   Design Point

                                                                B   Minimum Head
                         50% Load Flow    Design Flow
 Minimum Head equates to sensor setting at remote cooling coil in traditional system

     Brazil Visit 2012
Design Envelope – Values & Benefits
Operating Cost Savings

                                                 Power       Energy Savings
                             Constant speed
                         A                       32.03   Incremental Cumulative
                             throttled
                             Reduced speed
                         B   unthrottled –       27.11      15%         15%
                             constant flow
                             Reduced
                         C   constant speed –    19.36      29%         40%
                             variable flow
                             Variable speed –
                         D   variable flow –     14.35      26%         55%
                             Mech. Room Sensor
                             Design Envelope
                         E                       7.32       49%         77%
                             sensorless




Brazil Visit 2012
Design Envelope IVS
Operating Cost Savings

Total Cost = Operating Cost (3 yrs) + First Cost

                                                   Design Envelope
                                                   Savings:
                                                   More than  60%
                                                   vs. throttled

                                                   More than  35%

                                     Envelope
                                      Design
                                                   vs. mech. room sensor




Brazil Visit 2012
Sensorless Control




                     Sensorless control
                     Featured on Armstrong Design
                     Envelope pumps



Brazil Visit 2012
Sensorless Control

Mimics the performance of a
sensor by pre-programming
pump curve characteristics
into the IVS controls




Brazil Visit 2012
Sensorless Control

Works based on
4 parameters
•Power
•Speed
•Head
•Flow




Brazil Visit 2012
Sensorless Program Mapping


•Power, speed, flow
 and head are
 recorded from
 pump test.

•All Sensorless data
 from every pump is
 recorded and kept
 on file in database


Brazil Visit 2012
Sensorless Program Mapping


                  Series 4300
                  Design Envelope 0611-030.0
                  6x6x11.5 @ 11.44 in
            160
                      1848 rpm   57
            140                          68     77
                                                      82
                                                             84
            120                                                   85
                      1621 rpm                                         84
                                                                            82
            100                                                                   77
Head (ft)




                                                                                        68
             80

             60
                                                                                       30 hp
             40                         Control curve
            20
                      528 rpm


                  0        0.2    0.4         0.6      0.8         1        1.2          1.4   1.6
                                                     Flow (1,000 usgpm)




  Brazil Visit 2012
Sensorless Program Mapping

Design Envelope Series 4300 0611-030.0
       Design point = 1000 gpm at 80 ft


                     Flow   Head    Power   Frequency
                    (gpm)    (ft)   (bhp)      (Hz)
                    1000    80.0    25.2      55.3
                    900     70.9    19.8      51.2
                    800     62.7    15.2      47.3




Brazil Visit 2012
Sensorless Control – Detailed
                                                                            How do we get from 1 to 2?
Head




                                                    Original System Curve

                                               1                             1 Satisfied Flow & Head Operating
                                   2                                           Point (S1 System Curve)
        Control Curve                                                        S1 Operating Speed pump curve
                                                                 S1
           S2 System Curve
                                                                             P1 Power at current flow & head
                             S1 System Curve               S2
                                                                              2 Satisfied Flow & Head Operating
Power




                                                                                Point (S2 System Curve)

                                                                             S2 Operating Speed pump curve
                                               P1
                                   P2                       Flow             P2 Power at current flow & head
        Traditional Control
        Sensorless
        Operating point is wherever pump performance
                           where pump performance,
        curve intersects system resistance curve
        system resistance and control curves converge

   Brazil Visit 2012
Sensorless control – detailed
                                                                                Sensorless data

                                                                                 Flow    Head     Power   Freq.
                                                                                (gpm)     (ft)    (bhp)   (Hz)
                                                  Original System Curve
                                                                                 1000     80.0    25.2    55.3
                                                                                 900     70.9     19.8    51.2

                                                                                Constant speed
                                             1
                                                                                 900     88.0     23.8    55.3
                      S2 System Curve


                                                                               How we get from 1 to 2
                                                                               Speed is stable at 1 until system
                          2                                                    control valves (CV) modulate.
                                                                          S1
          urve                          S1 System Curve

    trol C                                                                     System has CV modulating
Con                                                                            closed resulting in a steeper S2
                                                                               system curve

                                                                               Reverses as CVs open


                                                            S2
  Brazil Visit 2012
Adjusting Sensorless On Site

3 parameters to adjust Sensorless control curve on site


                    Head




                                                Flow




Brazil Visit 2012
Sensorless on site

Payback on pump starts as soon as it is installed; no need to
wait months for controls contractor

                          4300 0611-030.0
                          Cost of pump = $9,702 USD
                          Assume $0.10/kWh
                          Variable flow-constant sp. op = $10,312/yr
                          Variable flow-variable sp. op = $6,145/yr
                          Savings = $4,167/yr


                          3 month savings =    $1,389
                          Or   14% of the pump cost!

Brazil Visit 2012
Sensorless for parallel pumping

Currently only available for single pump operation systems

                                     Sensorless for parallel
                                     pumping systems…


                                     Coming soon




Brazil Visit 2012
Case Study: Canada Square Building Retrofit

                               Background
                               •Constructed in 1972
                               •18 floor office tower
                               •37,000 m2 of commercial
                               office space.
                               •Armstrong supplied the VIL
                               pumps for initial
                               construction




Brazil Visit 2012
Brazil Visit 2012
Case Study: Canada Square Building Retrofit
Execution
• Original pumps 4300 6G 1700 gpm at
  140 ft, 75 hp
• Design Envelope 4300 IVS 1700 gpm
  at 136 ft, 75 hp

• Design Envelope IVS allowed designer
    to match pump performance to actual
    system conditions.
     Actual system HDesign = 85 ft (53Hz)

• Design Envelope IVS pump provided
    50% energy savings
•   Cost savings of $38,000 per year




Brazil Visit 2012
Summary of Sensorless Benefits

• Energy savings of 49% over mechanical room sensor
• Reduces installation time & cost
   • No wiring
   • No conduit
   • Savings of $2000
              Intelligence for your
• Eliminates potential problems with sensors


       Calibration pumping system
   •   Sensor failure
   •
   • Forgetting where it is located
• Easy on-site balancing and immediate energy savings
   • Readjust the setpoint from the IVS
   • No wait for controls commissioning
• Ideal for retrofit projects
• Can send Sensorless data to the BMS
Brazil Visit 2012
Design Envelope IVS Pumping
Around the World




                    King’s Yard Energy Centre / Olympic Park
                                                London, UK

Brazil Visit 2012
ASHRAE 90.1 and Armstrong Solutions

ASHRAE 90.1                         Armstrong Solution
Proportional Balancing              • Design Envelope Pumps with
                                       • Easy adjustment of design head
                                       • Armstrong balancing valves
                                       • Flo-Trex Valves
                                              • Throttling IF and WHEN
                                                needed
                                                (saves expensive retrofit)

Need to achieve 70% less power at   • Design Envelope Pumps with
50% flow in CW pumping Systems         • Correct lowest operating cost
                                         selections
                                       • Easy control
                                          • Sensorless
                                          • Armstrong controls
                                          • BMS
                                          • Sensored

Larger Pipe Avoided                 With Design Envelope Pumps

All Pumps over 1 HP (3/4 kw) should have integrated controls!
Brazil Visit 2012
Design Envelope Pressure Boosters

                     • Lowest Energy
                        • VMS more efficiency than single
                          stage
                        • Utilizes suction design over
                          design for energy savings
                        • Pressure set back
                     • Lowest life cost
                        • Flush valves lasted longer due to
                          lower constant pressures
                        • Slower speed and pressure
                          swings improves equipment life,
                          reduced maintenance and noise
                          from slower speeds, no pressure
                          swings / PRV’s
                        • Security -Safe fill mode
                        • No bypass maintenance -Design
                          Envelope Booster has electronic
                          control




Brazil Visit 2012
Design Envelope IVS Pumping


     •ASHRAE 90.1 Conformance
     •         PLUS
     •Lowest Installed Cost
     •Lowest Life Cycle Cost




Brazil Visit 2012
Summary
• Design Envelope thinking
• All pumping should have integrated
 controls. (constant speed pumping is
 obsolete and soon to be illegal)
   • HVAC and Pressure booster pumps
• Design Envelope pumps are selected to
  right of pump best efficiency point in a
  simplified / risk free method
• Use Vertical Inline pumps, suction
  guides and Flotrex valves
• Twin and DualArm provide even lower
  cost and space
• If conventional controls valves used –
  Use manual balancing valves


   • Lowest first cost
   • Lowest energy and life
       cost
Brazil Visit 2012

More Related Content

What's hot

Lighting , case study & specification
Lighting , case study & specificationLighting , case study & specification
Lighting , case study & specification
Abhiniti Garg
 
Hydronic heating & cooling system design presentation
Hydronic heating &  cooling system design presentationHydronic heating &  cooling system design presentation
Hydronic heating & cooling system design presentation
kshitiz pandit
 
Urban Data Platform Vienna
Urban Data Platform ViennaUrban Data Platform Vienna
Urban Data Platform Vienna
Stadt Wien
 
Lucknow
LucknowLucknow
Lucknow
Sunita Sinha
 
SERVICES
SERVICESSERVICES
SERVICES
SmritiGupta102
 
solar passive system for buildings
solar passive system  for buildingssolar passive system  for buildings
solar passive system for buildings
Garima Sharma
 
Solar thermal modeling - IES-VE
Solar thermal modeling - IES-VESolar thermal modeling - IES-VE
Solar thermal modeling - IES-VE
Anantharaman K
 
Power scenerio in india
Power scenerio in indiaPower scenerio in india
Power scenerio in india
Charanjiv Singh
 
Axial Pump Senatorlibya
Axial Pump SenatorlibyaAxial Pump Senatorlibya
Axial Pump Senatorlibya
Assistant Mechanical Engineer
 
WALMI Bhopal final.pptx
WALMI Bhopal final.pptxWALMI Bhopal final.pptx
WALMI Bhopal final.pptx
ChinmoyGhosh40
 
Energy efficient hvac
Energy efficient hvac Energy efficient hvac
Vapour Absorption Refrigeration System
Vapour Absorption Refrigeration SystemVapour Absorption Refrigeration System
Vapour Absorption Refrigeration System
Jaswanth Gejjala
 
Dc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and TipsDc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and Tips
Simon MECO FanCoil Unit
 
Air conditioning introduction
Air conditioning introductionAir conditioning introduction
Air conditioning introduction
tyeman1
 

What's hot (14)

Lighting , case study & specification
Lighting , case study & specificationLighting , case study & specification
Lighting , case study & specification
 
Hydronic heating & cooling system design presentation
Hydronic heating &  cooling system design presentationHydronic heating &  cooling system design presentation
Hydronic heating & cooling system design presentation
 
Urban Data Platform Vienna
Urban Data Platform ViennaUrban Data Platform Vienna
Urban Data Platform Vienna
 
Lucknow
LucknowLucknow
Lucknow
 
SERVICES
SERVICESSERVICES
SERVICES
 
solar passive system for buildings
solar passive system  for buildingssolar passive system  for buildings
solar passive system for buildings
 
Solar thermal modeling - IES-VE
Solar thermal modeling - IES-VESolar thermal modeling - IES-VE
Solar thermal modeling - IES-VE
 
Power scenerio in india
Power scenerio in indiaPower scenerio in india
Power scenerio in india
 
Axial Pump Senatorlibya
Axial Pump SenatorlibyaAxial Pump Senatorlibya
Axial Pump Senatorlibya
 
WALMI Bhopal final.pptx
WALMI Bhopal final.pptxWALMI Bhopal final.pptx
WALMI Bhopal final.pptx
 
Energy efficient hvac
Energy efficient hvac Energy efficient hvac
Energy efficient hvac
 
Vapour Absorption Refrigeration System
Vapour Absorption Refrigeration SystemVapour Absorption Refrigeration System
Vapour Absorption Refrigeration System
 
Dc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and TipsDc inverter vrf installation instructions and Tips
Dc inverter vrf installation instructions and Tips
 
Air conditioning introduction
Air conditioning introductionAir conditioning introduction
Air conditioning introduction
 

Viewers also liked

Ashrae 90.1 and the future of pumping part 1
Ashrae 90.1 and the future of pumping part 1Ashrae 90.1 and the future of pumping part 1
Ashrae 90.1 and the future of pumping part 1
ArmstrongIntegrated
 
Refrigeration Piping Handbook Dupont
Refrigeration Piping Handbook DupontRefrigeration Piping Handbook Dupont
Refrigeration Piping Handbook Dupont
Luiz Carlos Martinelli Júnior
 
What is ASHRAE 90.1?
What is ASHRAE 90.1?What is ASHRAE 90.1?
What is ASHRAE 90.1?
CannonDesign
 
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
Norrazman Zaiha Zainol
 
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th EdHeating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
aakumawa
 
piping design engineering by hamed motlagh
piping design engineering by hamed motlaghpiping design engineering by hamed motlagh
piping design engineering by hamed motlagh
Hamed Motlagh
 
[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii
Luis Luis
 
Centrifugal pump lecture 1
Centrifugal pump lecture 1Centrifugal pump lecture 1
Centrifugal pump lecture 1
Rahul Singhal
 
Astronomy slideshow
Astronomy slideshowAstronomy slideshow
Astronomy slideshow
aimorales
 
Introduction to Pumps
Introduction to PumpsIntroduction to Pumps
Introduction to Pumps
mohdalaamri
 
Astronomy
AstronomyAstronomy
Cooling load calculations
Cooling load calculationsCooling load calculations
Cooling load calculations
Waleed Alyafie
 
Centrifugal pump
Centrifugal pumpCentrifugal pump
Centrifugal pump
Tarun Kumar
 
Centrifugal Pump
Centrifugal PumpCentrifugal Pump
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Varun Patel
 
Piping engineering guide
Piping engineering guidePiping engineering guide
Piping engineering guide
ram111eg
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
hvactrg1
 
Isometric projections for engineering students
Isometric projections for engineering studentsIsometric projections for engineering students
Isometric projections for engineering students
Akshay Darji
 
Complete Astronomy Unit PPT
Complete Astronomy Unit PPTComplete Astronomy Unit PPT
Complete Astronomy Unit PPT
West Hollow MS Ms. Gill
 
Thermodynamics Chapter 3- Heat Transfer
Thermodynamics Chapter 3- Heat TransferThermodynamics Chapter 3- Heat Transfer
Thermodynamics Chapter 3- Heat Transfer
VJTI Production
 

Viewers also liked (20)

Ashrae 90.1 and the future of pumping part 1
Ashrae 90.1 and the future of pumping part 1Ashrae 90.1 and the future of pumping part 1
Ashrae 90.1 and the future of pumping part 1
 
Refrigeration Piping Handbook Dupont
Refrigeration Piping Handbook DupontRefrigeration Piping Handbook Dupont
Refrigeration Piping Handbook Dupont
 
What is ASHRAE 90.1?
What is ASHRAE 90.1?What is ASHRAE 90.1?
What is ASHRAE 90.1?
 
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
2012 ASHRAE HANDBOOK: HVAC SYSTEMS AND EQUIPMENT
 
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th EdHeating, Ventilating and Air Conditional: Analysis and Design 6th Ed
Heating, Ventilating and Air Conditional: Analysis and Design 6th Ed
 
piping design engineering by hamed motlagh
piping design engineering by hamed motlaghpiping design engineering by hamed motlagh
piping design engineering by hamed motlagh
 
[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii[Point] pipe stress analysis by computer-caesar ii
[Point] pipe stress analysis by computer-caesar ii
 
Centrifugal pump lecture 1
Centrifugal pump lecture 1Centrifugal pump lecture 1
Centrifugal pump lecture 1
 
Astronomy slideshow
Astronomy slideshowAstronomy slideshow
Astronomy slideshow
 
Introduction to Pumps
Introduction to PumpsIntroduction to Pumps
Introduction to Pumps
 
Astronomy
AstronomyAstronomy
Astronomy
 
Cooling load calculations
Cooling load calculationsCooling load calculations
Cooling load calculations
 
Centrifugal pump
Centrifugal pumpCentrifugal pump
Centrifugal pump
 
Centrifugal Pump
Centrifugal PumpCentrifugal Pump
Centrifugal Pump
 
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
Piping Training course-How to be an Expert in Pipe & Fittings for Oil & Gas c...
 
Piping engineering guide
Piping engineering guidePiping engineering guide
Piping engineering guide
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
Isometric projections for engineering students
Isometric projections for engineering studentsIsometric projections for engineering students
Isometric projections for engineering students
 
Complete Astronomy Unit PPT
Complete Astronomy Unit PPTComplete Astronomy Unit PPT
Complete Astronomy Unit PPT
 
Thermodynamics Chapter 3- Heat Transfer
Thermodynamics Chapter 3- Heat TransferThermodynamics Chapter 3- Heat Transfer
Thermodynamics Chapter 3- Heat Transfer
 

Similar to Ashrae 90.1 and the future of pumping part 2

Fxlq
FxlqFxlq
Fxlq
tiger1202
 
Garden denver
Garden denverGarden denver
Garden denver
Eric Hernández
 
Renova: Turborex Freios
Renova: Turborex FreiosRenova: Turborex Freios
Renova: Turborex Freios
mdedal
 
Renova turborex brakes freios pneumaticos
Renova turborex brakes freios pneumaticosRenova turborex brakes freios pneumaticos
Renova turborex brakes freios pneumaticos
mdedal
 
Fxuq
FxuqFxuq
Fxuq
tiger1202
 
ROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTION
ROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTIONROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTION
ROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTION
iQHub
 
KBDF AC Drive Sales Sheet
KBDF AC Drive Sales SheetKBDF AC Drive Sales Sheet
KBDF AC Drive Sales Sheet
KB Electronics, Inc
 
Selecting the right pump for the application
Selecting the right pump for the applicationSelecting the right pump for the application
Selecting the right pump for the application
Brian Gongol
 
Apbu Casing Drilling Review Dec2010
Apbu  Casing Drilling Review Dec2010Apbu  Casing Drilling Review Dec2010
Apbu Casing Drilling Review Dec2010
CalHolt
 
Caterpillar Tier 4 Final Customer Presentation11.17.pptx
Caterpillar Tier 4 Final Customer Presentation11.17.pptxCaterpillar Tier 4 Final Customer Presentation11.17.pptx
Caterpillar Tier 4 Final Customer Presentation11.17.pptx
MiguelGutierrez218105
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
Greg Stover
 
Product Family
Product FamilyProduct Family
Product Family
Dan Valentino
 
Ac890 Px Advanced Cooled
Ac890 Px Advanced CooledAc890 Px Advanced Cooled
Ac890 Px Advanced Cooled
ldgroves
 
iDiff 2008 conference #11 IP-Racine Barco
iDiff 2008 conference #11 IP-Racine   BarcoiDiff 2008 conference #11 IP-Racine   Barco
iDiff 2008 conference #11 IP-Racine Barco
Benoit Michel
 
Session 33 Henrik Tengstrand
Session 33 Henrik TengstrandSession 33 Henrik Tengstrand
Session 33 Henrik Tengstrand
Transportforum (VTI)
 
Mach 4
Mach 4Mach 4
Evapco Eco-Cooler Overview
Evapco Eco-Cooler OverviewEvapco Eco-Cooler Overview
Evapco Eco-Cooler Overview
CASAIRCO
 
Innovative projects in the refrigeration and Air Conditioning sector
Innovative projects in the refrigeration and Air Conditioning sector Innovative projects in the refrigeration and Air Conditioning sector
Innovative projects in the refrigeration and Air Conditioning sector
UNEP OzonAction
 
Sp1370 perkins
Sp1370 perkinsSp1370 perkins
Sp1370 perkins
SUNSHINE MACHINERY
 
DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...
DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...
DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...
DANA Steel Processing Industries LLC(UAE) / DANA Steels Pvt Ltd ( INDIA) (www.danagroups.com)
 

Similar to Ashrae 90.1 and the future of pumping part 2 (20)

Fxlq
FxlqFxlq
Fxlq
 
Garden denver
Garden denverGarden denver
Garden denver
 
Renova: Turborex Freios
Renova: Turborex FreiosRenova: Turborex Freios
Renova: Turborex Freios
 
Renova turborex brakes freios pneumaticos
Renova turborex brakes freios pneumaticosRenova turborex brakes freios pneumaticos
Renova turborex brakes freios pneumaticos
 
Fxuq
FxuqFxuq
Fxuq
 
ROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTION
ROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTIONROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTION
ROLE OF BIT STEERABLE SYSTEM IN PRODUCTION OPTIMIZATION & COST REDUCTION
 
KBDF AC Drive Sales Sheet
KBDF AC Drive Sales SheetKBDF AC Drive Sales Sheet
KBDF AC Drive Sales Sheet
 
Selecting the right pump for the application
Selecting the right pump for the applicationSelecting the right pump for the application
Selecting the right pump for the application
 
Apbu Casing Drilling Review Dec2010
Apbu  Casing Drilling Review Dec2010Apbu  Casing Drilling Review Dec2010
Apbu Casing Drilling Review Dec2010
 
Caterpillar Tier 4 Final Customer Presentation11.17.pptx
Caterpillar Tier 4 Final Customer Presentation11.17.pptxCaterpillar Tier 4 Final Customer Presentation11.17.pptx
Caterpillar Tier 4 Final Customer Presentation11.17.pptx
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Product Family
Product FamilyProduct Family
Product Family
 
Ac890 Px Advanced Cooled
Ac890 Px Advanced CooledAc890 Px Advanced Cooled
Ac890 Px Advanced Cooled
 
iDiff 2008 conference #11 IP-Racine Barco
iDiff 2008 conference #11 IP-Racine   BarcoiDiff 2008 conference #11 IP-Racine   Barco
iDiff 2008 conference #11 IP-Racine Barco
 
Session 33 Henrik Tengstrand
Session 33 Henrik TengstrandSession 33 Henrik Tengstrand
Session 33 Henrik Tengstrand
 
Mach 4
Mach 4Mach 4
Mach 4
 
Evapco Eco-Cooler Overview
Evapco Eco-Cooler OverviewEvapco Eco-Cooler Overview
Evapco Eco-Cooler Overview
 
Innovative projects in the refrigeration and Air Conditioning sector
Innovative projects in the refrigeration and Air Conditioning sector Innovative projects in the refrigeration and Air Conditioning sector
Innovative projects in the refrigeration and Air Conditioning sector
 
Sp1370 perkins
Sp1370 perkinsSp1370 perkins
Sp1370 perkins
 
DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...
DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...
DANA DOMESTIC WATER CHILLERS UAE OMAN QATAR BAHRAIN JORDAN SYRIA QATAR SAUDI ...
 

Recently uploaded

GNSS spoofing via SDR (Criptored Talks 2024)
GNSS spoofing via SDR (Criptored Talks 2024)GNSS spoofing via SDR (Criptored Talks 2024)
GNSS spoofing via SDR (Criptored Talks 2024)
Javier Junquera
 
Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024
Jason Packer
 
5th LF Energy Power Grid Model Meet-up Slides
5th LF Energy Power Grid Model Meet-up Slides5th LF Energy Power Grid Model Meet-up Slides
5th LF Energy Power Grid Model Meet-up Slides
DanBrown980551
 
Introduction of Cybersecurity with OSS at Code Europe 2024
Introduction of Cybersecurity with OSS  at Code Europe 2024Introduction of Cybersecurity with OSS  at Code Europe 2024
Introduction of Cybersecurity with OSS at Code Europe 2024
Hiroshi SHIBATA
 
Programming Foundation Models with DSPy - Meetup Slides
Programming Foundation Models with DSPy - Meetup SlidesProgramming Foundation Models with DSPy - Meetup Slides
Programming Foundation Models with DSPy - Meetup Slides
Zilliz
 
[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...
[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...
[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...
Jason Yip
 
GraphRAG for LifeSciences Hands-On with the Clinical Knowledge Graph
GraphRAG for LifeSciences Hands-On with the Clinical Knowledge GraphGraphRAG for LifeSciences Hands-On with the Clinical Knowledge Graph
GraphRAG for LifeSciences Hands-On with the Clinical Knowledge Graph
Neo4j
 
Main news related to the CCS TSI 2023 (2023/1695)
Main news related to the CCS TSI 2023 (2023/1695)Main news related to the CCS TSI 2023 (2023/1695)
Main news related to the CCS TSI 2023 (2023/1695)
Jakub Marek
 
Northern Engraving | Nameplate Manufacturing Process - 2024
Northern Engraving | Nameplate Manufacturing Process - 2024Northern Engraving | Nameplate Manufacturing Process - 2024
Northern Engraving | Nameplate Manufacturing Process - 2024
Northern Engraving
 
Digital Banking in the Cloud: How Citizens Bank Unlocked Their Mainframe
Digital Banking in the Cloud: How Citizens Bank Unlocked Their MainframeDigital Banking in the Cloud: How Citizens Bank Unlocked Their Mainframe
Digital Banking in the Cloud: How Citizens Bank Unlocked Their Mainframe
Precisely
 
Apps Break Data
Apps Break DataApps Break Data
Apps Break Data
Ivo Velitchkov
 
Nordic Marketo Engage User Group_June 13_ 2024.pptx
Nordic Marketo Engage User Group_June 13_ 2024.pptxNordic Marketo Engage User Group_June 13_ 2024.pptx
Nordic Marketo Engage User Group_June 13_ 2024.pptx
MichaelKnudsen27
 
Principle of conventional tomography-Bibash Shahi ppt..pptx
Principle of conventional tomography-Bibash Shahi ppt..pptxPrinciple of conventional tomography-Bibash Shahi ppt..pptx
Principle of conventional tomography-Bibash Shahi ppt..pptx
BibashShahi
 
JavaLand 2024: Application Development Green Masterplan
JavaLand 2024: Application Development Green MasterplanJavaLand 2024: Application Development Green Masterplan
JavaLand 2024: Application Development Green Masterplan
Miro Wengner
 
9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...
9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...
9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...
saastr
 
Choosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptxChoosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptx
Brandon Minnick, MBA
 
Generating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and MilvusGenerating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and Milvus
Zilliz
 
Skybuffer SAM4U tool for SAP license adoption
Skybuffer SAM4U tool for SAP license adoptionSkybuffer SAM4U tool for SAP license adoption
Skybuffer SAM4U tool for SAP license adoption
Tatiana Kojar
 
zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...
zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...
zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...
Alex Pruden
 
The Microsoft 365 Migration Tutorial For Beginner.pptx
The Microsoft 365 Migration Tutorial For Beginner.pptxThe Microsoft 365 Migration Tutorial For Beginner.pptx
The Microsoft 365 Migration Tutorial For Beginner.pptx
operationspcvita
 

Recently uploaded (20)

GNSS spoofing via SDR (Criptored Talks 2024)
GNSS spoofing via SDR (Criptored Talks 2024)GNSS spoofing via SDR (Criptored Talks 2024)
GNSS spoofing via SDR (Criptored Talks 2024)
 
Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024Columbus Data & Analytics Wednesdays - June 2024
Columbus Data & Analytics Wednesdays - June 2024
 
5th LF Energy Power Grid Model Meet-up Slides
5th LF Energy Power Grid Model Meet-up Slides5th LF Energy Power Grid Model Meet-up Slides
5th LF Energy Power Grid Model Meet-up Slides
 
Introduction of Cybersecurity with OSS at Code Europe 2024
Introduction of Cybersecurity with OSS  at Code Europe 2024Introduction of Cybersecurity with OSS  at Code Europe 2024
Introduction of Cybersecurity with OSS at Code Europe 2024
 
Programming Foundation Models with DSPy - Meetup Slides
Programming Foundation Models with DSPy - Meetup SlidesProgramming Foundation Models with DSPy - Meetup Slides
Programming Foundation Models with DSPy - Meetup Slides
 
[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...
[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...
[OReilly Superstream] Occupy the Space: A grassroots guide to engineering (an...
 
GraphRAG for LifeSciences Hands-On with the Clinical Knowledge Graph
GraphRAG for LifeSciences Hands-On with the Clinical Knowledge GraphGraphRAG for LifeSciences Hands-On with the Clinical Knowledge Graph
GraphRAG for LifeSciences Hands-On with the Clinical Knowledge Graph
 
Main news related to the CCS TSI 2023 (2023/1695)
Main news related to the CCS TSI 2023 (2023/1695)Main news related to the CCS TSI 2023 (2023/1695)
Main news related to the CCS TSI 2023 (2023/1695)
 
Northern Engraving | Nameplate Manufacturing Process - 2024
Northern Engraving | Nameplate Manufacturing Process - 2024Northern Engraving | Nameplate Manufacturing Process - 2024
Northern Engraving | Nameplate Manufacturing Process - 2024
 
Digital Banking in the Cloud: How Citizens Bank Unlocked Their Mainframe
Digital Banking in the Cloud: How Citizens Bank Unlocked Their MainframeDigital Banking in the Cloud: How Citizens Bank Unlocked Their Mainframe
Digital Banking in the Cloud: How Citizens Bank Unlocked Their Mainframe
 
Apps Break Data
Apps Break DataApps Break Data
Apps Break Data
 
Nordic Marketo Engage User Group_June 13_ 2024.pptx
Nordic Marketo Engage User Group_June 13_ 2024.pptxNordic Marketo Engage User Group_June 13_ 2024.pptx
Nordic Marketo Engage User Group_June 13_ 2024.pptx
 
Principle of conventional tomography-Bibash Shahi ppt..pptx
Principle of conventional tomography-Bibash Shahi ppt..pptxPrinciple of conventional tomography-Bibash Shahi ppt..pptx
Principle of conventional tomography-Bibash Shahi ppt..pptx
 
JavaLand 2024: Application Development Green Masterplan
JavaLand 2024: Application Development Green MasterplanJavaLand 2024: Application Development Green Masterplan
JavaLand 2024: Application Development Green Masterplan
 
9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...
9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...
9 CEO's who hit $100m ARR Share Their Top Growth Tactics Nathan Latka, Founde...
 
Choosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptxChoosing The Best AWS Service For Your Website + API.pptx
Choosing The Best AWS Service For Your Website + API.pptx
 
Generating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and MilvusGenerating privacy-protected synthetic data using Secludy and Milvus
Generating privacy-protected synthetic data using Secludy and Milvus
 
Skybuffer SAM4U tool for SAP license adoption
Skybuffer SAM4U tool for SAP license adoptionSkybuffer SAM4U tool for SAP license adoption
Skybuffer SAM4U tool for SAP license adoption
 
zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...
zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...
zkStudyClub - LatticeFold: A Lattice-based Folding Scheme and its Application...
 
The Microsoft 365 Migration Tutorial For Beginner.pptx
The Microsoft 365 Migration Tutorial For Beginner.pptxThe Microsoft 365 Migration Tutorial For Beginner.pptx
The Microsoft 365 Migration Tutorial For Beginner.pptx
 

Ashrae 90.1 and the future of pumping part 2

  • 1. Further Design Envelope pumping value vs. end suction pump • First cost savings • Pipe savings • Floor Space savings • Maintenance Savings • Savings on reselection VS. Brazil Visit 2012
  • 2. End suction pump installation • Coupling re-alignment • Grouting • Inertia pad • Concrete base • Flex connectors Brazil Visit 2012
  • 3. Design Envelope – values & benefits First cost savings 3 pump system 3 pump system VIL Horizontal Split Case 0611-030.0 150x120x300 Savings Installation $19,572 $8,327 cost $11,245 (=57%) Floor space 105.7 sq. ft 44.2 sq. ft $9,225 ($150 / sq. ft) Brazil Visit 2012
  • 4. Design Envelope – values & benefits Floor space savings Brazil Visit 2012
  • 5. Design Envelope – values & benefits Pipe savings (Glendale Arena, Phoenix) Less pipe = less friction loss resulting in operating cost savings: $6,600 (est. from TDH reduction) Savings Piping $225,975 $128,960 cost $97,015 (= 43%) Length 2751 ft 1723 ft of pipe (2751/100=27.51x (1723/100=17.23x 1028 ft 3’tdh=82.53’tdh) 3’tdh=51.69’tdh) Brazil Visit 2012
  • 6. Design Envelope – values & benefits Maintenance savings (Edmonton Airport) $8200 annual savings due to faster mechanical seal changes Brazil Visit 2012
  • 7. Design Envelope IVS – Why You Should Use It • Energy savings • First cost savings • Motor / control / sizing More than 20% • Pipe savings first cost savings • Floor space savings • Maintenance savings More than 30% • Wiring savings life cycle cost savings • Harmonic control savings • Sensorless savings on a 6” Design Envelope IVS pump compared to end-suction with VFD • Commissioning savings on wall (doesn’t include pipe savings) • Flow/energy metering • Savings on re-selections Brazil Visit 2012
  • 8. Legislative Compliance • Design Envelope IVS (DIN / IEC configuration) pumps conform to 2013 AND 2015 requirements in Europe (MEI 0.4) • Motor control combination is 2017 legislation compliant • Constant speed circulators are generally illegal in Europe ( 20 to 2500) beginning January 2013 • DOE in USA has indicated it’s intension to legislate pump efficiency • My prediction is constant speed pumping will be illegal in the future Brazil Visit 2012
  • 9. Design Envelope IVS Pumping Suite 4300 4302 4380 4382 Indoors Integrated to 350hp to 100hp to 7.5hp to 7.5hp Standalone 400-1250hp Outdoors Integrated to 125hp to 100hp to 7.5hp to 7.5hp Brazil Visit 2012
  • 10. Introduction DualArm / Twin Pump = 2 rotating assemblies in 1 casing Brazil Visit 2012
  • 11. Differences from dualARM Casings Twin DualARM No handles – flapper on discharge Valve handles & locking mechanism only on both suction and discharge Brazil Visit 2012
  • 12. Differences dualARM / Twin Functionality Hydraulics Duty- Parallel Oversized Isolation Servicing standby operation ports valve operation ● up to 1,300 gpm ● up to 120 ft Blank Twin ● up to 40 hp     plate required ● up to 1,500 gpm ● up to 400 ft dualARM ● up to 100 hp     Valve isolation Brazil Visit 2012
  • 13. Differences from dualARM Servicing Twin DualARM Blanking plate Valve isolation Use handles to lock Brazil Visit 2012
  • 14. Twin or dualARM – Which one to use? Feature Twin DualARM Redundancy   Parallel operation   Critical service no down-time   High pressure   Brazil Visit 2012
  • 15. Key values & benefits •Redundancy •Compact •Installation savings Brazil Visit 2012
  • 16. Key values & benefits Redundancy • HVAC pump systems are typically designed as N+1 (where N = number of pumps) • The “+1” is to ensure redundancy • These systems operate in duty- standby mode only Brazil Visit 2012
  • 17. Key values & benefits Compact • One of the smallest footprints in the industry compared to other pump configurations • In some units, flange-to-flange is less than a single VIL Brazil Visit 2012
  • 18. Twin pump – values & benefits Floor space savings dualARM Twin End suctions VILs Brazil Visit 2012
  • 19. Twin pump – values & benefits Floor space savings Ratio to end suction Model Footprint (sq-ft) pump 4030 3x2.5x8 2 End suctions w/ 5hp motor 25.0 1.00 2 VILs 4300 0308-005.0 10.9 0.44 dualARM 4302 0408-005.0 8.7 0.35 Twin 4312 0308-005.0 6.4 0.26 Brazil Visit 2012
  • 20. Twin pump – values & benefits Installation savings 2 pump system 1 Design Envelope IVS End Suction units Twin pumping unit 3x2.5x8 4312 0308-005.0 No coupling re- alignment No grouting No inertia base No concrete pad No flex connectors Savings Installation $5,136 $2,010 cost $3,126 (= 61%) Floor space 25.0 sq. ft 6.4 sq. ft $2,790 ($150 / sq. ft) Brazil Visit 2012
  • 21. Differences from dualARM Price Footprint Twin 1.10 0.60 dualARM 1.50 0.80 2 VILs 1.00 1.00 Brazil Visit 2012
  • 22. Sensorless Agenda • Traditional control with sensors • Sensorless control • Introduction • Factory loading of program map • Benefits of Sensorless control over sensors • Sensorless in action (video) • Case study – Canada Square Building Retrofit Brazil Visit 2012
  • 23. Design Envelope – Sensorless Control Brazil Visit 2012
  • 24. Traditional Control with Differential Pressure Sensor Pump, VFD, and sensor to control HVAC systems Brazil Visit 2012
  • 25. Traditional Control with Differential Pressure Sensor Possible sensor locations 1)Mechanical room 2)Remote load 3)Other Brazil Visit 2012
  • 26. Sensor Location – In Mechanical Room (Variable Flow Secondary) Local Differential Pressure sensor (In Mech Room) Brazil Visit 2012
  • 27. Sensor Location – In Mechanical Room Supply Return Sensor Brazil Visit 2012
  • 28. Sensor Location – In Mechanical Room Cooling coils (Typical) Head Design Speed B 50% Load Speed A Operating Curve with DP sensor Min. Head Pumps System A Design Point B Minimum Head 50% Load Flow Design Flow Minimum Head equates to sensor setting across the pump in traditional system Brazil Visit 2012
  • 29. Sensor Location – Remote Load Remote Differential Pressure sensor (Most remote load) Brazil Visit 2012
  • 30. Sensor location – Remote load Cooling coils (Typical) with DP sensor Head Design Speed A 50% Load Speed urve ve l C ur C tro nting Pumps B Coa er Op Min. Head System A Design Point B Minimum Head 50% Load Flow Design Flow Minimum Head equates to sensor setting at remote cooling coil in traditional system Brazil Visit 2012
  • 31. Design Envelope – Values & Benefits Operating Cost Savings Power Energy Savings Constant speed A 32.03 Incremental Cumulative throttled Reduced speed B unthrottled – 27.11 15% 15% constant flow Reduced C constant speed – 19.36 29% 40% variable flow Variable speed – D variable flow – 14.35 26% 55% Mech. Room Sensor Design Envelope E 7.32 49% 77% sensorless Brazil Visit 2012
  • 32. Design Envelope IVS Operating Cost Savings Total Cost = Operating Cost (3 yrs) + First Cost Design Envelope Savings: More than 60% vs. throttled More than 35% Envelope Design vs. mech. room sensor Brazil Visit 2012
  • 33. Sensorless Control Sensorless control Featured on Armstrong Design Envelope pumps Brazil Visit 2012
  • 34. Sensorless Control Mimics the performance of a sensor by pre-programming pump curve characteristics into the IVS controls Brazil Visit 2012
  • 35. Sensorless Control Works based on 4 parameters •Power •Speed •Head •Flow Brazil Visit 2012
  • 36. Sensorless Program Mapping •Power, speed, flow and head are recorded from pump test. •All Sensorless data from every pump is recorded and kept on file in database Brazil Visit 2012
  • 37. Sensorless Program Mapping Series 4300 Design Envelope 0611-030.0 6x6x11.5 @ 11.44 in 160 1848 rpm 57 140 68 77 82 84 120 85 1621 rpm 84 82 100 77 Head (ft) 68 80 60 30 hp 40 Control curve 20 528 rpm 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 Flow (1,000 usgpm) Brazil Visit 2012
  • 38. Sensorless Program Mapping Design Envelope Series 4300 0611-030.0 Design point = 1000 gpm at 80 ft Flow Head Power Frequency (gpm) (ft) (bhp) (Hz) 1000 80.0 25.2 55.3 900 70.9 19.8 51.2 800 62.7 15.2 47.3 Brazil Visit 2012
  • 39. Sensorless Control – Detailed How do we get from 1 to 2? Head Original System Curve 1 1 Satisfied Flow & Head Operating 2 Point (S1 System Curve) Control Curve S1 Operating Speed pump curve S1 S2 System Curve P1 Power at current flow & head S1 System Curve S2 2 Satisfied Flow & Head Operating Power Point (S2 System Curve) S2 Operating Speed pump curve P1 P2 Flow P2 Power at current flow & head Traditional Control Sensorless Operating point is wherever pump performance where pump performance, curve intersects system resistance curve system resistance and control curves converge Brazil Visit 2012
  • 40. Sensorless control – detailed Sensorless data Flow Head Power Freq. (gpm) (ft) (bhp) (Hz) Original System Curve 1000 80.0 25.2 55.3 900 70.9 19.8 51.2 Constant speed 1 900 88.0 23.8 55.3 S2 System Curve How we get from 1 to 2 Speed is stable at 1 until system 2 control valves (CV) modulate. S1 urve S1 System Curve trol C System has CV modulating Con closed resulting in a steeper S2 system curve Reverses as CVs open S2 Brazil Visit 2012
  • 41. Adjusting Sensorless On Site 3 parameters to adjust Sensorless control curve on site Head Flow Brazil Visit 2012
  • 42. Sensorless on site Payback on pump starts as soon as it is installed; no need to wait months for controls contractor 4300 0611-030.0 Cost of pump = $9,702 USD Assume $0.10/kWh Variable flow-constant sp. op = $10,312/yr Variable flow-variable sp. op = $6,145/yr Savings = $4,167/yr 3 month savings = $1,389 Or 14% of the pump cost! Brazil Visit 2012
  • 43. Sensorless for parallel pumping Currently only available for single pump operation systems Sensorless for parallel pumping systems… Coming soon Brazil Visit 2012
  • 44. Case Study: Canada Square Building Retrofit Background •Constructed in 1972 •18 floor office tower •37,000 m2 of commercial office space. •Armstrong supplied the VIL pumps for initial construction Brazil Visit 2012
  • 46. Case Study: Canada Square Building Retrofit Execution • Original pumps 4300 6G 1700 gpm at 140 ft, 75 hp • Design Envelope 4300 IVS 1700 gpm at 136 ft, 75 hp • Design Envelope IVS allowed designer to match pump performance to actual system conditions. Actual system HDesign = 85 ft (53Hz) • Design Envelope IVS pump provided 50% energy savings • Cost savings of $38,000 per year Brazil Visit 2012
  • 47. Summary of Sensorless Benefits • Energy savings of 49% over mechanical room sensor • Reduces installation time & cost • No wiring • No conduit • Savings of $2000 Intelligence for your • Eliminates potential problems with sensors Calibration pumping system • Sensor failure • • Forgetting where it is located • Easy on-site balancing and immediate energy savings • Readjust the setpoint from the IVS • No wait for controls commissioning • Ideal for retrofit projects • Can send Sensorless data to the BMS Brazil Visit 2012
  • 48. Design Envelope IVS Pumping Around the World King’s Yard Energy Centre / Olympic Park London, UK Brazil Visit 2012
  • 49. ASHRAE 90.1 and Armstrong Solutions ASHRAE 90.1 Armstrong Solution Proportional Balancing • Design Envelope Pumps with • Easy adjustment of design head • Armstrong balancing valves • Flo-Trex Valves • Throttling IF and WHEN needed (saves expensive retrofit) Need to achieve 70% less power at • Design Envelope Pumps with 50% flow in CW pumping Systems • Correct lowest operating cost selections • Easy control • Sensorless • Armstrong controls • BMS • Sensored Larger Pipe Avoided With Design Envelope Pumps All Pumps over 1 HP (3/4 kw) should have integrated controls! Brazil Visit 2012
  • 50. Design Envelope Pressure Boosters • Lowest Energy • VMS more efficiency than single stage • Utilizes suction design over design for energy savings • Pressure set back • Lowest life cost • Flush valves lasted longer due to lower constant pressures • Slower speed and pressure swings improves equipment life, reduced maintenance and noise from slower speeds, no pressure swings / PRV’s • Security -Safe fill mode • No bypass maintenance -Design Envelope Booster has electronic control Brazil Visit 2012
  • 51. Design Envelope IVS Pumping •ASHRAE 90.1 Conformance • PLUS •Lowest Installed Cost •Lowest Life Cycle Cost Brazil Visit 2012
  • 52. Summary • Design Envelope thinking • All pumping should have integrated controls. (constant speed pumping is obsolete and soon to be illegal) • HVAC and Pressure booster pumps • Design Envelope pumps are selected to right of pump best efficiency point in a simplified / risk free method • Use Vertical Inline pumps, suction guides and Flotrex valves • Twin and DualArm provide even lower cost and space • If conventional controls valves used – Use manual balancing valves • Lowest first cost • Lowest energy and life cost Brazil Visit 2012

Editor's Notes

  1. A long list of savings that adds up to a LCC and a true value based offering.
  2. In a 3 pump system shown here (NOTE: We don’t show the VFDs on the wall or integrated on the motor) But we eliminate the flex connectors, the concrete bases, inertia pads, no realignment of the flex coupling during commissioning. HSC versus VIL Assume 3 pump system - 6x5x12 versus 6x6x11.5 (2-duty / 1-standby) Installation cost = $19,572 vs $8,327 105.7 sf vs 44.2 sf; diff. = 61.5 sf and if we assume $150 / sf, that’s $9,225
  3. LEFT: BAYFRONT TOWERS, Tampa, FL Compact mechanical room with no space for two individual pumps and no space to mount drives on the wall. Simple single large AHU avoided using DP sensor by using sensorless design. Pumps also have auto alternating feature. Worked out of the box with only a slight adjustment to the minimum maintained pressure to accommodate the twin chillers minimum flow requirement. What is not shown in this picture is the two chillers and twin buffer capacity tanks and expansion control tank. There’s a lot of equipment in this little room! 4302 8x8x10-20 hp DualArm DE-IVS Sensorless unit we sold this past year. The DualArm IVS Sensorless pump has been in operation for almost ¾’s of a year. We took out an old water source Air Handler replacing it with a chilled water AHU, Twin Chillers, the IVS dual Arm, a buffer capacity tank, air purger and expansion tank all in the same room we took the old AHU out of…No small task. It worked right out of the box with only a slight adjustment to the minimum maintained pressure. The original set point was below the chillers minimum flow requirement. Otherwise – Flawless! RIGHT: SHOREWOOD PACKAGING, Danville, VA If no floor space, mount the pumps off the ground!! Commercial real estate cost $120/ sq ft, +50% Joe’s numbers on wall mounting?
  4. The VILs present a huge opportunity for pipe savings as they can be mounted directly to the chillers, boilers, and cooling towers. On average the pipe savings are reduced by 40-50%. Here’s an example of a plant room optimization for Glendale Arena, home of the Phoenix Coyotes. On the left are HSC. On the right the VILs are mounted directly onto the chillers saving 43% of piping. In this case, the pipe savings pretty well paid for the pumps. Ran AOL 2400 gpm @ 50 ft vs 2400 gpm @ 80 ft and looked at difference in op cost. 14477 vs 7893 = $6600.
  5. The most common replaced item on pumps is the mechanical seal. Seal changeout is much faster 30mins versus 2 hrs compared to base-mount. Also 4300 VILs don’t use bearings which dramatically reduces failures and maintenance costs.
  6. A long list of savings that adds up to a LCC and a true value based offering.
  7. Armstrong Vertical inline pumps with Design Envelope IVS integrated controls. Series 4300 pumps are available up to 350 hp with integrated controls. Series 4380 close-coupled pumps are available up to 7.5 hp with integrated controls.
  8. The twin pump uses 2 rotating assemblies in 1 shared casing. The twin 4312 and 4392 use the same rotating assemblies as the 4300 and 4380 vertical inline pumps.
  9. Casings differences.
  10. Servicing of twin pumps is not as convenient as the dualARM; both pump rotating assemblies must be shutdown in order to begin maintenance of either seal. Since the twin pumps do not feature built-in isolation valves, the pumping unit must be isolated by separate external valving. While the 4312 split-coupled pump features an outside seal, and can be changed without removing the motor, the Series 4392 close-coupled twin pump requires installing a blank plate over one side of the pump casing before the rotating assembly can be accessed and the seal changed.
  11. Twin pumps provide redundancy but require the system to be temporarily shut down (and the blank plate installed) to service a pump head. The dualARM, with its locking valves, can direct the fluid to the opposite pump head and continue to operate without shut down. For critical services that cannot afford down time, such as cooling for data centers and hospitals the dualARM should be used. The twin pump is available only in bronze-fitted construction rated for ANSI 125. The dualARM can be used in higher pressure services with ductile iron bronze-fitted construction for ANSI 250.
  12. In some cases the flange to flange dimension is smaller than a single VIL!
  13. A twin pump installation occupies almost four times less space than an installation with two end-suction base-mounted pumps. Compared to its dualARM counterpart, the twin pump’s installed footprint can use 20-30% less space.
  14. We ’ ll look at traditional flow control with DP sensor – some of the strategies to get optimum energy savings at part-load. What are some of the pros/cons. Then we ’ ll go into an introduction to sensorless control that is a key feature of our Design Envelope pumps, how we do it, as well as why it presents advantages over sensors. After that, we ’ ll run a short clip of the sensorless display unit in action followed by a case study and then some questions.
  15. If equipped with the IVS Sensorless feature, the pump’s performance curves against power and speed are pre-programmed into the controls. During operation, the power and speed of the pump are monitored, enabling the controller to establish the hydraulic performance and position the pump’s head-flow characteristic to the system requirements. As the building’s control valves open or close to manage load, the IVS Sensorless controls can intelligently slow down or speed up the pump to maintain the pressure setpoint. The built-in PID controller converts the pressure setpoint to head. Head squared is proportional to flow, flow is proportional to speed.
  16. With variable frequency drives coming down in price and improved reliability over the years, the building industry has changed over to using variable speed pumps with 2 way valves. Instead of bypassing the excess flow, today we would slow the pump down to reduce capacity to the coil.   The mechanism to control the speed of the pump has traditionally been a sensor. The sensor would typically measure differential pressure or temperature of the system and have the variable speed controls respond by speeding up or slow down to control the pump.
  17. In this simplified chilled water system example, our chiller and pump are found in the basement mechanical room and the pump distributes chilled water to the cooling coils. The building ’ s temperature controls are connected to control valves that manage the flow rate to the cooling coils (load). Traditionally, a differential pressure sensor would be installed across the line to measure the changes in pressure from the valves opening and closing. As the control valves open for more cooling, the system resistance is reduced and the differential pressure across the valve decreases. The variable speed controls react to this change by increasing the pump speed to maintain the pressure setpoint (or the desired pressure). If the control valves close to reduce the cooling output, the differential pressure across the valve increases, and the variable speed controls reduce the pump speed to maintain the pressure setpoint (or the desired pressure). “ desired pressure (the Setpoint) with the actual pressure (the Feedback) from a pressure sensor and adjusts the pump speed to maintain the pressure at the desired level. ” But there are a number of scenarios that come up when dealing with sensors; most notably is where to install the DP sensor. The common thinking suggests that the sensor be installed at the most remote load. Another is to keep things simple and install it in the mechanical room. Another is to install it at 2/3rds from the pump. There are benefits and disadvantages to each of these strategies in terms of energy consumption and installed cost and we ’ ll look at each of them in the next few slides.
  18. In a chilled water system, a building ’ s temperature controls are connected to control valves that manage the amount of flow rate to the cooling coils. As the control valves open for more cooling, the differential pressure across the cooling coil, valve and piping will begin to decrease, and the IVS controls react to this change by speeding up the pump to maintain the pressure setpoint. If the control valve closes for less cooling, the differential pressure across the coil will increase, and the IVS controls slow down the pump to maintain the pressure setpoint. To ensure the coil is satisfied, a Minimum Head is introduced so that the pressure drop across this load is always satisfied. Our new pump performance curve is now the Control Curve (in blue). The Minimum Head is usually established in the field during the commissioning process by installing differential pressure sensors across the remote load and setting the minimum required head/pressure and wiring it back to the variable speed controls. In this case, the Minimum Head is the same as the design head which doesn ’t result in much energy savings; in fact this configuration won’t even meet the ASHRAE 90.1 energy standard – but it is very simple to install. The built-in PID controller converts the pressure setpoint to head Head squared is proportional to flow, and flow is proportional to speed
  19. In a chilled water system, a building ’ s temperature controls are connected to control valves that manage the amount of flow rate to the cooling coils. As the control valves open for more cooling, the differential pressure across the cooling coil, valve and piping will begin to decrease, and the IVS controls react to this change by speeding up the pump to maintain the pressure setpoint. If the control valve closes for less cooling, the differential pressure across the coil will increase, and the IVS controls slow down the pump to maintain the pressure setpoint. To ensure the coil is satisfied, a Minimum Head is introduced so that the pressure drop across this load is always satisfied. Our new pump performance curve is now the Control Curve (in blue). The Minimum Head is usually established in the field during the commissioning process by installing differential pressure sensors across the remote load and setting the minimum required head/pressure and wiring it back to the variable speed controls. This configuration provides tremendous energy savings, meeting ASHRAE 90.1 standard for energy efficient operation – but it is difficult to install. The built-in PID controller converts the pressure setpoint to head Head squared is proportional to flow, and flow is proportional to speed There ’ s a lot to think about just on where to place the sensor to get maximum energy savings and to ensure all the loads are satisfied.
  20. Comparison of the 2 strategies we just discussed. D = mechanical room sensor E = remote load sensor or Design Envelope Sensorless Why is the Design Envelope Sensorless the same performance as remote load sensor? (A: Because the Sensorless control can provide the same performance as a remote load sensor)
  21. Armstrong innovated the Sensorless pump control technology which has been used in Europe for 15 years specifically for the HVAC industry. The Sensorless function acts as a “virtual sensor” and allows us to control the pump in the same way as sensor - only without the sensor.
  22. With these 4 parameters, any point on the curve can be determined. Similar to a sizing selection program, if you input flow and head, you get as an output – power and speed. The sensorless control looks at its flow and head to calculate head and speed.
  23. For simplicity, let ’ s look at 3 sample points and apply them in a pumping system to understand the details of how sensorless control works.
  24. The slide is illustrating a system friction design curve [S1 System curve] A pump performance curve at full design speed (S1) is selected to intersect the system curve at the design flow and head conditions. The corresponding power drawn is shown below the performance curves. The control curve is set via the VFD graphical interface device by the input of the design flow, head and minimum system pressure (On the vertical [y] axis). As the building conditioned spaces reach the high tolerances levels for the set point conditions, the system 2-way control valves will modulate closed, increasing the resistance to flow and creating a new system resistance curve (Similar to the S2 System curve). This will cause the pump to move left on the S1 performance curve (1), and will pump less water because of the valves throttling to a higher pressure. The power at the new operating point will take less power (2) than the original operating conditions and the Sensorless Control logic recognizes that this power reading is incorrect for the current operating speed and thus reduces the motor speed (Pump curve S2) until the power and speed converge on the control curve (3 & 4). The unit will operate at the new operating point (3) at the reduced power (4) until the control valves react again to conditioned space environment change and modulate appropriately. Thus the IVS Sensorless Controlled pumping package will react in an identical manner to a pump controlled by feedback from a remotely mounted system DP sensor, without the need to purchase, install and wire the remote sensor.
  25. The slide is illustrating a system friction design curve [S1 System curve] A pump performance curve at full design speed (S1) is selected to intersect the system curve at the design flow and head conditions. The corresponding power drawn is shown below the performance curves. The control curve is set via the VFD graphical interface device by the input of the design flow, head and minimum system pressure (On the vertical [y] axis). As the building conditioned spaces reach the high tolerances levels for the set point conditions, the system 2-way control valves will modulate closed, increasing the resistance to flow and creating a new system resistance curve (Similar to the S2 System curve). This will cause the pump to move left on the S1 performance curve (1), and will pump less water because of the valves throttling to a higher pressure. The power at the new operating point will take less power (2) than the original operating conditions and the Sensorless Control logic recognizes that this power reading is incorrect for the current operating speed and thus reduces the motor speed (Pump curve S2) until the power and speed converge on the control curve (3 & 4). The unit will operate at the new operating point (3) at the reduced power (4) until the control valves react again to conditioned space environment change and modulate appropriately. Thus the IVS Sensorless Controlled pumping package will react in an identical manner to a pump controlled by feedback from a remotely mounted system DP sensor, without the need to purchase, install and wire the remote sensor.
  26. Generally if a system is overdesigned, the design point ends up drifting to the right of the curve. The head is lower than anticipated and the system needs to be balanced with a circuit balancing valve. Instead of introducing a restriction or a pressure drop in the form of a balancing valve, the Sensorless control curve can be adjusted through the keypad controls. There are 3 parameters built into the Design Envelope controls that define the control curve. Those are the setpoint (desired pressure) P20-21, the minimum head P22-87, and design flow P22-89. (Note that the Design Envelope pump would still work when the design point is over-estimated, however it doesn ’ t begin to reduce its speed until the system is operating below the pre-programmed design flow.)
  27. *(Comparison of variable flow-constant speed operation to variable flow-variable speed operation) During a building ’ s commissioning, the pumps and 2-way control valves are installed. The control valves open and close as they would under normal operation but the controls contractor has not commissioned the sensors yet; this typically takes 3-4 months. The Design Envelope sensorless pump can react to the changes in system resistance from the valves opening and closing and adjust its speed to meet demand – as soon as it is installed. The savings during those first 3 months can payoff up to 14% of the pump cost.
  28. Armstrong ’ s Sensorless control is currently only available for singe pump operation systems. It can be used for duty-standby operation but cannot do parallel pumping control. There are some complex control calculations required to stage multiple pumps off and on along a dynamic pump curve. However this feature is currently in development and should be available by the end of the year.
  29. 2180 Yonge Street is a complex of three interconnected office buildings located in downtown Toronto. The complex includes a small shopping concourse, an office tower and a multiplex cinema. Constructed in 1972, the office tower offers 18 floors and a total of 402,277 square feet (37,373 m 2 ) of commercial office space. Armstrong supplied the pumps for the initial construction of this tower. At the time, Vertical In-Line Pumps were a relatively new, market-leading design.
  30. Analysis of the original pumps showed they were oversized. Design Envelope IVS solution allowed the system designer to better match the performance of the pumps to the actual system conditions. Actual system Hdesign = 85 ft (53hz)
  31. Today we ’ll be discussing….