Analysis of Example Capacitor Bank Switching Solution and
Recommendations for Revision
Author: Joe Rostron, P.E. 3/13/2007
Southern States LLC, Hampton, GA
Editor: David Childress 8/22/07
Southern States LLC, Hampton, GA
Abstract - The life of SF6 interrupters is limited in applications where daily switching of
capacitor banks causes high cumulative damage to the contacts and to the nozzles. This report
analyzes this from a generic point of view and from an application specific point of view.
Traditional solution methodologies suggested by standards do not offer the best alternative now
available as a result of the development of a new, reliable, application-specific, pre-insertion
resistor type capacitor switching device—Southern States CapSwitcher
®
. This new device
allows the elimination of many, if not all, of the reactors previously used to limit the inrush
currents. The reactors have been necessary to limit the damage to and premature failures of
general-purpose devices such as circuit breakers and circuit switchers. The adoption of the
Southern States CapSwitcher
®
results in a significant cost savings of up to 33%. Additional
benefits include space savings, a reduction in voltage transients and current transients, and
significant improvements in reliability.
Introduction – Back-to-back switching of capacitor banks presents a very tough duty on
switching devices because of the combination of the high inrush currents and the frequent
switching of larger and larger banks. Early switching devices such as oil circuit breakers,
vacuum switches, and vacuum circuit breakers have interrupter characteristics that cause
significant damage to the interrupters as a result of high inrush currents. While oil was more
sensitive to high di/dt and vacuum was more sensitive to high peak currents, both have largely
faded from applications at transmission voltages. The advent of SF6 devices has significantly
reduced the severity of the problems of capacitor switching applications; however, problems
continue to persist and cause premature failure of some SF6 capacitor switching devices. Some
SF6 capacitor switching devices also require the use of reactors in the circuit for higher duty
capacitor switching applications. The introduction of Southern States CapSwitcher
®
, an
application-specific SF6 capacitor switching device equipped with pre-insertion resistors, gives
utility engineers an economical and compact solution to this very difficult switching application.
The use of general-purpose SF6 devices for capacitor switching duty is no longer the most
reliable and economical solution. The application-specific SF6 capacitor switching device,
Southern States CapSwitcher
®
, is not only more compact and economical but also reduces
voltage surges on the power grid better and has a much longer operational life than other SF6
devices.
Example Standard Capacitor Bank Configuration - A substation arrangement with a single
general purpose circuit breaker protecting three capacitor banks (36.8 MVAR each) and using
two circuit switchers, one circuit switcher each to energize the second and third banks, is
evaluated on a comparative basis and used as a basis for making recommendations for
improvements. The capacitor banks are arranged to be switched in three steps with reactors for
current inrush and outrush control. All three are protected against a possible fault in any one of
Page 2 of 10
them by the single general-purpose circuit breaker which is also required to switch on the first
capacitor bank.
The peak inrush current in capacitor switching applications can be quite high, and ANSI
standards have recommended limiting this inrush current to 16 kA peak at a frequency of up to
4.2 kHz by applying series reactors in the circuit. This is a quite common solution for back-to-
back switching of capacitor banks. Given the available alternatives, this use of reactors was a
major improvement over the previous option of switching capacitor banks without them.
These three capacitor banks are connected to the bus as is shown in the diagram below. The
circuit breaker is connected to the substation bus and then connected to an outrush reactor before
an interconnection point where three capacitor banks are all connected through inrush reactors.
Two circuit switchers are then used to control the second and third banks after the first bank is
switched on by the circuit breaker. A TRV (Transient Recovery Voltage) control capacitor is
used to control the TRV for a reactor fed fault should a capacitor bank or any other component
flash over to ground.
Circuit Switchers
Circuit Breaker
Outrush Reactor
Inrush Reactors
TRV Control
Capacitor
Page 3 of 10
Interrupter Arcing Damage - The damage to contacts and to nozzles is a function of the current
magnitude and the duration of the arcing. It is generally accepted that arc damage is related to
I2
t. It is on this basis that looking at the next four simulations show this arc damage index in
terms of this equation. These simulations also show that back-to-back switching has a
significantly higher damage index than single bank switching as the closing currents are much
higher. Although this is common knowledge, these simulations show the magnitude of this
difference in this specific application.
The first and second simulations are for the example configuration with inrush and outrush
reactors, circuit switchers, and a circuit breaker. The third and fourth simulations are for the
application of a special purpose capacitor switching device, Southern States CapSwitcher
®
,
without the use of inrush reactors. The presence of the CapSwitcher
®
’s pre-insertion resistor
dramatically limits the currents. The details of the circuit being simulated are shown in the
appendix of this report.
Example Configuration – Back-to-Back Switching with Inductors (Simulation 1) – Last
Bank Energized = 49,650 (I2
t) Main Contact Arcing Energy
Page 4 of 10
Example Standard Configuration – First Bank Switching with Inductors (Simulation 2) –
First Bank Energized = 13,554 (I2
t) Main Contact Arcing Energy
Revised Configuration With CapSwitcher
®
Having 40 Ohm Pre-Insertion Resistor –
Back-to-Back Switching Without Inductors (Simulation 3) - Last Bank Energized = 176
(I2
t) Main Contact Arcing Energy
Page 5 of 10
Proposed Configuration (With Overvoltage Control) With CapSwitcher
®
Having 40
Ohm Pre-Insertion Resistor Being Used On The First Bank Switched – First Bank
Switching Without Inductors (Simulation 4) - First Bank Energized = 104 (I2
t) Main
Contact Arcing Energy
The reduction in damage index due to using the pre-insertion resistor equipped CapSwitcher
®
is rather dramatic and hence the expected life of the contacts in the interrupter is also anticipated
to be significantly longer as the predominant switching mode is the daily capacitor bank
switching rather than the occasional fault clearing. Hopefully there is never a need for clearing
faults on a capacitor bank, but one must be prepared for that possibility. This reduction in arcing
damage also extends the interrupter life for that potential time when it is required that a fault be
interrupted and cleared.
The reason for concern about this arcing damage due to capacitor switching is the fact that
interrupter life is significantly reduced and the effects are cumulative over time. Power tests in
laboratories generally demonstrate capability of new devices but are rarely done with hundreds
of operations in power test labs on 72.5 kV and higher voltage rated equipment. This is
principally because the cost of doing these tests is generally quite expensive. As a result of this,
reliance on actual field experience is the best method to verify cumulative arcing damage on
interrupter nozzles and contacts, but this does take time to expose weaknesses and verify field
performance. In the absence of many years of field experience, calculations of damage from
arcing are made to compare design differences and application differences.
The results of such calculations are shown in the following Life Calculation Table. This
compares the Southern States CapSwitcher
®
with a circuit switcher used in capacitor bank
switching applications. The numbers in the chart highlighted in bold are taken from available
literature from that circuit switcher. The numbers with a tan background show the closing
operations one would expect if the maximum switching current were present for routine
capacitor switching. The Southern States CapSwitcher
®
has a design topology that makes it
Page 6 of 10
impossible for the inrush current to get to its maximum magnitude. This is so because the pre-
insertion resistor in the CapSwitcher
®
limits the magnitude of the inrush current. The inrush
reactors limit the inrush for the circuit switchers. The expected switching life is shown in yellow
(back-to-back applications) and green (single bank applications) for both types of devices.
Clearly, there is more damage and expected shorter contact & nozzle life for both designs in the
back-to-back switching as compared to single bank switching.
Life Calculation Table
KEY
ANSI Max.
Back-to-Back
1st Bank
Exp. = 2 Exp. = 1.75
Current Erosion Life Opening Closing Current Erosion Life Opening Closing
KA I^Exp.2 * t * No. Operations Operations KA I^Exp.2 * t * No. Operations Operations
40 192 10 5 40 NA NA NA
31.5 192 16 10 31.5 NA NA NA
25.0 192 26 25 25.0 ?? ?? ??
20.0 192 40 60 20.0 22.7 10 30
16.0 192 63 188 16.0 22.7 15 44
12.5 192 102 307 12.5 22.7 23 68
10.0 192 160 480 10.0 22.7 34 101
8.0 192 253 759 8.0 22.7 50 151
6.3 192 401 1,202 6.3 22.7 75 225
5.0 192 634 1,901 5.0 22.7 112 337
4.0 192 1003 3,008 4.0 22.7 168 503
3.2 192 1587 4,760 3.2 22.7 250 751
2.5 192 2510 7,531 2.5 22.7 374 1,122
2.0 192 3972 11,915 2.0 22.7 559 1,677
1.6 192 6284 18,852 1.6 22.7 835 2,505
1.3 192 9943 29,829 1.3 22.7 1247 3,742
1.0 192 15732 47,195 1.0 22.7 1864 5,591
0.8 192 24891 74,673 0.8 22.7 2784 8,353
0.6 192 39383 118,149 0.6 22.7 4160 12,480
0.5 192 62312 186,937 0.5 22.7 6215 18,645
0.4 192 98592 295,775 0.4 22.7 9286 27,857
Assumption "t" = 12 ms Opening & 4 ms Closing JRR 2-13-07
Contact & Nozzle Life Calculations
Example Of Switching Configuration For 3 Capacitor Banks
CapSwitcher® 145 kV without Reactors Circuit Switcher with Reactors
The results of the analysis clearly show an increase of more than 200 to 1 in the expected life of
the interrupter contacts and nozzle for the Southern States CapSwitcher
®
with its pre-insertion
resistor versus the circuit switcher. It also follows that there is no additional advantage to using
inrush reactors with the CapSwitcher
®
as they provide no additional reduction in the inrush
current. The intrinsic interrupter design capability (Erosion Life – 192 vs. 22.7) shows an 8 to 1
improvement when using the CapSwitcher
®
in lieu of the circuit switcher in this comparison
simply based upon the intrinsic interrupter design. The rest of the improvement in interrupter
contact life and interrupter nozzle life comes from the fact that the pre-insertion resistor is much
better at limiting the inrush currents than is reasonably possible with the use of reactors.
Voltage Transients - These are significantly reduced by the use of the CapSwitcher
®
and are
most dramatic when comparing the second simulation to the fourth. These are simulations of
switching on the first capacitor bank with the general purpose SF6 circuit breaker and with a
CapSwitcher
®
, respectively. The reduction of the current transients is equally impressive.
Page 7 of 10
Cost Savings From Changing Away From The Example Solution - It is clear that the
previously mentioned improvements have a substantial impact from a reliability and life cycle
point of view. Additionally, not having to replace equipment that is subject to failures from high
operational life in-service is a further advantage. Changing to the use of the CapSwitcher
®
with its pre-insertion resistor and eliminating inrush reactors results in significant savings as
well. In that the inrush reactors are a necessary solution for capacitor switching devices without
surge control, their need is eliminated by the newer technological approach of using the
CapSwitcher
®
with its pre-insertion resistors, and the CapSwitcher
®
is now available and
in service at many utilities. The elimination of these otherwise-needed components saves
considerably on the installed cost of a substation capacitor bank switching solution.
The use of the CapSwitcher
®
results in a space savings as well; however, this was not
included as a financial benefit. This advantage can be significant in applications where there is a
need to retrofit or upgrade existing capacitor banks in older substations if there is no space to
install reactors.
The table below also shows there are possible cost savings of up to 24% for substations that have
a 63 kA fault level and up to 33% for substations that have a 40 kA fault level. The savings are
based on the substation being reconfigured to use CapSwitcher
®
s instead of a circuit breaker,
two circuit switchers, and reactors. The tables below outline the configuration options evaluated
and their respective savings.
Cost Comparison Tables
JRR - 2-21-2007
Unit per
Price (k$) Quantity Extended Quantity Extended Quantity Extended
Standard Circuit Breaker (63 kA) 69 1 69 K$ 1 69 K$ 1 69 K$
Standard Circuit Breaker (40 kA) 53 0 0 0
Inrush Reactor (200 A- 33 kA) 5.5 9 49.5 K$ 0 0 K$ 0 0 K$
Outrush Reactor (450 A- 40 kA) 13 3 39 K$ 3 39 K$ 0 0 K$
L-G Capacitor for TRV Control 3 3 9 K$ 3 9 K$ 0 0 K$
Support Structure for XL or XC 1.5 15 22.5 K$ 6 9 K$ 0 0 K$
Foundation for XL or XC 3 15 45 K$ 6 18 K$ 0 0 K$
Circuit Switcher - 40 kAClose 34 2 68 K$ 0 0 K$ 0 0 K$
CapSwitcher® - 63 kAClose 59 0 0 K$ 2 118 K$ 3 177 K$
Equipment Total 302 K$ 262 K$ 246 K$
Equipment Savings 0 K$ 40 K$ 56 K$
Installed Estimate 1.5 Factor 453 K$ 393 K$ 369 K$
Life Cycle Costs for 20 Years
Replace Interrupters
@8 Yrs. Circuit Switcher 5 3 15 K$ 0 0 K$ 0 0 K$
Circuit Breaker Not Required
@16 Yrs. Circuit Switcher 5 9 45 K$ 0 0 K$ 0 0 K$
CapSwitcher® Not Required
Total Costs 513 K$ 393 K$ 369 K$
Net Savings 0% 0 K$ 23% 120 K$ 28% 144 K$
Substation Cost Configuration Comparison
SSLLC - Proposed (With
Voltage Control)SSLLC SuggestedExample Standard Configuration
145 kV- 63 kA- Three Capacitor Banks (36.8 MVAR each) in Parallel
Page 8 of 10
It is also possible to eliminate the circuit breaker outright where substation faults are at or below
40 kA by using the 40 kA interrupting capability of the CapSwitcher
®
and enabling the
CapSwitcher
®
’s inherent fault interrupting capability by providing the CapSwitcher
®
with
current sensing via the SSIPower LLC CMD
TM
three phase non-contact current transformer.
This solution amounts to a possible savings of up to 33% ($154,000) in total life cycle cost.
JRR - 2-17-2007
Unit per
Price (k$) Quantity Extended Quantity Extended Quantity Extended
Standard Circuit Breaker (63 kA) 69 0 0 K$ 0 0 K$ 0 0 K$
Standard Circuit Breaker (40 kA) 53 1 53 K$ 1 53 K$ 0 0 K$
CMD™on Disconnect Switch 15 0 0 K$ 0 0 K$ 2 30 K$
Inrush Reactor (200 A- 33 kA) 4 9 36 K$ 0 0 K$ 0 0 K$
Outrush Reactor (450 A- 40 kA) 13 3 39 K$ 3 39 K$ 0 0 K$
L-G Capacitor for TRV Control 2 3 6 K$ 3 6 K$ 0 0 K$
Support Structure for XL or XC 1.5 15 22.5 K$ 6 9 K$ 0 0 K$
Foundation for XL or XC 3 15 45 K$ 6 18 K$ 0 0 K$
Circuit Switcher - 40 kAClose 34 2 68 K$ 0 0 K$ 0 0 K$
CapSwitcher® - 63 kAClose 59 0 0 K$ 2 118 K$ 3 177 K$
Equipment Total 269.5 K$ 243 K$ 207 K$
Equipment Savings 0 K$ 27 K$ 63 K$
Installed Estimate 1.5 Factor 404 K$ 365 K$ 311 K$
Life Cycle Costs for 20 Years
Replace Interrupters
@8 Yrs. Circuit Switcher 5 3 15 K$ 0 0 K$ 0 0 K$
Circuit Breaker Not Required
@16 Yrs. Circuit Switcher 5 9 45 K$ 0 0 K$ 0 0 K$
CapSwitcher® Not Required
Total Costs 464 K$ 365 K$ 311 K$
Net Savings 0% 0 K$ 21% 100 K$ 33% 154 K$
Substation Cost Configuration Comparison
145 kV- 40 kA- Three Capacitor Banks (36.8 MVAR each) in Parallel
Example Standard Configuration SSLLC Suggested
SSLLC - Proposed (With
Voltage Control)
Summary - The reliability of example capacitor bank switching arrangement can be
significantly improved and cost reduced by the adoption of the CapSwitcher
®
, Southern
States definite purpose capacitor switching device. The cost savings can be as high as 24% for
substations that have 63 kA fault levels and up to 33% for substations with 40 kA fault levels. In
addition, voltage transients and inrush currents will also be reduced compared to the current
example capacitor bank switching configuration. Several alternatives and configurations are
presented here, allowing the customer to choose the desired configuration based on specific
installation needs for new and existing substations.
Conclusion - The application of Southern States CapSwitcher
®
, a pre-insertion resistor
device, in capacitor bank switching substation applications will increase the reliability and
equipment life while also reducing costs as compared to the example capacitor switching
configuration. This is because the CapSwitcher
®
is designed for twice the number of
mechanical operations of most other available equipment and because the CapSwitcher
®
eliminates the need for inrush reactors. Additionally, the life of the interrupter is 10 to 200 times
Page 9 of 10
that of other devices used in this capacitor switching application because of the Southern States
CapSwitcher
®
’s pre-insertion resistor. The recommendation of eliminating the inrush
reactors allows a smaller substation footprint and saves $100,000 per installation (20 %). The
opportunity exists to increase this savings to 24% for substations having 63 kA available fault
current.
The cost savings opportunity increases up to 33% ($154,000) for a 40 kA available fault current
substation should there be a desire to have a different capacitor switching solution for 40 kA
available fault current substations versus 63 kA available fault current substations. The most
cost effective proposed solutions also provide voltage surge control when switching the capacitor
banks. The adoption of these recommended solutions will provide significant cost savings,
increased reliability, and reduced life cycle costs.
Author Biography – Joe Rostron received his Bachelor of Science degree in Mechanical
Engineering from Washington State University in 1970 and his Masters Degree in Business
Administration from the University of Pittsburgh in 1984. He has been employed since 1970 by
Westinghouse, ABB Power T&D, Siemens Power Transmission and Distribution, and Southern
States LLC with titles of Development Engineer, Engineering Manager, Product Manager, Sr.
Vice President-Engineering, and is now President of SSIPower LLC (a Southern States
company). He has 31 U.S. patents focusing on high voltage circuit breakers and other innovative
power system technologies. He is a professional engineer in Pennsylvania and is also a member
of IEEE and ASME. His experience covers a wide range of responsibilities for energy product
design, development, and testing of new concepts/products; constantly seeking innovation to
resolve high voltage power concerns to improve operational efficiencies and to reduce costs. His
focus has been on national energy problems and development of new modern products for
customer needs.
Editor Biography – David Childress received his Bachelor of Science degree in Engineering
from Mississippi State University in 1991. He joined Siemens Energy & Automation in 1991 as
an Application Engineer responsible for circuit switchers and disconnect switches and later
joined Southern States in 1997 holding positions of Regional Manager, International Sales
Manager, Product Manager, and Marketing Manager of Southern States Power Switching
Division. He is presently Marketing Manager of SSIPower LLC (a Southern States company)
responsible for the marketing, promotion, and sale of three-phase non-contact current
transformers. He is a member of IEEE; a multi-published technical paper author; an author of
over 100 catalog flyers, catalog bulletins, and other technical/product related documents; and has
recently co-authored a chapter for the Electric Power Substations Engineering Book-Second
Edition entitled “High Voltage Switching Equipment” (ISBN: 978-0-8493-7383-1)
Editor Note – The economics shown in this paper are specific to the project, configuration, and
ratings being analyzed but are representative of the achievable savings for a variety of capacitor
switching applications. The performance and installed life enhancement of converting to the
Southern States CapSwitcher
®
high voltage capacitor switching device with current sensing
via the SSIPower LLC CMD
TM
three phase non-contact current transformer are not specific to
just this project, configuration, and ratings; being instead highly representative of many capacitor
switching applications.
Page 10 of 10
Appendix
Fixed Inductor Capacitor Switching
CapSwitcher
®
Capacitor Switching

More Related Content

What's hot

High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...Ali Sepehri
 
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...VLSICS Design
 
Condition based monitoring
Condition based monitoringCondition based monitoring
Condition based monitoringNiraj Agrawal
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersAli Sepehri
 
Principles Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPrinciples Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPower System Operation
 
AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100Ali Sepehri
 
Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Vincent Wedelich, PE MBA
 
Vsc based hvdc transmission
Vsc based hvdc transmissionVsc based hvdc transmission
Vsc based hvdc transmissionjawaharramaya
 
Hvdc proven technology
Hvdc proven technologyHvdc proven technology
Hvdc proven technologyjefryleal
 
VSC based HVDC system
VSC based HVDC systemVSC based HVDC system
VSC based HVDC systemmdhsudhan
 
HVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading TechnologyHVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading TechnologyDixit Patel
 
High Voltage Direct Current Transmission System
High Voltage Direct Current Transmission SystemHigh Voltage Direct Current Transmission System
High Voltage Direct Current Transmission SystemNadeem Khilji
 
Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...Naveed Shahzad
 
High Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionHigh Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionZunAib Ali
 
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...Ali Sepehri
 

What's hot (20)

High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
 
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
 
Condition based monitoring
Condition based monitoringCondition based monitoring
Condition based monitoring
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit Breakers
 
Link
LinkLink
Link
 
Vsc based hvdc
Vsc based hvdcVsc based hvdc
Vsc based hvdc
 
Principles Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC SchemesPrinciples Control & Protection of HVDC Schemes
Principles Control & Protection of HVDC Schemes
 
AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100
 
Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...
 
FAULT ANALYSIS IN HVDC & HVAC TRANSMISSION LINE
FAULT ANALYSIS IN HVDC & HVAC TRANSMISSION LINEFAULT ANALYSIS IN HVDC & HVAC TRANSMISSION LINE
FAULT ANALYSIS IN HVDC & HVAC TRANSMISSION LINE
 
Vsc based hvdc transmission
Vsc based hvdc transmissionVsc based hvdc transmission
Vsc based hvdc transmission
 
Hvdc proven technology
Hvdc proven technologyHvdc proven technology
Hvdc proven technology
 
VSC based HVDC system
VSC based HVDC systemVSC based HVDC system
VSC based HVDC system
 
HVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading TechnologyHVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading Technology
 
IJET-V3I2P1
IJET-V3I2P1IJET-V3I2P1
IJET-V3I2P1
 
High Voltage Direct Current Transmission System
High Voltage Direct Current Transmission SystemHigh Voltage Direct Current Transmission System
High Voltage Direct Current Transmission System
 
Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...Conventional and emerging converter technologies in hvdc power transmission s...
Conventional and emerging converter technologies in hvdc power transmission s...
 
High Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmissionHigh Voltage Dc (HVDC) transmission
High Voltage Dc (HVDC) transmission
 
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
 
B 24
B 24B 24
B 24
 

Viewers also liked

DMA Brochure
DMA BrochureDMA Brochure
DMA BrochureDMA Group
 
Bwpaper2
Bwpaper2Bwpaper2
Bwpaper2f95346
 
The nature and scope of marketing
The nature and scope of marketingThe nature and scope of marketing
The nature and scope of marketingf95346
 
Gre322me
Gre322meGre322me
Gre322mef95346
 
DMA Brochure
DMA BrochureDMA Brochure
DMA BrochureDMA Group
 
Bacon Guzenko Requirements traceability
Bacon Guzenko Requirements traceabilityBacon Guzenko Requirements traceability
Bacon Guzenko Requirements traceabilityDmitry Guzenko
 
BACON 2016: Requirements Traceability
BACON 2016: Requirements TraceabilityBACON 2016: Requirements Traceability
BACON 2016: Requirements TraceabilityDmitry Guzenko
 
Marketing planning
Marketing planningMarketing planning
Marketing planningf95346
 

Viewers also liked (10)

DMA Brochure
DMA BrochureDMA Brochure
DMA Brochure
 
Bwpaper2
Bwpaper2Bwpaper2
Bwpaper2
 
The nature and scope of marketing
The nature and scope of marketingThe nature and scope of marketing
The nature and scope of marketing
 
Gre322me
Gre322meGre322me
Gre322me
 
DMA Brochure
DMA BrochureDMA Brochure
DMA Brochure
 
Bacon Guzenko Requirements traceability
Bacon Guzenko Requirements traceabilityBacon Guzenko Requirements traceability
Bacon Guzenko Requirements traceability
 
BACON 2016: Requirements Traceability
BACON 2016: Requirements TraceabilityBACON 2016: Requirements Traceability
BACON 2016: Requirements Traceability
 
Marketing planning
Marketing planningMarketing planning
Marketing planning
 
AF-23- IPv6 Security_Final
AF-23- IPv6 Security_FinalAF-23- IPv6 Security_Final
AF-23- IPv6 Security_Final
 
Resume___RVG
Resume___RVGResume___RVG
Resume___RVG
 

Similar to Analysis of example_capacitor_bank_switching_solution_and_recommendations_for_revision

SIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOAD
SIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOADSIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOAD
SIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOADijiert bestjournal
 
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...IJERA Editor
 
Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Alexander Decker
 
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)sunny katyara
 
Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...
Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...
Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...IJERA Editor
 
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...eeiej_journal
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...IJERA Editor
 
22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septianIAESIJEECS
 
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...Editor IJCATR
 
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...IRJET Journal
 
High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...
High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...
High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...IRJET Journal
 
A fuzzy logic controlled dc dc converter for an
A fuzzy logic controlled dc dc converter for anA fuzzy logic controlled dc dc converter for an
A fuzzy logic controlled dc dc converter for aneSAT Publishing House
 
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...IJERA Editor
 
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...IJERA Editor
 
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...IJMTST Journal
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...MABUSUBANI SHAIK
 
A DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle Selection
A DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle SelectionA DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle Selection
A DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle SelectionIJMER
 

Similar to Analysis of example_capacitor_bank_switching_solution_and_recommendations_for_revision (20)

SIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOAD
SIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOADSIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOAD
SIMULATION STUDY OF QZSI Z-SOURCE INVERTER FOR RESISTIVE AND INDUCTIVE LOAD
 
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
 
Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...
 
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
 
Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...
Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...
Control Method for Unified Power Quality Conditioner Using Fuzzy Based Nine-S...
 
R01043105113
R01043105113R01043105113
R01043105113
 
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
 
22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian
 
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
The DC-fault Blocking Capability by a New Hybrid Multilevel Converter in HVDC...
 
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
IRJET- Review on Various Topologis used for Decoupling of Fluctuating Power i...
 
High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...
High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...
High-Power Bidirectional Dual Active Bridge and Double Dual Active Bridge DC-...
 
Ssfcl
SsfclSsfcl
Ssfcl
 
A fuzzy logic controlled dc dc converter for an
A fuzzy logic controlled dc dc converter for anA fuzzy logic controlled dc dc converter for an
A fuzzy logic controlled dc dc converter for an
 
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
 
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
A Novel Control Method for Unified Power Quality Conditioner Using Nine-Switc...
 
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
A Novel Integrated AC-DC Five Level Converter Strategy for Power Factor Corre...
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
 
A DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle Selection
A DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle SelectionA DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle Selection
A DC-DC Converter with Ripple Current Cancellation Based On Duty Cycle Selection
 

Recently uploaded

chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 

Recently uploaded (20)

chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 

Analysis of example_capacitor_bank_switching_solution_and_recommendations_for_revision

  • 1. Page 1 of 10 Analysis of Example Capacitor Bank Switching Solution and Recommendations for Revision Author: Joe Rostron, P.E. 3/13/2007 Southern States LLC, Hampton, GA Editor: David Childress 8/22/07 Southern States LLC, Hampton, GA Abstract - The life of SF6 interrupters is limited in applications where daily switching of capacitor banks causes high cumulative damage to the contacts and to the nozzles. This report analyzes this from a generic point of view and from an application specific point of view. Traditional solution methodologies suggested by standards do not offer the best alternative now available as a result of the development of a new, reliable, application-specific, pre-insertion resistor type capacitor switching device—Southern States CapSwitcher ® . This new device allows the elimination of many, if not all, of the reactors previously used to limit the inrush currents. The reactors have been necessary to limit the damage to and premature failures of general-purpose devices such as circuit breakers and circuit switchers. The adoption of the Southern States CapSwitcher ® results in a significant cost savings of up to 33%. Additional benefits include space savings, a reduction in voltage transients and current transients, and significant improvements in reliability. Introduction – Back-to-back switching of capacitor banks presents a very tough duty on switching devices because of the combination of the high inrush currents and the frequent switching of larger and larger banks. Early switching devices such as oil circuit breakers, vacuum switches, and vacuum circuit breakers have interrupter characteristics that cause significant damage to the interrupters as a result of high inrush currents. While oil was more sensitive to high di/dt and vacuum was more sensitive to high peak currents, both have largely faded from applications at transmission voltages. The advent of SF6 devices has significantly reduced the severity of the problems of capacitor switching applications; however, problems continue to persist and cause premature failure of some SF6 capacitor switching devices. Some SF6 capacitor switching devices also require the use of reactors in the circuit for higher duty capacitor switching applications. The introduction of Southern States CapSwitcher ® , an application-specific SF6 capacitor switching device equipped with pre-insertion resistors, gives utility engineers an economical and compact solution to this very difficult switching application. The use of general-purpose SF6 devices for capacitor switching duty is no longer the most reliable and economical solution. The application-specific SF6 capacitor switching device, Southern States CapSwitcher ® , is not only more compact and economical but also reduces voltage surges on the power grid better and has a much longer operational life than other SF6 devices. Example Standard Capacitor Bank Configuration - A substation arrangement with a single general purpose circuit breaker protecting three capacitor banks (36.8 MVAR each) and using two circuit switchers, one circuit switcher each to energize the second and third banks, is evaluated on a comparative basis and used as a basis for making recommendations for improvements. The capacitor banks are arranged to be switched in three steps with reactors for current inrush and outrush control. All three are protected against a possible fault in any one of
  • 2. Page 2 of 10 them by the single general-purpose circuit breaker which is also required to switch on the first capacitor bank. The peak inrush current in capacitor switching applications can be quite high, and ANSI standards have recommended limiting this inrush current to 16 kA peak at a frequency of up to 4.2 kHz by applying series reactors in the circuit. This is a quite common solution for back-to- back switching of capacitor banks. Given the available alternatives, this use of reactors was a major improvement over the previous option of switching capacitor banks without them. These three capacitor banks are connected to the bus as is shown in the diagram below. The circuit breaker is connected to the substation bus and then connected to an outrush reactor before an interconnection point where three capacitor banks are all connected through inrush reactors. Two circuit switchers are then used to control the second and third banks after the first bank is switched on by the circuit breaker. A TRV (Transient Recovery Voltage) control capacitor is used to control the TRV for a reactor fed fault should a capacitor bank or any other component flash over to ground. Circuit Switchers Circuit Breaker Outrush Reactor Inrush Reactors TRV Control Capacitor
  • 3. Page 3 of 10 Interrupter Arcing Damage - The damage to contacts and to nozzles is a function of the current magnitude and the duration of the arcing. It is generally accepted that arc damage is related to I2 t. It is on this basis that looking at the next four simulations show this arc damage index in terms of this equation. These simulations also show that back-to-back switching has a significantly higher damage index than single bank switching as the closing currents are much higher. Although this is common knowledge, these simulations show the magnitude of this difference in this specific application. The first and second simulations are for the example configuration with inrush and outrush reactors, circuit switchers, and a circuit breaker. The third and fourth simulations are for the application of a special purpose capacitor switching device, Southern States CapSwitcher ® , without the use of inrush reactors. The presence of the CapSwitcher ® ’s pre-insertion resistor dramatically limits the currents. The details of the circuit being simulated are shown in the appendix of this report. Example Configuration – Back-to-Back Switching with Inductors (Simulation 1) – Last Bank Energized = 49,650 (I2 t) Main Contact Arcing Energy
  • 4. Page 4 of 10 Example Standard Configuration – First Bank Switching with Inductors (Simulation 2) – First Bank Energized = 13,554 (I2 t) Main Contact Arcing Energy Revised Configuration With CapSwitcher ® Having 40 Ohm Pre-Insertion Resistor – Back-to-Back Switching Without Inductors (Simulation 3) - Last Bank Energized = 176 (I2 t) Main Contact Arcing Energy
  • 5. Page 5 of 10 Proposed Configuration (With Overvoltage Control) With CapSwitcher ® Having 40 Ohm Pre-Insertion Resistor Being Used On The First Bank Switched – First Bank Switching Without Inductors (Simulation 4) - First Bank Energized = 104 (I2 t) Main Contact Arcing Energy The reduction in damage index due to using the pre-insertion resistor equipped CapSwitcher ® is rather dramatic and hence the expected life of the contacts in the interrupter is also anticipated to be significantly longer as the predominant switching mode is the daily capacitor bank switching rather than the occasional fault clearing. Hopefully there is never a need for clearing faults on a capacitor bank, but one must be prepared for that possibility. This reduction in arcing damage also extends the interrupter life for that potential time when it is required that a fault be interrupted and cleared. The reason for concern about this arcing damage due to capacitor switching is the fact that interrupter life is significantly reduced and the effects are cumulative over time. Power tests in laboratories generally demonstrate capability of new devices but are rarely done with hundreds of operations in power test labs on 72.5 kV and higher voltage rated equipment. This is principally because the cost of doing these tests is generally quite expensive. As a result of this, reliance on actual field experience is the best method to verify cumulative arcing damage on interrupter nozzles and contacts, but this does take time to expose weaknesses and verify field performance. In the absence of many years of field experience, calculations of damage from arcing are made to compare design differences and application differences. The results of such calculations are shown in the following Life Calculation Table. This compares the Southern States CapSwitcher ® with a circuit switcher used in capacitor bank switching applications. The numbers in the chart highlighted in bold are taken from available literature from that circuit switcher. The numbers with a tan background show the closing operations one would expect if the maximum switching current were present for routine capacitor switching. The Southern States CapSwitcher ® has a design topology that makes it
  • 6. Page 6 of 10 impossible for the inrush current to get to its maximum magnitude. This is so because the pre- insertion resistor in the CapSwitcher ® limits the magnitude of the inrush current. The inrush reactors limit the inrush for the circuit switchers. The expected switching life is shown in yellow (back-to-back applications) and green (single bank applications) for both types of devices. Clearly, there is more damage and expected shorter contact & nozzle life for both designs in the back-to-back switching as compared to single bank switching. Life Calculation Table KEY ANSI Max. Back-to-Back 1st Bank Exp. = 2 Exp. = 1.75 Current Erosion Life Opening Closing Current Erosion Life Opening Closing KA I^Exp.2 * t * No. Operations Operations KA I^Exp.2 * t * No. Operations Operations 40 192 10 5 40 NA NA NA 31.5 192 16 10 31.5 NA NA NA 25.0 192 26 25 25.0 ?? ?? ?? 20.0 192 40 60 20.0 22.7 10 30 16.0 192 63 188 16.0 22.7 15 44 12.5 192 102 307 12.5 22.7 23 68 10.0 192 160 480 10.0 22.7 34 101 8.0 192 253 759 8.0 22.7 50 151 6.3 192 401 1,202 6.3 22.7 75 225 5.0 192 634 1,901 5.0 22.7 112 337 4.0 192 1003 3,008 4.0 22.7 168 503 3.2 192 1587 4,760 3.2 22.7 250 751 2.5 192 2510 7,531 2.5 22.7 374 1,122 2.0 192 3972 11,915 2.0 22.7 559 1,677 1.6 192 6284 18,852 1.6 22.7 835 2,505 1.3 192 9943 29,829 1.3 22.7 1247 3,742 1.0 192 15732 47,195 1.0 22.7 1864 5,591 0.8 192 24891 74,673 0.8 22.7 2784 8,353 0.6 192 39383 118,149 0.6 22.7 4160 12,480 0.5 192 62312 186,937 0.5 22.7 6215 18,645 0.4 192 98592 295,775 0.4 22.7 9286 27,857 Assumption "t" = 12 ms Opening & 4 ms Closing JRR 2-13-07 Contact & Nozzle Life Calculations Example Of Switching Configuration For 3 Capacitor Banks CapSwitcher® 145 kV without Reactors Circuit Switcher with Reactors The results of the analysis clearly show an increase of more than 200 to 1 in the expected life of the interrupter contacts and nozzle for the Southern States CapSwitcher ® with its pre-insertion resistor versus the circuit switcher. It also follows that there is no additional advantage to using inrush reactors with the CapSwitcher ® as they provide no additional reduction in the inrush current. The intrinsic interrupter design capability (Erosion Life – 192 vs. 22.7) shows an 8 to 1 improvement when using the CapSwitcher ® in lieu of the circuit switcher in this comparison simply based upon the intrinsic interrupter design. The rest of the improvement in interrupter contact life and interrupter nozzle life comes from the fact that the pre-insertion resistor is much better at limiting the inrush currents than is reasonably possible with the use of reactors. Voltage Transients - These are significantly reduced by the use of the CapSwitcher ® and are most dramatic when comparing the second simulation to the fourth. These are simulations of switching on the first capacitor bank with the general purpose SF6 circuit breaker and with a CapSwitcher ® , respectively. The reduction of the current transients is equally impressive.
  • 7. Page 7 of 10 Cost Savings From Changing Away From The Example Solution - It is clear that the previously mentioned improvements have a substantial impact from a reliability and life cycle point of view. Additionally, not having to replace equipment that is subject to failures from high operational life in-service is a further advantage. Changing to the use of the CapSwitcher ® with its pre-insertion resistor and eliminating inrush reactors results in significant savings as well. In that the inrush reactors are a necessary solution for capacitor switching devices without surge control, their need is eliminated by the newer technological approach of using the CapSwitcher ® with its pre-insertion resistors, and the CapSwitcher ® is now available and in service at many utilities. The elimination of these otherwise-needed components saves considerably on the installed cost of a substation capacitor bank switching solution. The use of the CapSwitcher ® results in a space savings as well; however, this was not included as a financial benefit. This advantage can be significant in applications where there is a need to retrofit or upgrade existing capacitor banks in older substations if there is no space to install reactors. The table below also shows there are possible cost savings of up to 24% for substations that have a 63 kA fault level and up to 33% for substations that have a 40 kA fault level. The savings are based on the substation being reconfigured to use CapSwitcher ® s instead of a circuit breaker, two circuit switchers, and reactors. The tables below outline the configuration options evaluated and their respective savings. Cost Comparison Tables JRR - 2-21-2007 Unit per Price (k$) Quantity Extended Quantity Extended Quantity Extended Standard Circuit Breaker (63 kA) 69 1 69 K$ 1 69 K$ 1 69 K$ Standard Circuit Breaker (40 kA) 53 0 0 0 Inrush Reactor (200 A- 33 kA) 5.5 9 49.5 K$ 0 0 K$ 0 0 K$ Outrush Reactor (450 A- 40 kA) 13 3 39 K$ 3 39 K$ 0 0 K$ L-G Capacitor for TRV Control 3 3 9 K$ 3 9 K$ 0 0 K$ Support Structure for XL or XC 1.5 15 22.5 K$ 6 9 K$ 0 0 K$ Foundation for XL or XC 3 15 45 K$ 6 18 K$ 0 0 K$ Circuit Switcher - 40 kAClose 34 2 68 K$ 0 0 K$ 0 0 K$ CapSwitcher® - 63 kAClose 59 0 0 K$ 2 118 K$ 3 177 K$ Equipment Total 302 K$ 262 K$ 246 K$ Equipment Savings 0 K$ 40 K$ 56 K$ Installed Estimate 1.5 Factor 453 K$ 393 K$ 369 K$ Life Cycle Costs for 20 Years Replace Interrupters @8 Yrs. Circuit Switcher 5 3 15 K$ 0 0 K$ 0 0 K$ Circuit Breaker Not Required @16 Yrs. Circuit Switcher 5 9 45 K$ 0 0 K$ 0 0 K$ CapSwitcher® Not Required Total Costs 513 K$ 393 K$ 369 K$ Net Savings 0% 0 K$ 23% 120 K$ 28% 144 K$ Substation Cost Configuration Comparison SSLLC - Proposed (With Voltage Control)SSLLC SuggestedExample Standard Configuration 145 kV- 63 kA- Three Capacitor Banks (36.8 MVAR each) in Parallel
  • 8. Page 8 of 10 It is also possible to eliminate the circuit breaker outright where substation faults are at or below 40 kA by using the 40 kA interrupting capability of the CapSwitcher ® and enabling the CapSwitcher ® ’s inherent fault interrupting capability by providing the CapSwitcher ® with current sensing via the SSIPower LLC CMD TM three phase non-contact current transformer. This solution amounts to a possible savings of up to 33% ($154,000) in total life cycle cost. JRR - 2-17-2007 Unit per Price (k$) Quantity Extended Quantity Extended Quantity Extended Standard Circuit Breaker (63 kA) 69 0 0 K$ 0 0 K$ 0 0 K$ Standard Circuit Breaker (40 kA) 53 1 53 K$ 1 53 K$ 0 0 K$ CMD™on Disconnect Switch 15 0 0 K$ 0 0 K$ 2 30 K$ Inrush Reactor (200 A- 33 kA) 4 9 36 K$ 0 0 K$ 0 0 K$ Outrush Reactor (450 A- 40 kA) 13 3 39 K$ 3 39 K$ 0 0 K$ L-G Capacitor for TRV Control 2 3 6 K$ 3 6 K$ 0 0 K$ Support Structure for XL or XC 1.5 15 22.5 K$ 6 9 K$ 0 0 K$ Foundation for XL or XC 3 15 45 K$ 6 18 K$ 0 0 K$ Circuit Switcher - 40 kAClose 34 2 68 K$ 0 0 K$ 0 0 K$ CapSwitcher® - 63 kAClose 59 0 0 K$ 2 118 K$ 3 177 K$ Equipment Total 269.5 K$ 243 K$ 207 K$ Equipment Savings 0 K$ 27 K$ 63 K$ Installed Estimate 1.5 Factor 404 K$ 365 K$ 311 K$ Life Cycle Costs for 20 Years Replace Interrupters @8 Yrs. Circuit Switcher 5 3 15 K$ 0 0 K$ 0 0 K$ Circuit Breaker Not Required @16 Yrs. Circuit Switcher 5 9 45 K$ 0 0 K$ 0 0 K$ CapSwitcher® Not Required Total Costs 464 K$ 365 K$ 311 K$ Net Savings 0% 0 K$ 21% 100 K$ 33% 154 K$ Substation Cost Configuration Comparison 145 kV- 40 kA- Three Capacitor Banks (36.8 MVAR each) in Parallel Example Standard Configuration SSLLC Suggested SSLLC - Proposed (With Voltage Control) Summary - The reliability of example capacitor bank switching arrangement can be significantly improved and cost reduced by the adoption of the CapSwitcher ® , Southern States definite purpose capacitor switching device. The cost savings can be as high as 24% for substations that have 63 kA fault levels and up to 33% for substations with 40 kA fault levels. In addition, voltage transients and inrush currents will also be reduced compared to the current example capacitor bank switching configuration. Several alternatives and configurations are presented here, allowing the customer to choose the desired configuration based on specific installation needs for new and existing substations. Conclusion - The application of Southern States CapSwitcher ® , a pre-insertion resistor device, in capacitor bank switching substation applications will increase the reliability and equipment life while also reducing costs as compared to the example capacitor switching configuration. This is because the CapSwitcher ® is designed for twice the number of mechanical operations of most other available equipment and because the CapSwitcher ® eliminates the need for inrush reactors. Additionally, the life of the interrupter is 10 to 200 times
  • 9. Page 9 of 10 that of other devices used in this capacitor switching application because of the Southern States CapSwitcher ® ’s pre-insertion resistor. The recommendation of eliminating the inrush reactors allows a smaller substation footprint and saves $100,000 per installation (20 %). The opportunity exists to increase this savings to 24% for substations having 63 kA available fault current. The cost savings opportunity increases up to 33% ($154,000) for a 40 kA available fault current substation should there be a desire to have a different capacitor switching solution for 40 kA available fault current substations versus 63 kA available fault current substations. The most cost effective proposed solutions also provide voltage surge control when switching the capacitor banks. The adoption of these recommended solutions will provide significant cost savings, increased reliability, and reduced life cycle costs. Author Biography – Joe Rostron received his Bachelor of Science degree in Mechanical Engineering from Washington State University in 1970 and his Masters Degree in Business Administration from the University of Pittsburgh in 1984. He has been employed since 1970 by Westinghouse, ABB Power T&D, Siemens Power Transmission and Distribution, and Southern States LLC with titles of Development Engineer, Engineering Manager, Product Manager, Sr. Vice President-Engineering, and is now President of SSIPower LLC (a Southern States company). He has 31 U.S. patents focusing on high voltage circuit breakers and other innovative power system technologies. He is a professional engineer in Pennsylvania and is also a member of IEEE and ASME. His experience covers a wide range of responsibilities for energy product design, development, and testing of new concepts/products; constantly seeking innovation to resolve high voltage power concerns to improve operational efficiencies and to reduce costs. His focus has been on national energy problems and development of new modern products for customer needs. Editor Biography – David Childress received his Bachelor of Science degree in Engineering from Mississippi State University in 1991. He joined Siemens Energy & Automation in 1991 as an Application Engineer responsible for circuit switchers and disconnect switches and later joined Southern States in 1997 holding positions of Regional Manager, International Sales Manager, Product Manager, and Marketing Manager of Southern States Power Switching Division. He is presently Marketing Manager of SSIPower LLC (a Southern States company) responsible for the marketing, promotion, and sale of three-phase non-contact current transformers. He is a member of IEEE; a multi-published technical paper author; an author of over 100 catalog flyers, catalog bulletins, and other technical/product related documents; and has recently co-authored a chapter for the Electric Power Substations Engineering Book-Second Edition entitled “High Voltage Switching Equipment” (ISBN: 978-0-8493-7383-1) Editor Note – The economics shown in this paper are specific to the project, configuration, and ratings being analyzed but are representative of the achievable savings for a variety of capacitor switching applications. The performance and installed life enhancement of converting to the Southern States CapSwitcher ® high voltage capacitor switching device with current sensing via the SSIPower LLC CMD TM three phase non-contact current transformer are not specific to just this project, configuration, and ratings; being instead highly representative of many capacitor switching applications.
  • 10. Page 10 of 10 Appendix Fixed Inductor Capacitor Switching CapSwitcher ® Capacitor Switching