Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 1
Presenter: Bernd Sommer
PTD EA12
Phone 0911-433-8222
Fax 0911-433-7396
email Bernd.Sommer@siemens.com
Training: Generator Protection
Machine Protection SIPROTEC 4
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 2
Generator, Motor and Transformer Protection
is part of the
SIPROTEC 4 family of
numerical
protection, control and
automation devices
by
SIEMENS
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 3
SIPROTEC 4 is the actual family of protection and control devices.
This family offers with a lot of new features a high
flexibility in applications.
The machine protection uses the advantages of this
new family.
By now the former devices V3 are sustituted by
the V4 technique.
7UM511
7UM512
7UM515
7UM516
7UT51
7UM61
7UM62
What is SIPROTEC 4?
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 4
 additional logic
NEGATOR
AND-GATTER
OR-GATTER
XOR-GATTER
TIMER
 interlocking
 processing measured values
The Integrated Configuration Tool CFC saves
external wiring
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 5
I1: 400.9A f:50.0Hz
U: 12.22kV
P :+8.03MW cos
Q :+2.64MVar
L1 402.1A Max450.1A
L2 401.2A Max421.2A
L3 401.0A Max431.4A
E 00.0A
% IL UL-E UL-L
L1 100.0 100.4 100.1
L2 100.4 100.3 100.0
L3 100.1 100.1 100.4
direct measured values: error < 0,5%
derived values: error < 1%
Voltages:
L1 - E
L2 - E
L3 - E
L1 - L2
L2 - L3
L3 - L1
Currents:
IL1
IL2
IL3
IE
IL1 MIN
IL2 MIN
IL3 MIN
IL1 MAX
IL2 MAX
IL3 MAX
Power:
P
Q
S
Counters
f
cos phi All values are accessible via the serial interface!
Comprehensive Measured Value Processing gives an
overview about the process
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 6
Pin Lugs
Solid Conductors
Ring Lugs
Robust Terminals Guarantee a Reliable Connection
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 7
Fault
Measured
Values
Counters
Param.II
Convenient and fast access to frequently
used control sequences
4 Freely Configurable Function Keys
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 8
Fibre optic
Electrical
 Exchange
 Retro-fit
 IEC 60870-5-103
 Profibus FMS
 Profibus DP
 Modbus RTU
 DNP 3
 Ethernet
IEC61850
Flexible Interfaces Open for Different Communication
Solutions
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 9
Control system
for power plants
Profibus DP
7UM622 7UM621 7UM612 7UT612
7UT613
Unit Protection
Modem
Modem
RS 485
DIGSI 4
Remote Control
Telephone Network
Annunciations
Measurands
Example for Communication
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 10
Operator control
and process
7UM622 7UM621 7UM612 7UT612
7UT613
Unit Protection
DIGSI 4
Remote Control
RS 485
Modem
Modem
Telephone Network
Control system
for power plants
Profibus DP
SICAM
IEC 60870-5-103
Annunciations
Measurands
Annunciations
Measurands
Fault records
with IEC
Example for Communication
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 11
7UM621 7UM611
7UT613
Unit Protection
7SJ63 7UM621
7SJ62
Auxilary
Switchgear
Profibus DP
Modem
Modem
RS 485
DIGSI 4
Remote Control
Telephone Network
Control system
for power plants
Profibus DP
Annunciations
Measurands
Control of AUX
Example for Communication
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 12
Operator control
and process
SICAM
IEC 60870-5-103
7UM621 7UM611
7UT633
Unit Protection
IEC 60870-5-103
Modem
Modem
RS 485
DIGSI 4
Remote Control
Telephone Network
Control system
for power plants
Profibus DP
7SJ63 7UM621
7SJ62
Auxilary Switchgear
Annunciations
Measurands
Control of AUX
Example for Communication
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 13
22Bit
ADC
22 Bit
ADC
U
I
32Bit
P
Memory
Serial
Interface
Local
HMI
BO
BI
Modern high integrated Circuits guarantees
a high Power and Reliability
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 14
Masking
Test and Diagnostics
Fault Analysis
Editing the
Graphic Display
All Siemens numerical protection devices are
operated with only one program!
Convenient Operation with DIGSI 4
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 15
7UM6, 7UT6
RS 485
 Connection of up to 2 temperature boxes to the service interface
 Electric interface RS485
 Monitoring of up to 12 temperature measurements
 Indication of temperatures as operational measured values
 Monitoring of temperature set-points for alarming
 Integration of temperature measurement for hot spot calculation (oil temperature)
External Temperature Measuring with Thermobox and
Serial Transmission
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 16
Currents on the high
and low voltage side
of the transformer
Tripping characteristic
with the settings and
actual operating points
Commissioning Support with the
Browser- Technology
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 17
+
large
medium
small
G
Generators
M
large
Induction Motors
Synchronous Motors
+
large Transformers
7UM6
The Universal Protection for
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 18
7UM611
3 x U, 1 x Ue
3 x I; 1 x Iee
7 binary inputs (6r; 1)
11 binary outputs (2r, 5r; 4)
Same functions - different number of binary inputs and outputs
7UM612 3 x U, 1 x Ue
3 x I; 1 x Iee
15 binary inputs (6r; 3r, 6)
19 binary outputs (2r, 3r, 5r; 9)
Use, where more binary inputs and outputs are required
(medium and large power plants)
r: common root
Protection Unit 7UM61 in 2 Models
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 19
Function Mix 7UM61
 Stator earth-fault prot., non-/, directional (59N, 64G, 67G)
 Sensitive eath-fault prot., rotor earth-fault prot. (50/51GN, 64R)
 Overload protection (49)
 Definite time overcurrent prot. with undervoltage seal-in (51)
 Definite time overcurrent prot., directional (50/51/67)
 Inverse time overcurrent prot. (controlled, restraint) (51V)
 Over voltage protection (59)
 Under voltage protection (27)
 Frequency protection (81)
 Reverse-power protection (32R)
 Overexcitation protection (24)
 Fuse Failure Monitor (60FL)
 External trip coupling
 Trip circuit supervision (74TC)
 Forward-power protection (32F)
 Underexcitation protection (40)
 Negative sequence protection (46)
 Circuit-breaker prot. (50BF)
 Inadvertant energization protection (50/27)
 100%-stator-earth-fault prot. with 3rd harmonics (59TN, 27TN)
 Impedance protection with I>/U<-pick-up (21)
7UM611
7UM612
A
-
Basic
B
-
Standard
C
-
Full
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 20
A - Basic: (7UM611)
Protection of small generators (<1 MW - 3 MW)
Back-up protection of parallel connected transformers
Network decoupling using CFC
B - Standard: (7UM611, 7UM612)
Protection of generators (2 MW - 5 MW)
Back-up protection of power plants(> 5 MW)
Protection of synchronous motors
C - Full: (7UM611, 7UM612)
Protection Group 2 (back-up protection)
of generators (> 5MW)
100% stator earth-fault protection (3rd harmonic)
Function Mix 7UM61 – Application
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 21
It contains all functions for the protection of medium and large
generators (> 5MW);
with differential protection; as well as supplementary functions
for large generators
It contains all functions for the
protection of large induction and synchronous
motors
It contains all functions for the protection of
transformers, especially if additional functions
are required (U, f, U0, U/f)
7UM62 - The Universal Machine Protection
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 22
Same functions - different number of binary inputs and outputs
7UM621
3 x U, 1 x Ue
6 x I; 2 x Iee
3 x Measuring Transducers
7 binary inputs (5r; 2)
12 binary outputs (5r; 7)
7UM622
3 x U, 1 x Ue
6 x I; 2 x Iee
3 x Measuring Transducers
15 binary inputs (5r; 3r, 7)
19 binary outputs (5r, 3r, 12)
Use, where more binary inputs and outputs
are required (large power plants, process of
external non-electrical signals)
r: common root
Protection Unit 7UM62 in 2 Models
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 23
Additional to the functions of
7UM61 (Standard or Full):
 Differential protection (87G/87T)
 Temperature supervision (Thermobox) (38)
 Start inhibit for motors (49Rotor)
 Rotor earth-fault protection (fn, R-measuring) (64R)
 DC-voltage protection (59N DC)
 Earth current differential protection (REF 87GN)
 Out of step protection (78)
 Overcurrent protection during start up (51)
 Rotor earth-fault protection 1 - 3 Hz-measuring (64R)
 100% stator earth-fault protection with 20 Hz (64G-100%)
 Rate-of-frequency protection df/dt (81R)
 Vector jump (voltage)
Trafo
+
7UM
61
Stand.
Motor
+
7UM
61
Stand.
Geno
Basic
+
7UM61
Stand.
Geno
Standard
+
7UM
61
Full
Geno
Full
+
7UM61
Full
Options
to
all
functions
7UM621
7UM622
Function Mix 7UM62
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 24
H - Transformer 7UM62 (incl. 7UM61 Standard):
Main protection for large transformers with
additional functions
Parallel connected transformers
B - Generator Standard 7UM62 (incl. 7MU61 Full):
Main protection for generators > (5 - 10) MW
Back-up protection for power plants
F - Asynchronous Motor 7UM62 (incl. 7UM61 Standard):
Main protection for induction motors > 1 MW
A - Generator Basic 7UM62 (incl. 7UM61 Standard):
Main protection for generators > (2 -5) MW
Main protection for synchronous motors
C - Generator Full 7UM62 (incl. 7MU61 Full):
Main protection for large generators > 50 MW
Back-up protection for power plants
Function Mix 7UM62 – Application
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 25
7UT612
 7 x I (1A, 5A, 0,1A), 1 x Iee
 3 binary inputs (2r; 1)
 4 binary outputs (4)
 System interface
 IEC 60870-5-103
 Profibus FMS
 Profibus DP
 DNP3.0
 Modbus ASCII/RTU
 Service interface
 DIGSI4 operation
 Modem connection
 Temperature box
 Time synchronisation
 Front service interface
r: common root
Differential Protection 7UT612
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 26
7UT612
 Differential prot. for two terminal, 3-phase prot. objects (87) Transformer,
auto transformer, generator/motor, small busbar
(3-phase), busbar (single phase),
 Differential earth fault prot. (87N)
 Definite time/IDMT phase over current (50/51)
 Definite time/IDMT earth over current 3I0 (50/51N)
 Definite time/IDMT earth over current (50/51G)
 Definite time single phase over current prot. (suitable for high impedance
circulating current prot. (87GD), tank prot.)
 Overload prot. with thermal image according to IEC60255-8 (49)
 Hot spot calc. with determination of the relative rate of aging according to
IEC60354
 Coupling of external signals
 Trip circuit supervision (74TC)
 Negative sequence protection (46)
 Breaker failure protection (50BF)
 Operational measured values, fault recording
Scope of Functions 7UT6
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 27
*) in preparation
 7UT612 for 2-terminal protected objects -
 7 x I (1A, 5A, 0,1A), 1 x Iee
 3 binary inputs, 4 binary outputs, 1 life-contact
 7UT613 for 3-terminal protected objects *)
 11 x I (1A, 5A), 1 x Iee
 5 binary inputs, 7 binary outputs, 1 life-contact
 7UT633 for 3-terminal protected objects *)
 11 x I (1A, 5A), 1 x Iee, 3 x Uph, 1 x Ue
 21 binary inputs, 23 binary outputs, 1 life-contact
 7UT635 for 5-terminal protected objects *)
 16 x I (1A, 5A, 0,1A), 1 x Iee, 3 x Uph, 1 x Ue
 21 binary inputs, 15 binary outputs, 1 life-contact
7UT6xx - Family, Hardware Variants
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 28
 Large frequency range from 11Hz to 69 Hz;
high measuring accuracy (U,I <0,5%; S< 1%, f<10 mHz)
 All implemented protection functions run in parallel with
out limitation (functionality depends on the connection)
 International protection standards (IEC, ANSI)
 Disturbance recorder with instantaneous or rms values
(calculated values, every cycle; length max. 80 s)
 Commissioning aids (check of BI, BO, separate blocking
of the TRIP command during primary test for each function)
 Application focused selection of protection functions
Highlights 7UM61 / 7UM62
Energy Sector
Copyright
©
Siemens
AG
2008.
All
rights
reserved.
Siemens Power Academy TD
02 Machine Protection SIPROTEC 4
Using numerical machine and motor protection
Version: C 3_Page 29
 Hardware and software based on SIPROTEC 4
 Fundamental adoption of proven algorithms from 7UM5x
 Extension and new combination of protection functions
 The implemented functions fulfil the protection requirements for
direct connection and unit connection schemes
 With the of combination 7UM61, 7UM62, 7UT61, 7UT 63 as well as
7SJ6 flexible redundancy concepts can be achieved
 The communication with control systems is realized with e.g.
Profibus DP (annunciations and measurements)
 Price scaling of devices through function splitting
Summary

More Related Content

Similar to 02_C_3_Machine Protection SIPROTEC 4.ppt

Spam 20
Spam 20Spam 20
7SJ62 Multifunction Over Current Protection Relay
7SJ62 Multifunction Over Current Protection Relay7SJ62 Multifunction Over Current Protection Relay
7SJ62 Multifunction Over Current Protection Relay
ashwini reliserv
 
Siemens catalog tong hop low voltage motor
Siemens catalog tong hop low voltage motorSiemens catalog tong hop low voltage motor
Siemens catalog tong hop low voltage motor
Dien Ha The
 
09-1 Machine Prot. Exercises.ppt
09-1 Machine Prot. Exercises.ppt09-1 Machine Prot. Exercises.ppt
09-1 Machine Prot. Exercises.ppt
MAHMOUDMOHAMED431205
 
Catalogues sepam 20 40 60 80
Catalogues sepam 20 40 60 80Catalogues sepam 20 40 60 80
Catalogues sepam 20 40 60 80
Hoàng Phương JSC
 
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
Optimus Energy Philippines
 
Protection, Automation and Monitoring: SIPROTEC 5 v7.9/v8.0
Protection, Automation and Monitoring:  SIPROTEC 5 v7.9/v8.0Protection, Automation and Monitoring:  SIPROTEC 5 v7.9/v8.0
Protection, Automation and Monitoring: SIPROTEC 5 v7.9/v8.0
Ryan O'Mara
 
7SJ64 Relay
7SJ64 Relay7SJ64 Relay
7SJ64 Relay
ashwini reliserv
 
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Dien Ha The
 
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...
Dien Ha The
 
Sepam 20 2009
Sepam 20   2009Sepam 20   2009
Sepam 20 2009
Hoàng Phương JSC
 
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_enA6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
tekhakko
 
7SJ61 Over Current Relay
7SJ61 Over Current Relay7SJ61 Over Current Relay
7SJ61 Over Current Relay
ashwini reliserv
 
rodamientos motores siemens
rodamientos motores siemensrodamientos motores siemens
rodamientos motores siemens
victordavalos5
 
Riello aros-central-transformer-based-solar-inverters
Riello aros-central-transformer-based-solar-invertersRiello aros-central-transformer-based-solar-inverters
Riello aros-central-transformer-based-solar-inverters
Electrical and renewable energy engineering
 
Rūpnieciskā automatizācija ar WAGO risinājumiem
Rūpnieciskā automatizācija ar WAGO risinājumiemRūpnieciskā automatizācija ar WAGO risinājumiem
Rūpnieciskā automatizācija ar WAGO risinājumiem
Elektrumlv
 
Software-supported testing - SENTRON 3WA air circuit breakers .pdf
Software-supported testing - SENTRON 3WA air circuit breakers .pdfSoftware-supported testing - SENTRON 3WA air circuit breakers .pdf
Software-supported testing - SENTRON 3WA air circuit breakers .pdf
AldoBarajas6
 
15_C_3_Numerical paralleling device_7VE6.ppt
15_C_3_Numerical paralleling device_7VE6.ppt15_C_3_Numerical paralleling device_7VE6.ppt
15_C_3_Numerical paralleling device_7VE6.ppt
MAHMOUDMOHAMED431205
 
Emdg c10065-02-7600 relay-selection_guide_edition_7_en
Emdg c10065-02-7600 relay-selection_guide_edition_7_enEmdg c10065-02-7600 relay-selection_guide_edition_7_en
Emdg c10065-02-7600 relay-selection_guide_edition_7_en
nguyenvantrungnguyen
 
Cpu226
Cpu226Cpu226

Similar to 02_C_3_Machine Protection SIPROTEC 4.ppt (20)

Spam 20
Spam 20Spam 20
Spam 20
 
7SJ62 Multifunction Over Current Protection Relay
7SJ62 Multifunction Over Current Protection Relay7SJ62 Multifunction Over Current Protection Relay
7SJ62 Multifunction Over Current Protection Relay
 
Siemens catalog tong hop low voltage motor
Siemens catalog tong hop low voltage motorSiemens catalog tong hop low voltage motor
Siemens catalog tong hop low voltage motor
 
09-1 Machine Prot. Exercises.ppt
09-1 Machine Prot. Exercises.ppt09-1 Machine Prot. Exercises.ppt
09-1 Machine Prot. Exercises.ppt
 
Catalogues sepam 20 40 60 80
Catalogues sepam 20 40 60 80Catalogues sepam 20 40 60 80
Catalogues sepam 20 40 60 80
 
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
 
Protection, Automation and Monitoring: SIPROTEC 5 v7.9/v8.0
Protection, Automation and Monitoring:  SIPROTEC 5 v7.9/v8.0Protection, Automation and Monitoring:  SIPROTEC 5 v7.9/v8.0
Protection, Automation and Monitoring: SIPROTEC 5 v7.9/v8.0
 
7SJ64 Relay
7SJ64 Relay7SJ64 Relay
7SJ64 Relay
 
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910
 
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...
Ls catalog thiet bi tu dong imp intelligent motor_protectionrelay_e_0910_dien...
 
Sepam 20 2009
Sepam 20   2009Sepam 20   2009
Sepam 20 2009
 
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_enA6 v10370250 variable speed drive for pumps and fans sinamics g_en
A6 v10370250 variable speed drive for pumps and fans sinamics g_en
 
7SJ61 Over Current Relay
7SJ61 Over Current Relay7SJ61 Over Current Relay
7SJ61 Over Current Relay
 
rodamientos motores siemens
rodamientos motores siemensrodamientos motores siemens
rodamientos motores siemens
 
Riello aros-central-transformer-based-solar-inverters
Riello aros-central-transformer-based-solar-invertersRiello aros-central-transformer-based-solar-inverters
Riello aros-central-transformer-based-solar-inverters
 
Rūpnieciskā automatizācija ar WAGO risinājumiem
Rūpnieciskā automatizācija ar WAGO risinājumiemRūpnieciskā automatizācija ar WAGO risinājumiem
Rūpnieciskā automatizācija ar WAGO risinājumiem
 
Software-supported testing - SENTRON 3WA air circuit breakers .pdf
Software-supported testing - SENTRON 3WA air circuit breakers .pdfSoftware-supported testing - SENTRON 3WA air circuit breakers .pdf
Software-supported testing - SENTRON 3WA air circuit breakers .pdf
 
15_C_3_Numerical paralleling device_7VE6.ppt
15_C_3_Numerical paralleling device_7VE6.ppt15_C_3_Numerical paralleling device_7VE6.ppt
15_C_3_Numerical paralleling device_7VE6.ppt
 
Emdg c10065-02-7600 relay-selection_guide_edition_7_en
Emdg c10065-02-7600 relay-selection_guide_edition_7_enEmdg c10065-02-7600 relay-selection_guide_edition_7_en
Emdg c10065-02-7600 relay-selection_guide_edition_7_en
 
Cpu226
Cpu226Cpu226
Cpu226
 

More from MAHMOUDMOHAMED431205

OC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptxOC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptx
MAHMOUDMOHAMED431205
 
protection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptxprotection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptx
MAHMOUDMOHAMED431205
 
cathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptxcathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptx
MAHMOUDMOHAMED431205
 
plan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptxplan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptx
MAHMOUDMOHAMED431205
 
Meduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptxMeduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptx
MAHMOUDMOHAMED431205
 
power Tr 2 course.ppt
power Tr 2 course.pptpower Tr 2 course.ppt
power Tr 2 course.ppt
MAHMOUDMOHAMED431205
 
power Tr 1 course.ppt
power Tr 1 course.pptpower Tr 1 course.ppt
power Tr 1 course.ppt
MAHMOUDMOHAMED431205
 
MOTOR PROTECTION.pptx
MOTOR PROTECTION.pptxMOTOR PROTECTION.pptx
MOTOR PROTECTION.pptx
MAHMOUDMOHAMED431205
 
Meduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptxMeduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptx
MAHMOUDMOHAMED431205
 
Single Line Diagram.pptx
Single Line Diagram.pptxSingle Line Diagram.pptx
Single Line Diagram.pptx
MAHMOUDMOHAMED431205
 
CT and VT.pptx
CT and VT.pptxCT and VT.pptx
CT and VT.pptx
MAHMOUDMOHAMED431205
 
power cable1.ppt
power cable1.pptpower cable1.ppt
power cable1.ppt
MAHMOUDMOHAMED431205
 
MOTOR PROTECTION.pptx
MOTOR PROTECTION.pptxMOTOR PROTECTION.pptx
MOTOR PROTECTION.pptx
MAHMOUDMOHAMED431205
 
starting current of motor.pptx
starting current of motor.pptxstarting current of motor.pptx
starting current of motor.pptx
MAHMOUDMOHAMED431205
 
protection Training.pptx
protection Training.pptxprotection Training.pptx
protection Training.pptx
MAHMOUDMOHAMED431205
 
09-2 Machine Prot. Exercises en Synchro.ppt
09-2 Machine Prot. Exercises en Synchro.ppt09-2 Machine Prot. Exercises en Synchro.ppt
09-2 Machine Prot. Exercises en Synchro.ppt
MAHMOUDMOHAMED431205
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt
MAHMOUDMOHAMED431205
 
08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt
MAHMOUDMOHAMED431205
 

More from MAHMOUDMOHAMED431205 (20)

OC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptxOC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptx
 
protection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptxprotection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptx
 
cathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptxcathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptx
 
plan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptxplan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptx
 
Meduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptxMeduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptx
 
power Tr 2 course.ppt
power Tr 2 course.pptpower Tr 2 course.ppt
power Tr 2 course.ppt
 
power Tr 1 course.ppt
power Tr 1 course.pptpower Tr 1 course.ppt
power Tr 1 course.ppt
 
MOTOR PROTECTION.pptx
MOTOR PROTECTION.pptxMOTOR PROTECTION.pptx
MOTOR PROTECTION.pptx
 
Meduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptxMeduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptx
 
Single Line Diagram.pptx
Single Line Diagram.pptxSingle Line Diagram.pptx
Single Line Diagram.pptx
 
CT and VT.pptx
CT and VT.pptxCT and VT.pptx
CT and VT.pptx
 
power cable 3.pptx
power cable 3.pptxpower cable 3.pptx
power cable 3.pptx
 
power cable 2.pptx
power cable 2.pptxpower cable 2.pptx
power cable 2.pptx
 
power cable1.ppt
power cable1.pptpower cable1.ppt
power cable1.ppt
 
MOTOR PROTECTION.pptx
MOTOR PROTECTION.pptxMOTOR PROTECTION.pptx
MOTOR PROTECTION.pptx
 
starting current of motor.pptx
starting current of motor.pptxstarting current of motor.pptx
starting current of motor.pptx
 
protection Training.pptx
protection Training.pptxprotection Training.pptx
protection Training.pptx
 
09-2 Machine Prot. Exercises en Synchro.ppt
09-2 Machine Prot. Exercises en Synchro.ppt09-2 Machine Prot. Exercises en Synchro.ppt
09-2 Machine Prot. Exercises en Synchro.ppt
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt
 
08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt
 

Recently uploaded

Computational Engineering IITH Presentation
Computational Engineering IITH PresentationComputational Engineering IITH Presentation
Computational Engineering IITH Presentation
co23btech11018
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
SUTEJAS
 
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
ihlasbinance2003
 
Eric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball play
Eric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball playEric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball play
Eric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball play
enizeyimana36
 
basic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdfbasic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdf
NidhalKahouli2
 
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
IJECEIAES
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
KrishnaveniKrishnara1
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
Aditya Rajan Patra
 
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTCHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
jpsjournal1
 
New techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdfNew techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdf
wisnuprabawa3
 
Manufacturing Process of molasses based distillery ppt.pptx
Manufacturing Process of molasses based distillery ppt.pptxManufacturing Process of molasses based distillery ppt.pptx
Manufacturing Process of molasses based distillery ppt.pptx
Madan Karki
 
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdfBPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
MIGUELANGEL966976
 
Engine Lubrication performance System.pdf
Engine Lubrication performance System.pdfEngine Lubrication performance System.pdf
Engine Lubrication performance System.pdf
mamamaam477
 
The Python for beginners. This is an advance computer language.
The Python for beginners. This is an advance computer language.The Python for beginners. This is an advance computer language.
The Python for beginners. This is an advance computer language.
sachin chaurasia
 
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
171ticu
 
International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...
gerogepatton
 
2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf
2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf
2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf
Yasser Mahgoub
 
A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...
nooriasukmaningtyas
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
Dr Ramhari Poudyal
 
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptxML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
JamalHussainArman
 

Recently uploaded (20)

Computational Engineering IITH Presentation
Computational Engineering IITH PresentationComputational Engineering IITH Presentation
Computational Engineering IITH Presentation
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
 
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
 
Eric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball play
Eric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball playEric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball play
Eric Nizeyimana's document 2006 from gicumbi to ttc nyamata handball play
 
basic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdfbasic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdf
 
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
 
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTCHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
 
New techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdfNew techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdf
 
Manufacturing Process of molasses based distillery ppt.pptx
Manufacturing Process of molasses based distillery ppt.pptxManufacturing Process of molasses based distillery ppt.pptx
Manufacturing Process of molasses based distillery ppt.pptx
 
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdfBPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
 
Engine Lubrication performance System.pdf
Engine Lubrication performance System.pdfEngine Lubrication performance System.pdf
Engine Lubrication performance System.pdf
 
The Python for beginners. This is an advance computer language.
The Python for beginners. This is an advance computer language.The Python for beginners. This is an advance computer language.
The Python for beginners. This is an advance computer language.
 
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样官方认证美国密歇根州立大学毕业证学位证书原版一模一样
官方认证美国密歇根州立大学毕业证学位证书原版一模一样
 
International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...
 
2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf
2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf
2008 BUILDING CONSTRUCTION Illustrated - Ching Chapter 02 The Building.pdf
 
A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
 
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptxML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
 

02_C_3_Machine Protection SIPROTEC 4.ppt

  • 1. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 1 Presenter: Bernd Sommer PTD EA12 Phone 0911-433-8222 Fax 0911-433-7396 email Bernd.Sommer@siemens.com Training: Generator Protection Machine Protection SIPROTEC 4
  • 2. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 2 Generator, Motor and Transformer Protection is part of the SIPROTEC 4 family of numerical protection, control and automation devices by SIEMENS
  • 3. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 3 SIPROTEC 4 is the actual family of protection and control devices. This family offers with a lot of new features a high flexibility in applications. The machine protection uses the advantages of this new family. By now the former devices V3 are sustituted by the V4 technique. 7UM511 7UM512 7UM515 7UM516 7UT51 7UM61 7UM62 What is SIPROTEC 4?
  • 4. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 4  additional logic NEGATOR AND-GATTER OR-GATTER XOR-GATTER TIMER  interlocking  processing measured values The Integrated Configuration Tool CFC saves external wiring
  • 5. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 5 I1: 400.9A f:50.0Hz U: 12.22kV P :+8.03MW cos Q :+2.64MVar L1 402.1A Max450.1A L2 401.2A Max421.2A L3 401.0A Max431.4A E 00.0A % IL UL-E UL-L L1 100.0 100.4 100.1 L2 100.4 100.3 100.0 L3 100.1 100.1 100.4 direct measured values: error < 0,5% derived values: error < 1% Voltages: L1 - E L2 - E L3 - E L1 - L2 L2 - L3 L3 - L1 Currents: IL1 IL2 IL3 IE IL1 MIN IL2 MIN IL3 MIN IL1 MAX IL2 MAX IL3 MAX Power: P Q S Counters f cos phi All values are accessible via the serial interface! Comprehensive Measured Value Processing gives an overview about the process
  • 6. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 6 Pin Lugs Solid Conductors Ring Lugs Robust Terminals Guarantee a Reliable Connection
  • 7. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 7 Fault Measured Values Counters Param.II Convenient and fast access to frequently used control sequences 4 Freely Configurable Function Keys
  • 8. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 8 Fibre optic Electrical  Exchange  Retro-fit  IEC 60870-5-103  Profibus FMS  Profibus DP  Modbus RTU  DNP 3  Ethernet IEC61850 Flexible Interfaces Open for Different Communication Solutions
  • 9. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 9 Control system for power plants Profibus DP 7UM622 7UM621 7UM612 7UT612 7UT613 Unit Protection Modem Modem RS 485 DIGSI 4 Remote Control Telephone Network Annunciations Measurands Example for Communication
  • 10. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 10 Operator control and process 7UM622 7UM621 7UM612 7UT612 7UT613 Unit Protection DIGSI 4 Remote Control RS 485 Modem Modem Telephone Network Control system for power plants Profibus DP SICAM IEC 60870-5-103 Annunciations Measurands Annunciations Measurands Fault records with IEC Example for Communication
  • 11. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 11 7UM621 7UM611 7UT613 Unit Protection 7SJ63 7UM621 7SJ62 Auxilary Switchgear Profibus DP Modem Modem RS 485 DIGSI 4 Remote Control Telephone Network Control system for power plants Profibus DP Annunciations Measurands Control of AUX Example for Communication
  • 12. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 12 Operator control and process SICAM IEC 60870-5-103 7UM621 7UM611 7UT633 Unit Protection IEC 60870-5-103 Modem Modem RS 485 DIGSI 4 Remote Control Telephone Network Control system for power plants Profibus DP 7SJ63 7UM621 7SJ62 Auxilary Switchgear Annunciations Measurands Control of AUX Example for Communication
  • 13. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 13 22Bit ADC 22 Bit ADC U I 32Bit P Memory Serial Interface Local HMI BO BI Modern high integrated Circuits guarantees a high Power and Reliability
  • 14. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 14 Masking Test and Diagnostics Fault Analysis Editing the Graphic Display All Siemens numerical protection devices are operated with only one program! Convenient Operation with DIGSI 4
  • 15. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 15 7UM6, 7UT6 RS 485  Connection of up to 2 temperature boxes to the service interface  Electric interface RS485  Monitoring of up to 12 temperature measurements  Indication of temperatures as operational measured values  Monitoring of temperature set-points for alarming  Integration of temperature measurement for hot spot calculation (oil temperature) External Temperature Measuring with Thermobox and Serial Transmission
  • 16. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 16 Currents on the high and low voltage side of the transformer Tripping characteristic with the settings and actual operating points Commissioning Support with the Browser- Technology
  • 17. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 17 + large medium small G Generators M large Induction Motors Synchronous Motors + large Transformers 7UM6 The Universal Protection for
  • 18. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 18 7UM611 3 x U, 1 x Ue 3 x I; 1 x Iee 7 binary inputs (6r; 1) 11 binary outputs (2r, 5r; 4) Same functions - different number of binary inputs and outputs 7UM612 3 x U, 1 x Ue 3 x I; 1 x Iee 15 binary inputs (6r; 3r, 6) 19 binary outputs (2r, 3r, 5r; 9) Use, where more binary inputs and outputs are required (medium and large power plants) r: common root Protection Unit 7UM61 in 2 Models
  • 19. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 19 Function Mix 7UM61  Stator earth-fault prot., non-/, directional (59N, 64G, 67G)  Sensitive eath-fault prot., rotor earth-fault prot. (50/51GN, 64R)  Overload protection (49)  Definite time overcurrent prot. with undervoltage seal-in (51)  Definite time overcurrent prot., directional (50/51/67)  Inverse time overcurrent prot. (controlled, restraint) (51V)  Over voltage protection (59)  Under voltage protection (27)  Frequency protection (81)  Reverse-power protection (32R)  Overexcitation protection (24)  Fuse Failure Monitor (60FL)  External trip coupling  Trip circuit supervision (74TC)  Forward-power protection (32F)  Underexcitation protection (40)  Negative sequence protection (46)  Circuit-breaker prot. (50BF)  Inadvertant energization protection (50/27)  100%-stator-earth-fault prot. with 3rd harmonics (59TN, 27TN)  Impedance protection with I>/U<-pick-up (21) 7UM611 7UM612 A - Basic B - Standard C - Full
  • 20. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 20 A - Basic: (7UM611) Protection of small generators (<1 MW - 3 MW) Back-up protection of parallel connected transformers Network decoupling using CFC B - Standard: (7UM611, 7UM612) Protection of generators (2 MW - 5 MW) Back-up protection of power plants(> 5 MW) Protection of synchronous motors C - Full: (7UM611, 7UM612) Protection Group 2 (back-up protection) of generators (> 5MW) 100% stator earth-fault protection (3rd harmonic) Function Mix 7UM61 – Application
  • 21. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 21 It contains all functions for the protection of medium and large generators (> 5MW); with differential protection; as well as supplementary functions for large generators It contains all functions for the protection of large induction and synchronous motors It contains all functions for the protection of transformers, especially if additional functions are required (U, f, U0, U/f) 7UM62 - The Universal Machine Protection
  • 22. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 22 Same functions - different number of binary inputs and outputs 7UM621 3 x U, 1 x Ue 6 x I; 2 x Iee 3 x Measuring Transducers 7 binary inputs (5r; 2) 12 binary outputs (5r; 7) 7UM622 3 x U, 1 x Ue 6 x I; 2 x Iee 3 x Measuring Transducers 15 binary inputs (5r; 3r, 7) 19 binary outputs (5r, 3r, 12) Use, where more binary inputs and outputs are required (large power plants, process of external non-electrical signals) r: common root Protection Unit 7UM62 in 2 Models
  • 23. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 23 Additional to the functions of 7UM61 (Standard or Full):  Differential protection (87G/87T)  Temperature supervision (Thermobox) (38)  Start inhibit for motors (49Rotor)  Rotor earth-fault protection (fn, R-measuring) (64R)  DC-voltage protection (59N DC)  Earth current differential protection (REF 87GN)  Out of step protection (78)  Overcurrent protection during start up (51)  Rotor earth-fault protection 1 - 3 Hz-measuring (64R)  100% stator earth-fault protection with 20 Hz (64G-100%)  Rate-of-frequency protection df/dt (81R)  Vector jump (voltage) Trafo + 7UM 61 Stand. Motor + 7UM 61 Stand. Geno Basic + 7UM61 Stand. Geno Standard + 7UM 61 Full Geno Full + 7UM61 Full Options to all functions 7UM621 7UM622 Function Mix 7UM62
  • 24. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 24 H - Transformer 7UM62 (incl. 7UM61 Standard): Main protection for large transformers with additional functions Parallel connected transformers B - Generator Standard 7UM62 (incl. 7MU61 Full): Main protection for generators > (5 - 10) MW Back-up protection for power plants F - Asynchronous Motor 7UM62 (incl. 7UM61 Standard): Main protection for induction motors > 1 MW A - Generator Basic 7UM62 (incl. 7UM61 Standard): Main protection for generators > (2 -5) MW Main protection for synchronous motors C - Generator Full 7UM62 (incl. 7MU61 Full): Main protection for large generators > 50 MW Back-up protection for power plants Function Mix 7UM62 – Application
  • 25. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 25 7UT612  7 x I (1A, 5A, 0,1A), 1 x Iee  3 binary inputs (2r; 1)  4 binary outputs (4)  System interface  IEC 60870-5-103  Profibus FMS  Profibus DP  DNP3.0  Modbus ASCII/RTU  Service interface  DIGSI4 operation  Modem connection  Temperature box  Time synchronisation  Front service interface r: common root Differential Protection 7UT612
  • 26. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 26 7UT612  Differential prot. for two terminal, 3-phase prot. objects (87) Transformer, auto transformer, generator/motor, small busbar (3-phase), busbar (single phase),  Differential earth fault prot. (87N)  Definite time/IDMT phase over current (50/51)  Definite time/IDMT earth over current 3I0 (50/51N)  Definite time/IDMT earth over current (50/51G)  Definite time single phase over current prot. (suitable for high impedance circulating current prot. (87GD), tank prot.)  Overload prot. with thermal image according to IEC60255-8 (49)  Hot spot calc. with determination of the relative rate of aging according to IEC60354  Coupling of external signals  Trip circuit supervision (74TC)  Negative sequence protection (46)  Breaker failure protection (50BF)  Operational measured values, fault recording Scope of Functions 7UT6
  • 27. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 27 *) in preparation  7UT612 for 2-terminal protected objects -  7 x I (1A, 5A, 0,1A), 1 x Iee  3 binary inputs, 4 binary outputs, 1 life-contact  7UT613 for 3-terminal protected objects *)  11 x I (1A, 5A), 1 x Iee  5 binary inputs, 7 binary outputs, 1 life-contact  7UT633 for 3-terminal protected objects *)  11 x I (1A, 5A), 1 x Iee, 3 x Uph, 1 x Ue  21 binary inputs, 23 binary outputs, 1 life-contact  7UT635 for 5-terminal protected objects *)  16 x I (1A, 5A, 0,1A), 1 x Iee, 3 x Uph, 1 x Ue  21 binary inputs, 15 binary outputs, 1 life-contact 7UT6xx - Family, Hardware Variants
  • 28. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 28  Large frequency range from 11Hz to 69 Hz; high measuring accuracy (U,I <0,5%; S< 1%, f<10 mHz)  All implemented protection functions run in parallel with out limitation (functionality depends on the connection)  International protection standards (IEC, ANSI)  Disturbance recorder with instantaneous or rms values (calculated values, every cycle; length max. 80 s)  Commissioning aids (check of BI, BO, separate blocking of the TRIP command during primary test for each function)  Application focused selection of protection functions Highlights 7UM61 / 7UM62
  • 29. Energy Sector Copyright © Siemens AG 2008. All rights reserved. Siemens Power Academy TD 02 Machine Protection SIPROTEC 4 Using numerical machine and motor protection Version: C 3_Page 29  Hardware and software based on SIPROTEC 4  Fundamental adoption of proven algorithms from 7UM5x  Extension and new combination of protection functions  The implemented functions fulfil the protection requirements for direct connection and unit connection schemes  With the of combination 7UM61, 7UM62, 7UT61, 7UT 63 as well as 7SJ6 flexible redundancy concepts can be achieved  The communication with control systems is realized with e.g. Profibus DP (annunciations and measurements)  Price scaling of devices through function splitting Summary