More Related Content
Similar to 02_D03_Basic funtion of SIPROTEC 5_2012.ppt (20)
02_D03_Basic funtion of SIPROTEC 5_2012.ppt
- 2. Copyright
©
Siemens
AG
2012.
All
rights
reserved.
Siemens Power Academy TD
02 Basic function of SIPROTEC 5
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D_03_Page 2
Funciones básicas de SIPROTEC 5
SIPROTEC 5
50 51
87L 50BF 25 79
21
A V f P Q cos φ A max
-kWh
+kWh
SW HW ∑ I=0
SF6 loss Pick up CB Live time
Trip log Status log Alarm log
Local Remode SLD
Sequences
Bay Interlocking
DCF 77
GPS IRIG B IEC 103
IEC 103 IEC 61850 GOOSE
Safe CT Interlock Passwort
BI BO Interfase I-Simulation
Protection
Control
Feeder Monitoring
Automation-Logic
Data Acquisition
Communication
Security
Test
Measurement
Time Synchronization
Fault Recording
Metering
Self Monitoring
- 3. Copyright
©
Siemens
AG
2012.
All
rights
reserved.
Siemens Power Academy TD
02 Basic function of SIPROTEC 5
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D_03_Page 3
SIPROTEC 5 Protection Application
SIPROTEC 5 includes all protection functions for transmission and subtransmission networks
SIPROTEC 5 is applicable for different substation designs
Single, double and triple busbar designs
1,5 CB schemes, ….
Application templates are available for different schemes
Pre configuration reduces the engineering efforts
User defined standards leads simplification and repeatability
Copying of functions and setting between the devices
The library concept increases the flexibility
Required functions can easily be loaded into the device
A wide range of proven protection functions are available
Possible extensions are made simple (add stages, zones,..)
A clear functional structure (function groups) clusters the functions, allows flexible
applications and guarantees correct operation
SIPROTEC 5
Protection
Control
Feeder Monitoring
Automation-Logic
Data Acquisition
Communication
Security
Test
Measurement
Time Synchronization
Fault Recording
Metering
Self Monitoring
- 4. Copyright
©
Siemens
AG
2012.
All
rights
reserved.
Siemens Power Academy TD
02 Basic function of SIPROTEC 5
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D_03_Page 4
SIPROTEC 5 Control and Automation
SIPROTEC 5
Protection
Control
Feeder Monitoring
Automation-Logic
Data Acquisition
Communication
Security
Test
Measurement
Time Synchronization
Fault Recording
Metering
Self Monitoring
SIPROTEC 5 includes all functions for Control and Automation of transmission
and subtransmission networks
CFC (continuous function chart) includes all elements for interlocking
Local control on the device
Remote control through DIGSI
Remote control from the SSA through serial interface
Application templates are available with predefined interlocking
Pre configuration reduces the engineering efforts
User defined standardization
Complete Station interlocking through IEC61850 and GOOSE
Automation solutions
Tap changer control
Intelligent load shedding (active power + frequency)
Network changeover, stability supervision
Management of distributed generation in Smart Grid plants
- 5. Copyright
©
Siemens
AG
2012.
All
rights
reserved.
Siemens Power Academy TD
02 Basic function of SIPROTEC 5
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D_03_Page 5
SIPROTEC 5 Monitoring
SIPROTEC 5
Protection
Control
Feeder Monitoring
Automation-Logic
Data Acquisition
Communication
Security
Test
Measurement
Time Synchronization
Fault Recording
Metering
Self Monitoring
SIPROTEC 5 includes all functions for effective monitoring of transmission
and subtransmission network
Self supervision
All internal hardware components and external interfaces, runtime of software
Clear text indication (cause of failure and countermeasure)
Monitoring of primary equipment
Operational log records process data with a time stamp (up to 2000 events)
Monitoring of the system through measurement supervision (voltage and frequency, power
and load) and through measuring transducer (analogue 4 to 20 mA ) inputs
(SF6 loss, gas pressure, temperature,…)
Powerful fault analysis
Fault recording with a high sampling rate and a long period (8 kHz & 20s or 1 kHz & 160 s)
Trip log with 1 ms resolution and up to 1000 events
- 6. Copyright
©
Siemens
AG
2012.
All
rights
reserved.
Siemens Power Academy TD
02 Basic function of SIPROTEC 5
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D_03_Page 6
SIPROTEC 5 Communication
SIPROTEC 5
Protection
Control
Feeder Monitoring
Automation-Logic
Data Acquisition
Communication
Security
Test
Measurement
Time Synchronization
Fault Recording
Metering
Self Monitoring
SICAM PAS
Netzleitstelle
SICAM PAS
Redundant interfacing to control center,
e.g. with DNP3, (black)
• Connection to both substation systems
• IEC 61850 (blue)
IEC 60870-5-103 (rot)
Separate connection to field level for
GOOSE communication IEC 61850 (grün)
Separate connection to DIGSI 5 – PC with
Ethernet IEC 61850
SIPROTEC 5 SIPROTEC 5
DIGSI 5
- 7. Copyright
©
Siemens
AG
2012.
All
rights
reserved.
Siemens Power Academy TD
02 Basic function of SIPROTEC 5
SIPROTEC 5/ DIGSI 5 Basic Course
Version: D_03_Page 7
SIPROTEC 5 Communication
SIPROTEC 5
Protection
Control
Feeder Monitoring
Automation-Logic
Data Acquisition
Communication
Security
Test
Measurement
Time Synchronization
Fault Recording
Metering
Self Monitoring
SIPROTEC 5 includes powerful communication functionality
Flexible communication modules standard hardware components (physical hardware is independent
of software)
Support of standard communication protocols
IEC 61850; IEC 60870-5-103
DNPi 3.0,….
Flexible communication solutions are possible
Double 103 protocol
Redundant topologies with SSA
Powerful protection data interface (for differential protection, data exchange in substation, DIGSI 5
communication)
Communication is the key feature of all applications
Smart grid means flexibility in communication
SIPROTEC 5 supports Cyber Security requirements
Present standards are fulfilled (NERC CIP, BDEW,…)
DIGSI 5 communication with encryption and strong password access