Design Fuzzy-PI Based Controller
Thermal - Thermal Area Interconnected Power System
Ajay Kumar Maurya
1
Ph.D. Scholar, Department of Electrical Engineering,
1
Lecturer, Department of Electrical & Electronics Technology,
2
Professor, Department of Electrical Engineering, IFTM University, Moradabad, UP, India
3
Associate Professor, Department of EEE, SRMS College of Engineering and Technology, Bareilly, UP, India
ABSTRACT
This paper presents how to design proportional
integral controller and Fuzzy-PI based controller for
efficiently load frequency control. Loads on the
electrical system always vary in relation to that time,
which results in diversity of frequency, causing
frequency control problems to be loaded. The
frequency difference is highly undesirable and the
maximum allowable difference in frequency is ± 0.5
Hz. This paper load frequency control is done by PI
controller, which is a conventional controller. This
type of controller is slow and the controller does not
allow the designer to keep in mind the potential
change in operating conditions and non
the generator unit. To overcome these flaws, new
intelligent controllers like Fuzzy-PI Controller are
presented to extinguish tie-line power due to deviation
in frequency and various load disturbances.
The effectiveness of the proposed controller has been
confirmed using the MATLAB / SIMULINK
software. The results show that the PI-fuzzy controller
provides fast response, little undershoots and
negligible overshoot with small state transfer time to
reach the final stable position.
KEY WORDS: PI controller, Fuzzy controller, two
area power system, load frequency control
1. INTRODUCTION
For large power systems consisting of interconnected
control areas, load frequencies, it is important to keep
the frequency and the inter-area energy close to the
planned values. The mechanical input power is used
to control the frequency of the generators
International Journal of Trend in Scientific Research and Development (IJTSRD)
International Open Access Journal | www.ijtsrd.com
ISSN No: 2456 - 6470 | Volume - 3 | Issue – 1 | Nov
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
PI Based Controller for Load Frequency Control
Thermal Area Interconnected Power System
Ajay Kumar Maurya1
, Dr. G. K. Banerjee2
, Dr. Piush Kumar
Ph.D. Scholar, Department of Electrical Engineering, IFTM University, Moradabad, U
ical & Electronics Technology, Federal TVET Institute, Addis Ababa , Ethiopia
Professor, Department of Electrical Engineering, IFTM University, Moradabad, UP, India
Department of EEE, SRMS College of Engineering and Technology, Bareilly, UP, India
This paper presents how to design proportional
PI based controller for
efficiently load frequency control. Loads on the
electrical system always vary in relation to that time,
which results in diversity of frequency, causing
frequency control problems to be loaded. The
frequency difference is highly undesirable and the
m allowable difference in frequency is ± 0.5
This paper load frequency control is done by PI
controller, which is a conventional controller. This
type of controller is slow and the controller does not
allow the designer to keep in mind the potential
ange in operating conditions and non-linearity in
the generator unit. To overcome these flaws, new
PI Controller are
line power due to deviation
in frequency and various load disturbances.
effectiveness of the proposed controller has been
confirmed using the MATLAB / SIMULINK
fuzzy controller
provides fast response, little undershoots and
negligible overshoot with small state transfer time to
PI controller, Fuzzy controller, two
area power system, load frequency control
For large power systems consisting of interconnected
control areas, load frequencies, it is important to keep
area energy close to the
planned values. The mechanical input power is used
to control the frequency of the generators, and the
change in frequency and line voltage is measured,
which is a measure of the change in rotor angle. A
well designed power system should be able to
guarantee the acceptable quality of the power supply
by keeping the frequency and voltage levels
tolerable limits.
Changes in the network load mainly affect the system
frequency, while the reactive power is less sensitive to
frequency changes and depends mainly on voltage
fluctuations. Thus, the control of the active and
reactive power in the power grid is treated separately.
The load frequency control is mainly concerned with
the control of the system frequency and the active
power, while the automatic voltage regulator loop
regulates the changes of the reactive power and
voltage magnitude. Load frequency control is the
basis of many advanced concepts of large scale
control of the power system.
The load frequency control (LFC) controls the actual
power and frequency. MATLAB provides an
excellent environment
programming. It has great flexibility and utility for
engineering applications. SIMULINK is a visual
modeling tool, which works on MATLAB shell. The
goal of the load frequency control (LFC) is to
maintain zero steady state errors in a multi area
interconnected power system.
and frequency from the nominal values, when there is
any mismatch in real power and reactive power
generations and demands. It can be provided by
sensitivity analysis that mismatches in the real power
balance affects primarily the sys
Research and Development (IJTSRD)
www.ijtsrd.com
1 | Nov – Dec 2018
Dec 2018 Page: 928
or Load Frequency Control of
Thermal Area Interconnected Power System
Dr. Piush Kumar3
versity, Moradabad, Uttar Pradesh, India
Federal TVET Institute, Addis Ababa , Ethiopia
Professor, Department of Electrical Engineering, IFTM University, Moradabad, UP, India
Department of EEE, SRMS College of Engineering and Technology, Bareilly, UP, India
change in frequency and line voltage is measured,
which is a measure of the change in rotor angle. A
well designed power system should be able to
guarantee the acceptable quality of the power supply
by keeping the frequency and voltage levels within
Changes in the network load mainly affect the system
frequency, while the reactive power is less sensitive to
frequency changes and depends mainly on voltage
fluctuations. Thus, the control of the active and
power grid is treated separately.
The load frequency control is mainly concerned with
the control of the system frequency and the active
power, while the automatic voltage regulator loop
regulates the changes of the reactive power and
ad frequency control is the
basis of many advanced concepts of large scale
The load frequency control (LFC) controls the actual
MATLAB provides an
for modeling and
great flexibility and utility for
engineering applications. SIMULINK is a visual
modeling tool, which works on MATLAB shell. The
goal of the load frequency control (LFC) is to
maintain zero steady state errors in a multi area
interconnected power system. The change in voltage
and frequency from the nominal values, when there is
any mismatch in real power and reactive power
generations and demands. It can be provided by
sensitivity analysis that mismatches in the real power
balance affects primarily the system frequency, but
International Journal of Trend in Scientific Research and
@ IJTSRD | Available Online @ www.ijtsrd.com
leaves the bus voltage essentially unaffected.
control system is essential to cancel the effects of the
sudden load changes and to keep the frequency at the
nominal value [3–5]
1.1 TWO-area power system model
A two-area interconnected thermal power system as
shown in Fig. 1 is considered. The system is widely
used in literature for the design and analysis of AGC
[7]. In Fig. 1, B1 and B2 are the frequency bias
parameters; ACE1 and ACE2 are area control errors;
X1 and X2 are the control outputs from the controller;
R1 and R2 are the governor speed regulation
parameters in p.u. Hz; TH1 and TH2
governor time constants in seconds; Δ
are the governor output command (p.u.);
are the turbine time constant in seconds;
ΔPT 2 are the change in turbine output powers;
and ΔPE2 are the load demand changes;
are the power system gains; TP1 and TP2
system time constant in seconds;
incremental change in tie line power (p.u.);
Δf2 are the system frequency deviations in Hz. The
relevant parameters are given in Appendix A.
Figure 1: Two area Thermal–Thermal plant with
conventional PI controller
1.2 Modeling of the tie-line
The well known power transfer equation is
1 2o
1 2 1 2
V V
P s in ( )
x
   
Where 1 and 2 are the angles of end voltages V
and V2 respectively. The sequence of subscript
indicates that the tie line defines positive in power
direction 1 to 2.
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
leaves the bus voltage essentially unaffected. So, a
control system is essential to cancel the effects of the
sudden load changes and to keep the frequency at the
area interconnected thermal power system as
shown in Fig. 1 is considered. The system is widely
used in literature for the design and analysis of AGC
are the frequency bias
are area control errors;
are the control outputs from the controller;
are the governor speed regulation
are the speed
ΔPH1 and ΔPH2
are the governor output command (p.u.); TT1 and TT 2
are the turbine time constant in seconds; ΔPT1 and
are the change in turbine output powers; ΔPE1
are the load demand changes; KP1 and KP2
2 are the power
system time constant in seconds; ΔPTie is the
incremental change in tie line power (p.u.); Δf1 and
are the system frequency deviations in Hz. The
relevant parameters are given in Appendix A.
Thermal plant with
conventional PI controller
The well known power transfer equation is
(1)
are the angles of end voltages V1
The sequence of subscript
positive in power
For tiny deviation in the angles and the tie line
changes with the power amount
1 2
12 1 2 1 2
V V
P cos( )( )
x
       
In accordance with the concept of "electrical stiffness"
of synchronous machines, we define
coefficient" of a line
𝑇 =
| | | |
cos (
Thus the equation (2) can be written as
o
1 2 1 2P T ( )      
Figure 2: Conventional Two Area System: Basic
Block Diagram
The frequency deviation is related to
angle by the formula
1 d ( )
f
2 dt
   
 

or d ( )
dt
 
 
or 2 2    
Thus the equation (3.4) can be written as
 t t
o
12 1 20 0
P 2 T f dt f dt      
Taking Laplace transformation of equation

o
12 1 2
2 T
P (s) f (s) f (s)
s

    
The above equation can be represented as in figure (3)
Figure 3: Block Diagram Representation of a Tie
Line
Similarly the incremented tie line power expected
from area 2 is given by

o
12 2 1
2 T
P (s) f (s) f (s)
s

    
Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 929
For tiny deviation in the angles and the tie line
changes with the power amount
12 1 2 1 2P cos( )( )        (2)
In accordance with the concept of "electrical stiffness"
of synchronous machines, we define "synchronizing
(𝛿 − 𝛿 ) (3)
Thus the equation (2) can be written as
1 2 1 2P T ( )       (4)
Figure 2: Conventional Two Area System: Basic
Block Diagram
The frequency deviation is related to the reference
1 d ( )
2 dt
   1 d( )
2 dt



d ( )
2 f
 
 
0
2 2
t
f d t    
Thus the equation (3.4) can be written as
t t
12 1 20 0
P 2 T f dt f dt      
Taking Laplace transformation of equation
12 1 2P (s) f (s) f (s)     (5)
The above equation can be represented as in figure (3)
Figure 3: Block Diagram Representation of a Tie –
Similarly the incremented tie line power expected
12 2 1P (s) f (s) f (s)    
International Journal of Trend in Scientific Research and
@ IJTSRD | Available Online @ www.ijtsrd.com
The power balance equation for single area can be
given by
So for the double area, the equation should be
modified as follows
1 1
1 1 1 1 1 2
2 ( )
T E
o
H d f
P P B f P
f d t

       
  1
T1 E1 12 1 1 1
o
2H
P (s) P (s) P (s) s f (s) B f (s)
f
        
If 𝑇 = 𝐾 =
Equation (6) can be written as
1 P1 T 1 E 1 1 2f (s) G (s) P (s) P (s) P (s)      
P 1
P 1
P 1
K
G (s )
1 sT


Thus the complete block diagram representation of
two area load frequency control is given in figure (1).
2. Ziegler -Nichols Rule Based Tuning
For comparison the PID controller was tuned using
conventional Ziegler –Nichols tuning rule based on
the critical gain Ku and critical period P
Ku and Pu were calculated from the sustained
oscillations of the output by employing only
proportional controller. The sustained oscillation
response with proportional controller under critical
gain is shown in Figure (4). As per the Ziegler
Nichols rule the settings for PID controller parameter
are given in the following table [1]. Controller
parameters calculated for conventional controller are
given in Table [2].
Table 1: Ziegler-Nichols tuning rules
Type of control Gc(s) K
Proportional (P) Kc
0.5
K
Proportional–
Integral(PI) c
i
1
K 1
sT
 
 
 
0.45K
Proportional-
Integral-
Derivative (PID)
c d
i
1
K 1 sT
sT
 
  
 
0.6K
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
The power balance equation for single area can be
So for the double area, the equation should be
1 1 1 1 1 2P P B f P       
T1 E1 12 1 1 1P (s) P (s) P (s) s f (s) B f (s)         (6)
1 P1 T 1 E1 12f (s) G (s) P (s) P (s) P (s)      
Thus the complete block diagram representation of
two area load frequency control is given in figure (1).
Nichols Rule Based Tuning
For comparison the PID controller was tuned using
Nichols tuning rule based on
and critical period Pu. Values of
were calculated from the sustained
oscillations of the output by employing only
nal controller. The sustained oscillation
response with proportional controller under critical
gain is shown in Figure (4). As per the Ziegler-
Nichols rule the settings for PID controller parameter
are given in the following table [1]. Controller
s calculated for conventional controller are
Nichols tuning rules
Kc Ti Td
0.5
Ku
- -
u0.45K uP
1.2
-
u0.6K uP
2
uP
8
Figure 4: System response with proportional
controller under critical gain
Table 2: Controller Parameters for conventional
controller
Kc T
0.45.Ku= 0.66 Pu /1.2 =
3. Different types of controllers
3.1 PI - Controller
The 'PI' controller will eliminate forced oscillations
and steady state error, which will
operation of the on-off controller and the 'P'
controller, respectively. However, starting an integral
mode has a negative impact on the response speed and
overall stability of the system.
Therefore, the PI controller does not increase the
reaction rate. It can be expected because the PI
controller has no means of predicting what will
happen to the bug in the near future. This problem can
be solved by introducing a derivative mode that is
able to predict what will happen to the error in the
near future and thus reduce it [13]
3.2 Fuzzy Controller
The general architecture of a fuzzy controller is
depicted in Figure (5) [14]. The origin of a fuzzy
controller is an fuzzy inference engine (FIS), which
includes fuzzification,, knowledge base evalu
and defuzzification in the data flow.
systems are the error and the change in the error of the
feedback loop, while the output is the control action.
There are 7 trapezoidal membership functions in each
input i.e.NB (Negative Big), NM (Negative Medium),
NS (Negative Small), Z (Zero), PS (Positive Small),
PM (Positive Medium), PB (Positive Big). The
mamdani rule base adopted here and the
0 0.5 1 1.5 2
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
Time (sec)
FrequencyDeviation(Hz.)
Pu = 1.2
Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 930
Figure 4: System response with proportional
controller under critical gain
Table 2: Controller Parameters for conventional
controller
i Ki
/1.2 = 1
Kc/Ti =
0.66
Different types of controllers
The 'PI' controller will eliminate forced oscillations
and steady state error, which will result in the
off controller and the 'P'
controller, respectively. However, starting an integral
mode has a negative impact on the response speed and
overall stability of the system.
Therefore, the PI controller does not increase the
eaction rate. It can be expected because the PI
controller has no means of predicting what will
happen to the bug in the near future. This problem can
be solved by introducing a derivative mode that is
able to predict what will happen to the error in the
ear future and thus reduce it [13]
The general architecture of a fuzzy controller is
depicted in Figure (5) [14]. The origin of a fuzzy
controller is an fuzzy inference engine (FIS), which
includes fuzzification,, knowledge base evaluation
in the data flow. The inputs to the
systems are the error and the change in the error of the
feedback loop, while the output is the control action.
There are 7 trapezoidal membership functions in each
NM (Negative Medium),
NS (Negative Small), Z (Zero), PS (Positive Small),
PM (Positive Medium), PB (Positive Big). The
mamdani rule base adopted here and the
2.5 3 3.5 4
Time (sec)
Ku = 1.467
International Journal of Trend in Scientific Research and
@ IJTSRD | Available Online @ www.ijtsrd.com
defuzzification process is centroid method. The fuzzy
rules are shown in Table [3].
Figure 5: Structure of fuzzy logic controller
Table 3: Fuzzy Rule Base
E
∆E
NB NM NS ZE PS
NB PB PB PB PB PM
NM PB PM PM PM PS
NS PM PM PS PS PS
ZE NS NS NS ZE PS
PS ZE NS NS NS NS
PM NS NS NM NM NM
PB NS NM NB NB NB
A fuzzy system is described by a set of IF
rules and uses diverse membership functions. To
solve the load-frequency control problem in fuzzy
controller, controller inputs are Area Control Error
and derivative of Area Control Error and its
considered as the control signal. The member ship
function uses in fuzzy logic controller for Error,
change in Error and output is shown in figure (5).
Figure 5: Membership functions of inputs (E,
and output
3.3 PI- Fuzzy Logic Controller
A Fuzzy-PI controller designed based on a linear
model of power system under the loading condition
FLC designed to eliminate the need for continuous
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
defuzzification process is centroid method. The fuzzy
Structure of fuzzy logic controller
Table 3: Fuzzy Rule Base
PM PB
PM PS
PS PS
PS ZE
PS PS
NM NM
NB NB
NB NB
A fuzzy system is described by a set of IF-THEN
rules and uses diverse membership functions. To
frequency control problem in fuzzy
controller, controller inputs are Area Control Error
and derivative of Area Control Error and its output are
considered as the control signal. The member ship
function uses in fuzzy logic controller for Error,
change in Error and output is shown in figure (5).
Membership functions of inputs (E, ΔE)
PI controller designed based on a linear
model of power system under the loading condition
FLC designed to eliminate the need for continuous
operator attention and used automatically to adjust
some variables the process variable is kept
reference value. A FLC consists of three sections
Namely, fuzzifier, rule base, and defuzzifier.
Fuzzy-PI controller structure is shown in Figure (6).
Figure 6: PI-Fuzzy Logic controller in Simulink
4. Results and Simulation
Performed simulations using PI and Fuzzy
controllers applied to a two area interconnected power
systems. The developed system is simulated with 10
% step load disturbance in area 1. Due to this the
change in dynamic responses of the system has been
observed, as shown in below Figures. It is examine
from the output responses that the proposed Fuzzy
Controller is stable and less oscillations and the
settling time also improved considerably. Also this
output justified that this interconnection is valid for
Thermal-Thermal systems. For conventional PI
controller and Fuzzy-PI controller, the main objective
is to improve the control performance
4.1 Uncontrolled case
The frequency changes in area
10% step load perturbation is shown in figure (7).
There is a steady state error in the response.
Figure 7: Two area Thermal
(Uncontrolled) with a disturbance of
area-1: Frequency deviation of area
4.2 Controlled Case with Proportional plus
Integral Controller
The frequency changes in area
10% step load perturbation is shown in figure (8) and
(9). (10% step load perturbation is given in area
Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 931
attention and used automatically to adjust
process variable is kept at the
reference value. A FLC consists of three sections
Namely, fuzzifier, rule base, and defuzzifier. The
controller structure is shown in Figure (6).
zzy Logic controller in Simulink
simulations using PI and Fuzzy-PI
controllers applied to a two area interconnected power
systems. The developed system is simulated with 10
% step load disturbance in area 1. Due to this the
change in dynamic responses of the system has been
hown in below Figures. It is examine
from the output responses that the proposed Fuzzy-PI
Controller is stable and less oscillations and the
settling time also improved considerably. Also this
output justified that this interconnection is valid for
Thermal systems. For conventional PI
PI controller, the main objective
is to improve the control performance
The frequency changes in area-1 and area-2 for the
10% step load perturbation is shown in figure (7).
There is a steady state error in the response.
Two area Thermal-Thermal plant
disturbance of 10 % in
1: Frequency deviation of area -1 and area – 2
Controlled Case with Proportional plus
The frequency changes in area-1 and area-2 for the
10% step load perturbation is shown in figure (8) and
(9). (10% step load perturbation is given in area -1).
International Journal of Trend in Scientific Research and
@ IJTSRD | Available Online @ www.ijtsrd.com
The steady state error is zero in this case. The
frequency deviation of area-1 is much more
Figure 8: Two area Thermal-Thermal plant
(Controlled with PI) with Disturbance of 10 % in
area-1: Frequency deviation of area
Figure 9: Two area Thermal-Thermal plant
(Controlled with PI) with a Disturbance of 10 % in
area-1: Frequency deviation of ar
4.3 Controlled Case with Fuzzy-PI Controller
The frequency changes in area-1 and area
10% step load perturbation is shown in figure (10) and
(11). (10% step load perturbation is given in
The steady state error is zero in this case. The
frequency deviation of area-1 is much more
0 5 10 15 20 25 30 35
Time (Second)
-0.07
-0.06
-0.05
-0.04
-0.03
-0.02
-0.01
0
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
The steady state error is zero in this case. The
1 is much more
Thermal plant
Disturbance of 10 % in
1: Frequency deviation of area -1
Thermal plant
Disturbance of 10 % in
1: Frequency deviation of area -2
PI Controller
1 and area-2 for the
10% step load perturbation is shown in figure (10) and
(11). (10% step load perturbation is given in area -1).
The steady state error is zero in this case. The
1 is much more
Figure 10: Two area Thermal
(Controlled with Fuzzy-PI) With disturbance of 10
% in area-1: Frequency deviation of area
Figure 11: Two area Thermal
(Controlled with Fuzzy-PI) With Disturbance of 10
% in area-1: Frequency deviation of area
4.4 Comparison between PI and Fuzzy
Controller
Figure 12: Comparison result between Fuzzy
and PI controller with Disturban
area-1: Frequency deviation of area
40 45 50
Area 2
PI Controller
Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 932
Figure 10: Two area Thermal-Thermal plant
With disturbance of 10
1: Frequency deviation of area -1
wo area Thermal-Thermal plant
With Disturbance of 10
1: Frequency deviation of area -2
Comparison between PI and Fuzzy-PI
Figure 12: Comparison result between Fuzzy-PI
Disturbance of 10 % in
1: Frequency deviation of area -1
International Journal of Trend in Scientific Research and
@ IJTSRD | Available Online @ www.ijtsrd.com
Figure 13: Comparison result between Fuzzy
and PI controller in with Disturbance of 10 % in
area-1: Frequency deviation of area
The comparison of peak undershoots; Peak Overshoot
and Settling Time via PI controller and Fuzzy
controller are given in Table [3].
Table 3: Thermal-Thermal plant: PI Controller Vs
Fuzzy-PI Controller
Peak
Undershoot
Peak
Overshoot
Two
Area
Area
-1
Area
-2
Area
-1
Area
-2
PI
Control
ler
-
0.15
57
-
0.06
29
0.02
97
0.00
03
PI-
Fuzzy
Control
ler
-
0.13
20
-
0.05
62
0.00
27
0.00
00
5. Conclusion
In this paper a new technique Fuzzy-PI controller is
designed for automatic load frequency control of
interconnected Thermal - Thermal systems. The
controller performances Fuzzy-PI approach is in work
for a Load Frequency Control for Generation of
Interconnected Power System. The proposed
controller can handle the non-linearity and at the same
time faster than other conventional controllers. Also
the simulation results are compared with a
conventional other controller. From the Result shown
in figure (8) to figure (13). The results obtained for
double area Thermal-Thermal plant shows the
superiority such controllers over the conventional PI
controllers. In Fuzzy-PI Controller the settling time
has been reduced in area1 and area 2 are 5.63 sec and
6.30 sec respectively. It is explicit that the
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
Figure 13: Comparison result between Fuzzy-PI
Disturbance of 10 % in
1: Frequency deviation of area -2
The comparison of peak undershoots; Peak Overshoot
and Settling Time via PI controller and Fuzzy-PI
Thermal plant: PI Controller Vs
Settling
Time(Sec)
Are
a-1
Are
a-2
12.8
8
14.8
5
7.25 8.55
PI controller is
designed for automatic load frequency control of
Thermal systems. The
PI approach is in work
for a Load Frequency Control for Generation of
nected Power System. The proposed
linearity and at the same
time faster than other conventional controllers. Also
the simulation results are compared with a
conventional other controller. From the Result shown
figure (13). The results obtained for
Thermal plant shows the
superiority such controllers over the conventional PI
PI Controller the settling time
has been reduced in area1 and area 2 are 5.63 sec and
spectively. It is explicit that the
performance in term of settling time and overshoot of
fuzzy-PI controller is better. There is no steady state
error. So fuzzy-PI controller shows its effectiveness
over the conventional PI controller.
The result shows that the proposed intelligent
controller is having improved dynamic response and
at the same time faster than conventional
APPENDIX
Parameter
KP1 = KP2 120 Hz. / p.u. MW
KH1 =KH2 1 Hz. / p.u. MW
KT1 =KT2 1 Hz. / p.u. MW
TP1 = TP2
TH1 =TH2 0.08 Sec.
TT1 = TT2
B1 = B2 0.425 p.u. MW / Hz.
R1 = R2 2.4 Hz. / p.u. MW
To 0.0867 p.u. MW/Hz
References
1. O.I. Elgerd, Electric Energy Systems Theory
Introduction, second ed., Tata McGraw Hill, New
Delhi, 2000.
2. P. Kundur, Power System Stability and Control,
eighth reprint, Tata McGraw Hill, New Delhi,
2009.
3. H. Bevrani, Robust Power System Frequency
Control, Springer, New York, 2009.
4. I.P. Kumar, D.P. Kothari, Recent philosophies of
automatic generation control strate
systems, IEEE Trans. Power Syst. 20 (2005) 346
357.
5. H. Shayaghi, H.A. Shayanfar, A. Jalili, Load
frequency control strategies: a state of the art
survey for the researcher, Energy Convers.
Manag. 50 (2009) 344–354.
6. K.P.S. Parmar, S. Majhi, D.
frequency control of a realistic power system with
multi-source power generation, Int. J. Electr.
Power Energy Syst. 42 (2012) 426
7. U.K. Rout, R.K. Sahu, S. Panda, Design and
analysis of differential evolution algorithm based
automatic generation control for interconnected
power system, Ain Shams Eng. J. 4 (3) (2013)
409–421.
8. M. Masiala, M. Ghribi and A. Kaddouri, Senior
Member, “An Adaptive Fuzzy Controller Gain
Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 933
performance in term of settling time and overshoot of
PI controller is better. There is no steady state
PI controller shows its effectiveness
over the conventional PI controller.
hat the proposed intelligent
controller is having improved dynamic response and
at the same time faster than conventional controller
Value
120 Hz. / p.u. MW
1 Hz. / p.u. MW
1 Hz. / p.u. MW
20 Sec.
0.08 Sec.
0.3 Sec.
0.425 p.u. MW / Hz.
2.4 Hz. / p.u. MW
0.0867 p.u. MW/Hz
O.I. Elgerd, Electric Energy Systems Theory – An
Introduction, second ed., Tata McGraw Hill, New
Kundur, Power System Stability and Control,
eighth reprint, Tata McGraw Hill, New Delhi,
H. Bevrani, Robust Power System Frequency
Control, Springer, New York, 2009.
I.P. Kumar, D.P. Kothari, Recent philosophies of
automatic generation control strategies in power
systems, IEEE Trans. Power Syst. 20 (2005) 346–
H. Shayaghi, H.A. Shayanfar, A. Jalili, Load
frequency control strategies: a state of the art
survey for the researcher, Energy Convers.
354.
K.P.S. Parmar, S. Majhi, D.P. Kothari, Load
frequency control of a realistic power system with
source power generation, Int. J. Electr.
Power Energy Syst. 42 (2012) 426–433.
U.K. Rout, R.K. Sahu, S. Panda, Design and
analysis of differential evolution algorithm based
generation control for interconnected
power system, Ain Shams Eng. J. 4 (3) (2013)
M. Masiala, M. Ghribi and A. Kaddouri, Senior
“An Adaptive Fuzzy Controller Gain
International Journal of Trend in Scientific Research and
@ IJTSRD | Available Online @ www.ijtsrd.com
Scheduling For Power System Load
Control” Dept. of Electrical
University de Moncton, New Brunswick, Canada
1515 -1520, IEEE International Conference on
Industrial Technology (ICIT), 2004
9. N. Jaleeli, D. N. Ewart, and L. H. Fink.
“Understanding Automtic Generation Control.”
IEEE Transactions on Power Systems,
No.3. August 1992, pp.1106-1122
10. L.C. Saikia, J. Nanda, S. Mishra, Performance
comparison of several classical controllers in
AGC for multi-area interconnected thermal
system, Int. J. Electr. Power Energy Syst. 33
(2011) 394–401.
11. S.A. Taher, M.H. Fini, S.F. Aliabadi, Fractional
order PID controller design for LFC in electric
power systems using imperialist competitive
algorithm, Ain Shams Eng. J. 5 (2014) 121
12. Ramanand Kashyap, Prof. S.S. Sankeswari, Prof.
B. A. Patil ,Load Frequency Control Using Fuzzy
PI Controller Generation of Interconnected Hydro
Power System ,International Journal of Emerging
Technology and Advanced Engineering, Volume
3, Issue 9, September 2013
13. Vasadi Srinivasa Rao, P. D. Srinivas, CH. Ravi
Kumar, Load Frequency Control (LFC) of Three
Area Interconnected Power System using
Adaptive Neuro Fuzzy Interface System,
International Journal of Scientific Engineering and
Technology Research ISSN 2319
Vol.04,Issue.43, October-2015, Pages:9482
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
Scheduling For Power System Load -- Frequency
Engineering,
University de Moncton, New Brunswick, Canada
IEEE International Conference on
and L. H. Fink.
“Understanding Automtic Generation Control.”
Systems, Vol. 7.
L.C. Saikia, J. Nanda, S. Mishra, Performance
comparison of several classical controllers in
area interconnected thermal
system, Int. J. Electr. Power Energy Syst. 33
, M.H. Fini, S.F. Aliabadi, Fractional
order PID controller design for LFC in electric
power systems using imperialist competitive
algorithm, Ain Shams Eng. J. 5 (2014) 121–135.
Ramanand Kashyap, Prof. S.S. Sankeswari, Prof.
trol Using Fuzzy-
PI Controller Generation of Interconnected Hydro
International Journal of Emerging
Technology and Advanced Engineering, Volume
Vasadi Srinivasa Rao, P. D. Srinivas, CH. Ravi
ntrol (LFC) of Three
Area Interconnected Power System using
Adaptive Neuro Fuzzy Interface System,
International Journal of Scientific Engineering and
Technology Research ISSN 2319-8885
2015, Pages:9482-9488
14. Sateesh Kumar Vavilala,
Machavarapu Suman , Load Frequency Control of
Two Area Interconnected Power System Using
Conventional and Intelligent Controllers,
Journal of Engineering Research and
Applications, ISSN : 2248
Version 3), January 2014, pp.156
15. J. Nanda and B. L. Kaul, "Automatic generation
control of an interconnected power system",
IEE, Vol 125, No. 5, 1978, pp. 385
16. Nilay.N.Shah, Aditya. D. Chafekar and Dwij.
N.Mehta, “Automatic Load Frequency Control of
Two Area Power System With Conventional and
Fuzzy Logic Control” International Journal of
Research in Engineering and Technology, Volume
1, Issue 3 ,Nov. 2012, pp. 343
17. Saravuth Pothiya, Issarachai Ngamroo, Suwan
Runggeratigul, and Prinya Tantaswadi, “Design of
Optimal Fuzzy Logic based PI Controller using
Multiple Tabu Search Algorithm for Load
Frequency Control” International Journal of
Control, Automation, and Systems, vol. 4, no. 2,
pp. 155-164, April 2006
18. Xiangping Meng, Qingxian Gong, Lei Feng, Wen
Zheng, Weijun Zhang, “PI Fuzzy Sliding Mode
Load Frequency. Control of Multiarea
Interconnected Power Systems” IEEE
International Symposium on
Houston Texas, pp. 1023-1027,
Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 934
Sateesh Kumar Vavilala, R S Srinivas,
Machavarapu Suman , Load Frequency Control of
Two Area Interconnected Power System Using
Conventional and Intelligent Controllers, Int.
Journal of Engineering Research and
Applications, ISSN : 2248-9622, Vol. 4, Issue 1(
2014, pp.156-160
L. Kaul, "Automatic generation
control of an interconnected power system", Proc.
Vol 125, No. 5, 1978, pp. 385-390
Nilay.N.Shah, Aditya. D. Chafekar and Dwij.
N.Mehta, “Automatic Load Frequency Control of
r System With Conventional and
Fuzzy Logic Control” International Journal of
Research in Engineering and Technology, Volume
1, Issue 3 ,Nov. 2012, pp. 343-347.
Saravuth Pothiya, Issarachai Ngamroo, Suwan
Runggeratigul, and Prinya Tantaswadi, “Design of
imal Fuzzy Logic based PI Controller using
Multiple Tabu Search Algorithm for Load
International Journal of
Control, Automation, and Systems, vol. 4, no. 2,
Xiangping Meng, Qingxian Gong, Lei Feng, Wen
un Zhang, “PI Fuzzy Sliding Mode
Load Frequency. Control of Multiarea
Interconnected Power Systems” IEEE
Symposium on Intelligent Control
1027, October 2003

More Related Content

What's hot

A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
ijtsrd
 
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
IJMTST Journal
 

What's hot (20)

Fi34989995
Fi34989995Fi34989995
Fi34989995
 
Class 27 signal processing techniques for the future smart grid.pdf
Class 27 signal processing techniques for the future smart grid.pdfClass 27 signal processing techniques for the future smart grid.pdf
Class 27 signal processing techniques for the future smart grid.pdf
 
Hioki pq3198 pq3100_e4-11m_power_quality_analyzer
Hioki pq3198 pq3100_e4-11m_power_quality_analyzer Hioki pq3198 pq3100_e4-11m_power_quality_analyzer
Hioki pq3198 pq3100_e4-11m_power_quality_analyzer
 
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
 
Power quality improvement techniques
Power quality improvement techniquesPower quality improvement techniques
Power quality improvement techniques
 
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
 
Maximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systemsMaximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systems
 
Automatic load frequency control of two area power system with conventional a...
Automatic load frequency control of two area power system with conventional a...Automatic load frequency control of two area power system with conventional a...
Automatic load frequency control of two area power system with conventional a...
 
IRJET- Load Frequency Control of an Interconnected Power System using Grey Wo...
IRJET- Load Frequency Control of an Interconnected Power System using Grey Wo...IRJET- Load Frequency Control of an Interconnected Power System using Grey Wo...
IRJET- Load Frequency Control of an Interconnected Power System using Grey Wo...
 
A Novel Multi Level Converter Unified Power – Quality (MC-UPQC) Conditioning ...
A Novel Multi Level Converter Unified Power – Quality (MC-UPQC) Conditioning ...A Novel Multi Level Converter Unified Power – Quality (MC-UPQC) Conditioning ...
A Novel Multi Level Converter Unified Power – Quality (MC-UPQC) Conditioning ...
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
 
Power quality monitoring (PQM)
Power quality monitoring (PQM)Power quality monitoring (PQM)
Power quality monitoring (PQM)
 
Power system stabilisation based on ga anfis in generators
Power system stabilisation based on ga anfis in generatorsPower system stabilisation based on ga anfis in generators
Power system stabilisation based on ga anfis in generators
 
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
 
Paper id 41201606
Paper id 41201606Paper id 41201606
Paper id 41201606
 
Smart grid communications and measurement technology
Smart grid communications and measurement technologySmart grid communications and measurement technology
Smart grid communications and measurement technology
 
A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...A review on SVC control for power system stability with and without auxiliary...
A review on SVC control for power system stability with and without auxiliary...
 
Adaptability of Distribution Automation System to Electric Power Quality Moni...
Adaptability of Distribution Automation System to Electric Power Quality Moni...Adaptability of Distribution Automation System to Electric Power Quality Moni...
Adaptability of Distribution Automation System to Electric Power Quality Moni...
 
Web based power quality monitoring system
Web based power quality monitoring systemWeb based power quality monitoring system
Web based power quality monitoring system
 
A Review paper on variable frequency drive
A Review paper on variable frequency driveA Review paper on variable frequency drive
A Review paper on variable frequency drive
 

Similar to Design Fuzzy-PI Based Controller for Load Frequency Control of Thermal - Thermal Area Interconnected Power System

Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
ijtsrd
 
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
IAEME Publication
 
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET Journal
 
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
ijtsrd
 
Power Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source ConvertersPower Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source Converters
IJRST Journal
 

Similar to Design Fuzzy-PI Based Controller for Load Frequency Control of Thermal - Thermal Area Interconnected Power System (20)

Differential game approach for the analysis of two area load frequency control
Differential game approach for the analysis of two area load frequency controlDifferential game approach for the analysis of two area load frequency control
Differential game approach for the analysis of two area load frequency control
 
Aa4103156160
Aa4103156160Aa4103156160
Aa4103156160
 
Bc35306309
Bc35306309Bc35306309
Bc35306309
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
Optimization Technique for Power Quality Improvement using DSTATCOM Neural Ne...
 
Improved Controller for the Dual Topology of the Unified Power Quality Condit...
Improved Controller for the Dual Topology of the Unified Power Quality Condit...Improved Controller for the Dual Topology of the Unified Power Quality Condit...
Improved Controller for the Dual Topology of the Unified Power Quality Condit...
 
Pc3426502658
Pc3426502658Pc3426502658
Pc3426502658
 
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
 
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
Comparision of pi, fuzzy & neuro fuzzy controller based multi converter unifi...
 
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
 
11.voltage dip mitigation in distribution system by using d statcom
11.voltage dip mitigation in distribution system by using d statcom11.voltage dip mitigation in distribution system by using d statcom
11.voltage dip mitigation in distribution system by using d statcom
 
Voltage dip mitigation in distribution system by using d statcom
Voltage dip mitigation in distribution system by using d statcomVoltage dip mitigation in distribution system by using d statcom
Voltage dip mitigation in distribution system by using d statcom
 
Ee33783786
Ee33783786Ee33783786
Ee33783786
 
Ee33783786
Ee33783786Ee33783786
Ee33783786
 
Presentation1
Presentation1Presentation1
Presentation1
 
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...Application of Unified Power Flow Controller in Nigeria Power System for Impr...
Application of Unified Power Flow Controller in Nigeria Power System for Impr...
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Power Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source ConvertersPower Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source Converters
 
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
Load Frequency Control of Multi Area System using Integral-Fuzzy ControllerLoad Frequency Control of Multi Area System using Integral-Fuzzy Controller
Load Frequency Control of Multi Area System using Integral-Fuzzy Controller
 

More from ijtsrd

‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation
ijtsrd
 
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and ProspectsDynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
ijtsrd
 
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
ijtsrd
 
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
ijtsrd
 
Problems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A StudyProblems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A Study
ijtsrd
 
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
ijtsrd
 
A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...
ijtsrd
 
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
ijtsrd
 
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
ijtsrd
 
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. SadikuSustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
ijtsrd
 
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
ijtsrd
 
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
ijtsrd
 
Activating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment MapActivating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment Map
ijtsrd
 
Educational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger SocietyEducational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger Society
ijtsrd
 
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
ijtsrd
 

More from ijtsrd (20)

‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation
 
Edge Computing in Space Enhancing Data Processing and Communication for Space...
Edge Computing in Space Enhancing Data Processing and Communication for Space...Edge Computing in Space Enhancing Data Processing and Communication for Space...
Edge Computing in Space Enhancing Data Processing and Communication for Space...
 
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and ProspectsDynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
 
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
 
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
 
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
 
Problems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A StudyProblems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A Study
 
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
 
The Impact of Educational Background and Professional Training on Human Right...
The Impact of Educational Background and Professional Training on Human Right...The Impact of Educational Background and Professional Training on Human Right...
The Impact of Educational Background and Professional Training on Human Right...
 
A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...
 
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
 
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
 
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. SadikuSustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
 
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
 
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
 
Activating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment MapActivating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment Map
 
Educational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger SocietyEducational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger Society
 
Integration of Indian Indigenous Knowledge System in Management Prospects and...
Integration of Indian Indigenous Knowledge System in Management Prospects and...Integration of Indian Indigenous Knowledge System in Management Prospects and...
Integration of Indian Indigenous Knowledge System in Management Prospects and...
 
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
 
Streamlining Data Collection eCRF Design and Machine Learning
Streamlining Data Collection eCRF Design and Machine LearningStreamlining Data Collection eCRF Design and Machine Learning
Streamlining Data Collection eCRF Design and Machine Learning
 

Recently uploaded

Query optimization and processing for advanced database systems
Query optimization and processing for advanced database systemsQuery optimization and processing for advanced database systems
Query optimization and processing for advanced database systems
meharikiros2
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
hublikarsn
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 

Recently uploaded (20)

Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
8086 Microprocessor Architecture: 16-bit microprocessor
8086 Microprocessor Architecture: 16-bit microprocessor8086 Microprocessor Architecture: 16-bit microprocessor
8086 Microprocessor Architecture: 16-bit microprocessor
 
Signal Processing and Linear System Analysis
Signal Processing and Linear System AnalysisSignal Processing and Linear System Analysis
Signal Processing and Linear System Analysis
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
Query optimization and processing for advanced database systems
Query optimization and processing for advanced database systemsQuery optimization and processing for advanced database systems
Query optimization and processing for advanced database systems
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
fitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .pptfitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .ppt
 
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 

Design Fuzzy-PI Based Controller for Load Frequency Control of Thermal - Thermal Area Interconnected Power System

  • 1. International Journal of Trend in International Open ISSN No: 2456 @ IJTSRD | Available Online @ www.ijtsrd.com Design Fuzzy-PI Based Controller Thermal - Thermal Area Interconnected Power System Ajay Kumar Maurya 1 Ph.D. Scholar, Department of Electrical Engineering, 1 Lecturer, Department of Electrical & Electronics Technology, 2 Professor, Department of Electrical Engineering, IFTM University, Moradabad, UP, India 3 Associate Professor, Department of EEE, SRMS College of Engineering and Technology, Bareilly, UP, India ABSTRACT This paper presents how to design proportional integral controller and Fuzzy-PI based controller for efficiently load frequency control. Loads on the electrical system always vary in relation to that time, which results in diversity of frequency, causing frequency control problems to be loaded. The frequency difference is highly undesirable and the maximum allowable difference in frequency is ± 0.5 Hz. This paper load frequency control is done by PI controller, which is a conventional controller. This type of controller is slow and the controller does not allow the designer to keep in mind the potential change in operating conditions and non the generator unit. To overcome these flaws, new intelligent controllers like Fuzzy-PI Controller are presented to extinguish tie-line power due to deviation in frequency and various load disturbances. The effectiveness of the proposed controller has been confirmed using the MATLAB / SIMULINK software. The results show that the PI-fuzzy controller provides fast response, little undershoots and negligible overshoot with small state transfer time to reach the final stable position. KEY WORDS: PI controller, Fuzzy controller, two area power system, load frequency control 1. INTRODUCTION For large power systems consisting of interconnected control areas, load frequencies, it is important to keep the frequency and the inter-area energy close to the planned values. The mechanical input power is used to control the frequency of the generators International Journal of Trend in Scientific Research and Development (IJTSRD) International Open Access Journal | www.ijtsrd.com ISSN No: 2456 - 6470 | Volume - 3 | Issue – 1 | Nov www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 PI Based Controller for Load Frequency Control Thermal Area Interconnected Power System Ajay Kumar Maurya1 , Dr. G. K. Banerjee2 , Dr. Piush Kumar Ph.D. Scholar, Department of Electrical Engineering, IFTM University, Moradabad, U ical & Electronics Technology, Federal TVET Institute, Addis Ababa , Ethiopia Professor, Department of Electrical Engineering, IFTM University, Moradabad, UP, India Department of EEE, SRMS College of Engineering and Technology, Bareilly, UP, India This paper presents how to design proportional PI based controller for efficiently load frequency control. Loads on the electrical system always vary in relation to that time, which results in diversity of frequency, causing frequency control problems to be loaded. The frequency difference is highly undesirable and the m allowable difference in frequency is ± 0.5 This paper load frequency control is done by PI controller, which is a conventional controller. This type of controller is slow and the controller does not allow the designer to keep in mind the potential ange in operating conditions and non-linearity in the generator unit. To overcome these flaws, new PI Controller are line power due to deviation in frequency and various load disturbances. effectiveness of the proposed controller has been confirmed using the MATLAB / SIMULINK fuzzy controller provides fast response, little undershoots and negligible overshoot with small state transfer time to PI controller, Fuzzy controller, two area power system, load frequency control For large power systems consisting of interconnected control areas, load frequencies, it is important to keep area energy close to the planned values. The mechanical input power is used to control the frequency of the generators, and the change in frequency and line voltage is measured, which is a measure of the change in rotor angle. A well designed power system should be able to guarantee the acceptable quality of the power supply by keeping the frequency and voltage levels tolerable limits. Changes in the network load mainly affect the system frequency, while the reactive power is less sensitive to frequency changes and depends mainly on voltage fluctuations. Thus, the control of the active and reactive power in the power grid is treated separately. The load frequency control is mainly concerned with the control of the system frequency and the active power, while the automatic voltage regulator loop regulates the changes of the reactive power and voltage magnitude. Load frequency control is the basis of many advanced concepts of large scale control of the power system. The load frequency control (LFC) controls the actual power and frequency. MATLAB provides an excellent environment programming. It has great flexibility and utility for engineering applications. SIMULINK is a visual modeling tool, which works on MATLAB shell. The goal of the load frequency control (LFC) is to maintain zero steady state errors in a multi area interconnected power system. and frequency from the nominal values, when there is any mismatch in real power and reactive power generations and demands. It can be provided by sensitivity analysis that mismatches in the real power balance affects primarily the sys Research and Development (IJTSRD) www.ijtsrd.com 1 | Nov – Dec 2018 Dec 2018 Page: 928 or Load Frequency Control of Thermal Area Interconnected Power System Dr. Piush Kumar3 versity, Moradabad, Uttar Pradesh, India Federal TVET Institute, Addis Ababa , Ethiopia Professor, Department of Electrical Engineering, IFTM University, Moradabad, UP, India Department of EEE, SRMS College of Engineering and Technology, Bareilly, UP, India change in frequency and line voltage is measured, which is a measure of the change in rotor angle. A well designed power system should be able to guarantee the acceptable quality of the power supply by keeping the frequency and voltage levels within Changes in the network load mainly affect the system frequency, while the reactive power is less sensitive to frequency changes and depends mainly on voltage fluctuations. Thus, the control of the active and power grid is treated separately. The load frequency control is mainly concerned with the control of the system frequency and the active power, while the automatic voltage regulator loop regulates the changes of the reactive power and ad frequency control is the basis of many advanced concepts of large scale The load frequency control (LFC) controls the actual MATLAB provides an for modeling and great flexibility and utility for engineering applications. SIMULINK is a visual modeling tool, which works on MATLAB shell. The goal of the load frequency control (LFC) is to maintain zero steady state errors in a multi area interconnected power system. The change in voltage and frequency from the nominal values, when there is any mismatch in real power and reactive power generations and demands. It can be provided by sensitivity analysis that mismatches in the real power balance affects primarily the system frequency, but
  • 2. International Journal of Trend in Scientific Research and @ IJTSRD | Available Online @ www.ijtsrd.com leaves the bus voltage essentially unaffected. control system is essential to cancel the effects of the sudden load changes and to keep the frequency at the nominal value [3–5] 1.1 TWO-area power system model A two-area interconnected thermal power system as shown in Fig. 1 is considered. The system is widely used in literature for the design and analysis of AGC [7]. In Fig. 1, B1 and B2 are the frequency bias parameters; ACE1 and ACE2 are area control errors; X1 and X2 are the control outputs from the controller; R1 and R2 are the governor speed regulation parameters in p.u. Hz; TH1 and TH2 governor time constants in seconds; Δ are the governor output command (p.u.); are the turbine time constant in seconds; ΔPT 2 are the change in turbine output powers; and ΔPE2 are the load demand changes; are the power system gains; TP1 and TP2 system time constant in seconds; incremental change in tie line power (p.u.); Δf2 are the system frequency deviations in Hz. The relevant parameters are given in Appendix A. Figure 1: Two area Thermal–Thermal plant with conventional PI controller 1.2 Modeling of the tie-line The well known power transfer equation is 1 2o 1 2 1 2 V V P s in ( ) x     Where 1 and 2 are the angles of end voltages V and V2 respectively. The sequence of subscript indicates that the tie line defines positive in power direction 1 to 2. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 leaves the bus voltage essentially unaffected. So, a control system is essential to cancel the effects of the sudden load changes and to keep the frequency at the area interconnected thermal power system as shown in Fig. 1 is considered. The system is widely used in literature for the design and analysis of AGC are the frequency bias are area control errors; are the control outputs from the controller; are the governor speed regulation are the speed ΔPH1 and ΔPH2 are the governor output command (p.u.); TT1 and TT 2 are the turbine time constant in seconds; ΔPT1 and are the change in turbine output powers; ΔPE1 are the load demand changes; KP1 and KP2 2 are the power system time constant in seconds; ΔPTie is the incremental change in tie line power (p.u.); Δf1 and are the system frequency deviations in Hz. The relevant parameters are given in Appendix A. Thermal plant with conventional PI controller The well known power transfer equation is (1) are the angles of end voltages V1 The sequence of subscript positive in power For tiny deviation in the angles and the tie line changes with the power amount 1 2 12 1 2 1 2 V V P cos( )( ) x         In accordance with the concept of "electrical stiffness" of synchronous machines, we define coefficient" of a line 𝑇 = | | | | cos ( Thus the equation (2) can be written as o 1 2 1 2P T ( )       Figure 2: Conventional Two Area System: Basic Block Diagram The frequency deviation is related to angle by the formula 1 d ( ) f 2 dt        or d ( ) dt     or 2 2     Thus the equation (3.4) can be written as  t t o 12 1 20 0 P 2 T f dt f dt       Taking Laplace transformation of equation  o 12 1 2 2 T P (s) f (s) f (s) s       The above equation can be represented as in figure (3) Figure 3: Block Diagram Representation of a Tie Line Similarly the incremented tie line power expected from area 2 is given by  o 12 2 1 2 T P (s) f (s) f (s) s       Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 929 For tiny deviation in the angles and the tie line changes with the power amount 12 1 2 1 2P cos( )( )        (2) In accordance with the concept of "electrical stiffness" of synchronous machines, we define "synchronizing (𝛿 − 𝛿 ) (3) Thus the equation (2) can be written as 1 2 1 2P T ( )       (4) Figure 2: Conventional Two Area System: Basic Block Diagram The frequency deviation is related to the reference 1 d ( ) 2 dt    1 d( ) 2 dt    d ( ) 2 f     0 2 2 t f d t     Thus the equation (3.4) can be written as t t 12 1 20 0 P 2 T f dt f dt       Taking Laplace transformation of equation 12 1 2P (s) f (s) f (s)     (5) The above equation can be represented as in figure (3) Figure 3: Block Diagram Representation of a Tie – Similarly the incremented tie line power expected 12 2 1P (s) f (s) f (s)    
  • 3. International Journal of Trend in Scientific Research and @ IJTSRD | Available Online @ www.ijtsrd.com The power balance equation for single area can be given by So for the double area, the equation should be modified as follows 1 1 1 1 1 1 1 2 2 ( ) T E o H d f P P B f P f d t            1 T1 E1 12 1 1 1 o 2H P (s) P (s) P (s) s f (s) B f (s) f          If 𝑇 = 𝐾 = Equation (6) can be written as 1 P1 T 1 E 1 1 2f (s) G (s) P (s) P (s) P (s)       P 1 P 1 P 1 K G (s ) 1 sT   Thus the complete block diagram representation of two area load frequency control is given in figure (1). 2. Ziegler -Nichols Rule Based Tuning For comparison the PID controller was tuned using conventional Ziegler –Nichols tuning rule based on the critical gain Ku and critical period P Ku and Pu were calculated from the sustained oscillations of the output by employing only proportional controller. The sustained oscillation response with proportional controller under critical gain is shown in Figure (4). As per the Ziegler Nichols rule the settings for PID controller parameter are given in the following table [1]. Controller parameters calculated for conventional controller are given in Table [2]. Table 1: Ziegler-Nichols tuning rules Type of control Gc(s) K Proportional (P) Kc 0.5 K Proportional– Integral(PI) c i 1 K 1 sT       0.45K Proportional- Integral- Derivative (PID) c d i 1 K 1 sT sT        0.6K International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 The power balance equation for single area can be So for the double area, the equation should be 1 1 1 1 1 2P P B f P        T1 E1 12 1 1 1P (s) P (s) P (s) s f (s) B f (s)         (6) 1 P1 T 1 E1 12f (s) G (s) P (s) P (s) P (s)       Thus the complete block diagram representation of two area load frequency control is given in figure (1). Nichols Rule Based Tuning For comparison the PID controller was tuned using Nichols tuning rule based on and critical period Pu. Values of were calculated from the sustained oscillations of the output by employing only nal controller. The sustained oscillation response with proportional controller under critical gain is shown in Figure (4). As per the Ziegler- Nichols rule the settings for PID controller parameter are given in the following table [1]. Controller s calculated for conventional controller are Nichols tuning rules Kc Ti Td 0.5 Ku - - u0.45K uP 1.2 - u0.6K uP 2 uP 8 Figure 4: System response with proportional controller under critical gain Table 2: Controller Parameters for conventional controller Kc T 0.45.Ku= 0.66 Pu /1.2 = 3. Different types of controllers 3.1 PI - Controller The 'PI' controller will eliminate forced oscillations and steady state error, which will operation of the on-off controller and the 'P' controller, respectively. However, starting an integral mode has a negative impact on the response speed and overall stability of the system. Therefore, the PI controller does not increase the reaction rate. It can be expected because the PI controller has no means of predicting what will happen to the bug in the near future. This problem can be solved by introducing a derivative mode that is able to predict what will happen to the error in the near future and thus reduce it [13] 3.2 Fuzzy Controller The general architecture of a fuzzy controller is depicted in Figure (5) [14]. The origin of a fuzzy controller is an fuzzy inference engine (FIS), which includes fuzzification,, knowledge base evalu and defuzzification in the data flow. systems are the error and the change in the error of the feedback loop, while the output is the control action. There are 7 trapezoidal membership functions in each input i.e.NB (Negative Big), NM (Negative Medium), NS (Negative Small), Z (Zero), PS (Positive Small), PM (Positive Medium), PB (Positive Big). The mamdani rule base adopted here and the 0 0.5 1 1.5 2 -0.2 -0.15 -0.1 -0.05 0 0.05 0.1 0.15 Time (sec) FrequencyDeviation(Hz.) Pu = 1.2 Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 930 Figure 4: System response with proportional controller under critical gain Table 2: Controller Parameters for conventional controller i Ki /1.2 = 1 Kc/Ti = 0.66 Different types of controllers The 'PI' controller will eliminate forced oscillations and steady state error, which will result in the off controller and the 'P' controller, respectively. However, starting an integral mode has a negative impact on the response speed and overall stability of the system. Therefore, the PI controller does not increase the eaction rate. It can be expected because the PI controller has no means of predicting what will happen to the bug in the near future. This problem can be solved by introducing a derivative mode that is able to predict what will happen to the error in the ear future and thus reduce it [13] The general architecture of a fuzzy controller is depicted in Figure (5) [14]. The origin of a fuzzy controller is an fuzzy inference engine (FIS), which includes fuzzification,, knowledge base evaluation in the data flow. The inputs to the systems are the error and the change in the error of the feedback loop, while the output is the control action. There are 7 trapezoidal membership functions in each NM (Negative Medium), NS (Negative Small), Z (Zero), PS (Positive Small), PM (Positive Medium), PB (Positive Big). The mamdani rule base adopted here and the 2.5 3 3.5 4 Time (sec) Ku = 1.467
  • 4. International Journal of Trend in Scientific Research and @ IJTSRD | Available Online @ www.ijtsrd.com defuzzification process is centroid method. The fuzzy rules are shown in Table [3]. Figure 5: Structure of fuzzy logic controller Table 3: Fuzzy Rule Base E ∆E NB NM NS ZE PS NB PB PB PB PB PM NM PB PM PM PM PS NS PM PM PS PS PS ZE NS NS NS ZE PS PS ZE NS NS NS NS PM NS NS NM NM NM PB NS NM NB NB NB A fuzzy system is described by a set of IF rules and uses diverse membership functions. To solve the load-frequency control problem in fuzzy controller, controller inputs are Area Control Error and derivative of Area Control Error and its considered as the control signal. The member ship function uses in fuzzy logic controller for Error, change in Error and output is shown in figure (5). Figure 5: Membership functions of inputs (E, and output 3.3 PI- Fuzzy Logic Controller A Fuzzy-PI controller designed based on a linear model of power system under the loading condition FLC designed to eliminate the need for continuous International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 defuzzification process is centroid method. The fuzzy Structure of fuzzy logic controller Table 3: Fuzzy Rule Base PM PB PM PS PS PS PS ZE PS PS NM NM NB NB NB NB A fuzzy system is described by a set of IF-THEN rules and uses diverse membership functions. To frequency control problem in fuzzy controller, controller inputs are Area Control Error and derivative of Area Control Error and its output are considered as the control signal. The member ship function uses in fuzzy logic controller for Error, change in Error and output is shown in figure (5). Membership functions of inputs (E, ΔE) PI controller designed based on a linear model of power system under the loading condition FLC designed to eliminate the need for continuous operator attention and used automatically to adjust some variables the process variable is kept reference value. A FLC consists of three sections Namely, fuzzifier, rule base, and defuzzifier. Fuzzy-PI controller structure is shown in Figure (6). Figure 6: PI-Fuzzy Logic controller in Simulink 4. Results and Simulation Performed simulations using PI and Fuzzy controllers applied to a two area interconnected power systems. The developed system is simulated with 10 % step load disturbance in area 1. Due to this the change in dynamic responses of the system has been observed, as shown in below Figures. It is examine from the output responses that the proposed Fuzzy Controller is stable and less oscillations and the settling time also improved considerably. Also this output justified that this interconnection is valid for Thermal-Thermal systems. For conventional PI controller and Fuzzy-PI controller, the main objective is to improve the control performance 4.1 Uncontrolled case The frequency changes in area 10% step load perturbation is shown in figure (7). There is a steady state error in the response. Figure 7: Two area Thermal (Uncontrolled) with a disturbance of area-1: Frequency deviation of area 4.2 Controlled Case with Proportional plus Integral Controller The frequency changes in area 10% step load perturbation is shown in figure (8) and (9). (10% step load perturbation is given in area Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 931 attention and used automatically to adjust process variable is kept at the reference value. A FLC consists of three sections Namely, fuzzifier, rule base, and defuzzifier. The controller structure is shown in Figure (6). zzy Logic controller in Simulink simulations using PI and Fuzzy-PI controllers applied to a two area interconnected power systems. The developed system is simulated with 10 % step load disturbance in area 1. Due to this the change in dynamic responses of the system has been hown in below Figures. It is examine from the output responses that the proposed Fuzzy-PI Controller is stable and less oscillations and the settling time also improved considerably. Also this output justified that this interconnection is valid for Thermal systems. For conventional PI PI controller, the main objective is to improve the control performance The frequency changes in area-1 and area-2 for the 10% step load perturbation is shown in figure (7). There is a steady state error in the response. Two area Thermal-Thermal plant disturbance of 10 % in 1: Frequency deviation of area -1 and area – 2 Controlled Case with Proportional plus The frequency changes in area-1 and area-2 for the 10% step load perturbation is shown in figure (8) and (9). (10% step load perturbation is given in area -1).
  • 5. International Journal of Trend in Scientific Research and @ IJTSRD | Available Online @ www.ijtsrd.com The steady state error is zero in this case. The frequency deviation of area-1 is much more Figure 8: Two area Thermal-Thermal plant (Controlled with PI) with Disturbance of 10 % in area-1: Frequency deviation of area Figure 9: Two area Thermal-Thermal plant (Controlled with PI) with a Disturbance of 10 % in area-1: Frequency deviation of ar 4.3 Controlled Case with Fuzzy-PI Controller The frequency changes in area-1 and area 10% step load perturbation is shown in figure (10) and (11). (10% step load perturbation is given in The steady state error is zero in this case. The frequency deviation of area-1 is much more 0 5 10 15 20 25 30 35 Time (Second) -0.07 -0.06 -0.05 -0.04 -0.03 -0.02 -0.01 0 International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 The steady state error is zero in this case. The 1 is much more Thermal plant Disturbance of 10 % in 1: Frequency deviation of area -1 Thermal plant Disturbance of 10 % in 1: Frequency deviation of area -2 PI Controller 1 and area-2 for the 10% step load perturbation is shown in figure (10) and (11). (10% step load perturbation is given in area -1). The steady state error is zero in this case. The 1 is much more Figure 10: Two area Thermal (Controlled with Fuzzy-PI) With disturbance of 10 % in area-1: Frequency deviation of area Figure 11: Two area Thermal (Controlled with Fuzzy-PI) With Disturbance of 10 % in area-1: Frequency deviation of area 4.4 Comparison between PI and Fuzzy Controller Figure 12: Comparison result between Fuzzy and PI controller with Disturban area-1: Frequency deviation of area 40 45 50 Area 2 PI Controller Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 932 Figure 10: Two area Thermal-Thermal plant With disturbance of 10 1: Frequency deviation of area -1 wo area Thermal-Thermal plant With Disturbance of 10 1: Frequency deviation of area -2 Comparison between PI and Fuzzy-PI Figure 12: Comparison result between Fuzzy-PI Disturbance of 10 % in 1: Frequency deviation of area -1
  • 6. International Journal of Trend in Scientific Research and @ IJTSRD | Available Online @ www.ijtsrd.com Figure 13: Comparison result between Fuzzy and PI controller in with Disturbance of 10 % in area-1: Frequency deviation of area The comparison of peak undershoots; Peak Overshoot and Settling Time via PI controller and Fuzzy controller are given in Table [3]. Table 3: Thermal-Thermal plant: PI Controller Vs Fuzzy-PI Controller Peak Undershoot Peak Overshoot Two Area Area -1 Area -2 Area -1 Area -2 PI Control ler - 0.15 57 - 0.06 29 0.02 97 0.00 03 PI- Fuzzy Control ler - 0.13 20 - 0.05 62 0.00 27 0.00 00 5. Conclusion In this paper a new technique Fuzzy-PI controller is designed for automatic load frequency control of interconnected Thermal - Thermal systems. The controller performances Fuzzy-PI approach is in work for a Load Frequency Control for Generation of Interconnected Power System. The proposed controller can handle the non-linearity and at the same time faster than other conventional controllers. Also the simulation results are compared with a conventional other controller. From the Result shown in figure (8) to figure (13). The results obtained for double area Thermal-Thermal plant shows the superiority such controllers over the conventional PI controllers. In Fuzzy-PI Controller the settling time has been reduced in area1 and area 2 are 5.63 sec and 6.30 sec respectively. It is explicit that the International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 Figure 13: Comparison result between Fuzzy-PI Disturbance of 10 % in 1: Frequency deviation of area -2 The comparison of peak undershoots; Peak Overshoot and Settling Time via PI controller and Fuzzy-PI Thermal plant: PI Controller Vs Settling Time(Sec) Are a-1 Are a-2 12.8 8 14.8 5 7.25 8.55 PI controller is designed for automatic load frequency control of Thermal systems. The PI approach is in work for a Load Frequency Control for Generation of nected Power System. The proposed linearity and at the same time faster than other conventional controllers. Also the simulation results are compared with a conventional other controller. From the Result shown figure (13). The results obtained for Thermal plant shows the superiority such controllers over the conventional PI PI Controller the settling time has been reduced in area1 and area 2 are 5.63 sec and spectively. It is explicit that the performance in term of settling time and overshoot of fuzzy-PI controller is better. There is no steady state error. So fuzzy-PI controller shows its effectiveness over the conventional PI controller. The result shows that the proposed intelligent controller is having improved dynamic response and at the same time faster than conventional APPENDIX Parameter KP1 = KP2 120 Hz. / p.u. MW KH1 =KH2 1 Hz. / p.u. MW KT1 =KT2 1 Hz. / p.u. MW TP1 = TP2 TH1 =TH2 0.08 Sec. TT1 = TT2 B1 = B2 0.425 p.u. MW / Hz. R1 = R2 2.4 Hz. / p.u. MW To 0.0867 p.u. MW/Hz References 1. O.I. Elgerd, Electric Energy Systems Theory Introduction, second ed., Tata McGraw Hill, New Delhi, 2000. 2. P. Kundur, Power System Stability and Control, eighth reprint, Tata McGraw Hill, New Delhi, 2009. 3. H. Bevrani, Robust Power System Frequency Control, Springer, New York, 2009. 4. I.P. Kumar, D.P. Kothari, Recent philosophies of automatic generation control strate systems, IEEE Trans. Power Syst. 20 (2005) 346 357. 5. H. Shayaghi, H.A. Shayanfar, A. Jalili, Load frequency control strategies: a state of the art survey for the researcher, Energy Convers. Manag. 50 (2009) 344–354. 6. K.P.S. Parmar, S. Majhi, D. frequency control of a realistic power system with multi-source power generation, Int. J. Electr. Power Energy Syst. 42 (2012) 426 7. U.K. Rout, R.K. Sahu, S. Panda, Design and analysis of differential evolution algorithm based automatic generation control for interconnected power system, Ain Shams Eng. J. 4 (3) (2013) 409–421. 8. M. Masiala, M. Ghribi and A. Kaddouri, Senior Member, “An Adaptive Fuzzy Controller Gain Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 933 performance in term of settling time and overshoot of PI controller is better. There is no steady state PI controller shows its effectiveness over the conventional PI controller. hat the proposed intelligent controller is having improved dynamic response and at the same time faster than conventional controller Value 120 Hz. / p.u. MW 1 Hz. / p.u. MW 1 Hz. / p.u. MW 20 Sec. 0.08 Sec. 0.3 Sec. 0.425 p.u. MW / Hz. 2.4 Hz. / p.u. MW 0.0867 p.u. MW/Hz O.I. Elgerd, Electric Energy Systems Theory – An Introduction, second ed., Tata McGraw Hill, New Kundur, Power System Stability and Control, eighth reprint, Tata McGraw Hill, New Delhi, H. Bevrani, Robust Power System Frequency Control, Springer, New York, 2009. I.P. Kumar, D.P. Kothari, Recent philosophies of automatic generation control strategies in power systems, IEEE Trans. Power Syst. 20 (2005) 346– H. Shayaghi, H.A. Shayanfar, A. Jalili, Load frequency control strategies: a state of the art survey for the researcher, Energy Convers. 354. K.P.S. Parmar, S. Majhi, D.P. Kothari, Load frequency control of a realistic power system with source power generation, Int. J. Electr. Power Energy Syst. 42 (2012) 426–433. U.K. Rout, R.K. Sahu, S. Panda, Design and analysis of differential evolution algorithm based generation control for interconnected power system, Ain Shams Eng. J. 4 (3) (2013) M. Masiala, M. Ghribi and A. Kaddouri, Senior “An Adaptive Fuzzy Controller Gain
  • 7. International Journal of Trend in Scientific Research and @ IJTSRD | Available Online @ www.ijtsrd.com Scheduling For Power System Load Control” Dept. of Electrical University de Moncton, New Brunswick, Canada 1515 -1520, IEEE International Conference on Industrial Technology (ICIT), 2004 9. N. Jaleeli, D. N. Ewart, and L. H. Fink. “Understanding Automtic Generation Control.” IEEE Transactions on Power Systems, No.3. August 1992, pp.1106-1122 10. L.C. Saikia, J. Nanda, S. Mishra, Performance comparison of several classical controllers in AGC for multi-area interconnected thermal system, Int. J. Electr. Power Energy Syst. 33 (2011) 394–401. 11. S.A. Taher, M.H. Fini, S.F. Aliabadi, Fractional order PID controller design for LFC in electric power systems using imperialist competitive algorithm, Ain Shams Eng. J. 5 (2014) 121 12. Ramanand Kashyap, Prof. S.S. Sankeswari, Prof. B. A. Patil ,Load Frequency Control Using Fuzzy PI Controller Generation of Interconnected Hydro Power System ,International Journal of Emerging Technology and Advanced Engineering, Volume 3, Issue 9, September 2013 13. Vasadi Srinivasa Rao, P. D. Srinivas, CH. Ravi Kumar, Load Frequency Control (LFC) of Three Area Interconnected Power System using Adaptive Neuro Fuzzy Interface System, International Journal of Scientific Engineering and Technology Research ISSN 2319 Vol.04,Issue.43, October-2015, Pages:9482 International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 Scheduling For Power System Load -- Frequency Engineering, University de Moncton, New Brunswick, Canada IEEE International Conference on and L. H. Fink. “Understanding Automtic Generation Control.” Systems, Vol. 7. L.C. Saikia, J. Nanda, S. Mishra, Performance comparison of several classical controllers in area interconnected thermal system, Int. J. Electr. Power Energy Syst. 33 , M.H. Fini, S.F. Aliabadi, Fractional order PID controller design for LFC in electric power systems using imperialist competitive algorithm, Ain Shams Eng. J. 5 (2014) 121–135. Ramanand Kashyap, Prof. S.S. Sankeswari, Prof. trol Using Fuzzy- PI Controller Generation of Interconnected Hydro International Journal of Emerging Technology and Advanced Engineering, Volume Vasadi Srinivasa Rao, P. D. Srinivas, CH. Ravi ntrol (LFC) of Three Area Interconnected Power System using Adaptive Neuro Fuzzy Interface System, International Journal of Scientific Engineering and Technology Research ISSN 2319-8885 2015, Pages:9482-9488 14. Sateesh Kumar Vavilala, Machavarapu Suman , Load Frequency Control of Two Area Interconnected Power System Using Conventional and Intelligent Controllers, Journal of Engineering Research and Applications, ISSN : 2248 Version 3), January 2014, pp.156 15. J. Nanda and B. L. Kaul, "Automatic generation control of an interconnected power system", IEE, Vol 125, No. 5, 1978, pp. 385 16. Nilay.N.Shah, Aditya. D. Chafekar and Dwij. N.Mehta, “Automatic Load Frequency Control of Two Area Power System With Conventional and Fuzzy Logic Control” International Journal of Research in Engineering and Technology, Volume 1, Issue 3 ,Nov. 2012, pp. 343 17. Saravuth Pothiya, Issarachai Ngamroo, Suwan Runggeratigul, and Prinya Tantaswadi, “Design of Optimal Fuzzy Logic based PI Controller using Multiple Tabu Search Algorithm for Load Frequency Control” International Journal of Control, Automation, and Systems, vol. 4, no. 2, pp. 155-164, April 2006 18. Xiangping Meng, Qingxian Gong, Lei Feng, Wen Zheng, Weijun Zhang, “PI Fuzzy Sliding Mode Load Frequency. Control of Multiarea Interconnected Power Systems” IEEE International Symposium on Houston Texas, pp. 1023-1027, Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 934 Sateesh Kumar Vavilala, R S Srinivas, Machavarapu Suman , Load Frequency Control of Two Area Interconnected Power System Using Conventional and Intelligent Controllers, Int. Journal of Engineering Research and Applications, ISSN : 2248-9622, Vol. 4, Issue 1( 2014, pp.156-160 L. Kaul, "Automatic generation control of an interconnected power system", Proc. Vol 125, No. 5, 1978, pp. 385-390 Nilay.N.Shah, Aditya. D. Chafekar and Dwij. N.Mehta, “Automatic Load Frequency Control of r System With Conventional and Fuzzy Logic Control” International Journal of Research in Engineering and Technology, Volume 1, Issue 3 ,Nov. 2012, pp. 343-347. Saravuth Pothiya, Issarachai Ngamroo, Suwan Runggeratigul, and Prinya Tantaswadi, “Design of imal Fuzzy Logic based PI Controller using Multiple Tabu Search Algorithm for Load International Journal of Control, Automation, and Systems, vol. 4, no. 2, Xiangping Meng, Qingxian Gong, Lei Feng, Wen un Zhang, “PI Fuzzy Sliding Mode Load Frequency. Control of Multiarea Interconnected Power Systems” IEEE Symposium on Intelligent Control 1027, October 2003