SlideShare a Scribd company logo
1 of 74
Electrical and I&C Dept., Steag
Encotec India
1
Presented By: Vinod J. Patel
To
Vector groups of Transformer
Training on
Electrical and I&C Dept., Steag
Encotec India
2
Introduction to Vector Group
• The vector group marks the circuitry of
windings and their phase position to each
other. It consists of a capital and small
letter plus a code number. The capital
letter A, B, C refers to the HV winding
and the lower case a, b, c to the LV
winding with (A), (B), (C) for a tertiary
winding, where provided. Neutral
terminals precede line terminals.
Electrical and I&C Dept., Steag
Encotec India
3
Introduction to Vector Group
• Each winding has two ends designated by
the subscript numbers 1, 2, or if there are
intermediary tapings (or there are
sections of the same winding) these are
numbered in order to their separation
from end 1. The most common vector
groups are summarized alongside, input
left-hand, output right-hand. Unless
otherwise requested.
Electrical and I&C Dept., Steag
Encotec India
4
Requirement of Vector Group
• In 3 phase transformers polarity alone is
insufficient to represent the relation between
HV and LV windings. In addition to the
terminal marking on HV and LV side voltage
vector diagram are required to show the
angular displacement between HV and LV
winding. Vector group is necessary to indicate
the terminal marking and the phase
displacement between primary and secondary
voltages or currents.
Electrical and I&C Dept., Steag
Encotec India
5
Under normal condition the line to line
voltages on HV side are displaced from
corresponding voltages on LV sides. Also
line to neutral voltage on HV side are
displaced from corresponding voltages on
LV side. The displacement depend upon the
transformer connections. As per IS 2026-
1972, there are four vector groups of
standard connections
Requirement of Vector Group
Electrical and I&C Dept., Steag
Encotec India
6
Phase shifts in Star Delta
Transformers
• Positive & Negative phase sequence voltages
and currents undergo a phase shift in passing
through a star-delta transformer which
depends on labeling of terminals.
• Before considering the phase shift, we need to
discuss the standard polarity marking of a
single phase transformer as shown in the
figure-1. The transformer ends marked with a
dot have the same polarity. Therefore, voltage
VHH' is in phase with voltage VLL'.
Electrical and I&C Dept., Steag
Encotec India
7
VHH'
H
H'
VLL'
L
L'
I1 I2
Figure-1
Polarity Marking of a single phase
transformer
Electrical and I&C Dept., Steag
Encotec India
8
• Consider now a star/delta transformer
with terminal labeling as indicated in
Figure-2. Windings shown parallel to
each other are magnetically coupled.
Assume that the transformer is excited
with positive sequence voltages and
carries positive sequence currents. With
the polarity mark shown, we can
immediately draw the phasor diagram of
Figure-3.
Phase shifts in Star Delta
Transformers
Electrical and I&C Dept., Steag
Encotec India
9
• The following relatdionship between the
voltages on two sides of the transformer
is observed from the phasor diagram.
Positive sequence line voltages on star
side lead the corresponding voltages on
the delta side by 30 deg. The same also
applies for the line currents.
Phase shifts in Star Delta
Transformers
Electrical and I&C Dept., Steag
Encotec India
10
A
B
C
N
a
c
b
Star side quantities lead delta side quantity by 30 deg.
Figure-2
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
11
VAB1
VBC1
VCA1
VCN1
VAN1
VBN1
Vab1
Vca1
Vbc1
30 deg.
Positive Sequence Voltage on a Star / Dleta Transformer
Figure-3
Phasor diagram of star-delta Transformer
Electrical and I&C Dept., Steag
Encotec India
12
• If the delta side is connected as shown in Figure-4
the phase shift reverses; the delta side quantities
lead the star side quantity by 30 deg.
A
B
C
N
c
b
a
Delta side quantities lead Star side quantity by 30 deg.
Figure-4
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
13
• Instead if the transformer of Figure-2 is now
excited by negative phase sequence voltages &
currents, the voltage phasor diagram will be as
shown in Figure-5.
VAB2
VCA2
VBC2
VBN2
VAN2
VCN2
Vab2
Vbc2
Vca2
30 deg.
Negative Sequence Voltage on a Star / Dleta Transformer
Figure-5
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
14
• The phase shift in comparison to
positive sequence case now reverses,
i.e. the star side quantities lag the
delta side quantities by 30 deg. The
result for figure- 4 also
correspondingly reverses.
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
15
• It is assumed that a star/delta
transformer is so labeled that the positive
sequence quantities on the HV side lead
their corresponding positive sequence
quantities on the LV side by 30 deg. The
reverse is the case of negative sequence
quantities wherein HV quantities lag the
corresponding LV quantities by 30 deg.
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
16
• The interconnection of the phase windings to give
a three phase, three-or four wire supply provides
three alternative modes of connection
(1) Mesh or Delta
(2) Star
(3) Zig-zag
Each of these can be achieved in two ways.
For Example a star Connection may be had by
joining together A1, B1 and C1, to form the
neutral and using A2, B2 and C2 as line terminals.
Alternatively A2, B2 and C2 may be joined to give
neutral and A1, B1 and C1 may be used as line
terminals.
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
17
• Since primary and secondary can be
treated in either of these ways, at least
twelve methods of connection are
possible. These are arranged in four main
groups, as given below, according to the
phase displacement which exists between
the line voltages on the two sides of the
transformer.
Star Delta Transformation
Electrical and I&C Dept., Steag
Encotec India
18
Vector Groups (Group-1)
• Group 1: Zero phase displacement
(Yy0, Dd0, Dz0)
1) Yy0: Star – Star Connection
2) Dd0: Delta – Delta Connection
3) Dz0: Delta – Zig-zag Connection
Electrical and I&C Dept., Steag
Encotec India
19
Yy0: Star – Star Connection
Electrical and I&C Dept., Steag
Encotec India
20
Dd0: Delta – Delta Connection
Electrical and I&C Dept., Steag
Encotec India
21
Dz0: Delta – Zig-zag Connection
Electrical and I&C Dept., Steag
Encotec India
22
• Group 2: 180 degree phase
displacement (Yy6, Dd6, Dz6)
1) Yy6: Star – Star Connection
2) Dd6: Delta – Delta Connection
3) Dz6: Delta – Zig-zag Connection
Vector Groups (Group-2)
Electrical and I&C Dept., Steag
Encotec India
23
Yy6: Star – Star Connection
Electrical and I&C Dept., Steag
Encotec India
24
Dd6: Delta – Delta Connection
Electrical and I&C Dept., Steag
Encotec India
25
Dz6: Delta – Zig-zag Connection
Electrical and I&C Dept., Steag
Encotec India
26
• Group 3: 30 degree lag phase
displacement (Dy1, Yd1, Yz1)
1) Dy1: Delta – Star Connection
2) Yd1: Star – Delta Connection
3) Yz1: Star – Zig-zag Connection
Vector Groups (Group-3)
Electrical and I&C Dept., Steag
Encotec India
27
Dy1: Delta – Star Connection
Electrical and I&C Dept., Steag
Encotec India
28
Yd1: Star – Delta Connection
Electrical and I&C Dept., Steag
Encotec India
29
Yz1: Star – Zig-zag Connection
Electrical and I&C Dept., Steag
Encotec India
30
• Group 4: 30 degree lead phase
displacement (Dy11, Yd11, Yz11)
1) Dy11: Delta – Star Connection
2) Yd11: Star – Delta Connection
3) Yz11: Star – Zig-zag Connection
Vector Groups (Group-4)
Electrical and I&C Dept., Steag
Encotec India
31
Dy11: Delta – Star Connection
Electrical and I&C Dept., Steag
Encotec India
32
Yd11: Star – Delta Connection
Electrical and I&C Dept., Steag
Encotec India
33
Yz11: Star – Zig-zag Connection
Electrical and I&C Dept., Steag
Encotec India
34
Symbol Description
• Phase displacement zero = 0
• Phase displacement 180 degree = 6
• Phase displacement 30 degree lag = 1
• Phase displacement 30 degree lead = 11
• Letter Y represents star connected HV
• Letter y represents star connected LV
• Letter D represents delta connected HV
• Letter d represents delta connected LV
• Letter Z represents star connected zig-zag
Electrical and I&C Dept., Steag
Encotec India
35
• The most popular method of connecting
transformer is the delta-star connections
(4, Dy11). The connection diagram
illustrates the relative position of the
terminals in the terminal box and the
internal connections that are made. The
HV winding is connected to a 3-wire
supply, of phase sequence A, B, C, and at
the instant chosen the potential of A is at
its maximum positive value. Thus the line
voltages on the HV side will form an
equilateral triangle.
Description of Dy11
Electrical and I&C Dept., Steag
Encotec India
36
• The line terminals are A2, B2 and C2 and
the corners of the triangles are so
marked. It is to be noted that phase A of
the transformer lies between A2 and B2,
Phase B between B2 and C2 and phase C
between C2 and A2 owing to internal
connections used.
Description of Dy11
Electrical and I&C Dept., Steag
Encotec India
37
• From the phasor diagrams of induced
voltages for HV and LV sides it is
observed that the voltage of the HV line
A2 is at the maximum value, the LV line
a2 has been advanced 30 degree. In fact
the transformer connections have
produced this displacement of 30 degree
for all lines.
Description of Dy11
Electrical and I&C Dept., Steag
Encotec India
38
• All the other methods of connections in the
same main group no. 4 gives a similar 30 degree
advance which is the basis of classification.
• With group no. 1 there is no phase
displacement but the group no. 2 gives the
phase displacement of 180 degree. Group no. 3
cause the LV line voltage to lag by 30 degree.
• For parallel operation of transformers the
essential requirement is that the transformer
connections belong to the same main group.
Description of Vector Groups
Electrical and I&C Dept., Steag
Encotec India
39
• It is possible to obtain any desired phase
shift with a three phase transformer if the
primary and / secondary windings are
divided into a sufficient number of
sections. The Zig-Zag connection is one
example of a sectionalized winding.
Description of Vector Groups
Electrical and I&C Dept., Steag
Encotec India
40
• 15 percent more turns are required for a given
total voltage per phase compared with a
normal phase connection in Zig-zag winding,
which may increase in the frame size for the
given rating.
• Nevertheless, the advantages of zig-zag
arrangement may offset the cost; unbalanced
loads on the secondary side are distributed
better on the primary side.
• The zig-zag / star connection has been
employed where delta connections were
mechanically weak (on account of large
number of turns and small copper sections) in
HV transformers.
Description of Vector Groups
Electrical and I&C Dept., Steag
Encotec India
41
• In star connection with earthed neutral the
maximum voltage of the phase winding to
ground is 1/V3 (or 57.7%) of the line voltage,
while in delta connection this is equal to the line
voltage in case of earthing of one of the line
during a fault. Therefore, Phase voltage, turns
and insulation are less in star connection than
those in delta connection and for very high
voltage transformers the star connection on HV
side is about 10% cheaper than delta
connection.
Choice between Star and Delta connection
Electrical and I&C Dept., Steag
Encotec India
42
• A delta connected primary is necessary for a
star connected LV secondary feeding mixed
three phase and single phase loads. In case of
unbalanced single phase loads on secondary,
delta connected primary is necessitated to
permit the flow of zero sequence current I0=
In/3 = 1/3 (IA + IB + IC) so that IA + IB + IC =
0.
• This means that only positive and negative
sequence current flows in the lines on the delta
side.
Choice between Star and Delta connection
Electrical and I&C Dept., Steag
Encotec India
43
• This could also be achieved by star
connected primary provided the primary
and secondary star points are earthed,
but this is not recommended because of
flow of ground current for unbalanced
secondary loads.
Choice between Star and Delta connection
Electrical and I&C Dept., Steag
Encotec India
44
Choice of Transformer
connections:
(A) Star-Star (Yy0 or Yy6) connections:
This type of transformer is most
economical for small current and high
voltage transformers. The advantages
and disadvantages of such arrangement
are as under.
Electrical and I&C Dept., Steag
Encotec India
45
Star-Star (Yy0 or Yy6)
connections
• Advantages:
• The number of turns per phase and the amount
of insulation is minimum because phase voltage
= 1/V3 of line voltage.
• There is no phase displacement between
primary and secondary voltages.
• With star point available on both sides it is
possible to provide neutral connection.
• Economical for small HV transformer.
Electrical and I&C Dept., Steag
Encotec India
46
Star-Star (Yy0 or Yy6)
connections
• Disadvantages:
• If the load on secondary side of transformer is
unbalanced, the phase voltages of load side change
unless the load star point is earthed. The difficulty of
shifting neutral can be overcome by connecting the
primary star point to the star point of the Generator.
• The primary of the transformer draws a magnetizing
current which has third and fifth harmonics. If neutral
of primary is not connected to neutral of Generator, the
third and fifth harmonics current can not flow hence
the flux in the core can not be sinusoidal wave and,
therefore, the voltages will be distorted. By connecting
the primary neutral to Generator neutral, the path for
return of these third and fifth harmonics current is
provided and, therefore, the trouble of distortion of
voltage is overcome.
Electrical and I&C Dept., Steag
Encotec India
47
Star-Star (Yy0 or Yy6)
connections
• Disadvantages:
• Even if neutral of primary is connected to
neutral of Generator or earthed, still the third
harmonic is present in the alternator voltage
form, it will appear on secondary side. Though
the secondary line voltages do not contain third
harmonic voltage; but third harmonic voltages
are additive in the neutral and cause the
current in the neutral of triple frequency ( 3rd
harmonic) which will cause interference to the
nearby communication system.
• Third harmonic voltages may be high in shell
type 3 phase transformers.
Electrical and I&C Dept., Steag
Encotec India
48
Delta-Delta (Dd0 or Dd6)
connections
• This arrangement is generally used in system
which carry large current or low voltages and
especially when continuity of service must be
maintained even though one of the phase
develops fault. When one of the phase is
removed in delta-delta connected
transformers, operation continues on what is
known as open delta. By being operated in
this way , the transformer delivers three
phase currents and voltages in their correct
phase relationship but the capacity of the
transformer is reduced to 57.7% of what it
was all three phase winding sound.
Electrical and I&C Dept., Steag
Encotec India
49
Delta-Delta (Dd0 or Dd6)
connections
• Advantages:
• There is no phase displacement between
the primary and secondary voltages.
• There is no distortion of flux, because the
third harmonic component of
magnetizing current can flow in delta
connected primary winding without
flowing in the line wires.
Electrical and I&C Dept., Steag
Encotec India
50
Delta-Delta (Dd0 or Dd6)
connections
• Advantages:
• The cross section of conductor is reduced
because the phase currents is 1/V3 times
of the line current.
• No difficulty is experienced due to
unbalancing of loads on secondary side.
• Suitable for large HV transformers
• Large load unbalance can be tolerated,
3rd harmonic voltages are damped out.
Electrical and I&C Dept., Steag
Encotec India
51
Delta-Delta (Dd0 or Dd6)
connections
• Disadvantages:
• More insulation is required in
comparison to star-star connections.
• The absence of star point may be
disadvantageous. If one line gets earthed
due to fault, maximum voltage between
windings and core will be full line
voltage.
Electrical and I&C Dept., Steag
Encotec India
52
Star-Delta (Yd1 or Yd11)
connections
This type of transformer connection is
used principally where the voltage is to be
stepped down as, for example, at the end
of a transmission line. In this type of
connection of transformers the neutral of
the primary winding is earthed. In this
system line voltage ratio is 1/V3 times of
transformer turn ratio and secondary line
voltages have a phase shift of +/- 30
degree with respect to primary line
voltages.
Electrical and I&C Dept., Steag
Encotec India
53
Star-Delta (Yd1 or Yd11)
connections
On the HV side of the transformer,
insulation is stressed only to the extent of
57.7% of the line voltage and, therefore,
there is some saving in the cost of
insulation. Very common for supply
networks. One star point for a neutral to
serve mixed 1 phase and 3 phase loads.
Electrical and I&C Dept., Steag
Encotec India
54
Delta-Star (Dy1 or Dy11)
connections
This scheme of connection is generally used
where it is necessary to step up the voltage as
for example, at the beginning of a HT
transmission system. On the high voltage side
of the transformer, insulation is stressed only
to the extent of 57.7% of line to line voltage.
Another advantage is that the neutral point is
stable and will not float when load is
unbalanced. There is no distortion of flux
because the existence of a delta connection
allows a path for the 3rd harmonic currents.
Electrical and I&C Dept., Steag
Encotec India
55
Delta-Star (Dy1 or Dy11)
connections
In this scheme of connection the line
voltage ratio is V3 times of transformer
turn ratio and the secondary line voltage
have a phase shit of +/- 30 degree with
respect to primary line voltages.
Electrical and I&C Dept., Steag
Encotec India
56
Delta-Star (Dy1 or Dy11)
connections
The neutral of the secondary is grounded to
provide 3-phase, 4-wire system and this scheme
of connection is widely used in distribution
system because it can be used to serve both the
three phase power equipment and single phase
lighting circuits. In such case the 11,000 / 400 V
transformer connections provide a four wire
secondary, with neutral supplying the 4th wire.
The three phase equipment is connected to the
line wires to operate at 400V while the lighting
equipment is connected between one of the line
wires and neutral to operate at 230 Volts.
Electrical and I&C Dept., Steag
Encotec India
57
Delta-Star (Dy1 or Dy11)
connections
• Used for distribution transformer. Star
side is used on load side.
• Star-Delta or Delta-Star connected
transformers can not be operated in
parallel with star-star or delta-delta
connected transformer even though the
voltage ratio are correctly adjusted as
there will be a 30 degree phase difference
between corresponding voltages on the
secondary sides.
Electrical and I&C Dept., Steag
Encotec India
58
Interconnected star/star (Zig-Zag)
• Reduces 3rd harmonic voltages and not
sensitive to condition of unbalanced
loading.
• Restricted to low voltage windings.
• Phase voltages are composed of half
voltages with 60 degree displacement,
15% more turns are required.
• Some times used in rectifier supply.
Electrical and I&C Dept., Steag
Encotec India
59
• A three phase transformer is either in the form
of a three phase unit or in the form of a bank of
three single phase units.
• A single three phase unit is less costly (cost less
by 15%) than a bank of 3 single phase unit.
• Star-Star connection is used for connecting
together two high voltage transmission system
of unequal voltage. In this case it is necessary
that the connection used to be such as not to
cause a shift in phase form primary to
secondary. Therefore only two connections are
applicable, namely, Star – Star and Delta –
Delta.
Arrangements of 3 phase Transformer and
connections
Electrical and I&C Dept., Steag
Encotec India
60
• For high voltage Star – Star connection is
preferred because the voltage stresses of the
winding to the ground with neutral grounded
are only 58% of the voltage stress to ground of
similar units connected delta to delta. When the
star to star connection is used for this purpose a
tertiary winding is provided to suppress the
third harmonic voltages which would otherwise
appear on the system.
Arrangements of 3 phase
Transformer and connections
Electrical and I&C Dept., Steag
Encotec India
61
• The tertiary is a third winding and is often used
in power transformers to provide station power
requirements or tie with synchronous
condenser.
• The disturbances from harmonic voltages and
currents constitute one of the objections to this
use of Star-Star connected transformer.
Another objection in its use is that unbalanced
loads can not be carried on the secondary side
unless the primary neutral or fourth wire is
provided.
Arrangements of 3 phase
Transformer and connections
Electrical and I&C Dept., Steag
Encotec India
62
• Another objection is that it is practically
impossible to construct 3-single phase
units, or even a three phase unit, in which
the magnetizing currents of each of the
three windings are exactly identical. This
makes it impossible to have perfectly
balanced voltages in each of the three
windings of the star – star connection.
Arrangements of 3 phase
Transformer and connections
Electrical and I&C Dept., Steag
Encotec India
63
Harmonics:
• A sinusoidal wave form of current or voltage
consists of only one frequency component
called fundamental. Such a sinusoidal
waveform does not contain harmonics of other
frequencies.
• A non sinusoidal periodic waveform can be
considered to be composed of several sinusoidal
waveforms of fundamental frequencies and
other harmonic frequencies.
• Harmonic currents cause additional I2R loss,
core loss, magnetic interference with protective
relays and interference in communication
circuits. Thus the harmonics should be avoided.
Electrical and I&C Dept., Steag
Encotec India
64
Harmonics:
• Harmonics are caused by high flux densities in
the core of power transformers. If the cross
section of core is insufficient, the core gets
saturated. The operating point is on the non
linear region of the B/H curve. Even if primary
voltage have sinusoidal waveform, the
secondary waveform may be non sinusoidal
because of magnetic core. If the core cross
section is inadequate, core gets saturated and
3rd harmonics are generally present in the
secondary waveform.
• Harmonics are caused by operation of thyristor
controlled devices.
Electrical and I&C Dept., Steag
Encotec India
65
Effect of Transformer connection
on harmonics
• Single phase transformer:
• If core is not saturated, i.e. if operating
point of magnetizing current is in the line
portion of B/H curve, harmonics are not
present. If core saturates, 3rd harmonic
e.m.fs and 3rd harmonic currents
induced on the secondary side.
Electrical and I&C Dept., Steag
Encotec India
66
A) Three phase banks of 3 single phase
transformer:
• The method of connection decides the
harmonic generation
1)Delta-delta connection: Delta connection
provides closed path to 3rd harmonic e.m.f
which circulate 3rd harmonic currents in
closed delta. The 3rd harmonic voltage drop
within the closed delta. As a result on 3rd
harmonic voltages appear at line terminals.
Similar behaviors occur in the Delta-delta
connection for 5th and 7th harmonics.
Effect of Transformer connection
on harmonics
Electrical and I&C Dept., Steag
Encotec India
67
A) Three phase banks of 3 single phase
transformer:
2) Stat-delta connection and Delta-star
connection without neutral wire or neutral
grounding:
3rd harmonic voltages and currents circulate
in closed delta and are absent on line terminal
on delta side however the waveform departs
from true sinusoidal waveform as 3rd
harmonic currents can not circulate on star
side.
Effect of Transformer connection
on harmonics
Electrical and I&C Dept., Steag
Encotec India
68
A) Three phase banks of 3 single phase
transformer:
3) Star-star connection without neutral
earthing:
There is no path for circulation of 3rd
harmonic current the neutral point oscillates.
The line to neutral point voltages of all the 3
phases fluctuate.
Effect of Transformer connection
on harmonics
Electrical and I&C Dept., Steag
Encotec India
69
A) Three phase banks of 3 single phase
transformer:
4) Star-star connection with neutral:
The presence of neutral connection
provides path for 3rd harmonic
compensating currents.
Effect of Transformer connection
on harmonics
Electrical and I&C Dept., Steag
Encotec India
70
B) Three phase transformer units:
• It is desirable to distinguish between the cases
where the phases are magnetically separate,
and those where they are magnetically (as
well as electrically) interlinked. In 3-phase
shell types transformer the magnetic circuit
are separate and do not interact and the
discussion for the 3 bank of 1 phase
transformer will apply.
Effect of Transformer connection
on harmonics
Electrical and I&C Dept., Steag
Encotec India
71
B) Three phase transformer units:
• In the more common 3 phase 3 limb core type unit,
however, this is not so, any 3rd harmonics are all
upward or downward at a given instant in the limbs,
and their return path must be external (i.e. in the air,
oil or the wall of tank). These paths have a high
reluctance and there is a strong tendency to suppress
3rd harmonic core fluxes. The residuals may cause
eddy current loss in the tank, an effect cancelled it a
copper band is fitted around the inside perimeter of the
tank.
• In five limbed cores, the end limbs provide a
magnetic path for third harmonic fluxes.
Effect of Transformer connection
on harmonics
Electrical and I&C Dept., Steag
Encotec India
72
Paralleling of a transformer of group 3
with transformer of group 4
• Group 3 has phase displacement of 30
degree lag, i.e. -30 degree. Group 4 has
phase displacement of 30 degree lead, i.e.
+30 degree. A transformer of group 3 can
be connected in parallel with that of
group 4 by cross connecting any two of
the three external connections on HV
side, without any other changes.
Electrical and I&C Dept., Steag
Encotec India
73
Paralleling of a transformer of group 3
with transformer of group 4
• Alternatively any two LV connections may be
cross connected without other change.
• Thus connect A, B, C of transformer X to
busbars r,y,b and a,b,c of transformer Y to bus
bar R,Y,B.
• Connect a, c, b of transformer X to bus bar
r,y,b and a,b,c of transformer to busbar r,y,b to
adjust the phase displacement difference
between group 3 and group 4.
Electrical and I&C Dept., Steag
Encotec India
74
Paralleling of a transformer of group 1
with transformer of group 2
• Group 1 has zero displacement and
group 2 has 180 degree phase
displacement. For parallel operations,
one of the internal connections of all the
three winding of one of the transformers
on one side only (either HV or LV) is
necessary to be changed. Thus bringing
same phase shift, i.e. zero degrees or 180
degree in both transformers.

More Related Content

What's hot

Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relayCS V
 
Facts static voltage & phase angle regulators
Facts   static voltage & phase angle regulatorsFacts   static voltage & phase angle regulators
Facts static voltage & phase angle regulatorsSITCOE, Yadrav
 
Dc Choppers
Dc ChoppersDc Choppers
Dc Choppersstooty s
 
Three phase-controlled-rectifiers
Three phase-controlled-rectifiersThree phase-controlled-rectifiers
Three phase-controlled-rectifiersTejas Deshpande
 
Solid state transformer ppt
Solid state transformer pptSolid state transformer ppt
Solid state transformer pptAKHILASS
 
Control of hvdc system
Control of hvdc systemControl of hvdc system
Control of hvdc systemAazim Rasool
 
Active, reactive and apparent power
Active, reactive and apparent powerActive, reactive and apparent power
Active, reactive and apparent powerSourabh sharma
 
DC potentiometers
DC potentiometersDC potentiometers
DC potentiometerstadi1padma
 
PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:Duddu Rajesh
 
Introduction to electrical circuits
Introduction to electrical circuitsIntroduction to electrical circuits
Introduction to electrical circuitsVenu Gopal Reddy
 
Power quality notes unit 1
Power quality notes unit  1 Power quality notes unit  1
Power quality notes unit 1 Dilip kumar
 
Power electronic converter in wind turbine.1.
Power electronic converter in wind turbine.1.Power electronic converter in wind turbine.1.
Power electronic converter in wind turbine.1.SonuKumarBairwa
 
Principles of power systems v. k. mehta and r. mehta
Principles of power systems v. k. mehta and r. mehtaPrinciples of power systems v. k. mehta and r. mehta
Principles of power systems v. k. mehta and r. mehtaManoj Chowdary
 

What's hot (20)

FACT devices
FACT devicesFACT devices
FACT devices
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Facts static voltage & phase angle regulators
Facts   static voltage & phase angle regulatorsFacts   static voltage & phase angle regulators
Facts static voltage & phase angle regulators
 
UPQC ppt main
UPQC ppt mainUPQC ppt main
UPQC ppt main
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Dc Choppers
Dc ChoppersDc Choppers
Dc Choppers
 
Three phase-controlled-rectifiers
Three phase-controlled-rectifiersThree phase-controlled-rectifiers
Three phase-controlled-rectifiers
 
Solid state transformer ppt
Solid state transformer pptSolid state transformer ppt
Solid state transformer ppt
 
Two Quadrant chopper
Two Quadrant chopperTwo Quadrant chopper
Two Quadrant chopper
 
Dc machines2
Dc machines2Dc machines2
Dc machines2
 
Control of hvdc system
Control of hvdc systemControl of hvdc system
Control of hvdc system
 
Active, reactive and apparent power
Active, reactive and apparent powerActive, reactive and apparent power
Active, reactive and apparent power
 
DC potentiometers
DC potentiometersDC potentiometers
DC potentiometers
 
PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:PERFORMANCE OF TRANSMISSION LINES:
PERFORMANCE OF TRANSMISSION LINES:
 
Introduction to electrical circuits
Introduction to electrical circuitsIntroduction to electrical circuits
Introduction to electrical circuits
 
DC DC Converter
DC DC ConverterDC DC Converter
DC DC Converter
 
Overcurrent Protection
Overcurrent ProtectionOvercurrent Protection
Overcurrent Protection
 
Power quality notes unit 1
Power quality notes unit  1 Power quality notes unit  1
Power quality notes unit 1
 
Power electronic converter in wind turbine.1.
Power electronic converter in wind turbine.1.Power electronic converter in wind turbine.1.
Power electronic converter in wind turbine.1.
 
Principles of power systems v. k. mehta and r. mehta
Principles of power systems v. k. mehta and r. mehtaPrinciples of power systems v. k. mehta and r. mehta
Principles of power systems v. k. mehta and r. mehta
 

Similar to 332038674-Vector-Group-of-Transformers.ppt

Diode Applications & Transistor Basics
Diode Applications & Transistor BasicsDiode Applications & Transistor Basics
Diode Applications & Transistor BasicsA B Shinde
 
Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...
Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...
Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...IRJET Journal
 
Electronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. KawareElectronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. KawareProf. Swapnil V. Kaware
 
Improved High Gain Dc-Dc Converter with Reduced Noise
Improved High Gain Dc-Dc Converter with Reduced NoiseImproved High Gain Dc-Dc Converter with Reduced Noise
Improved High Gain Dc-Dc Converter with Reduced NoiseIRJET Journal
 
Performance Comparison of Multi Input Capacitor Converter Circuits
Performance Comparison of Multi Input Capacitor Converter CircuitsPerformance Comparison of Multi Input Capacitor Converter Circuits
Performance Comparison of Multi Input Capacitor Converter CircuitsIJECEIAES
 
IRJET- Comparative Analysis for Power Quality Improvenment of Cascaded an...
IRJET-  	  Comparative Analysis for Power Quality Improvenment of Cascaded an...IRJET-  	  Comparative Analysis for Power Quality Improvenment of Cascaded an...
IRJET- Comparative Analysis for Power Quality Improvenment of Cascaded an...IRJET Journal
 
IRJET- A Comparative Study of Multilevel Inverter Topologies
IRJET- A Comparative Study of Multilevel Inverter TopologiesIRJET- A Comparative Study of Multilevel Inverter Topologies
IRJET- A Comparative Study of Multilevel Inverter TopologiesIRJET Journal
 
A Single Switch High Gain Coupled Inductor Boost Converter
A Single Switch High Gain Coupled Inductor Boost ConverterA Single Switch High Gain Coupled Inductor Boost Converter
A Single Switch High Gain Coupled Inductor Boost ConverterIRJET Journal
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Hybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic ApplicationHybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic ApplicationPremier Publishers
 
Microelectronic circuits and devices: chapter one
Microelectronic circuits and devices: chapter oneMicroelectronic circuits and devices: chapter one
Microelectronic circuits and devices: chapter onemuhabaw amare
 
A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...
A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...
A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...IDES Editor
 
Switched Inductor Based Buck-Boost Transformerless Inverter
Switched Inductor Based Buck-Boost Transformerless InverterSwitched Inductor Based Buck-Boost Transformerless Inverter
Switched Inductor Based Buck-Boost Transformerless InverterIRJET Journal
 

Similar to 332038674-Vector-Group-of-Transformers.ppt (20)

Diode Applications & Transistor Basics
Diode Applications & Transistor BasicsDiode Applications & Transistor Basics
Diode Applications & Transistor Basics
 
207137236 ee2207-lm
207137236 ee2207-lm207137236 ee2207-lm
207137236 ee2207-lm
 
Evandro lab 4
Evandro lab 4Evandro lab 4
Evandro lab 4
 
Evandro lab 4
Evandro lab 4Evandro lab 4
Evandro lab 4
 
Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...
Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...
Multi Pulse Rectifier Using Different Phase Shifting Transformers and its THD...
 
D05432435
D05432435D05432435
D05432435
 
Lecture Two.pptx
Lecture Two.pptxLecture Two.pptx
Lecture Two.pptx
 
Electronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. KawareElectronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. Kaware
 
Improved High Gain Dc-Dc Converter with Reduced Noise
Improved High Gain Dc-Dc Converter with Reduced NoiseImproved High Gain Dc-Dc Converter with Reduced Noise
Improved High Gain Dc-Dc Converter with Reduced Noise
 
Performance Comparison of Multi Input Capacitor Converter Circuits
Performance Comparison of Multi Input Capacitor Converter CircuitsPerformance Comparison of Multi Input Capacitor Converter Circuits
Performance Comparison of Multi Input Capacitor Converter Circuits
 
IRJET- Comparative Analysis for Power Quality Improvenment of Cascaded an...
IRJET-  	  Comparative Analysis for Power Quality Improvenment of Cascaded an...IRJET-  	  Comparative Analysis for Power Quality Improvenment of Cascaded an...
IRJET- Comparative Analysis for Power Quality Improvenment of Cascaded an...
 
IRJET- A Comparative Study of Multilevel Inverter Topologies
IRJET- A Comparative Study of Multilevel Inverter TopologiesIRJET- A Comparative Study of Multilevel Inverter Topologies
IRJET- A Comparative Study of Multilevel Inverter Topologies
 
A Single Switch High Gain Coupled Inductor Boost Converter
A Single Switch High Gain Coupled Inductor Boost ConverterA Single Switch High Gain Coupled Inductor Boost Converter
A Single Switch High Gain Coupled Inductor Boost Converter
 
Ade manual final
Ade manual finalAde manual final
Ade manual final
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Hybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic ApplicationHybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic Application
 
Microelectronic circuits and devices: chapter one
Microelectronic circuits and devices: chapter oneMicroelectronic circuits and devices: chapter one
Microelectronic circuits and devices: chapter one
 
A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...
A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...
A Single-Stage High-Frequency Isolated Secondary- Side Controlled AC-DC Conve...
 
Chapter02
Chapter02Chapter02
Chapter02
 
Switched Inductor Based Buck-Boost Transformerless Inverter
Switched Inductor Based Buck-Boost Transformerless InverterSwitched Inductor Based Buck-Boost Transformerless Inverter
Switched Inductor Based Buck-Boost Transformerless Inverter
 

More from Satish Pydimarla

Testing_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptTesting_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptSatish Pydimarla
 
Zaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptZaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptSatish Pydimarla
 
transformerprotection-180102061059.pdf
transformerprotection-180102061059.pdftransformerprotection-180102061059.pdf
transformerprotection-180102061059.pdfSatish Pydimarla
 
3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptxSatish Pydimarla
 
Presentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxPresentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxSatish Pydimarla
 
understandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxunderstandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxSatish Pydimarla
 
transformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxtransformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxSatish Pydimarla
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation TransformersSatish Pydimarla
 
Understanding_lightning_protection.pptx
Understanding_lightning_protection.pptxUnderstanding_lightning_protection.pptx
Understanding_lightning_protection.pptxSatish Pydimarla
 
Construction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxConstruction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxSatish Pydimarla
 
high-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptxhigh-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptxSatish Pydimarla
 

More from Satish Pydimarla (20)

9310091.ppt
9310091.ppt9310091.ppt
9310091.ppt
 
control room.pptx
control room.pptxcontrol room.pptx
control room.pptx
 
Thermovision Test.ppt
Thermovision Test.pptThermovision Test.ppt
Thermovision Test.ppt
 
4143813.ppt
4143813.ppt4143813.ppt
4143813.ppt
 
Transformer_theory.pptx
Transformer_theory.pptxTransformer_theory.pptx
Transformer_theory.pptx
 
Testing_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.pptTesting_of_transformers_adjusted.ppt
Testing_of_transformers_adjusted.ppt
 
Zaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.pptZaragoza Factory_Our product_ EN.ppt
Zaragoza Factory_Our product_ EN.ppt
 
transformerprotection-180102061059.pdf
transformerprotection-180102061059.pdftransformerprotection-180102061059.pdf
transformerprotection-180102061059.pdf
 
3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx3-Phase-Transformer (1).pptx
3-Phase-Transformer (1).pptx
 
Electrical_Engg_Basic.PPT
Electrical_Engg_Basic.PPTElectrical_Engg_Basic.PPT
Electrical_Engg_Basic.PPT
 
Presentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptxPresentation-Kalinga Stadium.pptx
Presentation-Kalinga Stadium.pptx
 
understandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptxunderstandingtransformervectorgroup-180629014651.pptx
understandingtransformervectorgroup-180629014651.pptx
 
transformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptxtransformeronno-load-200825063948.pptx
transformeronno-load-200825063948.pptx
 
tcee-161003100321.pptx
tcee-161003100321.pptxtcee-161003100321.pptx
tcee-161003100321.pptx
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation Transformers
 
Understanding_lightning_protection.pptx
Understanding_lightning_protection.pptxUnderstanding_lightning_protection.pptx
Understanding_lightning_protection.pptx
 
Understanding VCB.pptx
Understanding VCB.pptxUnderstanding VCB.pptx
Understanding VCB.pptx
 
CT & PT.pptx
CT & PT.pptxCT & PT.pptx
CT & PT.pptx
 
Construction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptxConstruction of HV Transmission Lines etc.pptx
Construction of HV Transmission Lines etc.pptx
 
high-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptxhigh-voltage-dc-transmission-hvdc PKP.pptx
high-voltage-dc-transmission-hvdc PKP.pptx
 

Recently uploaded

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 

Recently uploaded (20)

9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 

332038674-Vector-Group-of-Transformers.ppt

  • 1. Electrical and I&C Dept., Steag Encotec India 1 Presented By: Vinod J. Patel To Vector groups of Transformer Training on
  • 2. Electrical and I&C Dept., Steag Encotec India 2 Introduction to Vector Group • The vector group marks the circuitry of windings and their phase position to each other. It consists of a capital and small letter plus a code number. The capital letter A, B, C refers to the HV winding and the lower case a, b, c to the LV winding with (A), (B), (C) for a tertiary winding, where provided. Neutral terminals precede line terminals.
  • 3. Electrical and I&C Dept., Steag Encotec India 3 Introduction to Vector Group • Each winding has two ends designated by the subscript numbers 1, 2, or if there are intermediary tapings (or there are sections of the same winding) these are numbered in order to their separation from end 1. The most common vector groups are summarized alongside, input left-hand, output right-hand. Unless otherwise requested.
  • 4. Electrical and I&C Dept., Steag Encotec India 4 Requirement of Vector Group • In 3 phase transformers polarity alone is insufficient to represent the relation between HV and LV windings. In addition to the terminal marking on HV and LV side voltage vector diagram are required to show the angular displacement between HV and LV winding. Vector group is necessary to indicate the terminal marking and the phase displacement between primary and secondary voltages or currents.
  • 5. Electrical and I&C Dept., Steag Encotec India 5 Under normal condition the line to line voltages on HV side are displaced from corresponding voltages on LV sides. Also line to neutral voltage on HV side are displaced from corresponding voltages on LV side. The displacement depend upon the transformer connections. As per IS 2026- 1972, there are four vector groups of standard connections Requirement of Vector Group
  • 6. Electrical and I&C Dept., Steag Encotec India 6 Phase shifts in Star Delta Transformers • Positive & Negative phase sequence voltages and currents undergo a phase shift in passing through a star-delta transformer which depends on labeling of terminals. • Before considering the phase shift, we need to discuss the standard polarity marking of a single phase transformer as shown in the figure-1. The transformer ends marked with a dot have the same polarity. Therefore, voltage VHH' is in phase with voltage VLL'.
  • 7. Electrical and I&C Dept., Steag Encotec India 7 VHH' H H' VLL' L L' I1 I2 Figure-1 Polarity Marking of a single phase transformer
  • 8. Electrical and I&C Dept., Steag Encotec India 8 • Consider now a star/delta transformer with terminal labeling as indicated in Figure-2. Windings shown parallel to each other are magnetically coupled. Assume that the transformer is excited with positive sequence voltages and carries positive sequence currents. With the polarity mark shown, we can immediately draw the phasor diagram of Figure-3. Phase shifts in Star Delta Transformers
  • 9. Electrical and I&C Dept., Steag Encotec India 9 • The following relatdionship between the voltages on two sides of the transformer is observed from the phasor diagram. Positive sequence line voltages on star side lead the corresponding voltages on the delta side by 30 deg. The same also applies for the line currents. Phase shifts in Star Delta Transformers
  • 10. Electrical and I&C Dept., Steag Encotec India 10 A B C N a c b Star side quantities lead delta side quantity by 30 deg. Figure-2 Star Delta Transformation
  • 11. Electrical and I&C Dept., Steag Encotec India 11 VAB1 VBC1 VCA1 VCN1 VAN1 VBN1 Vab1 Vca1 Vbc1 30 deg. Positive Sequence Voltage on a Star / Dleta Transformer Figure-3 Phasor diagram of star-delta Transformer
  • 12. Electrical and I&C Dept., Steag Encotec India 12 • If the delta side is connected as shown in Figure-4 the phase shift reverses; the delta side quantities lead the star side quantity by 30 deg. A B C N c b a Delta side quantities lead Star side quantity by 30 deg. Figure-4 Star Delta Transformation
  • 13. Electrical and I&C Dept., Steag Encotec India 13 • Instead if the transformer of Figure-2 is now excited by negative phase sequence voltages & currents, the voltage phasor diagram will be as shown in Figure-5. VAB2 VCA2 VBC2 VBN2 VAN2 VCN2 Vab2 Vbc2 Vca2 30 deg. Negative Sequence Voltage on a Star / Dleta Transformer Figure-5 Star Delta Transformation
  • 14. Electrical and I&C Dept., Steag Encotec India 14 • The phase shift in comparison to positive sequence case now reverses, i.e. the star side quantities lag the delta side quantities by 30 deg. The result for figure- 4 also correspondingly reverses. Star Delta Transformation
  • 15. Electrical and I&C Dept., Steag Encotec India 15 • It is assumed that a star/delta transformer is so labeled that the positive sequence quantities on the HV side lead their corresponding positive sequence quantities on the LV side by 30 deg. The reverse is the case of negative sequence quantities wherein HV quantities lag the corresponding LV quantities by 30 deg. Star Delta Transformation
  • 16. Electrical and I&C Dept., Steag Encotec India 16 • The interconnection of the phase windings to give a three phase, three-or four wire supply provides three alternative modes of connection (1) Mesh or Delta (2) Star (3) Zig-zag Each of these can be achieved in two ways. For Example a star Connection may be had by joining together A1, B1 and C1, to form the neutral and using A2, B2 and C2 as line terminals. Alternatively A2, B2 and C2 may be joined to give neutral and A1, B1 and C1 may be used as line terminals. Star Delta Transformation
  • 17. Electrical and I&C Dept., Steag Encotec India 17 • Since primary and secondary can be treated in either of these ways, at least twelve methods of connection are possible. These are arranged in four main groups, as given below, according to the phase displacement which exists between the line voltages on the two sides of the transformer. Star Delta Transformation
  • 18. Electrical and I&C Dept., Steag Encotec India 18 Vector Groups (Group-1) • Group 1: Zero phase displacement (Yy0, Dd0, Dz0) 1) Yy0: Star – Star Connection 2) Dd0: Delta – Delta Connection 3) Dz0: Delta – Zig-zag Connection
  • 19. Electrical and I&C Dept., Steag Encotec India 19 Yy0: Star – Star Connection
  • 20. Electrical and I&C Dept., Steag Encotec India 20 Dd0: Delta – Delta Connection
  • 21. Electrical and I&C Dept., Steag Encotec India 21 Dz0: Delta – Zig-zag Connection
  • 22. Electrical and I&C Dept., Steag Encotec India 22 • Group 2: 180 degree phase displacement (Yy6, Dd6, Dz6) 1) Yy6: Star – Star Connection 2) Dd6: Delta – Delta Connection 3) Dz6: Delta – Zig-zag Connection Vector Groups (Group-2)
  • 23. Electrical and I&C Dept., Steag Encotec India 23 Yy6: Star – Star Connection
  • 24. Electrical and I&C Dept., Steag Encotec India 24 Dd6: Delta – Delta Connection
  • 25. Electrical and I&C Dept., Steag Encotec India 25 Dz6: Delta – Zig-zag Connection
  • 26. Electrical and I&C Dept., Steag Encotec India 26 • Group 3: 30 degree lag phase displacement (Dy1, Yd1, Yz1) 1) Dy1: Delta – Star Connection 2) Yd1: Star – Delta Connection 3) Yz1: Star – Zig-zag Connection Vector Groups (Group-3)
  • 27. Electrical and I&C Dept., Steag Encotec India 27 Dy1: Delta – Star Connection
  • 28. Electrical and I&C Dept., Steag Encotec India 28 Yd1: Star – Delta Connection
  • 29. Electrical and I&C Dept., Steag Encotec India 29 Yz1: Star – Zig-zag Connection
  • 30. Electrical and I&C Dept., Steag Encotec India 30 • Group 4: 30 degree lead phase displacement (Dy11, Yd11, Yz11) 1) Dy11: Delta – Star Connection 2) Yd11: Star – Delta Connection 3) Yz11: Star – Zig-zag Connection Vector Groups (Group-4)
  • 31. Electrical and I&C Dept., Steag Encotec India 31 Dy11: Delta – Star Connection
  • 32. Electrical and I&C Dept., Steag Encotec India 32 Yd11: Star – Delta Connection
  • 33. Electrical and I&C Dept., Steag Encotec India 33 Yz11: Star – Zig-zag Connection
  • 34. Electrical and I&C Dept., Steag Encotec India 34 Symbol Description • Phase displacement zero = 0 • Phase displacement 180 degree = 6 • Phase displacement 30 degree lag = 1 • Phase displacement 30 degree lead = 11 • Letter Y represents star connected HV • Letter y represents star connected LV • Letter D represents delta connected HV • Letter d represents delta connected LV • Letter Z represents star connected zig-zag
  • 35. Electrical and I&C Dept., Steag Encotec India 35 • The most popular method of connecting transformer is the delta-star connections (4, Dy11). The connection diagram illustrates the relative position of the terminals in the terminal box and the internal connections that are made. The HV winding is connected to a 3-wire supply, of phase sequence A, B, C, and at the instant chosen the potential of A is at its maximum positive value. Thus the line voltages on the HV side will form an equilateral triangle. Description of Dy11
  • 36. Electrical and I&C Dept., Steag Encotec India 36 • The line terminals are A2, B2 and C2 and the corners of the triangles are so marked. It is to be noted that phase A of the transformer lies between A2 and B2, Phase B between B2 and C2 and phase C between C2 and A2 owing to internal connections used. Description of Dy11
  • 37. Electrical and I&C Dept., Steag Encotec India 37 • From the phasor diagrams of induced voltages for HV and LV sides it is observed that the voltage of the HV line A2 is at the maximum value, the LV line a2 has been advanced 30 degree. In fact the transformer connections have produced this displacement of 30 degree for all lines. Description of Dy11
  • 38. Electrical and I&C Dept., Steag Encotec India 38 • All the other methods of connections in the same main group no. 4 gives a similar 30 degree advance which is the basis of classification. • With group no. 1 there is no phase displacement but the group no. 2 gives the phase displacement of 180 degree. Group no. 3 cause the LV line voltage to lag by 30 degree. • For parallel operation of transformers the essential requirement is that the transformer connections belong to the same main group. Description of Vector Groups
  • 39. Electrical and I&C Dept., Steag Encotec India 39 • It is possible to obtain any desired phase shift with a three phase transformer if the primary and / secondary windings are divided into a sufficient number of sections. The Zig-Zag connection is one example of a sectionalized winding. Description of Vector Groups
  • 40. Electrical and I&C Dept., Steag Encotec India 40 • 15 percent more turns are required for a given total voltage per phase compared with a normal phase connection in Zig-zag winding, which may increase in the frame size for the given rating. • Nevertheless, the advantages of zig-zag arrangement may offset the cost; unbalanced loads on the secondary side are distributed better on the primary side. • The zig-zag / star connection has been employed where delta connections were mechanically weak (on account of large number of turns and small copper sections) in HV transformers. Description of Vector Groups
  • 41. Electrical and I&C Dept., Steag Encotec India 41 • In star connection with earthed neutral the maximum voltage of the phase winding to ground is 1/V3 (or 57.7%) of the line voltage, while in delta connection this is equal to the line voltage in case of earthing of one of the line during a fault. Therefore, Phase voltage, turns and insulation are less in star connection than those in delta connection and for very high voltage transformers the star connection on HV side is about 10% cheaper than delta connection. Choice between Star and Delta connection
  • 42. Electrical and I&C Dept., Steag Encotec India 42 • A delta connected primary is necessary for a star connected LV secondary feeding mixed three phase and single phase loads. In case of unbalanced single phase loads on secondary, delta connected primary is necessitated to permit the flow of zero sequence current I0= In/3 = 1/3 (IA + IB + IC) so that IA + IB + IC = 0. • This means that only positive and negative sequence current flows in the lines on the delta side. Choice between Star and Delta connection
  • 43. Electrical and I&C Dept., Steag Encotec India 43 • This could also be achieved by star connected primary provided the primary and secondary star points are earthed, but this is not recommended because of flow of ground current for unbalanced secondary loads. Choice between Star and Delta connection
  • 44. Electrical and I&C Dept., Steag Encotec India 44 Choice of Transformer connections: (A) Star-Star (Yy0 or Yy6) connections: This type of transformer is most economical for small current and high voltage transformers. The advantages and disadvantages of such arrangement are as under.
  • 45. Electrical and I&C Dept., Steag Encotec India 45 Star-Star (Yy0 or Yy6) connections • Advantages: • The number of turns per phase and the amount of insulation is minimum because phase voltage = 1/V3 of line voltage. • There is no phase displacement between primary and secondary voltages. • With star point available on both sides it is possible to provide neutral connection. • Economical for small HV transformer.
  • 46. Electrical and I&C Dept., Steag Encotec India 46 Star-Star (Yy0 or Yy6) connections • Disadvantages: • If the load on secondary side of transformer is unbalanced, the phase voltages of load side change unless the load star point is earthed. The difficulty of shifting neutral can be overcome by connecting the primary star point to the star point of the Generator. • The primary of the transformer draws a magnetizing current which has third and fifth harmonics. If neutral of primary is not connected to neutral of Generator, the third and fifth harmonics current can not flow hence the flux in the core can not be sinusoidal wave and, therefore, the voltages will be distorted. By connecting the primary neutral to Generator neutral, the path for return of these third and fifth harmonics current is provided and, therefore, the trouble of distortion of voltage is overcome.
  • 47. Electrical and I&C Dept., Steag Encotec India 47 Star-Star (Yy0 or Yy6) connections • Disadvantages: • Even if neutral of primary is connected to neutral of Generator or earthed, still the third harmonic is present in the alternator voltage form, it will appear on secondary side. Though the secondary line voltages do not contain third harmonic voltage; but third harmonic voltages are additive in the neutral and cause the current in the neutral of triple frequency ( 3rd harmonic) which will cause interference to the nearby communication system. • Third harmonic voltages may be high in shell type 3 phase transformers.
  • 48. Electrical and I&C Dept., Steag Encotec India 48 Delta-Delta (Dd0 or Dd6) connections • This arrangement is generally used in system which carry large current or low voltages and especially when continuity of service must be maintained even though one of the phase develops fault. When one of the phase is removed in delta-delta connected transformers, operation continues on what is known as open delta. By being operated in this way , the transformer delivers three phase currents and voltages in their correct phase relationship but the capacity of the transformer is reduced to 57.7% of what it was all three phase winding sound.
  • 49. Electrical and I&C Dept., Steag Encotec India 49 Delta-Delta (Dd0 or Dd6) connections • Advantages: • There is no phase displacement between the primary and secondary voltages. • There is no distortion of flux, because the third harmonic component of magnetizing current can flow in delta connected primary winding without flowing in the line wires.
  • 50. Electrical and I&C Dept., Steag Encotec India 50 Delta-Delta (Dd0 or Dd6) connections • Advantages: • The cross section of conductor is reduced because the phase currents is 1/V3 times of the line current. • No difficulty is experienced due to unbalancing of loads on secondary side. • Suitable for large HV transformers • Large load unbalance can be tolerated, 3rd harmonic voltages are damped out.
  • 51. Electrical and I&C Dept., Steag Encotec India 51 Delta-Delta (Dd0 or Dd6) connections • Disadvantages: • More insulation is required in comparison to star-star connections. • The absence of star point may be disadvantageous. If one line gets earthed due to fault, maximum voltage between windings and core will be full line voltage.
  • 52. Electrical and I&C Dept., Steag Encotec India 52 Star-Delta (Yd1 or Yd11) connections This type of transformer connection is used principally where the voltage is to be stepped down as, for example, at the end of a transmission line. In this type of connection of transformers the neutral of the primary winding is earthed. In this system line voltage ratio is 1/V3 times of transformer turn ratio and secondary line voltages have a phase shift of +/- 30 degree with respect to primary line voltages.
  • 53. Electrical and I&C Dept., Steag Encotec India 53 Star-Delta (Yd1 or Yd11) connections On the HV side of the transformer, insulation is stressed only to the extent of 57.7% of the line voltage and, therefore, there is some saving in the cost of insulation. Very common for supply networks. One star point for a neutral to serve mixed 1 phase and 3 phase loads.
  • 54. Electrical and I&C Dept., Steag Encotec India 54 Delta-Star (Dy1 or Dy11) connections This scheme of connection is generally used where it is necessary to step up the voltage as for example, at the beginning of a HT transmission system. On the high voltage side of the transformer, insulation is stressed only to the extent of 57.7% of line to line voltage. Another advantage is that the neutral point is stable and will not float when load is unbalanced. There is no distortion of flux because the existence of a delta connection allows a path for the 3rd harmonic currents.
  • 55. Electrical and I&C Dept., Steag Encotec India 55 Delta-Star (Dy1 or Dy11) connections In this scheme of connection the line voltage ratio is V3 times of transformer turn ratio and the secondary line voltage have a phase shit of +/- 30 degree with respect to primary line voltages.
  • 56. Electrical and I&C Dept., Steag Encotec India 56 Delta-Star (Dy1 or Dy11) connections The neutral of the secondary is grounded to provide 3-phase, 4-wire system and this scheme of connection is widely used in distribution system because it can be used to serve both the three phase power equipment and single phase lighting circuits. In such case the 11,000 / 400 V transformer connections provide a four wire secondary, with neutral supplying the 4th wire. The three phase equipment is connected to the line wires to operate at 400V while the lighting equipment is connected between one of the line wires and neutral to operate at 230 Volts.
  • 57. Electrical and I&C Dept., Steag Encotec India 57 Delta-Star (Dy1 or Dy11) connections • Used for distribution transformer. Star side is used on load side. • Star-Delta or Delta-Star connected transformers can not be operated in parallel with star-star or delta-delta connected transformer even though the voltage ratio are correctly adjusted as there will be a 30 degree phase difference between corresponding voltages on the secondary sides.
  • 58. Electrical and I&C Dept., Steag Encotec India 58 Interconnected star/star (Zig-Zag) • Reduces 3rd harmonic voltages and not sensitive to condition of unbalanced loading. • Restricted to low voltage windings. • Phase voltages are composed of half voltages with 60 degree displacement, 15% more turns are required. • Some times used in rectifier supply.
  • 59. Electrical and I&C Dept., Steag Encotec India 59 • A three phase transformer is either in the form of a three phase unit or in the form of a bank of three single phase units. • A single three phase unit is less costly (cost less by 15%) than a bank of 3 single phase unit. • Star-Star connection is used for connecting together two high voltage transmission system of unequal voltage. In this case it is necessary that the connection used to be such as not to cause a shift in phase form primary to secondary. Therefore only two connections are applicable, namely, Star – Star and Delta – Delta. Arrangements of 3 phase Transformer and connections
  • 60. Electrical and I&C Dept., Steag Encotec India 60 • For high voltage Star – Star connection is preferred because the voltage stresses of the winding to the ground with neutral grounded are only 58% of the voltage stress to ground of similar units connected delta to delta. When the star to star connection is used for this purpose a tertiary winding is provided to suppress the third harmonic voltages which would otherwise appear on the system. Arrangements of 3 phase Transformer and connections
  • 61. Electrical and I&C Dept., Steag Encotec India 61 • The tertiary is a third winding and is often used in power transformers to provide station power requirements or tie with synchronous condenser. • The disturbances from harmonic voltages and currents constitute one of the objections to this use of Star-Star connected transformer. Another objection in its use is that unbalanced loads can not be carried on the secondary side unless the primary neutral or fourth wire is provided. Arrangements of 3 phase Transformer and connections
  • 62. Electrical and I&C Dept., Steag Encotec India 62 • Another objection is that it is practically impossible to construct 3-single phase units, or even a three phase unit, in which the magnetizing currents of each of the three windings are exactly identical. This makes it impossible to have perfectly balanced voltages in each of the three windings of the star – star connection. Arrangements of 3 phase Transformer and connections
  • 63. Electrical and I&C Dept., Steag Encotec India 63 Harmonics: • A sinusoidal wave form of current or voltage consists of only one frequency component called fundamental. Such a sinusoidal waveform does not contain harmonics of other frequencies. • A non sinusoidal periodic waveform can be considered to be composed of several sinusoidal waveforms of fundamental frequencies and other harmonic frequencies. • Harmonic currents cause additional I2R loss, core loss, magnetic interference with protective relays and interference in communication circuits. Thus the harmonics should be avoided.
  • 64. Electrical and I&C Dept., Steag Encotec India 64 Harmonics: • Harmonics are caused by high flux densities in the core of power transformers. If the cross section of core is insufficient, the core gets saturated. The operating point is on the non linear region of the B/H curve. Even if primary voltage have sinusoidal waveform, the secondary waveform may be non sinusoidal because of magnetic core. If the core cross section is inadequate, core gets saturated and 3rd harmonics are generally present in the secondary waveform. • Harmonics are caused by operation of thyristor controlled devices.
  • 65. Electrical and I&C Dept., Steag Encotec India 65 Effect of Transformer connection on harmonics • Single phase transformer: • If core is not saturated, i.e. if operating point of magnetizing current is in the line portion of B/H curve, harmonics are not present. If core saturates, 3rd harmonic e.m.fs and 3rd harmonic currents induced on the secondary side.
  • 66. Electrical and I&C Dept., Steag Encotec India 66 A) Three phase banks of 3 single phase transformer: • The method of connection decides the harmonic generation 1)Delta-delta connection: Delta connection provides closed path to 3rd harmonic e.m.f which circulate 3rd harmonic currents in closed delta. The 3rd harmonic voltage drop within the closed delta. As a result on 3rd harmonic voltages appear at line terminals. Similar behaviors occur in the Delta-delta connection for 5th and 7th harmonics. Effect of Transformer connection on harmonics
  • 67. Electrical and I&C Dept., Steag Encotec India 67 A) Three phase banks of 3 single phase transformer: 2) Stat-delta connection and Delta-star connection without neutral wire or neutral grounding: 3rd harmonic voltages and currents circulate in closed delta and are absent on line terminal on delta side however the waveform departs from true sinusoidal waveform as 3rd harmonic currents can not circulate on star side. Effect of Transformer connection on harmonics
  • 68. Electrical and I&C Dept., Steag Encotec India 68 A) Three phase banks of 3 single phase transformer: 3) Star-star connection without neutral earthing: There is no path for circulation of 3rd harmonic current the neutral point oscillates. The line to neutral point voltages of all the 3 phases fluctuate. Effect of Transformer connection on harmonics
  • 69. Electrical and I&C Dept., Steag Encotec India 69 A) Three phase banks of 3 single phase transformer: 4) Star-star connection with neutral: The presence of neutral connection provides path for 3rd harmonic compensating currents. Effect of Transformer connection on harmonics
  • 70. Electrical and I&C Dept., Steag Encotec India 70 B) Three phase transformer units: • It is desirable to distinguish between the cases where the phases are magnetically separate, and those where they are magnetically (as well as electrically) interlinked. In 3-phase shell types transformer the magnetic circuit are separate and do not interact and the discussion for the 3 bank of 1 phase transformer will apply. Effect of Transformer connection on harmonics
  • 71. Electrical and I&C Dept., Steag Encotec India 71 B) Three phase transformer units: • In the more common 3 phase 3 limb core type unit, however, this is not so, any 3rd harmonics are all upward or downward at a given instant in the limbs, and their return path must be external (i.e. in the air, oil or the wall of tank). These paths have a high reluctance and there is a strong tendency to suppress 3rd harmonic core fluxes. The residuals may cause eddy current loss in the tank, an effect cancelled it a copper band is fitted around the inside perimeter of the tank. • In five limbed cores, the end limbs provide a magnetic path for third harmonic fluxes. Effect of Transformer connection on harmonics
  • 72. Electrical and I&C Dept., Steag Encotec India 72 Paralleling of a transformer of group 3 with transformer of group 4 • Group 3 has phase displacement of 30 degree lag, i.e. -30 degree. Group 4 has phase displacement of 30 degree lead, i.e. +30 degree. A transformer of group 3 can be connected in parallel with that of group 4 by cross connecting any two of the three external connections on HV side, without any other changes.
  • 73. Electrical and I&C Dept., Steag Encotec India 73 Paralleling of a transformer of group 3 with transformer of group 4 • Alternatively any two LV connections may be cross connected without other change. • Thus connect A, B, C of transformer X to busbars r,y,b and a,b,c of transformer Y to bus bar R,Y,B. • Connect a, c, b of transformer X to bus bar r,y,b and a,b,c of transformer to busbar r,y,b to adjust the phase displacement difference between group 3 and group 4.
  • 74. Electrical and I&C Dept., Steag Encotec India 74 Paralleling of a transformer of group 1 with transformer of group 2 • Group 1 has zero displacement and group 2 has 180 degree phase displacement. For parallel operations, one of the internal connections of all the three winding of one of the transformers on one side only (either HV or LV) is necessary to be changed. Thus bringing same phase shift, i.e. zero degrees or 180 degree in both transformers.