BAZIAN STEAL FACTORY
S/S 132/11kV, 1x30/40MVA
EARTHING SYSTEM CALCULATION
Kurdistan Region
Sulaimani
May 2011
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 2 
Contents:
1. Introduction............................................................................................................. 3
2. List of references and symbols............................................................................... 4
2.1 List of references............................................................................................... 4
2.2 List of symbols................................................................................................... 4
3. Soil resistivity measurements ................................................................................. 5
4. Earthing Calculation Details to IEEE Std. 80-2000 ................................................. 6
4.1. Grid Conductor Sizing...................................................................................... 6
4.2. Calculation od current flowing between ground grid and earth ........................ 6
4.3. Tolerable Step and Touch Voltages................................................................. 7
4.3.1. Reduction Factor Due to Resistivity of Crush Rock Surface...................... 7
4.3.2. Touch and Step Voltage Criteria................................................................ 8
5. Principal results of the CDEGS software calculations .......................................... 10
5.1 Resistance of Electrode System (See Appendix 7)......................................... 10
5.2 Maximaum value od Grand Potential Rise GPR (See Appendices 7 and 15). 10
5.3 Touch voltage (See Appendix 8)..................................................................... 10
5.4 Step Voltage (See Appendix 8)....................................................................... 10
6. Appendices........................................................................................................... 11
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 3 
1. Introduction
The project of earthing system is prepared in accordance with the requirements of
the investor and Standard: IEEE 80 –2000 Guide for Safety in Substation Grounding.
Specific resistance is calculated on the basis of measured values of soil resistivity.
The earthing system is designed so that the allowable touch and step voltages do not
be exceeded.
The calculation is done using the software CDEG MultiGround TM SES - Safe
Engineering Services & technologies ltd. Canada whose results are shown in
Appendices.
The result shows that the touch and step voltages are within the permissible limits.
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 4 
2. List of references and symbols
2.1 List of references
[1] IEEE Std 80-2000
IEEE Guide for Safety in AC Substation Grounding
[2] CDEG Software Package, 1998
Current Distribution, Electromagnetic Interference, Grounding and Soil
Structure Analysis
2.2 List of symbols
f Network frequency Hz
Un Nominal system voltage kV
Ifs Single pole short circuit current kA
Ik3 Symmetrical three phase short-circuit current kA
Ik1 Single phase to earth short-circuit current kA
lg Grid current discharged into grounding system kA
Rg Grounding system resistance Ω
Z1 Direct impedance Zpu
Zo Homopolar impedance Zpu
Estep Step voltage V
Etouch Touch voltage V
Cs Reduction factor
ρs Surface resistivity (gravel area) Ωm
hs Thickness of gravel m
Tm Maximum allowable temperature of buried conductor °C
Ta Ambient temperature °C
Ko Ko = Ao 1/Ao with temperature coefficient of resistivity at 0 ° C °C
αr Thermal resistivity coefficient at the referent temperature °C-1
ρr
Resistivity of the grounding conductor at the referent soil
temperature (20°C)
μΩ/cm
TCAP Thermal capacity of copper J/cm3
/°C
Amin Minimal section of the conductor mm2
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 5 
3. Soil resistivity measurements
Document already exists and it is Expected Soill Resistivity Study of Bazian Steal
Factory S/S-132/11kV, 1X30/40MVA.
That document should be placed here (suggested).
The measured resistance values at particular site as well as computed output of soil
resistivity results are enclosed in Appendices 1 to 4.
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 6 
4. Earthing Calculation Details to IEEE Std. 80-2000
4.1. Grid Conductor Sizing
Required minimum earth grid conductor size:
Where:
Single pole short circuit current: Ifs = 31,5 kA
Duration of fault current: tc = 0,5 s
Thermal resistivity coefficient at the referent temperature ( 20°C): αr= 0,00381 1/ ˚C
Resistivity of the grounding conductor at the referent soil temperature: ρr= 1,78 μΩ·cm
Thermal capacity of copper: TCAP=3,42J/cm3
/˚C
Max allowable temperature for brazed joint: Tm = 1084 ˚C
Ambient temperature: Ta = 40 ˚C
Ko=1/Ao at 0°C K0 = 235
Therefore:
Note:
According to customer's specification earth grid conductor shall not be less than 120
sqmm, therefore the earth grid conductor size to be used is 120 sqmm.
4.2. Calculation od current flowing between ground grid and earth
(Eq.2))(31500
3
1,1
1
3 A
Z
U
I n
k =
⋅
⋅
=
)1.(
1ln
10
0
4
min Eq
TK
TT
TCAP
ραt
IA
a
am
rrc
fs
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
+
−
+⋅
⋅⋅⋅
⋅=
2
4
4,80
40242
401084
1ln
42,3
1078,100381,05,0
5,31 mmA =
⎟
⎠
⎞
⎜
⎝
⎛
+
−
+⋅
⋅⋅⋅
⋅=
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 7 
Where:
Symmetrical three phase short-circuit current (r.m.s.) Ik3=31.5 kA
Nominal system voltage Un=132 kV
Positive sequence impedance at the fault location Z1
)3.(
10
2
31,13 3
021
1 Eq
ZZ
I
ZZZ
U
I kn
k
+
⋅
=
++
⋅⋅
=
Single phase to earth fault current Ik
Ratio of zero-sequence impedance to positive sequence lZ0/Z1l=3
impedance to network as viewed from fault location in case
of solidly earthed neutral
Therefore,
)(18900
32
315003
1 AIk =
+
×
=
Earth wires of coupled transmission lines or cable sheets connected to the earthing
system carry out part of the fault current as result of magnetic coupling. This effect is
accounted fir by reduction factor SF.
)4.(1 EqISI kFg ×=
Where:
Grid current discharged into grounding system Ig
Current division dactor that flows between ground Sf=0,6
grid and surrounding earth
Phase to earth fault current Ik1=18900 (kA)
Therefore, grid current:
)(11350189006,0 AIg =×=
4.3. Tolerable Step and Touch Voltages
4.3.1. Reduction Factor Due to Resistivity of Crush Rock Surface
120 mm thick layer of crushed rock is spread on the earth's surface above ground
grid in the switchyard to increase the contact resistance between the soil and the feet
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 8 
of the personnel in the substation. Cs-reduction factor for derating the nominal value
of surface layer resistivity determined as follows:
)5.(
09.02
1
09.01 Eq
s
h
s
s
C
⎥
⎥
⎥
⎥
⎥
⎦
⎤
⎢
⎢
⎢
⎢
⎢
⎣
⎡
+⋅
−
⋅−=
ρ
ρ
Where:
Earth resistivity ρ = * Ωm
Crush rock resistivity ρs = 3000 Ωm
Thickness of the crushed rock surface layer hs = 0.12 m
* Value to be obtained from the earth resistivity calculation (See Appendix 3).
4.3.2. Touch and Step Voltage Criteria
The safety of a person depends on preventing the critical amount of shock energy
from being absorbed before the fault is cleared and system de-energized. The
maximum driving voltage of any accidental circuit should not exceed the limits
defined below. For touch and step voltage the limits defined in IEEE Std 80-2000 are:
For a 50 kg body weight:
)6.(116.0
5.11000
Eq
s
t
ss
C
touch
E ⋅
⋅⋅+
=
ρ
)7.(116.0
61000
Eq
s
t
ss
C
step
E ⋅
⋅⋅+
=
ρ
For a 70 kg body weight:
)6.(157.0
5.11000
Eq
s
t
ss
C
touch
E ⋅
⋅⋅+
=
ρ
)7.(157.0
61000
Eq
s
t
ss
C
step
E ⋅
⋅⋅+
=
ρ
Where:
Shock duration in sec (exposure time) ts= 0,35 s
Resistivity of the surface material ρs = 3000 Ωm
Reduction factor Cs
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 9 
The safe touch and step voltages to be used for verification of grounding design is
calculated using MALT engineering module of CDEGS computer program. In the
Appendix 7 the computer printouts are presented.
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 10 
5. Principal results of the CDEGS software calculations
Configuration of the substation's grounding grid can be seen in Appendix 6.
5.1 Resistance of Electrode System (See Appendix 7)
Rg = 0.31847 (Ω)
Conclusion: The resistance of the electrode system is less than 1 Ω, so the system
satisfies principal IEEE Std 80-2000 condition.
5.2 Maximaum value od Grand Potential Rise GPR (See Appendices 7
and 15)
GPR = Ig · Rg = 3518.7 (V)
5.3 Touch voltage (See Appendix 8)
Allowed Touch Voltage Etouch = 953.8 (V)
Conclusion: The maximum touch voltages within the switchyard (see Appendix 9),
around the transformer (see Appendix 10), entry gates (see Appendix 11), nearby
substation fence (see Appendix 12) and capacitor banks (see Appendix 13) are
below the safety limit (allowable values).
5.4 Step Voltage (See Appendix 8)
Allowed Touch Voltage Estep = 3052,8 (V)
Conclusion: The maximum step voltages in the substation (see Appendix 14) are
below the safety limits.
Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA 
Earthing System Calculation  Page 11 
6. Appendices
Appendix 1: Axis layout of the soil resistivity measurements
Appendix 2: Soil resistivity measurements
Appendix 3: Results of the soil resistivity measurements
Appendix 4: Specific soil resistivity curve
Appendix 5: Cross-section of the grounding conductor
Appendix 6: Configuration of the grounding mesh
Appendix 7: Principal results of the CDEGS software calculations
Appendix 8: Touch and step voltage results
Appendix 9: Touch voltages within the switchyard
Appendix 10: Touch voltages in the transformer area
Appendix 11: Touch voltages around the entry gates
Appendix 12: Touch voltages of the substation fence
Appendix 13: Touch voltages around the capacitor banks
Appendix 14: Step voltage within the substation
Appendix 15: Scalar potentials (3D potential distribution) GPR-Grand Potential Rise
Appendix 16: Maximum touch voltages that appear within the substation (Layout)
Appendix 17: Maximum step voltages that appear within the substation (Layout)
APPENDIX 1: Axis layout of the soil resistivity measurements
APPENDIX 2: Soil resistivity measurements
Project: Bazian Steel Factory S/S 132/11kV, 1x30/40 MVA
Date: April 2011
Coordinate x y z
a
Resistivity
St-1 (Ohm.m)
Resistivity
St-2 (Ohm.m)
Resistivity
St-3 (Ohm.m)
1.0 85.008 79.65257 83.22914
1.5 57.85749 56.45829 57.36814
2.2 52.16137 56.11358 53.68251
3.3 34.15519 38.88249 36.34149
4.6 32.54881 29.17451 29.57931
6.8 33.11597 25.50143 21.98522
10 34.75811 31.05606 23.16537
14.1 39.6214 33.52021 31.48885
Latitude
Longitude
Elevation
35 07 45.8
45 40 36.4
600
35 07 46.5
45 40 38.8
600
35 07 45.3
45 40 39.1
601
APPENDIX 3: Results of the soil resistivity measurements
=========< R E S I S T I V I T Y ( SYSTEM INFORMATION SUMMARY ) >=========
Run ID......................................: BSF
System of Units ............................: Meters
Soil Type Selected..........................: Multi-Layer Horizontal
RMS error between measured and calculated...: 13.741 in percent resistivities
<--- LAYER CHARACTERISTICS --> Reflection Resistivity
Layer Resistivity Thickness Coefficient Contrast
Number (ohm-m) (Meters) (p.u.) Ratio
====== ============== ============== ============ ============
1 infinite infinite 0.0 1.0
2 94.31239 1.084724 -1.0000 0.94312E-18
3 25.34191 0.9349011 -0.57641 0.26870
4 27.93612 infinite 0.48692E-01 1.1024
APPENDIX 5: Cross-section of the grounding conductor
Ampacity Function Report
CDEGS Conductor Ampacity Calculation (per IEEE Standard 80)
Computation Results:
Minimum Conductor Size:
162,3677 MCM
82,2531 sq. mm
0,2015 in (radius)
5,1169 mm (radius)
Input Data:
Symmetrical RMS Current Magnitude: 31,5 kA
Maximum Fault Duration: 0,5 s
Ambient Temperature: 40 °C
Maximum Allowable Temperature: 1084,0000 °C (fusing temperature)
Conductor Type: Copper, commercial hard drawn (97% conductivity)
Decrement Factor: 1,0313
X/R: 10
Frequency: 50 Hz
Material Constants of Conductor:
Name: Copper, commercial hard drawn (97% conductivity)
Reference Temperature for Material Constants: 20,0000 °C
Thermal Coefficient of Resistivity at Reference Temperature: 0,00381 1/°C
Fusing Temperature of Conductor: 1084,0000 °C
Resistivity of Conductor at Reference Temperature: 1,7800 μΩ⋅cm
Thermal Capacity per Unit Volume: 3,4200 J/cm3 · °C
PROFILE1
PROFILE2
PROFILE15PROFILE16PROFILE14PROFILE13
PROFILE17
PROFILE18
PROFILE25
PROFILE24
PROFILE19PROFILE20PROFILE21
PROFILE12
PROFILE11
PROFILE22
PROFILE23
PROFILE6
PROFILE5
PROFILE7
PROFILE3
PROFILE4
PROFILE9
PROFILE10
PROFILE8
APPENDIX 6: Configuration of the grounding mesh (Touch and Step Voltages Profiles)
APPENDIX 7: Principal results of the CDEGS software calculations
===========< G R O U N D I N G ( SYSTEM INFORMATION SUMMARY ) >===========
Run ID......................................: Bazian Steel Factory
System of Units ............................: Metric
Earth Potential Calculations................: Multiple Electrode Case
Mutual Resistance Calculations..............: NO
Type of Electrodes Considered...............: Both Main + Buried Electrode
Soil Type Selected..........................: Multi-Layer Horizontal
SPLITS/FCDIST Scaling Factor................: 11.350
MULTI-LAYER EARTH CHARACTERISTICS USED BY PROGRAM
-------------------------------------------------
Common layer height : 0.183602 METERS
LAYER TYPE REFLECTION RESISTIVITY HEIGHT
No. COEFFICIENT (ohm-meter) METERS
----- ------ ------------- ------------- -------------
1 Air 0.00000 0.100000E+21 0.100000E+11
2 Soil -0.999990 94.3124 1.10161
3 Soil -0.576415 25.3419 0.918011
4 Soil 0.486921E-01 27.9361 0.100000E+11
CONFIGURATION OF MAIN ELECTRODE
===============================
Original Electrical Current Flowing In Electrode..: 1000.0 amperes
Current Scaling Factor (SPLITS/FCDIST/specified)..: 11.350
Adjusted Electrical Current Flowing In Electrode..: 11350. amperes
Number of Conductors in Electrode.................: 37
Resistance of Electrode System....................: 0.31847 ohms
SUBDIVISION
===========
Grand Total of Conductors After Subdivision.: 1858
EARTH POTENTIAL COMPUTATIONS < Returns & Buried Structures >
============================
Number of Return Grounds................: 0
Number of Buried Structures.............: 1
MODULE NAME : BURIED STRUCTURES
================================
Number of Buried Structures.............: 1
Structure No. of Start End
Number Conductors < Conductor No >
--------- ---------- ------- --------
1 20 1859 1878
EARTH POTENTIAL COMPUTATIONS
============================
Main Electrode Potential Rise (GPR).....: 3518.7 volts
Return Electrode Potential Rise (GPR)...: 0.0000 volts
(based on two representative points)
Buried Metallic Structure No.1 Potential Rise (GPR).....: 2394.8 volts
TOTAL BURIED LENGTH OF MAIN ELECTRODE: 872.344 METERS
TOTAL BURIED LENGTH OF RETURN ELECTRODE: 0.000 METERS
TOTAL BURIED LENGTH OF METALLIC STRUCTURES: 30.000 METERS
TOTAL BURIED LENGTH OF GROUNDING NETWORK: 902.344 METERS
APPENDIX 8: Touch and step voltages results
>> Safety Calculations Table
System Frequency............................(Hertz).: 50.000
System X/R..........................................: 10.000
Surface Layer Thickness.....................( m )...: 0.12000
Number of Surface Layer Resistivities...............: 10
Starting Surface Layer Resistivity..........(ohm-m).: NONE
Incremental Surface Layer Resistivity.......(ohm-m).: 500.00
Equivalent Sub-Surface Layer Resistivity....(ohm-m).: 94.312
Body Resistance Calculation..........: IEEE 80
Fibrillation Current Calculation.....: IEEE 80 (70kg)
Foot Resistance Calculation..........: IEEE (Std.80) Series Expansion Cs
User Defined Extra Foot Resistance: 0.0000 ohms
==========================================================================
| Fault Clearing Time ( sec)| 0.125 | 0.350 | 0.500|
+----------------------------+---------------+---------------+-----------+
| Decrement Factor | 1.120 | 1.044 | 1.000 |
| Fibrillation Current (amps)| 0.396 | 0.254 | 0.222 |
| Body Resistance (ohms)| 1000.00 | 1000.00 | 1000.00 |
==========================================================================
==========================================================================
| SURFACE | FAULT CLEARING TIME | |
| LAYER |-----------------+-----------------+-----------------| |
| RESIST- | 0.125 sec. | 0.350 sec. | 0.500 sec. | FOOT |
| IVITY |-----------------|-----------------|-----------------| RESIST-|
| (OHM-M) | STEP | TOUCH | STEP | TOUCH | STEP | TOUCH | ANCE: |
| | VOLTAGE| VOLTAGE| VOLTAGE| VOLTAGE| VOLTAGE| VOLTAGE| 1 FOOT |
| | (VOLTS)| (VOLTS)| (VOLTS)| (VOLTS)| (VOLTS)| (VOLTS)| (OHMS) |
==========================================================================
| NONE | 630.2| 454.9| 403.8| 291.5| 352.9| 254.8| 294.7|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 500.0| 1232.3| 605.4| 789.8| 388.0| 690.2| 339.1| 1054.2|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 1000.0| 1942.1| 782.9| 1244.6| 501.7| 1087.6| 438.4| 1949.3|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 1500.0| 2648.4| 959.4| 1697.3| 614.9| 1483.2| 537.3| 2840.1|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 2000.0| 3353.8| 1135.8| 2149.3| 727.9| 1878.2| 636.1| 3729.7|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 2500.0| 4058.8| 1312.0| 2601.1| 840.8| 2273.1| 734.8| 4618.8|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 3000.0| 4763.6| 1488.3| *3052.8| *953.8| 2667.8| 833.5| 5507.7|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 3500.0| 5468.4| 1664.5| 3504.5| 1066.7| 3062.5| 932.1| 6396.5|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 4000.0| 6173.2| 1840.6| 3956.2| 1179.6| 3457.2| 1030.8| 7285.4|
|---------+--------+--------+--------+--------+--------+--------+--------+
| 4500.0| 6878.0| 2016.9| 4407.9| 1292.5| 3851.9| 1129.5| 8174.3|
|---------+--------+--------+--------+--------+--------+--------+--------+
* NOTE * Safety limit
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1
Bsf earthing system calculation-1

More Related Content

What's hot

Generator capability curve
Generator capability curveGenerator capability curve
Generator capability curvePhadindra Poudel
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.Geetesh Verma
 
BREAKDOWN IN LIQUIDS_NDS
BREAKDOWN IN LIQUIDS_NDSBREAKDOWN IN LIQUIDS_NDS
BREAKDOWN IN LIQUIDS_NDSNiraj Solanki
 
Circuit Breaker: Part 2
Circuit Breaker: Part 2Circuit Breaker: Part 2
Circuit Breaker: Part 2Dr. Rohit Babu
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptxUtthejNani1
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersShailendra Shakya
 
V/F control of Induction Motor - Variable voltage and Variable frequency
V/F control of Induction Motor - Variable voltage and Variable frequencyV/F control of Induction Motor - Variable voltage and Variable frequency
V/F control of Induction Motor - Variable voltage and Variable frequencyCitharthan Durairaj
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculationsmichaeljmack
 
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptxSuhailAbdul2
 
Construction of three phase induction motor
Construction of three phase induction motorConstruction of three phase induction motor
Construction of three phase induction motorDr.Raja R
 
Power cable - Voltage drop
Power cable - Voltage dropPower cable - Voltage drop
Power cable - Voltage dropLeonardo ENERGY
 
Fault location for transmission line
Fault location  for transmission lineFault location  for transmission line
Fault location for transmission linemohammed shareef
 

What's hot (20)

Generator capability curve
Generator capability curveGenerator capability curve
Generator capability curve
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.
 
DC MICROGRID PPT.pptx
DC MICROGRID PPT.pptxDC MICROGRID PPT.pptx
DC MICROGRID PPT.pptx
 
BREAKDOWN IN LIQUIDS_NDS
BREAKDOWN IN LIQUIDS_NDSBREAKDOWN IN LIQUIDS_NDS
BREAKDOWN IN LIQUIDS_NDS
 
Z bus building algorithm
Z bus building algorithmZ bus building algorithm
Z bus building algorithm
 
Circuit Breaker: Part 2
Circuit Breaker: Part 2Circuit Breaker: Part 2
Circuit Breaker: Part 2
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
 
Mod5part1
Mod5part1Mod5part1
Mod5part1
 
Generator capability curve
Generator capability curve Generator capability curve
Generator capability curve
 
Out of step
Out of stepOut of step
Out of step
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit Breakers
 
V/F control of Induction Motor - Variable voltage and Variable frequency
V/F control of Induction Motor - Variable voltage and Variable frequencyV/F control of Induction Motor - Variable voltage and Variable frequency
V/F control of Induction Motor - Variable voltage and Variable frequency
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
 
Earthing
EarthingEarthing
Earthing
 
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptx
 
Construction of three phase induction motor
Construction of three phase induction motorConstruction of three phase induction motor
Construction of three phase induction motor
 
Relay testing procedure
Relay testing procedure Relay testing procedure
Relay testing procedure
 
Power cable - Voltage drop
Power cable - Voltage dropPower cable - Voltage drop
Power cable - Voltage drop
 
Fault location for transmission line
Fault location  for transmission lineFault location  for transmission line
Fault location for transmission line
 
To study of Shaded pole Induction motor
To study of Shaded pole Induction motorTo study of Shaded pole Induction motor
To study of Shaded pole Induction motor
 

Similar to Bsf earthing system calculation-1

Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems SafetyTalia Carbis
 
1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docxjackiewalcutt
 
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPEVHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPEhtrindia
 
Design And Analysis Of Low Power High Performance Single Bit Full Adder
Design And Analysis Of Low Power High Performance Single Bit Full AdderDesign And Analysis Of Low Power High Performance Single Bit Full Adder
Design And Analysis Of Low Power High Performance Single Bit Full AdderIJTET Journal
 
Grounding System Analysis
Grounding System AnalysisGrounding System Analysis
Grounding System Analysisijtsrd
 
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas ElectronicsOriginal N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas ElectronicsAUTHELECTRONIC
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substationijtsrd
 
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englishHtr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englishSiddheshPathak3
 
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...htrindia
 
Datasheet
DatasheetDatasheet
Datasheetolvit
 
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englishHtr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englishhtrindia
 
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415Patrick Volluz
 
Technical presentation on modern earthing
Technical presentation on modern earthingTechnical presentation on modern earthing
Technical presentation on modern earthingPankaj Chakraborty
 
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWSyamsirAbduh2
 
Generator rotor earth fault protection
Generator rotor earth fault protectionGenerator rotor earth fault protection
Generator rotor earth fault protectionAditya Parmar
 
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...AUTHELECTRONIC
 
Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...
Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...
Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...AUTHELECTRONIC
 

Similar to Bsf earthing system calculation-1 (20)

Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems Safety
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
 
1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx
 
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPEVHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
VHIA - WIRE WOUND RESISTORS SILICONE COATED TYPE
 
Design And Analysis Of Low Power High Performance Single Bit Full Adder
Design And Analysis Of Low Power High Performance Single Bit Full AdderDesign And Analysis Of Low Power High Performance Single Bit Full Adder
Design And Analysis Of Low Power High Performance Single Bit Full Adder
 
Grounding System Analysis
Grounding System AnalysisGrounding System Analysis
Grounding System Analysis
 
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas ElectronicsOriginal N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
 
Design of Grounding System for Substation
Design of Grounding System for SubstationDesign of Grounding System for Substation
Design of Grounding System for Substation
 
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englishHtr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
 
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englis...
 
Datasheet
DatasheetDatasheet
Datasheet
 
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-englishHtr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
Htr india-products-wire-wound-resistors-silicone-coated-resistors-vhia-english
 
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415SG104136BEN_B07_Brochure_UR6-10-15 T_0415
SG104136BEN_B07_Brochure_UR6-10-15 T_0415
 
Technical presentation on modern earthing
Technical presentation on modern earthingTechnical presentation on modern earthing
Technical presentation on modern earthing
 
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
 
Generator rotor earth fault protection
Generator rotor earth fault protectionGenerator rotor earth fault protection
Generator rotor earth fault protection
 
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
Original N Channel Mosfet FQD10N60C STD10NM60N 10NM60 10N60 10A 600V TO-252 N...
 
Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...
Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...
Original N-channel 600 V 0.160 Ω 19 A PowerFLAT™ 8x8 HV ultra low gate charge...
 
Datasheet
DatasheetDatasheet
Datasheet
 
Sample Coordination Study
Sample Coordination StudySample Coordination Study
Sample Coordination Study
 

More from Raymund Cortez

060626 huawei umts end to-end solution (1)
060626 huawei umts end to-end solution (1)060626 huawei umts end to-end solution (1)
060626 huawei umts end to-end solution (1)Raymund Cortez
 
Electrical engineer primer
Electrical engineer primerElectrical engineer primer
Electrical engineer primerRaymund Cortez
 
Calculation exaple for x to r ratio
Calculation exaple for x to r ratioCalculation exaple for x to r ratio
Calculation exaple for x to r ratioRaymund Cortez
 
Master low-voltage saudi cable co.
Master low-voltage saudi cable co.Master low-voltage saudi cable co.
Master low-voltage saudi cable co.Raymund Cortez
 
Sec electrical utility characteristic
Sec electrical utility characteristicSec electrical utility characteristic
Sec electrical utility characteristicRaymund Cortez
 
Calculation of short_circuit_currents
Calculation of short_circuit_currentsCalculation of short_circuit_currents
Calculation of short_circuit_currentsRaymund Cortez
 
Motor protection customer-final
Motor protection   customer-finalMotor protection   customer-final
Motor protection customer-finalRaymund Cortez
 
55418233 ieee-c37-96-motor-protection-1
55418233 ieee-c37-96-motor-protection-155418233 ieee-c37-96-motor-protection-1
55418233 ieee-c37-96-motor-protection-1Raymund Cortez
 
Ieee c57123 ieee_guide_for_transformer_loss_management_200204
Ieee c57123 ieee_guide_for_transformer_loss_management_200204Ieee c57123 ieee_guide_for_transformer_loss_management_200204
Ieee c57123 ieee_guide_for_transformer_loss_management_200204Raymund Cortez
 
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limitsMeeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limitsRaymund Cortez
 

More from Raymund Cortez (14)

060626 huawei umts end to-end solution (1)
060626 huawei umts end to-end solution (1)060626 huawei umts end to-end solution (1)
060626 huawei umts end to-end solution (1)
 
Electrical engineer primer
Electrical engineer primerElectrical engineer primer
Electrical engineer primer
 
Iec standards
Iec standardsIec standards
Iec standards
 
Calculation exaple for x to r ratio
Calculation exaple for x to r ratioCalculation exaple for x to r ratio
Calculation exaple for x to r ratio
 
Dps 02 rev02
Dps 02 rev02Dps 02 rev02
Dps 02 rev02
 
Master low-voltage saudi cable co.
Master low-voltage saudi cable co.Master low-voltage saudi cable co.
Master low-voltage saudi cable co.
 
Sec electrical utility characteristic
Sec electrical utility characteristicSec electrical utility characteristic
Sec electrical utility characteristic
 
Calculation of short_circuit_currents
Calculation of short_circuit_currentsCalculation of short_circuit_currents
Calculation of short_circuit_currents
 
01 sdms-01 rev01
01 sdms-01 rev0101 sdms-01 rev01
01 sdms-01 rev01
 
Motor protection customer-final
Motor protection   customer-finalMotor protection   customer-final
Motor protection customer-final
 
55418233 ieee-c37-96-motor-protection-1
55418233 ieee-c37-96-motor-protection-155418233 ieee-c37-96-motor-protection-1
55418233 ieee-c37-96-motor-protection-1
 
Ieee c57123 ieee_guide_for_transformer_loss_management_200204
Ieee c57123 ieee_guide_for_transformer_loss_management_200204Ieee c57123 ieee_guide_for_transformer_loss_management_200204
Ieee c57123 ieee_guide_for_transformer_loss_management_200204
 
Micrologic 5 6_2
Micrologic 5 6_2Micrologic 5 6_2
Micrologic 5 6_2
 
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limitsMeeting ieee 519 1992 using harmonic guard passive filters harmonic limits
Meeting ieee 519 1992 using harmonic guard passive filters harmonic limits
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 

Bsf earthing system calculation-1

  • 1. BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011
  • 2. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 2  Contents: 1. Introduction............................................................................................................. 3 2. List of references and symbols............................................................................... 4 2.1 List of references............................................................................................... 4 2.2 List of symbols................................................................................................... 4 3. Soil resistivity measurements ................................................................................. 5 4. Earthing Calculation Details to IEEE Std. 80-2000 ................................................. 6 4.1. Grid Conductor Sizing...................................................................................... 6 4.2. Calculation od current flowing between ground grid and earth ........................ 6 4.3. Tolerable Step and Touch Voltages................................................................. 7 4.3.1. Reduction Factor Due to Resistivity of Crush Rock Surface...................... 7 4.3.2. Touch and Step Voltage Criteria................................................................ 8 5. Principal results of the CDEGS software calculations .......................................... 10 5.1 Resistance of Electrode System (See Appendix 7)......................................... 10 5.2 Maximaum value od Grand Potential Rise GPR (See Appendices 7 and 15). 10 5.3 Touch voltage (See Appendix 8)..................................................................... 10 5.4 Step Voltage (See Appendix 8)....................................................................... 10 6. Appendices........................................................................................................... 11
  • 3. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 3  1. Introduction The project of earthing system is prepared in accordance with the requirements of the investor and Standard: IEEE 80 –2000 Guide for Safety in Substation Grounding. Specific resistance is calculated on the basis of measured values of soil resistivity. The earthing system is designed so that the allowable touch and step voltages do not be exceeded. The calculation is done using the software CDEG MultiGround TM SES - Safe Engineering Services & technologies ltd. Canada whose results are shown in Appendices. The result shows that the touch and step voltages are within the permissible limits.
  • 4. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 4  2. List of references and symbols 2.1 List of references [1] IEEE Std 80-2000 IEEE Guide for Safety in AC Substation Grounding [2] CDEG Software Package, 1998 Current Distribution, Electromagnetic Interference, Grounding and Soil Structure Analysis 2.2 List of symbols f Network frequency Hz Un Nominal system voltage kV Ifs Single pole short circuit current kA Ik3 Symmetrical three phase short-circuit current kA Ik1 Single phase to earth short-circuit current kA lg Grid current discharged into grounding system kA Rg Grounding system resistance Ω Z1 Direct impedance Zpu Zo Homopolar impedance Zpu Estep Step voltage V Etouch Touch voltage V Cs Reduction factor ρs Surface resistivity (gravel area) Ωm hs Thickness of gravel m Tm Maximum allowable temperature of buried conductor °C Ta Ambient temperature °C Ko Ko = Ao 1/Ao with temperature coefficient of resistivity at 0 ° C °C αr Thermal resistivity coefficient at the referent temperature °C-1 ρr Resistivity of the grounding conductor at the referent soil temperature (20°C) μΩ/cm TCAP Thermal capacity of copper J/cm3 /°C Amin Minimal section of the conductor mm2
  • 5. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 5  3. Soil resistivity measurements Document already exists and it is Expected Soill Resistivity Study of Bazian Steal Factory S/S-132/11kV, 1X30/40MVA. That document should be placed here (suggested). The measured resistance values at particular site as well as computed output of soil resistivity results are enclosed in Appendices 1 to 4.
  • 6. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 6  4. Earthing Calculation Details to IEEE Std. 80-2000 4.1. Grid Conductor Sizing Required minimum earth grid conductor size: Where: Single pole short circuit current: Ifs = 31,5 kA Duration of fault current: tc = 0,5 s Thermal resistivity coefficient at the referent temperature ( 20°C): αr= 0,00381 1/ ˚C Resistivity of the grounding conductor at the referent soil temperature: ρr= 1,78 μΩ·cm Thermal capacity of copper: TCAP=3,42J/cm3 /˚C Max allowable temperature for brazed joint: Tm = 1084 ˚C Ambient temperature: Ta = 40 ˚C Ko=1/Ao at 0°C K0 = 235 Therefore: Note: According to customer's specification earth grid conductor shall not be less than 120 sqmm, therefore the earth grid conductor size to be used is 120 sqmm. 4.2. Calculation od current flowing between ground grid and earth (Eq.2))(31500 3 1,1 1 3 A Z U I n k = ⋅ ⋅ = )1.( 1ln 10 0 4 min Eq TK TT TCAP ραt IA a am rrc fs ⎟⎟ ⎠ ⎞ ⎜⎜ ⎝ ⎛ + − +⋅ ⋅⋅⋅ ⋅= 2 4 4,80 40242 401084 1ln 42,3 1078,100381,05,0 5,31 mmA = ⎟ ⎠ ⎞ ⎜ ⎝ ⎛ + − +⋅ ⋅⋅⋅ ⋅=
  • 7. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 7  Where: Symmetrical three phase short-circuit current (r.m.s.) Ik3=31.5 kA Nominal system voltage Un=132 kV Positive sequence impedance at the fault location Z1 )3.( 10 2 31,13 3 021 1 Eq ZZ I ZZZ U I kn k + ⋅ = ++ ⋅⋅ = Single phase to earth fault current Ik Ratio of zero-sequence impedance to positive sequence lZ0/Z1l=3 impedance to network as viewed from fault location in case of solidly earthed neutral Therefore, )(18900 32 315003 1 AIk = + × = Earth wires of coupled transmission lines or cable sheets connected to the earthing system carry out part of the fault current as result of magnetic coupling. This effect is accounted fir by reduction factor SF. )4.(1 EqISI kFg ×= Where: Grid current discharged into grounding system Ig Current division dactor that flows between ground Sf=0,6 grid and surrounding earth Phase to earth fault current Ik1=18900 (kA) Therefore, grid current: )(11350189006,0 AIg =×= 4.3. Tolerable Step and Touch Voltages 4.3.1. Reduction Factor Due to Resistivity of Crush Rock Surface 120 mm thick layer of crushed rock is spread on the earth's surface above ground grid in the switchyard to increase the contact resistance between the soil and the feet
  • 8. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 8  of the personnel in the substation. Cs-reduction factor for derating the nominal value of surface layer resistivity determined as follows: )5.( 09.02 1 09.01 Eq s h s s C ⎥ ⎥ ⎥ ⎥ ⎥ ⎦ ⎤ ⎢ ⎢ ⎢ ⎢ ⎢ ⎣ ⎡ +⋅ − ⋅−= ρ ρ Where: Earth resistivity ρ = * Ωm Crush rock resistivity ρs = 3000 Ωm Thickness of the crushed rock surface layer hs = 0.12 m * Value to be obtained from the earth resistivity calculation (See Appendix 3). 4.3.2. Touch and Step Voltage Criteria The safety of a person depends on preventing the critical amount of shock energy from being absorbed before the fault is cleared and system de-energized. The maximum driving voltage of any accidental circuit should not exceed the limits defined below. For touch and step voltage the limits defined in IEEE Std 80-2000 are: For a 50 kg body weight: )6.(116.0 5.11000 Eq s t ss C touch E ⋅ ⋅⋅+ = ρ )7.(116.0 61000 Eq s t ss C step E ⋅ ⋅⋅+ = ρ For a 70 kg body weight: )6.(157.0 5.11000 Eq s t ss C touch E ⋅ ⋅⋅+ = ρ )7.(157.0 61000 Eq s t ss C step E ⋅ ⋅⋅+ = ρ Where: Shock duration in sec (exposure time) ts= 0,35 s Resistivity of the surface material ρs = 3000 Ωm Reduction factor Cs
  • 9. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 9  The safe touch and step voltages to be used for verification of grounding design is calculated using MALT engineering module of CDEGS computer program. In the Appendix 7 the computer printouts are presented.
  • 10. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 10  5. Principal results of the CDEGS software calculations Configuration of the substation's grounding grid can be seen in Appendix 6. 5.1 Resistance of Electrode System (See Appendix 7) Rg = 0.31847 (Ω) Conclusion: The resistance of the electrode system is less than 1 Ω, so the system satisfies principal IEEE Std 80-2000 condition. 5.2 Maximaum value od Grand Potential Rise GPR (See Appendices 7 and 15) GPR = Ig · Rg = 3518.7 (V) 5.3 Touch voltage (See Appendix 8) Allowed Touch Voltage Etouch = 953.8 (V) Conclusion: The maximum touch voltages within the switchyard (see Appendix 9), around the transformer (see Appendix 10), entry gates (see Appendix 11), nearby substation fence (see Appendix 12) and capacitor banks (see Appendix 13) are below the safety limit (allowable values). 5.4 Step Voltage (See Appendix 8) Allowed Touch Voltage Estep = 3052,8 (V) Conclusion: The maximum step voltages in the substation (see Appendix 14) are below the safety limits.
  • 11. Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA  Earthing System Calculation  Page 11  6. Appendices Appendix 1: Axis layout of the soil resistivity measurements Appendix 2: Soil resistivity measurements Appendix 3: Results of the soil resistivity measurements Appendix 4: Specific soil resistivity curve Appendix 5: Cross-section of the grounding conductor Appendix 6: Configuration of the grounding mesh Appendix 7: Principal results of the CDEGS software calculations Appendix 8: Touch and step voltage results Appendix 9: Touch voltages within the switchyard Appendix 10: Touch voltages in the transformer area Appendix 11: Touch voltages around the entry gates Appendix 12: Touch voltages of the substation fence Appendix 13: Touch voltages around the capacitor banks Appendix 14: Step voltage within the substation Appendix 15: Scalar potentials (3D potential distribution) GPR-Grand Potential Rise Appendix 16: Maximum touch voltages that appear within the substation (Layout) Appendix 17: Maximum step voltages that appear within the substation (Layout)
  • 12. APPENDIX 1: Axis layout of the soil resistivity measurements
  • 13. APPENDIX 2: Soil resistivity measurements Project: Bazian Steel Factory S/S 132/11kV, 1x30/40 MVA Date: April 2011 Coordinate x y z a Resistivity St-1 (Ohm.m) Resistivity St-2 (Ohm.m) Resistivity St-3 (Ohm.m) 1.0 85.008 79.65257 83.22914 1.5 57.85749 56.45829 57.36814 2.2 52.16137 56.11358 53.68251 3.3 34.15519 38.88249 36.34149 4.6 32.54881 29.17451 29.57931 6.8 33.11597 25.50143 21.98522 10 34.75811 31.05606 23.16537 14.1 39.6214 33.52021 31.48885 Latitude Longitude Elevation 35 07 45.8 45 40 36.4 600 35 07 46.5 45 40 38.8 600 35 07 45.3 45 40 39.1 601
  • 14. APPENDIX 3: Results of the soil resistivity measurements =========< R E S I S T I V I T Y ( SYSTEM INFORMATION SUMMARY ) >========= Run ID......................................: BSF System of Units ............................: Meters Soil Type Selected..........................: Multi-Layer Horizontal RMS error between measured and calculated...: 13.741 in percent resistivities <--- LAYER CHARACTERISTICS --> Reflection Resistivity Layer Resistivity Thickness Coefficient Contrast Number (ohm-m) (Meters) (p.u.) Ratio ====== ============== ============== ============ ============ 1 infinite infinite 0.0 1.0 2 94.31239 1.084724 -1.0000 0.94312E-18 3 25.34191 0.9349011 -0.57641 0.26870 4 27.93612 infinite 0.48692E-01 1.1024
  • 15.
  • 16. APPENDIX 5: Cross-section of the grounding conductor Ampacity Function Report CDEGS Conductor Ampacity Calculation (per IEEE Standard 80) Computation Results: Minimum Conductor Size: 162,3677 MCM 82,2531 sq. mm 0,2015 in (radius) 5,1169 mm (radius) Input Data: Symmetrical RMS Current Magnitude: 31,5 kA Maximum Fault Duration: 0,5 s Ambient Temperature: 40 °C Maximum Allowable Temperature: 1084,0000 °C (fusing temperature) Conductor Type: Copper, commercial hard drawn (97% conductivity) Decrement Factor: 1,0313 X/R: 10 Frequency: 50 Hz Material Constants of Conductor: Name: Copper, commercial hard drawn (97% conductivity) Reference Temperature for Material Constants: 20,0000 °C Thermal Coefficient of Resistivity at Reference Temperature: 0,00381 1/°C Fusing Temperature of Conductor: 1084,0000 °C Resistivity of Conductor at Reference Temperature: 1,7800 μΩ⋅cm Thermal Capacity per Unit Volume: 3,4200 J/cm3 · °C
  • 18. APPENDIX 7: Principal results of the CDEGS software calculations ===========< G R O U N D I N G ( SYSTEM INFORMATION SUMMARY ) >=========== Run ID......................................: Bazian Steel Factory System of Units ............................: Metric Earth Potential Calculations................: Multiple Electrode Case Mutual Resistance Calculations..............: NO Type of Electrodes Considered...............: Both Main + Buried Electrode Soil Type Selected..........................: Multi-Layer Horizontal SPLITS/FCDIST Scaling Factor................: 11.350 MULTI-LAYER EARTH CHARACTERISTICS USED BY PROGRAM ------------------------------------------------- Common layer height : 0.183602 METERS LAYER TYPE REFLECTION RESISTIVITY HEIGHT No. COEFFICIENT (ohm-meter) METERS ----- ------ ------------- ------------- ------------- 1 Air 0.00000 0.100000E+21 0.100000E+11 2 Soil -0.999990 94.3124 1.10161 3 Soil -0.576415 25.3419 0.918011 4 Soil 0.486921E-01 27.9361 0.100000E+11 CONFIGURATION OF MAIN ELECTRODE =============================== Original Electrical Current Flowing In Electrode..: 1000.0 amperes Current Scaling Factor (SPLITS/FCDIST/specified)..: 11.350 Adjusted Electrical Current Flowing In Electrode..: 11350. amperes Number of Conductors in Electrode.................: 37 Resistance of Electrode System....................: 0.31847 ohms SUBDIVISION =========== Grand Total of Conductors After Subdivision.: 1858 EARTH POTENTIAL COMPUTATIONS < Returns & Buried Structures > ============================ Number of Return Grounds................: 0 Number of Buried Structures.............: 1 MODULE NAME : BURIED STRUCTURES ================================ Number of Buried Structures.............: 1 Structure No. of Start End Number Conductors < Conductor No > --------- ---------- ------- -------- 1 20 1859 1878
  • 19. EARTH POTENTIAL COMPUTATIONS ============================ Main Electrode Potential Rise (GPR).....: 3518.7 volts Return Electrode Potential Rise (GPR)...: 0.0000 volts (based on two representative points) Buried Metallic Structure No.1 Potential Rise (GPR).....: 2394.8 volts TOTAL BURIED LENGTH OF MAIN ELECTRODE: 872.344 METERS TOTAL BURIED LENGTH OF RETURN ELECTRODE: 0.000 METERS TOTAL BURIED LENGTH OF METALLIC STRUCTURES: 30.000 METERS TOTAL BURIED LENGTH OF GROUNDING NETWORK: 902.344 METERS
  • 20. APPENDIX 8: Touch and step voltages results >> Safety Calculations Table System Frequency............................(Hertz).: 50.000 System X/R..........................................: 10.000 Surface Layer Thickness.....................( m )...: 0.12000 Number of Surface Layer Resistivities...............: 10 Starting Surface Layer Resistivity..........(ohm-m).: NONE Incremental Surface Layer Resistivity.......(ohm-m).: 500.00 Equivalent Sub-Surface Layer Resistivity....(ohm-m).: 94.312 Body Resistance Calculation..........: IEEE 80 Fibrillation Current Calculation.....: IEEE 80 (70kg) Foot Resistance Calculation..........: IEEE (Std.80) Series Expansion Cs User Defined Extra Foot Resistance: 0.0000 ohms ========================================================================== | Fault Clearing Time ( sec)| 0.125 | 0.350 | 0.500| +----------------------------+---------------+---------------+-----------+ | Decrement Factor | 1.120 | 1.044 | 1.000 | | Fibrillation Current (amps)| 0.396 | 0.254 | 0.222 | | Body Resistance (ohms)| 1000.00 | 1000.00 | 1000.00 | ========================================================================== ========================================================================== | SURFACE | FAULT CLEARING TIME | | | LAYER |-----------------+-----------------+-----------------| | | RESIST- | 0.125 sec. | 0.350 sec. | 0.500 sec. | FOOT | | IVITY |-----------------|-----------------|-----------------| RESIST-| | (OHM-M) | STEP | TOUCH | STEP | TOUCH | STEP | TOUCH | ANCE: | | | VOLTAGE| VOLTAGE| VOLTAGE| VOLTAGE| VOLTAGE| VOLTAGE| 1 FOOT | | | (VOLTS)| (VOLTS)| (VOLTS)| (VOLTS)| (VOLTS)| (VOLTS)| (OHMS) | ========================================================================== | NONE | 630.2| 454.9| 403.8| 291.5| 352.9| 254.8| 294.7| |---------+--------+--------+--------+--------+--------+--------+--------+ | 500.0| 1232.3| 605.4| 789.8| 388.0| 690.2| 339.1| 1054.2| |---------+--------+--------+--------+--------+--------+--------+--------+ | 1000.0| 1942.1| 782.9| 1244.6| 501.7| 1087.6| 438.4| 1949.3| |---------+--------+--------+--------+--------+--------+--------+--------+ | 1500.0| 2648.4| 959.4| 1697.3| 614.9| 1483.2| 537.3| 2840.1| |---------+--------+--------+--------+--------+--------+--------+--------+ | 2000.0| 3353.8| 1135.8| 2149.3| 727.9| 1878.2| 636.1| 3729.7| |---------+--------+--------+--------+--------+--------+--------+--------+ | 2500.0| 4058.8| 1312.0| 2601.1| 840.8| 2273.1| 734.8| 4618.8| |---------+--------+--------+--------+--------+--------+--------+--------+ | 3000.0| 4763.6| 1488.3| *3052.8| *953.8| 2667.8| 833.5| 5507.7| |---------+--------+--------+--------+--------+--------+--------+--------+ | 3500.0| 5468.4| 1664.5| 3504.5| 1066.7| 3062.5| 932.1| 6396.5| |---------+--------+--------+--------+--------+--------+--------+--------+ | 4000.0| 6173.2| 1840.6| 3956.2| 1179.6| 3457.2| 1030.8| 7285.4| |---------+--------+--------+--------+--------+--------+--------+--------+ | 4500.0| 6878.0| 2016.9| 4407.9| 1292.5| 3851.9| 1129.5| 8174.3| |---------+--------+--------+--------+--------+--------+--------+--------+ * NOTE * Safety limit