Energy Procedia 56 (2014) 510 – 517
Available online at www.sciencedirect.com
ScienceDirect
1876-6102 © 2014 Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/3.0/).
Peer-review under responsibility of COE of Sustainalble Energy System, Rajamangala University of Technology Thanyaburi (RMUTT)
doi:10.1016/j.egypro.2014.07.186
11th Eco-Energy and Materials Science and Engineering (11th EMSES)
The Enhanced Performance SVC for Transient Instability
Oscillation Damping
Phinit Srithorna
*, Natthawut Theejanthuekb
a
Rajamangala University of Technology Isan, 744 Suranarai Rd, Muang, Nakhonratchasima,30000, Thailand
b
Synchotron Light Research Institute (Public organization ), Nakhonratchasima,30000, Thailand
Abstract
To utilise green energy, renewables have penetrated into utility. However, its intermittent nature affects on power quality and
network stability. Static var compensators (SVCs) have been installed in order to gain power quality improvement. Nevertheless,
lacking of real power support, the SVCs cannot minimise any instability. This paper presents a technique to provide the SVCs the
ability to enhance their performance. Dynamic oscillation damper is co-located with a typical SVC, offering ability to damp
oscillations. Simulation shows the proposed system performance was greatly enhanced. This envisages future applications,
where a combination of distributed generators and renewables causes severe interaction.
© 2014 The Authors. Published by Elsevier Ltd.
Peer-review under responsibility of COE of Sustainalble Energy System, Rajamangala University of Technology Thanyaburi
(RMUTT).
Keywords: SVC; electromechanical interaction; frequency overshoot; transient instability; renewables disadvantage.
1. Introduction
Over the past ten years, applications of renewable energy in power systems have been the most common issue
mentioned amongst operators, and also encouraged with governmental policies, in order to utilise more green
energy. However the penetration of renewable energy into the grid brings with it an intermittent characteristic that
usually results in power quality problem [1]-[2], and possibly leading to stability concerns. As most of power
* Corresponding author. Tel.: +66(0)-4425-2659; fax: +66(0)-4425-2659.
E-mail address: phinit.sr@rmuti.ac.th
© 2014 Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/3.0/).
Peer-review under responsibility of COE of Sustainalble Energy System, Rajamangala University of Technology Thanyaburi (RMUTT)
Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 511
networks employ rotating generator, which in normal situations its speed and field excitation control system will
able to cope with gradual variations supplying power to loads with a constant frequency and voltage.
But if any transient events like sudden load switching, renewable discontinuing, and fault occurring in the
systems, it is inevitable that generators will have to cope with more stress; generators try to regulate the incoming
mechanical power in order to match its output change. Inside the generator the relevant speed controller, which is
responsible for regulating the system frequency, will try to keep the generator tracking the instant real power change
[3]. However some limitations due to the mechanical movement result in generator delay to respond to an immediate
variation of the electrical output; severe oscillation instability may occur, and can be classified as one of the critical
situations further leading to failure operation of the whole system [3]-[4].
This instability is one of considering problems in the system employing a combination of one distributed
generator and renewables as the main power supply; the system protection may detect the above mentioned
abnormal condition as a problem and separates the involved source components out of the network. Furthermore,
any modern sensitive components may suffer from this swing of the system frequency. Hence, to have an ability to
minimize the transient instability inside the system is one of the most desirable features. Recently this requirement,
in conjunction with the aim to have the system voltage stabilized instantaneously, has introduced the use of flexible
ac transmission system devices (FACTS) in power networks [4]-[8]. Static var compensator (SVC), the ubiquitous
FACTS devices that can perform fast respond to the change in power systems [9]-[11]. Compared with the others,
despite of its voltage dependence, it can be applied without any complicated control system, and installed
inexpensively.
The main objective of this paper is to present a technique to enhance power system dynamic behavior using a
SVC plus a variable power absorber. A typical SVC installed for power quality improvement is incorporated with
the absorber enhancing the overall system operation capability. The attractive feature of this implementation is
highlighted through a tight control of a collaborating process of reactive power compensation and real power support
instantly. To illustrate the enhanced performance, generator interacting to a critical stress due to fault was simulated
using Simulink; the real separate system supplying electrical energy to a sensitive process in synchrotron light
research institute was modelled in the simulation, and was carried out in order to analyze for system security
enhancement. Brief details of why the excess power during transients should be absorbed immediately are also
included in this paper.
2. Dynamic oscillation damping
The system configured with a typical SVC plus a dynamic power absorber unit installed near a generator is
shown in Fig. 1; the generator (G ) and its relevant turbine (TB ) are located at bus 1 supplying the demanded power
to the grid through a feeder line R+jX (a simplified transformer and line impedance) linking to bus 2. The
generator’s ancillary system is modelled as a local load RA shunted at bus 1. Generator’s speed and field excitation
are controlled adequately with standard requirements as described in [3]; speed will be regulated relating to real
power ( P ) transmitted from the generator to load, whilst field excitation will regulate terminal voltage
corresponding to reactive power (Q ) compensated at any time.
In principle, the generator will track the change of output variations in order to keep balance of the incoming
mechanical power ( inP ) and the output electrical power ( outP ) as in (1); lossP is power loss due to the insights of
generator structure and its operation as described in [3]-[4]. If outP is varied (electrical power varied according to
load conditions), the governor will start adjusting input power inP in order to give the generator an ability to track
the change; the overall turbine control system will consequently respond to the modulation command. As a result, if
the change of power flow is not significant, the variation of generator rotating speed will be in an acceptable
behavior; depending on the controls, the system itself will resume back in the intact condition within a short period.
This reaction is the process that the system frequency can be regulated - constant frequency can be seen directly
relating to generators’ speed. Some partial swings may be noticed during this critical period, resulting in accelerated
rotating when inP > outP + lossP , and if inP < outP + lossP the generator rotating will be decelerated [3].
in out lossP P P (1)
512 Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517
Fig. 1. System configuration
However, as mentioned previously, when the system has to deal with any significant power variations like
sudden change of heavy loads and the critical situation due to a fault nearby, generator‘s burden will be changed
immediately. During this obvious transient period, according to mechanical inertia of the turbine ancillary system,
the incoming power will still be fed with the pre-change input; there will be some excess power on the generator at
the moment the fault occurs. Instability spinning can be seen, and can further affect the whole system eventually.
To minimise the mentioned instability behavior, for this project, the SVC consisting of a fixed capacitor (FC) and
a thyristor controlled reactor (TCR) that already installed for a dynamic power quality improvement at bus 1 will be
enhanced by co-locating a dynamic oscillation damping unit as shown in Fig. 1; damping resistor (RD) is used for
dissipating the excess power. In this paper, bus 1 is then set as the point of common coupling (PCC) of the system.
Damping actions will be modulated by adjusting the triggering of anti-parallel SCRs connected series with the
resistor. From the system shown in Fig. 1, the inductor TCRL current will be adjusted according to the control of
reactive power compensation. The fixed capacitor rating can be determined using the same concept as designed for
power factor correction, rated depending on the reactive power ( Q ) to be compensated using (2). And as the
controlled reactor will be used for fine-tune cancellation of this capacitance, the same rating is provided for
calculation of the thyristor controlled reactor as in (3).
2
2
Q
C
fV
(2)
2
cX
L
f
(3)
Damping resistor rating is designed with an approach concerning a mixture of the maximum transferred power
and the rule of thumb that any faster response can be achieved using a higher power resistor for bursting out the
excess energy. For the enhancement, both of the system frequency ( f ) and voltage (V ) have to be monitored and
passed to the controller; errors of these two quantities will be used for providing compensating actions as described
with the conceptual control detailed in the following sections.
3. Control of a dynamic oscillation damping
As the objectives of this project are to regulate the voltage and to enhance the overall system stability during the
transients, voltage regulating will be achieved dynamically by controlling the SVC current; while the dynamic
absorber offers a fast dissipation of the excess power in order to minimise the mentioned instability. Therefore, the
absorber needs a tight control that can provide real power support incorporated with reactive power compensation,
and able to deal with transients precisely. The control concept for the enhanced system is then designed as shown in
Fig.2 and 3.
DDU
Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 513
Fig. 2. Voltage control loop
Fig. 3 Frequency control loop
As illustrated in Fig. 2 the monitored a-b-c frame of reference voltage is transformed to reference frame
before calculating for the error; the voltage is therefore examined instantly. Loop controller will provide the
thyristor controlled reactor firing angle ( TCR ). This compensated angle is then passed to controlling reactive power
compensation. As a consequence, during the transients, SVCI which represents the flow of reactive power will track
the instant change, and resulting in fast regulation of the voltage magnitude. To add the proposed ability in order to
absorb the excess power during the period of fault, system frequency f is monitored and directly passed to the
controller in order to provide a precisely modulated angle for the oscillation damper thyristor.
During the fault oscillation, whenever the system frequency rises up exceeding the nominal value of 50Hz, the
absorbing process will be activated automatically. Although these two control loops are designed to function
independently from each other, damping current ( dampI ) and the SVC current ( SVCI ) will be synchronised with the
instability oscillation. For this project, both the loop controllers are designed and tuned using standard Ziegler –
Nichols heuristic approach [12].
According to the above mentioned, the inductor and capacitor current will be cancelled each other related to
controlling trigger pulse [5]-[8]. The dynamic oscillation damping unit will be controlled according to the system
frequency regulation. Damping current will then be modulated accurately corresponding to generator’s
electromechanical oscillation during the transients. Damping current is indicative of how the excess power being
minimised, which highlights the additional ability of the improved system. The instability oscillation originated
from critical situations in power system will then be minimized instantly.
4. Simulation
A single-line diagram of the power system configured with a typical SVC employed for power quality
improvement is shown in Fig.1, which is conformed with a real distributed system supplying energy to sensitive
equipment. The SVC had been installed at bus 1, where some components may suffer from frequency fluctuations.
Hence, aiming to stabilize this system, the dynamic oscillation dumping was added, and the overall system as shown
in Fig. 1 was modelled in Simulink. Brief details of the important components are listed in Table 1. Both the
standard speed and field excitation control loops for the generator were implemented as explained in [3, 4, 13].
Critical situation caused a fault inside were simulated and described comparatively as in subsection 4.1, 4.2, and 4.3
respectively.
DDU
DDU
514 Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517
Table 1. System components.
Component Details Value
Generator and
turbine
Nominal power
Nominal voltage
Nominal frequency
470kVA
400V
50Hz
Feeder line R+jX 0.03+j0.1885
SVC FC-TCR 350kVar
LOAD Bending magnet 15kW
RA 1kW
RD Damping load resistor 12kW
4.1. System without compensation
The system previously mentioned as shown in Fig. 1, but consisting of power source (generator and turbine with
its ancillary system), feeder line, and load were modelled in Simulink [13]; both the SVC and oscillation damping
unit were not included in the system. Simulation of this uncompensated system was carried out with an impact of a
fault imposed on the system at bus 2. The system voltage magnitude and frequency variation before, during, and
when the fault was cleared are shown in Fig. 4 and 5 respectively.
As expected, the voltage magnitude illustrated in Fig. 4 shows that generator control system can stabilise both the
system voltage and frequency gradually. However, overshoots of the voltage due to a sudden change of the current
can be seen when the fault occurred at time t = 7s; instant drop of the voltage occurred before the generator control
system detected and provided a proper compensation. Also when the fault was cleared at t = 9s, the same excitation
controller responded to the overshoots by adjusting field current; which results in the overshoot mitigated, and
approached the command value within a period of around 2s.
Similarly, the system frequency overshoots occurred during this transient. Although the generator speed loop
detected this variation, but its mechanical slow response caused the overshoots appear as depicted in Fig. 5; the
control functioned to mitigate it, but slowly in process. When the fault was cleared, the generator oscillation
damping process took around 5s to achieve normal frequency value.
Fig. 4 Vpcc of the system without any compensation
Generator acillary and
Local load
Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 515
f
Fig. 5 Frequency of the system without any compensation
4.2. System with a typical SVC
With the aim to stabilise the voltage, a plan to install an ordinary SVC had been considered, and was modelled in
the system at the PCC for simulation and analysis. The relevant results illustrated in Fig. 6, the trace marked “with
SVC”, shows that the SVC able to provide reactive power precisely to the grid, even during situation under stress
due to fault, magnitude of the voltage at PCC was regulated around the set-point instantly. The overshoot of the
voltage was reduced to the demand level by around five times faster than that of the uncompensated system did as
described in subsection 4.1. Only a slight variation appears on PCCV waveform at the time when the fault occurred
and was cleared off as illustrated.
However, in terms of system stability, the trace marked “with SVC“ illustrated in Fig. 7 shows that the ordinary
SVC could not provide an adequate real power support to the system; as can be seen that system frequency was still
being oscillated during and after the fault. Furthermore, during the fault period, the generator had been controlled to
circulate more power in order to keep the voltage stabilised, resulting in an obvious variation of the system
frequency.
Owing to results shown in Fig.7, the ordinary SVC is not a recommended solution for improving this power
system stability, especially during transient events. Therefore, real power support should be prepared to give ability
to coping with instability due to any instant mismatched power to the system.
4.3. System with a typical SVC plus a dynamic oscillation damping
A planned solution for this project to keep the generator operated in a condition that can deal with future critical
situations like fault and load switching is to add a dynamic oscillation damping unit (DDU) co-located with the SVC
installed for power quality improvement as shown in Fig. 1; shunt-connected to the SVC. With these components,
reactive power compensation is modulated by the SVC, while the damping unit is responsible for real power
absorption and results in the waveform marked “with SVC & Dynamic Absorber” shown in Fig. 6 and 7
respectively.
The system voltage was regulated similarly to the result described in previous section (with a typical SVC). Fast
response of the SVC to the voltage change kept the variation of the PCCV in a narrow range, and approaching steady
state within a short period. At the same time, the DDU was controlled to get rid of the excess power instantly. As
described previously, when the excess real power was forcibly passed to the generator, the DDU absorbed that
power immediately. The power was then dissipated correspondingly to generator’s oscillation.
As shown in Fig. 7, with this ability added to the system, frequency overshoot was obviously damped by
approximately five orders of the magnitude. This damped system implies that a smooth running of the generator
during the fault can be seen. However, when the fault was cleared, lacking of an ability to inject real power, fast
change of the system frequency was not minimised as seen during the period from t=9s to 10s of the waveform
shown in Fig. 7. However any instability overshoots after that period was precisely obvious damped.
516 Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517
Fig. 6. Vpcc of the system with and without compensation
Fig. 7 Frequency of the system with and without compensation
5. Conclusion
The combination of a typical SVC and a dynamic oscillation damping unit has been described for enhancing
transient performance of a separate power system in order to cope with an instant imbalance power. Providing this
electronically damping ability aims to compensate for the delay inherited from the mechanical input of the system
generator. The dynamic damping unit works as an energy absorber respecting to electromechanical oscillation of the
source generator. Closed loop controls of the SVC and the co-located absorber have been designed in order to
modulate power circulating between the grid and the SVC. As illustrated, the reactive power loop control has been
achieved the aim to regulate the system voltage. Whilst closed loop control of the oscillation damping unit has been
accomplished using the modulation of thyristor trigger angle, tracking the system frequency, which reflects the
generator swing damped precisely.
From the results it can be said that, during fault, the overall control system provides the combined set ability to
interacting to the critical situation instantly. Not only reactive power was compensated, but also a precise amount of
the excess power was absorbed and dissipated out; clarity of the synchronised damping pattern has been mentioned.
This tuned interaction results in the generator’s oscillation damped electronically and satisfactorily. Also, it can be
concluded that co-locating the typical SVC with the DDU can offer the benefits to power systems, preventing
instability oscillation due to their own inevitably mechanical delay.
Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 517
References
[1] Arai J, Iba K, Funabashi T, Nakanishi Y, Koyanagi K, Yokoyama R. Power electronics and its applications to renewable energy in Japan.
IEEE circuits and systems Magazine: Vol.8: No.3; 2008; p.52-66.
[2] Srithorn P, Aten M, and Parashar R. Series connection of supercapacitor modules for energy storage. IET Power Electronics, Machines and
Drives; 2006.
[3] Kundur P. Power System Stability and Control. McGraw-Hill Inc; 1994.
[4] Srithorn P, Sumner M, Yao Liangzhong, and Parashar R. Power system stabilisation using STATCOM with supercapacitors. IEEE Industry
Applications Society Annual Meeting; 2008, p.1-8.
[5] Acha E, Agelidis V G, Anaya-Lara O, and Miller T J E. Power Electronic Control in Electrical Systems: 1st ed. Newnes; 2002.
[6] Hingorani N G, Gyugyi L. Understanding FACTS: concepts and technology of flexible AC transmission systems. IEEE Press New York;
2000.
[7] Zhang X P, Pal B, and Rehtanz C. Flexible AC transmission systems: modelling and control. Springer Berlin; 2006.
[8] Song Y H, and Johns A T. Flexible ac transmission systems (FACTS). Institution of Electrical Engineers London; 1999.
[9] H. C-T, C. H-J, and C. C-S. Power Quality Assessment of Large Motor Starting and Loading for the Integrated Steel-Making Cogeneration
Facility. IEEE Trans on Industry Applications: Vol.43: No.2: 2007; p.395-402.
[10] Milanovic J V, and Yan Z. Global Minimization of Financial Losses Due to Voltage Sags With FACTS Based Devices. IEEE Trans on
Power Delivery: Vol.25: No. 1; 2010; p.298-306.
[11] Juanjuan W, Chuang F, and Yao Z. SVC Control System Based on Instantaneous Reactive Power Theory and Fuzzy PID. IEEE Trans on
Industry Applications: Vol.55: No.4; 2008; p.1658-1665.
[12] Basilio J C, and Matos S R. Design of PI and PID Controllers with Transient Performance Specification. IEEE Trans on Education: Vol. 45:
No. 4; 2002; p. 364-370.
[13] MATLAB7, Simulink 6.0; The MathWorks Inc; 1986-2006.

More Related Content

What's hot

Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EINext Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Tao Yang
 

What's hot (20)

IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
IRJET- Comparative Study of Common Methods of Frequency Response using MTDC G...
 
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEMLOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
LOAD SHEDDING DESIGN FOR AN INDUSTRIAL COGENERATION SYSTEM
 
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
Flux Based Sensorless Speed Sensing and Real and Reactive Power Flow Control ...
 
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
Improvement of Power Quality in PMSG Based Wind Integrated System using FACTS...
 
0178__Waseda__HCMUT
0178__Waseda__HCMUT0178__Waseda__HCMUT
0178__Waseda__HCMUT
 
40220140505011
4022014050501140220140505011
40220140505011
 
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EINext Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
 
Droop control approach for power sharing in AC microgrid
Droop control approach for power sharing in AC microgrid Droop control approach for power sharing in AC microgrid
Droop control approach for power sharing in AC microgrid
 
Lu3620212028
Lu3620212028Lu3620212028
Lu3620212028
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
Voltage Compensation in Wind Power System using STATCOM Controlled by Soft Co...
 
At4101261265
At4101261265At4101261265
At4101261265
 
Power Quality Problems and Solutions
Power Quality Problems and Solutions Power Quality Problems and Solutions
Power Quality Problems and Solutions
 
Maximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systemsMaximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systems
 
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic ControllerSTATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
STATCOM Based Wind Energy System by using Hybrid Fuzzy Logic Controller
 
Load modelling in distributed generation planning
Load modelling in distributed generation planningLoad modelling in distributed generation planning
Load modelling in distributed generation planning
 
4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter
 
IRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS ControllersIRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS Controllers
 
Microgrid stability and control modes
Microgrid stability and control modes Microgrid stability and control modes
Microgrid stability and control modes
 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
 

Similar to The Enhanced Performance SVC for Transient Instability Oscillation Damping

Development of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization ApproachDevelopment of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization Approach
ijtsrd
 

Similar to The Enhanced Performance SVC for Transient Instability Oscillation Damping (20)

P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPP-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
 
High_reactive_power_DOC.docx
High_reactive_power_DOC.docxHigh_reactive_power_DOC.docx
High_reactive_power_DOC.docx
 
Advance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQCAdvance Technology in Application of Four Leg Inverters to UPQC
Advance Technology in Application of Four Leg Inverters to UPQC
 
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
Stability Improvement in Grid Connected Multi Area System using ANFIS Based S...
 
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
 
Transient Stability Analysis with SSSC and UPFC in Multi-Machine Power System...
Transient Stability Analysis with SSSC and UPFC in Multi-Machine Power System...Transient Stability Analysis with SSSC and UPFC in Multi-Machine Power System...
Transient Stability Analysis with SSSC and UPFC in Multi-Machine Power System...
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
 
Grid_Inertia_and_Frequency_Control_in_Power_Systems_with_High_Penetration_of_...
Grid_Inertia_and_Frequency_Control_in_Power_Systems_with_High_Penetration_of_...Grid_Inertia_and_Frequency_Control_in_Power_Systems_with_High_Penetration_of_...
Grid_Inertia_and_Frequency_Control_in_Power_Systems_with_High_Penetration_of_...
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
 
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQCIRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
IRJET- A Comparison of Power Quality Improvement based on Controls of UPQC
 
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan [IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
[IJET-V1I5P10] Author: K.Dhivya, S.Nirmalrajan
 
Al4201250256
Al4201250256Al4201250256
Al4201250256
 
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll PlazasIRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
IRJET- Level of Service & Throughput Maximization at Operational Toll Plazas
 
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
IRJET- Different Control Strategies for Power Control of Voltage Source Conve...
 
Development of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization ApproachDevelopment of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization Approach
 
Et33879883
Et33879883Et33879883
Et33879883
 
Et33879883
Et33879883Et33879883
Et33879883
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Constant Frequency Operation of a Bulk Power System with Very High Levels of ...
Constant Frequency Operation of a Bulk Power System with Very High Levels of ...Constant Frequency Operation of a Bulk Power System with Very High Levels of ...
Constant Frequency Operation of a Bulk Power System with Very High Levels of ...
 
Swing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capabilitySwing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capability
 

More from Power System Operation

SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
Power System Operation
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
Power System Operation
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
Power System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 

Recently uploaded (20)

Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
fitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .pptfitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .ppt
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 

The Enhanced Performance SVC for Transient Instability Oscillation Damping

  • 1. Energy Procedia 56 (2014) 510 – 517 Available online at www.sciencedirect.com ScienceDirect 1876-6102 © 2014 Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/3.0/). Peer-review under responsibility of COE of Sustainalble Energy System, Rajamangala University of Technology Thanyaburi (RMUTT) doi:10.1016/j.egypro.2014.07.186 11th Eco-Energy and Materials Science and Engineering (11th EMSES) The Enhanced Performance SVC for Transient Instability Oscillation Damping Phinit Srithorna *, Natthawut Theejanthuekb a Rajamangala University of Technology Isan, 744 Suranarai Rd, Muang, Nakhonratchasima,30000, Thailand b Synchotron Light Research Institute (Public organization ), Nakhonratchasima,30000, Thailand Abstract To utilise green energy, renewables have penetrated into utility. However, its intermittent nature affects on power quality and network stability. Static var compensators (SVCs) have been installed in order to gain power quality improvement. Nevertheless, lacking of real power support, the SVCs cannot minimise any instability. This paper presents a technique to provide the SVCs the ability to enhance their performance. Dynamic oscillation damper is co-located with a typical SVC, offering ability to damp oscillations. Simulation shows the proposed system performance was greatly enhanced. This envisages future applications, where a combination of distributed generators and renewables causes severe interaction. © 2014 The Authors. Published by Elsevier Ltd. Peer-review under responsibility of COE of Sustainalble Energy System, Rajamangala University of Technology Thanyaburi (RMUTT). Keywords: SVC; electromechanical interaction; frequency overshoot; transient instability; renewables disadvantage. 1. Introduction Over the past ten years, applications of renewable energy in power systems have been the most common issue mentioned amongst operators, and also encouraged with governmental policies, in order to utilise more green energy. However the penetration of renewable energy into the grid brings with it an intermittent characteristic that usually results in power quality problem [1]-[2], and possibly leading to stability concerns. As most of power * Corresponding author. Tel.: +66(0)-4425-2659; fax: +66(0)-4425-2659. E-mail address: phinit.sr@rmuti.ac.th © 2014 Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/3.0/). Peer-review under responsibility of COE of Sustainalble Energy System, Rajamangala University of Technology Thanyaburi (RMUTT)
  • 2. Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 511 networks employ rotating generator, which in normal situations its speed and field excitation control system will able to cope with gradual variations supplying power to loads with a constant frequency and voltage. But if any transient events like sudden load switching, renewable discontinuing, and fault occurring in the systems, it is inevitable that generators will have to cope with more stress; generators try to regulate the incoming mechanical power in order to match its output change. Inside the generator the relevant speed controller, which is responsible for regulating the system frequency, will try to keep the generator tracking the instant real power change [3]. However some limitations due to the mechanical movement result in generator delay to respond to an immediate variation of the electrical output; severe oscillation instability may occur, and can be classified as one of the critical situations further leading to failure operation of the whole system [3]-[4]. This instability is one of considering problems in the system employing a combination of one distributed generator and renewables as the main power supply; the system protection may detect the above mentioned abnormal condition as a problem and separates the involved source components out of the network. Furthermore, any modern sensitive components may suffer from this swing of the system frequency. Hence, to have an ability to minimize the transient instability inside the system is one of the most desirable features. Recently this requirement, in conjunction with the aim to have the system voltage stabilized instantaneously, has introduced the use of flexible ac transmission system devices (FACTS) in power networks [4]-[8]. Static var compensator (SVC), the ubiquitous FACTS devices that can perform fast respond to the change in power systems [9]-[11]. Compared with the others, despite of its voltage dependence, it can be applied without any complicated control system, and installed inexpensively. The main objective of this paper is to present a technique to enhance power system dynamic behavior using a SVC plus a variable power absorber. A typical SVC installed for power quality improvement is incorporated with the absorber enhancing the overall system operation capability. The attractive feature of this implementation is highlighted through a tight control of a collaborating process of reactive power compensation and real power support instantly. To illustrate the enhanced performance, generator interacting to a critical stress due to fault was simulated using Simulink; the real separate system supplying electrical energy to a sensitive process in synchrotron light research institute was modelled in the simulation, and was carried out in order to analyze for system security enhancement. Brief details of why the excess power during transients should be absorbed immediately are also included in this paper. 2. Dynamic oscillation damping The system configured with a typical SVC plus a dynamic power absorber unit installed near a generator is shown in Fig. 1; the generator (G ) and its relevant turbine (TB ) are located at bus 1 supplying the demanded power to the grid through a feeder line R+jX (a simplified transformer and line impedance) linking to bus 2. The generator’s ancillary system is modelled as a local load RA shunted at bus 1. Generator’s speed and field excitation are controlled adequately with standard requirements as described in [3]; speed will be regulated relating to real power ( P ) transmitted from the generator to load, whilst field excitation will regulate terminal voltage corresponding to reactive power (Q ) compensated at any time. In principle, the generator will track the change of output variations in order to keep balance of the incoming mechanical power ( inP ) and the output electrical power ( outP ) as in (1); lossP is power loss due to the insights of generator structure and its operation as described in [3]-[4]. If outP is varied (electrical power varied according to load conditions), the governor will start adjusting input power inP in order to give the generator an ability to track the change; the overall turbine control system will consequently respond to the modulation command. As a result, if the change of power flow is not significant, the variation of generator rotating speed will be in an acceptable behavior; depending on the controls, the system itself will resume back in the intact condition within a short period. This reaction is the process that the system frequency can be regulated - constant frequency can be seen directly relating to generators’ speed. Some partial swings may be noticed during this critical period, resulting in accelerated rotating when inP > outP + lossP , and if inP < outP + lossP the generator rotating will be decelerated [3]. in out lossP P P (1)
  • 3. 512 Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 Fig. 1. System configuration However, as mentioned previously, when the system has to deal with any significant power variations like sudden change of heavy loads and the critical situation due to a fault nearby, generator‘s burden will be changed immediately. During this obvious transient period, according to mechanical inertia of the turbine ancillary system, the incoming power will still be fed with the pre-change input; there will be some excess power on the generator at the moment the fault occurs. Instability spinning can be seen, and can further affect the whole system eventually. To minimise the mentioned instability behavior, for this project, the SVC consisting of a fixed capacitor (FC) and a thyristor controlled reactor (TCR) that already installed for a dynamic power quality improvement at bus 1 will be enhanced by co-locating a dynamic oscillation damping unit as shown in Fig. 1; damping resistor (RD) is used for dissipating the excess power. In this paper, bus 1 is then set as the point of common coupling (PCC) of the system. Damping actions will be modulated by adjusting the triggering of anti-parallel SCRs connected series with the resistor. From the system shown in Fig. 1, the inductor TCRL current will be adjusted according to the control of reactive power compensation. The fixed capacitor rating can be determined using the same concept as designed for power factor correction, rated depending on the reactive power ( Q ) to be compensated using (2). And as the controlled reactor will be used for fine-tune cancellation of this capacitance, the same rating is provided for calculation of the thyristor controlled reactor as in (3). 2 2 Q C fV (2) 2 cX L f (3) Damping resistor rating is designed with an approach concerning a mixture of the maximum transferred power and the rule of thumb that any faster response can be achieved using a higher power resistor for bursting out the excess energy. For the enhancement, both of the system frequency ( f ) and voltage (V ) have to be monitored and passed to the controller; errors of these two quantities will be used for providing compensating actions as described with the conceptual control detailed in the following sections. 3. Control of a dynamic oscillation damping As the objectives of this project are to regulate the voltage and to enhance the overall system stability during the transients, voltage regulating will be achieved dynamically by controlling the SVC current; while the dynamic absorber offers a fast dissipation of the excess power in order to minimise the mentioned instability. Therefore, the absorber needs a tight control that can provide real power support incorporated with reactive power compensation, and able to deal with transients precisely. The control concept for the enhanced system is then designed as shown in Fig.2 and 3. DDU
  • 4. Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 513 Fig. 2. Voltage control loop Fig. 3 Frequency control loop As illustrated in Fig. 2 the monitored a-b-c frame of reference voltage is transformed to reference frame before calculating for the error; the voltage is therefore examined instantly. Loop controller will provide the thyristor controlled reactor firing angle ( TCR ). This compensated angle is then passed to controlling reactive power compensation. As a consequence, during the transients, SVCI which represents the flow of reactive power will track the instant change, and resulting in fast regulation of the voltage magnitude. To add the proposed ability in order to absorb the excess power during the period of fault, system frequency f is monitored and directly passed to the controller in order to provide a precisely modulated angle for the oscillation damper thyristor. During the fault oscillation, whenever the system frequency rises up exceeding the nominal value of 50Hz, the absorbing process will be activated automatically. Although these two control loops are designed to function independently from each other, damping current ( dampI ) and the SVC current ( SVCI ) will be synchronised with the instability oscillation. For this project, both the loop controllers are designed and tuned using standard Ziegler – Nichols heuristic approach [12]. According to the above mentioned, the inductor and capacitor current will be cancelled each other related to controlling trigger pulse [5]-[8]. The dynamic oscillation damping unit will be controlled according to the system frequency regulation. Damping current will then be modulated accurately corresponding to generator’s electromechanical oscillation during the transients. Damping current is indicative of how the excess power being minimised, which highlights the additional ability of the improved system. The instability oscillation originated from critical situations in power system will then be minimized instantly. 4. Simulation A single-line diagram of the power system configured with a typical SVC employed for power quality improvement is shown in Fig.1, which is conformed with a real distributed system supplying energy to sensitive equipment. The SVC had been installed at bus 1, where some components may suffer from frequency fluctuations. Hence, aiming to stabilize this system, the dynamic oscillation dumping was added, and the overall system as shown in Fig. 1 was modelled in Simulink. Brief details of the important components are listed in Table 1. Both the standard speed and field excitation control loops for the generator were implemented as explained in [3, 4, 13]. Critical situation caused a fault inside were simulated and described comparatively as in subsection 4.1, 4.2, and 4.3 respectively. DDU DDU
  • 5. 514 Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 Table 1. System components. Component Details Value Generator and turbine Nominal power Nominal voltage Nominal frequency 470kVA 400V 50Hz Feeder line R+jX 0.03+j0.1885 SVC FC-TCR 350kVar LOAD Bending magnet 15kW RA 1kW RD Damping load resistor 12kW 4.1. System without compensation The system previously mentioned as shown in Fig. 1, but consisting of power source (generator and turbine with its ancillary system), feeder line, and load were modelled in Simulink [13]; both the SVC and oscillation damping unit were not included in the system. Simulation of this uncompensated system was carried out with an impact of a fault imposed on the system at bus 2. The system voltage magnitude and frequency variation before, during, and when the fault was cleared are shown in Fig. 4 and 5 respectively. As expected, the voltage magnitude illustrated in Fig. 4 shows that generator control system can stabilise both the system voltage and frequency gradually. However, overshoots of the voltage due to a sudden change of the current can be seen when the fault occurred at time t = 7s; instant drop of the voltage occurred before the generator control system detected and provided a proper compensation. Also when the fault was cleared at t = 9s, the same excitation controller responded to the overshoots by adjusting field current; which results in the overshoot mitigated, and approached the command value within a period of around 2s. Similarly, the system frequency overshoots occurred during this transient. Although the generator speed loop detected this variation, but its mechanical slow response caused the overshoots appear as depicted in Fig. 5; the control functioned to mitigate it, but slowly in process. When the fault was cleared, the generator oscillation damping process took around 5s to achieve normal frequency value. Fig. 4 Vpcc of the system without any compensation Generator acillary and Local load
  • 6. Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 515 f Fig. 5 Frequency of the system without any compensation 4.2. System with a typical SVC With the aim to stabilise the voltage, a plan to install an ordinary SVC had been considered, and was modelled in the system at the PCC for simulation and analysis. The relevant results illustrated in Fig. 6, the trace marked “with SVC”, shows that the SVC able to provide reactive power precisely to the grid, even during situation under stress due to fault, magnitude of the voltage at PCC was regulated around the set-point instantly. The overshoot of the voltage was reduced to the demand level by around five times faster than that of the uncompensated system did as described in subsection 4.1. Only a slight variation appears on PCCV waveform at the time when the fault occurred and was cleared off as illustrated. However, in terms of system stability, the trace marked “with SVC“ illustrated in Fig. 7 shows that the ordinary SVC could not provide an adequate real power support to the system; as can be seen that system frequency was still being oscillated during and after the fault. Furthermore, during the fault period, the generator had been controlled to circulate more power in order to keep the voltage stabilised, resulting in an obvious variation of the system frequency. Owing to results shown in Fig.7, the ordinary SVC is not a recommended solution for improving this power system stability, especially during transient events. Therefore, real power support should be prepared to give ability to coping with instability due to any instant mismatched power to the system. 4.3. System with a typical SVC plus a dynamic oscillation damping A planned solution for this project to keep the generator operated in a condition that can deal with future critical situations like fault and load switching is to add a dynamic oscillation damping unit (DDU) co-located with the SVC installed for power quality improvement as shown in Fig. 1; shunt-connected to the SVC. With these components, reactive power compensation is modulated by the SVC, while the damping unit is responsible for real power absorption and results in the waveform marked “with SVC & Dynamic Absorber” shown in Fig. 6 and 7 respectively. The system voltage was regulated similarly to the result described in previous section (with a typical SVC). Fast response of the SVC to the voltage change kept the variation of the PCCV in a narrow range, and approaching steady state within a short period. At the same time, the DDU was controlled to get rid of the excess power instantly. As described previously, when the excess real power was forcibly passed to the generator, the DDU absorbed that power immediately. The power was then dissipated correspondingly to generator’s oscillation. As shown in Fig. 7, with this ability added to the system, frequency overshoot was obviously damped by approximately five orders of the magnitude. This damped system implies that a smooth running of the generator during the fault can be seen. However, when the fault was cleared, lacking of an ability to inject real power, fast change of the system frequency was not minimised as seen during the period from t=9s to 10s of the waveform shown in Fig. 7. However any instability overshoots after that period was precisely obvious damped.
  • 7. 516 Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 Fig. 6. Vpcc of the system with and without compensation Fig. 7 Frequency of the system with and without compensation 5. Conclusion The combination of a typical SVC and a dynamic oscillation damping unit has been described for enhancing transient performance of a separate power system in order to cope with an instant imbalance power. Providing this electronically damping ability aims to compensate for the delay inherited from the mechanical input of the system generator. The dynamic damping unit works as an energy absorber respecting to electromechanical oscillation of the source generator. Closed loop controls of the SVC and the co-located absorber have been designed in order to modulate power circulating between the grid and the SVC. As illustrated, the reactive power loop control has been achieved the aim to regulate the system voltage. Whilst closed loop control of the oscillation damping unit has been accomplished using the modulation of thyristor trigger angle, tracking the system frequency, which reflects the generator swing damped precisely. From the results it can be said that, during fault, the overall control system provides the combined set ability to interacting to the critical situation instantly. Not only reactive power was compensated, but also a precise amount of the excess power was absorbed and dissipated out; clarity of the synchronised damping pattern has been mentioned. This tuned interaction results in the generator’s oscillation damped electronically and satisfactorily. Also, it can be concluded that co-locating the typical SVC with the DDU can offer the benefits to power systems, preventing instability oscillation due to their own inevitably mechanical delay.
  • 8. Phinit Srithorn and Natthawut Theejanthuek / Energy Procedia 56 (2014) 510 – 517 517 References [1] Arai J, Iba K, Funabashi T, Nakanishi Y, Koyanagi K, Yokoyama R. Power electronics and its applications to renewable energy in Japan. IEEE circuits and systems Magazine: Vol.8: No.3; 2008; p.52-66. [2] Srithorn P, Aten M, and Parashar R. Series connection of supercapacitor modules for energy storage. IET Power Electronics, Machines and Drives; 2006. [3] Kundur P. Power System Stability and Control. McGraw-Hill Inc; 1994. [4] Srithorn P, Sumner M, Yao Liangzhong, and Parashar R. Power system stabilisation using STATCOM with supercapacitors. IEEE Industry Applications Society Annual Meeting; 2008, p.1-8. [5] Acha E, Agelidis V G, Anaya-Lara O, and Miller T J E. Power Electronic Control in Electrical Systems: 1st ed. Newnes; 2002. [6] Hingorani N G, Gyugyi L. Understanding FACTS: concepts and technology of flexible AC transmission systems. IEEE Press New York; 2000. [7] Zhang X P, Pal B, and Rehtanz C. Flexible AC transmission systems: modelling and control. Springer Berlin; 2006. [8] Song Y H, and Johns A T. Flexible ac transmission systems (FACTS). Institution of Electrical Engineers London; 1999. [9] H. C-T, C. H-J, and C. C-S. Power Quality Assessment of Large Motor Starting and Loading for the Integrated Steel-Making Cogeneration Facility. IEEE Trans on Industry Applications: Vol.43: No.2: 2007; p.395-402. [10] Milanovic J V, and Yan Z. Global Minimization of Financial Losses Due to Voltage Sags With FACTS Based Devices. IEEE Trans on Power Delivery: Vol.25: No. 1; 2010; p.298-306. [11] Juanjuan W, Chuang F, and Yao Z. SVC Control System Based on Instantaneous Reactive Power Theory and Fuzzy PID. IEEE Trans on Industry Applications: Vol.55: No.4; 2008; p.1658-1665. [12] Basilio J C, and Matos S R. Design of PI and PID Controllers with Transient Performance Specification. IEEE Trans on Education: Vol. 45: No. 4; 2002; p. 364-370. [13] MATLAB7, Simulink 6.0; The MathWorks Inc; 1986-2006.