M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256

RESEARCH ARTICLE

www.ijera.com

OPEN ACCESS

Transient Stability Performance Analysis of Power System Using
Facts Devices
M. Srinivasa Rao1, L. Murali Mohan2
M-Tech Student Scholar, Department Of Electrical And Electronics Engineering, Pydah College Of Engineering
& Technology, Gambheram; Visakhapatnam; A.P, India
Assistant Professor, Project Guide, Department Of Electrical & Electronics Engineering, Pydah College Of
Engineering & Technology, Gambheram; Visakhapatnam; A.P, India

ABSTARCT
Transient stability is increasingly important for secure loading. Transient stability evaluation of large scale
power systems is an extremely intricate and highly non linear problem. An important function of transient
evaluation is to appraise the capability of the power system to with stand serious contingency in time, so that
some emergencies or preventive control can be carried out to prevent system breakdown, the fault current so
produced is diverted to the capacitor by using dual-STATCOM controller, results proved that voltage is
maintained nearly constant, surge currents decreased and oscillations in generator have damped and hence
system stability and continuity of supply are enhanced. If for UPFC, replacing series controller with shunt
controller, it works as dual STATCOM. It has advantages as series pulse controller is not required and same
pulses can be given to both STATCOMs. The shunt controller is so designed to act as low impedance path for
short circuit current, thereby surge currents can be diverted to VSC.
A general program for transient stability studies to incorporate FACTS devices is developed using
MATLAB/SIMULINK.
KEY WORDS: FACTS,power system stability, UPFC,STATCOM.

I.

Introduction

The power system may be thought of as a
large, interconnected nonlinear system with many
lightly damped electromechanical modes of
oscillation. If the damping of these modes becomes
too small or negative, it can impose severe
constraints on the system’s operation. It is thus
important to be able to determine their nature, find
stability limits and in many cases use controls to
prevent their instability.
Local oscillations are observed when one
particular plant swings against the rest of the system
or several generators at frequencies of typically 1 Hz
to 2 Hz. With the power industry moving toward
deregulation, long-distance power transfers are
steadily increasing, outpacing the addition of new
transmission facilities and causing the inter-area
oscillations to become more lightly damped. During
the last decade, FACTS devices have been employed
to damp power system oscillations. Sometimes, these
controllers are placed in the power system for some
other reasons (to improve the voltage stability or to
control power flow), then to damp power oscillations.
However, when installed, supplementary control can
be applied to existing controllers in order to improve
damping, as well as satisfy the primary requirements
of the device. In this paper a new control strategy for
unified power flow controller is proposed. The next
www.ijera.com

section describes the inter area oscillations in the
interconnected power systems. Structure of the
control system of the series part of the UPFC as
described in [12] has been given in section V. In
order to focus on the series part for its effectiveness
for damping, we consider only controlling series
injected voltage for damping control.
It is assumed that the control system has two
supplementary inputs. Further damping enhancement
can be accomplished by adjusting the proportional
gain or adding a supplementary damping signal. The
proposed control strategy has been demonstrated a on
two area 4-generator interconnected test system. .
The simulation results show the effect of active load
change on oscillations. Also It has been shown that
the UPFC with supplementary controller has a
significant impact in damping inter-area system
oscillations.
In this paper a new control strategy for
unified power flow controller is proposed. The next
section describes the inter area oscillations in the
interconnected power systems. Structure of the
control system of the series part of the UPFC as
described in [12] has been given in section V. In
order to focus on the series part for its effectiveness
for damping, we consider only controlling series
injected voltage for damping control. PI-type
regulators control the series injected voltage.
250 | P a g e
M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256
II.

FACTS DEVICS:

Flexible AC Transmission System (FACTS)
is a new integrated concept based on power
electronic switching converters and dynamic
controllers to enhance the system utilization and
power transfer capacity as well as the stability,
security, reliability and power quality of AC system
interconnections. Basic types of facts controllers are
controlled and operated in a way that it balances the
unbalanced voltages, involving transfer of energy
between phases.
1. Objective of the Shunt Controllers
Shunt controllers are similar to the series
controllers with the difference being that they inject
current into the system at the point where they are
connected. Variable shunt impedance connected to a
line causes a variable current flow by injecting a
current into the system. If the injected current is in
phase quadrature with the line voltage, the controller
adjusts reactive power while if the current is not in
phase quadrature, the controller adjusts real power.
Examples of such systems are Static Synchronous
Generator (SSG), Static Var Compensator (SVC).
They can be used as a good way to control the
voltage in and around the point of connection by
injecting active or reactive current into the system.
2. Objective of the Combined Series-Series
Controllers
A combined series-series controller may
have two configurations. One configuration consists
of series controllers operating in a coordinated
manner in a multiline transmission system. The other
configuration provides independent reactive power
control for each line of a multiline transmission
system and, at the same time, facilitates real power
transfer through the power link. An example of this
type of controller is the Interline Power Flow
Controller (IPFC), which helps in balancing both the
real and reactive power flows on the lines.
3. Objective of Combined Series-Shunt Controllers
A combined series-shunt controller may
have two configurations, one being two separate
series and shunt controllers that operate in a
coordinated manner and the other one being
interconnected series and shunt components. In each
configuration, the shunt component injects a current
into the system while the series component injects a
series voltage. When these two elements are unified,
a real power can be exchanged between them via the
power link. Examples of such controllers are UPFC
and Thyristor-Controlled Phase-Shifting Transformer
(TCPST). These make use of the advantages of both
series and shunt controllers and, hence, facilitate

www.ijera.com

www.ijera.com

effective and independent power/current flow and
line voltage control.

III.

INFLUENCE OF INERTIA
COEFFICIENT ON INTERAREA
OSCILLATIONS

A. Inter-area Oscillations A problem of interest in
the power system is the mitigation of inter-area
oscillations that often arise between areas in a large
interconnecting power network [13],[14]. These
oscillations are due to the dynamics of inter-area
power transfer and often exhibit poor damping when
the aggregate power transfer over a corridor is high
relative to the transmission strength [15],[16]. The
oscillation of one or more generators associated with
groups of generators in different areas oscillating
against each other is called inter-area modes. The
frequencies of the oscillations depend on the strength
of the system and on the moment of inertia of the
generator rotors. These frequencies are in the range
of 0.1-1.0Hz, in most practical system. The inter-area
oscillation limits the amount of power transfer on the
tie-lines between the regions containing the groups of
coherent generators.
B. Generator Equations The dynamic behaviour of
generators within a power system is of fundamental
importance to the overall quality of the power supply.
the mechanical equations of a rotating machine are
very well established and they are based on the swing
equations of the rotating inertia. Generator dynamics
is described by [17]. where M is the inertia
coefficient; D is the damping coefficient; Pm is the
mechanical power; Pg is the electrical real power; δ
is the rotor angle and Δω = dδ dt is the rotor speed
deviation. The swing equation relates the machine’s
rotor torque angle to the accelerating torque, which is
the difference between the shaft torque and
electromechanical torque. When there is an
equilibrium between the mechanical shaft and
braking electrical torques, the shaft speed will be
constant. Any imbalances between the torques will
cause the acceleration or deceleration of the machine
according to the lows of motion of a rotating body
[17].

where M is the inertia coefficient; D is the damping
coefficient; Pm is the mechanical power; Pg is the
electrical real power; δ is the rotor angle and Δω = dδ
dt is the rotor speed deviation. The swing equation
relates the machine’s rotor torque angle to the
accelerating torque, which is the difference between
the shaft torque and electromechanical torque. When
there is an equilibrium between the mechanical shaft
and braking electrical torques, the shaft speed will be
251 | P a g e
M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256
constant. Any imbalances between the torques will
cause the acceleration or deceleration of the machine
according to the laws of motion of a rotating body.

where
Tacc : Accelerating torque.
J : Combine moment of inertia of the generator and
turbine.
δm : Mechanical torque angle of the rotor.
t : time.
Tmech : Mechanical torque.
Telec : Electrical torque.
An increasing in the machine inertia constant
decreases both the natural frequency and the damping
ratio. Therefore the synchronous generators with
small coefficient of inertia are preferred for large
interconnected power systems.

IV.

Modeling of STATCOM controller:

The controller for STATCOM is shown in
fig1. The voltage and current are referred from area2
generator represented with Vabc and Iabc. With these
parameters, real and reactive powers are calculated.
These power system is controlled independently by
using transfer functions to derive direct and
quadrature axis voltages. These direct axis voltage
can control real power and quadrature axis will
control the reactive power flow from STATCOM.
The two phase voltages are converted into three
phase (dq -abc) voltages and this reference voltage is
fed to PWM converter to generate pulses to
STATCOM. This controls the direction of current
flow from STATCOM to system or vice-versa based
on difference in voltage magnitude at reference point
at STATCOM DC voltage. If at reference point,
voltage is higher, current will flow to STATCOM
and when at reference point are low, current flows
from STATCOM. The voltage at reference point can
be high due to Ferranti effect or sudden load throw
off, lightning and voltage may decrease due to heavy
loading or due to faults. The aim of STATCOM is
maintain constant voltage magnitude at reference
point, minimise inter-area oscillations
and to
enhance stability and reliability. The results are
compared without STATCOM and with STATCOM
for the circuit shown figure2 and figure 3. A three
phase to ground fault occurs at 0.1 seconds and clears
naturally at 0.2 seconds with fault resistance of 1mJ
respectively between phases and ground. Three
winding transformers are used; primary winding is
connected to area1, secondary winding is connected
to area2 and tertiary winding is connected to
STATCOM1.

www.ijera.com

www.ijera.com

Similarly it is done to STATCOM2. The
transformer voltages on area1 and area2 are 230kV
and on STATCOM side is 20kV. A capacitor of1mF
is connected common to both sides of IGBT based
voltage source inverter.200Amps, when fault
occurred; voltage became nearly zero in area1, where
as in area2, it is 0.5kV and current was500Amps.
When STATCOM is placed as it injects voltage and
current as shown in . It can clearly be seen that fault
current has mitigated and voltage on both sides are
compensated by VSC. The voltage sag is less than
10% and current is almost uniform. There will be
sub-transient and transient current waveforms with
STATCOM controller.The Generator stator voltage
(quadrature and direct axis) are in per unit (pu) and
pu rotor speed is without STATCOM and for area 1
and in area 2 with STATCOM. The stator quadrature
voltage for generator1 in area1 has decreased to
0.75p.u from 1p.u. during this transient time. With
STATCOM, the quadrature and direct axis voltages
are at equilibrium during and after fault.The stator
output current in per unit quantities are with out and
with STATCOM for area1 andarea2 generators.
During equilibrium, stator output current is 0.5A;
during transient is 3.6pu amps on area1 and 2.4pu on
area2 without STATCOM. With placement of
STATCOM, stator current is almost constant. The
sub-transient and transient current can be reduced by
taking a capacitor on VSC less than 3000uF. But it is
not fully capable of mitigating oscillations caused
due to such huge transients. In this analysis, the
capacitor is 10000uF with 10kV rating. DC voltage
across the capacitor bank at Voltage Source
Converter (VSC-STATCOM). The voltage is nearly
8000V dc during normal conditions. When fault
occurred at 0.1s, it has decreased to 7000V. This
stored capacitor voltage is used to compensate the
voltage on the source sides of area 1 and 2. Hence
voltage is compensated .as
The damping’s are very high without STATCOM,
but is very less with it. The ripples formed are due to
the fact that STATCOM capacitor is taking time to
reach steady state.

Fig1 matlab/simulink implementation of STATCOM
controller.
252 | P a g e
M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256
V.

MATLAB MODELEING AND
SIMULATION RESULTS

www.ijera.com

The source of 10000MVA 230KV source block is
connected to the same transmission line which is in pi
connected, which are connected to a three phase
tranformers. PWM voltage source inverter circuits
and a DC capacitor connected at its DC bus. An
IGBT-based PWM inverter is implemented using
Universal bridge block from Power Electronics
subset of PSB. Snubber circuits are connected in
parallel with each IGBT for protection.
Here simulation is carried out for the power system
without compensation and system with compensation
technique.
Rotor speed in pu

Fig.2 Matlab/Simulink power system analysis
without compensation
The fig2 shows the power system with pi
network transmission lines connected to three phase
transformers at section A and section B which are
inter connected to two sources and a three phase fault
is produced in the interconnected system and here
the simulation is carried out without any
compensation to the power system under fault
conditions,this is done to analyse the performance
characteristics of power system under fault
conditions.
Fig4 simulation result of rotor speed in pu
Here the fig4 shows the rotor speed wm in pu
Stator current in pu

Fig5 simulation result of stator current in pu

Fig3 Matlab/Simulink of Proposed power system
analysis with compensation
Fig.2 and Fig3 shows the Matlab/Simulink
Models of power system analysis with out
compensation circuit and with compensation circuit,
along with control circuit. The power circuit as well
as control system are modeled using Power System
Block set and Simulink. A synchronous machine of
13.8kv 200MVA is connected to a transmission line.
www.ijera.com

The fig5 shows the stator current of
synchronous machine
Va in pu

Fig6 simulation result of voltage va in pu
253 | P a g e
M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256
Scope1

www.ijera.com

Scope4

Fig7 simulation result of voltage and current of
generator
The fig7 shows the voltage and current measurement
of generator (13.8kv,200MVA) without
compensation
Scope2 section A

Fig10 simulation result of source voltage and current
of source 10000MVA 230KV
The fig 10 shows the voltage and current
measurement of source of 10000MVA 230 KV
without compensation under 3 phase fault condition.
Rotor speed

Fig8 simulation result of section A pi network
transmission line
The fig8 shows the voltage and current
measurement of section A transmission line without
compensation under 3 phase fault condition
Scope3

Fig11 simulation result of rotor speed in pu after
compensation
Stator current

section B

Fig12 simulation result of stator current in pu after
compensation
Fig9 simulation result of section pi network
transmission line
The fig9 shows the voltage and current
measurent of section transmission line without
compensation under 3 phase fault condition.
www.ijera.com

The fig 12 shows the simulation result of
stator current here the current waveform got balanced
and improved whwn compared to the result without
compensation

254 | P a g e
M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256
ltage va pu

www.ijera.com

The fig16 shows the voltage and current
measurement of section A transmission line with
compensation under 3 phase fault condition the
voltage and current has improved after compensation
Scope3 section B

Fig 13 simulation result of voltage pu
Vf pu

Fig17 simulation result section pi network
transmission line
The fig17 shows the voltage and current
measurement of section B transmission line with
compensation under 3 phase fault condition the
voltage and current has improved after compensation
Fig 14 simulation result of voltage in pu

Scope4

Scope1

Fig15 simulation result of voltage and current of
generator with compensation

Fig18 simulation result of source voltage and current
of source 10000MVA 230KV

The fig15 shows the voltage and current
measurement of generator(13.8kv,200MVA) with
compensation the voltage and current waveforms has
improved without any dampings under 3 phase fault
condition.

Fig18 shows the voltage and current
measurement of source of 10000MVA 230 KV with
compensation under 3 phase fault condition the
voltage and current waveforms are improved and
balanced by compensating.

Scope2 sectionA

Fig16 simulation result of section A pi network
transmission line
www.ijera.com

VI.

CONCLUSION AND FUTURE
SCOPE

This paper has demonstrated how important
it is for a large electrical system to have a well
designed FACTS device so that the system can
operate. If a severe three phase to ground fault occur
in the midpoint of the system, voltage in area1 and
area2 has dropped to zero and the current has
drastically increased, results in large oscillations in
generator real power without any controller. It can be
observed with STATCOM, these oscillations in real
power during such transients were mitigated. The
255 | P a g e
M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications
ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256
system regains its normal state after transients die out
is due to the action of PSS and AVR. If STATCOM
is not available, PSS fail to operate, this leads to
instability and may also cause the generator to
damage if proper action is not taken. In power
stations, the relays will identify such situations and
will trip the system from supplying power.This leads
to load shedding and severe inconvenience to the
customers. It can be observed that surge currents can
be bypassed to STATCOM which helps in
maintaining nearly constant voltage and current.
Working of STATCOM depends on the impedance of
the line, capacitor ratings, voltage that has to
compensate ,MVA rating of STATCOM transformer
and reactive power of the system. Generator stator
current has controlled with STATCOM and surge
currents are mitigated. Different facts devices like
SSSC, TCSR Can also be used for the power system
stability, FUZZY LOGIC techniques can be used for
controlling these FACTS devices for fast operation.

[8]

REFERENCES

[12]

[1]

[2]

[3]

[4]

[5]

[6]

[7]

Michael J. Basler and Richard C. Schaefer,
“Understanding Power System Stability”,
IEEE Trans. On Industry Application, Vol.
44, No. 2, March/April-2008, pp 463-474.
Yuan Yih Hsu and Kan Lee Liou, “Design
of PID power system stabilizers for
synchronous generators” IEEE Trans., 1987,
pp 343-348.
K.R. Padiyar, “Power System Dynamics:
Stability and Control,” Interline Publishing
Pvt. Ltd Bangalore, 1996.
Larsen, E.V, Sanchez-Gasca, J.J, Chow, J.H
and “Concepts for Design of FACTS
Controllers to Damp Power Swings”, IEEE
Trans.Power Syst, Volume: 10, Issue: 2, pp.
948-956, May 1995.
El-Moursi, M. S, Bak-Jensen, B, AbdelRahman, M. H, “Novel STATCOM
Controller for Mitigating SSR and Damping
Power System Oscillations in a Series
Compensated Wind Park,” IEEE Trans.
Power Delivery. vol. 25, no. 2, pp. 429–441,
Feb 2010.
Taheri,H, Shahabi,S, Taheri, Sh, Gholami, A
“Application of Static Synchronous Series
Compensator (SSSC) on Enhancement of
Voltage Stability and Power Oscillation
Damping ,” IEEE Conf, pp. 533 – 539,
2009.
Majumder, R, Pal, B. C, Dufour, C, and
Korba, P, “Design and real time
implementation of robust FACTS controller
for damping inter area oscillation,” IEEE
Trans. Power Syst., vol. 21, no. 2, pp. 809–
816, May 2006.

www.ijera.com

[9]

[10]

[11]

[13]

[14]

[15]

www.ijera.com

Varma, R. K, Auddy, S, and Semsedini, Y,
“Mitigation of sub synchronous resonance in
a series-compensated wind farm using
FACTS controllers,” IEEE Trans. Power
Del., vol. 23, no. 3, pp. 1645–1654, Jul.
2008.
Prasai,A and Divan, D. M, “Zero-energy sag
correctors optimizing dynamic voltage
restorers for industrial applications,” IEEE
Trans. Ind. Appl.,vol. 44, no. 6, pp. 1777–
1784, Nov./Dec. 2008.
Mathur, R.M, and Varma, R.K, “ThyristorBased FACTS Controllers for Electrical
Transmission Systems,” IEEE Press and
Wiley Interscience, New York, USA, Feb.
2002.
A. M .Kulkarni, K. R. Padiyar, “Damping of
power swings using series FACTS
controllers”, International Journal of
Electrical Power and Energy Systems, Vol.
21, no. 7, pp. 475-495, Oct. 1999.
G. N. Pillai, A. Ghosh, A. Joshi, “Torsional
interaction studies on a series compensator
based on solid-state synchronous voltage
source”, Industrial Technology 2000,
Proceedings
of
IEEE
International
Conference on, vol. 2, pp. 179-184, 19-22
Jan. 2000.
B. Han, S. Moon, J. Park, G. Karady,
“Dynamic characteristic analysis of multibridge PWM inverter for SSSC”, Power
Engineering Society Summer Meeting, 2000
IEEE, vol. 3, pp. 1618-1623, 16-20 Jul.
2000.
Jang-Ceol So; Sun IL Mooneun P; JongWoong Choe, “Design of a robust SSSC
supplementary controller to suppress the
SSR in the Series compensated system”,
Power Engineering Society Winter Meeting,
2001 IEEE, vol. 3, pp. 1283-1288, Jan.
2001.
I. Nagarimoo, “Application of static
synchronous series compensator (SSSC) to
stabilization of frequency oscillations in an
interconnected Power system”, Circuits and
Systems, 2001 ISCAS. The 2001 IEEE
International Symposium on, vol. 3, pp 113116, May. 2001.

256 | P a g e

More Related Content

What's hot

Voltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powerVoltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powereSAT Publishing House
 
Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...eSAT Journals
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesDr. Sudhir Kumar Srivastava
 
Power system stability and control using facts devices
Power system stability and control using facts devicesPower system stability and control using facts devices
Power system stability and control using facts devicesAjit Singh Rajawat
 
Voltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideVoltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideeSAT Journals
 
Transient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psatTransient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psateSAT Journals
 
Power system stability
Power  system  stabilityPower  system  stability
Power system stabilityrohit kumar
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
Power System Control
Power System ControlPower System Control
Power System ControlMansoor Magsi
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...IJSRD
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
203definitionclassificationofpowersystemstability
203definitionclassificationofpowersystemstability 203definitionclassificationofpowersystemstability
203definitionclassificationofpowersystemstability Venkata Tadi
 
Power System Stability & Control
Power System Stability & ControlPower System Stability & Control
Power System Stability & ControlAzimah Aziz
 
VFT Application for Asynchronous Power Transfer
VFT Application for Asynchronous Power TransferVFT Application for Asynchronous Power Transfer
VFT Application for Asynchronous Power TransferIDES Editor
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceinventy
 

What's hot (20)

Voltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive powerVoltage collapse mitigation by reactive power
Voltage collapse mitigation by reactive power
 
Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...
 
An Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation TechniquesAn Overview of Facts Devices used for Reactive Power Compensation Techniques
An Overview of Facts Devices used for Reactive Power Compensation Techniques
 
Power system stability and control using facts devices
Power system stability and control using facts devicesPower system stability and control using facts devices
Power system stability and control using facts devices
 
Voltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load sideVoltage collapse mitigation by reactive power compensation at the load side
Voltage collapse mitigation by reactive power compensation at the load side
 
Power System Stablity
Power System StablityPower System Stablity
Power System Stablity
 
Transient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psatTransient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psat
 
FACT devices
FACT devicesFACT devices
FACT devices
 
Power system stability
Power  system  stabilityPower  system  stability
Power system stability
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Power System Control
Power System ControlPower System Control
Power System Control
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
SMALL SIGNAL STABILITY
SMALL SIGNAL STABILITYSMALL SIGNAL STABILITY
SMALL SIGNAL STABILITY
 
SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
203definitionclassificationofpowersystemstability
203definitionclassificationofpowersystemstability 203definitionclassificationofpowersystemstability
203definitionclassificationofpowersystemstability
 
Chapter8
Chapter8Chapter8
Chapter8
 
Power System Stability & Control
Power System Stability & ControlPower System Stability & Control
Power System Stability & Control
 
VFT Application for Asynchronous Power Transfer
VFT Application for Asynchronous Power TransferVFT Application for Asynchronous Power Transfer
VFT Application for Asynchronous Power Transfer
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 

Viewers also liked (20)

At4201308314
At4201308314At4201308314
At4201308314
 
Aj4201235242
Aj4201235242Aj4201235242
Aj4201235242
 
Au4201315330
Au4201315330Au4201315330
Au4201315330
 
Ae4201209213
Ae4201209213Ae4201209213
Ae4201209213
 
Ax4201341346
Ax4201341346Ax4201341346
Ax4201341346
 
Ak4201243249
Ak4201243249Ak4201243249
Ak4201243249
 
H42013944
H42013944H42013944
H42013944
 
B41021318
B41021318B41021318
B41021318
 
Ka3617341739
Ka3617341739Ka3617341739
Ka3617341739
 
Ez35875879
Ez35875879Ez35875879
Ez35875879
 
Fe35907912
Fe35907912Fe35907912
Fe35907912
 
Dw35701704
Dw35701704Dw35701704
Dw35701704
 
Sathya Sai Baba
Sathya Sai BabaSathya Sai Baba
Sathya Sai Baba
 
Desejos
DesejosDesejos
Desejos
 
Encuesta nacional Cifras y Conceptos Canal Capital
Encuesta nacional Cifras y Conceptos Canal CapitalEncuesta nacional Cifras y Conceptos Canal Capital
Encuesta nacional Cifras y Conceptos Canal Capital
 
Ernesto Colman viaja a... Riviera Maya
Ernesto Colman viaja a... Riviera MayaErnesto Colman viaja a... Riviera Maya
Ernesto Colman viaja a... Riviera Maya
 
Militares
MilitaresMilitares
Militares
 
Participación juvenil
Participación juvenil Participación juvenil
Participación juvenil
 
Unidades didacticas departamento_pedagogia
Unidades didacticas departamento_pedagogiaUnidades didacticas departamento_pedagogia
Unidades didacticas departamento_pedagogia
 
Lectura tema 6 lengua
Lectura tema 6 lenguaLectura tema 6 lengua
Lectura tema 6 lengua
 

Similar to Al4201250256

International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Swing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capabilitySwing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capabilityeSAT Publishing House
 
Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...eSAT Journals
 
A Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization TechniquesA Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization TechniquesIJERA Editor
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Editor IJMTER
 
UPFC in order to Enhance the Power System Reliability
UPFC in order to Enhance the Power System ReliabilityUPFC in order to Enhance the Power System Reliability
UPFC in order to Enhance the Power System ReliabilityIJMER
 
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...paperpublications3
 
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...IJMER
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI) International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI) inventionjournals
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system IJECEIAES
 
Reactive power compesation using static syncronous series compensator-A Review
Reactive power compesation using static syncronous series compensator-A ReviewReactive power compesation using static syncronous series compensator-A Review
Reactive power compesation using static syncronous series compensator-A ReviewIRJET Journal
 
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...IJERA Editor
 

Similar to Al4201250256 (20)

International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Swing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capabilitySwing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capability
 
Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...
 
A Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization TechniquesA Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization Techniques
 
Et33879883
Et33879883Et33879883
Et33879883
 
Et33879883
Et33879883Et33879883
Et33879883
 
A350103
A350103A350103
A350103
 
A350103
A350103A350103
A350103
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
 
UPFC in order to Enhance the Power System Reliability
UPFC in order to Enhance the Power System ReliabilityUPFC in order to Enhance the Power System Reliability
UPFC in order to Enhance the Power System Reliability
 
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
 
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
Static Sustenance of Power System Stability Using FLC Based UPFC in SMIB Powe...
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI) International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system
 
Hs3414301435
Hs3414301435Hs3414301435
Hs3414301435
 
Reactive power compesation using static syncronous series compensator-A Review
Reactive power compesation using static syncronous series compensator-A ReviewReactive power compesation using static syncronous series compensator-A Review
Reactive power compesation using static syncronous series compensator-A Review
 
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
 

Recently uploaded

Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersThousandEyes
 
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphSIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphNeo4j
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024Scott Keck-Warren
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticscarlostorres15106
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesSinan KOZAK
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Wonjun Hwang
 
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks..."LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...Fwdays
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsAndrey Dotsenko
 
costume and set research powerpoint presentation
costume and set research powerpoint presentationcostume and set research powerpoint presentation
costume and set research powerpoint presentationphoebematthew05
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machinePadma Pradeep
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Alan Dix
 
Snow Chain-Integrated Tire for a Safe Drive on Winter Roads
Snow Chain-Integrated Tire for a Safe Drive on Winter RoadsSnow Chain-Integrated Tire for a Safe Drive on Winter Roads
Snow Chain-Integrated Tire for a Safe Drive on Winter RoadsHyundai Motor Group
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 

Recently uploaded (20)

Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food Manufacturing
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
 
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge GraphSIEMENS: RAPUNZEL – A Tale About Knowledge Graph
SIEMENS: RAPUNZEL – A Tale About Knowledge Graph
 
DMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special EditionDMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special Edition
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
Unblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen FramesUnblocking The Main Thread Solving ANRs and Frozen Frames
Unblocking The Main Thread Solving ANRs and Frozen Frames
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
 
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks..."LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
costume and set research powerpoint presentation
costume and set research powerpoint presentationcostume and set research powerpoint presentation
costume and set research powerpoint presentation
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machine
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
 
Hot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort Service
Hot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort ServiceHot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort Service
Hot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort Service
 
The transition to renewables in India.pdf
The transition to renewables in India.pdfThe transition to renewables in India.pdf
The transition to renewables in India.pdf
 
Vulnerability_Management_GRC_by Sohang Sengupta.pptx
Vulnerability_Management_GRC_by Sohang Sengupta.pptxVulnerability_Management_GRC_by Sohang Sengupta.pptx
Vulnerability_Management_GRC_by Sohang Sengupta.pptx
 
Snow Chain-Integrated Tire for a Safe Drive on Winter Roads
Snow Chain-Integrated Tire for a Safe Drive on Winter RoadsSnow Chain-Integrated Tire for a Safe Drive on Winter Roads
Snow Chain-Integrated Tire for a Safe Drive on Winter Roads
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 

Al4201250256

  • 1. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 RESEARCH ARTICLE www.ijera.com OPEN ACCESS Transient Stability Performance Analysis of Power System Using Facts Devices M. Srinivasa Rao1, L. Murali Mohan2 M-Tech Student Scholar, Department Of Electrical And Electronics Engineering, Pydah College Of Engineering & Technology, Gambheram; Visakhapatnam; A.P, India Assistant Professor, Project Guide, Department Of Electrical & Electronics Engineering, Pydah College Of Engineering & Technology, Gambheram; Visakhapatnam; A.P, India ABSTARCT Transient stability is increasingly important for secure loading. Transient stability evaluation of large scale power systems is an extremely intricate and highly non linear problem. An important function of transient evaluation is to appraise the capability of the power system to with stand serious contingency in time, so that some emergencies or preventive control can be carried out to prevent system breakdown, the fault current so produced is diverted to the capacitor by using dual-STATCOM controller, results proved that voltage is maintained nearly constant, surge currents decreased and oscillations in generator have damped and hence system stability and continuity of supply are enhanced. If for UPFC, replacing series controller with shunt controller, it works as dual STATCOM. It has advantages as series pulse controller is not required and same pulses can be given to both STATCOMs. The shunt controller is so designed to act as low impedance path for short circuit current, thereby surge currents can be diverted to VSC. A general program for transient stability studies to incorporate FACTS devices is developed using MATLAB/SIMULINK. KEY WORDS: FACTS,power system stability, UPFC,STATCOM. I. Introduction The power system may be thought of as a large, interconnected nonlinear system with many lightly damped electromechanical modes of oscillation. If the damping of these modes becomes too small or negative, it can impose severe constraints on the system’s operation. It is thus important to be able to determine their nature, find stability limits and in many cases use controls to prevent their instability. Local oscillations are observed when one particular plant swings against the rest of the system or several generators at frequencies of typically 1 Hz to 2 Hz. With the power industry moving toward deregulation, long-distance power transfers are steadily increasing, outpacing the addition of new transmission facilities and causing the inter-area oscillations to become more lightly damped. During the last decade, FACTS devices have been employed to damp power system oscillations. Sometimes, these controllers are placed in the power system for some other reasons (to improve the voltage stability or to control power flow), then to damp power oscillations. However, when installed, supplementary control can be applied to existing controllers in order to improve damping, as well as satisfy the primary requirements of the device. In this paper a new control strategy for unified power flow controller is proposed. The next www.ijera.com section describes the inter area oscillations in the interconnected power systems. Structure of the control system of the series part of the UPFC as described in [12] has been given in section V. In order to focus on the series part for its effectiveness for damping, we consider only controlling series injected voltage for damping control. It is assumed that the control system has two supplementary inputs. Further damping enhancement can be accomplished by adjusting the proportional gain or adding a supplementary damping signal. The proposed control strategy has been demonstrated a on two area 4-generator interconnected test system. . The simulation results show the effect of active load change on oscillations. Also It has been shown that the UPFC with supplementary controller has a significant impact in damping inter-area system oscillations. In this paper a new control strategy for unified power flow controller is proposed. The next section describes the inter area oscillations in the interconnected power systems. Structure of the control system of the series part of the UPFC as described in [12] has been given in section V. In order to focus on the series part for its effectiveness for damping, we consider only controlling series injected voltage for damping control. PI-type regulators control the series injected voltage. 250 | P a g e
  • 2. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 II. FACTS DEVICS: Flexible AC Transmission System (FACTS) is a new integrated concept based on power electronic switching converters and dynamic controllers to enhance the system utilization and power transfer capacity as well as the stability, security, reliability and power quality of AC system interconnections. Basic types of facts controllers are controlled and operated in a way that it balances the unbalanced voltages, involving transfer of energy between phases. 1. Objective of the Shunt Controllers Shunt controllers are similar to the series controllers with the difference being that they inject current into the system at the point where they are connected. Variable shunt impedance connected to a line causes a variable current flow by injecting a current into the system. If the injected current is in phase quadrature with the line voltage, the controller adjusts reactive power while if the current is not in phase quadrature, the controller adjusts real power. Examples of such systems are Static Synchronous Generator (SSG), Static Var Compensator (SVC). They can be used as a good way to control the voltage in and around the point of connection by injecting active or reactive current into the system. 2. Objective of the Combined Series-Series Controllers A combined series-series controller may have two configurations. One configuration consists of series controllers operating in a coordinated manner in a multiline transmission system. The other configuration provides independent reactive power control for each line of a multiline transmission system and, at the same time, facilitates real power transfer through the power link. An example of this type of controller is the Interline Power Flow Controller (IPFC), which helps in balancing both the real and reactive power flows on the lines. 3. Objective of Combined Series-Shunt Controllers A combined series-shunt controller may have two configurations, one being two separate series and shunt controllers that operate in a coordinated manner and the other one being interconnected series and shunt components. In each configuration, the shunt component injects a current into the system while the series component injects a series voltage. When these two elements are unified, a real power can be exchanged between them via the power link. Examples of such controllers are UPFC and Thyristor-Controlled Phase-Shifting Transformer (TCPST). These make use of the advantages of both series and shunt controllers and, hence, facilitate www.ijera.com www.ijera.com effective and independent power/current flow and line voltage control. III. INFLUENCE OF INERTIA COEFFICIENT ON INTERAREA OSCILLATIONS A. Inter-area Oscillations A problem of interest in the power system is the mitigation of inter-area oscillations that often arise between areas in a large interconnecting power network [13],[14]. These oscillations are due to the dynamics of inter-area power transfer and often exhibit poor damping when the aggregate power transfer over a corridor is high relative to the transmission strength [15],[16]. The oscillation of one or more generators associated with groups of generators in different areas oscillating against each other is called inter-area modes. The frequencies of the oscillations depend on the strength of the system and on the moment of inertia of the generator rotors. These frequencies are in the range of 0.1-1.0Hz, in most practical system. The inter-area oscillation limits the amount of power transfer on the tie-lines between the regions containing the groups of coherent generators. B. Generator Equations The dynamic behaviour of generators within a power system is of fundamental importance to the overall quality of the power supply. the mechanical equations of a rotating machine are very well established and they are based on the swing equations of the rotating inertia. Generator dynamics is described by [17]. where M is the inertia coefficient; D is the damping coefficient; Pm is the mechanical power; Pg is the electrical real power; δ is the rotor angle and Δω = dδ dt is the rotor speed deviation. The swing equation relates the machine’s rotor torque angle to the accelerating torque, which is the difference between the shaft torque and electromechanical torque. When there is an equilibrium between the mechanical shaft and braking electrical torques, the shaft speed will be constant. Any imbalances between the torques will cause the acceleration or deceleration of the machine according to the lows of motion of a rotating body [17]. where M is the inertia coefficient; D is the damping coefficient; Pm is the mechanical power; Pg is the electrical real power; δ is the rotor angle and Δω = dδ dt is the rotor speed deviation. The swing equation relates the machine’s rotor torque angle to the accelerating torque, which is the difference between the shaft torque and electromechanical torque. When there is an equilibrium between the mechanical shaft and braking electrical torques, the shaft speed will be 251 | P a g e
  • 3. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 constant. Any imbalances between the torques will cause the acceleration or deceleration of the machine according to the laws of motion of a rotating body. where Tacc : Accelerating torque. J : Combine moment of inertia of the generator and turbine. δm : Mechanical torque angle of the rotor. t : time. Tmech : Mechanical torque. Telec : Electrical torque. An increasing in the machine inertia constant decreases both the natural frequency and the damping ratio. Therefore the synchronous generators with small coefficient of inertia are preferred for large interconnected power systems. IV. Modeling of STATCOM controller: The controller for STATCOM is shown in fig1. The voltage and current are referred from area2 generator represented with Vabc and Iabc. With these parameters, real and reactive powers are calculated. These power system is controlled independently by using transfer functions to derive direct and quadrature axis voltages. These direct axis voltage can control real power and quadrature axis will control the reactive power flow from STATCOM. The two phase voltages are converted into three phase (dq -abc) voltages and this reference voltage is fed to PWM converter to generate pulses to STATCOM. This controls the direction of current flow from STATCOM to system or vice-versa based on difference in voltage magnitude at reference point at STATCOM DC voltage. If at reference point, voltage is higher, current will flow to STATCOM and when at reference point are low, current flows from STATCOM. The voltage at reference point can be high due to Ferranti effect or sudden load throw off, lightning and voltage may decrease due to heavy loading or due to faults. The aim of STATCOM is maintain constant voltage magnitude at reference point, minimise inter-area oscillations and to enhance stability and reliability. The results are compared without STATCOM and with STATCOM for the circuit shown figure2 and figure 3. A three phase to ground fault occurs at 0.1 seconds and clears naturally at 0.2 seconds with fault resistance of 1mJ respectively between phases and ground. Three winding transformers are used; primary winding is connected to area1, secondary winding is connected to area2 and tertiary winding is connected to STATCOM1. www.ijera.com www.ijera.com Similarly it is done to STATCOM2. The transformer voltages on area1 and area2 are 230kV and on STATCOM side is 20kV. A capacitor of1mF is connected common to both sides of IGBT based voltage source inverter.200Amps, when fault occurred; voltage became nearly zero in area1, where as in area2, it is 0.5kV and current was500Amps. When STATCOM is placed as it injects voltage and current as shown in . It can clearly be seen that fault current has mitigated and voltage on both sides are compensated by VSC. The voltage sag is less than 10% and current is almost uniform. There will be sub-transient and transient current waveforms with STATCOM controller.The Generator stator voltage (quadrature and direct axis) are in per unit (pu) and pu rotor speed is without STATCOM and for area 1 and in area 2 with STATCOM. The stator quadrature voltage for generator1 in area1 has decreased to 0.75p.u from 1p.u. during this transient time. With STATCOM, the quadrature and direct axis voltages are at equilibrium during and after fault.The stator output current in per unit quantities are with out and with STATCOM for area1 andarea2 generators. During equilibrium, stator output current is 0.5A; during transient is 3.6pu amps on area1 and 2.4pu on area2 without STATCOM. With placement of STATCOM, stator current is almost constant. The sub-transient and transient current can be reduced by taking a capacitor on VSC less than 3000uF. But it is not fully capable of mitigating oscillations caused due to such huge transients. In this analysis, the capacitor is 10000uF with 10kV rating. DC voltage across the capacitor bank at Voltage Source Converter (VSC-STATCOM). The voltage is nearly 8000V dc during normal conditions. When fault occurred at 0.1s, it has decreased to 7000V. This stored capacitor voltage is used to compensate the voltage on the source sides of area 1 and 2. Hence voltage is compensated .as The damping’s are very high without STATCOM, but is very less with it. The ripples formed are due to the fact that STATCOM capacitor is taking time to reach steady state. Fig1 matlab/simulink implementation of STATCOM controller. 252 | P a g e
  • 4. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 V. MATLAB MODELEING AND SIMULATION RESULTS www.ijera.com The source of 10000MVA 230KV source block is connected to the same transmission line which is in pi connected, which are connected to a three phase tranformers. PWM voltage source inverter circuits and a DC capacitor connected at its DC bus. An IGBT-based PWM inverter is implemented using Universal bridge block from Power Electronics subset of PSB. Snubber circuits are connected in parallel with each IGBT for protection. Here simulation is carried out for the power system without compensation and system with compensation technique. Rotor speed in pu Fig.2 Matlab/Simulink power system analysis without compensation The fig2 shows the power system with pi network transmission lines connected to three phase transformers at section A and section B which are inter connected to two sources and a three phase fault is produced in the interconnected system and here the simulation is carried out without any compensation to the power system under fault conditions,this is done to analyse the performance characteristics of power system under fault conditions. Fig4 simulation result of rotor speed in pu Here the fig4 shows the rotor speed wm in pu Stator current in pu Fig5 simulation result of stator current in pu Fig3 Matlab/Simulink of Proposed power system analysis with compensation Fig.2 and Fig3 shows the Matlab/Simulink Models of power system analysis with out compensation circuit and with compensation circuit, along with control circuit. The power circuit as well as control system are modeled using Power System Block set and Simulink. A synchronous machine of 13.8kv 200MVA is connected to a transmission line. www.ijera.com The fig5 shows the stator current of synchronous machine Va in pu Fig6 simulation result of voltage va in pu 253 | P a g e
  • 5. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 Scope1 www.ijera.com Scope4 Fig7 simulation result of voltage and current of generator The fig7 shows the voltage and current measurement of generator (13.8kv,200MVA) without compensation Scope2 section A Fig10 simulation result of source voltage and current of source 10000MVA 230KV The fig 10 shows the voltage and current measurement of source of 10000MVA 230 KV without compensation under 3 phase fault condition. Rotor speed Fig8 simulation result of section A pi network transmission line The fig8 shows the voltage and current measurement of section A transmission line without compensation under 3 phase fault condition Scope3 Fig11 simulation result of rotor speed in pu after compensation Stator current section B Fig12 simulation result of stator current in pu after compensation Fig9 simulation result of section pi network transmission line The fig9 shows the voltage and current measurent of section transmission line without compensation under 3 phase fault condition. www.ijera.com The fig 12 shows the simulation result of stator current here the current waveform got balanced and improved whwn compared to the result without compensation 254 | P a g e
  • 6. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 ltage va pu www.ijera.com The fig16 shows the voltage and current measurement of section A transmission line with compensation under 3 phase fault condition the voltage and current has improved after compensation Scope3 section B Fig 13 simulation result of voltage pu Vf pu Fig17 simulation result section pi network transmission line The fig17 shows the voltage and current measurement of section B transmission line with compensation under 3 phase fault condition the voltage and current has improved after compensation Fig 14 simulation result of voltage in pu Scope4 Scope1 Fig15 simulation result of voltage and current of generator with compensation Fig18 simulation result of source voltage and current of source 10000MVA 230KV The fig15 shows the voltage and current measurement of generator(13.8kv,200MVA) with compensation the voltage and current waveforms has improved without any dampings under 3 phase fault condition. Fig18 shows the voltage and current measurement of source of 10000MVA 230 KV with compensation under 3 phase fault condition the voltage and current waveforms are improved and balanced by compensating. Scope2 sectionA Fig16 simulation result of section A pi network transmission line www.ijera.com VI. CONCLUSION AND FUTURE SCOPE This paper has demonstrated how important it is for a large electrical system to have a well designed FACTS device so that the system can operate. If a severe three phase to ground fault occur in the midpoint of the system, voltage in area1 and area2 has dropped to zero and the current has drastically increased, results in large oscillations in generator real power without any controller. It can be observed with STATCOM, these oscillations in real power during such transients were mitigated. The 255 | P a g e
  • 7. M.Srinivasa Rao et al Int. Journal of Engineering Research and Applications ISSN : 2248-9622, Vol. 4, Issue 2( Version 1), February 2014, pp.250-256 system regains its normal state after transients die out is due to the action of PSS and AVR. If STATCOM is not available, PSS fail to operate, this leads to instability and may also cause the generator to damage if proper action is not taken. In power stations, the relays will identify such situations and will trip the system from supplying power.This leads to load shedding and severe inconvenience to the customers. It can be observed that surge currents can be bypassed to STATCOM which helps in maintaining nearly constant voltage and current. Working of STATCOM depends on the impedance of the line, capacitor ratings, voltage that has to compensate ,MVA rating of STATCOM transformer and reactive power of the system. Generator stator current has controlled with STATCOM and surge currents are mitigated. Different facts devices like SSSC, TCSR Can also be used for the power system stability, FUZZY LOGIC techniques can be used for controlling these FACTS devices for fast operation. [8] REFERENCES [12] [1] [2] [3] [4] [5] [6] [7] Michael J. Basler and Richard C. Schaefer, “Understanding Power System Stability”, IEEE Trans. On Industry Application, Vol. 44, No. 2, March/April-2008, pp 463-474. Yuan Yih Hsu and Kan Lee Liou, “Design of PID power system stabilizers for synchronous generators” IEEE Trans., 1987, pp 343-348. K.R. Padiyar, “Power System Dynamics: Stability and Control,” Interline Publishing Pvt. Ltd Bangalore, 1996. Larsen, E.V, Sanchez-Gasca, J.J, Chow, J.H and “Concepts for Design of FACTS Controllers to Damp Power Swings”, IEEE Trans.Power Syst, Volume: 10, Issue: 2, pp. 948-956, May 1995. El-Moursi, M. S, Bak-Jensen, B, AbdelRahman, M. H, “Novel STATCOM Controller for Mitigating SSR and Damping Power System Oscillations in a Series Compensated Wind Park,” IEEE Trans. Power Delivery. vol. 25, no. 2, pp. 429–441, Feb 2010. Taheri,H, Shahabi,S, Taheri, Sh, Gholami, A “Application of Static Synchronous Series Compensator (SSSC) on Enhancement of Voltage Stability and Power Oscillation Damping ,” IEEE Conf, pp. 533 – 539, 2009. Majumder, R, Pal, B. C, Dufour, C, and Korba, P, “Design and real time implementation of robust FACTS controller for damping inter area oscillation,” IEEE Trans. Power Syst., vol. 21, no. 2, pp. 809– 816, May 2006. www.ijera.com [9] [10] [11] [13] [14] [15] www.ijera.com Varma, R. K, Auddy, S, and Semsedini, Y, “Mitigation of sub synchronous resonance in a series-compensated wind farm using FACTS controllers,” IEEE Trans. Power Del., vol. 23, no. 3, pp. 1645–1654, Jul. 2008. Prasai,A and Divan, D. M, “Zero-energy sag correctors optimizing dynamic voltage restorers for industrial applications,” IEEE Trans. Ind. Appl.,vol. 44, no. 6, pp. 1777– 1784, Nov./Dec. 2008. Mathur, R.M, and Varma, R.K, “ThyristorBased FACTS Controllers for Electrical Transmission Systems,” IEEE Press and Wiley Interscience, New York, USA, Feb. 2002. A. M .Kulkarni, K. R. Padiyar, “Damping of power swings using series FACTS controllers”, International Journal of Electrical Power and Energy Systems, Vol. 21, no. 7, pp. 475-495, Oct. 1999. G. N. Pillai, A. Ghosh, A. Joshi, “Torsional interaction studies on a series compensator based on solid-state synchronous voltage source”, Industrial Technology 2000, Proceedings of IEEE International Conference on, vol. 2, pp. 179-184, 19-22 Jan. 2000. B. Han, S. Moon, J. Park, G. Karady, “Dynamic characteristic analysis of multibridge PWM inverter for SSSC”, Power Engineering Society Summer Meeting, 2000 IEEE, vol. 3, pp. 1618-1623, 16-20 Jul. 2000. Jang-Ceol So; Sun IL Mooneun P; JongWoong Choe, “Design of a robust SSSC supplementary controller to suppress the SSR in the Series compensated system”, Power Engineering Society Winter Meeting, 2001 IEEE, vol. 3, pp. 1283-1288, Jan. 2001. I. Nagarimoo, “Application of static synchronous series compensator (SSSC) to stabilization of frequency oscillations in an interconnected Power system”, Circuits and Systems, 2001 ISCAS. The 2001 IEEE International Symposium on, vol. 3, pp 113116, May. 2001. 256 | P a g e