International Journal of Power Electronics and Drive System (IJPEDS)
Vol. 11, No. 2, June 2020, pp. 931~941
ISSN: 2088-8694, DOI: 10.11591/ijpeds.v11.i2.pp931-941  931
Journal homepage: http://ijpeds.iaescore.com
Stability analysis of photovoltaic system under grid faults
Nivedita Pati1
, Babita Panda2
, Bhagabat Panda3
1,2 School of Electrical Engineering, KIIT University, India
1 Department of Electrical and Electronics Engineering, SIT Bhubaneswar, India
3 Department of Electrical Engineering, PMEC, India
Article Info ABSTRACT
Article history:
Received May 26, 2019
Revised Oct 22, 2019
Accepted Dec 5, 2019
This work includes the establishment of a Photovoltaic system connected to
the grid by means of an inverter. The fundamental goal of the work is to
incorporate an advanced active power flow management scheme in order to
adopt load at any weather condition along with the advantage of maximum
active power flow and zero harmonics from PV inverter to the grid. The
outcome of analysis and control design of grid connected PV inverter using a
Proportional-Integral (PI) control technique is based on synchronous dq
rotating reference frame so as to achieve maximum output voltage and record
the active power. It has been observed that the model provides a better rate of
stability as compared to the existing topology.
Keywords:
Boost converter
MPPT
Photovoltaic model
Proportional-integral controller
Pulse width modulation (PWM) This is an open access article under the CC BY-SA license.
Corresponding Author:
Nivedita Pati,
School of Electrical Engineering, KIIT University,
Bhubanewsar, 751024, India.
Email: nivedita.pati@silicon.ac.in
1. INTRODUCTION
As fossil fuels are depleting day by day, more research is going on harvesting electrical energy from
renewable energy. Among all other renewable energy sources, Solar and wind energies, are the maximum
accessible and dispersed all over the universe. Utilization of photovoltaic (PV) has been rising notably by
virtue of the fast advancement of power electronic techniques. Here the objective of the study is to get the
maximum energy efficiency under the different operating condition and to approach the design of a robust
controller having the ability to reject the noises. The main objective of the study is to coordinate the voltage,
the power injected into the utility. Many earlier works have inspected different control aspects of Inverter
that are connected to the grid. Most of the analysis is done to reduce the THD of the system. But very few of
them focus on stability issues of grid coonected PV system. Different Power quality issues of the grid
connected PV system are described by Vikas khare [1]. The author herself explained about the different types
of fault analysis in grid connected photovoltaic system [2]. M. G. Molina and L. E. Juanico explained the
designing of the photovoltaic structure connected to the grid [3]. The dynamic behavior of grid connected
Photovoltaic system is studied under the LLLG fault by author K. Manohar [4] and [5]. The proposed work
gives the information about a three-phase Pulse Width Modulated inverter modeling and its control strategy.
The single staged grid connected inverter gets its input from a dc-dc converter fed through a photovoltaic
input [6]. Particularly, the control design of grid connected inverter using the PI control technique has been
proposed in the dq rotating frame in order to achieve maximum output voltage and maximum active power.
A current control PWM technique has been suggested to provide the pulse for voltage source inverter.
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941
932
By virtue of the huge amount of interconnection of dispersed power generation to the grid in some
regions, uncertainty and fluctuation of a different parameter of the power system may appear which requires
proper design of controllers for stability analysis under variable conditions [7]. more importance is put on the
capability of a Distributed Power Generation System (DPGS) to overcome sharp grid disruptions such as
variations in voltage and frequency. This paper focuses on some desirable control techniques that DPGS can
follow during damaged grid circumstances. First, a grouping of different kinds of grid faults is illustrated,
and it ensured by some applications of the control technique during damaged grid circumstances. A. V.
Timbus [8] and [9]analyzed some possible control techniques that DPGS can follow during faulty grid
conditions followed by the grouping of different kinds of grid faults in this paper .The primary objective of
the control technique is reproduction of power, and also the generation of the currents referred which can
meet the grid power requirement. M.Cai [10] adopted a shunt controller for voltage dip compensation when a
fault is introduced in the grid. In [11, 12] dynamic stability of a Photovoltaic structure connected with a
distribution system is analyzed. Reference [13] and [14] has adopted a control technique to analyze the
dynamic stability of the PV System.
2. PROPOSED ACTIVE POWER FLOW CONTROL SCHEME FOR STABILITY ANALYSIS
This section describes the internal structure proposed control design which consists of an external
voltage circuit and an internal current circuit [15]. The proposed model is discussed in Figure 1. It consists of
a Solar (PV) system, step up converter, which is then interfaced with an inverter (VSI), a distribution
network, load and grid with a power flow controller. Figure 1 describes the circuit diagram of the
proposed structure.
Figure 1. Block diagram of Grid connected PV system
The suggested structure is built to control the various parameters like current, voltage and power
injected into the utility [16]. The 305 Solar Panel is being selected for designing of PV system using
MATLAB. MPPT approach is employed for enhancing the efficiency of the solar panel. The Perturb &
Observe (P&O) method is selected as the MPPT tracker whose primary goal is to obtain rapid and correct
tracking act and reduces oscillations with respect to changeable weather conditions. P&O method
implementation is quite cheap. The output of the boost converter which is1200 V DC is converted into 800V
AC by a voltage source inverter, then that voltage is increased to 11 KV by a step-up delta/star transformer.
2.1 Internal structure of control system
Figure 2 represents the circuit diagram representation of the control structure. It includes the abc-dq
transformation block, PLL block, PI controller and the PWM generator. The step-up converter to steps up the
voltage of the solar MPPT system while the MPPT generates the pulse for the converter. The PV system and
boost converters are connected to the voltage source converter.
 
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Stability analysis of photovoltaic system under grid faults (Nivedita Pati)
933
Figure 2. Block diagram of internal control structure
The speed of the control loop depends on the bandwidth of the loop. So by varying the cut-off
frequency of open loop transfer function (transfer function of inner loop multiplies with PI transfer function),
the differential speeds can be achieved. Since some of the state variables are multiplied with the control
inputs, the mathematical model of the converter becomes nonlinear.
2.2. DC-link voltage control scheme
The active power is restrained by the voltage at the DC-link with its desired value. Figure 3 shows
the internal structure of the dc-link voltage management strategy. It has six components: MPPT, voltage
compensator, limiter, current components, and integrator. Here dref
u
is a reference DC voltage recorded by
the maximum power point technique [17]. dref
u
correlates with the dc
u and the output signal is fed to the PI
compensator. The compensator sets up dref
i
which is the ref. the current value of the d-axis component. The
current controller sets up actual d-axis current d
i from ref. current value dref
i
and then
)
( d
pv i
i 
is passed
through an integrator which generates dc
u .
Figure 3. Inside structure of DC link voltage control scheme
(1)
(2)
(3)
(4)
(5)
 
 
 
 
 
Modulation 
and 
PWM 
Generator 
   abc 
 
                
               dq 
 
   abc 
 
                
               dq 
   PLL 
DC LINK PI  
CONTROLLER 
  CURRENT PI 
CONTROLLER 
  CURRENT PI 
CONTROLLER 
   wl 
‐wl 
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941
934
Where C is the capacitor, ic is current through the capacitor, ipv is the PV current, udc is the voltage
across DC link, udref the DC voltage reference, id is d-axis component of grid current, idref is it's a
reference value.
2.3. Internal current loop
The d−q transformation matrix is used for the conversion of three-axis grid voltage and current to
the dq reference frame. The AC grid voltage and current are converted into DC values with the help of abc →
dq transformation matrix, by regulating the variables. The phase angle is calculated with the help of PLL
(Phase Lock Loop) [18] which is further required for synchronization of grid voltage with controlled current.
To get the unity power factor, iqref*(reference reactive current) is set to zero. The Proportional-Integral
controllers provide the voltage outputs (Vd*, Vq*) which fed to the PWM generator to generates the pulses
used to for Inverter [19].
቎
Iୢ
I୯
I଴
቏ ൌ ට
ଶ
ଷ
ൈ T ൈ ൥
Iୟ
Iୠ
Iୡ
൩ (6)
By using the above formula given in (6), the abc-dq transformation is made where T is the
transformation matrix.
As the voltage of grid is cannot be managed, the ultimate desirable choice of governing the action of
the arrangement is by regulating the Id and Iq that is injecting to the grid. Figure 4 depicts output of a
compensator (Ud),is the control signal focusing on minimizing error as:
(7)
Correspondingly, the error signal that another regulator processes,
(8)
The error commands are fed to a PI regulator. The PI regulator constants are selected so that,
(9)
(10)
where is the time constant of the circuit. The internal control structure of the system is shown
in Figure 4.
Figure 4. Basic structure of pulse generation scheme
The PWM modulating commands are,
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Stability analysis of photovoltaic system under grid faults (Nivedita Pati)
935
(11)
(12)
Where are d-axis and q-axis factors of modulating commands, Vdc is the voltage at DC
link, are control signals of d-axis and q-axis, Usd, Usq are refined voltage of VSI, is the grid
frequency. The pulses are developed by conversion of d and q signals into a,b,c signals. By regulating md
and mq, the id and iq quickly follow their corresponding reference signals idref and iqref [20]. Then active
and reactive power of Photovoltaic arrangement are given as:
(13)
(14)
As the voltage at the grid is unmanageable, the ultimate practicable approach of monitoring the
arrangement is by regulating grid currents Id and Iq. As active power flow is reliant on the current Id, and
reactive power inserted to the grid is dependent on the current Iq and thus Iqref = 0 is set forcefully to make
zero reactive power [21, 22].
2.4. Simulink environment
The validity of the system is checked with the help of computer simulations. The
MATLAB/SIMULINK software is used to simulate the final system and for unusual circumstances, the
analysis is done. The symmetrical and unsymmetrical faults are created on the distribution network, for the
analysis of system behavior under fault [23].
3. SIMULATION OUTCOMES OF FAULT ANALYSIS
The simulation is conducted in order to achieve stability of the photovoltaic system under different
conditions of grid faults. The transient state stability of the system may be analyzed by many methods; here
some aspects are taken into account. The faults on the grid can be divided into two main groups.
a) Symmetrical fault: When an equal decrease in the magnitude of the grid voltage occurs in all three
phases whereas the system remains balanced. Symmetrical faults are not uncommon (they do happen
often: bus faults, lightning strikes in substations etc).
b) Unsymmetrical fault: When an unequal decrease in grid voltage occurs with alternation in phase in
between. This category of fault arises as more than one phase is shorted to ground or to one another.
The effectiveness of the control system is checked by considering three cases of grid faults. In each
of the cases, the result analysis is carried out that has been recorded for stability analysis [24].
case-1: Three phase to ground fault (LLLG fault): Three phases to ground fault is a familiar fault in the
industrial climate. The outcome of the PV circuit with a LLLG fault of 0.3 sec to 0.4 sec is analyzed in this
section.
case-2: LLG fault in distribution network: In this case, a double line to ground fault is simulated from 0.3
sec to 0.4 sec. When this type of fault occurs a sudden power surge is experienced in the converter. The
voltage of the converter rises rapidly and then recovers with an oscillation that lasts for a few cycles. This
response is generated with the PI controller.
case-3: LG fault in distribution network: In this case, a single line to ground fault is simulated.
The Figure 5 illustrates the Simulation model of the grid connected PV system. The sub-system of
the PV source includes a PV block, MPPT controller along with step up converter interfaced to the grid via
voltage source inverter. Table 1 gives system parameters data and specifications [25]. Here the system is
certified under the least fault circumstances.
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941
936
Figure 5. Simulation model of the proposed system
Table 1. System Parameter and Specifications
Parameter Values Parameter Values
The voltage at the Grid 11KV Vdc 1200V
Supply frequency 50 Hz Fsw_inv 2 kHz
Filter Inductor 10 mH Filter Capacitor 100µF
Inverter voltage 1200V Inverter output voltage after filtering 800V
Three phase line 15 km length Load 5MW,100VAR
3.1. Three phase to ground fault (LLLG fault)
The output waveforms of proposed structure with a LLLG fault are illustrated below. At t=0.3 sec to
0.4 sec, LLLG fault is inserted into the system. Figure 6(a) shows the waveform of DC voltage generated by
the boost converter. Figures 6(b) and 6(c) depict with LLLG fault the nature of 3-phase current and voltage at
the grid. Figures 6(d) and 6(e) show the variation of powers fed to the grid.
Figure 6(a) illustrates the waveform of the DC voltage produced by the step-up converter. Before
the application of the fault, DC voltage attains a value of 1200V. During the fault, DC voltage increases
suddenly from 1200 to 1600V. Just after 0.42 sec, 1200V is achieved.
Figure 6(b) depicts the response of a three-phase current in the course of the three-phase fault.
Ahead of the introduction of fault, current is settled at 5 A. When a fault is introduced at 0.3 sec the current
rises nearly to 180A (max) and certainly the current recovers its steady value of 5 A after the fault period.
Figure 6(c) indicates the nature of three-phase voltages at the time of LLLG fault. Ahead of the
application of fault, voltage is kept at 8KV (max). At the time of application of fault, the voltage at the grid is
zero from 0.3 to 0.4 sec. Later 0.4 sec, voltage settles to its constant value.
Figure 6(d) shows the waveform of active power fed to the grid at the time of the fault period from
0.3 sec to 0.4 sec. In the course of the fault period, both active, as well as reactive power, remains zero. At
0.45 sec power settles to its normal value.
In Figure, 6(e) it is observed that there is a very slight change in reactive power just after 0.4
seconds. Then after some time, it settles to its steady-state value.
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Stability analysis of photovoltaic system under grid faults (Nivedita Pati)
937
(a) (b)
(c) (d)
(e)
Figure 6. (a) DC voltage generated vs.time, (b) 3-phase current vs.time at grid, (c) 3-phase voltage vs .time at
grid, (d) Active power at grid, (e) Reactive power vs. time at the grid with LLLG fault
3.2. LLG fault at distribution network
The Figure 7(a) shows the DC voltage generated by the Step up converter along LLG fault.
Figures 7(b) and 7(c) depict 3-phase current and voltages at the grid along with LLG fault. Figures 7(d) and
7(e) illustrate the changes in active and reactive power. Figure 7(a) shows the DC voltage generated by the
boost converter is disrupted more than LLLG fault. With 0.3 sec DC voltage oscillates between 1200 to
1600V and then decreases to 1200V after the fault. Later at 0.41 sec, voltage settles to its steady-state value.
Figure 7(b) indicates the nature of three-phase voltages during LLG fault. The voltage at the grid is
disturbed from 0.3 to 0.4 sec. After 0.4-sec voltage settles to its regular value.
When a fault is introduced at 0.3 sec the current rises nearly to 100A (max) which is shown in
Figure 7(c). At 0.42 sec, current attains its original value. From Figure 7(d) it is observed that the real and
reactive power inserted to the grid is highly disrupted at the time of the LLG fault of 0.3 sec to 0.4 sec. At
0.43 sec power attains its steady-state value.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-200
-150
-100
-50
0
50
100
150
200
Time (s)
L
in
e
C
urre
nt
(A)
A
B
C
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941
938
Figure 7(e) shows the changes in the reactive power in the course of the fault period. The output
waveform depicts that the reactive power is negative during the fault period. Just after the clearance of fault,
growth is seen, then after some time, it settles to its normal value.
(a) (b)
(c) (d)
(e)
Figure 7. (a) Converter voltage vs. time with LLLG fault, (b) Grid voltage vs. time with LLLG fault
(c) Grid current with LLG fault, (d) Active power at the grid with LLG fault, (e) Reactive power vs. time at
the grid with LLG fault
3.3. LG Fault at distribution network
Figure 8(a) shows the voltage generated by the converter with LG fault. Figures 8(b) and 8(c) show
3-phase current and voltages at the grid with LG fault. Figures 8(d) and 8(e) show changes in active and
reactive power fed to the grid.
Figure 8(a) shows the voltage generated by the converter with LG fault is disturbed less than LLG
fault during the LG fault of 0.3 sec to 0.4 sec. At 0.42 sec the voltage reaches its regular value that is 1200V.
With 0.3 sec DC voltage oscillates between 1200 to 1400V and then decreases to 1200V after the clearance
of fault. After 0.42 sec voltage settles to its regular value. In Figure 8(b), it is shown that in the course of the
LG fault the grid voltage is disturbed from 0.3 to 0.4 sec. After 0.4 sec voltage settles to its regular value.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Time (s)
Voltage
(V)
0 0.1 0.2 0.3 0.4 0.5 0.6
-10
-8
-6
-4
-2
0
2
4
6
8
10
Time (s)
Phase
Voltage
(kV)
A
B
C
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-200
-150
-100
-50
0
50
100
150
200
Time (s)
Line
C
urrent
(A)
A
B
C
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-0.2
-0.1
0
0.1
0.2
0.3
0.4
Time (s)
A
ctive
Po
w
er
(M
W
))
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
0.2
Time (s)
Reactive
Power
(MVAR))
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Stability analysis of photovoltaic system under grid faults (Nivedita Pati)
939
Figure 8(c) depicts the current response for the SLG fault. The current rises from 5 A to 100 A
instantly during the fault. The fault is cleaned 1 sec later and the current grasp the normal value at t = 0.42 s.
Figure 8(d) shows the waveform of active power fed to the grid. It is visible that the power injected
to the grid is less disrupted during the LG fault than the LLG fault from 0.3 sec to 0.4 sec. At 0.42 sec power
attains its steady state value because of the action of a robust controller. Figure 8(e) shows the changes in
reactive power in the course of the fault period. It is less disrupted than LLG fault.
(a) (b)
(c) (d)
(e)
Figure 8. (a) Converter voltage with LG fault, (b), Grid voltage with SLG fault, (c) Grid current with SLG
fault, (d) Active power at the grid with SLG fault, (e) Reactive power at the grid with SLG fault
4. CONCLUSION
Initially, the system is simulated without any fault. The three types of faults are presented and the
impact on the system is studied under the presence of different types of faults. The simulation result is given
below for all types of faults. Nevertheless, there are countless processes to analyze the dynamic stability of
the structure, only important aspects are taken into consideration. This paper describes the effective
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Time (s)
Voltage
(V)
0 0.1 0.2 0.3 0.4 0.5 0.6
-10
-8
-6
-4
-2
0
2
4
6
8
10
Time (s)
Phase
Voltage
(kV)
A
B
C
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-200
-150
-100
-50
0
50
100
150
200
Time (s)
Line
Current
(A)
A
B
C
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-0.2
-0.1
0
0.1
0.2
0.3
0.4
Time (s)
Active
Power
(MW))
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
0.2
Time (s)
R
eactive
Power
(MVAR))
 ISSN: 2088-8694
Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941
940
achievement of the system. In this paper, the structure is certified under the least damaged circumstances i.e.
the symmetrical as well as unsymmetrical fault. Just after the fault, system parameters retain their original
values because of the robustness of the controller. The correctness of the current control scheme is
demonstrated by the result analysis. The output waveform compiled the validity of the used control
techniques since the delivered powers pursue the regular values, provided by the MPPT controller of the PV
system, both in a normal and abnormal condition.
REFERENCES
[1] V.khare, S.Nema, and P.Baredar, "Power quality disturbances in grid connected solar system its prevention",
International Journal of Engineering and Innovative Technology (IJEIT), Vol.1, Issue.5, pp 252-255, 2016.
[2] P. K. Hota, Babita Panda, Bhagabat Panda, "Fault analysis of grid connected photovoltaic system”,
American Journal of Electrical Power and Energy Systems, Vol. 5, No. 4,pp. 35-44, 2016.
[3] M. G. Molina and L. E. Juanico, “Dynamic modeling and control design of an advanced photovoltaic solar system
for distributed generation application”, Journal of Electrical Engineering: Theory and Application (JEETA),
Vol. 1, No. 3, pp.141-150, 2015.
[4] K.Manohar and P.Sobha Rani “MPPT and simulation for a grid-connected photovoltaic system and fault analysis”,
International Journal of Engineering and Science (IJES), Vol.1, Issue.2, pp.158-166, 2014.
[5] L. B. G. Campanhol1, S. A. Oliveira da Silva, V. D. Bacon, A. A. O. Junior, "Three-Phase Grid-Connected PV
System Operating with Feed-Forward Control Loop and Active Power- Line Conditioning Using NPC Inverter",
IECON Annual Conference of the IEEE Industrial Electronics Society, 2016.
[6] V. N. Lal; S. N. Singh “Control and Performance Analysis of a Single-Stage Utility-Scale Grid-Connected PV
System", IEEE Systems Journal, Vol. 11, issue 3, pp. 1601-1611, 2017.
[7] S. Izumi, Y. Karakawa, X. Xin, T. Yamasaki, "Stability Analysis of Power Systems with Photovoltaic Generators",
IEEE Conference on Decision and Control (CDC), 2016.
[8] A.V.Timbus, P.Rodriguez, R.Teodorescu, M.Liserre and F.Blaabjerg, "Control strategies for distributed power
generation systems operating on the faulty grid", IEEE International Symposium on Industrial Electronics,
pp.1601-1607, 2016.
[9] Y.Shi, Lu .Wang, Hui Li, "Control system design and Stability Analysis for a three phase SiC-based Filter-less
Grid-connected PV Inverter", IEEE Applied Power Electronics Conference and Exposition (APEC), 2018.
[10] W.Cai, H. Ren, Y.Jiao, M.Cai, X.Cheng, "Analysis and Simulation for Grid-Connected Photovoltaic System based
on MATLAB", International Conference on Electrical and Control Engineering (ICECE), Yichang, 2011,
pp.63-66.
[11] IEEE, “IEEE standard for interconnecting distributed resources with electric power systems,” Standards
Coordinating Committee, IEEE Standards 1547, 2003.
[12] A.Yazdani, P.P.Dash, "A Control Methodology and Characterization of Dynamics for a Photovoltaic (PV) System
Interfaced with a Distribution Network" IEEE Transactions on Power Delivery, Vol.24, No.3, pp.1538-1551,
July 2009.
[13] F.Blaabjerg, R.Teodorescu, M. Liserre, A.V.Timbus, "Overview of Control and Grid Synchronization for
Distributed Power Generation Systems", IEEE Transactions on Industrial Electronics, Vol.53, No.5, pp.1398-1409,
Oct. 2006.
[14] B.Saritha, E .Chris S, H. Shawn D and C.Jianwu, "Analysis and Control of Photovoltaic System: Application to a
high penetration Case Study", IEEE Systems Journal, Vol.6, No. 2, 2012.
[15] R.Sunny, R.Anto, "Harmonics Control and Performance Analysis of a Grid-Connected Photovoltaic System",
International Conference on Advanced Computing and Communication Systems (ICACCS), Coimbatore,
pp.1-6, 2013.
[16] Z.Dejia, Z.Zhengming, M.Eltawil, Y.Liqiang, "Design and Control of a Three-Phase Grid-connected photovoltaic
System with Developed Maximum Power Point Tracking", Twenty-Third Annual IEEE Applied Power Electronics
Conference and exposition, Austin, TX, pp.973-979, 2008.
[17] S.Meshram, G.Agnihotri, S.Gupta, "An Efficient Constant Current Controller for PV Solar Power Generator
Integrated with the Grid", Fifth IEEE Power India Conference, Murthal, pp.1-6, 2012.
[18] M.F.Schonardie, D.C.Martins, "Application of the dq0 Transformation in the Three-Phase Grid-Connected PV
Systems with Active and Reactive Power Control", IEEE International Conference on Sustainable Energy
Technologies, Singapore, pp. 18-23, 2008.
[19] S. B. Kjaer, J. K. Pedersen, F. Blaabjerg, “A Review of Single-Phase Grid-Connected Inverters for Photovoltaic
Modules”, IEEE Trans. IndAppl., Vol.41, No.5, pp.1292-1306, Sep./Oct. 2005.
[20] J.M.Carrasco, L.G.Franquelo, J.T. Bialasiewicz, E.Galvan, R.C.P.Guisado, M.A.M.Prats, J.I.Leon, N.Moreno-
Alfonso, “Power Electronic Systems for the Grid Integration of Renewable Energy Sources: A survey”,
IEEE Trans.on Ind. Electron, Vol.53, No.4, Aug. 2006, pp.1002-1016.
[21] J.H.R.Enslin, P.J.M.Heskes, “Harmonic Interaction between a Large Number of Distributed Power Inverters and
the Distribution Network”, IEEE Trans. on Power Electron, Vol.19, No.6, pp.1586-1593, Nov. 2004.
[22] N.Srisaen, A.Sangswang, “Effect of PV Grid-Connected System Location on a Distribution System”, Proc. ofIEEE
Asia Pacific Conf. on Circuit and Systems, pp.852-855, Dec. 2006.
Int J Pow Elec & Dri Syst ISSN: 2088-8694 
Stability analysis of photovoltaic system under grid faults (Nivedita Pati)
941
[23] S.A.Lakshmanan, A.Jain, B.S. Rajpurohit, "Grid voltage monitoring techniques for a single phase grid connected
solar PV system", IEEE 6th India International Conference on Power Electronics (IICPE), Kurukshetra,
pp.1-6, 2014.
[24] B.K.Naik, M.Das, T.K.Chatterjee, K.Chatterjee, "Study and implementation of synchronization algorithm in three-
phase grid connected PV system", 3rd International Conference on Recent Advances in Information Technology
(RAIT), Dhanbad, pp.304-309, 2016.
[25] Y.Teng, C.Xiong, C.Li, Z.Zhang, X.Yu, W.Zhang, "Study on harmonic and reactive current detection in grid-
connected PV Power stations", IEEE International Conference on Progress in Informatics and Computing (PIC),
Nanjing, 2015, pp. 433-437.
BIOGRAPHIES OF AUTHORS
Nivedita Pati, received the M.Tech degree from National Institute of Technology, Rourkela,
Odisha, India with a specialization in Control and Automation.
She is currently persuing her PhD in KIIT University and is working as an Assitant Professor
in Silicon Institute of Technology, Bhubaneswar,Odisha, India from 2012.
Her research interest includes Control Systems and Renewable Energy She is a member in
IEEE since last 7 years and has 5 IEEE conference and one journal publication.
Babita Panda received the B.Tech. degree in electrical engineering from the BIET, Bhadrak,
M.Tech and Ph D degree from Kalinga Institute of Industrial Techonology deemed to be
University. She is working as an Assistant Professor in the department of Electrical
Engineering at KIIT university since 16th August 2012.Her research interests include
distributed generation, renewable energy and power Electronics.
Dr. Bhagabat Panda received the Ph.D degree from Utkal University,M.Tech degree from and
B.Tech degree in Electrical Engg from VSSUT Burla, Sambalpur, Odisha. He is working as an
Associate Professor in the department of Electrical Engineering at PME College,
Barhampur.His research interests include distributed generation, renewable energy and power
System.

More Related Content

What's hot

Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsIJMTST Journal
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultselelijjournal
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system IJECEIAES
 
Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...journalBEEI
 
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...ijtsrd
 
Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...
Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...
Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...Francisco Gonzalez-Longatt
 
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EINext Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EITao Yang
 
Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter
Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter
Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter IJECEIAES
 
IRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand GesturesIRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand GesturesIRJET Journal
 

What's hot (19)

Performance improvement of decentralized control for bidirectional converters...
Performance improvement of decentralized control for bidirectional converters...Performance improvement of decentralized control for bidirectional converters...
Performance improvement of decentralized control for bidirectional converters...
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading Conditions
 
Modeling and design of an adaptive control for VSC-HVDC system under paramete...
Modeling and design of an adaptive control for VSC-HVDC system under paramete...Modeling and design of an adaptive control for VSC-HVDC system under paramete...
Modeling and design of an adaptive control for VSC-HVDC system under paramete...
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
J1103035766
J1103035766J1103035766
J1103035766
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system
 
Optimization The Performance of a Synchronization Controller For a 3-Phase Ph...
Optimization The Performance of a Synchronization Controller For a 3-Phase Ph...Optimization The Performance of a Synchronization Controller For a 3-Phase Ph...
Optimization The Performance of a Synchronization Controller For a 3-Phase Ph...
 
Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...Autonomous microgrid based parallel inverters using droop controller for impr...
Autonomous microgrid based parallel inverters using droop controller for impr...
 
Performance enhancement of BLDC motor using PID controller
Performance enhancement of BLDC motor using PID controllerPerformance enhancement of BLDC motor using PID controller
Performance enhancement of BLDC motor using PID controller
 
H1103034350
H1103034350H1103034350
H1103034350
 
A1103030111
A1103030111A1103030111
A1103030111
 
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
Control of Two Stage PV Power System under the Unbalanced Three Phase Grid Vo...
 
M0104198105
M0104198105M0104198105
M0104198105
 
J010417781
J010417781J010417781
J010417781
 
Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...
Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...
Design and Analysis of PID and Fuzzy-PID Controller for Voltage Control of DC...
 
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EINext Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
 
Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...Detailed analysis of grid connected and islanded operation modes based on P/U...
Detailed analysis of grid connected and islanded operation modes based on P/U...
 
Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter
Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter
Adaptive Fuzzy PI Current Control of Grid Interact PV Inverter
 
IRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand GesturesIRJET-Robot Control by using Human Hand Gestures
IRJET-Robot Control by using Human Hand Gestures
 

Similar to Stability analysis of photovoltaic system under grid faults

Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...
Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...
Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...IRJET Journal
 
Power Flow Control for Dc Microgrid Using MPPT Technique
Power Flow Control for Dc Microgrid Using MPPT TechniquePower Flow Control for Dc Microgrid Using MPPT Technique
Power Flow Control for Dc Microgrid Using MPPT TechniqueIRJET Journal
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterjournalBEEI
 
Control strategies for seamless transfer between the grid-connected and isla...
Control strategies for seamless transfer between  the grid-connected and isla...Control strategies for seamless transfer between  the grid-connected and isla...
Control strategies for seamless transfer between the grid-connected and isla...IJECEIAES
 
Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...
Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...
Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...Engnr Kami Zeb
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...IAES-IJPEDS
 
Boukhriss AECE.pdf
Boukhriss AECE.pdfBoukhriss AECE.pdf
Boukhriss AECE.pdfALIBOUKHRISS
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterjournalBEEI
 
An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...
An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...
An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...IRJET Journal
 
Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...IJECEIAES
 
Solar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid systemSolar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid systemIJECEIAES
 
4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filterEditorJST
 
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid SupplyIRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid SupplyIRJET Journal
 

Similar to Stability analysis of photovoltaic system under grid faults (20)

Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...
Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...
Performance of Maximum Power Point Tracking Algorithm based Photovoltaic Arra...
 
Power Flow Control for Dc Microgrid Using MPPT Technique
Power Flow Control for Dc Microgrid Using MPPT TechniquePower Flow Control for Dc Microgrid Using MPPT Technique
Power Flow Control for Dc Microgrid Using MPPT Technique
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
 
Control strategies for seamless transfer between the grid-connected and isla...
Control strategies for seamless transfer between  the grid-connected and isla...Control strategies for seamless transfer between  the grid-connected and isla...
Control strategies for seamless transfer between the grid-connected and isla...
 
Design and Development of Grid-connected Quasi-Z-Source PV Inverter
Design and Development of Grid-connected Quasi-Z-Source PV InverterDesign and Development of Grid-connected Quasi-Z-Source PV Inverter
Design and Development of Grid-connected Quasi-Z-Source PV Inverter
 
Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...
Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...
Design_of_Adaptive_Sliding_Mode_Controller_for_Single-Phase_Grid-Tied_PV_Syst...
 
MPPT & Power Factor Control for Grid Connected PV Systems with Fuzzy Logic Co...
MPPT & Power Factor Control for Grid Connected PV Systems with Fuzzy Logic Co...MPPT & Power Factor Control for Grid Connected PV Systems with Fuzzy Logic Co...
MPPT & Power Factor Control for Grid Connected PV Systems with Fuzzy Logic Co...
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
 
Boukhriss AECE.pdf
Boukhriss AECE.pdfBoukhriss AECE.pdf
Boukhriss AECE.pdf
 
An efficient dynamic power management model for a stand-alone DC Microgrid us...
An efficient dynamic power management model for a stand-alone DC Microgrid us...An efficient dynamic power management model for a stand-alone DC Microgrid us...
An efficient dynamic power management model for a stand-alone DC Microgrid us...
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
 
An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...
An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...
An Overview of MPPT for Photovoltaic Panels Using Various Artificial Intellig...
 
Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...
 
Fuzzy Logic based Maximum Power Point Tracker in Photovoltaic Cell
Fuzzy Logic based Maximum Power Point Tracker in Photovoltaic CellFuzzy Logic based Maximum Power Point Tracker in Photovoltaic Cell
Fuzzy Logic based Maximum Power Point Tracker in Photovoltaic Cell
 
Solar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid systemSolar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid system
 
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
Modeling and Simulation of Grid Connected PV Generation System Using Matlab/S...
 
Advanced Direct Power Control for Grid-connected Distribution Generation Syst...
Advanced Direct Power Control for Grid-connected Distribution Generation Syst...Advanced Direct Power Control for Grid-connected Distribution Generation Syst...
Advanced Direct Power Control for Grid-connected Distribution Generation Syst...
 
Harmonic stability analysis of multi-paralleled 3-phase PV inverters tied to ...
Harmonic stability analysis of multi-paralleled 3-phase PV inverters tied to ...Harmonic stability analysis of multi-paralleled 3-phase PV inverters tied to ...
Harmonic stability analysis of multi-paralleled 3-phase PV inverters tied to ...
 
4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter4.power quality improvement in dg system using shunt active filter
4.power quality improvement in dg system using shunt active filter
 
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid SupplyIRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
IRJET- A Review on Solar based Multilevel Inverter with Three Phase Grid Supply
 

More from International Journal of Power Electronics and Drive Systems

More from International Journal of Power Electronics and Drive Systems (20)

Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...
 
Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...Classification and direction discrimination of faults in transmission lines u...
Classification and direction discrimination of faults in transmission lines u...
 
Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...Integration of artificial neural networks for multi-source energy management ...
Integration of artificial neural networks for multi-source energy management ...
 
Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...Rotating blade faults classification of a rotor-disk-blade system using artif...
Rotating blade faults classification of a rotor-disk-blade system using artif...
 
Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...Artificial bee colony algorithm applied to optimal power flow solution incorp...
Artificial bee colony algorithm applied to optimal power flow solution incorp...
 
Soft computing and IoT based solar tracker
Soft computing and IoT based solar trackerSoft computing and IoT based solar tracker
Soft computing and IoT based solar tracker
 
Comparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farmsComparison of roughness index for Kitka and Koznica wind farms
Comparison of roughness index for Kitka and Koznica wind farms
 
Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...Primary frequency control of large-scale PV-connected multi-machine power sys...
Primary frequency control of large-scale PV-connected multi-machine power sys...
 
Performance of solar modules integrated with reflector
Performance of solar modules integrated with reflectorPerformance of solar modules integrated with reflector
Performance of solar modules integrated with reflector
 
Generator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion systemGenerator and grid side converter control for wind energy conversion system
Generator and grid side converter control for wind energy conversion system
 
Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...Wind speed modeling based on measurement data to predict future wind speed wi...
Wind speed modeling based on measurement data to predict future wind speed wi...
 
Comparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping systemComparison of PV panels MPPT techniques applied to solar water pumping system
Comparison of PV panels MPPT techniques applied to solar water pumping system
 
Prospect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in BangladeshProspect of renewable energy resources in Bangladesh
Prospect of renewable energy resources in Bangladesh
 
A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...A novel optimization of the particle swarm based maximum power point tracking...
A novel optimization of the particle swarm based maximum power point tracking...
 
Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...Voltage stability enhancement for large scale squirrel cage induction generat...
Voltage stability enhancement for large scale squirrel cage induction generat...
 
Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...Electrical and environmental parameters of the performance of polymer solar c...
Electrical and environmental parameters of the performance of polymer solar c...
 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
 
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
 
Simplified cascade multiphase DC-DC buck power converter for low voltage larg...
Simplified cascade multiphase DC-DC buck power converter for low voltage larg...Simplified cascade multiphase DC-DC buck power converter for low voltage larg...
Simplified cascade multiphase DC-DC buck power converter for low voltage larg...
 
Improved 25-level inverter topology with reduced part count for PV grid-tie a...
Improved 25-level inverter topology with reduced part count for PV grid-tie a...Improved 25-level inverter topology with reduced part count for PV grid-tie a...
Improved 25-level inverter topology with reduced part count for PV grid-tie a...
 

Recently uploaded

Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 

Recently uploaded (20)

Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 

Stability analysis of photovoltaic system under grid faults

  • 1. International Journal of Power Electronics and Drive System (IJPEDS) Vol. 11, No. 2, June 2020, pp. 931~941 ISSN: 2088-8694, DOI: 10.11591/ijpeds.v11.i2.pp931-941  931 Journal homepage: http://ijpeds.iaescore.com Stability analysis of photovoltaic system under grid faults Nivedita Pati1 , Babita Panda2 , Bhagabat Panda3 1,2 School of Electrical Engineering, KIIT University, India 1 Department of Electrical and Electronics Engineering, SIT Bhubaneswar, India 3 Department of Electrical Engineering, PMEC, India Article Info ABSTRACT Article history: Received May 26, 2019 Revised Oct 22, 2019 Accepted Dec 5, 2019 This work includes the establishment of a Photovoltaic system connected to the grid by means of an inverter. The fundamental goal of the work is to incorporate an advanced active power flow management scheme in order to adopt load at any weather condition along with the advantage of maximum active power flow and zero harmonics from PV inverter to the grid. The outcome of analysis and control design of grid connected PV inverter using a Proportional-Integral (PI) control technique is based on synchronous dq rotating reference frame so as to achieve maximum output voltage and record the active power. It has been observed that the model provides a better rate of stability as compared to the existing topology. Keywords: Boost converter MPPT Photovoltaic model Proportional-integral controller Pulse width modulation (PWM) This is an open access article under the CC BY-SA license. Corresponding Author: Nivedita Pati, School of Electrical Engineering, KIIT University, Bhubanewsar, 751024, India. Email: nivedita.pati@silicon.ac.in 1. INTRODUCTION As fossil fuels are depleting day by day, more research is going on harvesting electrical energy from renewable energy. Among all other renewable energy sources, Solar and wind energies, are the maximum accessible and dispersed all over the universe. Utilization of photovoltaic (PV) has been rising notably by virtue of the fast advancement of power electronic techniques. Here the objective of the study is to get the maximum energy efficiency under the different operating condition and to approach the design of a robust controller having the ability to reject the noises. The main objective of the study is to coordinate the voltage, the power injected into the utility. Many earlier works have inspected different control aspects of Inverter that are connected to the grid. Most of the analysis is done to reduce the THD of the system. But very few of them focus on stability issues of grid coonected PV system. Different Power quality issues of the grid connected PV system are described by Vikas khare [1]. The author herself explained about the different types of fault analysis in grid connected photovoltaic system [2]. M. G. Molina and L. E. Juanico explained the designing of the photovoltaic structure connected to the grid [3]. The dynamic behavior of grid connected Photovoltaic system is studied under the LLLG fault by author K. Manohar [4] and [5]. The proposed work gives the information about a three-phase Pulse Width Modulated inverter modeling and its control strategy. The single staged grid connected inverter gets its input from a dc-dc converter fed through a photovoltaic input [6]. Particularly, the control design of grid connected inverter using the PI control technique has been proposed in the dq rotating frame in order to achieve maximum output voltage and maximum active power. A current control PWM technique has been suggested to provide the pulse for voltage source inverter.
  • 2.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941 932 By virtue of the huge amount of interconnection of dispersed power generation to the grid in some regions, uncertainty and fluctuation of a different parameter of the power system may appear which requires proper design of controllers for stability analysis under variable conditions [7]. more importance is put on the capability of a Distributed Power Generation System (DPGS) to overcome sharp grid disruptions such as variations in voltage and frequency. This paper focuses on some desirable control techniques that DPGS can follow during damaged grid circumstances. First, a grouping of different kinds of grid faults is illustrated, and it ensured by some applications of the control technique during damaged grid circumstances. A. V. Timbus [8] and [9]analyzed some possible control techniques that DPGS can follow during faulty grid conditions followed by the grouping of different kinds of grid faults in this paper .The primary objective of the control technique is reproduction of power, and also the generation of the currents referred which can meet the grid power requirement. M.Cai [10] adopted a shunt controller for voltage dip compensation when a fault is introduced in the grid. In [11, 12] dynamic stability of a Photovoltaic structure connected with a distribution system is analyzed. Reference [13] and [14] has adopted a control technique to analyze the dynamic stability of the PV System. 2. PROPOSED ACTIVE POWER FLOW CONTROL SCHEME FOR STABILITY ANALYSIS This section describes the internal structure proposed control design which consists of an external voltage circuit and an internal current circuit [15]. The proposed model is discussed in Figure 1. It consists of a Solar (PV) system, step up converter, which is then interfaced with an inverter (VSI), a distribution network, load and grid with a power flow controller. Figure 1 describes the circuit diagram of the proposed structure. Figure 1. Block diagram of Grid connected PV system The suggested structure is built to control the various parameters like current, voltage and power injected into the utility [16]. The 305 Solar Panel is being selected for designing of PV system using MATLAB. MPPT approach is employed for enhancing the efficiency of the solar panel. The Perturb & Observe (P&O) method is selected as the MPPT tracker whose primary goal is to obtain rapid and correct tracking act and reduces oscillations with respect to changeable weather conditions. P&O method implementation is quite cheap. The output of the boost converter which is1200 V DC is converted into 800V AC by a voltage source inverter, then that voltage is increased to 11 KV by a step-up delta/star transformer. 2.1 Internal structure of control system Figure 2 represents the circuit diagram representation of the control structure. It includes the abc-dq transformation block, PLL block, PI controller and the PWM generator. The step-up converter to steps up the voltage of the solar MPPT system while the MPPT generates the pulse for the converter. The PV system and boost converters are connected to the voltage source converter.  
  • 3. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Stability analysis of photovoltaic system under grid faults (Nivedita Pati) 933 Figure 2. Block diagram of internal control structure The speed of the control loop depends on the bandwidth of the loop. So by varying the cut-off frequency of open loop transfer function (transfer function of inner loop multiplies with PI transfer function), the differential speeds can be achieved. Since some of the state variables are multiplied with the control inputs, the mathematical model of the converter becomes nonlinear. 2.2. DC-link voltage control scheme The active power is restrained by the voltage at the DC-link with its desired value. Figure 3 shows the internal structure of the dc-link voltage management strategy. It has six components: MPPT, voltage compensator, limiter, current components, and integrator. Here dref u is a reference DC voltage recorded by the maximum power point technique [17]. dref u correlates with the dc u and the output signal is fed to the PI compensator. The compensator sets up dref i which is the ref. the current value of the d-axis component. The current controller sets up actual d-axis current d i from ref. current value dref i and then ) ( d pv i i  is passed through an integrator which generates dc u . Figure 3. Inside structure of DC link voltage control scheme (1) (2) (3) (4) (5)           Modulation  and  PWM  Generator     abc                                    dq       abc                                    dq     PLL  DC LINK PI   CONTROLLER    CURRENT PI  CONTROLLER    CURRENT PI  CONTROLLER     wl  ‐wl 
  • 4.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941 934 Where C is the capacitor, ic is current through the capacitor, ipv is the PV current, udc is the voltage across DC link, udref the DC voltage reference, id is d-axis component of grid current, idref is it's a reference value. 2.3. Internal current loop The d−q transformation matrix is used for the conversion of three-axis grid voltage and current to the dq reference frame. The AC grid voltage and current are converted into DC values with the help of abc → dq transformation matrix, by regulating the variables. The phase angle is calculated with the help of PLL (Phase Lock Loop) [18] which is further required for synchronization of grid voltage with controlled current. To get the unity power factor, iqref*(reference reactive current) is set to zero. The Proportional-Integral controllers provide the voltage outputs (Vd*, Vq*) which fed to the PWM generator to generates the pulses used to for Inverter [19]. ቎ Iୢ I୯ I଴ ቏ ൌ ට ଶ ଷ ൈ T ൈ ൥ Iୟ Iୠ Iୡ ൩ (6) By using the above formula given in (6), the abc-dq transformation is made where T is the transformation matrix. As the voltage of grid is cannot be managed, the ultimate desirable choice of governing the action of the arrangement is by regulating the Id and Iq that is injecting to the grid. Figure 4 depicts output of a compensator (Ud),is the control signal focusing on minimizing error as: (7) Correspondingly, the error signal that another regulator processes, (8) The error commands are fed to a PI regulator. The PI regulator constants are selected so that, (9) (10) where is the time constant of the circuit. The internal control structure of the system is shown in Figure 4. Figure 4. Basic structure of pulse generation scheme The PWM modulating commands are,
  • 5. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Stability analysis of photovoltaic system under grid faults (Nivedita Pati) 935 (11) (12) Where are d-axis and q-axis factors of modulating commands, Vdc is the voltage at DC link, are control signals of d-axis and q-axis, Usd, Usq are refined voltage of VSI, is the grid frequency. The pulses are developed by conversion of d and q signals into a,b,c signals. By regulating md and mq, the id and iq quickly follow their corresponding reference signals idref and iqref [20]. Then active and reactive power of Photovoltaic arrangement are given as: (13) (14) As the voltage at the grid is unmanageable, the ultimate practicable approach of monitoring the arrangement is by regulating grid currents Id and Iq. As active power flow is reliant on the current Id, and reactive power inserted to the grid is dependent on the current Iq and thus Iqref = 0 is set forcefully to make zero reactive power [21, 22]. 2.4. Simulink environment The validity of the system is checked with the help of computer simulations. The MATLAB/SIMULINK software is used to simulate the final system and for unusual circumstances, the analysis is done. The symmetrical and unsymmetrical faults are created on the distribution network, for the analysis of system behavior under fault [23]. 3. SIMULATION OUTCOMES OF FAULT ANALYSIS The simulation is conducted in order to achieve stability of the photovoltaic system under different conditions of grid faults. The transient state stability of the system may be analyzed by many methods; here some aspects are taken into account. The faults on the grid can be divided into two main groups. a) Symmetrical fault: When an equal decrease in the magnitude of the grid voltage occurs in all three phases whereas the system remains balanced. Symmetrical faults are not uncommon (they do happen often: bus faults, lightning strikes in substations etc). b) Unsymmetrical fault: When an unequal decrease in grid voltage occurs with alternation in phase in between. This category of fault arises as more than one phase is shorted to ground or to one another. The effectiveness of the control system is checked by considering three cases of grid faults. In each of the cases, the result analysis is carried out that has been recorded for stability analysis [24]. case-1: Three phase to ground fault (LLLG fault): Three phases to ground fault is a familiar fault in the industrial climate. The outcome of the PV circuit with a LLLG fault of 0.3 sec to 0.4 sec is analyzed in this section. case-2: LLG fault in distribution network: In this case, a double line to ground fault is simulated from 0.3 sec to 0.4 sec. When this type of fault occurs a sudden power surge is experienced in the converter. The voltage of the converter rises rapidly and then recovers with an oscillation that lasts for a few cycles. This response is generated with the PI controller. case-3: LG fault in distribution network: In this case, a single line to ground fault is simulated. The Figure 5 illustrates the Simulation model of the grid connected PV system. The sub-system of the PV source includes a PV block, MPPT controller along with step up converter interfaced to the grid via voltage source inverter. Table 1 gives system parameters data and specifications [25]. Here the system is certified under the least fault circumstances.
  • 6.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941 936 Figure 5. Simulation model of the proposed system Table 1. System Parameter and Specifications Parameter Values Parameter Values The voltage at the Grid 11KV Vdc 1200V Supply frequency 50 Hz Fsw_inv 2 kHz Filter Inductor 10 mH Filter Capacitor 100µF Inverter voltage 1200V Inverter output voltage after filtering 800V Three phase line 15 km length Load 5MW,100VAR 3.1. Three phase to ground fault (LLLG fault) The output waveforms of proposed structure with a LLLG fault are illustrated below. At t=0.3 sec to 0.4 sec, LLLG fault is inserted into the system. Figure 6(a) shows the waveform of DC voltage generated by the boost converter. Figures 6(b) and 6(c) depict with LLLG fault the nature of 3-phase current and voltage at the grid. Figures 6(d) and 6(e) show the variation of powers fed to the grid. Figure 6(a) illustrates the waveform of the DC voltage produced by the step-up converter. Before the application of the fault, DC voltage attains a value of 1200V. During the fault, DC voltage increases suddenly from 1200 to 1600V. Just after 0.42 sec, 1200V is achieved. Figure 6(b) depicts the response of a three-phase current in the course of the three-phase fault. Ahead of the introduction of fault, current is settled at 5 A. When a fault is introduced at 0.3 sec the current rises nearly to 180A (max) and certainly the current recovers its steady value of 5 A after the fault period. Figure 6(c) indicates the nature of three-phase voltages at the time of LLLG fault. Ahead of the application of fault, voltage is kept at 8KV (max). At the time of application of fault, the voltage at the grid is zero from 0.3 to 0.4 sec. Later 0.4 sec, voltage settles to its constant value. Figure 6(d) shows the waveform of active power fed to the grid at the time of the fault period from 0.3 sec to 0.4 sec. In the course of the fault period, both active, as well as reactive power, remains zero. At 0.45 sec power settles to its normal value. In Figure, 6(e) it is observed that there is a very slight change in reactive power just after 0.4 seconds. Then after some time, it settles to its steady-state value.
  • 7. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Stability analysis of photovoltaic system under grid faults (Nivedita Pati) 937 (a) (b) (c) (d) (e) Figure 6. (a) DC voltage generated vs.time, (b) 3-phase current vs.time at grid, (c) 3-phase voltage vs .time at grid, (d) Active power at grid, (e) Reactive power vs. time at the grid with LLLG fault 3.2. LLG fault at distribution network The Figure 7(a) shows the DC voltage generated by the Step up converter along LLG fault. Figures 7(b) and 7(c) depict 3-phase current and voltages at the grid along with LLG fault. Figures 7(d) and 7(e) illustrate the changes in active and reactive power. Figure 7(a) shows the DC voltage generated by the boost converter is disrupted more than LLLG fault. With 0.3 sec DC voltage oscillates between 1200 to 1600V and then decreases to 1200V after the fault. Later at 0.41 sec, voltage settles to its steady-state value. Figure 7(b) indicates the nature of three-phase voltages during LLG fault. The voltage at the grid is disturbed from 0.3 to 0.4 sec. After 0.4-sec voltage settles to its regular value. When a fault is introduced at 0.3 sec the current rises nearly to 100A (max) which is shown in Figure 7(c). At 0.42 sec, current attains its original value. From Figure 7(d) it is observed that the real and reactive power inserted to the grid is highly disrupted at the time of the LLG fault of 0.3 sec to 0.4 sec. At 0.43 sec power attains its steady-state value. 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -200 -150 -100 -50 0 50 100 150 200 Time (s) L in e C urre nt (A) A B C
  • 8.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941 938 Figure 7(e) shows the changes in the reactive power in the course of the fault period. The output waveform depicts that the reactive power is negative during the fault period. Just after the clearance of fault, growth is seen, then after some time, it settles to its normal value. (a) (b) (c) (d) (e) Figure 7. (a) Converter voltage vs. time with LLLG fault, (b) Grid voltage vs. time with LLLG fault (c) Grid current with LLG fault, (d) Active power at the grid with LLG fault, (e) Reactive power vs. time at the grid with LLG fault 3.3. LG Fault at distribution network Figure 8(a) shows the voltage generated by the converter with LG fault. Figures 8(b) and 8(c) show 3-phase current and voltages at the grid with LG fault. Figures 8(d) and 8(e) show changes in active and reactive power fed to the grid. Figure 8(a) shows the voltage generated by the converter with LG fault is disturbed less than LLG fault during the LG fault of 0.3 sec to 0.4 sec. At 0.42 sec the voltage reaches its regular value that is 1200V. With 0.3 sec DC voltage oscillates between 1200 to 1400V and then decreases to 1200V after the clearance of fault. After 0.42 sec voltage settles to its regular value. In Figure 8(b), it is shown that in the course of the LG fault the grid voltage is disturbed from 0.3 to 0.4 sec. After 0.4 sec voltage settles to its regular value. 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 200 400 600 800 1000 1200 1400 1600 1800 2000 Time (s) Voltage (V) 0 0.1 0.2 0.3 0.4 0.5 0.6 -10 -8 -6 -4 -2 0 2 4 6 8 10 Time (s) Phase Voltage (kV) A B C 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -200 -150 -100 -50 0 50 100 150 200 Time (s) Line C urrent (A) A B C 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -0.2 -0.1 0 0.1 0.2 0.3 0.4 Time (s) A ctive Po w er (M W )) 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -0.2 -0.15 -0.1 -0.05 0 0.05 0.1 0.15 0.2 Time (s) Reactive Power (MVAR))
  • 9. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Stability analysis of photovoltaic system under grid faults (Nivedita Pati) 939 Figure 8(c) depicts the current response for the SLG fault. The current rises from 5 A to 100 A instantly during the fault. The fault is cleaned 1 sec later and the current grasp the normal value at t = 0.42 s. Figure 8(d) shows the waveform of active power fed to the grid. It is visible that the power injected to the grid is less disrupted during the LG fault than the LLG fault from 0.3 sec to 0.4 sec. At 0.42 sec power attains its steady state value because of the action of a robust controller. Figure 8(e) shows the changes in reactive power in the course of the fault period. It is less disrupted than LLG fault. (a) (b) (c) (d) (e) Figure 8. (a) Converter voltage with LG fault, (b), Grid voltage with SLG fault, (c) Grid current with SLG fault, (d) Active power at the grid with SLG fault, (e) Reactive power at the grid with SLG fault 4. CONCLUSION Initially, the system is simulated without any fault. The three types of faults are presented and the impact on the system is studied under the presence of different types of faults. The simulation result is given below for all types of faults. Nevertheless, there are countless processes to analyze the dynamic stability of the structure, only important aspects are taken into consideration. This paper describes the effective 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 200 400 600 800 1000 1200 1400 1600 1800 2000 Time (s) Voltage (V) 0 0.1 0.2 0.3 0.4 0.5 0.6 -10 -8 -6 -4 -2 0 2 4 6 8 10 Time (s) Phase Voltage (kV) A B C 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -200 -150 -100 -50 0 50 100 150 200 Time (s) Line Current (A) A B C 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -0.2 -0.1 0 0.1 0.2 0.3 0.4 Time (s) Active Power (MW)) 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 -0.2 -0.15 -0.1 -0.05 0 0.05 0.1 0.15 0.2 Time (s) R eactive Power (MVAR))
  • 10.  ISSN: 2088-8694 Int J Pow Elec & Dri Syst, Vol. 11, No. 2, June 2020 : 931 – 941 940 achievement of the system. In this paper, the structure is certified under the least damaged circumstances i.e. the symmetrical as well as unsymmetrical fault. Just after the fault, system parameters retain their original values because of the robustness of the controller. The correctness of the current control scheme is demonstrated by the result analysis. The output waveform compiled the validity of the used control techniques since the delivered powers pursue the regular values, provided by the MPPT controller of the PV system, both in a normal and abnormal condition. REFERENCES [1] V.khare, S.Nema, and P.Baredar, "Power quality disturbances in grid connected solar system its prevention", International Journal of Engineering and Innovative Technology (IJEIT), Vol.1, Issue.5, pp 252-255, 2016. [2] P. K. Hota, Babita Panda, Bhagabat Panda, "Fault analysis of grid connected photovoltaic system”, American Journal of Electrical Power and Energy Systems, Vol. 5, No. 4,pp. 35-44, 2016. [3] M. G. Molina and L. E. Juanico, “Dynamic modeling and control design of an advanced photovoltaic solar system for distributed generation application”, Journal of Electrical Engineering: Theory and Application (JEETA), Vol. 1, No. 3, pp.141-150, 2015. [4] K.Manohar and P.Sobha Rani “MPPT and simulation for a grid-connected photovoltaic system and fault analysis”, International Journal of Engineering and Science (IJES), Vol.1, Issue.2, pp.158-166, 2014. [5] L. B. G. Campanhol1, S. A. Oliveira da Silva, V. D. Bacon, A. A. O. Junior, "Three-Phase Grid-Connected PV System Operating with Feed-Forward Control Loop and Active Power- Line Conditioning Using NPC Inverter", IECON Annual Conference of the IEEE Industrial Electronics Society, 2016. [6] V. N. Lal; S. N. Singh “Control and Performance Analysis of a Single-Stage Utility-Scale Grid-Connected PV System", IEEE Systems Journal, Vol. 11, issue 3, pp. 1601-1611, 2017. [7] S. Izumi, Y. Karakawa, X. Xin, T. Yamasaki, "Stability Analysis of Power Systems with Photovoltaic Generators", IEEE Conference on Decision and Control (CDC), 2016. [8] A.V.Timbus, P.Rodriguez, R.Teodorescu, M.Liserre and F.Blaabjerg, "Control strategies for distributed power generation systems operating on the faulty grid", IEEE International Symposium on Industrial Electronics, pp.1601-1607, 2016. [9] Y.Shi, Lu .Wang, Hui Li, "Control system design and Stability Analysis for a three phase SiC-based Filter-less Grid-connected PV Inverter", IEEE Applied Power Electronics Conference and Exposition (APEC), 2018. [10] W.Cai, H. Ren, Y.Jiao, M.Cai, X.Cheng, "Analysis and Simulation for Grid-Connected Photovoltaic System based on MATLAB", International Conference on Electrical and Control Engineering (ICECE), Yichang, 2011, pp.63-66. [11] IEEE, “IEEE standard for interconnecting distributed resources with electric power systems,” Standards Coordinating Committee, IEEE Standards 1547, 2003. [12] A.Yazdani, P.P.Dash, "A Control Methodology and Characterization of Dynamics for a Photovoltaic (PV) System Interfaced with a Distribution Network" IEEE Transactions on Power Delivery, Vol.24, No.3, pp.1538-1551, July 2009. [13] F.Blaabjerg, R.Teodorescu, M. Liserre, A.V.Timbus, "Overview of Control and Grid Synchronization for Distributed Power Generation Systems", IEEE Transactions on Industrial Electronics, Vol.53, No.5, pp.1398-1409, Oct. 2006. [14] B.Saritha, E .Chris S, H. Shawn D and C.Jianwu, "Analysis and Control of Photovoltaic System: Application to a high penetration Case Study", IEEE Systems Journal, Vol.6, No. 2, 2012. [15] R.Sunny, R.Anto, "Harmonics Control and Performance Analysis of a Grid-Connected Photovoltaic System", International Conference on Advanced Computing and Communication Systems (ICACCS), Coimbatore, pp.1-6, 2013. [16] Z.Dejia, Z.Zhengming, M.Eltawil, Y.Liqiang, "Design and Control of a Three-Phase Grid-connected photovoltaic System with Developed Maximum Power Point Tracking", Twenty-Third Annual IEEE Applied Power Electronics Conference and exposition, Austin, TX, pp.973-979, 2008. [17] S.Meshram, G.Agnihotri, S.Gupta, "An Efficient Constant Current Controller for PV Solar Power Generator Integrated with the Grid", Fifth IEEE Power India Conference, Murthal, pp.1-6, 2012. [18] M.F.Schonardie, D.C.Martins, "Application of the dq0 Transformation in the Three-Phase Grid-Connected PV Systems with Active and Reactive Power Control", IEEE International Conference on Sustainable Energy Technologies, Singapore, pp. 18-23, 2008. [19] S. B. Kjaer, J. K. Pedersen, F. Blaabjerg, “A Review of Single-Phase Grid-Connected Inverters for Photovoltaic Modules”, IEEE Trans. IndAppl., Vol.41, No.5, pp.1292-1306, Sep./Oct. 2005. [20] J.M.Carrasco, L.G.Franquelo, J.T. Bialasiewicz, E.Galvan, R.C.P.Guisado, M.A.M.Prats, J.I.Leon, N.Moreno- Alfonso, “Power Electronic Systems for the Grid Integration of Renewable Energy Sources: A survey”, IEEE Trans.on Ind. Electron, Vol.53, No.4, Aug. 2006, pp.1002-1016. [21] J.H.R.Enslin, P.J.M.Heskes, “Harmonic Interaction between a Large Number of Distributed Power Inverters and the Distribution Network”, IEEE Trans. on Power Electron, Vol.19, No.6, pp.1586-1593, Nov. 2004. [22] N.Srisaen, A.Sangswang, “Effect of PV Grid-Connected System Location on a Distribution System”, Proc. ofIEEE Asia Pacific Conf. on Circuit and Systems, pp.852-855, Dec. 2006.
  • 11. Int J Pow Elec & Dri Syst ISSN: 2088-8694  Stability analysis of photovoltaic system under grid faults (Nivedita Pati) 941 [23] S.A.Lakshmanan, A.Jain, B.S. Rajpurohit, "Grid voltage monitoring techniques for a single phase grid connected solar PV system", IEEE 6th India International Conference on Power Electronics (IICPE), Kurukshetra, pp.1-6, 2014. [24] B.K.Naik, M.Das, T.K.Chatterjee, K.Chatterjee, "Study and implementation of synchronization algorithm in three- phase grid connected PV system", 3rd International Conference on Recent Advances in Information Technology (RAIT), Dhanbad, pp.304-309, 2016. [25] Y.Teng, C.Xiong, C.Li, Z.Zhang, X.Yu, W.Zhang, "Study on harmonic and reactive current detection in grid- connected PV Power stations", IEEE International Conference on Progress in Informatics and Computing (PIC), Nanjing, 2015, pp. 433-437. BIOGRAPHIES OF AUTHORS Nivedita Pati, received the M.Tech degree from National Institute of Technology, Rourkela, Odisha, India with a specialization in Control and Automation. She is currently persuing her PhD in KIIT University and is working as an Assitant Professor in Silicon Institute of Technology, Bhubaneswar,Odisha, India from 2012. Her research interest includes Control Systems and Renewable Energy She is a member in IEEE since last 7 years and has 5 IEEE conference and one journal publication. Babita Panda received the B.Tech. degree in electrical engineering from the BIET, Bhadrak, M.Tech and Ph D degree from Kalinga Institute of Industrial Techonology deemed to be University. She is working as an Assistant Professor in the department of Electrical Engineering at KIIT university since 16th August 2012.Her research interests include distributed generation, renewable energy and power Electronics. Dr. Bhagabat Panda received the Ph.D degree from Utkal University,M.Tech degree from and B.Tech degree in Electrical Engg from VSSUT Burla, Sambalpur, Odisha. He is working as an Associate Professor in the department of Electrical Engineering at PME College, Barhampur.His research interests include distributed generation, renewable energy and power System.