SlideShare a Scribd company logo
1 of 19
Copyright ยฉ P. Kundur
This material should not be used without the author's consent
POWER SYSTEM LOADS
15316k
15396k
PSL - 1
Load Modelling
1. Basic load modelling concepts
2. Static load models
3. Dynamic load models
4. Induction motors
5. Synchronous motors
6. Acquisition of load model
parameters
15396k
PSL - 2
Load Modelling
๏ฌ A typical load bus represented in stability studies is
composed of a large number of devices:
๏† fluorescent and incandescent lamps, refrigerators,
heaters, compressors, furnaces, and so on
๏ฌ The composition changes depending on many
factors, including:
๏† time
๏† weather conditions
๏† state of the economy
๏ฌ The exact composition at any particular time is
difficult to estimate. Even if the load composition
were known, it would be impractical to represent
each individual component.
๏ฌ For the above reasons, load representation is based
on considerable amount of simplification.
15396k
PSL - 3
Basic Load Modelling Concepts
๏ฌ The aggregated load is usually represented at a
transmission substation
๏† includes, in addition to the connected load
devices, the effects of step-down transformers,
subtransmission and distribution feeders, voltage
regulators, and VAr compensation
๏ฌ Load models are traditionally classified into:
๏† static load models
๏† dynamic load models
Fig. 7.1 Power system configuration identifying parts of the system represented as
load at a bulk power delivery point (Bus A)
15396k
PSL - 4
Static Load Models
๏ฌ Express the load characteristics as algebraic functions
of bus voltage magnitude and frequency.
๏ฌ Traditionally, voltage dependency has been
represented by the exponential model:
P0, Q0, and V0 are the values of the respective variables
at the initial operating condition.
For composite loads,
๏† exponent "a" ranges between 0.5 and 1.8
๏† exponent "b" ranges between 1.5 and 6
The exponent "b" is a nonlinear function of voltage.
This is caused by magnetic saturation of distribution
transformers and motors.
๏€จ ๏€ฉ
๏€จ ๏€ฉ
0
0
0
V
V
V
VQQ
VPP
b
a
๏€ฝ
๏€ฝ
๏€ฝ
15396k
PSL - 5
๏ฌ An alternative static model widely used is the
polynomial model:
This model is commonly referred to as the "ZIP" model,
as it is composed of constant impedance (Z), constant
current (I), and constant power (P) components.
๏ฌ The frequency dependency of load characteristics is
usually represented by multiplying the exponential or
polynomial model by a factor:
For example,
where ฮ”f is the frequency deviation (f-f0). Typically, Kpf
ranges from 0 to 3.0, and Kqf ranges from -2.0 to 0.
๏ฌ Response of most loads is fast and steady state
reached quickly, at least for modest changes in V and f.
๏† use of static model justified in such cases
๏› ๏ ๏€จ ๏€ฉ
๏› ๏ ๏€จ ๏€ฉfKqVqVqQQ
fKpVpVpPP
qf
pf
๏„
๏„
๏€ซ๏€ซ๏€ซ๏€ฝ
๏€ซ๏€ซ๏€ซ๏€ฝ
1
1
32
2
10
32
2
10
๏› ๏
๏› ๏32
2
10
32
2
10
qVqVqQQ
pVpVpPP
๏€ซ๏€ซ๏€ฝ
๏€ซ๏€ซ๏€ฝ
15396k
PSL - 6
Dynamic Load Models
๏ฌ In many cases, it is necessary to account for the
dynamics of loads. For example, studies of
๏† inter-area oscillations and voltage stability
๏† systems with large concentrations of motors
๏ฌ Typically, motors consume 60% to 70% of total energy
supplied by a power system
๏† dynamics attributable to motors are usually the
most significant aspects
๏ฌ Other dynamic aspects of load components include:
๏† Extinction of discharge (mercury vapour, sodium
vapour, fluorescent) lamps when voltage drops
below 0.7 to 0.8 pu and their restart after 1 or 2
seconds delay when voltage recovers.
๏† Operation of protective relays. For example, starter
contractors of industrial motors drop open when
voltage drops below 0.55 to 0.75 pu.
๏† Thermostatic control of loads such as space
heaters/coolers, water heaters and refrigerators -
operate longer during low voltages and hence, total
number of devices increase in a few minutes.
๏† Response of ULTCs on distribution transformers
and voltage regulators
15396k
PSL - 7
๏ฌ Composite model which represents the wide range of
characteristics exhibited by various load components:
๏ฌ A simple model for thermostatically controlled loads:
LH
H
PP
dt
d
K ๏€ญ๏€ฝ
๏ด
where
๏œ H = temperature of heated area
๏œ A = ambient temperature
PH = power from the heater = KHGV2
PL = heat loss by escape to ambient area = KA (๏œH- ๏œ A)
G = load conductance
The dynamic equation of a heating device may be written
as:
15396k
PSL - 8
Induction Motor
๏ฌ Carries alternating current in both stator and rotor
windings
๏† rotor windings are either short-circuited internally
or connected through slip rings to a passive
external circuit
๏ฌ The distinctive feature is that the rotor currents are
induced by electromagnetic induction.
๏ฌ The stator windings of a 3-phase induction machine
are similar to those of a synchronous machine
๏† produces a field rotating at synchronous speed
when balanced currents are applied
๏ฌ When there is a relative motion between the stator
field and the rotor, voltages and currents are
inducted in the rotor windings
๏† the frequency of the induced rotor voltages
depends on the slip speed
๏ฌ At no load, the machine operates with negligible slip.
If a mechanical load is applied, the slip increases.
15396k
PSL - 9
Modelling of Induction Motors
๏ฌ The general procedure is similar to that of a
synchronous machine
๏† first write basic equations in terms of phase (a,b,c)
variables
๏† then, transform equations into 'dq' reference
frame
๏ฌ In developing the model of an induction motor it is
worth noting the following of its features which differ
from those of the synchronous machine:
๏† rotor has a symmetrical structure; hence, d and q
axis equivalent circuits are identical
๏† rotor speed is not fixed; this has an impact on the
selection of dq reference frame
๏† there is no excitation source applied to the rotor;
consequently the rotor circuit dynamics are
determined by slip rather than by excitation
control.
๏† currents induced in shorted rotor windings
produce a field with the same number of poles as
in the stator; therefore, rotor windings may be
represented by equivalent 3-phase winding
15396k
PSL - 10
๏ฌ The 'dq' transformation:
๏† the preferred reference frame is one with axes
rotating at synchronous speed, rather than at rotor
speed
๏ฌ The machine equations in dq reference frame:
Stator flux linkages:
Rotor flux linkages:
Stator voltages:
Rotor voltages:
๏† The term pฮธr is the slip angular velocity and
represents the relative angular velocity between
the rotor and the reference dq axes.
qrmqsssqs
drmdsssds
iLiL
iLiL
๏€ซ๏€ฝ
๏€ซ๏€ฝ
๏™
๏™
qsmqrrrqr
dsmdrrrdr
iLiL
iLiL
๏€ซ๏€ฝ
๏€ซ๏€ฝ
๏™
๏™
qsdssqssqs
dsqssdssds
piRV
piRV
๏™๏™๏ท
๏™๏™๏ท
๏€ซ๏€ซ๏€ฝ
๏€ซ๏€ญ๏€ฝ
๏€จ ๏€ฉ
๏€จ ๏€ฉ qrdrrqrrqr
drqrrdrrdr
ppiRV
ppiRV
๏™๏™๏ฑ
๏™๏™๏ฑ
๏€ซ๏€ซ๏€ฝ
๏€ซ๏€ญ๏€ฝ
15396k
PSL - 11
๏ฌ For representation in stability studies, and are
neglected
๏† same as for synchronous machines, this
simplification is essential to ensure consistent models
used for network and induction motors
๏ฌ With the stator transients neglected, the per unit
induction motor electrical equations may be
summarized as:
Stator voltages in phasor form:
Rotor circuit dynamics:
Rotor acceleration equation:
Representation of an Induction Motor in
Stability Studies
dsp๏™ qsp๏™
๏€จ ๏€ฉ๏€จ ๏€ฉ ๏€จ ๏€ฉqdqsdsssqsds vjvjiiXjRjvv ๏‚ข๏€ซ๏‚ข๏€ซ๏€ซ๏‚ข๏€ซ๏€ฝ๏€ซ
๏€จ ๏€ฉ ๏€จ ๏€ฉ๏› ๏ qrqsssdd vpiXXv
T
vp ๏‚ข๏€ซ๏‚ข๏€ญ๏€ซ๏‚ข
๏‚ข
๏€ญ๏€ฝ๏‚ข ๏ฑ
0
1
๏€จ ๏€ฉ ๏€จ ๏€ฉ๏› ๏ drdsssqq vpiXXv
T
vp ๏‚ข๏€ญ๏€ญ๏€ญ๏‚ข
๏‚ข
๏€ญ๏€ฝ๏‚ข ๏ฑ
0
1
๏€จ ๏€ฉmer TT
H
p ๏€ญ๏€ฝ
2
1
๏ท
qsqdsde ivivT ๏‚ข๏€ซ๏‚ข๏€ฝ
15396k
PSL - 12
Synchronous Motor Model
๏ฌ A synchronous motor is modelled in the same
manner as a synchronous generator
๏† the only difference is that, instead of the prime
mover providing mechanical torque input to the
generator, the motor drives a mechanical load
๏ฌ As in the case of an induction motor, a commonly
used expression for the load torque is
Rotor acceleration equation is
m
rm TT ๏ท0๏€ฝ
๏€จ ๏€ฉme
r
TT
Hdt
d
๏€ญ๏€ฝ
2
1๏ท
15396k
PSL - 13
Acquisition of Load Model Parameters
๏ฌ Two basic approaches:
๏† measurement-based approach
๏† component based approach
๏ฌ Measurement-based approach
๏† load characteristics measured at representative
substations and feeders at selected times
๏† parameters of loads throughout the system extrapolated
from the above
๏ฌ Component-based approach
๏† involves building up the load model from information on
its constituent parts
๏† load supplied at a bulk power delivery point categorized
into load classes such as residential, commercial, and
industrial
๏† each load class represented in terms of its components
such as lighting, heating, refrigeration
๏† individual devices represented by their known
characteristics
15396k
PSL - 14
๏ฌ Composite load model derived by aggregating
individual loads
๏† EPRI LOADSYN program converts data on the
load class mix, components, and their
characteristics into the form required for stability
studies
15396k
PSL - 15
LOADSYN Program
๏ฌ Creates aggregated specific static models (ZIP) or
dynamic models (ZIP plus induction motor)
๏ฌ Is component based; the model parameters are
derived from
๏† load mix data: percentage of residential,
commercial and industrial class in each load (user
specified)
๏† class composition: percentage of load
components, e.g. heating, lighting, etc., in each
class (default data provided for North America)
๏† component characteristics: static and dynamic
parameters of each component (default data
provided)
๏ฌ Default data corresponds to fast dynamics and small
voltage excursions
๏ฌ Load characteristics for voltage stability studies
have not been investigated extensively
๏ฌ Distribution ULTC and voltage regulation is not
accounted for (therefore, ULTC models must be
included in the system data)
15396k
PSL - 16
Table 7.1 summarizes typical voltage and frequency dependent
characteristics of a number of load components.
Component Static Characteristics
Component
Power
Factor
โˆ‚P/โˆ‚V โˆ‚Q/โˆ‚V โˆ‚P/โˆ‚f โˆ‚Q/โˆ‚f
Air conditioner
- 3-phase central 0.90 0.088 2.5 0.98 -1.3
- 1-phase central 0.96 0.202 2.3 0.90 -2.7
- window type 0.82 0.468 2.5 0.56 -2.8
Water heaters,
1.0 2.0 0 0 0Range top, oven
Deep fryer
Dishwasher 0.99 1.8 3.6 0 -1.4
Clothes washer 0.65 0.08 1.6 3.0 1.8
Clothes dryer 0.99 2.0 3.2 0 -2.5
Refrigerator 0.8 0.77 2.5 0.53 -1.5
Television 0.8 2.0 5.1 0 -4.5
Incandescent lights 1.0 1.55 0 0 0
Fluorescent lights 0.9 0.96 7.4 1.0 -2.8
Industrial motors 0.88 0.07 0.5 2.5 1.2
Fan motors 0.87 0.08 1.6 2.9 1.7
Agricultural pumps 0.85 1.4 1.4 5.0 4.0
Arc furnace 0.70 2.3 1.6 -1.0 -1.0
Transformer (unloaded) 0.64 3.4 11.5 0 -11.8
Table 7.1
15396k
PSL - 17
Table 7.2 summarizes the sample characteristics of different load
classes.
Table 7.2
Load Class Static Characteristics
Load Class
Power
Factor
โˆ‚P/โˆ‚V โˆ‚Q/โˆ‚V โˆ‚P/โˆ‚f โˆ‚Q/โˆ‚f
Residential
- summer 0.9 1.2 2.9 0.8 -2.2
- winter 0.99 1.5 3.2 1.0 -1.5
Commercial
- summer 0.85 0.99 3.5 1.2 -1.6
- winter 0.9 1.3 3.1 1.5 -1.1
Industrial 0.85 0.18 6.0 2.6 1.6
Power plant auxiliaries 0.8 0.1 1.6 2.9 1.8
15396k
PSL - 18
Dynamic Characteristics
(i) The composite dynamic characteristics of a feeder
supplying predominantly a commercial load:
Rs = 0.001 Xs = 0.23 Xr = 0.23
Xm = 5.77 Rr = 0.012 H = 0.663 m = 5.0
(ii) A large industrial motor:
Rs = 0.012 Xs = 0.07 Xr = 0.165
Xm = 3.6 Rr = 0.01 H = 1.6 m = 2.0
(iii) A small industrial motor:
Rx = 0.025 Xs = 0.10 Xr = 0.17
Xm = 3.1 Rr = 0.02 H = 0.9 m = 2.0
The following are sample data for induction motor equivalents
representing three different types of load (see Fig. 7.7 for
definition of parameters).

More Related Content

What's hot

SAIEE_Word_Des_Ver 1.15_IPT
SAIEE_Word_Des_Ver 1.15_IPTSAIEE_Word_Des_Ver 1.15_IPT
SAIEE_Word_Des_Ver 1.15_IPT
Hannes Van Rooyen
ย 
Jg2516381645
Jg2516381645Jg2516381645
Jg2516381645
IJERA Editor
ย 
Ga2510971106
Ga2510971106Ga2510971106
Ga2510971106
IJERA Editor
ย 
BP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SM
BP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SMBP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SM
BP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SM
Steve Mappus
ย 
K046065864
K046065864K046065864
K046065864
IJERA Editor
ย 
Bs31473481
Bs31473481Bs31473481
Bs31473481
IJERA Editor
ย 

What's hot (18)

SAIEE_Word_Des_Ver 1.15_IPT
SAIEE_Word_Des_Ver 1.15_IPTSAIEE_Word_Des_Ver 1.15_IPT
SAIEE_Word_Des_Ver 1.15_IPT
ย 
Analysis and characterization of different high density on chip switched capa...
Analysis and characterization of different high density on chip switched capa...Analysis and characterization of different high density on chip switched capa...
Analysis and characterization of different high density on chip switched capa...
ย 
Jg2516381645
Jg2516381645Jg2516381645
Jg2516381645
ย 
boost driver
boost driverboost driver
boost driver
ย 
ETAP - Load flow and panel rev2014-1
ETAP - Load flow and panel   rev2014-1ETAP - Load flow and panel   rev2014-1
ETAP - Load flow and panel rev2014-1
ย 
Implementation of FC-TCR for Reactive Power Control
Implementation of FC-TCR for Reactive Power ControlImplementation of FC-TCR for Reactive Power Control
Implementation of FC-TCR for Reactive Power Control
ย 
PWM RECTIFIER
PWM RECTIFIERPWM RECTIFIER
PWM RECTIFIER
ย 
Configuration and working point and state estimation
Configuration and working point and state estimationConfiguration and working point and state estimation
Configuration and working point and state estimation
ย 
Ga2510971106
Ga2510971106Ga2510971106
Ga2510971106
ย 
BP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SM
BP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SMBP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SM
BP_2010_05_High Eff Low Profile ACDC Power_SMappus May 2010_Edit SM
ย 
SST
SSTSST
SST
ย 
K046065864
K046065864K046065864
K046065864
ย 
A Novel Control Method Of Variable Speed Pumped Storage Power Plant
A Novel Control Method Of Variable Speed Pumped Storage Power PlantA Novel Control Method Of Variable Speed Pumped Storage Power Plant
A Novel Control Method Of Variable Speed Pumped Storage Power Plant
ย 
236225174 psd-course-file-2011-12-1
236225174 psd-course-file-2011-12-1236225174 psd-course-file-2011-12-1
236225174 psd-course-file-2011-12-1
ย 
Performance Comparison of Star Connected Cascaded STATCOM Using Different PWM...
Performance Comparison of Star Connected Cascaded STATCOM Using Different PWM...Performance Comparison of Star Connected Cascaded STATCOM Using Different PWM...
Performance Comparison of Star Connected Cascaded STATCOM Using Different PWM...
ย 
Static Synchronous Series Compensator (SSSC) with Superconducting Magnetic En...
Static Synchronous Series Compensator (SSSC) with Superconducting Magnetic En...Static Synchronous Series Compensator (SSSC) with Superconducting Magnetic En...
Static Synchronous Series Compensator (SSSC) with Superconducting Magnetic En...
ย 
Technical seminar
Technical seminarTechnical seminar
Technical seminar
ย 
Bs31473481
Bs31473481Bs31473481
Bs31473481
ย 

Similar to POWER SYSTEM LOADS

harmonic analysis of 6 phase converter
harmonic analysis of 6 phase converterharmonic analysis of 6 phase converter
harmonic analysis of 6 phase converter
Rahul Kumar
ย 
1 s2.0-s187661021301103 x-main
1 s2.0-s187661021301103 x-main1 s2.0-s187661021301103 x-main
1 s2.0-s187661021301103 x-main
AhmedAljabari
ย 

Similar to POWER SYSTEM LOADS (20)

Time response of FOPID controlled PV based cascaded landsman converter-invert...
Time response of FOPID controlled PV based cascaded landsman converter-invert...Time response of FOPID controlled PV based cascaded landsman converter-invert...
Time response of FOPID controlled PV based cascaded landsman converter-invert...
ย 
A voltage sensitivity index application for power system load shedding consid...
A voltage sensitivity index application for power system load shedding consid...A voltage sensitivity index application for power system load shedding consid...
A voltage sensitivity index application for power system load shedding consid...
ย 
Emergency generator sizing and motor starting analysis
Emergency generator sizing and motor starting analysisEmergency generator sizing and motor starting analysis
Emergency generator sizing and motor starting analysis
ย 
Hq3513331337
Hq3513331337Hq3513331337
Hq3513331337
ย 
Indian journal 3
Indian journal 3Indian journal 3
Indian journal 3
ย 
harmonic analysis of 6 phase converter
harmonic analysis of 6 phase converterharmonic analysis of 6 phase converter
harmonic analysis of 6 phase converter
ย 
efficient topology for ev battery charging.docx
efficient topology for ev battery charging.docxefficient topology for ev battery charging.docx
efficient topology for ev battery charging.docx
ย 
A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...
A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...
A Novel Low Power-Application UPS Consisting of an APF - Correction Circuit &...
ย 
PARAMETER IDENTIFICATION AND MODELLING OF SEPARATELY EXCITED DC MOTOR
PARAMETER IDENTIFICATION AND MODELLING OF SEPARATELY EXCITED DC MOTOR PARAMETER IDENTIFICATION AND MODELLING OF SEPARATELY EXCITED DC MOTOR
PARAMETER IDENTIFICATION AND MODELLING OF SEPARATELY EXCITED DC MOTOR
ย 
1 s2.0-s187661021301103 x-main
1 s2.0-s187661021301103 x-main1 s2.0-s187661021301103 x-main
1 s2.0-s187661021301103 x-main
ย 
LoadModeling (1).ppt
LoadModeling (1).pptLoadModeling (1).ppt
LoadModeling (1).ppt
ย 
LoadModeling.ppt
LoadModeling.pptLoadModeling.ppt
LoadModeling.ppt
ย 
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTERSOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
SOLID STATE TRANSFORMER - USING FLYBACK CONVERTER
ย 
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB IRJET-Power Flow & Voltage Stability Analysis using MATLAB
IRJET-Power Flow & Voltage Stability Analysis using MATLAB
ย 
Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB Power Flow & Voltage Stability Analysis using MATLAB
Power Flow & Voltage Stability Analysis using MATLAB
ย 
Power Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series CompensationPower Quality Enhancement in an Isolated Power System Using Series Compensation
Power Quality Enhancement in an Isolated Power System Using Series Compensation
ย 
Analysis of a High Efficiency Boost-Inverter with Back-up Battery Storage in ...
Analysis of a High Efficiency Boost-Inverter with Back-up Battery Storage in ...Analysis of a High Efficiency Boost-Inverter with Back-up Battery Storage in ...
Analysis of a High Efficiency Boost-Inverter with Back-up Battery Storage in ...
ย 
Improvement In Pre-Regulation For Power Factor Using CUK Converter
Improvement In Pre-Regulation For Power Factor Using CUK ConverterImprovement In Pre-Regulation For Power Factor Using CUK Converter
Improvement In Pre-Regulation For Power Factor Using CUK Converter
ย 
Iaetsd power-frequency transient studies
Iaetsd power-frequency transient studiesIaetsd power-frequency transient studies
Iaetsd power-frequency transient studies
ย 
DC Bus Voltage Switched Control Method for Three Phase Voltage Source PWM Rec...
DC Bus Voltage Switched Control Method for Three Phase Voltage Source PWM Rec...DC Bus Voltage Switched Control Method for Three Phase Voltage Source PWM Rec...
DC Bus Voltage Switched Control Method for Three Phase Voltage Source PWM Rec...
ย 

More from Power System Operation

SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
Power System Operation
ย 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
Power System Operation
ย 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
Power System Operation
ย 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
ย 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
ย 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
ย 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
ย 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
ย 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
ย 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
ย 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
ย 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
ย 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
ย 
Gas Insulated Switchgear? Gas-Insulated High-Voltageย Switchgearย (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltageย Switchgearย (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltageย Switchgearย (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltageย Switchgearย (GIS)
ย 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
ย 
What is load management
What is load managementWhat is load management
What is load management
ย 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
ย 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
ย 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
ย 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
ย 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
ย 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
ย 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
ย 

Recently uploaded

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
ย 
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
dharasingh5698
ย 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
KreezheaRecto
ย 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
SUHANI PANDEY
ย 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
ย 
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 

Recently uploaded (20)

Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
ย 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
ย 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
ย 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
ย 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
ย 
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Netaji Nagar, Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
ย 
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor ๐Ÿ“ฑ {7001035870} VIP Escorts chittoor
ย 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ย 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
ย 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
ย 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
ย 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
ย 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
ย 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
ย 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
ย 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
ย 
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort ServiceCall Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
Call Girls in Ramesh Nagar Delhi ๐Ÿ’ฏ Call Us ๐Ÿ”9953056974 ๐Ÿ” Escort Service
ย 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
ย 

POWER SYSTEM LOADS

  • 1. Copyright ยฉ P. Kundur This material should not be used without the author's consent POWER SYSTEM LOADS 15316k
  • 2. 15396k PSL - 1 Load Modelling 1. Basic load modelling concepts 2. Static load models 3. Dynamic load models 4. Induction motors 5. Synchronous motors 6. Acquisition of load model parameters
  • 3. 15396k PSL - 2 Load Modelling ๏ฌ A typical load bus represented in stability studies is composed of a large number of devices: ๏† fluorescent and incandescent lamps, refrigerators, heaters, compressors, furnaces, and so on ๏ฌ The composition changes depending on many factors, including: ๏† time ๏† weather conditions ๏† state of the economy ๏ฌ The exact composition at any particular time is difficult to estimate. Even if the load composition were known, it would be impractical to represent each individual component. ๏ฌ For the above reasons, load representation is based on considerable amount of simplification.
  • 4. 15396k PSL - 3 Basic Load Modelling Concepts ๏ฌ The aggregated load is usually represented at a transmission substation ๏† includes, in addition to the connected load devices, the effects of step-down transformers, subtransmission and distribution feeders, voltage regulators, and VAr compensation ๏ฌ Load models are traditionally classified into: ๏† static load models ๏† dynamic load models Fig. 7.1 Power system configuration identifying parts of the system represented as load at a bulk power delivery point (Bus A)
  • 5. 15396k PSL - 4 Static Load Models ๏ฌ Express the load characteristics as algebraic functions of bus voltage magnitude and frequency. ๏ฌ Traditionally, voltage dependency has been represented by the exponential model: P0, Q0, and V0 are the values of the respective variables at the initial operating condition. For composite loads, ๏† exponent "a" ranges between 0.5 and 1.8 ๏† exponent "b" ranges between 1.5 and 6 The exponent "b" is a nonlinear function of voltage. This is caused by magnetic saturation of distribution transformers and motors. ๏€จ ๏€ฉ ๏€จ ๏€ฉ 0 0 0 V V V VQQ VPP b a ๏€ฝ ๏€ฝ ๏€ฝ
  • 6. 15396k PSL - 5 ๏ฌ An alternative static model widely used is the polynomial model: This model is commonly referred to as the "ZIP" model, as it is composed of constant impedance (Z), constant current (I), and constant power (P) components. ๏ฌ The frequency dependency of load characteristics is usually represented by multiplying the exponential or polynomial model by a factor: For example, where ฮ”f is the frequency deviation (f-f0). Typically, Kpf ranges from 0 to 3.0, and Kqf ranges from -2.0 to 0. ๏ฌ Response of most loads is fast and steady state reached quickly, at least for modest changes in V and f. ๏† use of static model justified in such cases ๏› ๏ ๏€จ ๏€ฉ ๏› ๏ ๏€จ ๏€ฉfKqVqVqQQ fKpVpVpPP qf pf ๏„ ๏„ ๏€ซ๏€ซ๏€ซ๏€ฝ ๏€ซ๏€ซ๏€ซ๏€ฝ 1 1 32 2 10 32 2 10 ๏› ๏ ๏› ๏32 2 10 32 2 10 qVqVqQQ pVpVpPP ๏€ซ๏€ซ๏€ฝ ๏€ซ๏€ซ๏€ฝ
  • 7. 15396k PSL - 6 Dynamic Load Models ๏ฌ In many cases, it is necessary to account for the dynamics of loads. For example, studies of ๏† inter-area oscillations and voltage stability ๏† systems with large concentrations of motors ๏ฌ Typically, motors consume 60% to 70% of total energy supplied by a power system ๏† dynamics attributable to motors are usually the most significant aspects ๏ฌ Other dynamic aspects of load components include: ๏† Extinction of discharge (mercury vapour, sodium vapour, fluorescent) lamps when voltage drops below 0.7 to 0.8 pu and their restart after 1 or 2 seconds delay when voltage recovers. ๏† Operation of protective relays. For example, starter contractors of industrial motors drop open when voltage drops below 0.55 to 0.75 pu. ๏† Thermostatic control of loads such as space heaters/coolers, water heaters and refrigerators - operate longer during low voltages and hence, total number of devices increase in a few minutes. ๏† Response of ULTCs on distribution transformers and voltage regulators
  • 8. 15396k PSL - 7 ๏ฌ Composite model which represents the wide range of characteristics exhibited by various load components: ๏ฌ A simple model for thermostatically controlled loads: LH H PP dt d K ๏€ญ๏€ฝ ๏ด where ๏œ H = temperature of heated area ๏œ A = ambient temperature PH = power from the heater = KHGV2 PL = heat loss by escape to ambient area = KA (๏œH- ๏œ A) G = load conductance The dynamic equation of a heating device may be written as:
  • 9. 15396k PSL - 8 Induction Motor ๏ฌ Carries alternating current in both stator and rotor windings ๏† rotor windings are either short-circuited internally or connected through slip rings to a passive external circuit ๏ฌ The distinctive feature is that the rotor currents are induced by electromagnetic induction. ๏ฌ The stator windings of a 3-phase induction machine are similar to those of a synchronous machine ๏† produces a field rotating at synchronous speed when balanced currents are applied ๏ฌ When there is a relative motion between the stator field and the rotor, voltages and currents are inducted in the rotor windings ๏† the frequency of the induced rotor voltages depends on the slip speed ๏ฌ At no load, the machine operates with negligible slip. If a mechanical load is applied, the slip increases.
  • 10. 15396k PSL - 9 Modelling of Induction Motors ๏ฌ The general procedure is similar to that of a synchronous machine ๏† first write basic equations in terms of phase (a,b,c) variables ๏† then, transform equations into 'dq' reference frame ๏ฌ In developing the model of an induction motor it is worth noting the following of its features which differ from those of the synchronous machine: ๏† rotor has a symmetrical structure; hence, d and q axis equivalent circuits are identical ๏† rotor speed is not fixed; this has an impact on the selection of dq reference frame ๏† there is no excitation source applied to the rotor; consequently the rotor circuit dynamics are determined by slip rather than by excitation control. ๏† currents induced in shorted rotor windings produce a field with the same number of poles as in the stator; therefore, rotor windings may be represented by equivalent 3-phase winding
  • 11. 15396k PSL - 10 ๏ฌ The 'dq' transformation: ๏† the preferred reference frame is one with axes rotating at synchronous speed, rather than at rotor speed ๏ฌ The machine equations in dq reference frame: Stator flux linkages: Rotor flux linkages: Stator voltages: Rotor voltages: ๏† The term pฮธr is the slip angular velocity and represents the relative angular velocity between the rotor and the reference dq axes. qrmqsssqs drmdsssds iLiL iLiL ๏€ซ๏€ฝ ๏€ซ๏€ฝ ๏™ ๏™ qsmqrrrqr dsmdrrrdr iLiL iLiL ๏€ซ๏€ฝ ๏€ซ๏€ฝ ๏™ ๏™ qsdssqssqs dsqssdssds piRV piRV ๏™๏™๏ท ๏™๏™๏ท ๏€ซ๏€ซ๏€ฝ ๏€ซ๏€ญ๏€ฝ ๏€จ ๏€ฉ ๏€จ ๏€ฉ qrdrrqrrqr drqrrdrrdr ppiRV ppiRV ๏™๏™๏ฑ ๏™๏™๏ฑ ๏€ซ๏€ซ๏€ฝ ๏€ซ๏€ญ๏€ฝ
  • 12. 15396k PSL - 11 ๏ฌ For representation in stability studies, and are neglected ๏† same as for synchronous machines, this simplification is essential to ensure consistent models used for network and induction motors ๏ฌ With the stator transients neglected, the per unit induction motor electrical equations may be summarized as: Stator voltages in phasor form: Rotor circuit dynamics: Rotor acceleration equation: Representation of an Induction Motor in Stability Studies dsp๏™ qsp๏™ ๏€จ ๏€ฉ๏€จ ๏€ฉ ๏€จ ๏€ฉqdqsdsssqsds vjvjiiXjRjvv ๏‚ข๏€ซ๏‚ข๏€ซ๏€ซ๏‚ข๏€ซ๏€ฝ๏€ซ ๏€จ ๏€ฉ ๏€จ ๏€ฉ๏› ๏ qrqsssdd vpiXXv T vp ๏‚ข๏€ซ๏‚ข๏€ญ๏€ซ๏‚ข ๏‚ข ๏€ญ๏€ฝ๏‚ข ๏ฑ 0 1 ๏€จ ๏€ฉ ๏€จ ๏€ฉ๏› ๏ drdsssqq vpiXXv T vp ๏‚ข๏€ญ๏€ญ๏€ญ๏‚ข ๏‚ข ๏€ญ๏€ฝ๏‚ข ๏ฑ 0 1 ๏€จ ๏€ฉmer TT H p ๏€ญ๏€ฝ 2 1 ๏ท qsqdsde ivivT ๏‚ข๏€ซ๏‚ข๏€ฝ
  • 13. 15396k PSL - 12 Synchronous Motor Model ๏ฌ A synchronous motor is modelled in the same manner as a synchronous generator ๏† the only difference is that, instead of the prime mover providing mechanical torque input to the generator, the motor drives a mechanical load ๏ฌ As in the case of an induction motor, a commonly used expression for the load torque is Rotor acceleration equation is m rm TT ๏ท0๏€ฝ ๏€จ ๏€ฉme r TT Hdt d ๏€ญ๏€ฝ 2 1๏ท
  • 14. 15396k PSL - 13 Acquisition of Load Model Parameters ๏ฌ Two basic approaches: ๏† measurement-based approach ๏† component based approach ๏ฌ Measurement-based approach ๏† load characteristics measured at representative substations and feeders at selected times ๏† parameters of loads throughout the system extrapolated from the above ๏ฌ Component-based approach ๏† involves building up the load model from information on its constituent parts ๏† load supplied at a bulk power delivery point categorized into load classes such as residential, commercial, and industrial ๏† each load class represented in terms of its components such as lighting, heating, refrigeration ๏† individual devices represented by their known characteristics
  • 15. 15396k PSL - 14 ๏ฌ Composite load model derived by aggregating individual loads ๏† EPRI LOADSYN program converts data on the load class mix, components, and their characteristics into the form required for stability studies
  • 16. 15396k PSL - 15 LOADSYN Program ๏ฌ Creates aggregated specific static models (ZIP) or dynamic models (ZIP plus induction motor) ๏ฌ Is component based; the model parameters are derived from ๏† load mix data: percentage of residential, commercial and industrial class in each load (user specified) ๏† class composition: percentage of load components, e.g. heating, lighting, etc., in each class (default data provided for North America) ๏† component characteristics: static and dynamic parameters of each component (default data provided) ๏ฌ Default data corresponds to fast dynamics and small voltage excursions ๏ฌ Load characteristics for voltage stability studies have not been investigated extensively ๏ฌ Distribution ULTC and voltage regulation is not accounted for (therefore, ULTC models must be included in the system data)
  • 17. 15396k PSL - 16 Table 7.1 summarizes typical voltage and frequency dependent characteristics of a number of load components. Component Static Characteristics Component Power Factor โˆ‚P/โˆ‚V โˆ‚Q/โˆ‚V โˆ‚P/โˆ‚f โˆ‚Q/โˆ‚f Air conditioner - 3-phase central 0.90 0.088 2.5 0.98 -1.3 - 1-phase central 0.96 0.202 2.3 0.90 -2.7 - window type 0.82 0.468 2.5 0.56 -2.8 Water heaters, 1.0 2.0 0 0 0Range top, oven Deep fryer Dishwasher 0.99 1.8 3.6 0 -1.4 Clothes washer 0.65 0.08 1.6 3.0 1.8 Clothes dryer 0.99 2.0 3.2 0 -2.5 Refrigerator 0.8 0.77 2.5 0.53 -1.5 Television 0.8 2.0 5.1 0 -4.5 Incandescent lights 1.0 1.55 0 0 0 Fluorescent lights 0.9 0.96 7.4 1.0 -2.8 Industrial motors 0.88 0.07 0.5 2.5 1.2 Fan motors 0.87 0.08 1.6 2.9 1.7 Agricultural pumps 0.85 1.4 1.4 5.0 4.0 Arc furnace 0.70 2.3 1.6 -1.0 -1.0 Transformer (unloaded) 0.64 3.4 11.5 0 -11.8 Table 7.1
  • 18. 15396k PSL - 17 Table 7.2 summarizes the sample characteristics of different load classes. Table 7.2 Load Class Static Characteristics Load Class Power Factor โˆ‚P/โˆ‚V โˆ‚Q/โˆ‚V โˆ‚P/โˆ‚f โˆ‚Q/โˆ‚f Residential - summer 0.9 1.2 2.9 0.8 -2.2 - winter 0.99 1.5 3.2 1.0 -1.5 Commercial - summer 0.85 0.99 3.5 1.2 -1.6 - winter 0.9 1.3 3.1 1.5 -1.1 Industrial 0.85 0.18 6.0 2.6 1.6 Power plant auxiliaries 0.8 0.1 1.6 2.9 1.8
  • 19. 15396k PSL - 18 Dynamic Characteristics (i) The composite dynamic characteristics of a feeder supplying predominantly a commercial load: Rs = 0.001 Xs = 0.23 Xr = 0.23 Xm = 5.77 Rr = 0.012 H = 0.663 m = 5.0 (ii) A large industrial motor: Rs = 0.012 Xs = 0.07 Xr = 0.165 Xm = 3.6 Rr = 0.01 H = 1.6 m = 2.0 (iii) A small industrial motor: Rx = 0.025 Xs = 0.10 Xr = 0.17 Xm = 3.1 Rr = 0.02 H = 0.9 m = 2.0 The following are sample data for induction motor equivalents representing three different types of load (see Fig. 7.7 for definition of parameters).