Design for safety and reliability –
appropriate connection provisions
for generator sets
White Paper
By Munir Kaderbhai, Sales Application Engineer
Standby electric generators provide
a welcome measure of protection
against a loss of power, but only if
the generators are properly installed
and applied. One of the most
crucial installation concerns is the
load conductors’ connection to the
generator set. The load conductors,
their connection points and routing
away from the generator set are the
means to transfer energy from the
emergency power source to the power
distribution system. If the quality of
these connections is jeopardized in
any way, it can lead to safety hazards
and make your emergency power
source unreliable.
Priorities and options in
generator connections
When reviewing the installation of your
emergency power supply system, give top
priority to proper electrical connections to
the generator. You should ensure that the
generator set is installed using appropriate
provisions to allow a reliable, economical and
safe connection.
There are several ways in which connections
to the generator can be made, and several
factors to keep in mind for proper connections,
including alternator and conductor overload
protection, disconnect requirements, conductor
size and vibration. The goal of this paper
is to highlight these factors and to provide
recommendations for safe, durable and reliable
load conductor connections.
Generator connection
options
Power connections to a generator set may be
made to generator-mounted circuit breakers
or, when alternator and conductor overload
protection is provided by a device such as
AmpSentry™
Protective Relay, directly to the
alternator terminals. In installations where there
is no integral Underwriters Laboratory®
(UL)
Listed means of protection for the generator
Power topic #9018 | Technical information from Cummins Power Generation
c
5
connection
provisions for
generator sets
M Y K
InitIals dateJOB #	CPG100249	 DATE	2.17.11
CLIENT	Cummins Power Generation
JOB DESCRIPTION	 White Paper
FLAT	 8.5" x 11"
BLEED	.125"
FOLDED	
FILE	 100%
COLOR	CMYK
CD	
AD	
CW	Don Flanagan
DS	
AM	Christie Graham
PM	 Katie DeSmet
CLIENT	
CPG100249_ConnProvGenSets 1 2/17/11 10:06 AM
02PowerTopic#9018
and its conductors, then connection to a circuit breaker
(CB) is common. Protection requirements are detailed in
National Electric Code (NEC) article 445.12.
Both molded case and insulated case CBs may be used
for generator sets. Molded case breakers are typically
mounted in a circuit breaker enclosure directly attached
to the alternator. The CB box may house single or
dual CBs depending on the application requirements.
Insulated case CBs are typically larger and more sensitive
to vibration. They are usually mounted in a freestanding
enclosure next to the generator.
If connections are being made to the generator via a
CB and if the CB does not include mechanical lugs,
then the installer needs to provide lugs for customer
connections. These lugs should be anti-rotational, to
prevent the connections from loosening due to vibration
or thermal expansion. It is important to verify that the
number of conductors per phase and the conductors’
size match the published lug quantities and capacities
on the CBs. The lug set-screws should be tightened
using torque values provided by the manufacturer, so
that the cables are not damaged.
If the generator has UL Listed integral means of
overload protection, oftentimes it’s beneficial to remove
the CB and make electrical connections directly to
the generator set. Removing the breaker can make
the task of selectively coordinating the overcurrent
protection devices downstream less complicated,
because then all of the CBs or fuses in the emergency
system can be provided by a single supplier. Without a
main CB on the generator, provisions to connect to the
generator set are provided via an entrance box.
Top entry versus bottom entry
Conductors can be routed into the CB or entrance box
through either the top or bottom surface of the box
(Figure 1). If you are the system designer, you should
specify on the facility drawings or in the specifications
whether the intention is to top-connect or bottom-
connect the generator set. Customer connection
points inside the box will typically be provided to a bus
bar. The bus bars must have NEMA two-hole patterns
to comply with the UL connection requirements. This
means that the conductors should be terminated using
either compression or mechanical lugs and should be
secured to the bus bars with proper fasteners.
www.cumminspower.com
©2011 Cummins Power Generation
Figure 1 - Circuit breaker box (left – bottom entry; right – top entry) – 1) neutral disconnect link; 2) grounding bus; 3) circuit breaker;
4) bottom-entry chute.
CPG100249_ConnProvGenSets 2 2/17/11 10:06 AM
Using a 100% rated CB assembly can allow the full
rating of the breaker to be utilized, and may allow the
use of a smaller CB frame size. This practice can help
reduce the cost of the breaker and also reduce the
amount of space occupied by the CB in the enclosure.
The total required cable size may also be reduced,
providing more room in the enclosure for the cables
and making it easier to connect to the bus bars.
Outdoor generator compliance —
service-rated equipment
NEC Article 225.31 requires a disconnect means for
conductors that supply or pass through the building
or structure. Article 225.36 states that the disconnect
means referred to in 225.31 shall be suitable for
use as service equipment. This requirement means
that if you have an outdoor generator set, there has
to be a service disconnect where the conductors
enter the building, and the disconnect has to be a
service entrance device. The NEC also requires each
disconnecting means that is installed and used as
a service disconnecting means to be identified as a
service disconnecting means [See Figure 2(2)].
Where an outdoor-housed generator is equipped
with readily accessible disconnection means located
within the site of the building or structure supplied, an
additional disconnecting means is not required where
ungrounded conductors pass through the building
[NEC Articles 700.12(B)(6), 701.12(B)(5), 702.11]. Note
that the disconnection means must be suitable for use
as service equipment and labeled as such.
Conduit and cable size
Conductors connected to the generator set’s
alternating current (AC) output should be sized as
03PowerTopic#9018
UL and the NEC require mechanical protection for
conductors. For top-entry installations, this protection
is typically provided by conduit. These conduits must
be flexible enough to handle generator set three-
dimensional vibration; they typically have a 90° bend
to help absorb vibration. For bottom-entry installations,
conduits may be required, depending on the location
of the electrical connection box. If the box is mounted
on the alternator, then cables running from the stub-up
area of the foundation and to the box cannot be left
exposed to accidental contact by unqualified persons
and must be protected with flexible conduits.
UL Listed 100% rated circuit
breaker assembly
Circuit breaker manufacturers test their breakers to be
able to handle 100% rated current for an unlimited time
under standard test conditions per UL489. Under these
test conditions, the CB is in free air and the ambient
temperature is maintained at 40°C.
In typical installations, however, the CB will be housed
in an enclosure, which can trap heat and increase
the temperature inside the box if the enclosure is not
adequately sized and ventilated. In thermomagnetic-
type circuit breakers, if the temperature within the
enclosure exceeds operational limits, it can cause
nuisance tripping of the breaker. Therefore, for
continuous loads, a typical CB assembly can be applied
at only 80% of its rated current. This could mean that
you will have to oversize your CB and its conductors in
order to operate the generator set at or near its rated
load for an extended period of time. All these factors
can add cost and complexity to the installation.
The NEC has an exception to this rule, which allows CB
assemblies to be rated at 100%. In contrast to standard
rated (or 80% rated) CBs, 100% rated assemblies can
carry 100% of the CB and conductor current rating. In
order to be 100% rated, the equipment must undergo
additional UL testing to ensure that the additional heat
generated by running higher currents through the
circuit will be safely dissipated and not cause a high
temperature rise within the enclosure. UL489 specifies
the minimum enclosure size and venting requirements
for the CB box.
In addition to meeting these size requirements, the
100% rated assembly must also be labeled as such by
the manufacturer [Figure 2 (1)]. Without this label, the
assembly will be considered 80%, even if the box size
and venting requirements are met.
www.cumminspower.com
©2011 Cummins Power Generation
Figure 2 - (1) The 100% CB assembly must be labeled by the manufacturer as
being 100% rated; (2) Equipment has to bear the marking “suitable for use as
service equipment”; (3) Use 90°C rated conductors but size based on ampacity
of 75°C.
CPG100249_ConnProvGenSets 3 2/17/11 10:06 AM
required by the load currents, the application and local
electrical codes. The generator set manufacturer will
typically specify line-line ampere ratings of a specific
generator set for the specific voltage selected.
The NEC handbook provides guidelines for the ampacity
of phase and neutral conductors connected to the
generator set. Article 445.13 requires that the ampacity
of conductors from the generator terminals to the first
distribution device(s) containing overcurrent protection
shall not be less than 115% of the nameplate rating
of the generator set. The exception is for generator
designs that have inherent means for preventing an
overload condition. For that case, conductors can be
rated at 100% of the nameplate current rating. NEC
Article 310 covers general requirements for conductors
and provides tables that can be used to help determine
minimum conductor size.
In larger generator set applications, both the size and the
number of the cables and conduits can get very large,
so it is important to ensure that electrical connection
boxes are sized appropriately, not only to accommodate
the cables/conduits but also to provide adequate
space for easy entry into the box. Most likely, you will
have more than one cable/conduit per phase, so there
should also be provisions in the entrance box for multiple
conduits. For example, multiple punch-outs and liquid
tight strain relief connectors are recommended. NEC
Article 445.16 also requires that cables that pass though
the opening in the enclosures be protected by bushings
from openings with sharp edges.
As an example, consider a 2MW generator set that
is rated at about 3000A at 480V. For a type RHW
copper cable with temperature rating of 75°C and an
ambient temperature of 30°C (86°F), the ampacity of
a 750 kcmil given by Table 310.15(B)(16) in the NEC
handbook is 475A. A total of eight cables will give a
total current rating of 3800A. It is good practice to
design for at least an ambient temperature of 40°C,
which requires the use of a 0.88 correction factor from
Table 310.15(B)(2)(a). This reduces the current rating
to 3344A. An additional correction factor of 0.7 from
Table 310.15(B)(3)(a) also must be applied if there are
more than three cables bundled together per raceway/
conduit, dropping the capacity and current rating of the
eight cables to 2340A.
This example demonstrates the fact that many large
cables can be required to be able to use the full rated
current output of the generator set. It also demonstrates
the importance of ensuring that the electrical connection
box not only allows entry for multiple cables but also has
sufficient space and sufficiently large entrance holes to
accommodate all these large cables. Having an adequately
sized electrical connection box is important, because it
provides adequate bend space for very large conductors
and allows ease of installation for the electrician.
Bus bar temperature rise
Per UL2200 requirements, the temperature of a bus
bar can be as high as 90°C over a 40°C ambient
temperature. Therefore, it is sometimes recommended
that the conductors connecting to the bus bars be
90°C rated. However, the conductors must still be
sized using the 75°C column in 310.15(B)(16) in the
NEC. This is because the terminations of electrical
utilization equipment, such as CBs, panelboards and
transfer switches, are rated for a maximum temperature
of 75°C.
Regarding temperatures, note that there are two
“flavors” of 100% rated CBs, which are defined by the
temperature limits at the wire terminal connection. The
temperature can either rise to a maximum temperature
of 50°C at a 40°C ambient, or it may rise to a
temperature of 60°C at the wire terminal connection
at a 40°C ambient. If the temperature rise is below
50°C, then you may use a 75°C rated conductor sized
to the 75°C chart. If the temperature rise is over 50°C
but below 60°C, then you have to use a 90°C rated
conductor sized to the 75°C chart. The manufacturer
may specify that you use 90°C rated wire-based
ampacity of 75°C wire [Figure 2(3)].
Bracing requirements
It is essential to have bracing and conductor spacing
supports that are physically and electrically able to
withstand expected mechanical forces and voltages.
Short circuit currents can induce tremendous magnetic
forces between conductors. If conductor bracing and
supports are not adequate, there could be enough
force to bend metals, to break insulators and to
disconnect any connector terminations that are not
securely fastened.
Generator sets are required by NFPA 110 to be short
circuit tested, and one part of that testing is to validate
the design of the electrical connection box. NFPA 110
section 5.2.3 (1) requires generators for Level 1 systems
to be specifically designed, assembled and tested to
ensure system operation under short circuits. Prototype
tests must be performed by the manufacturer to verify
that the generator can safely withstand the forces
associated with short circuit conditions.
04PowerTopic#9018
www.cumminspower.com
©2011 Cummins Power Generation
CPG100249_ConnProvGenSets 4 2/17/11 10:06 AM
Proper entrance box design for
handling generator set vibration
All generator sets vibrate during normal operation.
Greater movement can also occur upon sudden
load changes, fault events and/or during startup and
shutdown. In most generators the engine and alternator
— the main sources of vibration on the generator set
— are mounted on the generator set skid. In some
generator set designs, the electrical connection box
will be mounted directly on the alternator, which means
that electrical connections made within the box will
also be subjected to these vibrations. If these forces of
vibration are not mitigated, not only may rigid electrical
connections fail, but vibration forces can also be
transmitted by the stiff connections and cause damage
to the generator set components. Electrical connection
points on the generator — bushings, bus bars,
terminal blocks, etc. — are not designed to absorb
these stresses. Therefore, all electrical connections
to the generator must be able to absorb the vibration
movement and startup/shutdown movements.
The required solution is to use flexible interconnections
for generator set AC power cables and conduits,
so they are able to handle the vibration in all three
dimensions, and the relative movement between the
generator set and its foundation.1
However, situations
may arise where following such recommendations can
add complexity and cost to the overall design.
For example, in high-range (1 MW and above),
low-voltage (below 600V L-L) generator sets with
large current outputs, the size of the conduits can
become quite significant, making it more difficult to
achieve the S-shaped bends required to handle the
three-dimensional vibrations. This problem may be
exacerbated if there is limited space available for
bending the conduit. Limited space will make it difficult
to fit, maneuver and bend the thick conduits, despite
their flexibility.2
In some generator sets the electrical connection box is
mounted directly onto the generator skid (Figure 3).
This can be beneficial, especially if in-skid anti-vibration
mounts (AVMs) are used between the engine/alternator
and the skid. With in-skid AVMs, an electrical connection
box connected directly to the skid will be isolated from
the majority of the vibration generated by the engine/
alternator. This, in turn, will help reduce vibration stresses
at the electrical connection points, which are common
points of failure. This approach may help make the
generator more reliable. Note that generator sets
with in-skid AVMs may still need under-skid isolation
mounts, depending on local seismic requirements.
Another advantage of having the electrical connection
box directly on the skid is that it will be closer to the
foundation. Bottom-entry installations can cover
exposed power leads rising through the stub-up area
using either sheet metal ducts or chutes, which provide
protection from potentially hazardous contact with
power leads. This method allows cables to be run
directly from the stub-up area into the entrance box,
05PowerTopic#9018
www.cumminspower.com
©2011 Cummins Power Generation
Figure 3 - Left: Generator set with skid-mounted circuit breaker box.
Right: Detail showing in-skid anti-vibration mounts (AVMs).
1
Refer to Power Topic #6011: Flexible interconnections for
generator set AC power cables and conduits.
2
For systems of 600V and above, NEC bending require-
ments outlined in Article 300.31 have to be considered.
CPG100249_ConnProvGenSets 5 2/17/11 10:06 AM
06PowerTopic#9018
About the author
Munir Kaderbhai, sales application engineering,
joined Cummins Power Generation in 2010
as a point of contact for generator set sizing,
codes and standards, transfer switches and
general standby power systems application
considerations. Munir has an M.S. in electrical
engineering from North Dakota State University
(Fargo, ND) and a dual B.A. degree in physics and
mathematics from Concordia College (Moorhead, MN).
Prior to joining Cummins, he held electronic design
internships with a couple of construction and agricultural
equipment manufacturers and also worked in R&D at the
NDSU Center for Nanoscale Science & Engineering.
www.cumminspower.com
©2011 Cummins Power Generation Inc. All
rights reserved. Cummins Power Generation and
Cummins are registered trademarks of Cummins
Inc. “Our energy working for you.™
” is a trademark
of Cummins Power Generation.
PT-9018 (01/11)
and cables are much easier to bend than conduits.
Additionally, the metal plate at the bottom of the
electrical connection box can be removed, making it
even easier to route cables into the box. This approach
reduces the cost and complexity of the installation
while increasing reliability.
Conclusion
There are several options in making connections to the
generator set, and several factors to keep in mind for
proper cable termination:
Power cable connections to a generator set may be
terminated at the generator-mounted circuit breaker
or made directly to the alternator terminals.
If the generator has other means of overcurrent
protection, then removing the circuit breaker
altogether can be beneficial. However, it’s important
to ensure that the installation complies with all
applicable NEC rules.
Customers and system designers should work
closely with the Authority Having Jurisdiction (AHJ) to
ensure compliance with local codes.
The generator electrical connection box should be
large enough to accommodate large cables and
provide cable-bending space if required.
All electrical connections to the generator must be
able to absorb vibration movements. Selecting a
generator with a skid-mounted electrical connection
box may help reduce vibration stresses at the
electrical connection points and may also reduce
cable-bending requirements.
Proper design of the bracing and conductor spacing
supports is essential, and therefore prototype test
reports furnished by the generator set manufacturer
should be carefully reviewed.
The AC power supply interconnection to the
generator set must be designed and validated to
withstand damage due to forces of vibration induced
by seismic forces. Some local authorities require
third-party testing or certification of generator set
design to validate seismic performance. These tests
are performed to verify the generator set’s electrical
and mechanical system integrity.
Having a UL2200 Listed generator set is required by
most AHJs and for good reason: It ensures that you
are buying a product certified to meet stringent safety
standards set by a nationally recognized testing agency
and approved third party.
References
ANSI/NFPA 70, National Electrical Code, 2011
ANSI/NFPA 110, Generator Sets for Emergency and
Standby Power Applications
ANSI/NFPA 99, Health Care Facilities
CPG100249_ConnProvGenSets 6 2/17/11 10:06 AM

More Related Content

What's hot

Size a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpSize a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpBassam Gomaa
 
Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion linksing_eliali4748
 
Transmission Line Automation
Transmission Line AutomationTransmission Line Automation
Transmission Line AutomationKundan Kumar
 
MCC Motor Control Center 1
MCC Motor Control Center 1MCC Motor Control Center 1
MCC Motor Control Center 1Sakshi Vashist
 
2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...
2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...
2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...Schneider Electric
 
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...IJERA Editor
 
Microgrid Fault Stability and Protection Considerations
Microgrid Fault Stability and Protection ConsiderationsMicrogrid Fault Stability and Protection Considerations
Microgrid Fault Stability and Protection ConsiderationsPower System Operation
 
42jssc07-pfeiffer-proof
42jssc07-pfeiffer-proof42jssc07-pfeiffer-proof
42jssc07-pfeiffer-proofDavid Goren
 
Wago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalogWago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalogElectromate
 
ESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTD
ESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTDESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTD
ESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTDMahesh Chandra Manav
 
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET Journal
 
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...Power System Operation
 
presentation on power grid system
presentation on power grid systempresentation on power grid system
presentation on power grid systemrahul123gupta
 

What's hot (20)

European Grid Codes
European Grid CodesEuropean Grid Codes
European Grid Codes
 
01 sdms-01 rev01
01 sdms-01 rev0101 sdms-01 rev01
01 sdms-01 rev01
 
CWB Contactors
CWB ContactorsCWB Contactors
CWB Contactors
 
Size a circuit breaker for a fire pump
Size a circuit breaker for a fire pumpSize a circuit breaker for a fire pump
Size a circuit breaker for a fire pump
 
Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion links
 
Transmission Line Automation
Transmission Line AutomationTransmission Line Automation
Transmission Line Automation
 
MCC Motor Control Center 1
MCC Motor Control Center 1MCC Motor Control Center 1
MCC Motor Control Center 1
 
Vsd3
Vsd3Vsd3
Vsd3
 
2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...
2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...
2014 National Electrical Code: Top 10 Revisions Impacting Electrical Installa...
 
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
 
Microgrid Fault Stability and Protection Considerations
Microgrid Fault Stability and Protection ConsiderationsMicrogrid Fault Stability and Protection Considerations
Microgrid Fault Stability and Protection Considerations
 
42jssc07-pfeiffer-proof
42jssc07-pfeiffer-proof42jssc07-pfeiffer-proof
42jssc07-pfeiffer-proof
 
Wago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalogWago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalog
 
ESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTD
ESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTDESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTD
ESE Type Lightning Arretor NFC17-102(2011) Presentation by JMV LPS LTD
 
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
 
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
Determining Multiple Fault Ride-Through Requirements for Generating Systems i...
 
Abb rmu
Abb rmuAbb rmu
Abb rmu
 
Ppt iitr
Ppt iitrPpt iitr
Ppt iitr
 
Bussmann fuse-azzan-al-badi-trading-oman-muscat-medium-voltage-fuses
Bussmann fuse-azzan-al-badi-trading-oman-muscat-medium-voltage-fusesBussmann fuse-azzan-al-badi-trading-oman-muscat-medium-voltage-fuses
Bussmann fuse-azzan-al-badi-trading-oman-muscat-medium-voltage-fuses
 
presentation on power grid system
presentation on power grid systempresentation on power grid system
presentation on power grid system
 

Viewers also liked

Sales Engineer _Projects _ Pumps 2
Sales Engineer _Projects _ Pumps 2Sales Engineer _Projects _ Pumps 2
Sales Engineer _Projects _ Pumps 2AMIT CHAUHAN
 
Acoustics & Generator Ratings
Acoustics & Generator RatingsAcoustics & Generator Ratings
Acoustics & Generator RatingsJonny Rodgers
 
Top 8 pre sales engineer resume samples
Top 8 pre sales engineer resume samplesTop 8 pre sales engineer resume samples
Top 8 pre sales engineer resume samplesjomcoret
 
Importancia de las redes sociales
Importancia de las redes socialesImportancia de las redes sociales
Importancia de las redes socialesdavid9709
 
Facebook Contest Check List via ShortStack.com
Facebook Contest Check List via ShortStack.comFacebook Contest Check List via ShortStack.com
Facebook Contest Check List via ShortStack.comLuis Amendola
 
Cruise city break 2013 thursday
Cruise city break 2013 thursdayCruise city break 2013 thursday
Cruise city break 2013 thursdayShannon Collins
 
Innovación docente y uso de las TIC en la enseñanza universitaria
Innovación docente y uso de las TIC en la enseñanza universitariaInnovación docente y uso de las TIC en la enseñanza universitaria
Innovación docente y uso de las TIC en la enseñanza universitariaPatricio Perez-Guerrero
 
MundodasTribos:Últimas notícias
MundodasTribos:Últimas notíciasMundodasTribos:Últimas notícias
MundodasTribos:Últimas notíciasRaildaSilva2
 
O cavaleiro da dinamarca
O cavaleiro da dinamarcaO cavaleiro da dinamarca
O cavaleiro da dinamarcaFilipa19
 
1ο επιμ σεμιν διαπ εκπ 5 12-14
1ο επιμ σεμιν διαπ  εκπ 5 12-141ο επιμ σεμιν διαπ  εκπ 5 12-14
1ο επιμ σεμιν διαπ εκπ 5 12-14D K
 
الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎
الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎
الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎AbdelGhany ElTelbany
 
El nuevo papel del docente con las TIC
El nuevo papel del docente con las TICEl nuevo papel del docente con las TIC
El nuevo papel del docente con las TICJoshua Villalba
 
Universitario de tecnología contabilidad
Universitario de tecnología contabilidadUniversitario de tecnología contabilidad
Universitario de tecnología contabilidadkattyrojass
 
Revista de contabiliadad
Revista de contabiliadadRevista de contabiliadad
Revista de contabiliadadnickcasimiro
 
Canales Abiertos, Douglas Bravo CI: 17943257
Canales Abiertos, Douglas Bravo CI: 17943257Canales Abiertos, Douglas Bravo CI: 17943257
Canales Abiertos, Douglas Bravo CI: 17943257DouglasBM
 
Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...
Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...
Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...Principled Technologies
 

Viewers also liked (20)

Sales Engineer _Projects _ Pumps 2
Sales Engineer _Projects _ Pumps 2Sales Engineer _Projects _ Pumps 2
Sales Engineer _Projects _ Pumps 2
 
Acoustics & Generator Ratings
Acoustics & Generator RatingsAcoustics & Generator Ratings
Acoustics & Generator Ratings
 
Top 8 pre sales engineer resume samples
Top 8 pre sales engineer resume samplesTop 8 pre sales engineer resume samples
Top 8 pre sales engineer resume samples
 
SALE-NCC-Resume-05APR2016
SALE-NCC-Resume-05APR2016SALE-NCC-Resume-05APR2016
SALE-NCC-Resume-05APR2016
 
Importancia de las redes sociales
Importancia de las redes socialesImportancia de las redes sociales
Importancia de las redes sociales
 
Facebook Contest Check List via ShortStack.com
Facebook Contest Check List via ShortStack.comFacebook Contest Check List via ShortStack.com
Facebook Contest Check List via ShortStack.com
 
Cruise city break 2013 thursday
Cruise city break 2013 thursdayCruise city break 2013 thursday
Cruise city break 2013 thursday
 
Innovación docente y uso de las TIC en la enseñanza universitaria
Innovación docente y uso de las TIC en la enseñanza universitariaInnovación docente y uso de las TIC en la enseñanza universitaria
Innovación docente y uso de las TIC en la enseñanza universitaria
 
MundodasTribos:Últimas notícias
MundodasTribos:Últimas notíciasMundodasTribos:Últimas notícias
MundodasTribos:Últimas notícias
 
O cavaleiro da dinamarca
O cavaleiro da dinamarcaO cavaleiro da dinamarca
O cavaleiro da dinamarca
 
1ο επιμ σεμιν διαπ εκπ 5 12-14
1ο επιμ σεμιν διαπ  εκπ 5 12-141ο επιμ σεμιν διαπ  εκπ 5 12-14
1ο επιμ σεμιν διαπ εκπ 5 12-14
 
Planogramacion
PlanogramacionPlanogramacion
Planogramacion
 
Assignment 15 all
Assignment 15 allAssignment 15 all
Assignment 15 all
 
7 ejes de desarrollo
7 ejes de desarrollo7 ejes de desarrollo
7 ejes de desarrollo
 
الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎
الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎
الوقائع المصرية العدد 65 فى 21 مارس سنة 2015‎
 
El nuevo papel del docente con las TIC
El nuevo papel del docente con las TICEl nuevo papel del docente con las TIC
El nuevo papel del docente con las TIC
 
Universitario de tecnología contabilidad
Universitario de tecnología contabilidadUniversitario de tecnología contabilidad
Universitario de tecnología contabilidad
 
Revista de contabiliadad
Revista de contabiliadadRevista de contabiliadad
Revista de contabiliadad
 
Canales Abiertos, Douglas Bravo CI: 17943257
Canales Abiertos, Douglas Bravo CI: 17943257Canales Abiertos, Douglas Bravo CI: 17943257
Canales Abiertos, Douglas Bravo CI: 17943257
 
Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...
Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...
Intel processor-powered Windows 8 tablet vs. ARM processor-based Windows RT t...
 

Similar to PT-9018-ConnProvGenSets-en

3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdfShahrukhKhan424745
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DCMahesh Chandra Manav
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revisedBasudev patra
 
Access control basics-9
Access control basics-9Access control basics-9
Access control basics-9grantlerc
 
Understanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitUnderstanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitBassam Gomaa
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_advertsKhalid Sithari
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4AxelDijksman
 
NTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportNTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportAneel-k Suthar
 
ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...
ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...
ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...Thorne & Derrick International
 
Ansi mv tech_topics43_en
Ansi mv tech_topics43_enAnsi mv tech_topics43_en
Ansi mv tech_topics43_enANURAG GUPTA
 
Selecting proper dg set
Selecting proper dg setSelecting proper dg set
Selecting proper dg setMKJain1511
 
Motor control and protection
Motor control and protectionMotor control and protection
Motor control and protectionAllan Bernardino
 
National Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesNational Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesSchneider Electric
 

Similar to PT-9018-ConnProvGenSets-en (20)

Cable tray manual
Cable tray manualCable tray manual
Cable tray manual
 
3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DC
 
power 6210.pdf
power 6210.pdfpower 6210.pdf
power 6210.pdf
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
 
Access control basics-9
Access control basics-9Access control basics-9
Access control basics-9
 
11.docx
11.docx11.docx
11.docx
 
Understanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitUnderstanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuit
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
Universal Four Leg v4
Universal Four Leg v4Universal Four Leg v4
Universal Four Leg v4
 
NTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship reportNTDC 220kV Transmission gird station Internship report
NTDC 220kV Transmission gird station Internship report
 
ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...
ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...
ABB Medium Voltage Indoor Fuses - ABB CEF-VT High Voltage Current Limiting Fu...
 
Ansi mv tech_topics43_en
Ansi mv tech_topics43_enAnsi mv tech_topics43_en
Ansi mv tech_topics43_en
 
C2000 m en_20120201
C2000 m en_20120201C2000 m en_20120201
C2000 m en_20120201
 
Ocpd 07-23-13
Ocpd 07-23-13Ocpd 07-23-13
Ocpd 07-23-13
 
Distribution Automation_2012
Distribution Automation_2012Distribution Automation_2012
Distribution Automation_2012
 
Selecting proper dg set
Selecting proper dg setSelecting proper dg set
Selecting proper dg set
 
Motor control and protection
Motor control and protectionMotor control and protection
Motor control and protection
 
National Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code ChangesNational Electrical Code: 2014 Code Changes
National Electrical Code: 2014 Code Changes
 

PT-9018-ConnProvGenSets-en

  • 1. Design for safety and reliability – appropriate connection provisions for generator sets White Paper By Munir Kaderbhai, Sales Application Engineer Standby electric generators provide a welcome measure of protection against a loss of power, but only if the generators are properly installed and applied. One of the most crucial installation concerns is the load conductors’ connection to the generator set. The load conductors, their connection points and routing away from the generator set are the means to transfer energy from the emergency power source to the power distribution system. If the quality of these connections is jeopardized in any way, it can lead to safety hazards and make your emergency power source unreliable. Priorities and options in generator connections When reviewing the installation of your emergency power supply system, give top priority to proper electrical connections to the generator. You should ensure that the generator set is installed using appropriate provisions to allow a reliable, economical and safe connection. There are several ways in which connections to the generator can be made, and several factors to keep in mind for proper connections, including alternator and conductor overload protection, disconnect requirements, conductor size and vibration. The goal of this paper is to highlight these factors and to provide recommendations for safe, durable and reliable load conductor connections. Generator connection options Power connections to a generator set may be made to generator-mounted circuit breakers or, when alternator and conductor overload protection is provided by a device such as AmpSentry™ Protective Relay, directly to the alternator terminals. In installations where there is no integral Underwriters Laboratory® (UL) Listed means of protection for the generator Power topic #9018 | Technical information from Cummins Power Generation c 5 connection provisions for generator sets M Y K InitIals dateJOB # CPG100249 DATE 2.17.11 CLIENT Cummins Power Generation JOB DESCRIPTION White Paper FLAT 8.5" x 11" BLEED .125" FOLDED FILE 100% COLOR CMYK CD AD CW Don Flanagan DS AM Christie Graham PM Katie DeSmet CLIENT CPG100249_ConnProvGenSets 1 2/17/11 10:06 AM
  • 2. 02PowerTopic#9018 and its conductors, then connection to a circuit breaker (CB) is common. Protection requirements are detailed in National Electric Code (NEC) article 445.12. Both molded case and insulated case CBs may be used for generator sets. Molded case breakers are typically mounted in a circuit breaker enclosure directly attached to the alternator. The CB box may house single or dual CBs depending on the application requirements. Insulated case CBs are typically larger and more sensitive to vibration. They are usually mounted in a freestanding enclosure next to the generator. If connections are being made to the generator via a CB and if the CB does not include mechanical lugs, then the installer needs to provide lugs for customer connections. These lugs should be anti-rotational, to prevent the connections from loosening due to vibration or thermal expansion. It is important to verify that the number of conductors per phase and the conductors’ size match the published lug quantities and capacities on the CBs. The lug set-screws should be tightened using torque values provided by the manufacturer, so that the cables are not damaged. If the generator has UL Listed integral means of overload protection, oftentimes it’s beneficial to remove the CB and make electrical connections directly to the generator set. Removing the breaker can make the task of selectively coordinating the overcurrent protection devices downstream less complicated, because then all of the CBs or fuses in the emergency system can be provided by a single supplier. Without a main CB on the generator, provisions to connect to the generator set are provided via an entrance box. Top entry versus bottom entry Conductors can be routed into the CB or entrance box through either the top or bottom surface of the box (Figure 1). If you are the system designer, you should specify on the facility drawings or in the specifications whether the intention is to top-connect or bottom- connect the generator set. Customer connection points inside the box will typically be provided to a bus bar. The bus bars must have NEMA two-hole patterns to comply with the UL connection requirements. This means that the conductors should be terminated using either compression or mechanical lugs and should be secured to the bus bars with proper fasteners. www.cumminspower.com ©2011 Cummins Power Generation Figure 1 - Circuit breaker box (left – bottom entry; right – top entry) – 1) neutral disconnect link; 2) grounding bus; 3) circuit breaker; 4) bottom-entry chute. CPG100249_ConnProvGenSets 2 2/17/11 10:06 AM
  • 3. Using a 100% rated CB assembly can allow the full rating of the breaker to be utilized, and may allow the use of a smaller CB frame size. This practice can help reduce the cost of the breaker and also reduce the amount of space occupied by the CB in the enclosure. The total required cable size may also be reduced, providing more room in the enclosure for the cables and making it easier to connect to the bus bars. Outdoor generator compliance — service-rated equipment NEC Article 225.31 requires a disconnect means for conductors that supply or pass through the building or structure. Article 225.36 states that the disconnect means referred to in 225.31 shall be suitable for use as service equipment. This requirement means that if you have an outdoor generator set, there has to be a service disconnect where the conductors enter the building, and the disconnect has to be a service entrance device. The NEC also requires each disconnecting means that is installed and used as a service disconnecting means to be identified as a service disconnecting means [See Figure 2(2)]. Where an outdoor-housed generator is equipped with readily accessible disconnection means located within the site of the building or structure supplied, an additional disconnecting means is not required where ungrounded conductors pass through the building [NEC Articles 700.12(B)(6), 701.12(B)(5), 702.11]. Note that the disconnection means must be suitable for use as service equipment and labeled as such. Conduit and cable size Conductors connected to the generator set’s alternating current (AC) output should be sized as 03PowerTopic#9018 UL and the NEC require mechanical protection for conductors. For top-entry installations, this protection is typically provided by conduit. These conduits must be flexible enough to handle generator set three- dimensional vibration; they typically have a 90° bend to help absorb vibration. For bottom-entry installations, conduits may be required, depending on the location of the electrical connection box. If the box is mounted on the alternator, then cables running from the stub-up area of the foundation and to the box cannot be left exposed to accidental contact by unqualified persons and must be protected with flexible conduits. UL Listed 100% rated circuit breaker assembly Circuit breaker manufacturers test their breakers to be able to handle 100% rated current for an unlimited time under standard test conditions per UL489. Under these test conditions, the CB is in free air and the ambient temperature is maintained at 40°C. In typical installations, however, the CB will be housed in an enclosure, which can trap heat and increase the temperature inside the box if the enclosure is not adequately sized and ventilated. In thermomagnetic- type circuit breakers, if the temperature within the enclosure exceeds operational limits, it can cause nuisance tripping of the breaker. Therefore, for continuous loads, a typical CB assembly can be applied at only 80% of its rated current. This could mean that you will have to oversize your CB and its conductors in order to operate the generator set at or near its rated load for an extended period of time. All these factors can add cost and complexity to the installation. The NEC has an exception to this rule, which allows CB assemblies to be rated at 100%. In contrast to standard rated (or 80% rated) CBs, 100% rated assemblies can carry 100% of the CB and conductor current rating. In order to be 100% rated, the equipment must undergo additional UL testing to ensure that the additional heat generated by running higher currents through the circuit will be safely dissipated and not cause a high temperature rise within the enclosure. UL489 specifies the minimum enclosure size and venting requirements for the CB box. In addition to meeting these size requirements, the 100% rated assembly must also be labeled as such by the manufacturer [Figure 2 (1)]. Without this label, the assembly will be considered 80%, even if the box size and venting requirements are met. www.cumminspower.com ©2011 Cummins Power Generation Figure 2 - (1) The 100% CB assembly must be labeled by the manufacturer as being 100% rated; (2) Equipment has to bear the marking “suitable for use as service equipment”; (3) Use 90°C rated conductors but size based on ampacity of 75°C. CPG100249_ConnProvGenSets 3 2/17/11 10:06 AM
  • 4. required by the load currents, the application and local electrical codes. The generator set manufacturer will typically specify line-line ampere ratings of a specific generator set for the specific voltage selected. The NEC handbook provides guidelines for the ampacity of phase and neutral conductors connected to the generator set. Article 445.13 requires that the ampacity of conductors from the generator terminals to the first distribution device(s) containing overcurrent protection shall not be less than 115% of the nameplate rating of the generator set. The exception is for generator designs that have inherent means for preventing an overload condition. For that case, conductors can be rated at 100% of the nameplate current rating. NEC Article 310 covers general requirements for conductors and provides tables that can be used to help determine minimum conductor size. In larger generator set applications, both the size and the number of the cables and conduits can get very large, so it is important to ensure that electrical connection boxes are sized appropriately, not only to accommodate the cables/conduits but also to provide adequate space for easy entry into the box. Most likely, you will have more than one cable/conduit per phase, so there should also be provisions in the entrance box for multiple conduits. For example, multiple punch-outs and liquid tight strain relief connectors are recommended. NEC Article 445.16 also requires that cables that pass though the opening in the enclosures be protected by bushings from openings with sharp edges. As an example, consider a 2MW generator set that is rated at about 3000A at 480V. For a type RHW copper cable with temperature rating of 75°C and an ambient temperature of 30°C (86°F), the ampacity of a 750 kcmil given by Table 310.15(B)(16) in the NEC handbook is 475A. A total of eight cables will give a total current rating of 3800A. It is good practice to design for at least an ambient temperature of 40°C, which requires the use of a 0.88 correction factor from Table 310.15(B)(2)(a). This reduces the current rating to 3344A. An additional correction factor of 0.7 from Table 310.15(B)(3)(a) also must be applied if there are more than three cables bundled together per raceway/ conduit, dropping the capacity and current rating of the eight cables to 2340A. This example demonstrates the fact that many large cables can be required to be able to use the full rated current output of the generator set. It also demonstrates the importance of ensuring that the electrical connection box not only allows entry for multiple cables but also has sufficient space and sufficiently large entrance holes to accommodate all these large cables. Having an adequately sized electrical connection box is important, because it provides adequate bend space for very large conductors and allows ease of installation for the electrician. Bus bar temperature rise Per UL2200 requirements, the temperature of a bus bar can be as high as 90°C over a 40°C ambient temperature. Therefore, it is sometimes recommended that the conductors connecting to the bus bars be 90°C rated. However, the conductors must still be sized using the 75°C column in 310.15(B)(16) in the NEC. This is because the terminations of electrical utilization equipment, such as CBs, panelboards and transfer switches, are rated for a maximum temperature of 75°C. Regarding temperatures, note that there are two “flavors” of 100% rated CBs, which are defined by the temperature limits at the wire terminal connection. The temperature can either rise to a maximum temperature of 50°C at a 40°C ambient, or it may rise to a temperature of 60°C at the wire terminal connection at a 40°C ambient. If the temperature rise is below 50°C, then you may use a 75°C rated conductor sized to the 75°C chart. If the temperature rise is over 50°C but below 60°C, then you have to use a 90°C rated conductor sized to the 75°C chart. The manufacturer may specify that you use 90°C rated wire-based ampacity of 75°C wire [Figure 2(3)]. Bracing requirements It is essential to have bracing and conductor spacing supports that are physically and electrically able to withstand expected mechanical forces and voltages. Short circuit currents can induce tremendous magnetic forces between conductors. If conductor bracing and supports are not adequate, there could be enough force to bend metals, to break insulators and to disconnect any connector terminations that are not securely fastened. Generator sets are required by NFPA 110 to be short circuit tested, and one part of that testing is to validate the design of the electrical connection box. NFPA 110 section 5.2.3 (1) requires generators for Level 1 systems to be specifically designed, assembled and tested to ensure system operation under short circuits. Prototype tests must be performed by the manufacturer to verify that the generator can safely withstand the forces associated with short circuit conditions. 04PowerTopic#9018 www.cumminspower.com ©2011 Cummins Power Generation CPG100249_ConnProvGenSets 4 2/17/11 10:06 AM
  • 5. Proper entrance box design for handling generator set vibration All generator sets vibrate during normal operation. Greater movement can also occur upon sudden load changes, fault events and/or during startup and shutdown. In most generators the engine and alternator — the main sources of vibration on the generator set — are mounted on the generator set skid. In some generator set designs, the electrical connection box will be mounted directly on the alternator, which means that electrical connections made within the box will also be subjected to these vibrations. If these forces of vibration are not mitigated, not only may rigid electrical connections fail, but vibration forces can also be transmitted by the stiff connections and cause damage to the generator set components. Electrical connection points on the generator — bushings, bus bars, terminal blocks, etc. — are not designed to absorb these stresses. Therefore, all electrical connections to the generator must be able to absorb the vibration movement and startup/shutdown movements. The required solution is to use flexible interconnections for generator set AC power cables and conduits, so they are able to handle the vibration in all three dimensions, and the relative movement between the generator set and its foundation.1 However, situations may arise where following such recommendations can add complexity and cost to the overall design. For example, in high-range (1 MW and above), low-voltage (below 600V L-L) generator sets with large current outputs, the size of the conduits can become quite significant, making it more difficult to achieve the S-shaped bends required to handle the three-dimensional vibrations. This problem may be exacerbated if there is limited space available for bending the conduit. Limited space will make it difficult to fit, maneuver and bend the thick conduits, despite their flexibility.2 In some generator sets the electrical connection box is mounted directly onto the generator skid (Figure 3). This can be beneficial, especially if in-skid anti-vibration mounts (AVMs) are used between the engine/alternator and the skid. With in-skid AVMs, an electrical connection box connected directly to the skid will be isolated from the majority of the vibration generated by the engine/ alternator. This, in turn, will help reduce vibration stresses at the electrical connection points, which are common points of failure. This approach may help make the generator more reliable. Note that generator sets with in-skid AVMs may still need under-skid isolation mounts, depending on local seismic requirements. Another advantage of having the electrical connection box directly on the skid is that it will be closer to the foundation. Bottom-entry installations can cover exposed power leads rising through the stub-up area using either sheet metal ducts or chutes, which provide protection from potentially hazardous contact with power leads. This method allows cables to be run directly from the stub-up area into the entrance box, 05PowerTopic#9018 www.cumminspower.com ©2011 Cummins Power Generation Figure 3 - Left: Generator set with skid-mounted circuit breaker box. Right: Detail showing in-skid anti-vibration mounts (AVMs). 1 Refer to Power Topic #6011: Flexible interconnections for generator set AC power cables and conduits. 2 For systems of 600V and above, NEC bending require- ments outlined in Article 300.31 have to be considered. CPG100249_ConnProvGenSets 5 2/17/11 10:06 AM
  • 6. 06PowerTopic#9018 About the author Munir Kaderbhai, sales application engineering, joined Cummins Power Generation in 2010 as a point of contact for generator set sizing, codes and standards, transfer switches and general standby power systems application considerations. Munir has an M.S. in electrical engineering from North Dakota State University (Fargo, ND) and a dual B.A. degree in physics and mathematics from Concordia College (Moorhead, MN). Prior to joining Cummins, he held electronic design internships with a couple of construction and agricultural equipment manufacturers and also worked in R&D at the NDSU Center for Nanoscale Science & Engineering. www.cumminspower.com ©2011 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.™ ” is a trademark of Cummins Power Generation. PT-9018 (01/11) and cables are much easier to bend than conduits. Additionally, the metal plate at the bottom of the electrical connection box can be removed, making it even easier to route cables into the box. This approach reduces the cost and complexity of the installation while increasing reliability. Conclusion There are several options in making connections to the generator set, and several factors to keep in mind for proper cable termination: Power cable connections to a generator set may be terminated at the generator-mounted circuit breaker or made directly to the alternator terminals. If the generator has other means of overcurrent protection, then removing the circuit breaker altogether can be beneficial. However, it’s important to ensure that the installation complies with all applicable NEC rules. Customers and system designers should work closely with the Authority Having Jurisdiction (AHJ) to ensure compliance with local codes. The generator electrical connection box should be large enough to accommodate large cables and provide cable-bending space if required. All electrical connections to the generator must be able to absorb vibration movements. Selecting a generator with a skid-mounted electrical connection box may help reduce vibration stresses at the electrical connection points and may also reduce cable-bending requirements. Proper design of the bracing and conductor spacing supports is essential, and therefore prototype test reports furnished by the generator set manufacturer should be carefully reviewed. The AC power supply interconnection to the generator set must be designed and validated to withstand damage due to forces of vibration induced by seismic forces. Some local authorities require third-party testing or certification of generator set design to validate seismic performance. These tests are performed to verify the generator set’s electrical and mechanical system integrity. Having a UL2200 Listed generator set is required by most AHJs and for good reason: It ensures that you are buying a product certified to meet stringent safety standards set by a nationally recognized testing agency and approved third party. References ANSI/NFPA 70, National Electrical Code, 2011 ANSI/NFPA 110, Generator Sets for Emergency and Standby Power Applications ANSI/NFPA 99, Health Care Facilities CPG100249_ConnProvGenSets 6 2/17/11 10:06 AM