TechTopics No. 43
Interposing relay requirements
Answers for infrastructure.
A few salient points extracted from ANSI/IEEE C37.90 are:
	 5.7.1 Tripping output performance requirements:
	“Tripping output circuits shall meet the following
specification for performance: The contacts or output circuit
shall make and carry 30 A for at least 2000 operations in
a duty cycle... The load shall be resistive for both dc and
ac and the current shall be interrupted by independent
means…”
	 5.7.2 Continuous and interrupting ratings of tripping
output circuits:
“Tripping output contacts intended by the manufacturer to
be for tripping duty only shall be identified as such and may
have no continuous or interrupting duty…”
The requirement in ANSI/IEEE C37.90 for a making capability of
30 A is appropriate for older design circuit breakers. However,
the operating currents of modern circuit breakers are often
much lower than those of the historic designs, as indicated in
the table for the type GMSG circuit breaker above.
Remote control of circuit breakers is becoming much more
prevalent as the use of monitoring and central control
equipment grows. When remote control is used, interposing
relays are generally required to avoid a large voltage drop in
the close and trip coil circuits. Here are a few thoughts on the
proper selection of interposing relays.
Current ratings
Interposing relay contacts used in close and trip circuits must
have the ability to make and carry the current of the close
and trip coils. For our type GMSG circuit breakers, the control
current data is as follows:
The interposing relay contact is directly analogous to a tripping
output contact on a protective relay, so it is instructive to
review the requirements of ANSI/IEEE C37.90 for tripping
output contacts of protective relays.
Control voltage and current
Nominal rated control voltage Control voltage range Close coil current (A) Trip coil current (A)
Close Trip
48 Vdc 38-56 28-56 2.9 11.4/301
125 Vdc 100-140 70-140 1.0 4.8/7.41
250 Vdc 200-280 140-280 0.5 2.1/4.21
120 Vac 104-127 104-127 0.9 ---
240 Vac 208-254 208-254 0.4 ---
Footnote:	
1
First value is for five-cycle (83 ms) rated interrupting time, second value is for three-cycle (50 ms) rated interrupting time.
The philosophy embodied in ANSI/IEEE C37.90 is appropriate
for the application to tripping of circuit breakers, and
similar logic applies to application of interposing relays in
closing circuits. The interposing relay has to have a making
capability, but does not have to have a significant interrupting
capacity. This is so because the close and trip coil currents
are interrupted by the “a” or “b” switch contacts on the circuit
breaker.
Therefore, the interposing relay should be able to make the
current of the close or trip coil of the circuit breaker. The
contacts also need to be able to carry the current for the time
necessary for circuit breaker operation, but this is not a severe
requirement. The duration of the closing or tripping current
with modern circuit breakers is several tens of milliseconds,
so the relay is not required to carry the current for a long
time. The interposing relay contacts do not need to be able to
interrupt the coil currents.
Typical interposing relays
A wide variety of relays are suitable for use in interposing
relay applications. The most extensively-used relays over the
decades are the GE type HFA and Westinghouse (ABB) type
SG relays. These are older designs, and take somewhat more
space than newer relays, but have a long record of success.
More recently, a number of smaller relays have been used for
interposing applications. Among these are relays from Potter
 Brumfield (KRP), Struthers  Dunn (219) and even some of
the miniature (“ice cube”) relays from several suppliers. Any of
these relays are suitable provided they meet the voltage and
current requirements of the application.
Typical control scheme
The basic elements of typical controls are shown in the
schematic diagram. A few observations on the control scheme:
	Interposing relays are connected to the same control voltage
supply as is used for the circuit breaker. Many contacts
used to initiate remote closing or tripping, particularly PLC
contacts, cannot handle the higher control voltages (e.g.,
125 Vdc) used in the circuit breaker control scheme. In such
cases, the interposing relay coil should be connected to the
lower control voltage of the PLC (typically, 24 Vdc), and
actuated by the contact from the PLC. The interposing relay
output contact should be connected in the circuit breaker
control circuit.
	Interposing relay contacts must provide a signal duration
of at least 50 ms. Latched-type relays must not be used.
Maintained contacts must never be used to actuate a circuit
breaker close or trip circuit.
	The interposing relay coil should have a very low operating
current, to minimize voltage drop in the control circuit from
the remote actuating contact to the interposing relay coil.
	The minimum pickup voltage for the interposing relay must
be compatible with the minimum control voltage specified
in ANSI/IEEE standards for the switchgear. For dc tripping
circuits, the control voltage range in ANSI/IEEE C37.06 is
56 percent to 112 percent of the rated voltage. For example,
the range for 125 Vdc circuits is 70 to 140 Vdc. In contrast,
the control voltage range given in ANSI/IEEE C37.90 for
protective relays is 80 percent to 112 percent of rated
voltage, or 100 to 140 Vdc for our example.
	In this scheme, the circuit includes truck-operated cell (TOC)
contacts responsive to the position of the circuit breaker
in the cell. These contacts are used to make the local
control switch close contact (CS/C) operative only in the
TEST position. The local control switch trip contact (CS/T) is
operative in both the TEST and CONNECTED position. The
TOC contacts are used to make the remote control contacts
(201T and 201C) operative only in the CONNECTED position.
Most users prefer that remote control contacts be operative
only in the CONNECTED position. User preferences are less
pronounced regarding local control circuits, with some
users desiring that local circuits be operable only in the TEST
position, and others desiring that local control circuits be
operable in both CONNECTED and TEST positions.
The information provided in this document contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result of
further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the terms
of contract.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.
Siemens Industry, Inc.
7000 Siemens Road
Wendell, NC 27591
Subject to change without prior notice.
Order No.: E50001-F710-A331-X-4A00
All rights reserved.
© 2012 Siemens Industry, Inc.
For more information, contact: +1 (800) 347-6659
www.usa.siemens.com/techtopics
Symbols
52/a Aux switch (open when CB open)
52/b Aux switch (closed when CB open)
52SRC Close coil
52T Trip coil
CS/C Control switch (local) close contact
CS/T Control switch (local) trip contact
RL Red indicating lamp
GL Green indicating lamp
201C Interposing relay, close
201T Interposing relay, trip
TOC/a
Truck operated cell switch, closed when CB in
connected position
TOC/b
Truck operated cell switch, open when CB in
connected position
LS Limit switch (spring charged)

More Related Content

What's hot

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Maxpromotion
 
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15 Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15 ashwini reliserv
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersThorne & Derrick International
 
Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by NielsEquipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by NielsNiels Inderbiethen
 
Fuji sc and sw series contactors
Fuji sc and sw series contactorsFuji sc and sw series contactors
Fuji sc and sw series contactorsEko Kiswanto
 
03 - Control Relays & Timer - Fuji Electric
03 - Control Relays & Timer - Fuji Electric03 - Control Relays & Timer - Fuji Electric
03 - Control Relays & Timer - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"michaeljmack
 
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...Thorne & Derrick International
 
Catalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.comCatalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.comBeeteco
 

What's hot (18)

Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Kde200 user manual
Kde200 user manualKde200 user manual
Kde200 user manual
 
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15 Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
Auxiliary relay 7PJ12, 7PJ113, 7PJ11, 7PJ15
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
 
Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by NielsEquipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
Equipment Audits for LV, MV, HV for annual mandatory record keeping by Niels
 
Fuji sc and sw series contactors
Fuji sc and sw series contactorsFuji sc and sw series contactors
Fuji sc and sw series contactors
 
03 - Control Relays & Timer - Fuji Electric
03 - Control Relays & Timer - Fuji Electric03 - Control Relays & Timer - Fuji Electric
03 - Control Relays & Timer - Fuji Electric
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
 
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
36kV high voltage drawout VCB type switchgear
36kV high voltage drawout VCB type switchgear36kV high voltage drawout VCB type switchgear
36kV high voltage drawout VCB type switchgear
 
01 - Contactor - Fuji Electric
 01 - Contactor - Fuji Electric 01 - Contactor - Fuji Electric
01 - Contactor - Fuji Electric
 
Acb2
Acb2Acb2
Acb2
 
Training Adobe
Training AdobeTraining Adobe
Training Adobe
 
Catalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.comCatalog Contactor Fuji Electric - Beeteco.com
Catalog Contactor Fuji Electric - Beeteco.com
 

Similar to Ansi mv tech_topics43_en

Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
Advanced motion controls sx25a20
Advanced motion controls sx25a20Advanced motion controls sx25a20
Advanced motion controls sx25a20Electromate
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCTY TNHH HẠO PHƯƠNG
 
Advanced motion controls s60a8
Advanced motion controls s60a8Advanced motion controls s60a8
Advanced motion controls s60a8Electromate
 
Advanced motion controls s30a40
Advanced motion controls s30a40Advanced motion controls s30a40
Advanced motion controls s30a40Electromate
 
Advanced motion controls s60a40
Advanced motion controls s60a40Advanced motion controls s60a40
Advanced motion controls s60a40Electromate
 
Catalog cs switch disconnectors_dienhathe.vn
Catalog cs switch disconnectors_dienhathe.vnCatalog cs switch disconnectors_dienhathe.vn
Catalog cs switch disconnectors_dienhathe.vnDien Ha The
 
OneGear SMC 15kV Soft Starter
OneGear SMC 15kV Soft StarterOneGear SMC 15kV Soft Starter
OneGear SMC 15kV Soft StarterPaul Plavicheanu
 
Advanced motion controls s100a20
Advanced motion controls s100a20Advanced motion controls s100a20
Advanced motion controls s100a20Electromate
 
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...IRJET Journal
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40acElectromate
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40acElectromate
 
Advanced motion controls s100a8
Advanced motion controls s100a8Advanced motion controls s100a8
Advanced motion controls s100a8Electromate
 
Advanced motion controls s16a8
Advanced motion controls s16a8Advanced motion controls s16a8
Advanced motion controls s16a8Electromate
 
Advanced motion controls s100a40
Advanced motion controls s100a40Advanced motion controls s100a40
Advanced motion controls s100a40Electromate
 
Amp regen clamp_specsheet
Amp regen clamp_specsheetAmp regen clamp_specsheet
Amp regen clamp_specsheetElectromate
 
Advanced motion controls sx30a8
Advanced motion controls sx30a8Advanced motion controls sx30a8
Advanced motion controls sx30a8Electromate
 

Similar to Ansi mv tech_topics43_en (20)

How to build a Inverters
How to build a InvertersHow to build a Inverters
How to build a Inverters
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
Advanced motion controls sx25a20
Advanced motion controls sx25a20Advanced motion controls sx25a20
Advanced motion controls sx25a20
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
 
Advanced motion controls s60a8
Advanced motion controls s60a8Advanced motion controls s60a8
Advanced motion controls s60a8
 
Advanced motion controls s30a40
Advanced motion controls s30a40Advanced motion controls s30a40
Advanced motion controls s30a40
 
Advanced motion controls s60a40
Advanced motion controls s60a40Advanced motion controls s60a40
Advanced motion controls s60a40
 
Catalog cs switch disconnectors_dienhathe.vn
Catalog cs switch disconnectors_dienhathe.vnCatalog cs switch disconnectors_dienhathe.vn
Catalog cs switch disconnectors_dienhathe.vn
 
OneGear SMC 15kV Soft Starter
OneGear SMC 15kV Soft StarterOneGear SMC 15kV Soft Starter
OneGear SMC 15kV Soft Starter
 
7PG2111 Solkor Relay
7PG2111 Solkor Relay7PG2111 Solkor Relay
7PG2111 Solkor Relay
 
Advanced motion controls s100a20
Advanced motion controls s100a20Advanced motion controls s100a20
Advanced motion controls s100a20
 
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
 
Advanced motion controls s60a40ac
Advanced motion controls s60a40acAdvanced motion controls s60a40ac
Advanced motion controls s60a40ac
 
Advanced motion controls s100a40ac
Advanced motion controls s100a40acAdvanced motion controls s100a40ac
Advanced motion controls s100a40ac
 
Dec2001 contactor
Dec2001   contactorDec2001   contactor
Dec2001 contactor
 
Advanced motion controls s100a8
Advanced motion controls s100a8Advanced motion controls s100a8
Advanced motion controls s100a8
 
Advanced motion controls s16a8
Advanced motion controls s16a8Advanced motion controls s16a8
Advanced motion controls s16a8
 
Advanced motion controls s100a40
Advanced motion controls s100a40Advanced motion controls s100a40
Advanced motion controls s100a40
 
Amp regen clamp_specsheet
Amp regen clamp_specsheetAmp regen clamp_specsheet
Amp regen clamp_specsheet
 
Advanced motion controls sx30a8
Advanced motion controls sx30a8Advanced motion controls sx30a8
Advanced motion controls sx30a8
 

Recently uploaded

CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 

Recently uploaded (20)

CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 

Ansi mv tech_topics43_en

  • 1. www.usa.siemens.com/techtopics TechTopics No. 43 Interposing relay requirements Answers for infrastructure. A few salient points extracted from ANSI/IEEE C37.90 are: 5.7.1 Tripping output performance requirements: “Tripping output circuits shall meet the following specification for performance: The contacts or output circuit shall make and carry 30 A for at least 2000 operations in a duty cycle... The load shall be resistive for both dc and ac and the current shall be interrupted by independent means…” 5.7.2 Continuous and interrupting ratings of tripping output circuits: “Tripping output contacts intended by the manufacturer to be for tripping duty only shall be identified as such and may have no continuous or interrupting duty…” The requirement in ANSI/IEEE C37.90 for a making capability of 30 A is appropriate for older design circuit breakers. However, the operating currents of modern circuit breakers are often much lower than those of the historic designs, as indicated in the table for the type GMSG circuit breaker above. Remote control of circuit breakers is becoming much more prevalent as the use of monitoring and central control equipment grows. When remote control is used, interposing relays are generally required to avoid a large voltage drop in the close and trip coil circuits. Here are a few thoughts on the proper selection of interposing relays. Current ratings Interposing relay contacts used in close and trip circuits must have the ability to make and carry the current of the close and trip coils. For our type GMSG circuit breakers, the control current data is as follows: The interposing relay contact is directly analogous to a tripping output contact on a protective relay, so it is instructive to review the requirements of ANSI/IEEE C37.90 for tripping output contacts of protective relays. Control voltage and current Nominal rated control voltage Control voltage range Close coil current (A) Trip coil current (A) Close Trip 48 Vdc 38-56 28-56 2.9 11.4/301 125 Vdc 100-140 70-140 1.0 4.8/7.41 250 Vdc 200-280 140-280 0.5 2.1/4.21 120 Vac 104-127 104-127 0.9 --- 240 Vac 208-254 208-254 0.4 --- Footnote: 1 First value is for five-cycle (83 ms) rated interrupting time, second value is for three-cycle (50 ms) rated interrupting time.
  • 2. The philosophy embodied in ANSI/IEEE C37.90 is appropriate for the application to tripping of circuit breakers, and similar logic applies to application of interposing relays in closing circuits. The interposing relay has to have a making capability, but does not have to have a significant interrupting capacity. This is so because the close and trip coil currents are interrupted by the “a” or “b” switch contacts on the circuit breaker. Therefore, the interposing relay should be able to make the current of the close or trip coil of the circuit breaker. The contacts also need to be able to carry the current for the time necessary for circuit breaker operation, but this is not a severe requirement. The duration of the closing or tripping current with modern circuit breakers is several tens of milliseconds, so the relay is not required to carry the current for a long time. The interposing relay contacts do not need to be able to interrupt the coil currents. Typical interposing relays A wide variety of relays are suitable for use in interposing relay applications. The most extensively-used relays over the decades are the GE type HFA and Westinghouse (ABB) type SG relays. These are older designs, and take somewhat more space than newer relays, but have a long record of success. More recently, a number of smaller relays have been used for interposing applications. Among these are relays from Potter Brumfield (KRP), Struthers Dunn (219) and even some of the miniature (“ice cube”) relays from several suppliers. Any of these relays are suitable provided they meet the voltage and current requirements of the application. Typical control scheme The basic elements of typical controls are shown in the schematic diagram. A few observations on the control scheme: Interposing relays are connected to the same control voltage supply as is used for the circuit breaker. Many contacts used to initiate remote closing or tripping, particularly PLC contacts, cannot handle the higher control voltages (e.g., 125 Vdc) used in the circuit breaker control scheme. In such cases, the interposing relay coil should be connected to the lower control voltage of the PLC (typically, 24 Vdc), and actuated by the contact from the PLC. The interposing relay output contact should be connected in the circuit breaker control circuit. Interposing relay contacts must provide a signal duration of at least 50 ms. Latched-type relays must not be used. Maintained contacts must never be used to actuate a circuit breaker close or trip circuit. The interposing relay coil should have a very low operating current, to minimize voltage drop in the control circuit from the remote actuating contact to the interposing relay coil. The minimum pickup voltage for the interposing relay must be compatible with the minimum control voltage specified in ANSI/IEEE standards for the switchgear. For dc tripping circuits, the control voltage range in ANSI/IEEE C37.06 is 56 percent to 112 percent of the rated voltage. For example, the range for 125 Vdc circuits is 70 to 140 Vdc. In contrast, the control voltage range given in ANSI/IEEE C37.90 for protective relays is 80 percent to 112 percent of rated voltage, or 100 to 140 Vdc for our example. In this scheme, the circuit includes truck-operated cell (TOC) contacts responsive to the position of the circuit breaker in the cell. These contacts are used to make the local control switch close contact (CS/C) operative only in the TEST position. The local control switch trip contact (CS/T) is operative in both the TEST and CONNECTED position. The TOC contacts are used to make the remote control contacts (201T and 201C) operative only in the CONNECTED position. Most users prefer that remote control contacts be operative only in the CONNECTED position. User preferences are less pronounced regarding local control circuits, with some users desiring that local circuits be operable only in the TEST position, and others desiring that local control circuits be operable in both CONNECTED and TEST positions.
  • 3. The information provided in this document contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners. Siemens Industry, Inc. 7000 Siemens Road Wendell, NC 27591 Subject to change without prior notice. Order No.: E50001-F710-A331-X-4A00 All rights reserved. © 2012 Siemens Industry, Inc. For more information, contact: +1 (800) 347-6659 www.usa.siemens.com/techtopics Symbols 52/a Aux switch (open when CB open) 52/b Aux switch (closed when CB open) 52SRC Close coil 52T Trip coil CS/C Control switch (local) close contact CS/T Control switch (local) trip contact RL Red indicating lamp GL Green indicating lamp 201C Interposing relay, close 201T Interposing relay, trip TOC/a Truck operated cell switch, closed when CB in connected position TOC/b Truck operated cell switch, open when CB in connected position LS Limit switch (spring charged)