Siemens Power Academy TD
Machine Protection
SIPROTEC 7UM62
Exercises
Restricted © Siemens AG All rights reserved.
09-1_Page 2
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Single line diagram
7UM62.
-T1
50 MVA, YNd11
110 ±5·2.5% / 11 kV
uT(1) = 8 %
3 110 kV
side 1
iL1,2,3
uL1,2,3
G
3~
-G1
46.6 MVA
11kV ±7.5%
300/1A, 20VA
5P20, Rct=1.2Ω
3000/1A, 20VA
5P20, Rct=12Ω
300/1A, 20VA
5P20, Rct=1.2Ω
side 2
iL1,2,3
IEE2
UE
IEE1
Excit.
7XT71
TD1 (REF)
TD2 (REF)
TD3 (<Excit.)
Ucontr.
Umeas.
7XR6004
3PP1326
~
7XT34 7XT33
20Hz Gen.
3
kV
0.1
3
kV
0.1
3
kV
11
sensitive current input only!!
500V
3
kV/
11
Q7
Q8
3000/1A, 20VA
5P20, Rct=12Ω
400/5A 5/2
SEF (20Hz)
SEF (20Hz)
Restricted © Siemens AG All rights reserved.
09-1_Page 3
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Neutral transformer circuits *)
400/5A
1FS5
15VA
P1
RL
P2
1B1
1A4
1A3
1A1
7XT34
1B4 4A1
4A3
7XT33
20 Hz
Bandpass
20 Hz
Generator
S1
S2
7UM62.
R13 UE
R14
J8 IEE1
J7
max. 3A (20Hz)
Protection cubicle
.. mA
20Hz
500V
3
kV/
11
1A2
330Ω
660Ω
660Ω
Burden < 0.5Ω
*) for information only, not used for this exercises
Restricted © Siemens AG All rights reserved.
09-1_Page 4
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Required protection elements for the exercises
50/51 Over current I>
32R Reverse power
-- Decoupling (Threshold supervision)
87 Generator Differential Protection
59/67GN 90% Stator Earth Fault U0> (calculated)
46 Unbalanced Load (negative sequence
40 Under excitation
21 Impedance Protection
78 Out of Step (loss of synchronism) *
* Option
Restricted © Siemens AG All rights reserved.
09-1_Page 5
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Device configuration (partly)
for Decoupling
Option
Restricted © Siemens AG All rights reserved.
09-1_Page 6
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Power System Data 1 (1/4)
1)
1) Neutral transformer is high resistive
Restricted © Siemens AG All rights reserved.
09-1_Page 7
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Power System Data 1 (2/4)
Restricted © Siemens AG All rights reserved.
09-1_Page 8
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Power System Data 1 (3/4)
)
/ratio(U
U
U
U
U
Factor UE
0224
divider
NTsec
NTprim
Esec
VTprim


31.7
V/(5/2)
500
3
V/
11000
Factor UE
0224 

Refer to Setting Options for the UE Input and their Impact
on the Protection Functions (refer to slide No. 10)
Restricted © Siemens AG All rights reserved.
09-1_Page 9
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM1: Power System Data 1 (4/4)
Restricted © Siemens AG All rights reserved.
09-1_Page 10
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
Setting Options for the UE Input and their Impact
on the Protection Functions
Restricted © Siemens AG All rights reserved.
09-1_Page 11
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
Generator: electrical data (1/2)
Restricted © Siemens AG All rights reserved.
09-1_Page 12
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
Generator: electrical data (2/2)
Restricted © Siemens AG All rights reserved.
09-1_Page 13
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.0 Connection SIP4 7UM to CMC - Voltage
SIPROTEC 7UM622
CMC 256
Restricted © Siemens AG All rights reserved.
09-1_Page 14
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.0 Connection SIP4 7UM to CMC - Current
SIPROTEC 7UM622
CMC 256
Restricted © Siemens AG All rights reserved.
09-1_Page 15
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.0 Connection SIP4 7UM to CMC – Trip signal
SIPROTEC 7UM622
CMC 256
Trip signal
Restricted © Siemens AG All rights reserved.
09-1_Page 16
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.0 Connection binary inputs SIP4 7UM to CMC
SIPROTEC 7UM622
CMC 256
External signal
U aux dc = 110 V (Check MLFB)
Restricted © Siemens AG All rights reserved.
09-1_Page 17
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.1: Over current Protection I>
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 18
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.2: Reverse Power
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 19
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
E2.3: Decoupling, (Example with Threshold supervision) (1/3)
-dP (-50%)
<I2 (<10%)
I>> (3·IN, p.u.)
&
CFC
MV2<, 8503, 8504
MV4<, 8507, 8508
0113
07961
07963
01808
External Trip 1
04526
8602: t = 0.15s
S Q
R Q
0
T
It can be assumed that the Generator will run out of step in case a three-phase
short circuit close to the power station will last for (example) more than 150ms.
This situation can be described by the following AND logic.
If the fault is not cleared immediately the unit will be decoupled from the net after 150 ms.
Restricted © Siemens AG All rights reserved.
09-1_Page 20
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.3: Decoupling, (Example with Threshold supervision) (2/3)
Restricted © Siemens AG All rights reserved.
09-1_Page 21
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.3: Decoupling, (Example with Threshold supervision) (3/3)
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 22
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.4: Settings for Generator Differential Protection (1/2)
Tripping Characteristic 7UM6
2031
IDiff>>
2044A
BASE POINT 2
2021
IDiff>
2061A
I-ADD ON STAB
2042A
BASE POINT 1
2
0
4 8 10
6 12
0
2
1
4
3
6
5
Trip Block
2041A
SLOPE 1
2043A
SLOPE 2
Add-on
Stabilization
45°
InO
IRest
InO
IDiff
*)
*) Slope for Add-on Stabilization:
7UM6  Slope 1
Settings:
2021: 0.20 I/InO
2026A: 0.00 sec
2031: >(1/xd‘)·InO
≈ 5.50 I/InO
2036A: 0.00 sec
2041A: 0.25
2042A: 0.00 I/InO
2043A: 0.50
2044A: 2.50 I/InO
2061A: 3.00 I/InO
Duration of Add-on Stabilization
2062A: 15 Cycle
Crossblock Add-on Stabilization
2063A: 15 Cycle
Restricted © Siemens AG All rights reserved.
09-1_Page 23
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.4: Settings for Generator Differential Protection (2/2)
Restricted © Siemens AG All rights reserved.
09-1_Page 24
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.5: Settings for 90% Stator Earthfault (U0>, calculated) (1/2)
UL1
UL3
UL2
90%
L1
L2
L3
Settings (primary value):
5002: U0prim> = 100% - 90% = 10.0
%
5003: T = 0.30 sec
Fuse Failure Monitor (FFM) to be enabled
to block 90% SEF Element via CFC
Restricted © Siemens AG All rights reserved.
09-1_Page 25
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.5: Settings for 90% Stator Earthfault (U0>, calculated) (2/2)
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 26
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.6: Settings for unbalanced load (1/3)
Restricted © Siemens AG All rights reserved.
09-1_Page 27
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.6: Settings for unbalanced load (2/3)
Settings in primary values:
1702: I2prim> = I2perm prim / IN Machine = 8.0 %
1704: Kprim = (I2/IN)2·t = 20 s
1705: tCooldown = Kprim /(I2perm prim /IN Machine)2 = 20s/0.082 = 3125 s
1706: I2prim>> = 60.0%
1707: T I2>> = 3.00 sec
Conversion to secondary values:
1702: I2sec> = I2prim> · IN Machine/IN CT = 8.0% · 2446A/3000A = 6.5 %
1704: Ksec = Kprim · (IN Machine/IN CT)2 = 20s·(2446A/3000A)2 = 20s·0.664 = 13.30 s
1706: I2sec>> = I2prim>> · IN Machine/IN CT = 60.0% · 2446A/3000A ≈ 49 %
Restricted © Siemens AG All rights reserved.
09-1_Page 28
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.6: Settings for unbalanced load (3/3)
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 29
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.7: Settings for under excitation protection (1/4)
1
2
Generator capability diagram
(from Manufacturer)
Restricted © Siemens AG All rights reserved.
09-1_Page 30
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.7: Settings for under excitation protection (2/4)
Settings in primary values (using generator capability diagram)
3002: 1/xd1prim = 0.58
tan(1) = 0.7/0.2 = 3.5 , arctan(1) = 1.292
3003: 1 ≈ 74°
3005: 1/xd2prim = 0.44
3006: 2 = 90°
Conversion to secondary values:
CTprim
N
VTprim
N
NMACH
NMACH
dMach
dsec I
U
U
I
x
1
x
1



UNMACH = 11kV , UN VTprim = 11 kV
INMACH = 46600kVA/(√3·11kV) = 2446A
IN CTprim = 3000A
0.815
A
3000
V
11k
kV
11
A
2446
I
U
U
I
CTprim
N
VTprim
N
NMACH
NMACH





3002: 1/xd1sec = 0.58·0.815 ≈ 0.47
3005: 1/xd2sec = 0.44·0.815 ≈ 0.36
Restricted © Siemens AG All rights reserved.
09-1_Page 31
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.7: Settings for under excitation protection (3/4)
u
0
EXC
k
U
0.5
Exc
U
:
3013 

UEXC0 = 45V
ku (voltage divider) = 0.5 kΩ/ (0.5 kΩ+ 0.5 kΩ + 9 kΩ) = 20
3013 U Exc = 0.5·45 V /20 ≈ 1.13 V
generator
shaft
7XR6004 7UM62.
K13 +
TD1
K14
Excit.
K15 +
TD2
K16
20 kΩ
7XT71
27
25
19
21
15
17
A3
A11
A6
G
3~
20 kΩ
20 kΩ
B11
B18
B14
20 kΩ
control
meas.
Example:
LiYCY 4x1.5
Protection cubicle
3PP1326
500Ω
1
4 9 kΩ
2
500Ω
3
7UM62.
K17 +
TD3
K18
10µF
250V
1)
Restricted © Siemens AG All rights reserved.
09-1_Page 32
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.7: Settings for under excitation protection (4/4)
For this exercise 
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 33
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.8: Settings for impedance protection (1/4)
2*)
G
3~
Z< , 7UM6
X1 ≈ 0.70·X1 Transformer
T1,T1B
T2
X1  X1 Transformer
TEND
Z1
(R1,X1) Z2
(R2,X2)
Z1b
(R1b,X1b)
1*)
t
Z
1*) To be coordinated with net protection
2*) Setting can (must) be higher than the real Z up to the HV C.B.
BI. (activating Z1b)
Restricted © Siemens AG All rights reserved.
09-1_Page 34
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.8: Settings for impedance protection (2/4)
Im (Z)
Re (Z)
R1= Z1
X1=Z1
X2=Z2
X1b=Z1b
R2=Z2
R1b= Z1b
sec
3.00
T
:
here
protection
net
with
d
coordinate
be
to
T
:
3312
sec
0.50
T2
:
here
protection
net
with
d
coordinate
be
to
T2
:
3311
Ω
0.0
Z
:
here
protection
net
with
d
coordinate
be
to
Z
Z
S
U
100%
u
Z2
:
3310
T1
T1b
:
3309
2
k
:
here
k
S
U
100%
u
Z1b
:
3308
sec
0.10
T1
:
3307
70%
k
:
here
er
transform
into
reach
zone
Protection
k
S
U
100%
u
100%
k
Z1
:
3306
END
END
Net
Net
Net
Trf
N
2
Trf.LV
N
T
(prim)
x
x
Trf
N
2
Trf.LV
N
T
(prim)
r
r
Trf
N
2
Trf.LV
N
T
r
(prim)




















Restricted © Siemens AG All rights reserved.
09-1_Page 35
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.8: Settings for impedance protection (3/4)
sec
3.00
T
:
3312
sec
0.50
T2
:
3311
Ω
0.194
0Ω
MVA
50
kV
11
100%
8%
Z2
:
3310
0.10sec
T1b
:
3309
Ω
0.387
2
MVA
50
kV
11
100%
8%
Z1b
:
3308
sec
0.10
T1
:
3307
Ω
0.136
MVA
50
kV
11
100%
8%
100%
70%
Z1
:
3306
END
2
(prim)
2
(prim)
2
(prim)
















Conversion to secondary values:
Settings in primary values:
Ω
5.29
Ω
0.194
V
11000V/100
3000A/1A
Z2
k
k
Z2
:
3310
Ω
10.55
Ω
0.387
V
11000V/100
3000A/1A
Z1b
k
k
Z1b
:
3308
Ω
3.71
Ω
0.136
V
11000V/100
3000A/1A
Z1
k
k
Z1
:
3306
(prim)
VT
CT
(sec)
(prim)
VT
CT
(sec)
(prim)
VT
CT
(sec)















Restricted © Siemens AG All rights reserved.
09-1_Page 36
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.8: Settings for impedance protection (4/4)
Settings: primary values
Restricted © Siemens AG All rights reserved.
09-1_Page 37
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.9: Settings for out of step protection (1/3)




















90
P
:
3508
)
Z
(Z
0.289
Z
:
3504
Z
Z
:
3507
k
10Ω
Z
/U
U
/I
I
k
k
k
with
:
here
!
!
net
with the
d
coordinate
be
to
Z
5%)
8
k
:
(here
ormer
intoTransf
1
stic
Characteri
of
reach
k
S
100%
U
u
%
100
k
Z
:
3506
x
I
3
U
X
Z
:
3505
c(prim)
(prim)
b
a(prim)
c(prim)
d(prim)
sec
d(prim)
VTsn
VTpn
CTsn
CTpn
VT
CT
sec
d(prim)
r(OoS)
r(OoS)
Tr
N,
2
Tr(LV)
N,
T
r(OoS)
c(prim)
'
d
Gen
N,
Gen
N,
'
d
b(prim)

Za
Zb
Im (Z)
Re (Z)
Zd-Zc
Zc
Zd
φP
Char. 2
Char. 1
Restricted © Siemens AG All rights reserved.
09-1_Page 38
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.9: Settings for out of step protection (2/3)























90
P
:
3508
Ω
0.210
Ω)
0.165
Ω
(0.561
0.289
Z
:
3504
Ω
0.202
Ω
0.165
Ω
0.367
Z
-
Z
:
3507
Ω
0.367
27.27
Ω
10
Z
27.27
V
V/100
11000
A
A/1
3000
k
k
k
Ω
0.165
MVA
50
100%
kV
11
8%
100%
85%
Z
:
3506
Ω
0.561
0.216
2446A
3
11000V
Z
:
3505
a(prim)
c(prim)
d(prim)
d(prim)
VT
CT
sec
2
2
c(prim)
b(prim)

Settings in primary values:
Conversion to secondary values:
 
Ω
5.73
Ω
0.210
27.27
Z
k
Z
:
3504
Ω
5.51
Ω
202
.
0
27.27
Z
-
Z
k
Z
-
Z
:
3507
Ω
10
Z
Ω
4.50
Ω
0.165
27.27
Z
k
Z
:
3506
Ω
15.30
Ω
0.561
27.27
Z
k
Z
:
3505
above)
(from
27.27
k
a(prim)
sec
a(sec)
c(prim)
d(prim)
sec
c(sec)
d(sec)
d(sec)
c(prim)
sec
c(sec)
b(prim)
sec
b(sec)
sec






















Restricted © Siemens AG All rights reserved.
09-1_Page 39
Machine Protection 7UM62 Exercises
SIPROTEC 4 Generator protection Siemens Power Academy TD
EM2.9: Settings for out of step protection (3/3)
Settings: primary values

More Related Content

Similar to 09-1 Machine Prot. Exercises.ppt

04.ppt grd200 introduction 2020_july
04.ppt grd200 introduction 2020_july04.ppt grd200 introduction 2020_july
04.ppt grd200 introduction 2020_julyNgoc Tran
 
1SS412 PSpice Model (Free SPICE Model)
1SS412 PSpice Model (Free SPICE Model)1SS412 PSpice Model (Free SPICE Model)
1SS412 PSpice Model (Free SPICE Model)Tsuyoshi Horigome
 
1SS412 LTspice Model (Free SPICE Model)
1SS412 LTspice Model (Free SPICE Model)1SS412 LTspice Model (Free SPICE Model)
1SS412 LTspice Model (Free SPICE Model)Tsuyoshi Horigome
 
Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101Toàn Huỳnh
 
Original NPN Transistor DTC143ESATP DTC143 C143 TO-92 New
Original NPN Transistor DTC143ESATP DTC143 C143 TO-92 NewOriginal NPN Transistor DTC143ESATP DTC143 C143 TO-92 New
Original NPN Transistor DTC143ESATP DTC143 C143 TO-92 NewAUTHELECTRONIC
 
Checkout single phase induction motor catalogue and price list.
Checkout single phase induction motor catalogue and price list.Checkout single phase induction motor catalogue and price list.
Checkout single phase induction motor catalogue and price list.twinkleerai
 
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitOptimus Energy Philippines
 
CMH05A LTspice Model (Free SPICE Model)
CMH05A LTspice Model (Free SPICE Model)CMH05A LTspice Model (Free SPICE Model)
CMH05A LTspice Model (Free SPICE Model)Tsuyoshi Horigome
 
CMH05A PSpice Model (Free SPICE Model)
CMH05A PSpice Model (Free SPICE Model)CMH05A PSpice Model (Free SPICE Model)
CMH05A PSpice Model (Free SPICE Model)Tsuyoshi Horigome
 
CMH04 LTspice Model (Free SPICE Model)
CMH04 LTspice Model (Free SPICE Model)CMH04 LTspice Model (Free SPICE Model)
CMH04 LTspice Model (Free SPICE Model)Tsuyoshi Horigome
 
CMH04 PSpice Model (Free SPICE Model)
CMH04 PSpice Model (Free SPICE Model)CMH04 PSpice Model (Free SPICE Model)
CMH04 PSpice Model (Free SPICE Model)Tsuyoshi Horigome
 
Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...
Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...
Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...authelectroniccom
 
1SS397 Professional Model LTspice Model (Free SPICE Model)
1SS397 Professional Model LTspice Model (Free SPICE Model)1SS397 Professional Model LTspice Model (Free SPICE Model)
1SS397 Professional Model LTspice Model (Free SPICE Model)Tsuyoshi Horigome
 
1SS397 Professional Model PSpice Model (Free SPICE Model)
1SS397 Professional Model PSpice Model (Free SPICE Model)1SS397 Professional Model PSpice Model (Free SPICE Model)
1SS397 Professional Model PSpice Model (Free SPICE Model)Tsuyoshi Horigome
 
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1 INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1 MayankSunhare
 
Original PNP Transistor 2SA2098 SA2098 2098 TO-220 New Sanyo
Original PNP Transistor 2SA2098 SA2098 2098 TO-220 New SanyoOriginal PNP Transistor 2SA2098 SA2098 2098 TO-220 New Sanyo
Original PNP Transistor 2SA2098 SA2098 2098 TO-220 New SanyoAUTHELECTRONIC
 

Similar to 09-1 Machine Prot. Exercises.ppt (20)

04.ppt grd200 introduction 2020_july
04.ppt grd200 introduction 2020_july04.ppt grd200 introduction 2020_july
04.ppt grd200 introduction 2020_july
 
1SS412 PSpice Model (Free SPICE Model)
1SS412 PSpice Model (Free SPICE Model)1SS412 PSpice Model (Free SPICE Model)
1SS412 PSpice Model (Free SPICE Model)
 
1SS412 LTspice Model (Free SPICE Model)
1SS412 LTspice Model (Free SPICE Model)1SS412 LTspice Model (Free SPICE Model)
1SS412 LTspice Model (Free SPICE Model)
 
Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101Vlt hvac basic_quick_start_guide_fc101
Vlt hvac basic_quick_start_guide_fc101
 
Original NPN Transistor DTC143ESATP DTC143 C143 TO-92 New
Original NPN Transistor DTC143ESATP DTC143 C143 TO-92 NewOriginal NPN Transistor DTC143ESATP DTC143 C143 TO-92 New
Original NPN Transistor DTC143ESATP DTC143 C143 TO-92 New
 
Ddec pin dat
Ddec pin datDdec pin dat
Ddec pin dat
 
Checkout single phase induction motor catalogue and price list.
Checkout single phase induction motor catalogue and price list.Checkout single phase induction motor catalogue and price list.
Checkout single phase induction motor catalogue and price list.
 
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unitSolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
SolarEdge 82.8kW inverter with WiFi & SetApp - Primary unit
 
siprotec
siprotecsiprotec
siprotec
 
siprotec
siprotecsiprotec
siprotec
 
Bt138 datasheet
Bt138 datasheetBt138 datasheet
Bt138 datasheet
 
CMH05A LTspice Model (Free SPICE Model)
CMH05A LTspice Model (Free SPICE Model)CMH05A LTspice Model (Free SPICE Model)
CMH05A LTspice Model (Free SPICE Model)
 
CMH05A PSpice Model (Free SPICE Model)
CMH05A PSpice Model (Free SPICE Model)CMH05A PSpice Model (Free SPICE Model)
CMH05A PSpice Model (Free SPICE Model)
 
CMH04 LTspice Model (Free SPICE Model)
CMH04 LTspice Model (Free SPICE Model)CMH04 LTspice Model (Free SPICE Model)
CMH04 LTspice Model (Free SPICE Model)
 
CMH04 PSpice Model (Free SPICE Model)
CMH04 PSpice Model (Free SPICE Model)CMH04 PSpice Model (Free SPICE Model)
CMH04 PSpice Model (Free SPICE Model)
 
Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...
Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...
Original DARLING TRANSISTOR ARRAY IC ULQ2003A 2003A 2003 SOP-16 New Texas Ins...
 
1SS397 Professional Model LTspice Model (Free SPICE Model)
1SS397 Professional Model LTspice Model (Free SPICE Model)1SS397 Professional Model LTspice Model (Free SPICE Model)
1SS397 Professional Model LTspice Model (Free SPICE Model)
 
1SS397 Professional Model PSpice Model (Free SPICE Model)
1SS397 Professional Model PSpice Model (Free SPICE Model)1SS397 Professional Model PSpice Model (Free SPICE Model)
1SS397 Professional Model PSpice Model (Free SPICE Model)
 
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1 INTELLIGENT POWER MODULE Model No : PEC16DSMO1
INTELLIGENT POWER MODULE Model No : PEC16DSMO1
 
Original PNP Transistor 2SA2098 SA2098 2098 TO-220 New Sanyo
Original PNP Transistor 2SA2098 SA2098 2098 TO-220 New SanyoOriginal PNP Transistor 2SA2098 SA2098 2098 TO-220 New Sanyo
Original PNP Transistor 2SA2098 SA2098 2098 TO-220 New Sanyo
 

More from MAHMOUDMOHAMED431205

OC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptxOC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptxMAHMOUDMOHAMED431205
 
protection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptxprotection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptxMAHMOUDMOHAMED431205
 
cathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptxcathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptxMAHMOUDMOHAMED431205
 
plan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptxplan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptxMAHMOUDMOHAMED431205
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.pptMAHMOUDMOHAMED431205
 
08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.pptMAHMOUDMOHAMED431205
 

More from MAHMOUDMOHAMED431205 (19)

OC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptxOC Relay, types,constrcution,maintenance.pptx
OC Relay, types,constrcution,maintenance.pptx
 
protection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptxprotection functions.types.maintenance,alarms.pptx
protection functions.types.maintenance,alarms.pptx
 
cathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptxcathodic protection and maintenance requred 3.pptx
cathodic protection and maintenance requred 3.pptx
 
plan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptxplan for electrical technicianTraining .pptx
plan for electrical technicianTraining .pptx
 
Meduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptxMeduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptx
 
power Tr 2 course.ppt
power Tr 2 course.pptpower Tr 2 course.ppt
power Tr 2 course.ppt
 
power Tr 1 course.ppt
power Tr 1 course.pptpower Tr 1 course.ppt
power Tr 1 course.ppt
 
MOTOR PROTECTION.pptx
MOTOR PROTECTION.pptxMOTOR PROTECTION.pptx
MOTOR PROTECTION.pptx
 
Meduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptxMeduim Voltage Switchgear.pptx
Meduim Voltage Switchgear.pptx
 
Single Line Diagram.pptx
Single Line Diagram.pptxSingle Line Diagram.pptx
Single Line Diagram.pptx
 
CT and VT.pptx
CT and VT.pptxCT and VT.pptx
CT and VT.pptx
 
power cable 3.pptx
power cable 3.pptxpower cable 3.pptx
power cable 3.pptx
 
power cable 2.pptx
power cable 2.pptxpower cable 2.pptx
power cable 2.pptx
 
power cable1.ppt
power cable1.pptpower cable1.ppt
power cable1.ppt
 
MOTOR PROTECTION.pptx
MOTOR PROTECTION.pptxMOTOR PROTECTION.pptx
MOTOR PROTECTION.pptx
 
starting current of motor.pptx
starting current of motor.pptxstarting current of motor.pptx
starting current of motor.pptx
 
protection Training.pptx
protection Training.pptxprotection Training.pptx
protection Training.pptx
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt
 
08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt08_C_3_Basis Stator Earth Fault Protection.ppt
08_C_3_Basis Stator Earth Fault Protection.ppt
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 

09-1 Machine Prot. Exercises.ppt

  • 1. siemens.com/poweracademy Restricted © Siemens AG All rights reserved. Siemens Power Academy TD Machine Protection SIPROTEC 7UM62 Exercises
  • 2. Restricted © Siemens AG All rights reserved. 09-1_Page 2 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Single line diagram 7UM62. -T1 50 MVA, YNd11 110 ±5·2.5% / 11 kV uT(1) = 8 % 3 110 kV side 1 iL1,2,3 uL1,2,3 G 3~ -G1 46.6 MVA 11kV ±7.5% 300/1A, 20VA 5P20, Rct=1.2Ω 3000/1A, 20VA 5P20, Rct=12Ω 300/1A, 20VA 5P20, Rct=1.2Ω side 2 iL1,2,3 IEE2 UE IEE1 Excit. 7XT71 TD1 (REF) TD2 (REF) TD3 (<Excit.) Ucontr. Umeas. 7XR6004 3PP1326 ~ 7XT34 7XT33 20Hz Gen. 3 kV 0.1 3 kV 0.1 3 kV 11 sensitive current input only!! 500V 3 kV/ 11 Q7 Q8 3000/1A, 20VA 5P20, Rct=12Ω 400/5A 5/2 SEF (20Hz) SEF (20Hz)
  • 3. Restricted © Siemens AG All rights reserved. 09-1_Page 3 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Neutral transformer circuits *) 400/5A 1FS5 15VA P1 RL P2 1B1 1A4 1A3 1A1 7XT34 1B4 4A1 4A3 7XT33 20 Hz Bandpass 20 Hz Generator S1 S2 7UM62. R13 UE R14 J8 IEE1 J7 max. 3A (20Hz) Protection cubicle .. mA 20Hz 500V 3 kV/ 11 1A2 330Ω 660Ω 660Ω Burden < 0.5Ω *) for information only, not used for this exercises
  • 4. Restricted © Siemens AG All rights reserved. 09-1_Page 4 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Required protection elements for the exercises 50/51 Over current I> 32R Reverse power -- Decoupling (Threshold supervision) 87 Generator Differential Protection 59/67GN 90% Stator Earth Fault U0> (calculated) 46 Unbalanced Load (negative sequence 40 Under excitation 21 Impedance Protection 78 Out of Step (loss of synchronism) * * Option
  • 5. Restricted © Siemens AG All rights reserved. 09-1_Page 5 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Device configuration (partly) for Decoupling Option
  • 6. Restricted © Siemens AG All rights reserved. 09-1_Page 6 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Power System Data 1 (1/4) 1) 1) Neutral transformer is high resistive
  • 7. Restricted © Siemens AG All rights reserved. 09-1_Page 7 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Power System Data 1 (2/4)
  • 8. Restricted © Siemens AG All rights reserved. 09-1_Page 8 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Power System Data 1 (3/4) ) /ratio(U U U U U Factor UE 0224 divider NTsec NTprim Esec VTprim   31.7 V/(5/2) 500 3 V/ 11000 Factor UE 0224   Refer to Setting Options for the UE Input and their Impact on the Protection Functions (refer to slide No. 10)
  • 9. Restricted © Siemens AG All rights reserved. 09-1_Page 9 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM1: Power System Data 1 (4/4)
  • 10. Restricted © Siemens AG All rights reserved. 09-1_Page 10 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD Setting Options for the UE Input and their Impact on the Protection Functions
  • 11. Restricted © Siemens AG All rights reserved. 09-1_Page 11 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD Generator: electrical data (1/2)
  • 12. Restricted © Siemens AG All rights reserved. 09-1_Page 12 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD Generator: electrical data (2/2)
  • 13. Restricted © Siemens AG All rights reserved. 09-1_Page 13 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.0 Connection SIP4 7UM to CMC - Voltage SIPROTEC 7UM622 CMC 256
  • 14. Restricted © Siemens AG All rights reserved. 09-1_Page 14 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.0 Connection SIP4 7UM to CMC - Current SIPROTEC 7UM622 CMC 256
  • 15. Restricted © Siemens AG All rights reserved. 09-1_Page 15 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.0 Connection SIP4 7UM to CMC – Trip signal SIPROTEC 7UM622 CMC 256 Trip signal
  • 16. Restricted © Siemens AG All rights reserved. 09-1_Page 16 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.0 Connection binary inputs SIP4 7UM to CMC SIPROTEC 7UM622 CMC 256 External signal U aux dc = 110 V (Check MLFB)
  • 17. Restricted © Siemens AG All rights reserved. 09-1_Page 17 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.1: Over current Protection I> Settings: primary values
  • 18. Restricted © Siemens AG All rights reserved. 09-1_Page 18 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.2: Reverse Power Settings: primary values
  • 19. Restricted © Siemens AG All rights reserved. 09-1_Page 19 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD E2.3: Decoupling, (Example with Threshold supervision) (1/3) -dP (-50%) <I2 (<10%) I>> (3·IN, p.u.) & CFC MV2<, 8503, 8504 MV4<, 8507, 8508 0113 07961 07963 01808 External Trip 1 04526 8602: t = 0.15s S Q R Q 0 T It can be assumed that the Generator will run out of step in case a three-phase short circuit close to the power station will last for (example) more than 150ms. This situation can be described by the following AND logic. If the fault is not cleared immediately the unit will be decoupled from the net after 150 ms.
  • 20. Restricted © Siemens AG All rights reserved. 09-1_Page 20 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.3: Decoupling, (Example with Threshold supervision) (2/3)
  • 21. Restricted © Siemens AG All rights reserved. 09-1_Page 21 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.3: Decoupling, (Example with Threshold supervision) (3/3) Settings: primary values
  • 22. Restricted © Siemens AG All rights reserved. 09-1_Page 22 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.4: Settings for Generator Differential Protection (1/2) Tripping Characteristic 7UM6 2031 IDiff>> 2044A BASE POINT 2 2021 IDiff> 2061A I-ADD ON STAB 2042A BASE POINT 1 2 0 4 8 10 6 12 0 2 1 4 3 6 5 Trip Block 2041A SLOPE 1 2043A SLOPE 2 Add-on Stabilization 45° InO IRest InO IDiff *) *) Slope for Add-on Stabilization: 7UM6  Slope 1 Settings: 2021: 0.20 I/InO 2026A: 0.00 sec 2031: >(1/xd‘)·InO ≈ 5.50 I/InO 2036A: 0.00 sec 2041A: 0.25 2042A: 0.00 I/InO 2043A: 0.50 2044A: 2.50 I/InO 2061A: 3.00 I/InO Duration of Add-on Stabilization 2062A: 15 Cycle Crossblock Add-on Stabilization 2063A: 15 Cycle
  • 23. Restricted © Siemens AG All rights reserved. 09-1_Page 23 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.4: Settings for Generator Differential Protection (2/2)
  • 24. Restricted © Siemens AG All rights reserved. 09-1_Page 24 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.5: Settings for 90% Stator Earthfault (U0>, calculated) (1/2) UL1 UL3 UL2 90% L1 L2 L3 Settings (primary value): 5002: U0prim> = 100% - 90% = 10.0 % 5003: T = 0.30 sec Fuse Failure Monitor (FFM) to be enabled to block 90% SEF Element via CFC
  • 25. Restricted © Siemens AG All rights reserved. 09-1_Page 25 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.5: Settings for 90% Stator Earthfault (U0>, calculated) (2/2) Settings: primary values
  • 26. Restricted © Siemens AG All rights reserved. 09-1_Page 26 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.6: Settings for unbalanced load (1/3)
  • 27. Restricted © Siemens AG All rights reserved. 09-1_Page 27 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.6: Settings for unbalanced load (2/3) Settings in primary values: 1702: I2prim> = I2perm prim / IN Machine = 8.0 % 1704: Kprim = (I2/IN)2·t = 20 s 1705: tCooldown = Kprim /(I2perm prim /IN Machine)2 = 20s/0.082 = 3125 s 1706: I2prim>> = 60.0% 1707: T I2>> = 3.00 sec Conversion to secondary values: 1702: I2sec> = I2prim> · IN Machine/IN CT = 8.0% · 2446A/3000A = 6.5 % 1704: Ksec = Kprim · (IN Machine/IN CT)2 = 20s·(2446A/3000A)2 = 20s·0.664 = 13.30 s 1706: I2sec>> = I2prim>> · IN Machine/IN CT = 60.0% · 2446A/3000A ≈ 49 %
  • 28. Restricted © Siemens AG All rights reserved. 09-1_Page 28 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.6: Settings for unbalanced load (3/3) Settings: primary values
  • 29. Restricted © Siemens AG All rights reserved. 09-1_Page 29 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.7: Settings for under excitation protection (1/4) 1 2 Generator capability diagram (from Manufacturer)
  • 30. Restricted © Siemens AG All rights reserved. 09-1_Page 30 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.7: Settings for under excitation protection (2/4) Settings in primary values (using generator capability diagram) 3002: 1/xd1prim = 0.58 tan(1) = 0.7/0.2 = 3.5 , arctan(1) = 1.292 3003: 1 ≈ 74° 3005: 1/xd2prim = 0.44 3006: 2 = 90° Conversion to secondary values: CTprim N VTprim N NMACH NMACH dMach dsec I U U I x 1 x 1    UNMACH = 11kV , UN VTprim = 11 kV INMACH = 46600kVA/(√3·11kV) = 2446A IN CTprim = 3000A 0.815 A 3000 V 11k kV 11 A 2446 I U U I CTprim N VTprim N NMACH NMACH      3002: 1/xd1sec = 0.58·0.815 ≈ 0.47 3005: 1/xd2sec = 0.44·0.815 ≈ 0.36
  • 31. Restricted © Siemens AG All rights reserved. 09-1_Page 31 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.7: Settings for under excitation protection (3/4) u 0 EXC k U 0.5 Exc U : 3013   UEXC0 = 45V ku (voltage divider) = 0.5 kΩ/ (0.5 kΩ+ 0.5 kΩ + 9 kΩ) = 20 3013 U Exc = 0.5·45 V /20 ≈ 1.13 V generator shaft 7XR6004 7UM62. K13 + TD1 K14 Excit. K15 + TD2 K16 20 kΩ 7XT71 27 25 19 21 15 17 A3 A11 A6 G 3~ 20 kΩ 20 kΩ B11 B18 B14 20 kΩ control meas. Example: LiYCY 4x1.5 Protection cubicle 3PP1326 500Ω 1 4 9 kΩ 2 500Ω 3 7UM62. K17 + TD3 K18 10µF 250V 1)
  • 32. Restricted © Siemens AG All rights reserved. 09-1_Page 32 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.7: Settings for under excitation protection (4/4) For this exercise  Settings: primary values
  • 33. Restricted © Siemens AG All rights reserved. 09-1_Page 33 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.8: Settings for impedance protection (1/4) 2*) G 3~ Z< , 7UM6 X1 ≈ 0.70·X1 Transformer T1,T1B T2 X1  X1 Transformer TEND Z1 (R1,X1) Z2 (R2,X2) Z1b (R1b,X1b) 1*) t Z 1*) To be coordinated with net protection 2*) Setting can (must) be higher than the real Z up to the HV C.B. BI. (activating Z1b)
  • 34. Restricted © Siemens AG All rights reserved. 09-1_Page 34 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.8: Settings for impedance protection (2/4) Im (Z) Re (Z) R1= Z1 X1=Z1 X2=Z2 X1b=Z1b R2=Z2 R1b= Z1b sec 3.00 T : here protection net with d coordinate be to T : 3312 sec 0.50 T2 : here protection net with d coordinate be to T2 : 3311 Ω 0.0 Z : here protection net with d coordinate be to Z Z S U 100% u Z2 : 3310 T1 T1b : 3309 2 k : here k S U 100% u Z1b : 3308 sec 0.10 T1 : 3307 70% k : here er transform into reach zone Protection k S U 100% u 100% k Z1 : 3306 END END Net Net Net Trf N 2 Trf.LV N T (prim) x x Trf N 2 Trf.LV N T (prim) r r Trf N 2 Trf.LV N T r (prim)                    
  • 35. Restricted © Siemens AG All rights reserved. 09-1_Page 35 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.8: Settings for impedance protection (3/4) sec 3.00 T : 3312 sec 0.50 T2 : 3311 Ω 0.194 0Ω MVA 50 kV 11 100% 8% Z2 : 3310 0.10sec T1b : 3309 Ω 0.387 2 MVA 50 kV 11 100% 8% Z1b : 3308 sec 0.10 T1 : 3307 Ω 0.136 MVA 50 kV 11 100% 8% 100% 70% Z1 : 3306 END 2 (prim) 2 (prim) 2 (prim)                 Conversion to secondary values: Settings in primary values: Ω 5.29 Ω 0.194 V 11000V/100 3000A/1A Z2 k k Z2 : 3310 Ω 10.55 Ω 0.387 V 11000V/100 3000A/1A Z1b k k Z1b : 3308 Ω 3.71 Ω 0.136 V 11000V/100 3000A/1A Z1 k k Z1 : 3306 (prim) VT CT (sec) (prim) VT CT (sec) (prim) VT CT (sec)               
  • 36. Restricted © Siemens AG All rights reserved. 09-1_Page 36 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.8: Settings for impedance protection (4/4) Settings: primary values
  • 37. Restricted © Siemens AG All rights reserved. 09-1_Page 37 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.9: Settings for out of step protection (1/3)                     90 P : 3508 ) Z (Z 0.289 Z : 3504 Z Z : 3507 k 10Ω Z /U U /I I k k k with : here ! ! net with the d coordinate be to Z 5%) 8 k : (here ormer intoTransf 1 stic Characteri of reach k S 100% U u % 100 k Z : 3506 x I 3 U X Z : 3505 c(prim) (prim) b a(prim) c(prim) d(prim) sec d(prim) VTsn VTpn CTsn CTpn VT CT sec d(prim) r(OoS) r(OoS) Tr N, 2 Tr(LV) N, T r(OoS) c(prim) ' d Gen N, Gen N, ' d b(prim)  Za Zb Im (Z) Re (Z) Zd-Zc Zc Zd φP Char. 2 Char. 1
  • 38. Restricted © Siemens AG All rights reserved. 09-1_Page 38 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.9: Settings for out of step protection (2/3)                        90 P : 3508 Ω 0.210 Ω) 0.165 Ω (0.561 0.289 Z : 3504 Ω 0.202 Ω 0.165 Ω 0.367 Z - Z : 3507 Ω 0.367 27.27 Ω 10 Z 27.27 V V/100 11000 A A/1 3000 k k k Ω 0.165 MVA 50 100% kV 11 8% 100% 85% Z : 3506 Ω 0.561 0.216 2446A 3 11000V Z : 3505 a(prim) c(prim) d(prim) d(prim) VT CT sec 2 2 c(prim) b(prim)  Settings in primary values: Conversion to secondary values:   Ω 5.73 Ω 0.210 27.27 Z k Z : 3504 Ω 5.51 Ω 202 . 0 27.27 Z - Z k Z - Z : 3507 Ω 10 Z Ω 4.50 Ω 0.165 27.27 Z k Z : 3506 Ω 15.30 Ω 0.561 27.27 Z k Z : 3505 above) (from 27.27 k a(prim) sec a(sec) c(prim) d(prim) sec c(sec) d(sec) d(sec) c(prim) sec c(sec) b(prim) sec b(sec) sec                      
  • 39. Restricted © Siemens AG All rights reserved. 09-1_Page 39 Machine Protection 7UM62 Exercises SIPROTEC 4 Generator protection Siemens Power Academy TD EM2.9: Settings for out of step protection (3/3) Settings: primary values