User's
Manual VoltageProtectionRelay
User's
Manual
Features
• Low-set undervoltage stage with definite time or inverse time
• High-set undervoltage stage with definite time
• Low-set overvoltage stage with definite time or inverse time
• High-set overvoltage stage with definite time
• Negative sequence overvoltage protection
• Neutral displacement/ residual overvoltage protection
• Multi-function isolated digital input
• Fault data and event code recording
• Five programmable voltage-free output contacts
• Isolated RS485 Modbus-RTU communication
Table of Contents Page
1
For continuous product development, we reserve the right to supply
equipment which may vary from that described in this manual.
1. Introduction
2. Description of Operation
3. Display
4. Key Button Input
5. Programming
6. Soft Switches
7. Connection Diagram & Terminal Connection
8. Case Dimension
9. Technical Data
10. Test and Standards
11. Appendix A
12. Appendix B
13. Appendix C
2
3
12
22
24
27
52
58
59
61
62
63
64
2
Features
1. Introduction
The MU2300 voltage protection relay is a microprocessor based
numerical relay intended for the voltage protection in electrical
distribution network. It can also be used for generators, motors and
transformer protection.
A fully digital user interface with bright seven-segment display and
indicators provides a very user friendly access to all the measurements,
user parameters and records.
MU2300 uses a digital filter to extract the fundamental voltage
waveforms for the three phases, phase-to-phase voltage or phase-to-
neutral voltage, for the operation of the protection elements. Such
protection elements are undervoltage low-set and high-set; overvoltage
low-set and high-set; negative sequence overvoltage low-set; residual
overvoltage low-set.
Besides being operated from the front panel of MU2300, this relay can
also be accessed when connected to a networked system through its
isolated RS485 Modbus-RTU communication interface.
• Low-set undervoltage stage with definite-time or inverse time
• High-set undervoltage stage with definite-time
• Low-set overvoltage stage with definite-time or inverse time
• High-set overvoltage stage with definite-time
• Negative sequence overvoltage protection
• Neutral displacement/ residual overvoltage protection
• Multi-function isolated digital input
• Fault data and event code recording
• Five programmable voltage-free output contacts
• Isolated RS485 Modbus-RTU communication
3
2. Description of Operation
MU2300 is equipped with 3 accurate and independent voltage inputs
connected to the voltage transformers of the object to be protected. It
continuously monitors these voltage inputs’ fundamental frequency
components for the occurrence of faults. On detection of a fault, the relay
will start and then operated the trip output which is connected to the
circuit breaker or indicator. The phase-to-phase voltage, phase-to-neutral
voltage, negative sequence voltage and the residual voltage, measured at
the moment of tripping, will be recorded in the memories of the relay.
The relay has four different voltage transformer (VT) configurations.
Depending on the configuration chosen, the input voltages can be phase-
to-phase voltages or phase-to-neutral voltages. If the inputs are phase-to-
phase voltages, the protection setting is based on the phase-to-phase
voltages. However, if the configuration chosen is for phase-to-neutral
input voltages, the protection setting will then be based on the phase-to-
phase voltages and the derived phase-to-phase voltages are for
measurements only.
2.1 Undervoltage Elements (27)
The MU2300 has two stages for undervoltage protection, namely the low-
set undervoltage element and high-set undervoltage element.
When the voltage values fall below the set low-set undervoltage value,
the low-set undervoltage element will start and deliver a start signal to the
contact output (if assigned) and the front panel START indicator. After a
pre-set delay time, determined by the user’s selection between definite-
time and inverse time characteristic, the undervoltage element delivers a
trip signal to the contact output (if assigned) and the front panel TRIP
indicator. Similarly, the high-set undervoltage element will start and then
deliver a trip signal to the contact output (if assigned) and the front panel
indicators if the voltage falls below the set high-set undervoltage value
for duration longer than the high-set definite time.
The low-set and high-set elements can be selectively blocked by the
digital input if the appropriate switch setting in Soft Switch 9A and Soft
Switch 9B are set. The high-set stage can also be set out of operation by
Soft Switch 8.
4
When the relay is first powered on without any input voltages connected
to the VTs, the undervoltage elements are temporary disabled. The
undervoltage elements will be activated once any of the input voltages
exceeded 10V. To ensure that the undervoltage protection elements will
not trip the relay when the voltage inputs are energised, the delay time
should be set sufficiently long or the undervoltage elements are set to be
temporary blocked by the digital input.
2.1.1 Inverse time delay characteristic
The inverse characteristic for undervoltage U<, is defined by the
following equation:
TMS
t =
1 - V
Vs
where:
t = operating time in seconds
TMS = time multiplier setting
V = applied input voltage
Vs = relay setting voltage
NOTE: this equation is valid for Vs > V
5
1
10
100
1000
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
TMS=1
TMS=5
TMS=3
TMS=10
TMS=8
Applied voltage/relay setting voltage
Operatingtime(sec)
Undervoltage Characteristic
Figure 1: Inverse time curves for the undervoltage element “U<”
6
2.2 Overvoltage Elements (59)
The MU2300 has two stages for overvoltage protection, namely the low-
set overvoltage element and high-set overvoltage element.
When the voltage values rise above the set low-set overvoltage value, the
low-set overvoltage element will start and deliver a start signal to the
contact output (if assigned) and the front panel START indicator. After a
pre-set delay time, determined by the user’s selection between definite-
time and inverse time characteristic, the overvoltage element delivers a
trip signal to the contact output (if assigned) and the front panel TRIP
indicator. Similarly, the high-set overvoltage element will start and then
deliver a trip signal to the contact output (if assigned) and the front panel
indicators if the voltage values rise above the set high-set overvoltage
value for duration longer than the high-set definite time.
The low-set and high-set elements can be selectively blocked by the
digital input if the appropriate switch settings in Soft Switch 9A and Soft
Switch 9B are set. The high-set stage can also be set out of operation by
Soft Switch 8.
2.2.1 Inverse time delay characteristic
The inverse characteristic for overvoltage U>, is defined by the following
equation:
t = TMS
V - 1
Vs
where:
t = operating time in seconds
TMS = time multiplier setting
V = applied input voltage
Vs = relay setting voltage
NOTE: this equation is valid for V > Vs
|
7
0.01
0.1
1
10
100
1000
0 2 4 6 8 10 12 14 16 18 20
Applied voltage input/relay setting voltage
Operatingtime(sec)
TMS=1
TMS=8
TMS=10
TMS=5
TMS=3
Overvoltage Characteristic
Figure 2: Inverse time curves for the overvoltage element “U>”
8
2.3 Negative Sequence Overvoltage Element (47)
For negative sequence overvoltage on MU2300, there is only low-set
element. The negative sequence voltage is derived from the three phase-
to-neutral voltages measured from the voltage inputs if the relay is
configured in Soft Switch A to measure the phase-to-neutral voltages. If
the relay is configured in Soft Switch A to measure the phase-to-phase
voltages, the negative sequence voltage is derived from the phase-to-
phase voltage.
When the negative sequence voltage value rises above the set low-set
negative sequence value, the negative sequence low-set overvoltage
element will start and deliver a start signal to the contact output (if
assigned) and the front panel START indicator. After a pre-set delay time
determined by the user’s selection between definite-time and inverse time
the negative sequence overvoltage element delivers a trip signal to the
contact output (if assigned) and the front panel TRIP indicator.
The low-set element can be selectively blocked by the digital input if the
appropriate switch settings in Soft Switch 9A and Soft Switch 9B are set
accordingly.
2.3.1 Inverse time delay characteristic
The inverse characteristic for negative sequence overvoltage U2>,is
defined by the following equation:
TMS
t =
V - 1
Vs
where:
t = operating time in seconds
TMS = time multiplier setting
V = calculated negative sequence voltage
Vs = relay setting voltage
NOTE: this equation is valid for V > Vs
|
9
0.01
0.1
1
10
100
1000
0 2 4 6 8 10 12 14 16 18 20
Operatingtime(sec)
TMS=1
TMS=8
TMS=10
TMS=5
TMS=3
Figure 3: Inverse time curves for the overvoltage element “U2>”
Negative sequence overvoltage characteristic
Derived negative sequence overvoltage/relay setting voltage
10
2.4.1 Inverse time delay characteristic
The inverse characteristic for residual overvoltage U0>, is defined by the
following equation:
TMS
t =
V - 1
Vs
where:
t = operating time in seconds
TMS = time multiplier setting
V = applied or derived residual input voltage
Vs = relay setting voltage
NOTE: this equation is valid for V > Vs
2.4 Neutral displacement /Residual Overvoltage (59N)
For residual overvoltage on MU2300, there is only low-set element. The
residual voltage is either derived from the three phase-to-neutral voltage
measurements of the voltage inputs or is measured directly from the
residual voltage transformer depending on the setting of Soft Switch A. If
the relay is configured in Soft Switch A to measures the phase-to-phase
voltages, the residual voltage must be measured by the residual voltage
transformer.
When the residual overvoltage value rises above the set low-set residual
overvoltage value, the low-set residual overvoltage element will start and
deliver a start signal to the contact output (if assigned) and the front panel
START indicator. After a pre-set delay time, determined by the user’s
selection between definite-time and inverse time characteristic, the
residual overvoltage element delivers a trip signal to the contact output (if
assigned) and the front panel TRIP indicator.
The low-set element can be selectively blocked by the digital input if the
appropriate switch settings in Soft Switch 9A and Soft Switch 9B are set
accordingly.
11
0.01
0.1
1
10
100
1000
0 2 4 6 8 10 12 14 16 18 20
Operatingtime(sec)
TMS=1
TMS=8
TMS=10
TMS=5
TMS=3
Figure 4: Inverse time curves for the overvoltage element “U0>”
Residual overvoltage characteristic
Applied or derived residual voltage input/relay setting voltage
12
3. Display
a)
b)
c)
3.1 Indicators
This is the power indicator. It shows the presence of auxiliary power
supply to the MU2300 relay.
This indicator lights up when any or all of the protection elements,
namely, undervoltage protection, overvoltage protection, negative
sequence overvoltage and residual overvoltage elements are started
(pick-up).
This indicator lights up when any or all of the protection elements,
namely, undervoltage protection, overvoltage protection, negative
sequence overvoltage and residual overvoltage elements are started
(pick-up) due to fault conditions and subsequently tripped due to the
sustained fault condition.
13
e)
Number Value
Number Value
U12/ U1P
d) Digit display
The two formats of the display are as shown below:
The “Number” is for displaying the item selected and the “Value” is
to show the corresponding parameter associated with the item
“Number” selected.
When this indicator is lighted, the digit display is showing the value
of either U1 phase-to-neutral voltage or U12 phase-to-phase voltage.
When the phase-to-neutral voltage is shown, the “Number” field of
the digit display shows an alphabet “P” whereas when phase-to-
phase voltage is shown, the “Number” field displays an alphabet
“L”.
This indicator blinks when the undervoltage or overvoltage
protection element corresponding to U1 or U12 pick-up or tripped.
14
f)
g)
h)
i)
j)
k)
U23/U2P
U31/U3P
U0
U2
Record
Event
Similar to item e) above, this indicator shows the U2 phase-to-
neutral voltage or U23 phase-to-phase voltage.
Similar to item e) above, this indicator shows the U3 phase-to-
neutral voltage or U31 phase-to-phase voltage.
When this indicator is lighted, the digit display shows the residual
voltage. It blinks when the corresponding protection element pick-
up or trip.
When this indicator is lighted, the digit display shows the negative
sequence voltage. It blinks when the corresponding protection
element pick-up or trip.
This indicator will light up simultaneously with either U12/U1P,
U23/U2P, U31/U3P, U0, or U2. When lighted, the digit display is
showing the previously recorded voltages at then moment when
MU2300 trips. There are nine records available and each can be
viewed at by pressing the DOWN key. Record number 1 is the latest
record.
When this indicator is lighted, the digit display is showing the
recorded event code. There are 60 numbers of events available and
15
l)
m)
n)
o)
U<
tU<
U<<
tU<<
all the recorded events will be cleared when the auxiliary power
supply to MU2300 is disconnected. The event code is in Appendix
C.
All event registered will be displayed one-by-one automatically if
the relay is left untouched in this mode of for about 20 seconds.
When this indicator is lighted, the digit display shows the low-set
undervoltage setting. The “Number” field of the digit display
indicates whether it is a Group A or Group B setting. The “Value”
field shows the setting voltage.
When this indicator is lighted, depending on the user setting on Soft
Switch 7, the digit display will either show the TMS or the definite
time delay for low-set undervoltage. The “Number” field of the digit
display shows whether it is a Group A or Group B setting.
When this indicator is lighted, the digit display shows the high-set
undervoltage setting. The “Number” field of the digit display
indicates whether it is a Group A or Group B setting. The “Value”
field shows the setting voltage.
When this indicator is lighted, the digit display shows the high-set
definite time delay for undervoltage. The “Number” field of the
digit display shows whether it is a Group A or Group B setting.
16
p)
q)
r)
U>
tU>
U>>
tU>>
U2>
s)
t)
When this indicator is lighted, the digit display shows the low-set
overvoltage setting. The “Number” field of the digit display
indicates whether it is a Group A or Group B setting. The “Value”
field shows the setting voltage.
When this indicator is lighted, depending on the user setting on Soft
Switch 7, the digit display will either show the TMS or the definite
time delay for low-set overvoltage. The “Number” field of the digit
display shows whether it is a Group A or Group B setting.
When this indicator is lighted, the digit display shows the high-set
overvoltage setting. The “Number” field of the digit display
indicates whether it is a Group A or Group B setting. The “Value”
field shows the setting voltage.
When this indicator is lighted, the digit display shows the high-set
definite time delay for overvoltage. The “Number” field of the digit
display shows whether it is a Group A or Group B setting.
When this indicator is lighted, the digit display shows the low-set
negative sequence overvoltage setting. The “Number” field of the
digit display indicates whether it is a Group A or Group B setting.
The “Value” field shows the setting for the negative sequence
overvoltage.
17
tU2>
U0>
tU0>
INPUT
u)
v)
w)
x)
When this indicator is lighted, depending on the user setting on Soft
Switch 7, the digit display will either show the TMS multiplier or
the definite time delay for low-set negative sequence overvoltage.
The “Number” field of the digit display shows whether it is a Group
A or Group B setting.
When this indicator is lighted, the digit display shows the low-set
residual overvoltage setting. The “Number” field of the digit display
indicates whether it is a Group A or Group B setting. The “Value”
field shows the setting for the residual overvoltage.
When this indicator is lighted, depending on the user setting on Soft
Switch 7, the digit display will either show the TMS or the definite
time delay for low-set residual overvoltage. The “Number” field of
the digit display shows whether it is a Group A or Group B setting.
This indicator reflects the status of the external digital input
regardless of the soft switches setting. It is a direct mimic of the
status of the input. When voltage is applied to the digital input, the
indicator will turn on.
18
3.2 Normal Status Display
Under normal operating condition where non of the protection elements
have operated and the key are not pressed, all the indicators will be
switched off except the following:
a)
The AUX indicator shows that there is power supply to the relay.
b)
AUX
Blinking
The decimal point on the left-most digit blinks to indicate that the
relay is functioning normally.
19
3.3 Start Status Display
The Start indicator lights up when any of the protection elements pick-up
(started). Other indicators also lighted simultaneously to show which
protection elements have started.
START
U12/U1P
U23/U2P
U31/U3P
a) The Start indicator light up to indicate that the relay pick up.
b) One or more of the following indicators blink to indicate the sources
of the pick-up.
U0
U2
U<
U<<
U>
U>>
U2>
U0>
c) One or more of the following indicators blink to indicate that the
protection elements that have pick-up.
20
TRIP
U12/U1P
U23/U2P
3.4 Trip Status Display
The Trip indicator lights up when any of the protection elements trip.
Other indicators also lighted simultaneously to show which protection
elements have tripped.
a) The Trip indicator light up to indicates that the relay has tripped. It
stays steady when the condition for tripping has not been removed.
Otherwise, the indicator blinks.
b) One of the following indicators blink to indicate the sources of the
pick-up.
U31/U3P
U0
U2
U<
U<<
U>
U>>
U2>
U0>
c) One of the following indicators blink to indicate that the protection
elements that have pick-up.
21
Number Value
d) The digit display shows the value of the trip voltage at the moment
of tripping. The “Number” field of the digit display may indicate
an alphabet “L” or “P” which denote phase-to-phase voltage or
phase-to-neutral voltage respectively.
When the voltage value is not available, the display will show “-E-“
sign on the “Value” field.
22
START
U12
U1P
U23
U2P
U31
U3P
U0
U2
U12/U1P Record
U23/U2P Record
U31/U3P Record
U0 Record U<
tU<
U<<
tU<<
U>
tU>
U>>
tU>>
U2>
tU2>
U0>
U2 Record Event
tU0>
Other U12/U1P Record
Other U23/U2P Record
Other U31/U3P Record
Other U0 Record
Other U2 Record
*
*
*
*
*
* Use DOWN key
4. Key Button Input
a) RESET/STEP key
This key has two functions:
I. To reset the relay when the relay is tripped.
II. To select the items to be view at such as all the input voltages
and setting parameters.
The sequence of selection when the RESET/STEP key is pressed is
as shown below. Pressing the UP key will reverse the sequence.
23
b) The PROGRAM key
Item to be programmed is first selected by the RESET/STEP key.
Then pressing the PROGRAM key set the relay into programming
mode for the selected item. Value of the selected item can then be
changed by the UP or DOWN key. Pressing the PROGRAM key
again while in the programming mode will cause the relay to exit
from the programming mode with the new value saved into the non-
volatile memory.
The indicator adjacent to the PROGRAM key will light up when in
programming mode.
c) The UP and DOWN keys
These keys are for changing the value of the selected item while in
programming mode. Under non-programming mode, the UP key is
used as the reverse STEP key and the DOWN key is used for
changing the record number while in the recorded data retrieval
mode.
d) The SWITCH key
Press this key to step through all the soft switches.
24
5. Programming
5.1 To program the setting for U <, U <<, U >, U >>, U0 >,
and U2 >
Step 1
Select the required item by stepping through all the items using the
RESET/STEP key or the UP key. The corresponding light for the selected
item will be lighted.
Step 2
Press the PROGRAM key once. The indicator for the selected item will
blink and the indicator for PROGRAM key lights up to indicate that the
system is now in programming mode.
Step 3
Use the UP or DOWN key to select the desire value. Hold down the key
until the desired value appears.
25
Step 4
To save the changed value, press the PROGRAM key again. The
indicator for the PROGRAM key will turn off and the blinking indicator
for the selected item stop blinking.
To abort without saving the selected setting, press the RESET/STEP key.
Programming is prohibited when the relay is started or tripped.
26
5.2 To program the soft switches
Step1
Press the SWITCH key until the desired switch number appears on the
display.
Step 2
Press the PROGRAM key to enter into programming mode. The switch
number on the “Number” field of the digit display blinks to indicate that
the system is now in soft switch programming mode. The indicators for
the PROGRAM and the SWITCH keys also light up.
Step 3
Use the UP or DOWN key for changing the soft switch setting. Hold
down the key until the desired value appears.
Step 4
Press the PROGRAM key again to save the changed setting. The switch
number will stop blinking and the indicator for the PROGRAM key will
be switched off.
To abort without saving the change, press the SWITCH key or RESET/
STEP key. Programming is prohibited when the relay is started or tripped.
27
Switch
Number
Switch
Value
Digit2 Digit1
For contact output R1
6 Soft Switches
Soft switches are used to configure the features of the relay and the
functional characteristic of the relays outputs.
S1A.7 S1A.6 S1A.5 S1A.4 S1A.3 S1A.2 S1A.1 S1A.0
Default setting 1 0 1 0 1 0 1 0
Default setting –
hexadecimal
value
A A
User’s setting
User’s setting –
hexadecimal
value
Switch
Number
Switch
Value
Digit2 Digit1
or
For contact output R2
S2A.7 S2A.6 S2A.5 S1A.4 S2A.3 S1A.2 S2A.1 S2A.0
Default setting 0 1 0 1 0 1 0 1
Default setting –
hexadecimal value
5 5
User’s setting
User’s setting –
hexadecimal value
Soft Switch 1A to Soft Switch 5A
These switches are for configuring the output contacts R1 to R5 in
relation to low-set undervoltage U<, high-set undervoltage U<<, low-set
overvoltage U> and high-set overvoltage U>>.
28
For contact output R3
For contact output R4
For contact output R5
S3A.7 S3A.6 S3A.5 S3A.4 S3A.3 S3A.2 S3A.1 S3A.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal value
0 0
User’s setting
User’s setting –
hexadecimal value
S4A.7 S4A.6 S4A.5 S4A.4 S4A.3 S4A.2 S4A.1 S4A.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal value
0 0
User’s setting
User’s setting –
hexadecimal value
S5A.7 S5A.6 S5A.5 S5A.4 S5A.3 S5A.2 S5A.1 S5A.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal value
0 0
User’s setting
User’s setting –
hexadecimal value
SxA.0
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set undervoltage (U <) START signal.
1 = Rx is connected to low-set undervoltage START signal.
0 = Rx is disconnected to low-set undervoltage START signal
SxA.1
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set undervoltage (U <) TRIP signal.
1 = Rx is connected to low-set undervoltage TRIP signal.
0 = Rx is disconnected to low-set undervoltage TRIP signal.
29
SxA.2
This switch element is to connect/disconnect the corresponding contact
output Rx to high-set undervoltage (U <<) START signal.
1 = Rx is connected to high-set undervoltage START signal.
0 = Rx is disconnected to high-set undervoltage START signal.
SxA.3
This switch element is to connect/disconnect the corresponding contact
output Rx to high-set undervoltage (U <<) TRIP signal.
1 = Rx is connected to high-set undervoltage TRIP signal.
0 = Rx is disconnected to high-set undervoltage sTRIP signal.
SxA.4
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set overvoltage (U >) START signal.
1 = Rx is connected to low-set overvoltage START signal.
0 = Rx is disconnected to low-set overvoltage START signal.
SxA.5
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set overvoltage (U >) TRIP signal.
1 = Rx is connected to low-set overvoltage TRIP signal.
0 = Rx is disconnected to low-set overvoltage TRIP signal.
SxA.6
This switch element is to connect/disconnect the corresponding contact
output Rx to high-set overvoltage (U >>) START signal.
1 = Rx is connected to high-set overvoltage start signal.
0 = Rx is disconnected to high-set overvoltage start signal.
SxA.7
This switch element is to connect/disconnect the corresponding contact
output Rx to high-set overvoltage (U >>) TRIP signal.
1 = Rx is connected to high-set overvoltage trip signal.
0 = Rx is disconnected to low-set overvoltage trip signal.
30
Soft Switch 1B to Soft Switch 5B
These switches are for configuring the output contacts R1 to R5 in
relation to low-set negative sequence overvoltage U2> and low-set
residual overvoltage U0.
For contact output R1
For contact output R2
S1B.7 S1B.6 S1B.5 S1B.4 S1B.3 S1B.2 S1B.1 S1B.0
Default setting 0 0 1 0 0 0 1 0
Default setting –
hexadecimal
value
2 2
User’s setting
User’s setting –
hexadecimal
value
S2B.7 S2B.6 S2B.5 S2B.4 S2B.3 S2B.2 S2B.1 S2B.0
Default setting 0 0 0 1 0 0 0 1
Default setting –
hexadecimal
value
1 1
User’s setting
User’s setting –
hexadecimal
value
For contact output R3
S3B.7 S3B.6 S3B.5 S3B.4 S3B.3 S3B.2 S3B.1 S3B.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal
value
0 0
User’s setting
User’s setting –
hexadecimal
value
31
For contact output R4
For contact output R5
S4B.7 S4B.6 S4B.5 S4B.4 S4B.3 S4B.2 S4B.1 S4B.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal
value
0 0
User’s setting
User’s setting –
hexadecimal
value
S5B.7 S5B.6 S5B.5 S5B.4 S5B.3 S5B.2 S5B.1 S5B.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal
value
0 0
User’s setting
User’s setting –
hexadecimal
value
SxB.0
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set residual overvoltage (U0 >) START signal.
1 = Rx is connected to low-set residual overvoltage start signal
0 = Rx is disconnected to low-set residual overvoltage start
signal.
SxB.1
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set residual overvoltage (U0 >) TRIP signal.
1 = Rx is connected to low-set residual overvoltage
Rx is disconnected to low-set residual overvoltage
signal.
SxB.2
Not used.
SxB.3
Not used.
0 =
32
0 =
SxB.4
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set negative sequence overvoltage (U2 >) START signal.
1 = Rx is connected to low-set negative sequence overvoltage
start signal.
Rx is disconnected to low-set negative sequence
overvoltage start signal
SxB.5
This switch element is to connect/disconnect the corresponding contact
output Rx to low-set negative sequence overvoltage (U2 >) TRIP signal.
1 = Rx is connected to low-set negative sequence overvoltage
trip signal.
0 = Rx is disconnected to low-set negative sequence overvoltage
trip signal.
SxB.6
Not used.
SxB.7
Not used.
33
S6A.7 S6A.6 S6A.5 S6A.4 S6A.3 S6A.2 S6A.1 S6A.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal
value
0 0
User’s setting
User’s setting –
hexadecimal
value
Soft Switch 6A
This switch is for setting the characteristic of output contacts R1 to R5 in
relation to the START signal issued by the protection elements assigned
to them by Switch1A to Switch5A or Switch1B to Switch5B above.
These output contacts can be configured to be auto-reset type or manual-
reset type. For auto-reset type, the output contacts will automatically
return to the normal state upon removal of the condition which triggers
the START signal. In the case of manual-reset type, the output contacts
will latch on regardless of the condition which triggers the START signal
until the relay is manually reset by the user by pressing the RESET/STEP
key.
Switch elements S6A.5 and S6A.6 are for configuring the START signals
due to low-set/high-set undervoltage elements and low-set/high-set
overvoltage elements respectively such that condition for a valid START
signal to be effected on the output contacts R1 to R5 (if configured) can
either be from any one phase or from the three phases which occur
concurrently.
S6A.0
This switch element configures the characteristic of output contact R1 in
relation to START signal.
1 = Manual reset for R1.
0 = Auto reset for R1.
S6A.1
This switch element configures the characteristic of output contact R2 in
relation to START signal.
1 = Manual reset for R2.
0 = Auto reset for R2.
34
S6A.2
This switch element configures the characteristic of output contact R3 in
relation to START signal.
1 = Manual reset for R3.
0 = Auto reset for R3.
S6A.3
This switch element configures the characteristic of output contact R4 in
relation to START signal.
1 = Manual reset for R4.
0 = Auto reset for R4.
S6A.4
This switch element configures the characteristic of output contact R5 in
relation to START signal.
1 = Manual reset for R5.
0 = Auto reset for R5.
S6A.5
This switch element configures the START signal from low-set or high-
set undervoltage elements for R1 to R5 above.
1 =All three phases of the low-set or high-set undervoltage
elements must start concurrently for a valid START signal
to be delivered to R1 to R5.
0 = Any single or more phases low-set or high-set undervoltage
elements can trigger a valid START signal to R1 to R5.
S6A.6
This switch element configures the START signal from low-set or high-
set overvoltage elements for R1 to R5 above.
1 =All three phases of the low-set or high-set overvoltage
elements must start concurrently for a valid START signal
to be delivered to R1 to R5.
0 =Any single or more phases low-set or high-set overvoltage
elements can trigger a valid START signal to R1 to R5.
S6A.7
Not used.
35
S6B.7 S6B.6 S6B.5 S6B.4 S6B.3 S6B.2 S6B.1 S6B.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal
value
0 0
User’s setting
User’s setting –
hexadecimal
value
Soft Switch 6B
This switch is for setting the characteristic of output contacts R1 to R5 in
relation to the TRIP signal issued by the protection elements assigned to
them by Switch1A to Switch5A or Switch1B to Switch5B above. These
output contacts can be configured to be auto-reset type or manual-reset
type. For auto-reset type, the output contacts will automatically return to
the normal state upon removal of the condition which triggers the TRIP
signal. In the case of manual-reset type, the output contacts will latch on
regardless of the condition which triggers the TRIP signal until the relay
is manually reset by the user by pressing the RESET/STEP key.
Switch elements S6B.5 and S6B.6 are for configuring the TRIP signals
due to low-set/high-set undervoltage elements and low-set/high-set
overvoltage elements respectively such that condition for a valid TRIP
signal to be effected on the output contacts R1 to R5 (if configured) can
either be from any one phase or from the three phases which occur
concurrently.
S6B.0
This switch element configures the characteristic of output contact R1 in
relation to TRIP signal.
1 = Manual reset for R1.
0 = Auto reset for R1.
S6B.1
This switch element configures the characteristic of output contact R2 in
relation to TRIP signal.
1 = Manual reset for R2.
0 = Auto reset for R2.
36
S6B.2
This switch element configures the characteristic of output contact R3 in
relation to TRIP signal.
1 = Manual reset for R3.
0 = Auto reset for R3.
S6B.3
This switch element configures the characteristic of output contact R4 in
relation to TRIP signal.
1 = Manual reset for R4.
0 = Auto reset for R4.
S6B.4
This switch element configures the characteristic of output contact R5 in
relation to TRIP signal.
1 = Manual reset for R5.
0 = Auto reset for R5.
S6B.5
This switch element configures the TRIP signal from low-set or high-set
undervoltage elements for R1 to R5 above.
1 =All three phases of the low-set or high-set undervoltage
elements must TRIP concurrently for a valid TRIP signal to
be delivered to R1 to R5.
0 =Any single or more phases low-set or high-set undervoltage
elements can trigger a valid TRIP signal to R1 to R5.
S6B.6
This switch element configures the TRIP signal from low-set or high-set
overvoltage elements for R1 to R5 above.
1 =All three phases of the low-set or high-set overvoltage
elements must TRIP concurrently for a valid TRIP signal to
be delivered to R1 to R5.
0 =Any single or more phases low-set or high-set overvoltage
elements can trigger a valid TRIP signal to R1 to R5.
S6B.7
Not used.
37
S7.7 S7.6 S7.5 S7.4 S7.3 S7.2 S7.1 S7.0
Default setting 1 1 1 1 1 1 1 1
Default setting –
hexadecimal
value
F F
User’s setting
User’s setting –
hexadecimal
value
S7.0
Group A low-set undervoltage time delay setting.
1 = Inverse time
0 = Definite time
S7.1
Group A low-set overvoltage time delay setting.
1 = Inverse time
0 = Definite time
S7.2
Group A low-set negative sequence overvoltage time delay setting.
1 = Inverse time
0 = Definite time
(Group A)(Group B)
Soft Switch 7
This soft switch allows the user to choose between definite time setting
and inverse time setting for the low-set undervoltage, low-set over-
voltage, low-set negative sequence overvoltage and low-set residual
overvoltage.
There are two groups of settings available for the above protection
elements namely, Group A and Group B. All of the settings can be
individually set for either definite time or inverse time. Switch elements
S7.0 to S7.3 are for Group A settings and S7.4 to S7.7 are for Group B
settings.
38
S7.3
Group A low-set residual overvoltage time delay setting.
1 = Inverse time
0 = Definite time
S7.4
Group B low-set undervoltage time delay setting.
1 = Inverse time
0 = Definite time
S7.5
Group B low-set overvoltage time delay setting.
1 = Inverse time
0 = Definite time
S7.6
Group B low-set negative sequence overvoltage time delay setting.
1 = Inverse time
0 = Definite time
S7.7
Group B low-set residual overvoltage time delay setting.
1 = Inverse time
0 = Definite time
39
Soft Switch 8
This soft switch allows the user to enable or disable the high-set
undervoltage, high-set overvoltage, low-set residual overvoltage and low-
set negative sequence overvoltage for both Group A and Group B
S8.7 S8.6 S8.5 S8.4 S8.3 S8.2 S8.1 S8.0
Default setting 1 1 1 1 1 1 1 1
Default setting –
hexadecimal
value
F F
User’s setting
User’s setting –
hexadecimal
value
S8.0
For enabling Group A high-set undervoltage element.
1 = Enabled
0 = Disabled
S8.1
For enabling Group A high-set overvoltage element.
1 = Enabled
0 = Disabled
S8.2
For enabling Group A low-set residual overvoltage
1 = Enabled
0 = Disabled
S8.3
For enabling Group A low-set negative sequence overvoltage
1 = Enabled
0 = Disabled
(Group B) (Group A)
40
S8.4
For enabling Group B high-set undervoltage element.
1 = Enabled
0 = Disabled
S8.5
For enabling Group B high-set overvoltage element.
1 = Enabled
0 = Disabled
S8.6
For enabling Group B low-set residual overvoltage
1 = Enabled
0 = Disabled
S8.7
For enabling Group A low-set negative sequence overvoltage
1 = Enabled
0 = Disabled
41
Soft Switch 9A
This switch is for configuring the function of the digital input. Only one
selection is possible.
S9A.7 S9A.6 S9A.5 S9A.4 S9A.3 S9A.2 S9A.1 S9A.0
Default setting 0 0 0 0 1 0 0 0
Default setting –
hexadecimal
value
0 8
User’s setting
User’s setting –
hexadecimal
value
S9A.0
The input is configured for switching between Group A setting and Group
B setting.
1 = Selected.
0 = Not selected.
S9A.1
The input is configured as remote trip reset input.
1 = Selected.
0 = Not selected.
S9A.2
The input is configured as external tripping input source.
1 = Selected.
0 = Not selected.
S9A.3
The input is configured as blocking input.
1 = Selected.
0 = Not selected.
42
S9A.4
Not used.
S9A.5
Not used.
S9A.6
Not used.
S9A.7
Not used.
43
Soft Switch 9B
This switch will only function if switch element S9A.3 is set to 1 making
the digital input as a blocking input. The switch elements of Switch 9B
allow the user to individually select the blocking of low-set undervoltage,
low-set overvoltage, low-set negative sequence overvoltage, low-set
residual overvoltage, high-set undervoltage, and high-set overvoltage.
S9B.7 S9B.6 S9B.5 S9B.4 S9B.3 S9B.2 S9B.1 S9B.0
Default setting 0 0 0 0 0 0 0 0
Default setting –
hexadecimal
value
0 0
User’s setting
User’s setting –
hexadecimal
value
S9B.0
Low-set undervoltage blocked.
1 = Block
0 = Unblock
S9B.1
High-set undervoltage blocked.
1 = Block
0 = Unblock
S9B.2
Low-set overvoltage blocked.
1 = Block
0 = Unblock
S9B.3
High-set overvoltage blocked.
1 = Block
0 = Unblock
44
S9B.4
Low-set negative sequence overvoltage blocked.
1 = Block
0 = Unblock
S9B.5
Low-set residual overvoltage blocked.
1 = Block
0 = Unblock
S9B.6
Not used.
S9B.7
Not used.
45
SA.7 SA.6 SA.5 SA.4 SA.3 SA.2 SA.1 SA.0
Default setting 0 0 0 0 0 0 0 1
Default setting –
hexadecimal
value
0 1
User’s setting
User’s setting –
hexadecimal
value
Soft Switch A
This switch sets the voltage transformer (VT) configuration for MU2300.
There are 4 possible VT configurations as shown in Examples 1 to 4
under the “Connection Diagram & Terminal Connection” section. It is
important to choose the correct connection type failing which the wrong
voltages will be measured or derived by MU2300.
SA.0
This switch element is for selection of “3Vpn” configuration as shown in
Example 1. In this configuration, the measured voltages are the phase-to-
neutral voltage for the three phases. The phase-to-phase voltages and the
residual voltage are derived internally.
1 = selected
0 = Not selected
SA.1
This switch element is for selection of “3Vpn + Vo” configuration as
shown in Example 2. In this configuration, the measured voltages are the
phase-to-neutral voltage for the three phases and the residual overvoltage
The phase-to-phase voltages are derived internally.
1 = selected
0 = Not selected
46
SA.2
This switch element is for selection of “3Vpp + Vo” configuration as
shown in Example 3. In this configuration, the measured voltages are the
phase-to-phase voltage for the three phases and the residual overvoltage.
The phase-to-neutral voltages are not available.
1 = selected
0 = Not selected
SA.3
This switch element is for selection of “2Vpp + Vo” configuration as
shown in Example 4. In this configuration, the measured voltages are the
2 phase-to-phase voltages and the residual overvoltage. The third phase-
to-phase voltage is derived internally and phase-to-neutral voltages are
not available.
1 = selected
0 = Not selected
SA.4
Not used.
SA.5
Not used.
SA.6
Not used.
SA.7
Not used.
47
Soft Switch B
This soft switch selects the baud rate and data format of the serial
Modbus communication between the host computer (client) and the relay
MU2300 (server).
Digit 2 Digit 1
Default setting 4 7
User’s setting
Digit 1 is for selecting the communication baud rate.
Baud rate Value of Digit 1
300 1
600 2
1200 3
2400 4
4800 5
9600 6
19200 7
Digit 2 is for selecting the data format.
Data format Value of Digit 2
1 start bit, 8 data bits, no parity bit, 1 stop
bit
1
1 start bit, 8 data bits, no parity bit, 2 stop
bits
2
1 start bit, 8 data bits, odd parity bit, 1 stop
bit
3
1 start bit, 8 data bits, even parity bit, 1 stop
bit
4
48
Soft Switch C
This soft switch is for setting the device unit number of MU2300 in a
Modbus communication network. The setting range for the device unit is
from 1 to 127 and it is displayed and set in hexadecimal format.
Example:
If the selected unit number is 42, then the equivalent hexadecimal number
is 2A. For conversation between hexadecimal number and decimal
number, please refer to Appendix B.
The default unit number is 1.
49
Soft Switch D
This soft switch allows the user to either allow or disallow remote
programming or changing of the setting values of the MU2300 relay.
Once enabled, the remote host computer (client) is able to read and
modify all the settings and parameters of the relay through the serial
communication channel using Modbus protocol. Otherwise, only reading
of the setting values and relay parameters is possible.
1 – Remote programming is enabled.
0 – Remote programming is disabled.
The default setting for MU2300 is remote programming disabled (0).
50
Soft Switch E
This switch allows the contacts output of MU2300 to be manually and
individually switched on. This is very useful during testing and
commissioning of the relay.
Description Display Value
Off all contact outputs 00
On contact output R1 only 01
On contact output R2 only 02
On contact output R3 only 03
On contact output R4 only 04
On contact output R5 only 05
Steps to turn on a contact:
1. Select soft switch E by pressing the SWITCH key.
2. Press PROGRAM key.
3. Press UP or DOWN key to select the desired contact.
4. Press SWITCH or PROGRAM key to exit.
Note that all contacts will be switched OFF after the above test regardless
of the previous status of the contact outputs prior to the test.
51
Soft Switch F
This switch is for selecting the operation frequency of the electrical
system to be protected. It is crucial that the correct frequency of operation
be selected and failure to do so will give rise to wrong voltage
measurements.
0 – 50Hz system frequency
1 – 60Hz system frequency
7.1 Terminal Connection
Rear view of MU2300
52
7. Connection Diagram & Terminal Connection
Connection terminal
1
2
3
4
5
6
7
8
9
10
11
12
13 External digital input
14 External digital input
15 to 21 Not used
22 Termination resistor (for RS485)
23 RS485 negative terminal
24 RS485 positive terminal
25 Communication cable shield
26,27 Output contact R5
28 N.C. contact for IRF
29 N.O. contact for IRF
30 COMMON contact for IRF
31 Casing earth terminal
32 Auxiliary supply input (No polarity)
33 Auxiliary supply input (No polarity)
34 N.C. contact for tripping contact R1
35 N.O. contact for tripping contact R1
36 COMMON contact for contact R1
37,38 Output contact R2
39,40 Output contact R3
41,42 Output contact R4
53
Not used
Not used
Not used
Not used
VT input for residual voltage
VT input for residual voltage
VT input for phase A
VT input for phase A
VT input for phase B
VT input for phase B
VT input for phase C
VT input for phase C
Description of Function
54
MU2300
3
2
6
5
9
8
12
11
31
32
33
13
14
34
36
35
38
37
40
39
42
41
27
26
28
30
29
25
24
22
23
External
Digital
Input
Uaux
RS485
Communication
cableshield
Failure
Relay
Internal
R1
R2
R3
R4
R5
A
B
C
TripContact
TerminationResistor
N-
P+
A
BC
Phaserotation
Example 1: 3Vpn CONFIGURATION (Phase-Neutral)
55
MU2300
3
2
6
5
9
8
12
11
31
32
33
13
14
34
36
35
38
37
40
39
42
41
27
26
28
30
29
25
24
22
23
External
Digital
Input
Uaux
RS485
Communication
cableshield
Failure
Relay
Internal
R1
R2
R3
R4
R5
A
B
C
TripContact
TerminationResistor
N-
P+
A
BC
Phaserotation
Example 2: 3Vpn + V0 CONFIGURATION (Phase-Neutral) + residual
voltage.
56
MU2300
3
2
6
5
9
8
12
11
31
32
33
13
14
34
36
35
38
37
40
39
42
41
27
26
28
30
29
25
24
22
23
External
Digital
Input
Uaux
RS485
Communication
cableshield
Failure
Relay
Internal
R1
R2
R3
R4
R5
A
B
C
TripContact
TerminationResistor
N-
P+
A
BC
Phaserotation
Example 3: 3Vpp + V0 CONFIGURATION (Phase-Phase) + residual
voltage.
57
MU2300
3
2
6
5
9
8
12
11
31
32
33
13
14
34
36
35
38
37
40
39
42
41
27
26
28
30
29
25
24
22
23
External
Digital
Input
Uaux
RS485
Communication
cableshield
Failure
Relay
Internal
R1
R2
R3
R4
R5
A
B
C
TripContact
TerminationResistor
N-
P+
A
BC
Phaserotation
Example 4: 2Vpp + V0 CONFIGURATION + residual voltage
198
58
8. Case Dimension
59
9. Technical Data
i) Measuring Inputs
Rated Voltage Input * 57-130V
Frequency 50Hz or 60Hz
ii) Rated Auxiliary supply voltage
Model MU2300-150D 24~150V DC
Model MU2300-240AD 85~265V AC
110~340V DC
iii) Power Consumption 6-10VA typical (AC
auxiliary voltage)
5-9W typical(DC auxiliary
voltage)
iv) External Digital Input 80~250V AC/DC
*Maximum input voltage is 260V
Output
i) All contacts
Rated voltage 250V AC
Continuous carry 5A AC or DC
Make and carry for 0.2 sec 30A AC or DC
Expected electrical life (min
operation)
5,000,000
Operating time Maximum 15ms
Undervoltage element
i) Low set
Low set setting, U< 5-130V
Low set definite time, tU< 0-600s
Time multiplier, TMS 0.5-100
ii) High set
High set setting, U<< 5-130V
High set definite time, tU<< 0-600s
iii) Hysteresis 105%
Input
60
Overvoltage element
i) Low set
Low set setting, U> 5-200V
Low set definite time, tU> 0-600s
ii) High set
High set setting, U>> 5-260V
High set definite time, tU>> 0-600s
iii) Time multiplier, TMS 0.5-100
Negative sequence overvoltage element
i) Negetive sequence overvoltage
setting, U2>
5-200V
ii) Time multiplier, TMS 0.5-100
iii) Negative sequence overvoltage
definite time, tU2>
0-600s
Residual overvoltage element
i) Residual overvoltage setting, U0> 0.5-130V
ii) Time multiplier, TMS 0.5-100
iii) Residual overvoltage definite time
tU0>
0-600s
Communication
i) Hardware interface Isolated RS485
ii) Protocol Modbus-RTU
iii) Baud rate 300,600,1200,2400,4800,
9600,19200
61
10 Tests and Standards
High voltage dielectric withstand test. IEC60255-5 …... 2.0kV rms, 1 min
High voltage impulse test. IEC60255-5 ………….…….. 5kV, 1.2/50 s
Electrical fast transient. IEC61000-4-4,
Level 4, power supply inputs ………………………….... 4kV, 5/50ns
Electrical fast transient. IEC61000-4-4,
Level 4, other inputs …………..………………………... 2kV, 5/50ns
Electrostatic discharge. IEC61000-4-2
Class III, air discharge ……………………………….…. 8kV
Electrostatic discharge. IEC61000-4-2
Class III, contact discharge .………………….……….... 6kV
Enclosure protection when panel mounted ……............ IP54
u
Binary to hexadecimal- conversion table: -
Hexadecimal Binary
0 0000
1 0001
2 0010
3 0011
4 0100
5 0101
6 0110
7 0111
8 1000
9 1001
A 1010
B 1011
C 1100
D 1101
E 1110
F 1111
Decimal
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
62
11 Appendix A
Decimal to Hexadecimal Conversation
Decimal Hexadecimal Decimal Hexadecimal Decimal Hexadecimal
1 1 44 2C 87 57
2 2 45 2D 88 58
3 3 46 2E 89 59
4 4 47 2F 90 5A
5 5 48 30 91 5B
6 6 49 31 92 5C
7 7 50 32 93 5D
8 8 51 33 94 5E
9 9 52 34 95 5F
10 A 53 35 96 60
11 B 54 36 97 61
12 C 55 37 98 62
13 D 56 38 99 63
14 E 57 39 100 64
15 F 58 3A 101 65
16 10 59 3B 102 66
17 11 60 3C 103 67
18 12 61 3D 104 68
19 13 62 3E 105 69
20 14 63 3F 106 6A
21 15 64 40 107 6B
22 16 65 41 108 6C
23 17 66 42 109 6D
24 18 67 43 110 6E
25 19 68 44 111 6F
26 1A 69 45 112 70
27 1B 70 46 113 71
28 1C 71 47 114 72
29 1D 72 48 115 73
30 1E 73 49 116 74
31 1F 74 4A 117 75
32 20 75 4B 118 76
33 21 76 4C 119 77
34 22 77 4D 120 78
35 23 78 4E 121 79
36 24 79 4F 122 7A
37 25 80 50 123 7B
38 26 81 51 124 7C
39 27 82 52 125 7D
40 28 83 53 126 7E
41 29 84 54 127 7F
42 2A 85 55
43 2B 86 56
63
12 Appendix B
64
13 Appendix C
Event code:
Event code Description
00 U1P/U12 undervoltage U < start
01 U2P/U23 undervoltage U < start
02 U3P/U31 undervoltage U < start
03 U1P/U12 undervoltage U < trip
04 U2P/U23 undervoltage U < trip
05 U3P/U31 undervoltage U < trip
06 U1P/U12 undervoltage U << start
07 U2P/U23 undervoltage U << start
08 U3P/U31 undervoltage U << start
09 U1P/U12 undervoltage U << trip
10 U2P/U23 undervoltage U << trip
11 U3P/U31 undervoltage U << trip
40 U1P/U12 undervoltage U < start reset
41 U2P/U23 undervoltage U < start reset
42 U3P/U31 undervoltage U < start reset
43 U1P/U12 undervoltage U < trip reset
44 U2P/U23 undervoltage U < trip reset
45 U3P/U31 undervoltage U < trip reset
46 U1P/U12 undervoltage U << start reset
47 U2P/U23 undervoltage U << start reset
48 U3P/U31 undervoltage U << start reset
49 U1P/U12 undervoltage U << trip reset
50 U2P/U23 undervoltage U << trip reset
51 U3P/U31 undervoltage U << trip reset
12 U1P/U12 overvoltage U > start
13 U2P/U23 overvoltage U > start
14 U3P/U31 overvoltage U > start
15 U1P/U12 overvoltage U > trip
16 U2P/U23 overvoltage U > trip
17 U3P/U31 overvoltage U > trip
18 U1P/U12 overvoltage U >> start
65
19 U2P/U23 overvoltage U >> start
20 U3P/U31 overvoltage U >> start
21 U1P/U12 overvoltage U >> trip
22 U2P/U23 overvoltage U >> trip
23 U3P/U31 overvoltage U >> trip
52 U1P/U12 overvoltage U > start reset
53 U2P/U23 overvoltage U > start reset
54 U3P/U31 overvoltage U > start reset
55 U1P/U12 overvoltage U > trip reset
56 U2P/U23 overvoltage U > trip reset
57 U3P/U31 overvoltage U > trip reset
58 U1P/U12 overvoltage U >> start reset
59 U2P/U23 overvoltage U >> start reset
60 U3P/U31 overvoltage U >> start reset
61 U1P/U12 overvoltage U >> trip reset
62 U2P/U23 overvoltage U >> trip reset
63 U3P/U31 overvoltage U >> trip reset
24 Negative sequence overvoltage U2 > start
25 Negative sequence overvoltage U2 > trip
64 Negative sequence overvoltage U2 > start reset
65 Negative sequence overvoltage U2 > trip reset
26 Residual overvoltage U0 > start
27 Residual overvoltage U0 > trip
66 Residual overvoltage U0 > start reset
67 Residual overvoltage U0 > trip reset
A0 R1 activated
A1 R1 reset
A2 R2 activated
A3 R2 reset
A4 R3 activated
A5 R3 reset
A6 R4 activated
A7 R4 reset
66
A8 R5 activated
A9 R5 reset
B1 Digital input activated
B2 Digital input reset
E1 Tripped by external digital input
FE Relay is powered up
INDUSTRI TEKNOLOGI MIKRO BERHAD,
No. 1, Jalan TP 7/7, Sime UEP Industrial Park, 40400 Shah Alam, Selangor, Malaysia.
Tel: +603-5192 7155 Fax: +603-5192 7166 Website: www.itmikro.com
E-mail: sales@itmikro.com
MU2300-150806

More Related Content

What's hot

Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric CatalogueDaniel Wu
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric CatalogueAshley Lin
 
LV Compact Soft starter Familiarisation Presentation - SSUK
LV Compact Soft starter Familiarisation Presentation - SSUKLV Compact Soft starter Familiarisation Presentation - SSUK
LV Compact Soft starter Familiarisation Presentation - SSUKStuart Harvey
 
Thermostat with binary sensor input start guide
Thermostat with binary sensor input start guideThermostat with binary sensor input start guide
Thermostat with binary sensor input start guideDomotica daVinci
 
Minilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualMinilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualDomotica daVinci
 
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_engQubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_engDomotica daVinci
 
Mirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheetMirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheetAngus Sankaran
 
Pulse width modulation (PWM)
Pulse width modulation (PWM)Pulse width modulation (PWM)
Pulse width modulation (PWM)amar pandey
 
TENSE Elektrik-Elektronik Introducing Presentation
TENSE Elektrik-Elektronik Introducing PresentationTENSE Elektrik-Elektronik Introducing Presentation
TENSE Elektrik-Elektronik Introducing PresentationEmrullahAKGN
 
Current_Shap_Strat_Buck_PFC
Current_Shap_Strat_Buck_PFCCurrent_Shap_Strat_Buck_PFC
Current_Shap_Strat_Buck_PFCSteve Mappus
 

What's hot (17)

S123 b30u
S123 b30uS123 b30u
S123 b30u
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric Catalogue
 
Sinopak Electric Catalogue
Sinopak Electric CatalogueSinopak Electric Catalogue
Sinopak Electric Catalogue
 
LV Compact Soft starter Familiarisation Presentation - SSUK
LV Compact Soft starter Familiarisation Presentation - SSUKLV Compact Soft starter Familiarisation Presentation - SSUK
LV Compact Soft starter Familiarisation Presentation - SSUK
 
Thermostat with binary sensor input start guide
Thermostat with binary sensor input start guideThermostat with binary sensor input start guide
Thermostat with binary sensor input start guide
 
Pt4115 e
Pt4115 ePt4115 e
Pt4115 e
 
320 lecture7
320 lecture7320 lecture7
320 lecture7
 
L03.1 l aa tv philips
L03.1 l aa tv philipsL03.1 l aa tv philips
L03.1 l aa tv philips
 
Minilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manualMinilux light wired sensor for outdoor mounting 0-10V manual
Minilux light wired sensor for outdoor mounting 0-10V manual
 
Lm331
Lm331Lm331
Lm331
 
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_engQubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
 
Mirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheetMirus onics harmonic_mitigating_power_center_datasheet
Mirus onics harmonic_mitigating_power_center_datasheet
 
Pulse width modulation (PWM)
Pulse width modulation (PWM)Pulse width modulation (PWM)
Pulse width modulation (PWM)
 
An 1072
An 1072An 1072
An 1072
 
TENSE Elektrik-Elektronik Introducing Presentation
TENSE Elektrik-Elektronik Introducing PresentationTENSE Elektrik-Elektronik Introducing Presentation
TENSE Elektrik-Elektronik Introducing Presentation
 
Current_Shap_Strat_Buck_PFC
Current_Shap_Strat_Buck_PFCCurrent_Shap_Strat_Buck_PFC
Current_Shap_Strat_Buck_PFC
 

Similar to Catalog mikro mikro mu2300-user-dienhathe.vn

Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, DelhiMicrocontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, DelhiIndiaMART InterMESH Limited
 
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...IndiaMART InterMESH Limited
 
Protection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical RelayProtection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical Relayidescitation
 
Generator Transformer Protections.
Generator Transformer  Protections.Generator Transformer  Protections.
Generator Transformer Protections.Nischal Popat
 
Catalog mikro mikro mk300-user
Catalog mikro mikro mk300-userCatalog mikro mikro mk300-user
Catalog mikro mikro mk300-userDien Ha The
 
Catalog mikro mikro mk300-user
Catalog mikro mikro mk300-userCatalog mikro mikro mk300-user
Catalog mikro mikro mk300-userDien Ha The
 
Catalog mikro mikro mk300-user-dienhathe.vn
Catalog mikro mikro mk300-user-dienhathe.vnCatalog mikro mikro mk300-user-dienhathe.vn
Catalog mikro mikro mk300-user-dienhathe.vnDien Ha The
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...IRJET Journal
 
A project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and ArduinoA project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and ArduinoJawwad Sadiq Ayon
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Micro switch module qubino manual
Micro switch module qubino manualMicro switch module qubino manual
Micro switch module qubino manualDomotica daVinci
 
Gsm based transformer fault detection system
Gsm based transformer fault detection systemGsm based transformer fault detection system
Gsm based transformer fault detection systemKabilesh K
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
modeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorermodeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorervinay kumar mali
 
Lv side distributed power factor correction system
Lv side distributed power factor correction systemLv side distributed power factor correction system
Lv side distributed power factor correction systemeSAT Publishing House
 

Similar to Catalog mikro mikro mu2300-user-dienhathe.vn (20)

Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, DelhiMicrocontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
Microcontroller Based Devices By Novatek Electro (India) Pvt. Ltd, Delhi
 
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
Microcontroller Based Intelligent Devices By Novatek Electro India Private Li...
 
Catalog ind-2018-5
Catalog ind-2018-5Catalog ind-2018-5
Catalog ind-2018-5
 
Protection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical RelayProtection, Control and Operation of Transformer Using Numerical Relay
Protection, Control and Operation of Transformer Using Numerical Relay
 
Generator Transformer Protections.
Generator Transformer  Protections.Generator Transformer  Protections.
Generator Transformer Protections.
 
Ncp1032 d
Ncp1032 dNcp1032 d
Ncp1032 d
 
Lm555
Lm555Lm555
Lm555
 
Catalog mikro mikro mk300-user
Catalog mikro mikro mk300-userCatalog mikro mikro mk300-user
Catalog mikro mikro mk300-user
 
Catalog mikro mikro mk300-user
Catalog mikro mikro mk300-userCatalog mikro mikro mk300-user
Catalog mikro mikro mk300-user
 
Catalog mikro mikro mk300-user-dienhathe.vn
Catalog mikro mikro mk300-user-dienhathe.vnCatalog mikro mikro mk300-user-dienhathe.vn
Catalog mikro mikro mk300-user-dienhathe.vn
 
A4988
A4988A4988
A4988
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
 
A project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and ArduinoA project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and Arduino
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Micro switch module qubino manual
Micro switch module qubino manualMicro switch module qubino manual
Micro switch module qubino manual
 
Spx29300 t 2.5-tr
Spx29300 t 2.5-trSpx29300 t 2.5-tr
Spx29300 t 2.5-tr
 
Gsm based transformer fault detection system
Gsm based transformer fault detection systemGsm based transformer fault detection system
Gsm based transformer fault detection system
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
modeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorermodeling and simulation of a dynamic voltage restorer
modeling and simulation of a dynamic voltage restorer
 
Lv side distributed power factor correction system
Lv side distributed power factor correction systemLv side distributed power factor correction system
Lv side distributed power factor correction system
 

More from Dien Ha The

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Dien Ha The
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookDien Ha The
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseDien Ha The
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Dien Ha The
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalogDien Ha The
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbDien Ha The
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Dien Ha The
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsDien Ha The
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter familyDien Ha The
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesDien Ha The
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesDien Ha The
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuDien Ha The
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesDien Ha The
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Dien Ha The
 

More from Dien Ha The (20)

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.com
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library book
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalog
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcb
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new models
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter family
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din series
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 series
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj series
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
 

Recently uploaded

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...ranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 

Recently uploaded (20)

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 

Catalog mikro mikro mu2300-user-dienhathe.vn

  • 1. User's Manual VoltageProtectionRelay User's Manual Features • Low-set undervoltage stage with definite time or inverse time • High-set undervoltage stage with definite time • Low-set overvoltage stage with definite time or inverse time • High-set overvoltage stage with definite time • Negative sequence overvoltage protection • Neutral displacement/ residual overvoltage protection • Multi-function isolated digital input • Fault data and event code recording • Five programmable voltage-free output contacts • Isolated RS485 Modbus-RTU communication
  • 2. Table of Contents Page 1 For continuous product development, we reserve the right to supply equipment which may vary from that described in this manual. 1. Introduction 2. Description of Operation 3. Display 4. Key Button Input 5. Programming 6. Soft Switches 7. Connection Diagram & Terminal Connection 8. Case Dimension 9. Technical Data 10. Test and Standards 11. Appendix A 12. Appendix B 13. Appendix C 2 3 12 22 24 27 52 58 59 61 62 63 64
  • 3. 2 Features 1. Introduction The MU2300 voltage protection relay is a microprocessor based numerical relay intended for the voltage protection in electrical distribution network. It can also be used for generators, motors and transformer protection. A fully digital user interface with bright seven-segment display and indicators provides a very user friendly access to all the measurements, user parameters and records. MU2300 uses a digital filter to extract the fundamental voltage waveforms for the three phases, phase-to-phase voltage or phase-to- neutral voltage, for the operation of the protection elements. Such protection elements are undervoltage low-set and high-set; overvoltage low-set and high-set; negative sequence overvoltage low-set; residual overvoltage low-set. Besides being operated from the front panel of MU2300, this relay can also be accessed when connected to a networked system through its isolated RS485 Modbus-RTU communication interface. • Low-set undervoltage stage with definite-time or inverse time • High-set undervoltage stage with definite-time • Low-set overvoltage stage with definite-time or inverse time • High-set overvoltage stage with definite-time • Negative sequence overvoltage protection • Neutral displacement/ residual overvoltage protection • Multi-function isolated digital input • Fault data and event code recording • Five programmable voltage-free output contacts • Isolated RS485 Modbus-RTU communication
  • 4. 3 2. Description of Operation MU2300 is equipped with 3 accurate and independent voltage inputs connected to the voltage transformers of the object to be protected. It continuously monitors these voltage inputs’ fundamental frequency components for the occurrence of faults. On detection of a fault, the relay will start and then operated the trip output which is connected to the circuit breaker or indicator. The phase-to-phase voltage, phase-to-neutral voltage, negative sequence voltage and the residual voltage, measured at the moment of tripping, will be recorded in the memories of the relay. The relay has four different voltage transformer (VT) configurations. Depending on the configuration chosen, the input voltages can be phase- to-phase voltages or phase-to-neutral voltages. If the inputs are phase-to- phase voltages, the protection setting is based on the phase-to-phase voltages. However, if the configuration chosen is for phase-to-neutral input voltages, the protection setting will then be based on the phase-to- phase voltages and the derived phase-to-phase voltages are for measurements only. 2.1 Undervoltage Elements (27) The MU2300 has two stages for undervoltage protection, namely the low- set undervoltage element and high-set undervoltage element. When the voltage values fall below the set low-set undervoltage value, the low-set undervoltage element will start and deliver a start signal to the contact output (if assigned) and the front panel START indicator. After a pre-set delay time, determined by the user’s selection between definite- time and inverse time characteristic, the undervoltage element delivers a trip signal to the contact output (if assigned) and the front panel TRIP indicator. Similarly, the high-set undervoltage element will start and then deliver a trip signal to the contact output (if assigned) and the front panel indicators if the voltage falls below the set high-set undervoltage value for duration longer than the high-set definite time. The low-set and high-set elements can be selectively blocked by the digital input if the appropriate switch setting in Soft Switch 9A and Soft Switch 9B are set. The high-set stage can also be set out of operation by Soft Switch 8.
  • 5. 4 When the relay is first powered on without any input voltages connected to the VTs, the undervoltage elements are temporary disabled. The undervoltage elements will be activated once any of the input voltages exceeded 10V. To ensure that the undervoltage protection elements will not trip the relay when the voltage inputs are energised, the delay time should be set sufficiently long or the undervoltage elements are set to be temporary blocked by the digital input. 2.1.1 Inverse time delay characteristic The inverse characteristic for undervoltage U<, is defined by the following equation: TMS t = 1 - V Vs where: t = operating time in seconds TMS = time multiplier setting V = applied input voltage Vs = relay setting voltage NOTE: this equation is valid for Vs > V
  • 6. 5 1 10 100 1000 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 TMS=1 TMS=5 TMS=3 TMS=10 TMS=8 Applied voltage/relay setting voltage Operatingtime(sec) Undervoltage Characteristic Figure 1: Inverse time curves for the undervoltage element “U<”
  • 7. 6 2.2 Overvoltage Elements (59) The MU2300 has two stages for overvoltage protection, namely the low- set overvoltage element and high-set overvoltage element. When the voltage values rise above the set low-set overvoltage value, the low-set overvoltage element will start and deliver a start signal to the contact output (if assigned) and the front panel START indicator. After a pre-set delay time, determined by the user’s selection between definite- time and inverse time characteristic, the overvoltage element delivers a trip signal to the contact output (if assigned) and the front panel TRIP indicator. Similarly, the high-set overvoltage element will start and then deliver a trip signal to the contact output (if assigned) and the front panel indicators if the voltage values rise above the set high-set overvoltage value for duration longer than the high-set definite time. The low-set and high-set elements can be selectively blocked by the digital input if the appropriate switch settings in Soft Switch 9A and Soft Switch 9B are set. The high-set stage can also be set out of operation by Soft Switch 8. 2.2.1 Inverse time delay characteristic The inverse characteristic for overvoltage U>, is defined by the following equation: t = TMS V - 1 Vs where: t = operating time in seconds TMS = time multiplier setting V = applied input voltage Vs = relay setting voltage NOTE: this equation is valid for V > Vs |
  • 8. 7 0.01 0.1 1 10 100 1000 0 2 4 6 8 10 12 14 16 18 20 Applied voltage input/relay setting voltage Operatingtime(sec) TMS=1 TMS=8 TMS=10 TMS=5 TMS=3 Overvoltage Characteristic Figure 2: Inverse time curves for the overvoltage element “U>”
  • 9. 8 2.3 Negative Sequence Overvoltage Element (47) For negative sequence overvoltage on MU2300, there is only low-set element. The negative sequence voltage is derived from the three phase- to-neutral voltages measured from the voltage inputs if the relay is configured in Soft Switch A to measure the phase-to-neutral voltages. If the relay is configured in Soft Switch A to measure the phase-to-phase voltages, the negative sequence voltage is derived from the phase-to- phase voltage. When the negative sequence voltage value rises above the set low-set negative sequence value, the negative sequence low-set overvoltage element will start and deliver a start signal to the contact output (if assigned) and the front panel START indicator. After a pre-set delay time determined by the user’s selection between definite-time and inverse time the negative sequence overvoltage element delivers a trip signal to the contact output (if assigned) and the front panel TRIP indicator. The low-set element can be selectively blocked by the digital input if the appropriate switch settings in Soft Switch 9A and Soft Switch 9B are set accordingly. 2.3.1 Inverse time delay characteristic The inverse characteristic for negative sequence overvoltage U2>,is defined by the following equation: TMS t = V - 1 Vs where: t = operating time in seconds TMS = time multiplier setting V = calculated negative sequence voltage Vs = relay setting voltage NOTE: this equation is valid for V > Vs |
  • 10. 9 0.01 0.1 1 10 100 1000 0 2 4 6 8 10 12 14 16 18 20 Operatingtime(sec) TMS=1 TMS=8 TMS=10 TMS=5 TMS=3 Figure 3: Inverse time curves for the overvoltage element “U2>” Negative sequence overvoltage characteristic Derived negative sequence overvoltage/relay setting voltage
  • 11. 10 2.4.1 Inverse time delay characteristic The inverse characteristic for residual overvoltage U0>, is defined by the following equation: TMS t = V - 1 Vs where: t = operating time in seconds TMS = time multiplier setting V = applied or derived residual input voltage Vs = relay setting voltage NOTE: this equation is valid for V > Vs 2.4 Neutral displacement /Residual Overvoltage (59N) For residual overvoltage on MU2300, there is only low-set element. The residual voltage is either derived from the three phase-to-neutral voltage measurements of the voltage inputs or is measured directly from the residual voltage transformer depending on the setting of Soft Switch A. If the relay is configured in Soft Switch A to measures the phase-to-phase voltages, the residual voltage must be measured by the residual voltage transformer. When the residual overvoltage value rises above the set low-set residual overvoltage value, the low-set residual overvoltage element will start and deliver a start signal to the contact output (if assigned) and the front panel START indicator. After a pre-set delay time, determined by the user’s selection between definite-time and inverse time characteristic, the residual overvoltage element delivers a trip signal to the contact output (if assigned) and the front panel TRIP indicator. The low-set element can be selectively blocked by the digital input if the appropriate switch settings in Soft Switch 9A and Soft Switch 9B are set accordingly.
  • 12. 11 0.01 0.1 1 10 100 1000 0 2 4 6 8 10 12 14 16 18 20 Operatingtime(sec) TMS=1 TMS=8 TMS=10 TMS=5 TMS=3 Figure 4: Inverse time curves for the overvoltage element “U0>” Residual overvoltage characteristic Applied or derived residual voltage input/relay setting voltage
  • 13. 12 3. Display a) b) c) 3.1 Indicators This is the power indicator. It shows the presence of auxiliary power supply to the MU2300 relay. This indicator lights up when any or all of the protection elements, namely, undervoltage protection, overvoltage protection, negative sequence overvoltage and residual overvoltage elements are started (pick-up). This indicator lights up when any or all of the protection elements, namely, undervoltage protection, overvoltage protection, negative sequence overvoltage and residual overvoltage elements are started (pick-up) due to fault conditions and subsequently tripped due to the sustained fault condition.
  • 14. 13 e) Number Value Number Value U12/ U1P d) Digit display The two formats of the display are as shown below: The “Number” is for displaying the item selected and the “Value” is to show the corresponding parameter associated with the item “Number” selected. When this indicator is lighted, the digit display is showing the value of either U1 phase-to-neutral voltage or U12 phase-to-phase voltage. When the phase-to-neutral voltage is shown, the “Number” field of the digit display shows an alphabet “P” whereas when phase-to- phase voltage is shown, the “Number” field displays an alphabet “L”. This indicator blinks when the undervoltage or overvoltage protection element corresponding to U1 or U12 pick-up or tripped.
  • 15. 14 f) g) h) i) j) k) U23/U2P U31/U3P U0 U2 Record Event Similar to item e) above, this indicator shows the U2 phase-to- neutral voltage or U23 phase-to-phase voltage. Similar to item e) above, this indicator shows the U3 phase-to- neutral voltage or U31 phase-to-phase voltage. When this indicator is lighted, the digit display shows the residual voltage. It blinks when the corresponding protection element pick- up or trip. When this indicator is lighted, the digit display shows the negative sequence voltage. It blinks when the corresponding protection element pick-up or trip. This indicator will light up simultaneously with either U12/U1P, U23/U2P, U31/U3P, U0, or U2. When lighted, the digit display is showing the previously recorded voltages at then moment when MU2300 trips. There are nine records available and each can be viewed at by pressing the DOWN key. Record number 1 is the latest record. When this indicator is lighted, the digit display is showing the recorded event code. There are 60 numbers of events available and
  • 16. 15 l) m) n) o) U< tU< U<< tU<< all the recorded events will be cleared when the auxiliary power supply to MU2300 is disconnected. The event code is in Appendix C. All event registered will be displayed one-by-one automatically if the relay is left untouched in this mode of for about 20 seconds. When this indicator is lighted, the digit display shows the low-set undervoltage setting. The “Number” field of the digit display indicates whether it is a Group A or Group B setting. The “Value” field shows the setting voltage. When this indicator is lighted, depending on the user setting on Soft Switch 7, the digit display will either show the TMS or the definite time delay for low-set undervoltage. The “Number” field of the digit display shows whether it is a Group A or Group B setting. When this indicator is lighted, the digit display shows the high-set undervoltage setting. The “Number” field of the digit display indicates whether it is a Group A or Group B setting. The “Value” field shows the setting voltage. When this indicator is lighted, the digit display shows the high-set definite time delay for undervoltage. The “Number” field of the digit display shows whether it is a Group A or Group B setting.
  • 17. 16 p) q) r) U> tU> U>> tU>> U2> s) t) When this indicator is lighted, the digit display shows the low-set overvoltage setting. The “Number” field of the digit display indicates whether it is a Group A or Group B setting. The “Value” field shows the setting voltage. When this indicator is lighted, depending on the user setting on Soft Switch 7, the digit display will either show the TMS or the definite time delay for low-set overvoltage. The “Number” field of the digit display shows whether it is a Group A or Group B setting. When this indicator is lighted, the digit display shows the high-set overvoltage setting. The “Number” field of the digit display indicates whether it is a Group A or Group B setting. The “Value” field shows the setting voltage. When this indicator is lighted, the digit display shows the high-set definite time delay for overvoltage. The “Number” field of the digit display shows whether it is a Group A or Group B setting. When this indicator is lighted, the digit display shows the low-set negative sequence overvoltage setting. The “Number” field of the digit display indicates whether it is a Group A or Group B setting. The “Value” field shows the setting for the negative sequence overvoltage.
  • 18. 17 tU2> U0> tU0> INPUT u) v) w) x) When this indicator is lighted, depending on the user setting on Soft Switch 7, the digit display will either show the TMS multiplier or the definite time delay for low-set negative sequence overvoltage. The “Number” field of the digit display shows whether it is a Group A or Group B setting. When this indicator is lighted, the digit display shows the low-set residual overvoltage setting. The “Number” field of the digit display indicates whether it is a Group A or Group B setting. The “Value” field shows the setting for the residual overvoltage. When this indicator is lighted, depending on the user setting on Soft Switch 7, the digit display will either show the TMS or the definite time delay for low-set residual overvoltage. The “Number” field of the digit display shows whether it is a Group A or Group B setting. This indicator reflects the status of the external digital input regardless of the soft switches setting. It is a direct mimic of the status of the input. When voltage is applied to the digital input, the indicator will turn on.
  • 19. 18 3.2 Normal Status Display Under normal operating condition where non of the protection elements have operated and the key are not pressed, all the indicators will be switched off except the following: a) The AUX indicator shows that there is power supply to the relay. b) AUX Blinking The decimal point on the left-most digit blinks to indicate that the relay is functioning normally.
  • 20. 19 3.3 Start Status Display The Start indicator lights up when any of the protection elements pick-up (started). Other indicators also lighted simultaneously to show which protection elements have started. START U12/U1P U23/U2P U31/U3P a) The Start indicator light up to indicate that the relay pick up. b) One or more of the following indicators blink to indicate the sources of the pick-up. U0 U2 U< U<< U> U>> U2> U0> c) One or more of the following indicators blink to indicate that the protection elements that have pick-up.
  • 21. 20 TRIP U12/U1P U23/U2P 3.4 Trip Status Display The Trip indicator lights up when any of the protection elements trip. Other indicators also lighted simultaneously to show which protection elements have tripped. a) The Trip indicator light up to indicates that the relay has tripped. It stays steady when the condition for tripping has not been removed. Otherwise, the indicator blinks. b) One of the following indicators blink to indicate the sources of the pick-up. U31/U3P U0 U2 U< U<< U> U>> U2> U0> c) One of the following indicators blink to indicate that the protection elements that have pick-up.
  • 22. 21 Number Value d) The digit display shows the value of the trip voltage at the moment of tripping. The “Number” field of the digit display may indicate an alphabet “L” or “P” which denote phase-to-phase voltage or phase-to-neutral voltage respectively. When the voltage value is not available, the display will show “-E-“ sign on the “Value” field.
  • 23. 22 START U12 U1P U23 U2P U31 U3P U0 U2 U12/U1P Record U23/U2P Record U31/U3P Record U0 Record U< tU< U<< tU<< U> tU> U>> tU>> U2> tU2> U0> U2 Record Event tU0> Other U12/U1P Record Other U23/U2P Record Other U31/U3P Record Other U0 Record Other U2 Record * * * * * * Use DOWN key 4. Key Button Input a) RESET/STEP key This key has two functions: I. To reset the relay when the relay is tripped. II. To select the items to be view at such as all the input voltages and setting parameters. The sequence of selection when the RESET/STEP key is pressed is as shown below. Pressing the UP key will reverse the sequence.
  • 24. 23 b) The PROGRAM key Item to be programmed is first selected by the RESET/STEP key. Then pressing the PROGRAM key set the relay into programming mode for the selected item. Value of the selected item can then be changed by the UP or DOWN key. Pressing the PROGRAM key again while in the programming mode will cause the relay to exit from the programming mode with the new value saved into the non- volatile memory. The indicator adjacent to the PROGRAM key will light up when in programming mode. c) The UP and DOWN keys These keys are for changing the value of the selected item while in programming mode. Under non-programming mode, the UP key is used as the reverse STEP key and the DOWN key is used for changing the record number while in the recorded data retrieval mode. d) The SWITCH key Press this key to step through all the soft switches.
  • 25. 24 5. Programming 5.1 To program the setting for U <, U <<, U >, U >>, U0 >, and U2 > Step 1 Select the required item by stepping through all the items using the RESET/STEP key or the UP key. The corresponding light for the selected item will be lighted. Step 2 Press the PROGRAM key once. The indicator for the selected item will blink and the indicator for PROGRAM key lights up to indicate that the system is now in programming mode. Step 3 Use the UP or DOWN key to select the desire value. Hold down the key until the desired value appears.
  • 26. 25 Step 4 To save the changed value, press the PROGRAM key again. The indicator for the PROGRAM key will turn off and the blinking indicator for the selected item stop blinking. To abort without saving the selected setting, press the RESET/STEP key. Programming is prohibited when the relay is started or tripped.
  • 27. 26 5.2 To program the soft switches Step1 Press the SWITCH key until the desired switch number appears on the display. Step 2 Press the PROGRAM key to enter into programming mode. The switch number on the “Number” field of the digit display blinks to indicate that the system is now in soft switch programming mode. The indicators for the PROGRAM and the SWITCH keys also light up. Step 3 Use the UP or DOWN key for changing the soft switch setting. Hold down the key until the desired value appears. Step 4 Press the PROGRAM key again to save the changed setting. The switch number will stop blinking and the indicator for the PROGRAM key will be switched off. To abort without saving the change, press the SWITCH key or RESET/ STEP key. Programming is prohibited when the relay is started or tripped.
  • 28. 27 Switch Number Switch Value Digit2 Digit1 For contact output R1 6 Soft Switches Soft switches are used to configure the features of the relay and the functional characteristic of the relays outputs. S1A.7 S1A.6 S1A.5 S1A.4 S1A.3 S1A.2 S1A.1 S1A.0 Default setting 1 0 1 0 1 0 1 0 Default setting – hexadecimal value A A User’s setting User’s setting – hexadecimal value Switch Number Switch Value Digit2 Digit1 or For contact output R2 S2A.7 S2A.6 S2A.5 S1A.4 S2A.3 S1A.2 S2A.1 S2A.0 Default setting 0 1 0 1 0 1 0 1 Default setting – hexadecimal value 5 5 User’s setting User’s setting – hexadecimal value Soft Switch 1A to Soft Switch 5A These switches are for configuring the output contacts R1 to R5 in relation to low-set undervoltage U<, high-set undervoltage U<<, low-set overvoltage U> and high-set overvoltage U>>.
  • 29. 28 For contact output R3 For contact output R4 For contact output R5 S3A.7 S3A.6 S3A.5 S3A.4 S3A.3 S3A.2 S3A.1 S3A.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value S4A.7 S4A.6 S4A.5 S4A.4 S4A.3 S4A.2 S4A.1 S4A.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value S5A.7 S5A.6 S5A.5 S5A.4 S5A.3 S5A.2 S5A.1 S5A.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value SxA.0 This switch element is to connect/disconnect the corresponding contact output Rx to low-set undervoltage (U <) START signal. 1 = Rx is connected to low-set undervoltage START signal. 0 = Rx is disconnected to low-set undervoltage START signal SxA.1 This switch element is to connect/disconnect the corresponding contact output Rx to low-set undervoltage (U <) TRIP signal. 1 = Rx is connected to low-set undervoltage TRIP signal. 0 = Rx is disconnected to low-set undervoltage TRIP signal.
  • 30. 29 SxA.2 This switch element is to connect/disconnect the corresponding contact output Rx to high-set undervoltage (U <<) START signal. 1 = Rx is connected to high-set undervoltage START signal. 0 = Rx is disconnected to high-set undervoltage START signal. SxA.3 This switch element is to connect/disconnect the corresponding contact output Rx to high-set undervoltage (U <<) TRIP signal. 1 = Rx is connected to high-set undervoltage TRIP signal. 0 = Rx is disconnected to high-set undervoltage sTRIP signal. SxA.4 This switch element is to connect/disconnect the corresponding contact output Rx to low-set overvoltage (U >) START signal. 1 = Rx is connected to low-set overvoltage START signal. 0 = Rx is disconnected to low-set overvoltage START signal. SxA.5 This switch element is to connect/disconnect the corresponding contact output Rx to low-set overvoltage (U >) TRIP signal. 1 = Rx is connected to low-set overvoltage TRIP signal. 0 = Rx is disconnected to low-set overvoltage TRIP signal. SxA.6 This switch element is to connect/disconnect the corresponding contact output Rx to high-set overvoltage (U >>) START signal. 1 = Rx is connected to high-set overvoltage start signal. 0 = Rx is disconnected to high-set overvoltage start signal. SxA.7 This switch element is to connect/disconnect the corresponding contact output Rx to high-set overvoltage (U >>) TRIP signal. 1 = Rx is connected to high-set overvoltage trip signal. 0 = Rx is disconnected to low-set overvoltage trip signal.
  • 31. 30 Soft Switch 1B to Soft Switch 5B These switches are for configuring the output contacts R1 to R5 in relation to low-set negative sequence overvoltage U2> and low-set residual overvoltage U0. For contact output R1 For contact output R2 S1B.7 S1B.6 S1B.5 S1B.4 S1B.3 S1B.2 S1B.1 S1B.0 Default setting 0 0 1 0 0 0 1 0 Default setting – hexadecimal value 2 2 User’s setting User’s setting – hexadecimal value S2B.7 S2B.6 S2B.5 S2B.4 S2B.3 S2B.2 S2B.1 S2B.0 Default setting 0 0 0 1 0 0 0 1 Default setting – hexadecimal value 1 1 User’s setting User’s setting – hexadecimal value For contact output R3 S3B.7 S3B.6 S3B.5 S3B.4 S3B.3 S3B.2 S3B.1 S3B.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value
  • 32. 31 For contact output R4 For contact output R5 S4B.7 S4B.6 S4B.5 S4B.4 S4B.3 S4B.2 S4B.1 S4B.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value S5B.7 S5B.6 S5B.5 S5B.4 S5B.3 S5B.2 S5B.1 S5B.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value SxB.0 This switch element is to connect/disconnect the corresponding contact output Rx to low-set residual overvoltage (U0 >) START signal. 1 = Rx is connected to low-set residual overvoltage start signal 0 = Rx is disconnected to low-set residual overvoltage start signal. SxB.1 This switch element is to connect/disconnect the corresponding contact output Rx to low-set residual overvoltage (U0 >) TRIP signal. 1 = Rx is connected to low-set residual overvoltage Rx is disconnected to low-set residual overvoltage signal. SxB.2 Not used. SxB.3 Not used. 0 =
  • 33. 32 0 = SxB.4 This switch element is to connect/disconnect the corresponding contact output Rx to low-set negative sequence overvoltage (U2 >) START signal. 1 = Rx is connected to low-set negative sequence overvoltage start signal. Rx is disconnected to low-set negative sequence overvoltage start signal SxB.5 This switch element is to connect/disconnect the corresponding contact output Rx to low-set negative sequence overvoltage (U2 >) TRIP signal. 1 = Rx is connected to low-set negative sequence overvoltage trip signal. 0 = Rx is disconnected to low-set negative sequence overvoltage trip signal. SxB.6 Not used. SxB.7 Not used.
  • 34. 33 S6A.7 S6A.6 S6A.5 S6A.4 S6A.3 S6A.2 S6A.1 S6A.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value Soft Switch 6A This switch is for setting the characteristic of output contacts R1 to R5 in relation to the START signal issued by the protection elements assigned to them by Switch1A to Switch5A or Switch1B to Switch5B above. These output contacts can be configured to be auto-reset type or manual- reset type. For auto-reset type, the output contacts will automatically return to the normal state upon removal of the condition which triggers the START signal. In the case of manual-reset type, the output contacts will latch on regardless of the condition which triggers the START signal until the relay is manually reset by the user by pressing the RESET/STEP key. Switch elements S6A.5 and S6A.6 are for configuring the START signals due to low-set/high-set undervoltage elements and low-set/high-set overvoltage elements respectively such that condition for a valid START signal to be effected on the output contacts R1 to R5 (if configured) can either be from any one phase or from the three phases which occur concurrently. S6A.0 This switch element configures the characteristic of output contact R1 in relation to START signal. 1 = Manual reset for R1. 0 = Auto reset for R1. S6A.1 This switch element configures the characteristic of output contact R2 in relation to START signal. 1 = Manual reset for R2. 0 = Auto reset for R2.
  • 35. 34 S6A.2 This switch element configures the characteristic of output contact R3 in relation to START signal. 1 = Manual reset for R3. 0 = Auto reset for R3. S6A.3 This switch element configures the characteristic of output contact R4 in relation to START signal. 1 = Manual reset for R4. 0 = Auto reset for R4. S6A.4 This switch element configures the characteristic of output contact R5 in relation to START signal. 1 = Manual reset for R5. 0 = Auto reset for R5. S6A.5 This switch element configures the START signal from low-set or high- set undervoltage elements for R1 to R5 above. 1 =All three phases of the low-set or high-set undervoltage elements must start concurrently for a valid START signal to be delivered to R1 to R5. 0 = Any single or more phases low-set or high-set undervoltage elements can trigger a valid START signal to R1 to R5. S6A.6 This switch element configures the START signal from low-set or high- set overvoltage elements for R1 to R5 above. 1 =All three phases of the low-set or high-set overvoltage elements must start concurrently for a valid START signal to be delivered to R1 to R5. 0 =Any single or more phases low-set or high-set overvoltage elements can trigger a valid START signal to R1 to R5. S6A.7 Not used.
  • 36. 35 S6B.7 S6B.6 S6B.5 S6B.4 S6B.3 S6B.2 S6B.1 S6B.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value Soft Switch 6B This switch is for setting the characteristic of output contacts R1 to R5 in relation to the TRIP signal issued by the protection elements assigned to them by Switch1A to Switch5A or Switch1B to Switch5B above. These output contacts can be configured to be auto-reset type or manual-reset type. For auto-reset type, the output contacts will automatically return to the normal state upon removal of the condition which triggers the TRIP signal. In the case of manual-reset type, the output contacts will latch on regardless of the condition which triggers the TRIP signal until the relay is manually reset by the user by pressing the RESET/STEP key. Switch elements S6B.5 and S6B.6 are for configuring the TRIP signals due to low-set/high-set undervoltage elements and low-set/high-set overvoltage elements respectively such that condition for a valid TRIP signal to be effected on the output contacts R1 to R5 (if configured) can either be from any one phase or from the three phases which occur concurrently. S6B.0 This switch element configures the characteristic of output contact R1 in relation to TRIP signal. 1 = Manual reset for R1. 0 = Auto reset for R1. S6B.1 This switch element configures the characteristic of output contact R2 in relation to TRIP signal. 1 = Manual reset for R2. 0 = Auto reset for R2.
  • 37. 36 S6B.2 This switch element configures the characteristic of output contact R3 in relation to TRIP signal. 1 = Manual reset for R3. 0 = Auto reset for R3. S6B.3 This switch element configures the characteristic of output contact R4 in relation to TRIP signal. 1 = Manual reset for R4. 0 = Auto reset for R4. S6B.4 This switch element configures the characteristic of output contact R5 in relation to TRIP signal. 1 = Manual reset for R5. 0 = Auto reset for R5. S6B.5 This switch element configures the TRIP signal from low-set or high-set undervoltage elements for R1 to R5 above. 1 =All three phases of the low-set or high-set undervoltage elements must TRIP concurrently for a valid TRIP signal to be delivered to R1 to R5. 0 =Any single or more phases low-set or high-set undervoltage elements can trigger a valid TRIP signal to R1 to R5. S6B.6 This switch element configures the TRIP signal from low-set or high-set overvoltage elements for R1 to R5 above. 1 =All three phases of the low-set or high-set overvoltage elements must TRIP concurrently for a valid TRIP signal to be delivered to R1 to R5. 0 =Any single or more phases low-set or high-set overvoltage elements can trigger a valid TRIP signal to R1 to R5. S6B.7 Not used.
  • 38. 37 S7.7 S7.6 S7.5 S7.4 S7.3 S7.2 S7.1 S7.0 Default setting 1 1 1 1 1 1 1 1 Default setting – hexadecimal value F F User’s setting User’s setting – hexadecimal value S7.0 Group A low-set undervoltage time delay setting. 1 = Inverse time 0 = Definite time S7.1 Group A low-set overvoltage time delay setting. 1 = Inverse time 0 = Definite time S7.2 Group A low-set negative sequence overvoltage time delay setting. 1 = Inverse time 0 = Definite time (Group A)(Group B) Soft Switch 7 This soft switch allows the user to choose between definite time setting and inverse time setting for the low-set undervoltage, low-set over- voltage, low-set negative sequence overvoltage and low-set residual overvoltage. There are two groups of settings available for the above protection elements namely, Group A and Group B. All of the settings can be individually set for either definite time or inverse time. Switch elements S7.0 to S7.3 are for Group A settings and S7.4 to S7.7 are for Group B settings.
  • 39. 38 S7.3 Group A low-set residual overvoltage time delay setting. 1 = Inverse time 0 = Definite time S7.4 Group B low-set undervoltage time delay setting. 1 = Inverse time 0 = Definite time S7.5 Group B low-set overvoltage time delay setting. 1 = Inverse time 0 = Definite time S7.6 Group B low-set negative sequence overvoltage time delay setting. 1 = Inverse time 0 = Definite time S7.7 Group B low-set residual overvoltage time delay setting. 1 = Inverse time 0 = Definite time
  • 40. 39 Soft Switch 8 This soft switch allows the user to enable or disable the high-set undervoltage, high-set overvoltage, low-set residual overvoltage and low- set negative sequence overvoltage for both Group A and Group B S8.7 S8.6 S8.5 S8.4 S8.3 S8.2 S8.1 S8.0 Default setting 1 1 1 1 1 1 1 1 Default setting – hexadecimal value F F User’s setting User’s setting – hexadecimal value S8.0 For enabling Group A high-set undervoltage element. 1 = Enabled 0 = Disabled S8.1 For enabling Group A high-set overvoltage element. 1 = Enabled 0 = Disabled S8.2 For enabling Group A low-set residual overvoltage 1 = Enabled 0 = Disabled S8.3 For enabling Group A low-set negative sequence overvoltage 1 = Enabled 0 = Disabled (Group B) (Group A)
  • 41. 40 S8.4 For enabling Group B high-set undervoltage element. 1 = Enabled 0 = Disabled S8.5 For enabling Group B high-set overvoltage element. 1 = Enabled 0 = Disabled S8.6 For enabling Group B low-set residual overvoltage 1 = Enabled 0 = Disabled S8.7 For enabling Group A low-set negative sequence overvoltage 1 = Enabled 0 = Disabled
  • 42. 41 Soft Switch 9A This switch is for configuring the function of the digital input. Only one selection is possible. S9A.7 S9A.6 S9A.5 S9A.4 S9A.3 S9A.2 S9A.1 S9A.0 Default setting 0 0 0 0 1 0 0 0 Default setting – hexadecimal value 0 8 User’s setting User’s setting – hexadecimal value S9A.0 The input is configured for switching between Group A setting and Group B setting. 1 = Selected. 0 = Not selected. S9A.1 The input is configured as remote trip reset input. 1 = Selected. 0 = Not selected. S9A.2 The input is configured as external tripping input source. 1 = Selected. 0 = Not selected. S9A.3 The input is configured as blocking input. 1 = Selected. 0 = Not selected.
  • 44. 43 Soft Switch 9B This switch will only function if switch element S9A.3 is set to 1 making the digital input as a blocking input. The switch elements of Switch 9B allow the user to individually select the blocking of low-set undervoltage, low-set overvoltage, low-set negative sequence overvoltage, low-set residual overvoltage, high-set undervoltage, and high-set overvoltage. S9B.7 S9B.6 S9B.5 S9B.4 S9B.3 S9B.2 S9B.1 S9B.0 Default setting 0 0 0 0 0 0 0 0 Default setting – hexadecimal value 0 0 User’s setting User’s setting – hexadecimal value S9B.0 Low-set undervoltage blocked. 1 = Block 0 = Unblock S9B.1 High-set undervoltage blocked. 1 = Block 0 = Unblock S9B.2 Low-set overvoltage blocked. 1 = Block 0 = Unblock S9B.3 High-set overvoltage blocked. 1 = Block 0 = Unblock
  • 45. 44 S9B.4 Low-set negative sequence overvoltage blocked. 1 = Block 0 = Unblock S9B.5 Low-set residual overvoltage blocked. 1 = Block 0 = Unblock S9B.6 Not used. S9B.7 Not used.
  • 46. 45 SA.7 SA.6 SA.5 SA.4 SA.3 SA.2 SA.1 SA.0 Default setting 0 0 0 0 0 0 0 1 Default setting – hexadecimal value 0 1 User’s setting User’s setting – hexadecimal value Soft Switch A This switch sets the voltage transformer (VT) configuration for MU2300. There are 4 possible VT configurations as shown in Examples 1 to 4 under the “Connection Diagram & Terminal Connection” section. It is important to choose the correct connection type failing which the wrong voltages will be measured or derived by MU2300. SA.0 This switch element is for selection of “3Vpn” configuration as shown in Example 1. In this configuration, the measured voltages are the phase-to- neutral voltage for the three phases. The phase-to-phase voltages and the residual voltage are derived internally. 1 = selected 0 = Not selected SA.1 This switch element is for selection of “3Vpn + Vo” configuration as shown in Example 2. In this configuration, the measured voltages are the phase-to-neutral voltage for the three phases and the residual overvoltage The phase-to-phase voltages are derived internally. 1 = selected 0 = Not selected
  • 47. 46 SA.2 This switch element is for selection of “3Vpp + Vo” configuration as shown in Example 3. In this configuration, the measured voltages are the phase-to-phase voltage for the three phases and the residual overvoltage. The phase-to-neutral voltages are not available. 1 = selected 0 = Not selected SA.3 This switch element is for selection of “2Vpp + Vo” configuration as shown in Example 4. In this configuration, the measured voltages are the 2 phase-to-phase voltages and the residual overvoltage. The third phase- to-phase voltage is derived internally and phase-to-neutral voltages are not available. 1 = selected 0 = Not selected SA.4 Not used. SA.5 Not used. SA.6 Not used. SA.7 Not used.
  • 48. 47 Soft Switch B This soft switch selects the baud rate and data format of the serial Modbus communication between the host computer (client) and the relay MU2300 (server). Digit 2 Digit 1 Default setting 4 7 User’s setting Digit 1 is for selecting the communication baud rate. Baud rate Value of Digit 1 300 1 600 2 1200 3 2400 4 4800 5 9600 6 19200 7 Digit 2 is for selecting the data format. Data format Value of Digit 2 1 start bit, 8 data bits, no parity bit, 1 stop bit 1 1 start bit, 8 data bits, no parity bit, 2 stop bits 2 1 start bit, 8 data bits, odd parity bit, 1 stop bit 3 1 start bit, 8 data bits, even parity bit, 1 stop bit 4
  • 49. 48 Soft Switch C This soft switch is for setting the device unit number of MU2300 in a Modbus communication network. The setting range for the device unit is from 1 to 127 and it is displayed and set in hexadecimal format. Example: If the selected unit number is 42, then the equivalent hexadecimal number is 2A. For conversation between hexadecimal number and decimal number, please refer to Appendix B. The default unit number is 1.
  • 50. 49 Soft Switch D This soft switch allows the user to either allow or disallow remote programming or changing of the setting values of the MU2300 relay. Once enabled, the remote host computer (client) is able to read and modify all the settings and parameters of the relay through the serial communication channel using Modbus protocol. Otherwise, only reading of the setting values and relay parameters is possible. 1 – Remote programming is enabled. 0 – Remote programming is disabled. The default setting for MU2300 is remote programming disabled (0).
  • 51. 50 Soft Switch E This switch allows the contacts output of MU2300 to be manually and individually switched on. This is very useful during testing and commissioning of the relay. Description Display Value Off all contact outputs 00 On contact output R1 only 01 On contact output R2 only 02 On contact output R3 only 03 On contact output R4 only 04 On contact output R5 only 05 Steps to turn on a contact: 1. Select soft switch E by pressing the SWITCH key. 2. Press PROGRAM key. 3. Press UP or DOWN key to select the desired contact. 4. Press SWITCH or PROGRAM key to exit. Note that all contacts will be switched OFF after the above test regardless of the previous status of the contact outputs prior to the test.
  • 52. 51 Soft Switch F This switch is for selecting the operation frequency of the electrical system to be protected. It is crucial that the correct frequency of operation be selected and failure to do so will give rise to wrong voltage measurements. 0 – 50Hz system frequency 1 – 60Hz system frequency
  • 53. 7.1 Terminal Connection Rear view of MU2300 52 7. Connection Diagram & Terminal Connection
  • 54. Connection terminal 1 2 3 4 5 6 7 8 9 10 11 12 13 External digital input 14 External digital input 15 to 21 Not used 22 Termination resistor (for RS485) 23 RS485 negative terminal 24 RS485 positive terminal 25 Communication cable shield 26,27 Output contact R5 28 N.C. contact for IRF 29 N.O. contact for IRF 30 COMMON contact for IRF 31 Casing earth terminal 32 Auxiliary supply input (No polarity) 33 Auxiliary supply input (No polarity) 34 N.C. contact for tripping contact R1 35 N.O. contact for tripping contact R1 36 COMMON contact for contact R1 37,38 Output contact R2 39,40 Output contact R3 41,42 Output contact R4 53 Not used Not used Not used Not used VT input for residual voltage VT input for residual voltage VT input for phase A VT input for phase A VT input for phase B VT input for phase B VT input for phase C VT input for phase C Description of Function
  • 60. 59 9. Technical Data i) Measuring Inputs Rated Voltage Input * 57-130V Frequency 50Hz or 60Hz ii) Rated Auxiliary supply voltage Model MU2300-150D 24~150V DC Model MU2300-240AD 85~265V AC 110~340V DC iii) Power Consumption 6-10VA typical (AC auxiliary voltage) 5-9W typical(DC auxiliary voltage) iv) External Digital Input 80~250V AC/DC *Maximum input voltage is 260V Output i) All contacts Rated voltage 250V AC Continuous carry 5A AC or DC Make and carry for 0.2 sec 30A AC or DC Expected electrical life (min operation) 5,000,000 Operating time Maximum 15ms Undervoltage element i) Low set Low set setting, U< 5-130V Low set definite time, tU< 0-600s Time multiplier, TMS 0.5-100 ii) High set High set setting, U<< 5-130V High set definite time, tU<< 0-600s iii) Hysteresis 105% Input
  • 61. 60 Overvoltage element i) Low set Low set setting, U> 5-200V Low set definite time, tU> 0-600s ii) High set High set setting, U>> 5-260V High set definite time, tU>> 0-600s iii) Time multiplier, TMS 0.5-100 Negative sequence overvoltage element i) Negetive sequence overvoltage setting, U2> 5-200V ii) Time multiplier, TMS 0.5-100 iii) Negative sequence overvoltage definite time, tU2> 0-600s Residual overvoltage element i) Residual overvoltage setting, U0> 0.5-130V ii) Time multiplier, TMS 0.5-100 iii) Residual overvoltage definite time tU0> 0-600s Communication i) Hardware interface Isolated RS485 ii) Protocol Modbus-RTU iii) Baud rate 300,600,1200,2400,4800, 9600,19200
  • 62. 61 10 Tests and Standards High voltage dielectric withstand test. IEC60255-5 …... 2.0kV rms, 1 min High voltage impulse test. IEC60255-5 ………….…….. 5kV, 1.2/50 s Electrical fast transient. IEC61000-4-4, Level 4, power supply inputs ………………………….... 4kV, 5/50ns Electrical fast transient. IEC61000-4-4, Level 4, other inputs …………..………………………... 2kV, 5/50ns Electrostatic discharge. IEC61000-4-2 Class III, air discharge ……………………………….…. 8kV Electrostatic discharge. IEC61000-4-2 Class III, contact discharge .………………….……….... 6kV Enclosure protection when panel mounted ……............ IP54 u
  • 63. Binary to hexadecimal- conversion table: - Hexadecimal Binary 0 0000 1 0001 2 0010 3 0011 4 0100 5 0101 6 0110 7 0111 8 1000 9 1001 A 1010 B 1011 C 1100 D 1101 E 1110 F 1111 Decimal 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 62 11 Appendix A
  • 64. Decimal to Hexadecimal Conversation Decimal Hexadecimal Decimal Hexadecimal Decimal Hexadecimal 1 1 44 2C 87 57 2 2 45 2D 88 58 3 3 46 2E 89 59 4 4 47 2F 90 5A 5 5 48 30 91 5B 6 6 49 31 92 5C 7 7 50 32 93 5D 8 8 51 33 94 5E 9 9 52 34 95 5F 10 A 53 35 96 60 11 B 54 36 97 61 12 C 55 37 98 62 13 D 56 38 99 63 14 E 57 39 100 64 15 F 58 3A 101 65 16 10 59 3B 102 66 17 11 60 3C 103 67 18 12 61 3D 104 68 19 13 62 3E 105 69 20 14 63 3F 106 6A 21 15 64 40 107 6B 22 16 65 41 108 6C 23 17 66 42 109 6D 24 18 67 43 110 6E 25 19 68 44 111 6F 26 1A 69 45 112 70 27 1B 70 46 113 71 28 1C 71 47 114 72 29 1D 72 48 115 73 30 1E 73 49 116 74 31 1F 74 4A 117 75 32 20 75 4B 118 76 33 21 76 4C 119 77 34 22 77 4D 120 78 35 23 78 4E 121 79 36 24 79 4F 122 7A 37 25 80 50 123 7B 38 26 81 51 124 7C 39 27 82 52 125 7D 40 28 83 53 126 7E 41 29 84 54 127 7F 42 2A 85 55 43 2B 86 56 63 12 Appendix B
  • 65. 64 13 Appendix C Event code: Event code Description 00 U1P/U12 undervoltage U < start 01 U2P/U23 undervoltage U < start 02 U3P/U31 undervoltage U < start 03 U1P/U12 undervoltage U < trip 04 U2P/U23 undervoltage U < trip 05 U3P/U31 undervoltage U < trip 06 U1P/U12 undervoltage U << start 07 U2P/U23 undervoltage U << start 08 U3P/U31 undervoltage U << start 09 U1P/U12 undervoltage U << trip 10 U2P/U23 undervoltage U << trip 11 U3P/U31 undervoltage U << trip 40 U1P/U12 undervoltage U < start reset 41 U2P/U23 undervoltage U < start reset 42 U3P/U31 undervoltage U < start reset 43 U1P/U12 undervoltage U < trip reset 44 U2P/U23 undervoltage U < trip reset 45 U3P/U31 undervoltage U < trip reset 46 U1P/U12 undervoltage U << start reset 47 U2P/U23 undervoltage U << start reset 48 U3P/U31 undervoltage U << start reset 49 U1P/U12 undervoltage U << trip reset 50 U2P/U23 undervoltage U << trip reset 51 U3P/U31 undervoltage U << trip reset 12 U1P/U12 overvoltage U > start 13 U2P/U23 overvoltage U > start 14 U3P/U31 overvoltage U > start 15 U1P/U12 overvoltage U > trip 16 U2P/U23 overvoltage U > trip 17 U3P/U31 overvoltage U > trip 18 U1P/U12 overvoltage U >> start
  • 66. 65 19 U2P/U23 overvoltage U >> start 20 U3P/U31 overvoltage U >> start 21 U1P/U12 overvoltage U >> trip 22 U2P/U23 overvoltage U >> trip 23 U3P/U31 overvoltage U >> trip 52 U1P/U12 overvoltage U > start reset 53 U2P/U23 overvoltage U > start reset 54 U3P/U31 overvoltage U > start reset 55 U1P/U12 overvoltage U > trip reset 56 U2P/U23 overvoltage U > trip reset 57 U3P/U31 overvoltage U > trip reset 58 U1P/U12 overvoltage U >> start reset 59 U2P/U23 overvoltage U >> start reset 60 U3P/U31 overvoltage U >> start reset 61 U1P/U12 overvoltage U >> trip reset 62 U2P/U23 overvoltage U >> trip reset 63 U3P/U31 overvoltage U >> trip reset 24 Negative sequence overvoltage U2 > start 25 Negative sequence overvoltage U2 > trip 64 Negative sequence overvoltage U2 > start reset 65 Negative sequence overvoltage U2 > trip reset 26 Residual overvoltage U0 > start 27 Residual overvoltage U0 > trip 66 Residual overvoltage U0 > start reset 67 Residual overvoltage U0 > trip reset A0 R1 activated A1 R1 reset A2 R2 activated A3 R2 reset A4 R3 activated A5 R3 reset A6 R4 activated A7 R4 reset
  • 67. 66 A8 R5 activated A9 R5 reset B1 Digital input activated B2 Digital input reset E1 Tripped by external digital input FE Relay is powered up