3. INTRODUCTION
Fast acting static exciters with high ceiling voltages
coupled with high gain AVRs can improve transient
stability.
However they can also result in oscillatory instability by
negative damping of low frequency rotor oscillations.
4. CONTINUE…
Power System Stabilizers (PSS) with control inputs derived from rotor
speed, power or terminal frequency are used to modulate the generator
voltage and damp oscillations.
The application of PSS does not result in improvement of transient
stability.
The improvement in transient stability can be achieved by the
provision of discrete signals to control excitation during a
transient disturbance.
5. DETAILED INFORMATION
Ontario Hydro has developed a scheme where a signal
proportional to the rotor angle is used (during the transient
period) in addition to the terminal voltage and rotor speed
signals.
The rotor angle signal cannot be used continuously as
it results in dynamic instability.
7. OPERATION
The angle signal is derived by integrating the speed signal used as i/p signal
to PSS as shown in figure.
The angle signal is generated during a transient disturbance by closing the
switch S when there is a sudden drop in terminal voltage followed by the
rise in rotor speed above a preset value.
The relay contact S is opened when the speed drops below the preset level
or the exciter comes out of saturation.
8. CONTINUE…
The output of the integrator will then decay exponentially with time
constant T.
The value of this constant is chosen such that the output is
proportional to the rotor angle for the relevant oscillation
frequencies.
The effect of the discrete control is to maintain the field voltage and
consequently the terminal voltage at a high level during the positive
swing in the rotor angle.
9. CONTINUE…
However, the terminal voltage is limited to 1.15 pu.
From studies carried out, the discrete control of excitation
was found to be as effective as fast valving scheme in a
particular application where the interarea mode dominates
over local modes.
This rise in terminal voltage of 1.15 p.u. lasts for 1 sec.
affects step-up transformers & UATs.
11. ADVANTAGES
The problem associated with PSS of reduction in excitation
because of negative rotor speed deviation is overcome by
this method.
Alternative schemes give priority to improve the first swing
transient stability just after a large disturbance occurred.
It helps in damping post fault trajectories.
Provides max. field voltage when desired.
12. CONCLUSION
Discrete control of excitation system during transient
disturbance improves the transient stability of the power
system.
It maintain field voltage & as a result terminal voltage at
high values during +ve swing in rotor angle.
Protections in various parts of the system have to be
modified.