Publication
88CR2015
Please Contact Technical Support At 203-736-8890 With Any Additional Questions
Please Be Prepared To Provide Pump Serial Number During Call
Page
1 of 3
 
 
 
 
3-Phase Power Unbalance 
 
 
HOMA Submersible Motors will operate successfully with all three lines of the
supply voltage within + 10% of the nameplate rating. However, the slightest (1%)
unbalance in voltage between any of the three supply lines (phases) will cause a
significantly higher percentage of current unbalance within the motor. This
current unbalance is in the order of 6 to 10 times the measured voltage
unbalance. Further to the problem, some of this excessively high current is the
form of circulating currents within the stator, therefore, not readable at the control
box. The generation of these circulating current is best defined as follows:
 
From NEMA MG-1 part14, Page 11
“ The effect of unbalanced voltages on polyphase induction motors is
equivalent to the introduction of a “negative sequence voltage” having
a rotation opposite to that occurring with the balanced voltages. This
negative sequence voltage produces in the air gap a flux rotating
against the rotation of the rotor, tending to produce high currents. A
small negative sequence voltage may produce in the windings
currents considerably in excess of those present under balanced
conditions.”
 
Temperature rise within the stator windings will be proportional to the actual (not
measured) current imbalance. The increased heat should cause the winding
thermal sensors to react and shutdown the motor, provided the thermal sensors
are properly wired and the alarm is not overridden. However, continued
operation of the motor at elevated temperatures will lead to a breakdown of the
winding insulation. In addition, continued cyclic operation of thermal switches will
cause a decay of their set temperature, and may ultimately lead to their failure.
 
While the voltage unbalance has considerable effect on the stator winding,
problems will also arise within the shaft/rotor assembly. Induced circulating
current will cause the rotor to heat up. This may cause the rotor to expand, and
excessive heat will be directly transferred to the motor bearings and mechanical
seals through the shaft.
Publication
88CR2015
Please Contact Technical Support At 203-736-8890 With Any Additional Questions
Please Be Prepared To Provide Pump Serial Number During Call
Page
2 of 3
 
 
 
The percentage of voltage unbalance is commonly defined as:
	
	 	 % 100	 	
Vp	 Peak	Deviation	from	Average	Voltage
Va	 Average	Measured	Voltage
	
 
Ex. If the measured voltages are L1 = 452, L2 = 462, & L3 = 466, then the
average voltage (Va) is 460. The peak deviation from average (Vp) is 8, and the
percent voltage unbalance is:
	 	100	 	
8
460
1.47%	
 
The percentage of current unbalance is commonly defined as:
	 	 % 100	 	
Ip	 Peak	Deviation	from	Average	Current
Ia	 Average	Measured	Current
 
Ex. If the measured currents are L1 = 56.3 amps, L2 = 51.1 amps, & L3 = 58.7
amps, then the average current (Ia) is 55.36 amps. The peak deviation from
average (Ip) is 4.26 amps, and the percent current unbalance is:
	 	 % 100	 	
4.26
55.36
7.69%	
Measured current unbalance should not exceed (5%), and is generally due to
voltage unbalance in the supply. To determine if unbalance is coming from the
load or the source, use the following procedure.
1. Measure and record voltage on each power lead. (L1, L2, L3)
2. Change all three power leads as follows: L1 to L2, L2 to L3, L3 to L1.
3. Measure and record voltage on each lead again. (L1, L2, L3)
4. If the unbalanced leg follows the motor lead, then a problem exists
somewhere within the pump cable, connections, or stator winding.
5. If the unbalanced leg stays on the same control box terminal, and
jumps to a different pump lead number, then the problem is with the
supply or control box.
 
If the voltage unbalance is found to be with the supply, then it must be:
1. Corrected by inspection and repair control box wiring or components.
2. Corrected by working with the power company.
3. Reduced by decreasing the load on the motor.
4. Compensated for with an oversized motor to handle the additional heat
energy.
Publication
88CR2015
Please Contact Technical Support At 203-736-8890 With Any Additional Questions
Please Be Prepared To Provide Pump Serial Number During Call
Page
3 of 3
 
 
 
 
 
IMPORTANT: ANY VOLTAGE UNBALANCE WILL CAUSE ADDITIONAL HEAT
BUILDUP WITHIN THE MOTOR. THE DEGREE OF PROBLEMS AND/OR
DAMAGE WILL BE A FUNCTION OF THE VOLTAGE UNBALANCE AND THE
LOAD FACTOR OF THE MOTOR.
 
As a minimum, nuisance thermal tripping will occur. If this goes unchecked, the
following mechanical damage may occur.
 
Bearings - Grease will be melted out of upper bearing. Bearing will often
look dry.
Stator - Winding insulation will breakdown, ultimately causing a short in
the winding.
Rotor – May expand enough to contact the stator assembly. Will often be
blue in color due to the heat.
Upper Mechanical Seal – Elastomers will be hard and brittle from heat
exposure. Seal faces will often have heat checking them.
 
Continued operation of any pump with a significant (over 1%) voltage unbalance
will make the above list of damage a certainty at some point in the motors life.

More Related Content

What's hot

Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapilKapil Kantia
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protectionNischal Popat
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipmentsateesh kumar
 
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...dharmesh nakum
 
Single phasing of three phase induction motor
Single phasing of three phase induction motorSingle phasing of three phase induction motor
Single phasing of three phase induction motorJUNAID SK
 
Metering and protection
Metering and protectionMetering and protection
Metering and protectionDebashis Paul
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysiskirkusawi
 
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014Sheikh Imran
 
Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...
Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...
Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...Edgefxkits & Solutions
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic conceptsmichaeljmack
 
Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applicationselprocus
 
Parallel Operation on Alternators.
Parallel Operation on Alternators.Parallel Operation on Alternators.
Parallel Operation on Alternators.R-One Power
 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Insanul Aziz
 
Power Point Presentation For Symcom 2012
Power Point Presentation For Symcom 2012Power Point Presentation For Symcom 2012
Power Point Presentation For Symcom 2012Steve Johnson
 

What's hot (20)

Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapil
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protection
 
Project PPT
Project PPTProject PPT
Project PPT
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipment
 
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
 
Single phasing of three phase induction motor
Single phasing of three phase induction motorSingle phasing of three phase induction motor
Single phasing of three phase induction motor
 
Metering and protection
Metering and protectionMetering and protection
Metering and protection
 
Electric Fan
Electric FanElectric Fan
Electric Fan
 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
 
Industrial control motor overload protection
Industrial control motor overload protectionIndustrial control motor overload protection
Industrial control motor overload protection
 
Motor Protection
Motor ProtectionMotor Protection
Motor Protection
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
Diwan Annexure Starter panels Presentation Rev-1 Dt16-11-2014
 
Vk
VkVk
Vk
 
Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...
Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...
Automatic Star Delta Starter Using Relays And Adjustable Electronic Timer For...
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic concepts
 
Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applications
 
Parallel Operation on Alternators.
Parallel Operation on Alternators.Parallel Operation on Alternators.
Parallel Operation on Alternators.
 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14
 
Power Point Presentation For Symcom 2012
Power Point Presentation For Symcom 2012Power Point Presentation For Symcom 2012
Power Point Presentation For Symcom 2012
 

Similar to 3 phase power unbalance

Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.javid iqbal sodagar
 
Electrical engineering-portal.com-why does electric motor fail and what can y...
Electrical engineering-portal.com-why does electric motor fail and what can y...Electrical engineering-portal.com-why does electric motor fail and what can y...
Electrical engineering-portal.com-why does electric motor fail and what can y...Daniel García
 
Starting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motorsStarting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motorsmorin moli
 
Unbalanced Voltage Impacts and its Analysis on an Induction Motor
Unbalanced Voltage Impacts and its Analysis on an Induction MotorUnbalanced Voltage Impacts and its Analysis on an Induction Motor
Unbalanced Voltage Impacts and its Analysis on an Induction MotorIRJET Journal
 
IRJET- Power Quality and Harmonic Distortion
IRJET-  	  Power Quality and Harmonic DistortionIRJET-  	  Power Quality and Harmonic Distortion
IRJET- Power Quality and Harmonic DistortionIRJET Journal
 
Design turbo generator
Design turbo generatorDesign turbo generator
Design turbo generatorMolla Morshad
 
Equipment protection
Equipment protectionEquipment protection
Equipment protectionSlides Hub
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Groundingmichaeljmack
 
Effect of voltage sag and voltage unbalance on induction motor drives
Effect of voltage sag and voltage unbalance on induction motor drivesEffect of voltage sag and voltage unbalance on induction motor drives
Effect of voltage sag and voltage unbalance on induction motor drivesIJARIIT
 

Similar to 3 phase power unbalance (20)

Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
2435544 a w
2435544 a w2435544 a w
2435544 a w
 
(7) overfluxing
(7) overfluxing(7) overfluxing
(7) overfluxing
 
Electrical engineering-portal.com-why does electric motor fail and what can y...
Electrical engineering-portal.com-why does electric motor fail and what can y...Electrical engineering-portal.com-why does electric motor fail and what can y...
Electrical engineering-portal.com-why does electric motor fail and what can y...
 
Starting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motorsStarting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motors
 
WIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUESWIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUES
 
Unbalanced Voltage Impacts and its Analysis on an Induction Motor
Unbalanced Voltage Impacts and its Analysis on an Induction MotorUnbalanced Voltage Impacts and its Analysis on an Induction Motor
Unbalanced Voltage Impacts and its Analysis on an Induction Motor
 
IRJET- Power Quality and Harmonic Distortion
IRJET-  	  Power Quality and Harmonic DistortionIRJET-  	  Power Quality and Harmonic Distortion
IRJET- Power Quality and Harmonic Distortion
 
Design turbo generator
Design turbo generatorDesign turbo generator
Design turbo generator
 
(9) limitations
(9) limitations(9) limitations
(9) limitations
 
Gymr motor starting_solutions
Gymr motor starting_solutionsGymr motor starting_solutions
Gymr motor starting_solutions
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Equipment protection
Equipment protectionEquipment protection
Equipment protection
 
Chap16 254-279
Chap16 254-279Chap16 254-279
Chap16 254-279
 
Mech EE6365 EE lab_manual
Mech EE6365 EE lab_manualMech EE6365 EE lab_manual
Mech EE6365 EE lab_manual
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Grounding
 
Internship presentation
Internship presentationInternship presentation
Internship presentation
 
Motor starter
Motor starterMotor starter
Motor starter
 
Effect of voltage sag and voltage unbalance on induction motor drives
Effect of voltage sag and voltage unbalance on induction motor drivesEffect of voltage sag and voltage unbalance on induction motor drives
Effect of voltage sag and voltage unbalance on induction motor drives
 

Recently uploaded

Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxfenichawla
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 

Recently uploaded (20)

Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 

3 phase power unbalance

  • 1. Publication 88CR2015 Please Contact Technical Support At 203-736-8890 With Any Additional Questions Please Be Prepared To Provide Pump Serial Number During Call Page 1 of 3         3-Phase Power Unbalance      HOMA Submersible Motors will operate successfully with all three lines of the supply voltage within + 10% of the nameplate rating. However, the slightest (1%) unbalance in voltage between any of the three supply lines (phases) will cause a significantly higher percentage of current unbalance within the motor. This current unbalance is in the order of 6 to 10 times the measured voltage unbalance. Further to the problem, some of this excessively high current is the form of circulating currents within the stator, therefore, not readable at the control box. The generation of these circulating current is best defined as follows:   From NEMA MG-1 part14, Page 11 “ The effect of unbalanced voltages on polyphase induction motors is equivalent to the introduction of a “negative sequence voltage” having a rotation opposite to that occurring with the balanced voltages. This negative sequence voltage produces in the air gap a flux rotating against the rotation of the rotor, tending to produce high currents. A small negative sequence voltage may produce in the windings currents considerably in excess of those present under balanced conditions.”   Temperature rise within the stator windings will be proportional to the actual (not measured) current imbalance. The increased heat should cause the winding thermal sensors to react and shutdown the motor, provided the thermal sensors are properly wired and the alarm is not overridden. However, continued operation of the motor at elevated temperatures will lead to a breakdown of the winding insulation. In addition, continued cyclic operation of thermal switches will cause a decay of their set temperature, and may ultimately lead to their failure.   While the voltage unbalance has considerable effect on the stator winding, problems will also arise within the shaft/rotor assembly. Induced circulating current will cause the rotor to heat up. This may cause the rotor to expand, and excessive heat will be directly transferred to the motor bearings and mechanical seals through the shaft.
  • 2. Publication 88CR2015 Please Contact Technical Support At 203-736-8890 With Any Additional Questions Please Be Prepared To Provide Pump Serial Number During Call Page 2 of 3       The percentage of voltage unbalance is commonly defined as: % 100 Vp Peak Deviation from Average Voltage Va Average Measured Voltage   Ex. If the measured voltages are L1 = 452, L2 = 462, & L3 = 466, then the average voltage (Va) is 460. The peak deviation from average (Vp) is 8, and the percent voltage unbalance is: 100 8 460 1.47%   The percentage of current unbalance is commonly defined as: % 100 Ip Peak Deviation from Average Current Ia Average Measured Current   Ex. If the measured currents are L1 = 56.3 amps, L2 = 51.1 amps, & L3 = 58.7 amps, then the average current (Ia) is 55.36 amps. The peak deviation from average (Ip) is 4.26 amps, and the percent current unbalance is: % 100 4.26 55.36 7.69% Measured current unbalance should not exceed (5%), and is generally due to voltage unbalance in the supply. To determine if unbalance is coming from the load or the source, use the following procedure. 1. Measure and record voltage on each power lead. (L1, L2, L3) 2. Change all three power leads as follows: L1 to L2, L2 to L3, L3 to L1. 3. Measure and record voltage on each lead again. (L1, L2, L3) 4. If the unbalanced leg follows the motor lead, then a problem exists somewhere within the pump cable, connections, or stator winding. 5. If the unbalanced leg stays on the same control box terminal, and jumps to a different pump lead number, then the problem is with the supply or control box.   If the voltage unbalance is found to be with the supply, then it must be: 1. Corrected by inspection and repair control box wiring or components. 2. Corrected by working with the power company. 3. Reduced by decreasing the load on the motor. 4. Compensated for with an oversized motor to handle the additional heat energy.
  • 3. Publication 88CR2015 Please Contact Technical Support At 203-736-8890 With Any Additional Questions Please Be Prepared To Provide Pump Serial Number During Call Page 3 of 3           IMPORTANT: ANY VOLTAGE UNBALANCE WILL CAUSE ADDITIONAL HEAT BUILDUP WITHIN THE MOTOR. THE DEGREE OF PROBLEMS AND/OR DAMAGE WILL BE A FUNCTION OF THE VOLTAGE UNBALANCE AND THE LOAD FACTOR OF THE MOTOR.   As a minimum, nuisance thermal tripping will occur. If this goes unchecked, the following mechanical damage may occur.   Bearings - Grease will be melted out of upper bearing. Bearing will often look dry. Stator - Winding insulation will breakdown, ultimately causing a short in the winding. Rotor – May expand enough to contact the stator assembly. Will often be blue in color due to the heat. Upper Mechanical Seal – Elastomers will be hard and brittle from heat exposure. Seal faces will often have heat checking them.   Continued operation of any pump with a significant (over 1%) voltage unbalance will make the above list of damage a certainty at some point in the motors life.