VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-56
www.viva-technology.org/New/IJRI
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING
DPFC
Ms. Deepali Chavan1
, Ms. Dipali Hadal2
, Ms. Sfurti Raut3
, Prof. Kavita Mhaskar 4
1
(Department of Electrical Engineering, Viva Institute of Technology, India)
2
(Department of Electrical Engineering, Viva Institute of Technology, India)
3
(Department of Electrical Engineering, Viva Institute of Technology, India)
4
(Department of Electrical Engineering, Viva Institute of Technology, India)
Abstract : This project presents the MATLAB Simulation model of the Distributed Power Flow Controller in Transmission line. This
work will be a new component with the flexible ac transmission system, called as distributed power flow controller (DPFC). The
DPFC will be derived from the unified power flow controller system (UPFC). The DPFC can be considered as a UPFC with a common
dc link which is eliminated. The active power exchange between the series and shunt converters, through the common dc link in the
UPFC, is now through the transmission lines at the third-harmonic frequency. DPFC has the same control ability as the UPFC, which
adjusts line impedance, bus voltages, and the transmission lines.
Keywords : AC/DC converters, DPFC, MATLAB, Power electronics, Power flow controller, Third harmonic frequency,
Transmission line parameters control.
I. INTRODUCTION
The aging of networks and increasing demand make it desirable for power flow, to control the power transmission system
reliable and fast to the flexible ac transmission system, which is the application of power electronics in transmission system. The main
aim of this technology is to regulate and control the electric variables in the power system.
The DPFC is the new concept. It is the advance version of the UPFC (Unified Power Flow Controller). The Distributed power
flow controller is derived from the Unified Power Flow Controller (UPFC). The DPFC can be compared to a UPFC with an eliminated
common dc link. The active power ex-change between the series and shunt converters, which is through the common dc link in the
UPFC, is now through the transmission lines at the third-harmonic frequency. The DPFC employs the distributed FACTS (D-FACTS)
concept, which is used for multiple small-size single phase converters instead of the one large-size three phase series converter in the
UPFC. The multiple number of series converters provides redundancy, thereby increasing the system reliability. As the Distributed
FACTS converters are single phase and floating with respect to the ground, there is no high voltage isolation required between the
phases. According to this, the cost of the DPFC system is lower than the UPFC. The DPFC and UPFC has same control capabilities,
which comprises the adjustment of the line impedance, the bus voltages and, the transmission angle.
Advantages of the DPFC over UPFC:
The DPFC can be considered as a UPFC that employs the Distributed FACTS concept and the concept of exchanging power through
harmonic. Therefore, the DPFC inherits all the advantages of the UPFC and the Distributed FACTS, which are as follows.
1) High control capability
The DPFC can simultaneously control all the parameters of the power system: the line impedance, the bus voltages and, the
transmission angle, the elimination of the common dc link enables separated installation of the DPFC converters. The series and
shunt converters can be placed at the most effectively location. Due to the high control capability, the DPFC can also be used to
VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-57
www.viva-technology.org/New/IJRI
improve the power quality and system stability, such as low-frequency power oscillation damping, restoration the voltage sag,
or balancing asymmetry.
2) High reliability
The redundancy of the series converter improves reliability. In addition, the series and shunt converters are independent, and
the failure at one place will not influence to the other converters. In the series converter when a failure occurs, the converter will
be short circuited by bypass protection, thereby having little impact to the network. In the case of failure in the shunt converter,
the shunt converter will trip and the series converter will stop providing active compensation and will act as the Distributed
FACTS controller.
3) Low cost
There is no phase-to-phase voltage isolation required by the series converter, and also, the power rating of each converter is
small and can be easily produced in series production lines.
II. DPFC OPERATING PRINCIPLE
2.1Active power exchange with eliminated DC link
Within the Distributed power flow controller, the transmission line presents a common connection between the AC ports of
the series and the shunt converters. Therefore, it can exchange active power through the AC ports. This purpose is based on power
theory of non-sinusoidal components. According to the Fourier system analysis, non-sinusoidal voltage and current can be derived as
the sum of sinusoidal functions in different amplitudes with different frequencies. The active power resulting from this non-sinusoidal
current and voltage is defined as the mean value of the product of current and voltage. Due to the integrals of all the cross terms with
various frequencies are zero, produced active power can be expressed as,
P = 𝑣𝐼 𝑖𝐼 cos ∅𝐼 (1)
By applying this method to the Distributed Power Flow Controller, the shunt converter can absorb active power from the
grid at the fundamental frequency and inject the power back at a harmonic frequency. This active power harmonics flows through a
transmission line supplied with series converters. According to the required active power at the fundamental frequency, the DPFC
series converters generate a voltage at the harmonic frequency, therefore it actives power from harmonic components. Neglecting
losses, the active power generated at the fundamental frequency is equal to the absorbed power at the harmonic frequency.
2.2 Using third harmonic components
Due to the unique features of third harmonic frequency components in a three-phase system, the 3rd harmonic is applied for
active power exchange in the DPFC. In a three-phase system, the third harmonic in each phase is identical, which means they are
“Zero Sequences” components. Because the zero-sequence harmonic can be blocked by star-delta transformers and these are widely
absorbed in power systems, as there is no extra filter required to prevent harmonic leakage.
Figure 1: Active power exchange between DPFC converters
VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-58
www.viva-technology.org/New/IJRI
III. DPFC CONTROL
To control small size multiple converters, a DPFC consists of three types of controllers: central control, shunt control and
series control, the series and shunt control are localized controllers and are responsible for maintaining their own converters
parameters. The central control satisfies the DPFC functions at the power system level. The function of each controller is listed:
• Central control
The central control generates the reference signals for both the series and shunt converters of the DPFC. It controls function
of DPFC which depends on the specifics of the DPFC application at the power system level, such as power flow control, low frequency
power oscillation damping and balancing of asymmetrical components. According to the requirements, the central control gives
voltage reference signals for the series converters and reactive current signal for the shunt converter. All the reference signals generated
by the central control bothered the fundamental frequency components.
• Series control
Each converter of series has its own series control. The series controller is used to maintain the DC capacitor voltage of its
own converter, by using 3rd harmonic frequency components. The central control is required by additional to the generating series
voltage at the fundamental frequency.
• Shunt control
The objective of the shunt control is to inject a constant third harmonic current into the line to supply active power for the
series converters. At the same moment, it maintains the capacitor DC voltage of the shunt converter at a constant value from the grid
at the fundamental frequency by absorbing active power and injecting the reactive current at the fundamental frequency into the grid.
IV. ANALYSIS OF DPFC
In this steady-state behaviour of the DPFC is analysed, and the control capability of the DPFC is expressed in the parameters
of the network and the DPFC.
Figure 2: DPFC configuration
VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-59
www.viva-technology.org/New/IJRI
4.1 Fundamental frequency circuit
To simplify the distributed power flow controller (DPFC), the converters are replaced by controllable voltage sources in
series with impedance. Since at two different frequencies, each converter generates the voltage, it is represented by two series
connected controllable voltage sources, one at the fundamental frequency and the other at the third harmonic frequency. Assuming
that the transmission lines and the converters are lossless, the total active power generated by the two frequency voltage sources will
be zero. The small size multiple series converters are simplified as one large. In fig 3 a) Fundamental frequency circuit is shown.
In Fig, the DPFC is placed in a two-bus system with the sending end voltages and the receiving end voltages Vs and Vr, respectively.
The transmission line system is represented by an inductance L with the line current I. The injected voltages by all the DPFC series
converters are Vse,1 and Vse,3 at the fundamental and the third harmonic frequency, respectively. The shunt converter is connected
to the sending end bus through the inductor Lsh and generates the voltage Vsh,1 and Vsh,3; the injected current by the shunt converter
is Ish. The active power and reactive power flow at the receiving end are Pr and Qr, respectively.
This representation consists of both the third harmonics frequency and fundamental frequencies components. Based on the
superposition theorem, the circuit in Fig can be further simplified by being separated into two circuits at different frequencies. The
two circuits are isolated from each other, and the link the power flow control capability of the DPFC can be illustrated by the active
power Pr and reactive power Qr received at the receiving end. Due to these the DPFC circuit at the fundamental frequency behaves
the same as the UPFC, the active and reactive power flow can be derived as follows:
(Pr - Pro)2
+(Qr - Qro)2
= (
|𝑉||𝑉𝑆𝑒,1|
𝑋1
)
2 (2)
Pse,1 = Re (Vse,1 I1
*
) =
𝑋1
|𝑉𝑟|2
|𝑆𝑟||𝑆𝑟0| sin(𝜑𝑟0 − 𝜑𝑟) (3)
Fig, illustrates the relationship between Pse,1 and the power flow at the receiving end at a certain power angle θ. Consequently, the
series converter at the required active power can be written as follows:
Pse,1 = CA (o, r0, r) (4)
According to the Fig, the relationship between the power flow control range and the maximum active power requirement can be
represented by:
Pse,1, max =
|𝑋1||𝑆𝑟0|
|𝑉𝑟|2 |𝑆𝑟,𝑐| (5)
Figure 3: DPFC equivalent circuit a)Fundamental
VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-60
www.viva-technology.org/New/IJRI
Where |Sr, c | is the control range of the Distributed power flow controller
At the same time each converter in the DPFC generates two frequency voltages. According to these, the voltage rating of each
converter should be the sum of the maximum voltage of the two frequencies component.
Vse, max = |𝑉𝑠𝑒,1,𝑚𝑎𝑥| + |𝑉𝑠𝑒,3,𝑚𝑎𝑥| (6)
During the operation, the active power requirement of the series converter varies with the injected voltage at the fundamental
frequency. When it is low required, the series voltage at the third harmonic frequency will be smaller than |Vse, 3, max|. This potential
voltage which is in between Vse,3 and |Vse,3, max| can be used to control the power flow at the fundamental frequency, thereby
increasing the power flow control region of the DPFC. When Sr, c is perpendicular to the uncompensated power Sr0, the maximum
active power required by series converters, and the radius of the DPFC control region is given by:
|𝑆𝑟,𝑐| =
|𝑉𝑟||𝑉𝑠𝑒,1,𝑚𝑎𝑥|
𝑋1
(7)
If Sr,c is in the same line as Sr0 , the series converters only provide the reactive compensation and the boundary of the DPFC control
region will extended to:
|𝑆𝑟,𝑐| =
|𝑉𝑟|(|𝑉𝑠𝑒,1,𝑚𝑎𝑥|+|𝑉𝑠𝑒,3,𝑚𝑎𝑥|)
𝑋1
=
|𝑉𝑟||𝑉𝑠𝑒,𝑚𝑎𝑥|
𝑋1
(8)
4.2 Third harmonic frequency circuit
The 3rd harmonic component within the DPFC system is used to exchange active and reactive power between the shunt and
series converters. In fig 3 b) Third harmonic frequency circuit shown. Therefore, the voltages and currents at the 3rd harmonic
frequency are related to the required active power at the fundamental frequency. For the series converters, there is:
(Vse,3I3
*
) = -Pse,1 (9)
Absorbed power by the series converters at the third harmonic frequency is given by:
Pse,3 + jQse,3 = Vse,3I3
*
= Vsh,3(
𝑉𝑠ℎ,3−𝑉𝑠𝑒,3
𝑋3
, )
∗
(10)
Where X′3 = X3 + Xsh,3. By splitting the real and imaginary parts, the absorbed active and reactive power at 3rd harmonic frequency
can be expressed as:
Figure 4: DPFC Power flow control range
VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-61
www.viva-technology.org/New/IJRI
Pse,3 =
|𝑉𝑠𝑒,3||𝑉𝑠ℎ,3|
𝑋3
, sin 𝜃3
Qse,3 =
|𝑉𝑠𝑒,3|
𝑋3
, (|𝑉𝑠ℎ,3| cos 𝜃3 − |𝑉𝑠𝑒,3|)
(11)
Although here θ3 is the phase angle difference between the voltages Vsh,3 and Vse,3. For the series converters, any of the reactive
power at the third harmonic frequency results in unnecessary extra currents and voltages. Therefore, the reactive power flowing
through the series converters at the third harmonic frequency is controlled to be zero, which is Qse,3 = 0. It shows that the relationship
between the voltages Vsh,3 and Vse,3 is:
|𝑉𝑠𝑒,3| = |𝑉𝑠ℎ,3| cos 𝜃3
Pse,3 =
|𝑉𝑠ℎ,3|
𝑋3
, cos 𝜃3 sin𝜃3
(12)
The maximum value of cos θ3 sin θ3 is equal to 1/2, when the angle θ3 is 45◦. Therefore, to efficiently supply the active power
requirement Pse, 1, max, the injected voltage by the shunt converter at the third harmonic frequency should be:
|𝑉𝑠ℎ,3,𝑚𝑎𝑥| ≥ √2|𝑃𝑠𝑒,1,𝑚𝑎𝑥|𝑋3
,
2 (13)
The maximum voltage of the series converters at the 3rd harmonic frequency should comply with:
|𝑉𝑠𝑒,3,𝑚𝑎𝑥| ≤ |𝑉𝑠ℎ,3,𝑚𝑎𝑥| (14)
V. CONCLUSION
The DPFC appears from the UPFC and inherits the control capability of the UPFC, which is the simultaneous adjustment of
the line impedance, the bus voltage magnitude, and the transmission angle. The total cost of the DPFC is also lower than the UPFC,
because no high voltage isolation is required at the series converter part and the components rating is low. To improve power quality
in the power transmission system, the harmonics due to nonlinear loads, voltage swell and voltage sag are mitigated. By employing
the Distributed FACTS concept, the series converters of the UPFC and IPFC are distributed. Because of the redundancy of the series
converters, the reliability of the distributed power flow controller is increased without additional backup components. To reduce the
investment, the shunt converter can be adjusted from a STATCOM. A single-phase AC to DC converter can be connected back-to-
back to the DC side of the STATCOM, and its AC terminals are connected between the Star-Delta transformer’s neutral point and the
ground. The DPFC can simultaneously adjust the line impedance, the bus voltage, and the transmission angle. To obtain the same
control capability as the UPFC and IPFC, the rating of the DPFC converter at the fundamental frequency should be the same as the
UPFC. Because the currents and voltages at the 3rd harmonic frequency have to be added, the rating of the DPFC converter is slightly
huge than the UPFC and IPFC.
REFERENCES
[1] R. Lokeswar Reddy, K. Vasu “Designing Of Distributed Power- Flow Controller” ISSN: 22781676 Volume 2, Issue 5, PP 01-09, and Sep-Oct. 2012.
[2] V.Aathithya, S. Suresh “Using Distributed Power Flow Controller to Compensate Unbalanced Currents in Transmission Line” International Journal for Research
and Development in Engineering (IJRDE) ISSN: 2279-0500 pp- 171-176 Methods Enriching Power and Energy Development (MEPED) 2014.
[3] Akhib Khan Bahamani Department of Electrical Engineering International Conference on Electrical, Instrumentation and Communication Engineering
(ICEICE2017)
[4] Akula.N.V.V. Rajasekhar Assistant Professor: EEE Department International Conference on Electrical, Electronics, and Optimization Techniques (ICEEOT) –
2016
[5] B. singh S, K.Al-Haddad and A. Chandra,”A review of active filters for power quality improvement,”IEEE trans. Idn. Electron. Vol. 46, no, pp.960-971,1999.
[6] M. A. Hannan and Azah Mohamed, member IEEE “PSCAD/ENTDC Simulation of Unified series-shunt compensator for power quality improvement”, IEEE
Transaction on power delivery, vol.20, no.2, April 2005.
VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021)
ISSN(Online): 2581-7280
VIVA Institute of Technology
9th
National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021)
C-62
www.viva-technology.org/New/IJRI
[7] I Nita R. Patne, Krishna L. Thakre ”Factor Affecting Charactristics Of Voltage Sag Due to Fault In The Power System” Serbian Journal of Electrical
Engineering.vol.5,no.1,May 2008, pp.171-182.
[8] J. Pedra, L Sainz, F. Corcoles, and L. Guasch,”Symmetrical and unsymmetrical voltage sag effects on three-phase transformers,” Power Delivery, IEEE
Transactions on, vol.20,no.2, pp.1683-1691,2005.
[9] K. Nohara, A. Ueda, A. Torii, and D. Kae, “Compensating characteristics of a series-shunt active power filter considering unbalance source voltage and unbalance
load, “ in Power Conversion Conferenace-Nagoya,2007.PCC’07,2007,pp.1692-1697.’
[10] Y. Sozer and D. A. Torrey, ―Modeling and control of utility interactive inverters,‖ IEEE Trans. Power Electron., vol. 24, no. 11, pp. 2475–2483, Nov. 2009.
[11] L. Huber, B. T. Irving, and M. M. Jovanovic, ―Review and stability analysis of pll-based interleaving control of dcm/ccm boundary boost pfc converters,‖
IEEE Trans. Power Electron., vol. 24, no. 8, pp. 1992–1999, Aug. 2009
[12] M. Mohaddes, A. M. Gole, and S. Elez, ―Steady state frequency response of statcom,‖ IEEE Trans. Power Del., vol. 16, no. 1, pp. 18–23, Jan. 2001.

More Related Content

What's hot

Power Line Carrier Communication seminar
Power Line Carrier Communication seminarPower Line Carrier Communication seminar
Power Line Carrier Communication seminar
Aishwary Verma
 

What's hot (20)

Power Line Carrier Communication seminar
Power Line Carrier Communication seminarPower Line Carrier Communication seminar
Power Line Carrier Communication seminar
 
Me2420192024
Me2420192024Me2420192024
Me2420192024
 
Smart Metering - Power Management & Power Line Communications
Smart Metering - Power Management & Power Line CommunicationsSmart Metering - Power Management & Power Line Communications
Smart Metering - Power Management & Power Line Communications
 
Plcc
PlccPlcc
Plcc
 
Power Line Carrier Communication PLCC
Power Line Carrier Communication PLCCPower Line Carrier Communication PLCC
Power Line Carrier Communication PLCC
 
Plcc ppt1
Plcc ppt1Plcc ppt1
Plcc ppt1
 
Power line carrier communication
Power line carrier communicationPower line carrier communication
Power line carrier communication
 
Manufacturing of an insulator through embedded scada using power line carrier...
Manufacturing of an insulator through embedded scada using power line carrier...Manufacturing of an insulator through embedded scada using power line carrier...
Manufacturing of an insulator through embedded scada using power line carrier...
 
Ppt
PptPpt
Ppt
 
Plcc presentation
Plcc presentationPlcc presentation
Plcc presentation
 
Ppt.aslam
Ppt.aslamPpt.aslam
Ppt.aslam
 
PLCC application
PLCC applicationPLCC application
PLCC application
 
Low frequency ac transmission for power systems by Aamir Saleem
Low frequency ac transmission for power systems by Aamir SaleemLow frequency ac transmission for power systems by Aamir Saleem
Low frequency ac transmission for power systems by Aamir Saleem
 
POWER LINE CARRIER COMMUNICATION
POWER LINE CARRIER COMMUNICATIONPOWER LINE CARRIER COMMUNICATION
POWER LINE CARRIER COMMUNICATION
 
www.ijerd.com
www.ijerd.comwww.ijerd.com
www.ijerd.com
 
Power Line carrier communication
Power Line carrier communicationPower Line carrier communication
Power Line carrier communication
 
Rrvpnl summer-industrial-training-ajmer-in-power-line-carrier-communication
Rrvpnl summer-industrial-training-ajmer-in-power-line-carrier-communicationRrvpnl summer-industrial-training-ajmer-in-power-line-carrier-communication
Rrvpnl summer-industrial-training-ajmer-in-power-line-carrier-communication
 
Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...Control of grid connected inverter system for sinusoidal current injection wi...
Control of grid connected inverter system for sinusoidal current injection wi...
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 

Similar to POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC

Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controller
Sudeepthg Sudeepth
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
researchinventy
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...
eSAT Journals
 
A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...
A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...
A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...
ijtsrd
 
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
ijtsrd
 

Similar to POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC (20)

Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controller
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...
 
Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Usi...
Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Usi...Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Usi...
Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Usi...
 
H49034147
H49034147H49034147
H49034147
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...
 
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
 
IRJET- Review: Different Technology for Distributed Power Flow Controller
IRJET- Review: Different Technology for Distributed Power Flow ControllerIRJET- Review: Different Technology for Distributed Power Flow Controller
IRJET- Review: Different Technology for Distributed Power Flow Controller
 
Distributed power flow controller (naresh)
Distributed power flow controller (naresh)Distributed power flow controller (naresh)
Distributed power flow controller (naresh)
 
project report on IPFC
project report on IPFCproject report on IPFC
project report on IPFC
 
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
 
IJMTST020111
IJMTST020111IJMTST020111
IJMTST020111
 
Mitigation of Voltage Sag for Power Quality Improvement Using DPFC System
Mitigation of Voltage Sag for Power Quality Improvement Using DPFC SystemMitigation of Voltage Sag for Power Quality Improvement Using DPFC System
Mitigation of Voltage Sag for Power Quality Improvement Using DPFC System
 
A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...
A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...
A Review on Voltage Stability and Power Quality Improvement by using UPFC Con...
 
[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi
[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi
[IJET V2I5P4] Authors: Rachana Chavan, Rakesh Singh Lodhi
 
Ar4101248255
Ar4101248255Ar4101248255
Ar4101248255
 
A010240107
A010240107A010240107
A010240107
 
IRJET- Enhancement of Power Quality using DPFC
IRJET-  	  Enhancement of Power Quality using DPFCIRJET-  	  Enhancement of Power Quality using DPFC
IRJET- Enhancement of Power Quality using DPFC
 
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
 

More from vivatechijri

Structural and Morphological Studies of Nano Composite Polymer Gel Electroly...
Structural and Morphological Studies of Nano Composite  Polymer Gel Electroly...Structural and Morphological Studies of Nano Composite  Polymer Gel Electroly...
Structural and Morphological Studies of Nano Composite Polymer Gel Electroly...
vivatechijri
 
An Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGE
An Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGEAn Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGE
An Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGE
vivatechijri
 
Recommender Systems
Recommender SystemsRecommender Systems
Recommender Systems
vivatechijri
 
THE USABILITY METRICS FOR USER EXPERIENCE
THE USABILITY METRICS FOR USER EXPERIENCETHE USABILITY METRICS FOR USER EXPERIENCE
THE USABILITY METRICS FOR USER EXPERIENCE
vivatechijri
 

More from vivatechijri (20)

Understanding the Impact and Challenges of Corona Crisis on Education Sector...
Understanding the Impact and Challenges of Corona Crisis on  Education Sector...Understanding the Impact and Challenges of Corona Crisis on  Education Sector...
Understanding the Impact and Challenges of Corona Crisis on Education Sector...
 
LEADERSHIP ONLY CAN LEAD THE ORGANIZATION TOWARDS IMPROVEMENT AND DEVELOPMENT
LEADERSHIP ONLY CAN LEAD THE ORGANIZATION  TOWARDS IMPROVEMENT AND DEVELOPMENT  LEADERSHIP ONLY CAN LEAD THE ORGANIZATION  TOWARDS IMPROVEMENT AND DEVELOPMENT
LEADERSHIP ONLY CAN LEAD THE ORGANIZATION TOWARDS IMPROVEMENT AND DEVELOPMENT
 
A study on solving Assignment Problem
A study on solving Assignment ProblemA study on solving Assignment Problem
A study on solving Assignment Problem
 
Structural and Morphological Studies of Nano Composite Polymer Gel Electroly...
Structural and Morphological Studies of Nano Composite  Polymer Gel Electroly...Structural and Morphological Studies of Nano Composite  Polymer Gel Electroly...
Structural and Morphological Studies of Nano Composite Polymer Gel Electroly...
 
Theoretical study of two dimensional Nano sheet for gas sensing application
Theoretical study of two dimensional Nano sheet for gas sensing  applicationTheoretical study of two dimensional Nano sheet for gas sensing  application
Theoretical study of two dimensional Nano sheet for gas sensing application
 
METHODS FOR DETECTION OF COMMON ADULTERANTS IN FOOD
METHODS FOR DETECTION OF COMMON  ADULTERANTS IN FOODMETHODS FOR DETECTION OF COMMON  ADULTERANTS IN FOOD
METHODS FOR DETECTION OF COMMON ADULTERANTS IN FOOD
 
The Business Development Ethics
The Business Development EthicsThe Business Development Ethics
The Business Development Ethics
 
Digital Wellbeing
Digital WellbeingDigital Wellbeing
Digital Wellbeing
 
An Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGE
An Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGEAn Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGE
An Alternative to Hard Drives in the Coming Future:DNA-BASED DATA STORAGE
 
Enhancing The Capability of Chatbots
Enhancing The Capability of ChatbotsEnhancing The Capability of Chatbots
Enhancing The Capability of Chatbots
 
Smart Glasses Technology
Smart Glasses TechnologySmart Glasses Technology
Smart Glasses Technology
 
Future Applications of Smart Iot Devices
Future Applications of Smart Iot DevicesFuture Applications of Smart Iot Devices
Future Applications of Smart Iot Devices
 
Cross Platform Development Using Flutter
Cross Platform Development Using FlutterCross Platform Development Using Flutter
Cross Platform Development Using Flutter
 
3D INTERNET
3D INTERNET3D INTERNET
3D INTERNET
 
Recommender Systems
Recommender SystemsRecommender Systems
Recommender Systems
 
Light Fidelity(LiFi)- Wireless Optical Networking Technology
Light Fidelity(LiFi)- Wireless Optical Networking TechnologyLight Fidelity(LiFi)- Wireless Optical Networking Technology
Light Fidelity(LiFi)- Wireless Optical Networking Technology
 
Social media platform and Our right to privacy
Social media platform and Our right to privacySocial media platform and Our right to privacy
Social media platform and Our right to privacy
 
THE USABILITY METRICS FOR USER EXPERIENCE
THE USABILITY METRICS FOR USER EXPERIENCETHE USABILITY METRICS FOR USER EXPERIENCE
THE USABILITY METRICS FOR USER EXPERIENCE
 
Google File System
Google File SystemGoogle File System
Google File System
 
A Study of Tokenization of Real Estate Using Blockchain Technology
A Study of Tokenization of Real Estate Using Blockchain TechnologyA Study of Tokenization of Real Estate Using Blockchain Technology
A Study of Tokenization of Real Estate Using Blockchain Technology
 

Recently uploaded

1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
AldoGarca30
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 

Recently uploaded (20)

Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
1_Introduction + EAM Vocabulary + how to navigate in EAM.pdf
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Signal Processing and Linear System Analysis
Signal Processing and Linear System AnalysisSignal Processing and Linear System Analysis
Signal Processing and Linear System Analysis
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdf
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
 

POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC

  • 1. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-56 www.viva-technology.org/New/IJRI POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC Ms. Deepali Chavan1 , Ms. Dipali Hadal2 , Ms. Sfurti Raut3 , Prof. Kavita Mhaskar 4 1 (Department of Electrical Engineering, Viva Institute of Technology, India) 2 (Department of Electrical Engineering, Viva Institute of Technology, India) 3 (Department of Electrical Engineering, Viva Institute of Technology, India) 4 (Department of Electrical Engineering, Viva Institute of Technology, India) Abstract : This project presents the MATLAB Simulation model of the Distributed Power Flow Controller in Transmission line. This work will be a new component with the flexible ac transmission system, called as distributed power flow controller (DPFC). The DPFC will be derived from the unified power flow controller system (UPFC). The DPFC can be considered as a UPFC with a common dc link which is eliminated. The active power exchange between the series and shunt converters, through the common dc link in the UPFC, is now through the transmission lines at the third-harmonic frequency. DPFC has the same control ability as the UPFC, which adjusts line impedance, bus voltages, and the transmission lines. Keywords : AC/DC converters, DPFC, MATLAB, Power electronics, Power flow controller, Third harmonic frequency, Transmission line parameters control. I. INTRODUCTION The aging of networks and increasing demand make it desirable for power flow, to control the power transmission system reliable and fast to the flexible ac transmission system, which is the application of power electronics in transmission system. The main aim of this technology is to regulate and control the electric variables in the power system. The DPFC is the new concept. It is the advance version of the UPFC (Unified Power Flow Controller). The Distributed power flow controller is derived from the Unified Power Flow Controller (UPFC). The DPFC can be compared to a UPFC with an eliminated common dc link. The active power ex-change between the series and shunt converters, which is through the common dc link in the UPFC, is now through the transmission lines at the third-harmonic frequency. The DPFC employs the distributed FACTS (D-FACTS) concept, which is used for multiple small-size single phase converters instead of the one large-size three phase series converter in the UPFC. The multiple number of series converters provides redundancy, thereby increasing the system reliability. As the Distributed FACTS converters are single phase and floating with respect to the ground, there is no high voltage isolation required between the phases. According to this, the cost of the DPFC system is lower than the UPFC. The DPFC and UPFC has same control capabilities, which comprises the adjustment of the line impedance, the bus voltages and, the transmission angle. Advantages of the DPFC over UPFC: The DPFC can be considered as a UPFC that employs the Distributed FACTS concept and the concept of exchanging power through harmonic. Therefore, the DPFC inherits all the advantages of the UPFC and the Distributed FACTS, which are as follows. 1) High control capability The DPFC can simultaneously control all the parameters of the power system: the line impedance, the bus voltages and, the transmission angle, the elimination of the common dc link enables separated installation of the DPFC converters. The series and shunt converters can be placed at the most effectively location. Due to the high control capability, the DPFC can also be used to
  • 2. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-57 www.viva-technology.org/New/IJRI improve the power quality and system stability, such as low-frequency power oscillation damping, restoration the voltage sag, or balancing asymmetry. 2) High reliability The redundancy of the series converter improves reliability. In addition, the series and shunt converters are independent, and the failure at one place will not influence to the other converters. In the series converter when a failure occurs, the converter will be short circuited by bypass protection, thereby having little impact to the network. In the case of failure in the shunt converter, the shunt converter will trip and the series converter will stop providing active compensation and will act as the Distributed FACTS controller. 3) Low cost There is no phase-to-phase voltage isolation required by the series converter, and also, the power rating of each converter is small and can be easily produced in series production lines. II. DPFC OPERATING PRINCIPLE 2.1Active power exchange with eliminated DC link Within the Distributed power flow controller, the transmission line presents a common connection between the AC ports of the series and the shunt converters. Therefore, it can exchange active power through the AC ports. This purpose is based on power theory of non-sinusoidal components. According to the Fourier system analysis, non-sinusoidal voltage and current can be derived as the sum of sinusoidal functions in different amplitudes with different frequencies. The active power resulting from this non-sinusoidal current and voltage is defined as the mean value of the product of current and voltage. Due to the integrals of all the cross terms with various frequencies are zero, produced active power can be expressed as, P = 𝑣𝐼 𝑖𝐼 cos ∅𝐼 (1) By applying this method to the Distributed Power Flow Controller, the shunt converter can absorb active power from the grid at the fundamental frequency and inject the power back at a harmonic frequency. This active power harmonics flows through a transmission line supplied with series converters. According to the required active power at the fundamental frequency, the DPFC series converters generate a voltage at the harmonic frequency, therefore it actives power from harmonic components. Neglecting losses, the active power generated at the fundamental frequency is equal to the absorbed power at the harmonic frequency. 2.2 Using third harmonic components Due to the unique features of third harmonic frequency components in a three-phase system, the 3rd harmonic is applied for active power exchange in the DPFC. In a three-phase system, the third harmonic in each phase is identical, which means they are “Zero Sequences” components. Because the zero-sequence harmonic can be blocked by star-delta transformers and these are widely absorbed in power systems, as there is no extra filter required to prevent harmonic leakage. Figure 1: Active power exchange between DPFC converters
  • 3. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-58 www.viva-technology.org/New/IJRI III. DPFC CONTROL To control small size multiple converters, a DPFC consists of three types of controllers: central control, shunt control and series control, the series and shunt control are localized controllers and are responsible for maintaining their own converters parameters. The central control satisfies the DPFC functions at the power system level. The function of each controller is listed: • Central control The central control generates the reference signals for both the series and shunt converters of the DPFC. It controls function of DPFC which depends on the specifics of the DPFC application at the power system level, such as power flow control, low frequency power oscillation damping and balancing of asymmetrical components. According to the requirements, the central control gives voltage reference signals for the series converters and reactive current signal for the shunt converter. All the reference signals generated by the central control bothered the fundamental frequency components. • Series control Each converter of series has its own series control. The series controller is used to maintain the DC capacitor voltage of its own converter, by using 3rd harmonic frequency components. The central control is required by additional to the generating series voltage at the fundamental frequency. • Shunt control The objective of the shunt control is to inject a constant third harmonic current into the line to supply active power for the series converters. At the same moment, it maintains the capacitor DC voltage of the shunt converter at a constant value from the grid at the fundamental frequency by absorbing active power and injecting the reactive current at the fundamental frequency into the grid. IV. ANALYSIS OF DPFC In this steady-state behaviour of the DPFC is analysed, and the control capability of the DPFC is expressed in the parameters of the network and the DPFC. Figure 2: DPFC configuration
  • 4. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-59 www.viva-technology.org/New/IJRI 4.1 Fundamental frequency circuit To simplify the distributed power flow controller (DPFC), the converters are replaced by controllable voltage sources in series with impedance. Since at two different frequencies, each converter generates the voltage, it is represented by two series connected controllable voltage sources, one at the fundamental frequency and the other at the third harmonic frequency. Assuming that the transmission lines and the converters are lossless, the total active power generated by the two frequency voltage sources will be zero. The small size multiple series converters are simplified as one large. In fig 3 a) Fundamental frequency circuit is shown. In Fig, the DPFC is placed in a two-bus system with the sending end voltages and the receiving end voltages Vs and Vr, respectively. The transmission line system is represented by an inductance L with the line current I. The injected voltages by all the DPFC series converters are Vse,1 and Vse,3 at the fundamental and the third harmonic frequency, respectively. The shunt converter is connected to the sending end bus through the inductor Lsh and generates the voltage Vsh,1 and Vsh,3; the injected current by the shunt converter is Ish. The active power and reactive power flow at the receiving end are Pr and Qr, respectively. This representation consists of both the third harmonics frequency and fundamental frequencies components. Based on the superposition theorem, the circuit in Fig can be further simplified by being separated into two circuits at different frequencies. The two circuits are isolated from each other, and the link the power flow control capability of the DPFC can be illustrated by the active power Pr and reactive power Qr received at the receiving end. Due to these the DPFC circuit at the fundamental frequency behaves the same as the UPFC, the active and reactive power flow can be derived as follows: (Pr - Pro)2 +(Qr - Qro)2 = ( |𝑉||𝑉𝑆𝑒,1| 𝑋1 ) 2 (2) Pse,1 = Re (Vse,1 I1 * ) = 𝑋1 |𝑉𝑟|2 |𝑆𝑟||𝑆𝑟0| sin(𝜑𝑟0 − 𝜑𝑟) (3) Fig, illustrates the relationship between Pse,1 and the power flow at the receiving end at a certain power angle θ. Consequently, the series converter at the required active power can be written as follows: Pse,1 = CA (o, r0, r) (4) According to the Fig, the relationship between the power flow control range and the maximum active power requirement can be represented by: Pse,1, max = |𝑋1||𝑆𝑟0| |𝑉𝑟|2 |𝑆𝑟,𝑐| (5) Figure 3: DPFC equivalent circuit a)Fundamental
  • 5. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-60 www.viva-technology.org/New/IJRI Where |Sr, c | is the control range of the Distributed power flow controller At the same time each converter in the DPFC generates two frequency voltages. According to these, the voltage rating of each converter should be the sum of the maximum voltage of the two frequencies component. Vse, max = |𝑉𝑠𝑒,1,𝑚𝑎𝑥| + |𝑉𝑠𝑒,3,𝑚𝑎𝑥| (6) During the operation, the active power requirement of the series converter varies with the injected voltage at the fundamental frequency. When it is low required, the series voltage at the third harmonic frequency will be smaller than |Vse, 3, max|. This potential voltage which is in between Vse,3 and |Vse,3, max| can be used to control the power flow at the fundamental frequency, thereby increasing the power flow control region of the DPFC. When Sr, c is perpendicular to the uncompensated power Sr0, the maximum active power required by series converters, and the radius of the DPFC control region is given by: |𝑆𝑟,𝑐| = |𝑉𝑟||𝑉𝑠𝑒,1,𝑚𝑎𝑥| 𝑋1 (7) If Sr,c is in the same line as Sr0 , the series converters only provide the reactive compensation and the boundary of the DPFC control region will extended to: |𝑆𝑟,𝑐| = |𝑉𝑟|(|𝑉𝑠𝑒,1,𝑚𝑎𝑥|+|𝑉𝑠𝑒,3,𝑚𝑎𝑥|) 𝑋1 = |𝑉𝑟||𝑉𝑠𝑒,𝑚𝑎𝑥| 𝑋1 (8) 4.2 Third harmonic frequency circuit The 3rd harmonic component within the DPFC system is used to exchange active and reactive power between the shunt and series converters. In fig 3 b) Third harmonic frequency circuit shown. Therefore, the voltages and currents at the 3rd harmonic frequency are related to the required active power at the fundamental frequency. For the series converters, there is: (Vse,3I3 * ) = -Pse,1 (9) Absorbed power by the series converters at the third harmonic frequency is given by: Pse,3 + jQse,3 = Vse,3I3 * = Vsh,3( 𝑉𝑠ℎ,3−𝑉𝑠𝑒,3 𝑋3 , ) ∗ (10) Where X′3 = X3 + Xsh,3. By splitting the real and imaginary parts, the absorbed active and reactive power at 3rd harmonic frequency can be expressed as: Figure 4: DPFC Power flow control range
  • 6. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-61 www.viva-technology.org/New/IJRI Pse,3 = |𝑉𝑠𝑒,3||𝑉𝑠ℎ,3| 𝑋3 , sin 𝜃3 Qse,3 = |𝑉𝑠𝑒,3| 𝑋3 , (|𝑉𝑠ℎ,3| cos 𝜃3 − |𝑉𝑠𝑒,3|) (11) Although here θ3 is the phase angle difference between the voltages Vsh,3 and Vse,3. For the series converters, any of the reactive power at the third harmonic frequency results in unnecessary extra currents and voltages. Therefore, the reactive power flowing through the series converters at the third harmonic frequency is controlled to be zero, which is Qse,3 = 0. It shows that the relationship between the voltages Vsh,3 and Vse,3 is: |𝑉𝑠𝑒,3| = |𝑉𝑠ℎ,3| cos 𝜃3 Pse,3 = |𝑉𝑠ℎ,3| 𝑋3 , cos 𝜃3 sin𝜃3 (12) The maximum value of cos θ3 sin θ3 is equal to 1/2, when the angle θ3 is 45◦. Therefore, to efficiently supply the active power requirement Pse, 1, max, the injected voltage by the shunt converter at the third harmonic frequency should be: |𝑉𝑠ℎ,3,𝑚𝑎𝑥| ≥ √2|𝑃𝑠𝑒,1,𝑚𝑎𝑥|𝑋3 , 2 (13) The maximum voltage of the series converters at the 3rd harmonic frequency should comply with: |𝑉𝑠𝑒,3,𝑚𝑎𝑥| ≤ |𝑉𝑠ℎ,3,𝑚𝑎𝑥| (14) V. CONCLUSION The DPFC appears from the UPFC and inherits the control capability of the UPFC, which is the simultaneous adjustment of the line impedance, the bus voltage magnitude, and the transmission angle. The total cost of the DPFC is also lower than the UPFC, because no high voltage isolation is required at the series converter part and the components rating is low. To improve power quality in the power transmission system, the harmonics due to nonlinear loads, voltage swell and voltage sag are mitigated. By employing the Distributed FACTS concept, the series converters of the UPFC and IPFC are distributed. Because of the redundancy of the series converters, the reliability of the distributed power flow controller is increased without additional backup components. To reduce the investment, the shunt converter can be adjusted from a STATCOM. A single-phase AC to DC converter can be connected back-to- back to the DC side of the STATCOM, and its AC terminals are connected between the Star-Delta transformer’s neutral point and the ground. The DPFC can simultaneously adjust the line impedance, the bus voltage, and the transmission angle. To obtain the same control capability as the UPFC and IPFC, the rating of the DPFC converter at the fundamental frequency should be the same as the UPFC. Because the currents and voltages at the 3rd harmonic frequency have to be added, the rating of the DPFC converter is slightly huge than the UPFC and IPFC. REFERENCES [1] R. Lokeswar Reddy, K. Vasu “Designing Of Distributed Power- Flow Controller” ISSN: 22781676 Volume 2, Issue 5, PP 01-09, and Sep-Oct. 2012. [2] V.Aathithya, S. Suresh “Using Distributed Power Flow Controller to Compensate Unbalanced Currents in Transmission Line” International Journal for Research and Development in Engineering (IJRDE) ISSN: 2279-0500 pp- 171-176 Methods Enriching Power and Energy Development (MEPED) 2014. [3] Akhib Khan Bahamani Department of Electrical Engineering International Conference on Electrical, Instrumentation and Communication Engineering (ICEICE2017) [4] Akula.N.V.V. Rajasekhar Assistant Professor: EEE Department International Conference on Electrical, Electronics, and Optimization Techniques (ICEEOT) – 2016 [5] B. singh S, K.Al-Haddad and A. Chandra,”A review of active filters for power quality improvement,”IEEE trans. Idn. Electron. Vol. 46, no, pp.960-971,1999. [6] M. A. Hannan and Azah Mohamed, member IEEE “PSCAD/ENTDC Simulation of Unified series-shunt compensator for power quality improvement”, IEEE Transaction on power delivery, vol.20, no.2, April 2005.
  • 7. VIVA-Tech International Journal for Research and Innovation Volume 1, Issue 4 (2021) ISSN(Online): 2581-7280 VIVA Institute of Technology 9th National Conference on Role of Engineers in Nation Building – 2021 (NCRENB-2021) C-62 www.viva-technology.org/New/IJRI [7] I Nita R. Patne, Krishna L. Thakre ”Factor Affecting Charactristics Of Voltage Sag Due to Fault In The Power System” Serbian Journal of Electrical Engineering.vol.5,no.1,May 2008, pp.171-182. [8] J. Pedra, L Sainz, F. Corcoles, and L. Guasch,”Symmetrical and unsymmetrical voltage sag effects on three-phase transformers,” Power Delivery, IEEE Transactions on, vol.20,no.2, pp.1683-1691,2005. [9] K. Nohara, A. Ueda, A. Torii, and D. Kae, “Compensating characteristics of a series-shunt active power filter considering unbalance source voltage and unbalance load, “ in Power Conversion Conferenace-Nagoya,2007.PCC’07,2007,pp.1692-1697.’ [10] Y. Sozer and D. A. Torrey, ―Modeling and control of utility interactive inverters,‖ IEEE Trans. Power Electron., vol. 24, no. 11, pp. 2475–2483, Nov. 2009. [11] L. Huber, B. T. Irving, and M. M. Jovanovic, ―Review and stability analysis of pll-based interleaving control of dcm/ccm boundary boost pfc converters,‖ IEEE Trans. Power Electron., vol. 24, no. 8, pp. 1992–1999, Aug. 2009 [12] M. Mohaddes, A. M. Gole, and S. Elez, ―Steady state frequency response of statcom,‖ IEEE Trans. Power Del., vol. 16, no. 1, pp. 18–23, Jan. 2001.