P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 41 | P a g e 
Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Using Distributed Power Flow Controller P.NIRMALA1, SK.SAJIDA2, SK.JAN BHASHA3, PG Student [EPS], Dept. of EEE, ASIT, Gudur, SPSR Nellore (D), Andhra Pradesh, India1 Assistant Professor, Dept. of EEE, ASIT, Gudur, SPSR Nellore (D), Andhra Pradesh, India2 Associate Professor, Dept. of EEE, ASIT, Gudur, SPSR Nellore (D), Andhra Pradesh, India3 Abstract— Modern power utilities have to respond to a number of challenges such as growth of electricity demand specially in non-linear loads in power grids, consequently, That higher power quality should be considered. In this paper, DPFC which is similar to unified power flow controller (UPFC) in structure, which is used to mitigate the voltage sag and swell as a power quality issue. Unlike UPFC, the common dc-link in DPFC, between the shunt and series converter devices should be eliminated and three-phase series converter is divided to several single- phase series distributed converters through the power transmission line. And also to detect the voltage sags and find out the three single-phase reference voltages of DPFC, the synchronous reference frame method is proposed. Application of DPFC in power quality enhancement is simulated in Mat lab/Simulink environment which show the effectiveness of the proposed structure Index Terms—FACTS, power quality, sag and swell mitigation, distributed power flow controller. 
I. INTRODUCTION 
Recent developments in the electric utility industry are encouraging the entry of power quality issue [1]. Extending from the generation units to the utility customers, power quality is a measure of how the elements affect the system as a whole [2]. From customer point of view, the power quality issue is concerned about current, voltage or frequency deviation which results in power failure [3]. To solve the power quality problem in such a situation, the power electronic devices such as flexible alternating- current transmission system (FACTS) and custom power devices (DVR) which are used in transmission and distribution control, respectively, should be developed [4], [5], [6]. The impact of transient parameters in majority of transmission lines problems such as sag (voltage dip), swell (over voltage) and interruption, are also considerable [1]. To mitigate the mentioned power quality problems, the utilization of FACTS devices such as power flow controller (UPFC) and synchronous static compensator (STAT- COM) can be helpful [7] , [8]. In [9], the distributed power flow controller (DPFC) is presented which has a similar configuration to UPFC structure. As shown in Fig. 1, the DPFC is composed of a single shunt converter and multiple independent series converters which is used to balance the line parameters, such as line impedance, transmission angle and bus voltage magnitude [9], [10]. To detect the voltage sags and determine the three single-phase reference voltages of DPFC, the SRF method is also proposed as a detection and determination method. The work in this paper is organized as follows: the DPFC operation principle is debated in Section II. In Section III, the control strategy of DPFC based on SRF method is proposed. The impact of DPFC in power quality enhancement is investigated in Section IV. Finally, the case study and its simulation results are analyzed in the last part of this work. 
II. DPFC STRUCTURE 
The basic issues in DPFC principle are DC-link elimination and using 3rd-harmonic current to active power exchange. In the following subsections, the DPFC basic concepts are explained. 
A. Eliminate DC-Link and Power Exchange 
Within the DPFC, the transmission line is used as a connection between shunt converter output and AC port of series converters, instead of using DC- link for power exchange between converters. The method of power exchange in DPFC is based on power theory of non-sinusoidal components [9]. Non- sinusoidal voltage and current can be presented as the sum of sinusoidal components at different frequencies. It is the main result of Fourier analysis. The product of voltage and current components provides the active power. Since the integral of some terms with different frequencies are zero, so the active power equation is as follow: 
(1) 
Where Vi and Ii are the voltage and current at the ith harmonic frequency, respectively, and φi is the angle 
RESEARCH ARTICLE OPEN ACCESS
P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 42 | P a g e 
between the voltage and current at the same frequency. Equation. 1 expresses the active powers at different frequencies are independent from each others. Thus, the converter can absorb the active power in one frequency and generates output power in another frequency. Assume the DPFC is located in transmission line of a two-bus system; therefore, the power supply generates the active power and the shunt converter absorbs it in fundamental frequency of current. Meanwhile, the third harmonic component is trapped in Y-Δ transformer. Output terminal of the shunt converter injects the third harmonic current into the neutral of Δ-Y transformer. 
Consequently, the harmonic current flows through the transmission line. This harmonic current controls the dc voltage of series capacitors. Fig. 2 illustrates how the active power is exchanged between the shunt and series converters in the DPFC. 
Fig. 1.The DPFC structure. 
Fig. 2. Active power exchange between DPFC converters. 
B. The DPFC Advantages 
The DPFC in comparison with UPFC has some advantages, as follows: 
1) High control capability. 
The DPFC can control all parameters of transmission network: line impedance, transmission angle and bus voltage magnitude. 
2) High reliability. 
The series converters redundancy increases the DPFC reliability during converters operation [10]. It means, if one of series converters fails, the others can continue to work. 
3) Low cost. 
The single-phase converters rating, in comparison with three-phase converters is very low. Furthermore, the series converters, in this configuration, no need to any voltage isolation to connect in line. We can use the single turn transformers for series converters hanging. To explore the feasibility of the DPFC, a case study which is to use DPFC to replace UPFC of the Korea electric power corporation (KEPCO) is investigated. To achieve the same control capability as the UPFC, the DPFC construction requires less material [9]. 
III. DPFC CONTROL BASED ON SRF METHOD 
The DPFC has three control strategies: central controller, series control and shunt control, as shown in Fig. 3. 
A. Central Control 
This controller manages all the series and shunt controllers and sends reference signals to both of them. 
B. Series Control 
Each single-phase converter has its own series control through the line. This controller inputs are series capacitor voltages, line current and series voltage reference in dq-frame. Any series controller has one low-pass and one 3rd-pass filter to create fundamental and third harmonic current respectively. Two single-phase phase lock loop (PLL) are used to take frequency and phase information from network [11]. The simulated diagram of
P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 43 | P a g e 
series controller is shown in Fig. 4 
C. Shunt Control 
The shunt converter includes a three-phase converter which is back-to-back connected to a single-phase converter 
Fig .3.DPFC Control Structure. 
Fig. 4. The series control structure. 
Fig. 5. The shunt control configuration: (a) for fundamental frequency (b) for third-harmonic frequency 
The three-phase converter absorbs active power from grid at fundamental frequency and controls the dc voltage of capacitor between this converter and single-phase one. The shunt control structure block diagram is shown in Fig. 5.
P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 44 | P a g e 
D. Proposed Detection and Determination Methods 
To detect the voltage sags and determine the three single phase reference voltages of DPFC, the SRF method is introduced as a detection and determination method. The line-to-neutral voltages of grid in the pre-sag state are convicted from abc coordinate system to SRF (dq0) as the first step of this method. Then, the dq0 values of actual and reference line-neutral grid voltages are compared which the existence of the difference between them is representation of voltage sag and considered as the dq0 values of DPFC desired injected voltages. 
= (2) 
Fig.6.simulated model of the DPFC = (3) are the reference dq- component of DPFC desired injected voltages in the SRF, respectively. fig. 6. Simulated model of the 
IV. POWER QUALITY ENHANCEMENT 
This modeling has been developed using Mat lab/Simulink environment as shown in Fig. 6. The system is simulated with a three-phase source connected to a non-linear load. The simulation parameters are listed in Table 1. The supply is connected to load through the parallel transmission lines including the transmission line 1 and 2. The parallel transmission lines have same length. The DPFC is incorporated in transmission line 2. For analyzing dynamic performance, the inductive and capacitive loads are connected. The fault should be connected near the load to receive transient analysis. The shunt three-phase converter is connected to the transmission line 2 in parallel through a Y-Δ three- phase transformer, and series converters are distributed through this line. 
V. SIMULATION RESULTS 
The case study, considering sag/swell condition is implemented in single machine infinite bus system and analyzed results are as follows. To analyze voltage dip, a three-phase fault near the system load, as shown in Fig. 6 is created. The time duration for this fault is 0.5 seconds (500-1000 ms). The three-phase fault causes observable voltage sag during this time, as shown in Fig. 7. The voltage sag value is about 0.5 per unit. The DPFC can compensate the load voltage sag effectively. The voltage sag mitigation with DPFC is shown in Fig. 8. 
After creating three-phase fault, Fig. 9 depicts the load current swell around 1.1 per unit. The fault time duration is
P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 45 | P a g e 
0.5 seconds. In this case, after implementation of the DPFC, the load current magnitude is comparatively come down. The current swell mitigation for this case can be observed from Fig. 10. The load voltage harmonic analysis, using fast Fourier transform (FFT) of power GUI window by Simulink, as shown in Fig. 11. It can be seen, after DPFC implementation in system, the odd harmonics are reduced within acceptable limits and total harmonic distortion (THD) of load voltage is minimized. 
Fig. 7. Three-phase load voltage sag waveform 
Fig. 8. Mitigation of three-phase load voltage sag with DPFC. 
Fig. 9. Three-phase load current swell waveform 
Fig. 10. Mitigation of load current swell with DPFC.
P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 46 | P a g e 
Fig. 11. The load voltage THD. 
VI. CONCLUSION 
The power quality enhancement of the power transmission systems is an vital issue in power industry. In his study, the application of DPFC as a new FACTS device, in the voltage sag and swell mitigation of a system composed of a three-phase source connected to a non-linear load through the parallel transmission lines is simulated in Matlab/Simulink environment. The voltage dip is analyzed by implementing a three-phase fault close to the system load. To detect the voltage sags and determine the three single phase reference voltages of DPFC, the SRF method is used as a detection and determination method. The obtained simulation results show the effectiveness of DPFC in power quality enhancement, especially in sag and swell mitigation. 
TABLE I : THE SIMULATED SYSTEM PARAMETERS. 
Parameters 
values 
Three phase source 
Rated voltage 
230 [kV] 
Rated power/Frequency 
100[mW]/60[HZ] 
X/R 
3 
Short circuit capacity 
11000[MW] 
Transmission line 
Resistance 
0.012 [p.u./km] 
Inductance/Capacitance reactance 
0.12/0.12[p.u./km] 
Length of transmission line 
100 [km] 
REFERENCES 
[1.] J. Faiz, G. H. Shahgholian, and M. Torabian, “Design and simulation of UPFC or enhancement of power quality in transmission lines,” IEEE International Conference on Power System Technology, vol. 24, no. 4, 2010. 
[2.] E. Emanuel and J. A. McNeill, “Electric power quality,” Annu. Rev. Energy Environ, 1997. 
[3.] N. R. Patne and K. L. Thakre “Factor affecting characteristics of voltage sag due to fault in the power system,” Serbian Journal of Electrical engineering. vol. 5, no.1, 2008. 
[4.] J. R. Enslin, “Unified approach to power quality mitigation,” in Proc. IEEE Int. Symp. Industrial Electronics (ISIE ’98), vol. 1, 1998. 
[5.] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,” IEEE Trans. Ind. Electron. vol. 46, no. 5, pp. 960–971, 1999. 
[6.] M. A. Hannan and A. Mohamed, member IEEE, “PSCAD/EMTDC simulation of unified series- shunt compensator for power quality improvement,” IEEE Transactions on Power Delivery, vol. 20, no. 2, 2005. 
[7.] L. Olimpo and E. Acha, “Modeling and analysis of custom power systems by PSCAD/EMTDC,” IEEE
P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com 
ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 
www.ijera.com 47 | P a g e 
Trans. Power Delivery, vol. 17, no.1, pp. 266–272, 2002. 
[8.] P. Pohjanheimo and E. Lakervi, “Steady state modeling of custom power components in power distribution networks,” in Proc. IEEE Power Engineering Society Winter Meeting, vol. 4, Jan, pp. 2949–2954, 2000. 
[9.] Z. H. Yuan, S. W. H de Haan, B. Frreira, and D. Cevoric, “A FACTS device: Distributed power flow controller (DPFC),” IEEE Transaction on Power Electronics, vol.25, no.10, October, 2010. 
[10.] Z. H. Yuan, S. W. H de Haan, and B. Frreira “DPFC control during shunt converter failure,” IEEE Transaction on Power Electronics 2009. 
[11.] R. Zhang, M. Cardinal, P. Szczesny, and M. Dame. “A grid simulator with control of single-phase power converters in D.Q rotating frame,” 
P.Nirmala was born in Andhra Pradesh, India. She received the B.Tech degree in Electrical and Electronics Engineering from JNTU, Anantaapur in 2011 and pursuing M.Tech degree in Power Systems from JTNU, Anantapur, Andhra Pradesh, India. Her area of interest in the field of power systems and electric Drives. Email: nirmala.yadav39@gmail.com Shajida Shaik was born in Andhra Pradesh, India. She received the B.Tech degree in Electrical and Electronics Engineering from DR SGIET, A.P., in 2005 and M.E degree in osmania university, AP, in 2012.She is presently working as Asst.Professor Dept.EEE, Audisankara Institute of Technology-Gudur, Nellore, Andhrapradesh, India. 
Mr. Jan Bhasha Shaik was born in Andhra Pradesh, India. He received the B.Tech degree in Electrical and Electronics Engineering from JNT University, Hyderabad in 2004 and M.Tech degree in Power & Industrial Drives from JNT University Kakinada in 2010. He is currently pursuing the Ph.D. degree at the JNT University, Anantapur, Andhra Pradesh, India. He had worked as an Assistant Professor and IEEE student Branch counselor at Hi-Tech College of Engineering, and worked as an Assistant professor at KL University Guntur,AP. Currently He is working as an Associate Professor at Audisankara Institute of Technology, Gudur,AP. He was the academic project coordinator for Under-Graduate & Post Graduate students. His areas of interest are HVDC, FACTS & SMART GRID.

More Related Content

What's hot

POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...IJITE
 
An Optimal Power Flow (OPF) Method with Improved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method withImproved Voltage Stability AnalysisAn Optimal Power Flow (OPF) Method withImproved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method with Improved Voltage Stability AnalysisNiraj Solanki
 
Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerSudeepthg Sudeepth
 
Enhancement for Power Quality in Distribution Side Using Custom Power Devices
Enhancement for Power Quality in Distribution Side Using Custom Power DevicesEnhancement for Power Quality in Distribution Side Using Custom Power Devices
Enhancement for Power Quality in Distribution Side Using Custom Power DevicesIOSR Journals
 
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...IJERA Editor
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...IJPEDS-IAES
 
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...ijiert bestjournal
 
IRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET Journal
 
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...ijtsrd
 
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...IAES-IJPEDS
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...INFOGAIN PUBLICATION
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyDHEERAJ DHAKAR
 

What's hot (16)

POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
POWER STABILITY ANALYSIS OF A TRANSMISSION SYSTEM WITH A UNIFIED POWER FLOW C...
 
Icraie 2014-s mishra2
Icraie 2014-s mishra2Icraie 2014-s mishra2
Icraie 2014-s mishra2
 
An Optimal Power Flow (OPF) Method with Improved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method withImproved Voltage Stability AnalysisAn Optimal Power Flow (OPF) Method withImproved Voltage Stability Analysis
An Optimal Power Flow (OPF) Method with Improved Voltage Stability Analysis
 
G
GG
G
 
Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controller
 
Enhancement for Power Quality in Distribution Side Using Custom Power Devices
Enhancement for Power Quality in Distribution Side Using Custom Power DevicesEnhancement for Power Quality in Distribution Side Using Custom Power Devices
Enhancement for Power Quality in Distribution Side Using Custom Power Devices
 
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
Application of Backstepping to the Virtual Flux Direct Power Control of Five-...
 
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTI...
 
IRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel InverterIRJET- 127 Multilevel Inverter
IRJET- 127 Multilevel Inverter
 
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
Implementation on the dSPACE 1104 of VOC-SVM based anti-windup PI Controller ...
 
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...Design and Simulation of Power Factor Correction Boost Converter using Hyster...
Design and Simulation of Power Factor Correction Boost Converter using Hyster...
 
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
An Adaptive Neuro-Fuzzy Inference Distributed Power Flow Controller (DPFC) in...
 
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
Mitigation Unbalance Nonlinear Loads and Dissimilar Line Currents Using Shunt...
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topology
 

Viewers also liked

The walking dead 18
The walking dead 18 The walking dead 18
The walking dead 18 Azhroth B.S
 
BAKER 5 YEARS SERVICE LETTER
BAKER 5 YEARS SERVICE LETTERBAKER 5 YEARS SERVICE LETTER
BAKER 5 YEARS SERVICE LETTERHajesh Lodhi
 
Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...
Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...
Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...Dimas Soares Ferreira
 
Uma jornada de vitórias pdf
Uma jornada de vitórias pdfUma jornada de vitórias pdf
Uma jornada de vitórias pdfLau Barboza
 
Presentación para la romana
Presentación para  la romanaPresentación para  la romana
Presentación para la romanaJose Indraya
 
shuaa albalawi resume 1
shuaa albalawi resume 1shuaa albalawi resume 1
shuaa albalawi resume 1shuaa albalawi
 
Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...
Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...
Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...IJERA Editor
 
Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!
Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!
Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!ResellerClub
 
Adicionar ou remover programas
Adicionar ou remover programasAdicionar ou remover programas
Adicionar ou remover programasjoaopriostexx
 

Viewers also liked (20)

The walking dead 18
The walking dead 18 The walking dead 18
The walking dead 18
 
Freire en zipaquirá
Freire en zipaquiráFreire en zipaquirá
Freire en zipaquirá
 
BAKER 5 YEARS SERVICE LETTER
BAKER 5 YEARS SERVICE LETTERBAKER 5 YEARS SERVICE LETTER
BAKER 5 YEARS SERVICE LETTER
 
Lineamientos
LineamientosLineamientos
Lineamientos
 
1gara
1gara1gara
1gara
 
Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...
Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...
Dissertação Mestrado: O Orçamento Participativo como mecanismo de accountabil...
 
Excel 2007
Excel 2007Excel 2007
Excel 2007
 
Ouksé n°1
Ouksé n°1Ouksé n°1
Ouksé n°1
 
Angels
AngelsAngels
Angels
 
088 093
088 093088 093
088 093
 
Uma jornada de vitórias pdf
Uma jornada de vitórias pdfUma jornada de vitórias pdf
Uma jornada de vitórias pdf
 
Presentación para la romana
Presentación para  la romanaPresentación para  la romana
Presentación para la romana
 
Aula para 5º ano
Aula para 5º anoAula para 5º ano
Aula para 5º ano
 
Childhood
ChildhoodChildhood
Childhood
 
shuaa albalawi resume 1
shuaa albalawi resume 1shuaa albalawi resume 1
shuaa albalawi resume 1
 
Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...
Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...
Design and Implementation of Submicron Level 10T Full Adder in ALU Using Cell...
 
Ponencia colombia
Ponencia colombiaPonencia colombia
Ponencia colombia
 
Human Camouflage
Human CamouflageHuman Camouflage
Human Camouflage
 
Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!
Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!
Webinar: Reach out to over 1 Billion Internet Users with .ASIA Domains!
 
Adicionar ou remover programas
Adicionar ou remover programasAdicionar ou remover programas
Adicionar ou remover programas
 

Similar to H49034147

Distributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationDistributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationIJERA Editor
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET Journal
 
Performance of the dpfc before and during series converter failure
Performance of the dpfc before and during series converter failurePerformance of the dpfc before and during series converter failure
Performance of the dpfc before and during series converter failureIAEME Publication
 
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFCPOWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFCvivatechijri
 
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...IJERA Editor
 
Line Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFCLine Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFCIDES Editor
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...eSAT Journals
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...eSAT Publishing House
 
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...IJERA Editor
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...IJERA Editor
 
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...IRJET Journal
 
Review of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent YearsReview of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent YearsIJPEDS-IAES
 
Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerSudeepthg Sudeepth
 
Fd2427822788
Fd2427822788Fd2427822788
Fd2427822788IJMER
 

Similar to H49034147 (20)

Distributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) SimulationDistributed Power-Flow Controller (DPFC) Simulation
Distributed Power-Flow Controller (DPFC) Simulation
 
IJMTST020111
IJMTST020111IJMTST020111
IJMTST020111
 
Voltage Stability Improvement in Fourteen Bus System during Line Interruption...
Voltage Stability Improvement in Fourteen Bus System during Line Interruption...Voltage Stability Improvement in Fourteen Bus System during Line Interruption...
Voltage Stability Improvement in Fourteen Bus System during Line Interruption...
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
Performance of the dpfc before and during series converter failure
Performance of the dpfc before and during series converter failurePerformance of the dpfc before and during series converter failure
Performance of the dpfc before and during series converter failure
 
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFCPOWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
POWER QUALITY IMPROVEMENT IN TRANSMISSION LINE USING DPFC
 
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
 
Line Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFCLine Losses in the 14-Bus Power System Network using UPFC
Line Losses in the 14-Bus Power System Network using UPFC
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...
 
The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...The compensatation of unbalanced 3 phase currents in transmission systems on ...
The compensatation of unbalanced 3 phase currents in transmission systems on ...
 
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
 
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
 
Ijetr021134
Ijetr021134Ijetr021134
Ijetr021134
 
Ijetr021134
Ijetr021134Ijetr021134
Ijetr021134
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
 
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
Distribution Network Power Quality Improvement by D-STATCOM & DVR Under Vario...
 
Review of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent YearsReview of the UPFC Different Models in Recent Years
Review of the UPFC Different Models in Recent Years
 
Pe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controllerPe 2010 25-10-a facts device distributed power flow controller
Pe 2010 25-10-a facts device distributed power flow controller
 
Fd2427822788
Fd2427822788Fd2427822788
Fd2427822788
 

H49034147

  • 1. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 41 | P a g e Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Using Distributed Power Flow Controller P.NIRMALA1, SK.SAJIDA2, SK.JAN BHASHA3, PG Student [EPS], Dept. of EEE, ASIT, Gudur, SPSR Nellore (D), Andhra Pradesh, India1 Assistant Professor, Dept. of EEE, ASIT, Gudur, SPSR Nellore (D), Andhra Pradesh, India2 Associate Professor, Dept. of EEE, ASIT, Gudur, SPSR Nellore (D), Andhra Pradesh, India3 Abstract— Modern power utilities have to respond to a number of challenges such as growth of electricity demand specially in non-linear loads in power grids, consequently, That higher power quality should be considered. In this paper, DPFC which is similar to unified power flow controller (UPFC) in structure, which is used to mitigate the voltage sag and swell as a power quality issue. Unlike UPFC, the common dc-link in DPFC, between the shunt and series converter devices should be eliminated and three-phase series converter is divided to several single- phase series distributed converters through the power transmission line. And also to detect the voltage sags and find out the three single-phase reference voltages of DPFC, the synchronous reference frame method is proposed. Application of DPFC in power quality enhancement is simulated in Mat lab/Simulink environment which show the effectiveness of the proposed structure Index Terms—FACTS, power quality, sag and swell mitigation, distributed power flow controller. I. INTRODUCTION Recent developments in the electric utility industry are encouraging the entry of power quality issue [1]. Extending from the generation units to the utility customers, power quality is a measure of how the elements affect the system as a whole [2]. From customer point of view, the power quality issue is concerned about current, voltage or frequency deviation which results in power failure [3]. To solve the power quality problem in such a situation, the power electronic devices such as flexible alternating- current transmission system (FACTS) and custom power devices (DVR) which are used in transmission and distribution control, respectively, should be developed [4], [5], [6]. The impact of transient parameters in majority of transmission lines problems such as sag (voltage dip), swell (over voltage) and interruption, are also considerable [1]. To mitigate the mentioned power quality problems, the utilization of FACTS devices such as power flow controller (UPFC) and synchronous static compensator (STAT- COM) can be helpful [7] , [8]. In [9], the distributed power flow controller (DPFC) is presented which has a similar configuration to UPFC structure. As shown in Fig. 1, the DPFC is composed of a single shunt converter and multiple independent series converters which is used to balance the line parameters, such as line impedance, transmission angle and bus voltage magnitude [9], [10]. To detect the voltage sags and determine the three single-phase reference voltages of DPFC, the SRF method is also proposed as a detection and determination method. The work in this paper is organized as follows: the DPFC operation principle is debated in Section II. In Section III, the control strategy of DPFC based on SRF method is proposed. The impact of DPFC in power quality enhancement is investigated in Section IV. Finally, the case study and its simulation results are analyzed in the last part of this work. II. DPFC STRUCTURE The basic issues in DPFC principle are DC-link elimination and using 3rd-harmonic current to active power exchange. In the following subsections, the DPFC basic concepts are explained. A. Eliminate DC-Link and Power Exchange Within the DPFC, the transmission line is used as a connection between shunt converter output and AC port of series converters, instead of using DC- link for power exchange between converters. The method of power exchange in DPFC is based on power theory of non-sinusoidal components [9]. Non- sinusoidal voltage and current can be presented as the sum of sinusoidal components at different frequencies. It is the main result of Fourier analysis. The product of voltage and current components provides the active power. Since the integral of some terms with different frequencies are zero, so the active power equation is as follow: (1) Where Vi and Ii are the voltage and current at the ith harmonic frequency, respectively, and φi is the angle RESEARCH ARTICLE OPEN ACCESS
  • 2. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 42 | P a g e between the voltage and current at the same frequency. Equation. 1 expresses the active powers at different frequencies are independent from each others. Thus, the converter can absorb the active power in one frequency and generates output power in another frequency. Assume the DPFC is located in transmission line of a two-bus system; therefore, the power supply generates the active power and the shunt converter absorbs it in fundamental frequency of current. Meanwhile, the third harmonic component is trapped in Y-Δ transformer. Output terminal of the shunt converter injects the third harmonic current into the neutral of Δ-Y transformer. Consequently, the harmonic current flows through the transmission line. This harmonic current controls the dc voltage of series capacitors. Fig. 2 illustrates how the active power is exchanged between the shunt and series converters in the DPFC. Fig. 1.The DPFC structure. Fig. 2. Active power exchange between DPFC converters. B. The DPFC Advantages The DPFC in comparison with UPFC has some advantages, as follows: 1) High control capability. The DPFC can control all parameters of transmission network: line impedance, transmission angle and bus voltage magnitude. 2) High reliability. The series converters redundancy increases the DPFC reliability during converters operation [10]. It means, if one of series converters fails, the others can continue to work. 3) Low cost. The single-phase converters rating, in comparison with three-phase converters is very low. Furthermore, the series converters, in this configuration, no need to any voltage isolation to connect in line. We can use the single turn transformers for series converters hanging. To explore the feasibility of the DPFC, a case study which is to use DPFC to replace UPFC of the Korea electric power corporation (KEPCO) is investigated. To achieve the same control capability as the UPFC, the DPFC construction requires less material [9]. III. DPFC CONTROL BASED ON SRF METHOD The DPFC has three control strategies: central controller, series control and shunt control, as shown in Fig. 3. A. Central Control This controller manages all the series and shunt controllers and sends reference signals to both of them. B. Series Control Each single-phase converter has its own series control through the line. This controller inputs are series capacitor voltages, line current and series voltage reference in dq-frame. Any series controller has one low-pass and one 3rd-pass filter to create fundamental and third harmonic current respectively. Two single-phase phase lock loop (PLL) are used to take frequency and phase information from network [11]. The simulated diagram of
  • 3. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 43 | P a g e series controller is shown in Fig. 4 C. Shunt Control The shunt converter includes a three-phase converter which is back-to-back connected to a single-phase converter Fig .3.DPFC Control Structure. Fig. 4. The series control structure. Fig. 5. The shunt control configuration: (a) for fundamental frequency (b) for third-harmonic frequency The three-phase converter absorbs active power from grid at fundamental frequency and controls the dc voltage of capacitor between this converter and single-phase one. The shunt control structure block diagram is shown in Fig. 5.
  • 4. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 44 | P a g e D. Proposed Detection and Determination Methods To detect the voltage sags and determine the three single phase reference voltages of DPFC, the SRF method is introduced as a detection and determination method. The line-to-neutral voltages of grid in the pre-sag state are convicted from abc coordinate system to SRF (dq0) as the first step of this method. Then, the dq0 values of actual and reference line-neutral grid voltages are compared which the existence of the difference between them is representation of voltage sag and considered as the dq0 values of DPFC desired injected voltages. = (2) Fig.6.simulated model of the DPFC = (3) are the reference dq- component of DPFC desired injected voltages in the SRF, respectively. fig. 6. Simulated model of the IV. POWER QUALITY ENHANCEMENT This modeling has been developed using Mat lab/Simulink environment as shown in Fig. 6. The system is simulated with a three-phase source connected to a non-linear load. The simulation parameters are listed in Table 1. The supply is connected to load through the parallel transmission lines including the transmission line 1 and 2. The parallel transmission lines have same length. The DPFC is incorporated in transmission line 2. For analyzing dynamic performance, the inductive and capacitive loads are connected. The fault should be connected near the load to receive transient analysis. The shunt three-phase converter is connected to the transmission line 2 in parallel through a Y-Δ three- phase transformer, and series converters are distributed through this line. V. SIMULATION RESULTS The case study, considering sag/swell condition is implemented in single machine infinite bus system and analyzed results are as follows. To analyze voltage dip, a three-phase fault near the system load, as shown in Fig. 6 is created. The time duration for this fault is 0.5 seconds (500-1000 ms). The three-phase fault causes observable voltage sag during this time, as shown in Fig. 7. The voltage sag value is about 0.5 per unit. The DPFC can compensate the load voltage sag effectively. The voltage sag mitigation with DPFC is shown in Fig. 8. After creating three-phase fault, Fig. 9 depicts the load current swell around 1.1 per unit. The fault time duration is
  • 5. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 45 | P a g e 0.5 seconds. In this case, after implementation of the DPFC, the load current magnitude is comparatively come down. The current swell mitigation for this case can be observed from Fig. 10. The load voltage harmonic analysis, using fast Fourier transform (FFT) of power GUI window by Simulink, as shown in Fig. 11. It can be seen, after DPFC implementation in system, the odd harmonics are reduced within acceptable limits and total harmonic distortion (THD) of load voltage is minimized. Fig. 7. Three-phase load voltage sag waveform Fig. 8. Mitigation of three-phase load voltage sag with DPFC. Fig. 9. Three-phase load current swell waveform Fig. 10. Mitigation of load current swell with DPFC.
  • 6. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 46 | P a g e Fig. 11. The load voltage THD. VI. CONCLUSION The power quality enhancement of the power transmission systems is an vital issue in power industry. In his study, the application of DPFC as a new FACTS device, in the voltage sag and swell mitigation of a system composed of a three-phase source connected to a non-linear load through the parallel transmission lines is simulated in Matlab/Simulink environment. The voltage dip is analyzed by implementing a three-phase fault close to the system load. To detect the voltage sags and determine the three single phase reference voltages of DPFC, the SRF method is used as a detection and determination method. The obtained simulation results show the effectiveness of DPFC in power quality enhancement, especially in sag and swell mitigation. TABLE I : THE SIMULATED SYSTEM PARAMETERS. Parameters values Three phase source Rated voltage 230 [kV] Rated power/Frequency 100[mW]/60[HZ] X/R 3 Short circuit capacity 11000[MW] Transmission line Resistance 0.012 [p.u./km] Inductance/Capacitance reactance 0.12/0.12[p.u./km] Length of transmission line 100 [km] REFERENCES [1.] J. Faiz, G. H. Shahgholian, and M. Torabian, “Design and simulation of UPFC or enhancement of power quality in transmission lines,” IEEE International Conference on Power System Technology, vol. 24, no. 4, 2010. [2.] E. Emanuel and J. A. McNeill, “Electric power quality,” Annu. Rev. Energy Environ, 1997. [3.] N. R. Patne and K. L. Thakre “Factor affecting characteristics of voltage sag due to fault in the power system,” Serbian Journal of Electrical engineering. vol. 5, no.1, 2008. [4.] J. R. Enslin, “Unified approach to power quality mitigation,” in Proc. IEEE Int. Symp. Industrial Electronics (ISIE ’98), vol. 1, 1998. [5.] B. Singh, K. Al-Haddad, and A. Chandra, “A review of active filters for power quality improvement,” IEEE Trans. Ind. Electron. vol. 46, no. 5, pp. 960–971, 1999. [6.] M. A. Hannan and A. Mohamed, member IEEE, “PSCAD/EMTDC simulation of unified series- shunt compensator for power quality improvement,” IEEE Transactions on Power Delivery, vol. 20, no. 2, 2005. [7.] L. Olimpo and E. Acha, “Modeling and analysis of custom power systems by PSCAD/EMTDC,” IEEE
  • 7. P.NIRMALA et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 9( Version 3), September 2014, pp.41-47 www.ijera.com 47 | P a g e Trans. Power Delivery, vol. 17, no.1, pp. 266–272, 2002. [8.] P. Pohjanheimo and E. Lakervi, “Steady state modeling of custom power components in power distribution networks,” in Proc. IEEE Power Engineering Society Winter Meeting, vol. 4, Jan, pp. 2949–2954, 2000. [9.] Z. H. Yuan, S. W. H de Haan, B. Frreira, and D. Cevoric, “A FACTS device: Distributed power flow controller (DPFC),” IEEE Transaction on Power Electronics, vol.25, no.10, October, 2010. [10.] Z. H. Yuan, S. W. H de Haan, and B. Frreira “DPFC control during shunt converter failure,” IEEE Transaction on Power Electronics 2009. [11.] R. Zhang, M. Cardinal, P. Szczesny, and M. Dame. “A grid simulator with control of single-phase power converters in D.Q rotating frame,” P.Nirmala was born in Andhra Pradesh, India. She received the B.Tech degree in Electrical and Electronics Engineering from JNTU, Anantaapur in 2011 and pursuing M.Tech degree in Power Systems from JTNU, Anantapur, Andhra Pradesh, India. Her area of interest in the field of power systems and electric Drives. Email: nirmala.yadav39@gmail.com Shajida Shaik was born in Andhra Pradesh, India. She received the B.Tech degree in Electrical and Electronics Engineering from DR SGIET, A.P., in 2005 and M.E degree in osmania university, AP, in 2012.She is presently working as Asst.Professor Dept.EEE, Audisankara Institute of Technology-Gudur, Nellore, Andhrapradesh, India. Mr. Jan Bhasha Shaik was born in Andhra Pradesh, India. He received the B.Tech degree in Electrical and Electronics Engineering from JNT University, Hyderabad in 2004 and M.Tech degree in Power & Industrial Drives from JNT University Kakinada in 2010. He is currently pursuing the Ph.D. degree at the JNT University, Anantapur, Andhra Pradesh, India. He had worked as an Assistant Professor and IEEE student Branch counselor at Hi-Tech College of Engineering, and worked as an Assistant professor at KL University Guntur,AP. Currently He is working as an Associate Professor at Audisankara Institute of Technology, Gudur,AP. He was the academic project coordinator for Under-Graduate & Post Graduate students. His areas of interest are HVDC, FACTS & SMART GRID.