Arc Flash Safety
Arc Flash Safety
Arcing Fault Events
Arcing Fault Events
An arc is produced by flow of electrical
An arc is produced by flow of electrical
current through ionized air after an initial
current through ionized air after an initial
flashover or short circuit.
flashover or short circuit.
Arcs produce some of the highest
Arcs produce some of the highest
temperatures known to occur on earth –
temperatures known to occur on earth –
up to 35,000 degrees F. This is four times
up to 35,000 degrees F. This is four times
the surface temperature of the sun.
the surface temperature of the sun.
All known materials are vaporized at this
All known materials are vaporized at this
temperature.
temperature.
Arc Flash Effects
Arc Flash Effects
Average of 1,710 (reported) electrical
Average of 1,710 (reported) electrical
burns per year in USA
burns per year in USA
– Burn from intense heat
Burn from intense heat
– Trauma from blast pressure
Trauma from blast pressure
– Toxic gases from vaporized metal
Toxic gases from vaporized metal
– Sprayed molten metal droplets
Sprayed molten metal droplets
– Hearing damage from sound pressure wave
Hearing damage from sound pressure wave
– Eye damage
Eye damage
Electrical Safety Requirements
Electrical Safety Requirements
OSHA 1910.333 (a)(1) & NFPA 70E 130.1
OSHA 1910.333 (a)(1) & NFPA 70E 130.1
Qualified electrical workers shall not be asked
Qualified electrical workers shall not be asked
to work on equipment that is “hot” or “live”
to work on equipment that is “hot” or “live”
except for two reasons:
except for two reasons:
1.
1. De-energizing introduces additional or
De-energizing introduces additional or
increased hazards
increased hazards
 Such as cutting ventilation to a hazardous location
Such as cutting ventilation to a hazardous location
2.
2. Infeasible due to equipment design or
Infeasible due to equipment design or
operational limitations
operational limitations
 Such as doing voltage testing for diagnostics
Such as doing voltage testing for diagnostics
Elements of Arc Flash Safety
Elements of Arc Flash Safety
Defined responsibilities
Defined responsibilities
Calculation of degree of arc flash hazard
Calculation of degree of arc flash hazard
Personal protective equipment
Personal protective equipment
Training
Training
Tools for safe work
Tools for safe work
Warning labels on equipment
Warning labels on equipment
Responsibilities
Responsibilities
YSU will provide:
YSU will provide:
– PPE
PPE
– Training
Training
– Labeling
Labeling
– Insulated tools
Insulated tools
– Lock out/tag out
Lock out/tag out
devices
devices
YSU employee will:
YSU employee will:
– Follow safe work
Follow safe work
practices
practices
– Use appropriate
Use appropriate
insulated tools
insulated tools
– Wear PPE when
Wear PPE when
required
required
Arc Flash Hazard Analysis
Arc Flash Hazard Analysis
Determines flash protection boundary and
Determines flash protection boundary and
PPE requirements as a function of location
PPE requirements as a function of location
and work activity.
and work activity.
Arc flash hazard and flash protection
Arc flash hazard and flash protection
boundary varies with:
boundary varies with:
– Type of equipment and configuration
Type of equipment and configuration
– Available short circuit current
Available short circuit current
– Voltage
Voltage
– Predicted fault duration – protective devices
Predicted fault duration – protective devices
upstream on the arcing fault and their settings
upstream on the arcing fault and their settings
Flash Protection Boundary
Flash Protection Boundary
Linear distance from exposed live parts
Linear distance from exposed live parts
within which a person could receive
within which a person could receive
second degree burns resulting from an arc
second degree burns resulting from an arc
flash.
flash.
Flash Protection Boundaries
Flash Protection Boundaries
Limited Approach Boundary
Limited Approach Boundary
– Entered only by qualified persons or unqualified
Entered only by qualified persons or unqualified
persons escorted by qualified person
persons escorted by qualified person
Restricted Approach Boundary
Restricted Approach Boundary
– Entered only by qualified persons required to use
Entered only by qualified persons required to use
shock protection techniques and equipment
shock protection techniques and equipment
Prohibited Approach Boundary
Prohibited Approach Boundary
– Entered only by qualified persons requiring same
Entered only by qualified persons requiring same
protection as if in direct contact with live parts
protection as if in direct contact with live parts
Prohibited shock boundary: Qualified persons only - PPE as if direct
contact with live part
Restricted shock boundary: Qualified persons only
Limited shock boundary: Qualified or unqualified persons*
*only if accompanied by qualified person
Note: shock boundaries dependent on system voltage level
Flash Protection Boundary (FPB)
Must wear appropriate PPE
FPB dependent on fault level and
time duration.
Equipment
Approach Boundaries
Approach Boundaries
Each boundary is a
Each boundary is a
sphere to be
sphere to be
observed in all
observed in all
directions three
directions three
dimensionally.
dimensionally.
Labeling
Labeling
Switchboards, panel boards, industrial
Switchboards, panel boards, industrial
controls, etc. that require examination,
controls, etc. that require examination,
adjustment, or maintenance while
adjustment, or maintenance while
energized shall be labeled.
energized shall be labeled.
Labeling
Labeling
Labels shall be designed to warn of
Labels shall be designed to warn of
potential arc flash hazards
potential arc flash hazards
YSU will classify arc flash hazard labels
YSU will classify arc flash hazard labels
into two types:
into two types:
– Low voltage below 680 volts
Low voltage below 680 volts
– High voltage above 680 volts
High voltage above 680 volts
Insulated Tools
Insulated Tools
Flame retardant
Flame retardant
Double insulated. A first hi-visibility yellow
Double insulated. A first hi-visibility yellow
layer provides the insulation for the tool, and
layer provides the insulation for the tool, and
the outer hi-visibility orange layer protects the
the outer hi-visibility orange layer protects the
lower yellow layer.
lower yellow layer.
NOTE: If the yellow layer can
NOTE: If the yellow layer can
be seen through the orange
be seen through the orange
layer, the tool should be
layer, the tool should be
removed from service.
removed from service.
NFPA 70E 120.1
NFPA 70E 120.1
120.1 Process of Achieving an
120.1 Process of Achieving an
Electrically Safe Work Condition
Electrically Safe Work Condition
– An electrically safe work condition shall be
An electrically safe work condition shall be
achieved when performed in accordance
achieved when performed in accordance
with the procedures of 120.2 and verified by
with the procedures of 120.2 and verified by
the following process:
the following process:
Electrically Safe Work Condition
Electrically Safe Work Condition
1.
1. Determine all electrical sources using up-to-
Determine all electrical sources using up-to-
date information, drawings, diagrams, etc.
date information, drawings, diagrams, etc.
2.
2. After properly interrupting the load current,
After properly interrupting the load current,
open the disconnecting device(s) for each
open the disconnecting device(s) for each
source.
source.
– At this point, the equipment or circuit is simply
At this point, the equipment or circuit is simply
de-energized, not in an electrically safe work
de-energized, not in an electrically safe work
condition.
condition.
Electrically Safe Work Condition
Electrically Safe Work Condition
3.
3. Visually verify that disconnecting
Visually verify that disconnecting
means fully open if possible
means fully open if possible
4.
4. Apply lockout tagout devices
Apply lockout tagout devices
5.
5. Test for absence of voltage
Test for absence of voltage
 Verify proper operation of test
Verify proper operation of test
equipment
equipment
6.
6. Ground phase conductors if there
Ground phase conductors if there
is a possibility of induced
is a possibility of induced
voltages or stored energy
voltages or stored energy
Electrically Safe Work Condition
Electrically Safe Work Condition
Until these six steps have been executed,
Until these six steps have been executed,
some exposure to an electrical hazard still
some exposure to an electrical hazard still
exists and proper PPE is required.
exists and proper PPE is required.
Safe Work Practices
Safe Work Practices
For open box work where the circuit can
For open box work where the circuit can
not be de-energized, safe work practices
not be de-energized, safe work practices
will include:
will include:
– Use of insulated tools
Use of insulated tools
– Use of personal protective equipment
Use of personal protective equipment
– Not working alone
Not working alone
Safe Work Practices
Safe Work Practices
If the box is open and the circuit can not
If the box is open and the circuit can not
be de-energized personal protective
be de-energized personal protective
equipment is required; for 120 volts:
equipment is required; for 120 volts:
– Safety glasses
Safety glasses
– Cotton shirt and pants
Cotton shirt and pants
*Note: NFPA recommends cotton under
*Note: NFPA recommends cotton under
garments for use when an arc flash hazard is
garments for use when an arc flash hazard is
present.
present.
Safe Work Practices
Safe Work Practices
If the box is open and the circuit can not
If the box is open and the circuit can not
be de-energized, personal protective
be de-energized, personal protective
equipment is required; for 120-680 volts:
equipment is required; for 120-680 volts:
– Safety glasses, ear plugs
Safety glasses, ear plugs
– Cotton shirt and Indura pants
Cotton shirt and Indura pants
(MSU work uniform)
(MSU work uniform)
– Category 2 face shield
Category 2 face shield
– Category 2 Indura coat
Category 2 Indura coat
– Low voltage insulated gloves
Low voltage insulated gloves
Safe Work Practices
Safe Work Practices
If the box is open and the circuit
If the box is open and the circuit
can not be de-energized, personal
can not be de-energized, personal
protective equipment is required,
protective equipment is required,
for high voltage of 680V or higher:
for high voltage of 680V or higher:
– Safety glasses, ear plugs
Safety glasses, ear plugs
– Cotton shirt and Indura pants
Cotton shirt and Indura pants
– Category 4 hood
Category 4 hood
– Category 4 Indura coat and pants
Category 4 Indura coat and pants
– High voltage insulated gloves with
High voltage insulated gloves with
leather over gloves
leather over gloves
PPE – NFPA 70E Table 130.7
PPE – NFPA 70E Table 130.7
Typical Protective Clothing Systems
Hazard/Risk
Category
Clothing Description
(Typical number of clothing layers is given in parentheses)
RequiredMinimum
Arc Rating of PPE
[(J/cm
2
(cal/cm
2
)]
0 Non-melting, flammable materials (i.e., untreated cotton,
wool, rayon, or silk, or blends of these materials) with a
fabric weight at least 4.5 oz/yd
2
(1)
N/A
1 FR Shirt and FR pants or FR coverall (1) 16.74 (4)
2 Cotton underwear - conventional short sleeve and
brief/shorts, plus FR shirt and FR pants (1 or 2)
33.47 (8)
3 Cotton underwear plus FR shirt and FR pants plus FR
coverall, or cotton underwear plus two FR coveralls (2 or 3)
104.6 (25)
4 Cotton underwear plus FR shirt and FR pants plus multi-
layer flash suit (3, or more)
167.36 (40)
Summary
Summary
Equipment should be placed in an electrically
Equipment should be placed in an electrically
safe work condition prior to servicing the
safe work condition prior to servicing the
equipment.
equipment.
Safe work practices should be followed to
Safe work practices should be followed to
reduce the hazards associated with an arc
reduce the hazards associated with an arc
flash.
flash.
If necessary to work on live parts:
If necessary to work on live parts:
– 120 volts - safety glasses & cotton uniform
120 volts - safety glasses & cotton uniform
– 120-680 volts – Category 2 arc flash suit
120-680 volts – Category 2 arc flash suit
– 680 volts and above – Category 4 arc flash suit
680 volts and above – Category 4 arc flash suit

Training Presentation - Arc Flash Safety.ppt

  • 1.
  • 2.
    Arcing Fault Events ArcingFault Events An arc is produced by flow of electrical An arc is produced by flow of electrical current through ionized air after an initial current through ionized air after an initial flashover or short circuit. flashover or short circuit. Arcs produce some of the highest Arcs produce some of the highest temperatures known to occur on earth – temperatures known to occur on earth – up to 35,000 degrees F. This is four times up to 35,000 degrees F. This is four times the surface temperature of the sun. the surface temperature of the sun. All known materials are vaporized at this All known materials are vaporized at this temperature. temperature.
  • 3.
    Arc Flash Effects ArcFlash Effects Average of 1,710 (reported) electrical Average of 1,710 (reported) electrical burns per year in USA burns per year in USA – Burn from intense heat Burn from intense heat – Trauma from blast pressure Trauma from blast pressure – Toxic gases from vaporized metal Toxic gases from vaporized metal – Sprayed molten metal droplets Sprayed molten metal droplets – Hearing damage from sound pressure wave Hearing damage from sound pressure wave – Eye damage Eye damage
  • 9.
    Electrical Safety Requirements ElectricalSafety Requirements OSHA 1910.333 (a)(1) & NFPA 70E 130.1 OSHA 1910.333 (a)(1) & NFPA 70E 130.1 Qualified electrical workers shall not be asked Qualified electrical workers shall not be asked to work on equipment that is “hot” or “live” to work on equipment that is “hot” or “live” except for two reasons: except for two reasons: 1. 1. De-energizing introduces additional or De-energizing introduces additional or increased hazards increased hazards  Such as cutting ventilation to a hazardous location Such as cutting ventilation to a hazardous location 2. 2. Infeasible due to equipment design or Infeasible due to equipment design or operational limitations operational limitations  Such as doing voltage testing for diagnostics Such as doing voltage testing for diagnostics
  • 10.
    Elements of ArcFlash Safety Elements of Arc Flash Safety Defined responsibilities Defined responsibilities Calculation of degree of arc flash hazard Calculation of degree of arc flash hazard Personal protective equipment Personal protective equipment Training Training Tools for safe work Tools for safe work Warning labels on equipment Warning labels on equipment
  • 11.
    Responsibilities Responsibilities YSU will provide: YSUwill provide: – PPE PPE – Training Training – Labeling Labeling – Insulated tools Insulated tools – Lock out/tag out Lock out/tag out devices devices YSU employee will: YSU employee will: – Follow safe work Follow safe work practices practices – Use appropriate Use appropriate insulated tools insulated tools – Wear PPE when Wear PPE when required required
  • 12.
    Arc Flash HazardAnalysis Arc Flash Hazard Analysis Determines flash protection boundary and Determines flash protection boundary and PPE requirements as a function of location PPE requirements as a function of location and work activity. and work activity. Arc flash hazard and flash protection Arc flash hazard and flash protection boundary varies with: boundary varies with: – Type of equipment and configuration Type of equipment and configuration – Available short circuit current Available short circuit current – Voltage Voltage – Predicted fault duration – protective devices Predicted fault duration – protective devices upstream on the arcing fault and their settings upstream on the arcing fault and their settings
  • 13.
    Flash Protection Boundary FlashProtection Boundary Linear distance from exposed live parts Linear distance from exposed live parts within which a person could receive within which a person could receive second degree burns resulting from an arc second degree burns resulting from an arc flash. flash.
  • 14.
    Flash Protection Boundaries FlashProtection Boundaries Limited Approach Boundary Limited Approach Boundary – Entered only by qualified persons or unqualified Entered only by qualified persons or unqualified persons escorted by qualified person persons escorted by qualified person Restricted Approach Boundary Restricted Approach Boundary – Entered only by qualified persons required to use Entered only by qualified persons required to use shock protection techniques and equipment shock protection techniques and equipment Prohibited Approach Boundary Prohibited Approach Boundary – Entered only by qualified persons requiring same Entered only by qualified persons requiring same protection as if in direct contact with live parts protection as if in direct contact with live parts
  • 15.
    Prohibited shock boundary:Qualified persons only - PPE as if direct contact with live part Restricted shock boundary: Qualified persons only Limited shock boundary: Qualified or unqualified persons* *only if accompanied by qualified person Note: shock boundaries dependent on system voltage level Flash Protection Boundary (FPB) Must wear appropriate PPE FPB dependent on fault level and time duration. Equipment
  • 16.
    Approach Boundaries Approach Boundaries Eachboundary is a Each boundary is a sphere to be sphere to be observed in all observed in all directions three directions three dimensionally. dimensionally.
  • 17.
    Labeling Labeling Switchboards, panel boards,industrial Switchboards, panel boards, industrial controls, etc. that require examination, controls, etc. that require examination, adjustment, or maintenance while adjustment, or maintenance while energized shall be labeled. energized shall be labeled.
  • 18.
    Labeling Labeling Labels shall bedesigned to warn of Labels shall be designed to warn of potential arc flash hazards potential arc flash hazards YSU will classify arc flash hazard labels YSU will classify arc flash hazard labels into two types: into two types: – Low voltage below 680 volts Low voltage below 680 volts – High voltage above 680 volts High voltage above 680 volts
  • 19.
    Insulated Tools Insulated Tools Flameretardant Flame retardant Double insulated. A first hi-visibility yellow Double insulated. A first hi-visibility yellow layer provides the insulation for the tool, and layer provides the insulation for the tool, and the outer hi-visibility orange layer protects the the outer hi-visibility orange layer protects the lower yellow layer. lower yellow layer. NOTE: If the yellow layer can NOTE: If the yellow layer can be seen through the orange be seen through the orange layer, the tool should be layer, the tool should be removed from service. removed from service.
  • 20.
    NFPA 70E 120.1 NFPA70E 120.1 120.1 Process of Achieving an 120.1 Process of Achieving an Electrically Safe Work Condition Electrically Safe Work Condition – An electrically safe work condition shall be An electrically safe work condition shall be achieved when performed in accordance achieved when performed in accordance with the procedures of 120.2 and verified by with the procedures of 120.2 and verified by the following process: the following process:
  • 21.
    Electrically Safe WorkCondition Electrically Safe Work Condition 1. 1. Determine all electrical sources using up-to- Determine all electrical sources using up-to- date information, drawings, diagrams, etc. date information, drawings, diagrams, etc. 2. 2. After properly interrupting the load current, After properly interrupting the load current, open the disconnecting device(s) for each open the disconnecting device(s) for each source. source. – At this point, the equipment or circuit is simply At this point, the equipment or circuit is simply de-energized, not in an electrically safe work de-energized, not in an electrically safe work condition. condition.
  • 22.
    Electrically Safe WorkCondition Electrically Safe Work Condition 3. 3. Visually verify that disconnecting Visually verify that disconnecting means fully open if possible means fully open if possible 4. 4. Apply lockout tagout devices Apply lockout tagout devices 5. 5. Test for absence of voltage Test for absence of voltage  Verify proper operation of test Verify proper operation of test equipment equipment 6. 6. Ground phase conductors if there Ground phase conductors if there is a possibility of induced is a possibility of induced voltages or stored energy voltages or stored energy
  • 23.
    Electrically Safe WorkCondition Electrically Safe Work Condition Until these six steps have been executed, Until these six steps have been executed, some exposure to an electrical hazard still some exposure to an electrical hazard still exists and proper PPE is required. exists and proper PPE is required.
  • 24.
    Safe Work Practices SafeWork Practices For open box work where the circuit can For open box work where the circuit can not be de-energized, safe work practices not be de-energized, safe work practices will include: will include: – Use of insulated tools Use of insulated tools – Use of personal protective equipment Use of personal protective equipment – Not working alone Not working alone
  • 25.
    Safe Work Practices SafeWork Practices If the box is open and the circuit can not If the box is open and the circuit can not be de-energized personal protective be de-energized personal protective equipment is required; for 120 volts: equipment is required; for 120 volts: – Safety glasses Safety glasses – Cotton shirt and pants Cotton shirt and pants *Note: NFPA recommends cotton under *Note: NFPA recommends cotton under garments for use when an arc flash hazard is garments for use when an arc flash hazard is present. present.
  • 26.
    Safe Work Practices SafeWork Practices If the box is open and the circuit can not If the box is open and the circuit can not be de-energized, personal protective be de-energized, personal protective equipment is required; for 120-680 volts: equipment is required; for 120-680 volts: – Safety glasses, ear plugs Safety glasses, ear plugs – Cotton shirt and Indura pants Cotton shirt and Indura pants (MSU work uniform) (MSU work uniform) – Category 2 face shield Category 2 face shield – Category 2 Indura coat Category 2 Indura coat – Low voltage insulated gloves Low voltage insulated gloves
  • 27.
    Safe Work Practices SafeWork Practices If the box is open and the circuit If the box is open and the circuit can not be de-energized, personal can not be de-energized, personal protective equipment is required, protective equipment is required, for high voltage of 680V or higher: for high voltage of 680V or higher: – Safety glasses, ear plugs Safety glasses, ear plugs – Cotton shirt and Indura pants Cotton shirt and Indura pants – Category 4 hood Category 4 hood – Category 4 Indura coat and pants Category 4 Indura coat and pants – High voltage insulated gloves with High voltage insulated gloves with leather over gloves leather over gloves
  • 28.
    PPE – NFPA70E Table 130.7 PPE – NFPA 70E Table 130.7 Typical Protective Clothing Systems Hazard/Risk Category Clothing Description (Typical number of clothing layers is given in parentheses) RequiredMinimum Arc Rating of PPE [(J/cm 2 (cal/cm 2 )] 0 Non-melting, flammable materials (i.e., untreated cotton, wool, rayon, or silk, or blends of these materials) with a fabric weight at least 4.5 oz/yd 2 (1) N/A 1 FR Shirt and FR pants or FR coverall (1) 16.74 (4) 2 Cotton underwear - conventional short sleeve and brief/shorts, plus FR shirt and FR pants (1 or 2) 33.47 (8) 3 Cotton underwear plus FR shirt and FR pants plus FR coverall, or cotton underwear plus two FR coveralls (2 or 3) 104.6 (25) 4 Cotton underwear plus FR shirt and FR pants plus multi- layer flash suit (3, or more) 167.36 (40)
  • 29.
    Summary Summary Equipment should beplaced in an electrically Equipment should be placed in an electrically safe work condition prior to servicing the safe work condition prior to servicing the equipment. equipment. Safe work practices should be followed to Safe work practices should be followed to reduce the hazards associated with an arc reduce the hazards associated with an arc flash. flash. If necessary to work on live parts: If necessary to work on live parts: – 120 volts - safety glasses & cotton uniform 120 volts - safety glasses & cotton uniform – 120-680 volts – Category 2 arc flash suit 120-680 volts – Category 2 arc flash suit – 680 volts and above – Category 4 arc flash suit 680 volts and above – Category 4 arc flash suit